V1162

FD-C Series

Circular Single Blade

Externally Resettable

Combination Fire and

Volume Control Damper

• ES classified fire dampers with reduced smoke leakage characteristics (BS EN 1366-2)

• Aerodynamically Air Control tested to BS EN 1751

• Tested and assessed installation methods in differing supporting constructions (BS EN 1366-2)

• Integrated volume control capability

• Replaceable fusible link from outside of the ductwork

• Commissioning friendly

• External blade position indicator

• Damper casing conforms to BS EN 1506

ADE I
M

BR
I TA I N
M A N U FAC T U R E R S O F A I R , F I R E A N D S M O K E C O N T R O L P R O D U C T S
FD-C Series
Single Blade Circular Fire Dampers – Introduction

The FD-C Series The FD-C Series Range

The FD-C Manual Operation Single Blade Fire Damper with volume The BSB FD-C series is available in

control facility has been designed specifically for installations where space the following case diameters:

is at a premium and installation within the fire separation is not feasible. FD-C100 - 100mm diameter

The testing and resetting of the damper and thermal fuse external of the FD-C125 - 125mm diameter

duct allows for ease of commissioning and maintenance. NB: Access FD-C150 - 150mm diameter

panels may be required to comply with DW145 G.3.1.5. FD-C160 - 160mm diameter

The installation plate, with its engineered installation perforations, acts as FD-C200 - 200mm diameter

a template to allow the marking of the fixing positions on the surface FD-C250 - 250mm diameter

structure to which the plate will be affixed, allowing for a quick and FD-C300 - 300mm diameter

efficient install. FD-C315 - 315mm diameter

Introduction Testing and Conformities

What is a fire damper and why might they be needed?


Tested to EN1366-2
The FD-C Series Single Blade Circular Fire Damper is designed to
See installation details (Pages 6-11) for full details.
stop the spread of fire through ducts, walls, floors and ceilings.
Tested/assessed and achieved equivalent classification to:

The product range has many features and options to meet the
ES Classification (BS EN 1366-2/BS EN 13501-3)
requirements of specifiers, contractors, local and national authorities.
• BSB FD-C fitted with Installation Plate
Dampers are available to suit both low/medium and high velocity

applications. E180 - Blockwork/Masonr y wall

ES120 - Blockwork/Masonr y wall


What are the ‘E’ and ‘ES’ classifications?

To achieve the classifications to EN13501-3, fire dampers and fire E90 - Dr y Par tition wall

and smoke dampers shall be tested to EN1366-2 and a 300Pa ES90 - Dr y Par tition wall

pressure difference is applied across the damper. During the fire


FD-C Blade leakage
test period, the integrity of the seal between the damper and the

structure shall not have any gaps larger than 150mm x 6mm. There (BS EN 1751)

shall not be any sustained flaming. The largest size of damper to be • Class 2

manufactured for sale as a single section shall be fire tested.

E = Integrity

The maximum leakage permissible at 300Pa corrected to 20°C is


3 2 2
360m /hr/m (100 l/s/m ) throughout the fire test period.

ES = Integrity with Smoke Leakage Performance

The maximum leakage permissible at 300Pa corrected to 20°C is


3 2 2
200m /hr/m (55.5 l/s/m ) at ambient prior to the fire test and

throughout the fire test period. In addition, for the ES classification to


3 2
be attained, the smallest damper must also meet the 200m /hr/m

maximum leakage with a 300Pa pressure across the damper. (This is

equivalent to just 0.55 l/s on a 100x100 damper)

Fire dampers should be installed as tested.

Some applications (fan off) allow the use of tests under taken to BS

476-20/22 and this is also allowed worldwide in areas outside of the

EU. Test repor ts showing testing to EN 1366-2 should be acceptable

to meet the requirements of BS 476-20/22, but the reverse is

definitely not the case and no classifications are available.


FD-C Features and Benefits
However, as a word of caution, in whichever case, the correct model

must be selected, to match fire resistance time with installation • Tested and cer tified installation variants of the FD-C are available for

method and with the suppor ting construction (wall or floor). both blockwork and stud par titions.

