Troubleshooting SolarEdge Systems, Addendum (North America)ww

This addendum is a supplement to the SolarEdge Installation Guide versions 4.0 and above (P/Ns MAN-01-00002-4.0 and above;w
http://www.solaredge.us/sites/default/files/se-inverter-installation-guide.pdf). This document describes error codes and how to troubleshoot them.ww

Error Codes
The error messages include an error number (in firmware version 3.18xx and before) or a code (in firmware version 3.19xx and later) and a description:
Error Code XXX
(3xD2)
Error Code 3xD2

<Line 1>
<Line 2>

XXX: The error number (firmware version 3.18xx and before).


(#-X#): A code indicating the source of error and the error information (firmware version 3.19xx and later).
Line 1-2: Error description
The error numbers/ codes may differ depending on the inverter type (single phase or three phase) as described in the table below. For troubleshooting errors
that are not listed, contact SolarEdge support.
Make sure to have this information at hand when contacting SolarEdge Support for advanced troubleshooting.

WARNING!
All warnings and cautions in this manual should be adhered to while troubleshooting an error.
Tous les avertissements et précautions mentionnés dans ce manuel doivent être aussi appliqués en cas de dépannage.

Error # Single Phase Error # Three Phase LCD


Cause and Troubleshooting
Inverter Inverter Message
CPU v3.18xx CPU v3.19xx CPU v3.18xx CPU v3.19xx
and before and later and before and later
3x2,3xF, 8x11 -
4, 5, 8, 18- 2x13, 2x15, 45, 48, 50-
8x13, 8x3D,
23, 39, 42, 2x16, 3x2, 53, 94, 107- SW Error Contact SolarEdge Support.
8x4A - 8x4E,
45, 48 2x2D, 3xF 111,113
8x50
Wrong AC
N/A 112 8x4F Switch between L1 and L2 or L2 and L3 connections
connection
Ground current surge.
AC Current o Check the AC connection to the inverter
9, 13 2x9, 2xD N/A Surge o Check with the grid operator if a large surge source or irregular load exists near the
Vac surge site.
o If the grid does not have problems contact SolarEdge support.
Ground faults may occur due to insufficient insulation to the ground.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires
when the inverter cover is removed.
RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés
lorsque le couvercle de l'onduleur est retiré.
Only a qualified technician should handle this problem, and only after taking proper
precautions.
2xA, 2x25, 8x2B, 8x2C, Ground Current -
10, 37, 38 76, 77, 90 1. Turn the inverter ON/OFF switch to OFF.
2x26 8x39 RCD
2. Wait five minutes for the input capacitors to discharge.
3. Disconnect the AC breaker.
4. Disconnect the DC inputs.
5. Connect each DC string separately, turn the AC and the inverter ON/OFF switch to
ON, until the error appears for the faulty string.
o Do not connect strings with a grounding fault to the inverter. A certified installer must
fix the faulty string before connecting it to the inverter
o For further documentation, contact SolarEdge Support.

AC voltage surge. If the fault persists:

8x19/ 8x1A/ AC Voltage Too o Check the AC connection to inverter.


14 2xE 58/59/60
8x1B High (Line 1/2/3) o Verify that the inverter is set to the correct country.
o Check with the grid operator if a large surge source or irregular load
exists near the site.

1
Troubleshooting MAN-01-00332-1.1
Error Codes

Error # Single Phase Error # Three Phase LCD


Cause and Troubleshooting
Inverter Inverter Message
CPU v3.18xx CPU v3.19xx CPU v3.18xx CPU v3.19xx
and before and later and before and later
o Verify that the output wire size matches the distance between the inverter and the
location of the grid connection.
o Use a larger gauge wire for the AC output.
o Refer to the AC Wiring Application Note at
http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
The SolarEdge system normally eliminates DC overvoltage errors. If the fault persists:
o Turn OFF the inverter ON/OFF switch. If after five minutes, the LCD panel does not
show a low safety voltage (1V per optimizer), check which string is malfunctioning and
8x34, 8x35, DC Voltage Too
15 2xF 85, 86, 88, recheck its connections to the inverter.
8x37 High (surge)
o Proceed according to Power Optimizer Troubleshooting
o Re-commission all inverters in the site, as described in Commissioning the
Installation.
95, 106, 8x3E, 8x49,
125,126,
16, 149, 2x10, 2x95, 8x5C, 8x5D,
161, 162, Hardware Error Contact SolarEdge Support.
153, 181 2x59, 2xB5 8x75-79, 8x7A-
166, 172-
175 7F, 8x80-83

Over temperature
104, 163- Temperature Too
17 2x11 8x47, 8x77-79 o Verify proper inverter clearances.
165 High
o Make sure the heat-sink fins are clean and unobstructed.
Faulty Temp.
24 2x18 120 8x57 Broken or unconnected temperature sensor. Contact SolarEdge Support.
Sensor

PV solar array is not properly isolated from ground earth.


o Check the PV installation for isolation problems and ground leakage.
o Only a certified PV installer must fix the faulty string before
25 2x19 121 8x58 Isolation Fault connecting it to the inverter.
o Refer to
www.solaredge.us/files/pdfs/application_note_isolation_fault_
troubleshooting.pdf

