Unit-5 Transformer
Unit-5 Transformer
1 in which the switch S after disconnecting from the supply is The resistance of the primary winding is very low, and the primary current is high. So this current is much
thrown to terminals 1'2'. The machine then gets connected to a non-inductive load resistance RL. The higher than the rated full load primary winding current. Hence, as a result, the amount of heat produced
power drawn by this resistance will acts as a retarding torque on the armature which will make it slow will be greater and therefore, eddy current loss (I2R) loss will be more. Because of this, the insulations of
more quickly. the primary windings will get burnt, and the transformer will be damaged.
The primary and the secondary currents are inversely proportional to their respective turns.
The additional loss in the resistance will be equal to product of ammeter reading and the average
Turn Ratio:
reading of the voltmeter (for a fall of 5% of voltmeter reading, the time is noted.) The ammeter reading is Behaviour of Ideal Transformer:
It is defined as the ratio of primary to secondary turns.
also changing so its average reading is taken. Thus the additional losses is Ia2 (Ra + R). Let t1 be the time Consider the ideal transformer shown in the figure below. The voltage source V 1is applied across the
when armature is considered alone and t2 be the time when armature is connected across a load resistance, primary winding of the transformer. Their secondary winding is kept open. The N1 and N2 are the
V be average voltage across R and Ia be the average current and W' is additional retarding electrical numbers of turns of their primary and secondary winding.
torque supplied by motor. Fig: Simple Transformer
If N2 > N1 the transformer is called Step up transformer The current Im is the magnetizing current flows through the primary winding of the transformer. The
If N2 < N1 the transformer is called Step down transformer magnetizing current produces the flux φm in the core of the transformer. As the permeability of the core is
When the AC supply is given to the primary winding with a voltage of V1, an alternating flux ϕ sets up in
the core of the transformer, which links with the secondary winding and as a result of it, an emf is induced infinite, the flux of the core link with both the primary and secondary winding of the transformer.
Transformation Ratio:
in it called Mutually Induced emf. The direction of this induced emf is opposite to the applied voltage V1,
The transformation ratio is defined as the ratio of the secondary voltage to the primary voltage. It is
this is because of the Lenz’s law shown in the figure below
denoted by K.
If dN i.e. change in speed is same in two cases then
92 | P a g e 93 | P a g e 94 | P a g e 95 | P a g e
The function of flux is a sine function. The rate of change of flux with respect to time is derived (To minimize this leakage reactance, primary and secondary windings are not placed on separate legs, Since the transformation ratio is K, primary resistive and reactive drop as referred to secondary side will
mathematically. refer the diagram of core type and shell type transformer from construction of transformer.) be K times, i.e., K I1R1 and K I1X1 respectively. If I1 is substituted equal to KI2 then we have primary
resistive and reactive drop referred to secondary side equal to K2I2R1 and K2I2X1 respectively.
The derivation of EMF Equation of the transformer is shown below. Let Similarly
Practical Transformer with Resistance and Leakage Reactance
ϕm be the maximum value of flux in Weber In the following figure, leakage reactance and resistance of the primary winding as well as secondary
f be the supply frequency in Hz winding are taken out, representing a practical transformer.
N1 is the number of turns in the primary winding
N2 is the number of turns in the secondary winding
Φ is the flux per turn in Weber
Now, equating the equation (8) and (9) we get
Fig; Practical Transformer with Resistance And Leakage Reactance Total reactive drop in a transformer
Fig: Flux waveform
The above equation is called the turn ratio where K is known as transformation ratio.
As shown in the above figure that the flux changes from + ϕm to – ϕm in half a cycle of 1/2f seconds. Where, R1 and R2 = resistance of primary and secondary winding respectively
The equation (8) and (9) can also be written as shown below using the relation
By Faraday’s Law X1 and X2 = leakage reactance of primary and secondary winding resp.
(ϕm = Bm x Ai) where Ai is the iron area and Bm is the maximum value of flux density. The term
Let E1 is the emf induced in the primary winding Z1 and Z2 = Primary impedance and secondary impedance resp.