To ensure that all testing and assessments are traceable back to • All BSB tested installation methods give at least a E90 classification.

initial fire test repor ts, the BSB FD-C series is product cer tificated by

the Loss Prevention Cer tification Board (LPCB). This means that in Nom. Dia.
Weight Chart 250mm 320mm
addition to normal BS EN ISO 9001 compliance, the product is also (mm) no inst.plate with inst. plate
(kg approx.)
checked to ensure that same product is being manufactured that has
100 0.7 1.1
been tested or assessed.
125 0.8 1.5
BSB have a policy of continued testing and product cer tification to
150 1.1 1.7
tr y and provide as broad a number of installation methods as
160 1.2 1.8
possible.

200 1.6 2.4


BSB also follow regulation and standards development ver y carefully

250 2.4 3.4


to provide input on changes and to be able to pass on relevant

information to designers, specifiers, building control authorities 300 3.3 4.6

(BCA's) and installers. 3.6 5.0


315

2 www.bsb-dampers.co.uk
FD-C Series
Single Blade Circular Fire Dampers – Product Specification

Case

Galvanised mild steel to BS EN 10346 DX 51D Z275

0.6mm thick for 100mm dia. to 250mm dia.

0.7mm thick for 300mm dia. to 315mm dia.

Damper casing conforms to BS EN 1506.

Fusible Link

Fusible link externally replaceable rated at

72°C has been designed to alleviate

possible linear creep of the solder

joint. The thermal link is screwed

into position via the 12.5mm

diameter brass holder activating

the locking assembly from outside

the case in any position from fully

open to fully closed, allowing air

balance during the commissioning

of the ducted system.

Handle

The handle is a 8mm dia. preformed

400 series ferretic stainless steel rod

that allows the setting of the damper

to any set point or fully open

position. The blade angle is shown

via the graduated affixed label.

Installation Plate

The optional installation plate allows the

damper to be fixed into place from one side

only with no infill material being required. Use

either of the two appropriate 5mm dia. corner

fixing holes and all of the 5mm dia. mid

span fixing holes to secure the plate into position.

(Note: Option without installation plate is not CE marked)

Volume Control Application

The FD-C manual damper has the facility for volume control utilising the

seven presets at 10° set points from fully open to 30° from the fully

closed position.

The operating handle has been designed to be in line with the blade orientation thus providing an accurate guide to the blade set or released

position.

The FD-C manual damper continues to be a fully operational fire damper at these presets, and when released closed manually or through the

melting of the thermal fuse meets the test criteria of EN 1366-2 as provided in the relevant test repor ts.

Blade Seal (patent pending)

Layered glass woven sheets and

central intumescent disc to a

patented design that allows the

blade assembly to be of minimal

thickness, thus minimising

pressure loss, providing an

effective seal to comply with

EN 1366-2 achieving ES

classification.

Blade

Galvanised 1.2mm one piece

circular steel discs either side of

the patented seal design

providing a 5mm thick assembly

affixed by blade brackets to the

reset handle. Grade 430 stainless


Blade Closed Blade Open
steel option available.

www.bsb-dampers.co.uk 3
FD-C Series
Single Blade Circular Fire Dampers – Product Dimensions

The FD-C Series - MANUAL Operation

FD-C With
320
Installation Plate

A = 40mm

(100mm to 200mm diameter) or

60mm

(250mm to 315mm)
Diameter

C = 150mm

(100mm to 200mm diameter) or

110mm

(250mm to 315mm)

A C 35 35 20 A

60 13
60

* Plate Size (See Table Below)


75

45

Installation Plates 60
20mm
Dia. Plate Size Flange Size Spigot Length
radius
Model 2
(mm) (mm ) (mm) (mm) corners
60
FD-C100 100 220 60 40
See left
for details
FD-C125 125 245 60 40
of number
of fixing holes
FD-C150 150 270 60 40

FD-C160 160 280 60 40

Diameter
FD-C200 200 320 60 40

FD-C250 250 370 60 60

FD-C300 300 420 60 60


Installation
Plate to be
FD-C315 315 435 60 60
cut for fitting
to case - tack
welded
NB: Use either of the two appropriate 5mm dia. corner fixing holes
together
and all of the 5mm dia. mid span fixing holes to secure the plate into during fitment
position.

