ReleiDP-210S1650002r5 02
ReleiDP-210S1650002r5 02
ReleiDP-210S1650002r5 02
SERVICE INFORMATION
for the
iDP-210 Feeder Protection Control
and Monitoring System
with DNP3 or Modbus Communications
January 2005
For use with ProView 4.0.1 or later and for iDP-210 Scheme Files dated 1/1/2005 or later.
ProView, IDEA Workbench, User Workbench, Relay-Replay, and Virtual Test Set are trademarks of
Cooper Power Systems or its affiliates.
Windows, WORD, and Notepad are either registered trademarks or trademarks of Microsoft
Corporation in the United States and/or other countries.
Table of CONTENTS
SAFETY INFORMATION....................................................................................................................................... 12
1 INTRODUCTION..................................................................................................................................... 14
1.1 WHAT’S NEW?.............................................................................................................................................. 14
1.2 HOW DO I UPGRADE MY RELAY FROM PROVIEW 3.2.2 TO PROVIEW 4.0.1? ............................................. 15
1.3 COMPREHENSIVE FEEDER PROTECTION AND CONTROL FEATURES: ........................................................... 19
2 EDISON IDEA HARDWARE................................................................................................................ 24
2.1 HARDWARE INTRODUCTION ........................................................................................................................ 24
2.2 EDISON IDEA DC CONNECTION DIAGRAM WHERE OPTIONAL CONTACT I/O BOARD IS PRESENT......... 25
2.3 OUTLINE DRAWINGS .................................................................................................................................... 27
2.4 INPUT/OUTPUT DESCRIPTION SUMMARY.................................................................................................... 31
3 EDISON IDEAPLUS HARDWARE ..................................................................................................... 32
3.1 HARDWARE INTRODUCTION ........................................................................................................................ 32
3.2 IDEAPLUS DC CONNECTION DIAGRAM .................................................................................................... 33
3.3 DC WIRING DIAGRAM OF THE IDP-210 WITH IDEAPLUS HARDWARE IMPLEMENTING OPERATOR
WINDOW SUPERVISION OF THE FRONT PANEL CLOSE BUTTON .............................................................. 34
3.4 OUTLINE DRAWINGS .................................................................................................................................... 35
4 AC WIRING DIAGRAMS FOR IDEA AND IDEAPLUS HARDWARE ..................................... 44
4.1 AC TERMINAL INFORMATION ..................................................................................................................... 44
4.2 IDEA AC CONNECTION DIAGRAM - 4 VOLTAGE INPUTS, NORMAL ABC PHASE ROTATION ................. 45
4.3 IDEA AC CONNECTION DIAGRAM - 4 VOLTAGE INPUTS, ACB PHASE ROTATION ................................. 46
4.4 IDEA AC CONNECTION DIAGRAM - 4 VOLTAGE INPUTS, DELTA PT CONNECTION ................................ 47
4.5 IDEA AC CONNECTION DIAGRAM - 6 VOLTAGE INPUTS, NORMAL ABC PHASE ROTATION ................. 48
4.6 IDEA AC CONNECTION DIAGRAM - 6 VOLTAGE INPUTS, ACB PHASE ROTATION ................................. 49
4.7 IDEA AC CONNECTION DIAGRAM - 6 VOLTAGE INPUTS, DELTA PT CONNECTION ................................ 50
5 FRONT PANEL OPERATION.............................................................................................................. 51
5.1 INTRODUCTION ............................................................................................................................................. 51
5.2 FRONT PANEL ELEMENTS ............................................................................................................................ 52
5.3 ADJUSTING THE CONTRAST OF THE LCD.................................................................................................... 52
5.4 FRONT PANEL TARGETS .............................................................................................................................. 53
5.5 THE IDEAPLUS LOWER CONTROL PANEL ................................................................................................. 54
5.5.1 TRIP and CLOSE Controls................................................................................................................. 54
5.5.1.1 TRIP Button.......................................................................................................................................................54
5.5.1.2 CLOSE Button ..................................................................................................................................................54
5.5.2 Close Circuit Break ............................................................................................................................. 55
5.5.3 Hot Line Tag Control .......................................................................................................................... 55
5.5.3.1 Mechanical Hot Line Tag Switch (Ordering Option “T”)...............................................................................55
5.5.3.2 Software Controlled Close Inhibit Switch (Ordering Option “C”) .................................................................56
5.5.4 GND TRIP BLOCKED ....................................................................................................................... 56
5.5.5 NON RECLOSING.............................................................................................................................. 56
5.5.6 LOCAL MODE.................................................................................................................................... 56
5.5.7 USER OPTION #`1, #2, #3, #4, #5, #6............................................................................................... 57
5.6 HOTKEY OPERATIONS............................................................................................................................... 57
5.6.1 METERING Hotkey............................................................................................................................. 57
5.6.2 RESET TARGET Hotkey ..................................................................................................................... 57
5.6.3 LAST EVENT Hotkey .......................................................................................................................... 57
5.6.4 LAMP TEST Hotkey ............................................................................................................................ 57
5.6.5 SETTINGS Hotkey............................................................................................................................... 57
5.6.6 BREAKER STATUS Hotkey................................................................................................................ 57
5.6.7 ALARMS Hotkey.................................................................................................................................. 57
2
iDP-210 Feeder Relay Manual KA2048 520 REV07
3
iDP-210 Feeder Relay Manual KA2048 520 REV07
7.7 VIEW-ONLINE............................................................................................................................................... 97
7.8 DISPLAYING RELAY DATA .......................................................................................................................... 98
7.8.1 Application Diagram........................................................................................................................... 98
7.8.2 Display Targets.................................................................................................................................... 99
7.8.3 Display External Alarms ...................................................................................................................100
7.8.4 Display Internal Alarms ....................................................................................................................100
7.8.5 Display Contact Inputs and Outputs.................................................................................................101