96 | P a g e 97 | P a g e 98 | P a g e 99 | P a g e
The following steps are given below to draw the phasor diagram Now, N1I1’ = N2I2 The resistance and the leakage reactance of the windings result in a voltage drop, and hence secondary
1. The function of the magnetizing component is to produce the magnetizing flux, and thus, it will terminal voltage V2 is the phasor difference of E2and voltage drop.
be in phase with the flux. V2 = E2 – voltage drops
2. Induced emf in the primary and the secondary winding lags the flux ϕ by 90 degrees. I2 R2 is in phase with I2 and I2X2 is in quadrature with I2.
3. The primary copper loss is neglected, and secondary current losses are zero as I2 = 0. Therefore, Therefore, The total current flowing in the primary winding is the phasor sum of I1’ and I0.
the current I0 lags behind the voltage vector V1 by an angle ϕ0 called no-load power factor angle Primary applied voltage V1 is the phasor sum of V1’ and the voltage drop in the primary winding.
shown in the phasor diagram above. The phasor difference between V1 and I1 gives the power factor angle ϕ1 of the primary side of the Current I1’ is drawn equal and opposite to the current I2
4. The applied voltage V1 is drawn equal and opposite to the induced emf E1 because the difference transformer. V1 = V1’ + voltage drop
between the two, at no load, is negligible. The power factor of the secondary side depends upon the type of load connected to the transformer. I1R1 is in phase with I1 and I1XI is in quadrature with I1.
5. Active component Iw is drawn in phase with the applied voltage V1. If the load is inductive as shown in the above phasor diagram, the power factor will be lagging, and if the The phasor difference between V1 and I1 gives the power factor angle ϕ1 of the primary side of the
6. The phasor sum of magnetizing current Im and the working current Iw gives the no load current I0. load is capacitive, the power factor will be leading.The total primary current I1 is the vector sum of the transformer.
current I0 and I1’. i.e The power factor of the secondary side depends upon the type of load connected to the transformer.
If the load is inductive as shown in the above phasor diagram, the power factor will be lagging, and if the
load is capacitive, the power factor will be leading. Where I1R1 is the resistive drop in the primary
Fig: Operation of the Transformer on Load Condition
windings
When the load is connected to the secondary of the transformer, the I2current flows through their
I2X2 is the reactive drop in the secondary winding
secondary winding. The secondary current induces the magnetomotive force N2I2 on the secondary Phasor Diagram of Transformer on Inductive Load:
winding of the transformer. This force set up the flux φ2 in the transformer core. The flux φ2 oppose the The phasor diagram of the actual transformer when it is loaded inductively is shown below
Phasor Diagram of Transformer on Capacitive Load
flux φ, according to Lenz’s law
The Transformer on Capacitive load (leading power factor load) is shown below in the phasor
diagram.
The power factor of the load is leading. Therefore current I2 is drawn leading E2 The terminal voltage V2 across the load is equal to the induced emf E2 in the secondary winding less The equivalent resistance referred to secondary side is given as If the secondary terminals of the transformer are open circuited or no load is connected to the secondary
The resistance and the leakage reactance of the windings result in a voltage drop, and hence secondary voltage drop in the secondary winding. terminals, the no-load current flows through it. If the no current flows through the secondary terminals of
terminal voltage V2 is the phasor difference of E2and voltage drop. Primary reactance referred to secondary side is given as the transformer, the voltage drops across their resistive and reactive load become zero. The voltage drop
V2 = E2 – voltage drops Equivalent Circuit when all the Quantities are referred to Primary side: across the primary side of the transformer is negligible.
I2 R2 is in phase with I2 and I2X2 is in quadrature with I2. In this case to draw the equivalent circuit of the transformer all the quantities are to be referred to the
Current I1’ is drawn equal and opposite to the current I2 primary as shown in the figure below The equivalent reactance referred to secondary side is given as If the transformer is fully loaded, i.e., the load is connected to their secondary terminal, the voltage drops
The total current I1 flowing in the primary winding is the phasor sum of I1’ and I0. appear across it. The value of the voltage regulation should always be less for the better performance of
Primary applied voltage V1 is the phasor sum of V1’ and the voltage drop in the primary winding. transformer.