26 2x1A 122 8x59 Faulty AC Relay


RCD Sensor Contact SolarEdge support.
28 2x1C 124 8x5B
Error
o Check the grid connection.
o Check the GND connection.
Phase Balance
29, 30 2x1D, 2x1E N/A o Check the L1, L2 and Neutral connections.
Error
o Verify symmetric load between L1, and L2 .
o Consult the local grid authority.
Grid voltage is above the country limit.
o Verify that the inverter is set to the correct country.
o Turn OFF the inverters in the site and verify AC grid voltage.
8x1F/ 8x20/ AC Voltage Too
31, 33 2x1F, 2x21 64/65/66 o If the inverter is located far from the connection point to the grid, use a larger gauge AC
8x21 High (Line 1/2/3)
wire.
o Consult the grid operator.
o If permitted by local authorities, change the grid protection values.
8x1C/ 8x1D/
61/62/63, AC Voltage Too
32, 41 2x20, 2x29 8x1E
67/68/69 Low
8x22/8x23/8x24 o Verify that the inverter is set to the correct country.
AC Freq Too o Consult the grid operator.
34 2x22 79/80/81 8x2E/8x2F/8x30
High (Line 1/2/3) o If permitted by local authorities, change the grid protection values.
AC Freq Too Low
35 2x23 82/83/84 8x31/8x32/8x33
(Line 1/2/3)
DC Injection
36 2x24 72/74/75 8x27/8x29/8x2A Contact SolarEdge support.
(Line 1/2/3)
Grid is down. When AC grid voltage returns the inverter will restart after the reconnection
40 2x28 N/A Islanding time.
If the problem persists, consult with the grid operator.
No Country
44 2x2C 44 3xB Select the country
Selected
Phase
46 3xA 46 3xA Select Power Control è Phase Balance è Disable.
Unbalance

2 Troubleshooting MAN-01-00332-1.1
Error # Single Phase Error # Three Phase LCD
Cause and Troubleshooting
Inverter Inverter Message
CPU v3.18xx CPU v3.19xx CPU v3.18xx CPU v3.19xx
and before and later and before and later
Voltage too high
o Verify that the inverter is set to the correct country.
N/A 70 8x25 VLL Max
o Consult the grid operator.
o If permitted by local authorities, change the grid protection values.
o Verify that the inverter is set to the correct country.
N/A 71 8x26 VLL Min o Consult the grid operator.
o If permitted by local authorities, change the grid protection values.
N/A 78 8x2D Grid Sync Error Check grid voltage and frequency stability.

91/92/93
(TZ
8x3A/8x3B/
L1/L2/L3),
8x3C AC Over Current
N/A 96/97/98 Contact SolarEdge support.
8x3F/ 8x40/ Line 1/2/3
(Iac
8x41
L1/L2/L3
Max)
Communication
N/A 49 8x10 Contact SolarEdge support.
Error
o Verify that the inverter is set to the correct country.
8x42, 8x43, AC Voltage Too
N/A 99-101 o Consult the grid operator.
8x44 High Line 1/2/3
o If permitted by local authorities, change the grid protection values.
Temperature Too Make sure the inverter is installed in a location with ambient temperatures within the range
N/A 105 8x48
Low specified in the datasheet.
o Refer to www.solaredge.us/files/pdfs/application_note_isolation_fault_
RCD Current troubleshooting.pdf
N/A 114 8x51
Surge
o Contact SolarEdge support.
Unbalanced DC
N/A 115 8x52 Contact SolarEdge support.
Voltage
Common Voltage
N/A 116 8x53 Contact SolarEdge support.
Too High
Measurement
N/A 123 8x5A Contact SolarEdge support.
Error
Ground Current –
N/A 124 8x5B Contact SolarEdge support.
RCD
AC grid voltage malfunction. When AC voltage returns the inverter should restart after the
N/A 87 8x36 Islanding - Active reconnection time.
If the problem persists, consult with the grid operator.
AC grid voltage malfunction. When AC voltage returns the inverter should restart after the
Islanding -
144 2x90 89 8x38 reconnection time.
Passive
If the problem persists, consult with the grid operator.
145 2x91 102 8x45 UDC Max Contact SolarEdge support.

146 2x92 103 8x46 UDC Min Contact SolarEdge support.

147, 150,
147, 150, 3x11, 2x96, 3x11, 2x96, Arc Fault
151
151 2x97 2x97 Detected
Refer to Inverter Arc Detection and Interruption
Arc detector self-
152 2x98 152
test failed

3
Troubleshooting MAN-01-00332-1.1
System Warnings

System Warnings
Warnings are displayed in the initial status screen with the format: <Warning X>. For example:
Vac[V] Vdc[V] Pac[W]
1.0 0.5 0.0
P_OK: XXX/YYY <S_OK>
Warning 8 ON

The warning is a status screen. To view the warning description, press the LCD button.
The following is a list of system warnings:
Warning #
CPU v3.18xx and CPU v3.19xx and LCD text Comments and troubleshooting
before later
8x66 - 8x69
1-4, 6-7 Fan # Failure Clean or replace the fan
8x6A - 8x6F
Appears when trying to access the Setup menus during
5 Turn Switch Off to Configure
production

4 Troubleshooting MAN-01-00332-1.1