4 www.bsb-dampers.co.uk
FD-C Series
Single Blade Circular Fire Dampers – Specifications and Accessories

Installation Plate Detail Cleats

Cleats are factor y fitted as pairs to the damper installation plate on the

46.11mm same face as the control side, allowing the damper to be suppor ted via

drop roads. It is recommended that the installation plate is additional

utilised in the installation of the damper to ensure that the damper

does not move in a fire condition.

25mm See Below for Drop Rod details.

Installation Plate Cleats Detail

33
50

12mm dia.
50 57 40 fixing holes 40 57
Typical Tender/Specification Text
5
The BSB FD-C combination Fire and Volume Control Damper
51
shall pass the test requirements stated in EN 1366-2.

For maintenance of the integrity of compar tmentation the fire

damper shall have an E classification to EN 13501-3.

The damper shall have an ES classification complying with

EN1366-2 and EN 13501-3 and have a minimum E90 and ES90


Diameter
rating.

Damper casings shall conform to BS EN 1506.

For the protection of escape routes and areas with sleeping risk,

the FSD-C fire/smoke damper should be used. Please refer

Approved Document B (ADB).

The single blade layered design shall be held open against a

constant force spring that is released via a fusible link having an

alloy component that melts at 72°C allowing the spring

mechanism to close the damper.

The damper assembly and fusible link shall be safely tested and

released closed externally to the damper without the need for

specialist tools or access panels. NB: Access panels may be Drop Rod Studding Minimum Recommended Dia.

required to comply with DW145 G.3.1.5. Minimum loads are taken from the ASFP Blue Book and refers to

The fire damper body shall be fully welded to meet the air unprotected steel studding, generally up to 1.5m long.

tightness test requirements of HVCA specification DW144 to


The figures shown must be read in conjunction with the ASFP Blue
class A B & C to a maximum of 1000Pa and comply with EN1751.
Book.

The closed blade shall meet the air tightness test requirement of
>

BS EN 1751 Class 2. 60 mins - 15n/mm 2 Min. load

The BSB FD-C combination fire and volume control damper shall CSA Max. load per pair of
OD Pitch Core D
>

have a tested or assessed installation method that matches the (mm 2) studs (kg)

requirement of the suppor ting construction. DW145 Method 4


M6 6 1.00 4.772 17.9 54.7

Blockwork Walls and Par tition Walls refers.


M8 8 1.25 6.465 32.8 100.4

M10 10 1.50 8.158 52.3 159.8


Leakage Classification

Blade leakage classification is given numerically and case leakage M12 12 1.75 9.851 76.2 233.1

classification is given using capital letters.

• Class 4, 3, 2 or 1 refers to blade leakage –


120 mins - 10n/mm 2 Min. load
>

EN1751 section C .2 refers


CSA Max. load per pair of
• Class 4 achieving the lowest leakage.
OD Pitch Core D
>

(mm 2) studs (kg)


• Class A, B or C refers to casing leakage -

EN1751 section C .3 refers M6 6 1.00 4.772 17.9 36.5

• DW144 par t 8 table 17 and figure 178 refers.


M8 8 1.25 6.465 32.8 66.9
• Class C achieving the lowest leakage at elevated pressures.

M10 10 1.50 8.158 52.3 106.6


The above references are illustrated in the graphs on Pages 6, 7

and 9 of this brochure. M12 12 1.75 9.851 76.2 155.4

www.bsb-dampers.co.uk 5
FD-C Series
Single Blade Circular Fire Dampers – Product Testing

FD-C in Blockwork Wall - Damper as tested with Installation Plate and Handle to the inside of the furnace

Tested to BS EN 1366-2 - Test Report No. 276065 refers Test Conclusions:

The FD-C damper satisfied the requirements of BS EN 1366-2 and


• Fire and Volume Control dual function
BS EN 13501-3 achieving the lowest closed blade leakage of any
• Tested to BS EN 1366-2 and BS EN 13501-3
damper within its class.
• E180 integrity classification.
Dampers were tested affixed to the inside of the furnace wall and
• ES120 integrity classification.
also to the external wall of the furnace with the damper closed

blade being fully exposed to the furnace rapid rising temperature.