V1 = V1’ + voltage drop No load current I0 is hardly 3 to 5% of full load rated current, the parallel branch consisting of resistance
I1R1 is in phase with I1 and I1XI is in quadrature with I1. R0 and reactance X0 can be omitted without introducing any appreciable error in the behavior of the
transformer under the loaded condition.
The phasor difference between V1 and I1 gives the power factor angle ϕ1 of the primary side of the
Further simplification of the equivalent circuit of the transformer can be done by neglecting the parallel
transformer.
branch consisting R0 and X0. The simplified circuit diagram of the transformer is shown below
The power factor of the secondary side depends upon the type of load connected to the transformer.
EQUIVALENT CIRCUIT OF A TRANSFORMER: Fig: Circuit Diagram of Transformer when all the Secondary Quantities are Referred to Primary Side
The equivalent circuit diagram of any device can be quite helpful in predetermination of the behaviour of
The following are the values of resistance and reactance given below
the device under the various condition of operation. It is simply the circuit representation of the equation Fig: Equivalent Circuit of transformer
Secondary resistance referred to primary side is given as
describing the performance of the device.
From the circuit diagram shown above, the following conclusions are made
The simplified equivalent circuit of a transformer is drawn by representing all the parameters of the The primary voltage of the transformer is always greater than the emf induces on the primary side. V1>E1
transformer either on the secondary side or on the primary side. The equivalent circuit diagram of the The secondary terminal voltage at no load is always greater than the voltage at full load condition. E2>V2
The equivalent resistance referred to primary side is given as
transformer is shown below Fig: Simplified Equivalent Circuit Diagram of a Transformer By considering the above circuit diagram, the following equations are drawn
When the transformer is loaded with continuous supply voltage, the terminal voltage of the transformer For inductive load:
varies. The variation of voltage depends on the load and its power factor.
Equivalent Circuit when all the Quantities are referred to Secondary side: Mathematically, the voltage regulation is represented as
The equivalent circuit diagram of the transformer is shown below when all the quantities are referred to the
Fig: Equivalent circuit diagram of a transformer secondary side.
Let the equivalent circuit of a transformer having the transformation ratio K = E2/E1
The induced emf E1 is equal to the primary applied voltage V1 less primary voltage drop.This voltage
causes current I0 no load current in the primary winding of the transformer. The value of no-load current
Where,
is very small, and thus, it is neglected. Hence, I1 = I1’. The no load current is further divided into two
E2 – secondary terminal voltage at no load
components called magnetizing current (Im) and working current (Iw).
V2 – secondary terminal voltage at full load
These two components of no-load current are due to the current drawn by a noninductive resistance
The voltage regulation by considering the primary terminal voltage of the transformer is expressed as,
R0 and pure reactance X0 having voltage E1 or (V1 – primary voltage drop). Fig: Circuit Diagram of Transformer When All the Primary Quantities are Referred to Secondary Side Where,
The secondary current I2 is The following are the values of resistance and reactance given below
Primary resistance referred to secondary side is given as Let us understand the voltage regulation by taking an example explained below
The three phase power is used in almost all fields of electrical power system such as power generation,
THREE PHASE TRANSFORMER CONNECTIONS:
transmission and distribution sectors, also all the industrial sectors are supplied or connected with three
phase system. Therefore, to step-up (or increase) or step-down (or decrease) the voltages in the three Three phase transformer connections in three phase system, the three phases can be connected in either
phase systems, three phase transformers are used. As compared with the single phase transformer, there star or delta configuration. In case you are not familiar with those configurations, study the following
are numerous advantages with 3 phase transformer such as smaller and lighter to construct for the same image which explains star and delta configuration. In any of these configurations, there will be a phase
power handling capacity, better operating characteristics, etc. difference of 120° between any two phases.
