Circular Diffusers
Circular Diffusers
Circular Diffusers
INTRODUCTION
KMC Circular Diffusers have a circular cone with
elegant styling to provide maximum air diffusion
efficiency.
APPLICATION
Recommended for supply air, constant or variable
air volume heating, cooling, or ventilating
PRODUCT FEATURES
Removable inner core permits easy installation and
access to duct
Selection Procedure
Selections can be made by means of a straight
read-off from the “Performance Data” for the
selected model.
DIMENSION IN MM
Nominal Dia ØA ØB
150 158 243
200 198 285
250 245 332
300 315 398
350 352 438
400 398 482
450 448 560
*In the interest of product development, KMC reserves the right to make changes without notice.
w ww.kmcq ata r.co m 1 Company
Khalid Manufacturing
Model KCM
Circular Diffusers
Performance Data
Neck
Duct Area, m2
2.0 2.5 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
Neck Size
Velocity
Nominal
ø mm
Velocity
2.5 5 5 10 15 22.5 30 40 50 62.5
Pressure
CMH 109 136 163 218 272 326 367 422 476 530
Ps 7.5 12.5 20 25 42.5 52.5 67.5 87.5 112.5 140
150 0.015
NC <20 <20 <20 23 29 34 37 41 45 48
Throw 0.3 0.6 1.2 0.6 0.9 1.5 0.6 0.9 2.1 0.9 1.2 2.7 1.2 1.5 3.4 1.2 2.1 4.0 1.5 2.1 4.6 1.8 2.4 4.9 1.8 2.7 5.2 2.1 3.4 5.5
CMH 190 231 286 381 476 571 666 762 857 952
Ps 5 7.5 10 17.5 30 42.5 57.5 72.5 92.5 115
200 0.026
NC <20 <20 <20 20 26 31 36 39 43 45
Throw 0.6 0.9 1.5 0.6 0.9 2.1 0.9 1.2 2.4 1.2 1.5 3.4 1.5 2.1 4.3 1.5 2.4 4.9 1.8 3.0 5.8 2.1 3.4 6.7 2.4 3.7 7.0 2.7 4.3 7.3
CMH 299 367 449 598 748 884 1034 1183 1333 1482
Ps 2.5 5 7.5 12.5 20 27.5 37.5 47.5 60 75
250 0.041
NC <20 <20 <20 21 27 31 36 39 43 46
Throw 0.6 0.9 2.1 0.9 1.2 2.4 0.9 1.5 3.0 1.5 2.1 4.3 1.8 2.4 5.2 2.1 3.0 6.1 2.4 3.7 7.0 2.7 4.0 8.2 3.0 4.6 8.8 3.4 5.2 9.1
CMH 422 530 639 857 1074 1278 1496 1714 1918 2135
Ps 5 7.5 10 17.5 27.5 37.5 52.5 67.5 85 105
300 0.058
NC <20 <20 <20 27 33 38 42 46 49 52
Throw 0.9 1.2 2.4 0.9 1.5 3.0 1.2 1.8 3.7 1.8 2.4 5.2 2.1 3.0 6.4 2.4 3.7 7.6 3.0 4.3 8.8 3.4 5.2 10.1 3.7 5.8 10.7 4.3 6.4 11.0
CMH 666 830 1006 1333 1673 1999 2339 2666 3006 3332
Ps 2.5 5 7.5 12.5 20 27.5 37.5 47.5 60 75
350 0.089
NC <20 <20 21 28 34 39 44 47 51 53
Throw 0.9 1.5 3.0 1.2 1.8 4.0 1.5 2.4 4.6 2.1 3.0 6.1 2.7 4.0 7.9 3.0 4.6 9.5 3.7 5.5 11.0 4.3 6.1 12.5 4.6 7.0 13.1 5.2 7.6 14.0
NC 762 952 1142 1523 1904 2285 2666 3046 3250 3332
CMH (L) 7.5 12.5 20 25 37.5 47.5 60 70 87.5 115
400 0.117
Throw (L) <20 <20 21 28 34 39 44 47 51 53
CMH 0.9 1.5 3.0 1.2 1.8 4.0 1.5 2.4 4.6 2.1 3.0 6.1 2.7 4.0 7.9 3.0 4.6 8.5 3.7 5.5 9.8 4.3 6.1 10.7 4.6 7.0 11.6 5.2 7.6 13.4
NC 966 1197 1442 1918 2407 2883 3359 3849 4325 4801
CMH (L) 7.5 12.5 20 25 37.5 47.5 65 85 107.5 132.5
450 0.132
Throw (L) <20 <20 23 30 37 42 46 50 53 56
Throw (L) 1.5 2.1 3.7 1.8 3.0 4.6 2.4 3.7 5.8 2.7 4.3 7.6 3.0 4.6 9.5 3.7 5.8 10.7 4.3 6.7 12.2 4.9 7.6 13.1 5.8 8.5 14.0 6.4 9.5 14.6
Notes :
• Neck velocity in m/s, meters per second Throw
• The numbers shown are throw distances, in meters, measured
Test Standard along the jet trajectory axis relating to terminal velocities of 0.75
• ANSI / ASHRAE standard 70 m/s, 0.5 m/s & 0.25 m/s and include a surface effect
• Isothermal conditions • Terminal velocity is the air speed, in meters per second, measured
• Non-uniform air flow into diffusers increase sound levels, in the supply air stream.
operating pressures, and can distort the air distribution pattern • For exposed duct installations, throws are 70% of the table values
into the space above.
*In the interest of product development, KMC reserves the right to make changes without notice.