626077bc1a5f665b40561a40 - DPS 21DB-01DS
626077bc1a5f665b40561a40 - DPS 21DB-01DS
626077bc1a5f665b40561a40 - DPS 21DB-01DS
MAIN DATA
Prime power (PRP) 20.0 (kVA)
Prime power (PRP) 16.0 (kW)
Standby power (LTP) 21.5 (kVA)
Standby power (LTP) 17.0 (kW)
Voltage, Frequency, pf 415V, 50HZ @ 0.8
Sound pressure 7m dBA 65.0
ENGINE ALTERNATOR
Engine brand DEUTZ Alternator brand Stamford
Engine model F3M2011 Alternator model S0L2-G
Cylinders 3 P.R.P. Power 20.0 kVA
Speed 1500 rpm L.T.P. Power 21.5 kVA
Cubic capacity 2.33 L Connection Series Star
Air intake Aspirated Phases 3PH + N
Standard voltage 12Vdc Winding 12 terminals Winding 311
SAE 3-11.5 Terminal Number 12 nr.
BMEP 690 kPa IP Protection 23
Cooling Oil Electronic regulator AS540
Flywheel P.R.P. Power 19.4 kW Precision 1.0 +/- %
Flywheel Standby Power 20.4 kW
Precision class G2
Oil Quantity 8.5 L CONTROL SYSTEM
Engine coolant capacity NA Control system brand COMAP
Radiator standard ROA Control system model AMF 25
Heat from radiator 11.3 kW I/O expansion module (optional) BI08-EFCP
Heat from exhaust 18.1 kW Remote monitoring (optional) GSM/GRPS
Heat from radiation 0.0 kW Comms. expansion module (optional) RS232/RS485
Exhaust temperature 540 deg C
Cooling air flow 30.0 m3/min
Combustion air flow 0.00 m3/min FUEL CONSUMPTION
Exhaust gas flow 4.16 m3/min Fuel Cons. @ 100% (LTP) 5.6 l/h
TA Luft Standard Fuel Cons. @ 100% (PRP) 5.3 l/h
TA Luft/2 NA Fuel Cons. @ 75% (PRP) 4.0 l/h
EPA NA Fuel Cons. @ 50% (PRP) 3.1 l/h
Stage Stage 2 Fuel Cons. @ 25% (PRP) 2.5 l/h
DIMENSIONS & WEIGHT (ACOUSTIC CANOPY) REFERENCE CONDITIONS
Length 2030 mm Standard reference condition temp. 25deg C
Width 945 mm Altitude 100 masl
Height 1340 mm Relative humidity 30%
Mass (Dry) 830 kg Atmospheric pressure 100 kpa
Power factor 0.8 lag
Balanced load Non-distortional
Fuel consumption is nominal and refers to specific weight
BASE FRAME (ACOUSTIC CANOPY)
0.850kg/l.
Base frame model B1
Sound power levels refer to free field conditions:
Standard bunded tank 90 litres Installation site may influence the values.
Optional bunded tank 600 litres Dimensions, weights and other specifications contained in
the technical data sheet and related attachments are
nominal, subject to tolerances and refer to the model with
standard equipment. Any optional and additional
equipment / accessories can modify weight, dimensions
DIMENSIONS & WEIGHT (OPEN FRAME)
and performance.
Length NA
P.R.P. Prime Power-Continuous power at variable load
Width NA
The power that a generator can supply in continuous
Height NA service at a variable load for an unlimited number of hours
Mass (Dry) NA per year while respecting the maintenance intervals
established in the environmental conditions stated by the
manufacturer according to ISO8528-1. The average power
supplied over time and any applicable overload must be
less than the percentages stated by the manufacturer.
BASE FRAME (OPEN FRAME)
L.T.P. Limited-time running power-Limited power
Base frame model NA The maximum power that a generator can supply for a
Standard bunded tank NA limited time respecting the maintenance intervals
Optional bunded tank NA established in the environmental conditions stated by the
manufacturer according to ISO8528-1. The number of
hours per year is stated by the manufacturer. Overload is
not permitted.
For more information please contact your local DEUTZ Power Solutions sales partner.