• Complies with classes A, B & C of DW144.
The achieved ES classification ensures that in a fire condition the
• Surpasses minimum requirements on case leakage
non fire side is fully protected (from radiated heat) for the
• Surpasses minimum requirements on blade leakage
achieved period, providing vital time for the emergency ser vices to

respond, ensuring safe passage of escape and protection of

contents

VIEW FROM INSIDE FURNACE

750
NON
A FURNACE
FURNACE
SIDE
SIDE

1500

No infill
ATION
INSTALLATION required thus
allowing ease
PLATE of installation
as tested
BLOCKWORK
CKWORK
O5 X 50 LODEN
LL
WALL
ANCHORS
used to secure damper
installation plate to
blockwork

750
150

1500
M

N
Blade Leakage Graph Case Leakage Graph - Model FD-C100

1000 2000
3
4

ss
ss

la
la

C
C

-
-

1
1

5
5

2
7
7

ss
1

C
N
N

la

ss
E

la
E

Leakage C
-

1
1

5
Pressure Drop (Pa)

Duct Pressure (Pa)

7
5

1
7

1000 N
1

E
N
E

B
ss
la
C
100 1
5
7
1
N
E

100
A
ss
la
C
1
5
7
1
300mm dia. N
E
200mm dia.

100mm dia.

10
10
1 10 100 0.01 0.1 1

2 2
Leakage (l/s/m ) Leakage (l/s/m )

See Page 10 for Pressure Drop Graphs

6 www.bsb-dampers.co.uk
FD-C Series
Single Blade Circular Fire Dampers – Product Testing

FD-C in Blockwork Wall - Damper as tested with Installation Plate and Handle to the non furnace side

Tested to BS EN 1366-2 - Test Report No. 281585 refers Test Conclusions:

The FD-C damper satisfied the requirements of BS EN 1366-2 and


• Fire and Volume Control dual function
BS EN 13501-3 achieving the lowest closed blade leakage of any
• Tested to BS EN 1366-2 and BS EN 13501-3
damper within its class.
• DW145 Method 4 refers
Dampers were tested affixed to the inside of the furnace wall and
• E240 integrity classification.
also to the external wall of the furnace with the damper closed
• ES240 integrity classification.
blade being fully exposed to the furnace rapid rising temperature.

The achieved ES classification ensures that in a fire condition the


• Complies with classes A, B & C of DW144.
non fire side is fully protected (from radiated heat) for the
• Surpasses minimum requirements on case leakage
achieved period, providing vital time for the emergency ser vices to
• Surpasses minimum requirements on blade leakage
respond, ensuring safe passage of escape and protection of

contents

VIEW FROM NON-FURNACE SIDE (Plenum box removed)

750
NON
A FURNACE
FURNACE
SIDE
SIDE

1500 No infill
required thus
LLATION
INSTALLATION allowing ease
PLATE of installation
as tested
O5 X 50 LODEN BLOCKWORK
CKWORK
ANCHORS LL
WALL
used to secure damper
installation plate to
blockwork

750
150

1500
M

Blade Leakage Graph Case Leakage Graph - Model FD-C100

1000 2000
3
4

ss
ss

la
la

C
C

-
-

1
1

5
5

2
7
7

ss
1

C
N
N

la

ss
E

la
E

Leakage C
-

1
1

5
Pressure Drop (Pa)

Duct Pressure (Pa)

7
5

1
7

1000 N
1

E
N
E

B
ss
la
C
100 1
5
7
1
N
E

100
A
ss
la
C
1
5
7
1
300mm dia. N
E
200mm dia.

100mm dia.

10
10
1 10 100 0.01 0.1 1

2 2
Leakage (l/s/m ) Leakage (l/s/m )

See Page 10 for Pressure Drop Graphs

www.bsb-dampers.co.uk 7
FD-C Series
Single Blade Circular Fire Dampers – Product Testing

FD-C in Studwork - Thermal fuse inside and outside of furnace

Tested to BS EN 1366-2 - Test Report No. 276643 refers Test Conclusions:

The FD-C damper satisfied the requirements of BS EN 1366-2 and


• Fire and Volume Control dual function
BS EN 13501-3 achieving the lowest closed blade leakage of any
• Tested to BS EN 1366-2 and BS EN 13501-3
damper within its class.
• E90 integrity classification.
Dampers were tested affixed to the inside of the furnace wall and
• ES90 integrity classification.
also to the external wall of the furnace with the damper closed

blade being fully exposed to the furnace rapid rising temperature.


