Calculation Protection
Calculation Protection
2 Protection of Transformer
In 30 MVA transformer (1) and transformer (2), instantaneous overcurrent
relay and instantaneous overcurrent ground relay are not employed. But all 30 MVA
transformers are protected by master relay. For 10 MVA transformers, only time
overcurrent relay and time overcurrent ground relay are employed for protection.
For transformer protection, relay settings for time overcurrent and
instantaneous overcurrent relays are assigned as follow
For R51 100% -150% of maximum rated current
K
t TMS L
I
I S 1
where;
t = Operation Time
K = Factor (see table)
36
4.3 Calculation for Relay Setting of Transformer (100 MVA, 230/66 kV) at High
Tension.
= 100MVA
3 230 kV
= 251.02 A
Therefore CT ratio is selected as 200:5
Base Values are
= 9.4 A
Overcurrent setting is taken as 9.4 A
0.14 0
1.2 TMS 376.53
0.02
1
1809.81
TMS = 0.26
(2) Relay Setting Calculation for OCGR (51N)
Earth Fault Current = 30% of rated current
= 0.3× 251.02
= 75.31 A
Relay Current = Earth Fault Current × CT ratio
5
= 75.31×
200
= 1.882 A
OCGR (51N) current setting is taken as 1.882 A
= 132.8kV
0.01 (13.87 13.87 12) 529.04
= 631.66 A
Taking operating delay time as 1.2 second, the TMS is obtained from the following
relation:
K
t TMS L
I
I S 1
38
0.14 0
1.2 TMS 631.66 0.02
75.31 1
TMS = 0.37
(3) Relay Setting Calculation for IOCR (50)
Fault Current = 2.5 time of three phase short circuit current
= 2.5 × 1809.81
= 4524.53 A
Relay Current = Fault Current × CT ratio
5
= 4524.53 ×
200
= 113.113 A
Instantaneous overcurrent setting is taken as 113.113 A
4.4 Calculation for Relay Setting of Transformer (100 MVA, 230/66 kV) at Low
Tension.
= 100MVA
3 66kV
= 874.77 A
BaseMVA 33.3MVA
Base Current = = = 874.02 A
BasekV 38.1kV
BasekV 38.1kV
Base Impedance = = = 43.5 Ω
Rated Current 874.77 A
(1) Relay Setting Calculation for OCR (51)
= 1.5 × 874.77
= 1312.155 A
Relay Current = Fault Current × CT ratio
5
= 1312.155 ×
1000
=6.56 A
Overcurrent setting is taken as 6.56 A
Taking operating delay time as 1.2 second, the TMS is obtained from the following
relation:
K L
t TMS I α
I 1
s
0.14 0
1.2 TMS 1312.155 0.02
6314.8 1
TMS = 0.26
= 2203.98 A
Taking operating delay time as 1.2 second, the TMS is obtained from the following
relation:
K L
t TMS I α
I 1
s
0.14 0
1.2 TMS 2203.98 0.02
262.43 1
TMS = 0.37
(3) Relay Setting Calculation for IOCR (50)
Fault Current = 2.5 time of three phase short circuit current
= 2.5 × 6314.8
= 15787 A
Relay Current = Fault Current × CT ratio
5
= 15787 ×
1000
= 78.94 A
IOCR (50) current setting is taken as 78.94 A