Fig: Three phase transformer
Instead of using three single phase transformers, a three phase bank can be constructed with a single three
phase transformer consisting of six windings on a common multi-legged core. Due to this single unit,
weight as well as the cost is reduced as compared to three units of the same rating and also windings, the
amount of iron in the core and insulation materials are saved. Space required to install a single unit is less
compared with three unit bank. But the only disadvantage with single unit three phase transformer is if the Fig: Shell Type
fault occurs in any one of the phase, then entire unit must be removed from the service.
Working of Three Phase Transformers:
Construction of Three Phase Transformers: Consider the below figure in which the primary of the transformer is connected in star fashion on the
A three phase transformer can be constructed by using common magnetic core for both primary and cores. For simplicity, only primary winding is shown in the figure which is connected across the three
secondary windings. As we discussed in the case of single phase transformers, construction can be core phase AC supply. The three cores are arranged at an angle of 120 degrees to each other. The empty leg of
type or shell type. So for a bank of three phase core type transformer, three core type single phase each core is combined in such that they form center leg as shown in figure.
transformers are combined. Similarly, a bank of three phase shell type transformer is get by properly
combining three shell type single phase transformers. In a shell type transformer, EI laminated core
surrounds the coils whereas in core type coil surrounds the core.
This connection can be used even for unbalanced loading. The illustration shows how an open delta transformer is connected. On both the primary and secondary
Another advantage of this type of connection is that even if one transformer is disabled, system can THREE PHASE TO SIX PHASE CONVERSION there are only two windings. Even in this configuration, it is still possible to transform a three phase VA=3VLIph
continue to operate in open delta connection but with reduced available capacity. voltage. And for the open delta connection:
Star-Delta OR Wye-Delta (Y-Δ) In certain applications like thyristors and rectifiers six phase supply is required. Therefore it
The primary winding is star (Y) connected with grounded neutral and the secondary winding is becomes necessary to convert three phase a.c. supply into six phase. By using three identical single phase VA= Iph
delta connected. transformers suitably interconnected this can be achieved. The primary winding is connected in delta
This connection is mainly used in step down transformer at the substation end of the transmission whereas its secondary winding is split up into two halves. Thus conversion from 3 phase to six phase can Taking the ratio of open delta to closed delta power, gives:
line. be obtained by having two similar secondary windings for each of the primaries of the three phase
The ratio of secondary to primary line voltage is 1/√3 times the transformation ratio. transformer. This is showing in the Fig. 1. =0.577(or 57.7%)
There is 30° shift between the primary and secondary line voltages. Open delta transformers are three phase devices, with only two windings on each of the primary and
The three phase supply is given to primaries of the three transformers and six phase output can be secondary sides. While cheaper than a conventional three winding transformer, the open delta will only
Delta-Star OR Delta-Wye (Δ-Y) obtained from the six secondaries as shown. There are many ways of connecting these secondaries. Some deliver 57.7% of the power of a conventional transformer (not two thirds, 66.7% as may be expected).
The primary winding is connected in delta and the secondary winding is connected in star with of them are i) double delta ii) double star iii) dimetrical. The dimetrical connection is generally used in There is limited adoption of open delta transformers, although they can be useful in certain situations.
neutral grounded. Thus it can be used to provide 3-phase 4-wire service. practice.
Open Delta Transformer
This type of connection is mainly used in step-up transformer at the beginning of transmission line. Power Factor with Two Transformers in 3-Phase Open-Delta Configuration:
The ratio of secodary to primary line voltage is √3 times the transformation ratio.
Open delta transforms are not the commonly used. Typically they would be used for small loads where
There is 30° shift between the primary and secondary line voltages. The power factor of a typical T/F is 0.866, so the max output (KVA) of a T/F will be 86.6% of its rated
cost is important. Alternatively, they could be used as an emergency measure, should one winding only
of a transformer fail. capacity. Suppose we have three transformers each having the same rating (50 KVA). Then the total
Above transformer connection configurations are shown in the following figure. capacity is equal to 150 * 0.866=130 KVA and not 150 KVA. (The factor 0.866 is called the Utility
Sometimes you may hear an open delta transformer referred to as a V-connection transformer.
Factor.)