• Complies with classes A, B & C of DW144.
The achieved ES classification ensures that in a fire condition the
• Surpasses minimum requirements on case leakage
non fire side is fully protected (from radiated heat) for the
• Surpasses minimum requirements on blade leakage
achieved period, providing vital time for the emergency ser vices to

respond, ensuring safe passage of escape and protection of

contents

VIEW FROM NON-FURNACE SIDE

1500
NON
FURNACE FURNACE
SIDE SIDE

3000

900 1200

3000

The FD-C single blade combination fire and volume control

damper with its unique feature of requiring only a single installation

plate when being installed within tested applications, and without

the need for any infill between the damper body and the structure

that it sits within. Is the first damper of its type to achieve and

exceed the requirements of classification EN1366-2.


M

8 www.bsb-dampers.co.uk
FD-C Series
Single Blade Circular Fire Dampers – Product Testing

FD-C in Dry Wall - Test Report No. 276065 refers FD-C in Dry Wall - Test Report No. 276065 refers

Thermal fuse outside of furnace Thermal fuse inside of furnace

M
N

N
122 122

GTEC FIREBOARD GTEC FIREBOARD


ROCKWOOL ROCKWOOL
FLEXI SLAB FLEXI SLAB
(35KG/M3) (35KG/M3)
UT 72/R UT 72/R
TRACK TRACK
INSTALLATION
GTEC FIREBOARD PLATE
360 x 122 x 12.5 INSTALLATION
TYPE 5 GTEC FIREBOARD
PLATE 360 x 122 x 12.5
PLASTERBOARD TYPE 5
PLASTERBOARD

315MM DIA. DAMPER TESTED


315MM DIA. DAMPER TESTED

NON NON
FURNACE FURNACE FURNACE
FURNACE
SIDE SIDE SIDE
SIDE

DRY WALL SCREWS DRY WALL SCREWS


38 LONG 38 LONG

DRY WALL SCREWS DRY WALL SCREWS


38 LONG x 300 DRY WALL SCREWS DRY WALL SCREWS 38 LONG x 300
CENTRES 25 LONG 25 LONG CENTRES

O7.5 X 60 LONG STEEL


O7.5 X 60 LONG STEEL FIXINGS FIXINGS AT 600 CENTRES
AT 600 CENTRES

Blade Leakage Graph Case Leakage Graph - Model FD-C100

1000 2000
3
4

ss
ss

la
la

C
C

-
-

1
1

5
5

2
7
7

ss
1

C
N
N

la

ss
E

la
E

Leakage C
-

1
1

5
Pressure Drop (Pa)

Duct Pressure (Pa)

7
5

1
7

1000 N
1

E
N
E

B
ss
la
C
100 1
5
7
1
N
E

100
A
ss
la
C
1
5
7
1
300mm dia. N
E
200mm dia.

100mm dia.

10
10
1 10 100 0.01 0.1 1

2 2
Leakage (l/s/m ) Leakage (l/s/m )

See Page 10 for Pressure Drop Graphs

www.bsb-dampers.co.uk 9
FD-C Series
Single Blade Circular Fire Dampers – Performance Data

Performance Data

Pressure Drop Graph - Model FD-C100 Pressure Drop Graph - Model FD-C200

100mm diameter. 67.5° from open 200mm diameter. 67.5° from open

45° from open 45° from open


Free area = 64% Free area = 85%

22.5° from open 22.5° from open


Velocity range 0 to 10 m/s Velocity range 0 to 10 m/s
Fully open Fully open

1000 1000

100 100
Pressure Drop (Pa)

Pressure Drop (Pa)

10 10

1 1

1 10 11 12 1 10 11 12

Velocity (m/s) Velocity (m/s)

Pressure Drop Graph - Model FD-C300 Time / Temperature Curve - EN13501-4:2007

300mm diameter. 67.5° from open Standard Cur ve

45° from open BRE Test 276065


Free area = 91%

22.5° from open BRE Test 276066


Velocity range 0 to 10 m/s
Fully open

1000 1200

1100

1000

900

100
800
Pressure Drop (Pa)