Power Delivered:
Sometimes the power delivered by an open delta transformer is compared to that of an equivalent three If one transformer is removed, the total output of two T/Fs will be 100 * 0.866=86.6 KVA. From this
winding transformer. Typically figures like having 57.7% of the capacity of an equivalent three winding calculation, we see that output capacity is reduced when a Delta-Delta configuration is operated as an
transformer or 87% of two transformers (same winding size) are quoted. While you can think of the Open-Delta connection, i.e. with one T/F removed.
transformer in this manner, it is more fruitful not to consider comparisons but to the necessary
calculations on the open delta transformer. Let say the two T/Fs of Open-Delta configuration are supplying 3-phase power to a load having power
factor Cosα. The power factor of one T/F is Cos(30-α) and the other is Cos(30+α).
Case (i): When phase angle (α=0) is zero, mean load p.f=1 - each transformer has power factor =
Cos30 = 0.866
Case (ii):When phase angle is 30(α=30), mean load p.f=0.866, one T/F will have p.f of cos(30-30) =
Cos0 = 1 and the other will be operating at p.f of Cos(30+30) = Cos60 = 0.866
Case(iii):When phase angle is 60 (α=60), mean load p.f=0.5, then one T/F will have p.f of Cos(30-60)
= 0.866 and other will have a p.f of Cos(30+60) = Cos90 = 0.
From the third scenario we conclude that if we have a transformer Open-Delta configuration in which one
Fig. 1 The double delta connection
T/F is transferring power to an entire load at a p.f of 0.866, then the other one will not provide any load.
The same voltage turn in portion AN, ND and AD are shown by the equations, PRINCIPLE OF OPERATION OF AUTOTRANSFORMER:
The principle of operation of the transformer is the same as the one of the common transformer, and then
the relation between input and output voltages and input and output currents and the ratio of number of
turns between the primary and the secondary winding is the same.
The currents of the primary and secondary windings are flowing on the opposite directions, so the total
current flowing through the common part of the winding is equal to the difference between the current on
the low-voltage winding and the current on the high-voltage winding.
The identical, interchangeable transformers are used for Scott-T connection in which each transformer has
a primary winding of Tp turns and is provided with tapping at 0.289Tp , 0.5Tpand 0.866 Tp. A simplified diagram of a Step-down Auto Transformer is shown in figure below.
AN : ND = 2 : 1
1. The Scott-T connection is used in an electric furnace installation where it is desired to operate two
single-phase together and draw the balanced load from the three-phase supply.
2. It is used to supply the single phase loads such as electric train which are so scheduled as to keep
For keeping the voltage per turn same in the primary of the main transformer and the primary of the teaser
the load on the three phase system as nearly as possible. Fig: Auto transformer
transformer, the number of turns in the primary of the teaser transformer should be equal to √3/2T p.
= (V1-V2) I1 .....................................(2) Note that the resistance r1 and leakage reactance xl1 refer to that part of the winding where only the Off-load tap-changing transformer:
primary current flows. Similarly on the load side
In this method, the transformer is disconnected from the main supply when the tap setting is to be
Now, total VA input = V1 I1 we have,
changed. The tap setting is usually done manually. The off load tap changing transformer is shown in the
E2 = V2 + (I2 − I1)(r2 + jxl2)
figure below
Therefore,
The voltage ratio V1 : V2 = E1 : E2 = T1 : T2 = a where T1 is the total turns of the primary. Then E1 =
Transformed VA / Input VA = [(V1-V2) I1] / V1I1 aE2 and I2 = aI1
= 1 – V2/V1 The magnetization branch can now be hung across the mains for completeness. The above equivalent
circuit can now be compared with the approximate equivalent circuit of a two winding case Re = r1 + a 2
= 1-k r2 and Xe = xl1 + a 2xl2. Thus in the case of an auto transformer total value of the short circuit
impedance is lower and so also the percentage resistance and reactance. Thus the full load regulation is
Thus we see that out of total input VA, only a part of it is transformed by Transformer action and lower. Having a smaller value of short circuit impedance is sometimes considered to be a disadvantage.
remaining is therefore transferred by conduction. That is because the short circuit currents become very large in those cases. The efficiency is higher in
auto transformers compared to their two winding counter part at the same load. The phasor diagram of
Fig: Phasor Diagram
So, operation for the auto transformer drawing a load current at a lagging power factor angle of θ2 is shown
in Fig. 32. The magnetizing current is omitted here again for simplicity. On-load tap-changing transformer:
Conducted VA = Total Input – Transformed VA
Advantages of Auto transformer:
Less costly In order that the supply may not be interrupted, on-load tap changing transformer is used. Such a
Better regulation transformer is known as a tap-changing under load transformer. While tapping, two essential conditions
= V1I1 – (V1-V2) I1 ............................ From equation (1)
Low losses as compared to ordinary two winding transformer of the same rating. are to be fulfilled.
= V2I1
So, Disadvantages of Auto transformer: The load circuit should not be broken to avoid arcing and prevent the damage of contacts.
There are various advantages of the auto transformer, but then also one major disadvantage, why auto No parts of the windings should be short–circuited while adjusting the tap.
Conducted VA / Input VA = V2I1/ V1I1 transformer is not widely used, is that
= V2/V1= k The secondary winding is not insulated from the primary winding.
Thus in an Auto Transformer, a part of input power is delivered to the load by Transformer action while If an auto transformer is used to supply low voltage from a high voltage and there is a break in the
the remaining is by conduction method. Power transfer because of conduction method is possible in Auto secondary winding, the full primary voltage comes across the secondary terminal which is dangerous
Transformer because a part of winding is common to both the primary as well as secondary circuit. to the operator and the equipment. So the auto transformer should not be used to for interconnecting
high voltage and low voltage system.
EQUIVALENT CIRCUIT OF AUTOTRANSFORMER: Fig: Equivalent Circuit Used only in the limited places where a slight variation of the output voltage from input voltage is
From the foregoing study it is seen that there are several advantages in going in for the autotransformer required.
type of arrangement. The voltage/current transformation and impedance conversion aspects of a two
winding transformer are retained but with lesser material (and hence lesser weight) used. The losses are Applications of Auto transformer:
reduced increasing the efficiency. Reactance is reduced resulting in better regulation characteristics. All It is used as a starter to give upto 50 to 60% of full voltage to the stator of a squirrel cage induction
these benefits are enhanced as the voltage ratio approaches unity. The price that is required to be paid is motor during starting.
loss of electrical isolation and a larger short circuit current (and larger short circuit forces on the winding). It is used to give a small boost to a distribution cable, to correct the voltage drop.
It is also used as a voltage regulator
Used in power transmission and distribution system and also in the audio system and railways. The tap changing employing a center tapped reactor R show in the figure above. Here S is the diverter
switch, and 1, 2, 3 are selector switch. The transformer is in operation with switches 1 and S closed. To
TAP-CHANGING TRANSFORMERS change to tap 2, switch S is opened, and 2 is closed. Switch 1 is then opened, and S closed to complete the
Fig: Auto transformer on load The change of voltage is affected by changing the numbers of turns of the transformer provided with taps. tap change. It is to be noted that the diverter switch operates on load, and no current flows in the selector
For sufficiently close control of voltage, taps are usually provided on the high voltage windings of the switches during tap changing. During the tap change only half of the reactance which limits the
As mentioned earlier the magnetizing current can be neglected, for simplicity. Writing the Kirchoff’s transformer. There are two types of tap-changing transformers
equation to the primary and secondary
In a three-phase transformer, the non-sinusoidal nature of magnetising current produces sinusoidal flux
which gives rise to the undesirable phenomenon. The phase magnetising currents in transformer should
contain third harmonics and higher harmonics necessary to produce a sinusoidal flux.
If the phase voltage across each phase is to remain sinusoidal, then the phase magnetising currents must
be of the following form.
It is seen from equation (1), (2), and (3) that the third harmonics in the three currents are co-phase, that is
they have the same phase. The fifth harmonics have different phases.
Delta Connection
135 | P a g e