Temperature (°C)

700

600

500

10 400

300

200

100

1
0

1 10 11 12 0 30 60 90 120 150 180 210 240 270

Velocity (m/s) Time (minutes)

10 www.bsb-dampers.co.uk
FD-C Series
Single Blade Circular Fire Dampers – Installation and Maintenance

Installation Method Micro Switch

The factor y fitted micro switch to provide remote indication of the


DW145 Method 4 - Blockwork walls
damper blade status. The micro switch is fitted on the opposite side to
DW145 Method 4 - Partition walls
the operating handle where a purpose designed cam fitted to the

protruding blade operating spindle allows the release of the micro

switch actuating lever, allowing the snap action contacts 1NO + 1NC

to change state.

Wiring connections are made via M3, 5 terminal screw fixings.

Mechanical life: 1 million cycles

Complies with EN60204 and EN292 standards

Electrical data: Utilisation categories:

Thermal current (lth): 16A Alternate current: AC15 (50 ... 60Hz)

Rated insulation Ue (V) 250

voltage: 250VAC 300VDC


le (A) 5

Protection against
Direct current: DC13

Dry Wall Screws 38mm shor t circuits: fuse 10A 500V type gG
Ue (V) 24 125 250
long to affix installation
plate ensuring fixing Ie (A) 4 1,1 0,4
into dry lining metal frame

Micro Switch

Wiring Detail
Diameter

13 21

14 22

No infill required,
thus allowing
ease of installation
as tested

Snap-action

terminal cover

Maintenance Notes

FD-C Series dampers are designed for normal dr y filtered air systems.

A programme of planned inspections should be carried out to include

full operational checks, correct interface with, and function of, any

control systems, cleaning and light lubrication.


M

As a guide, this should take place on a maximum of six month inter vals.
122
Reference should be made to BS 5588-12 and BS 9999 for more
N
information.

Damper Free Area Records of damper installation and position shall be kept. Records of

Model Free Area Model Free Area the condition of the dampers and their functionality/repair etc should

be kept as these products come under the requirements of the


FD-C100 64% FD-C200 85%
Regulator y Reform (Fire safety) Order (RRFSO).
FD-C125 73% FD-C250 88%

These inspection and maintenance programmes may need to be


FD-C150 79% FD-C300 91%
repeated more regularly if the dampers are exposed to

FD-C160 81% FD-C315 91% inclement/dusty conditions or fresh air intakes and the frequency of

such checks should be developed based on site experience.

www.bsb-dampers.co.uk 11
FD-C Series
Single Blade Circular Fire Dampers – Ordering Codes

FD-C 200 G MS

FD-C Externally Resettable Circular Single Blade Damper

Diameter:

Blade Material

G Galvanised Mild Steel

S 430 Grade Stainless Steel

Accessories

MS Single Pole Micro Switch

CL Cleat

Air, Fire and Smoke Control Products in the BSB Range:

FSD-TD Series FSD-C Series SC Series FD Series FD-C Series


Fire/Smoke Dampers Circular Fire/Smoke Dampers Smoke Dampers Fire Dampers Circular Fire Dampers

SS Series HD Series BD Series VC Series Control Systems

SlimSeal Dampers Heavy Duty Dampers Backdraught Dampers Volume Control Dampers

For full details of the complete BSB Product Range, please refer to our individual product brochures, sales office or website.

BSB Engineering Ser vices Limited


Unit 56, Trinity Trade Centre, Mill Way, Sittingbourne, Kent ME10 2PD, UK • Tel: +44 (0)1795 422609 • Fax: +44 (0)1795 429543

For purchase orders and order related enquiries, please email: [email protected]

For pricing, technical and general enquiries, please email: [email protected]

Website: www.bsb-dampers.co.uk • A member of the Maico group

BSB Engineering Ser vices Ltd. reser ves the right to modify or withdraw any specification without prior notice that may result from

continuous product development. The information contained within this brochure is correct at the time of going to press. (FDC-02-2016)

ADE I
M A D E I N B R I TA I N
M

BR
Member of ADCAS Association Member of HEVAC Association bre Testing facility Assessed to ISO 9001 Cert. No. 828 I TA I N SOLD TO THE WORLD

You might also like