7.8.6 Display Recloser Status.....................................................................................................................102
7.8.7 Display Sync-Scope ...........................................................................................................................103
7.8.8 Display Breaker Statistics .................................................................................................................105
7.8.9 Display Fault Locator Results...........................................................................................................105
7.8.10 Display Data Profiler ........................................................................................................................106
7.9 DISPLAYING METERING DATA ..................................................................................................................109
7.10 CONFIGURING RELAY PASSWORD AND PROVIEW AND MMI CONTROL ................................................109
7.10.1 Enabling Relay MMI for Control Actions and Setting the Relay Password...................................110
7.10.2 Controlling the Operation of the Circuit Breaker from Within ProView .......................................111
8 PROTECTION AND CONTROL SETTINGS .................................................................................113
8.1 INTRODUCTION ...........................................................................................................................................113
8.2 VIEWING, SAVING AND LOADING SETTINGS ............................................................................................114
8.3 SETTING GROUPS .......................................................................................................................................115
8.3.1 Selecting a Setting Group to View and/or Modify............................................................................116
8.3.2 Selecting the Active Setting Group....................................................................................................117
8.3.3 Establishing Setting Group Names ...................................................................................................118
8.3.4 Copying Setting Groups ....................................................................................................................118
8.4 GENERAL SETTINGS ...................................................................................................................................119
8.4.1 General System Settings:...................................................................................................................119
8.5 OVERCURRENT ELEMENTS ........................................................................................................................122
8.5.1 Setting Directional Parameters.........................................................................................................122
8.5.1.1 Setting Maximum Torque Angles and Polarization Method ........................................................................122
8.5.1.2 Setting Directional Fault Detectors.................................................................................................................124
8.5.2 Overcurrent elements ........................................................................................................................126
8.5.2.1 Phase Overcurrent ...........................................................................................................................................126
8.5.2.2 Ground Overcurrent ........................................................................................................................................129
8.5.2.3 Negative Sequence Overcurrent .....................................................................................................................131
8.5.2.4 iDP-210 Inverse Time Characteristics:...........................................................................................................133
8.6 RECLOSING .................................................................................................................................................148
8.6.1 General Recloser Setup .....................................................................................................................148
8.6.1.1 Setting the Reclose Shots ................................................................................................................................149
8.6.1.2 Recloser Miscellaneous Settings.....................................................................................................................149
8.6.1.3 Fast Reclose Shots...........................................................................................................................................151
8.6.1.4 Controlling Recloser Operation in the Presence of Alarms...........................................................................151
8.6.1.5 Pausing the Recloser........................................................................................................................................152
8.6.1.6 Setting Sequence Coordination.......................................................................................................................153
8.6.2 Defining Reclose and Lockout Action...............................................................................................153
8.7 SYNC-CHECK ..............................................................................................................................................155
8.7.1.1 Dead Bus and Hot Bus Determination ...........................................................................................................157
8.7.1.2 Voltage Phase Determination .........................................................................................................................157
8.7.1.3 Determination of In-Synch Conditions ..........................................................................................................158
8.7.1.4 Use of the Operator Window and Anti-Pump Settings .................................................................................159
8.7.1.5 Synch-Check Settings .....................................................................................................................................160
8.8 VOLTAGE ELEMENTS .................................................................................................................................162
8.9 REVERSE POWER ........................................................................................................................................164
8.10 FUSE FAIL LOGIC (LOSS OF POTENTIAL)...................................................................................................165
8.10.1 Fuse Failure Logic ............................................................................................................................165
8.10.2 Fuse Failure Settings.........................................................................................................................166
8.11 FREQUENCY ELEMENTS .............................................................................................................................169
8.12 BREAKER SETTINGS ...................................................................................................................................173
4
iDP-210 Feeder Relay Manual KA2048 520 REV07
11 TROUBLESHOOTING.........................................................................................................................206
11.1 HARDWARE ................................................................................................................................................206
11.1.1 If the Edison Idea or IdeaPLUS fails to operate, no lamps are illuminated and the LCD display is
blank-..................................................................................................................................................206
11.1.2 If the Edison Idea or IdeaPLUS fails to operate, most or all LEDs are illuminated, and the LCD
display shows all “A” characters only-............................................................................................206
11.1.3 If you cannot establish a communication link between ProView and the Edison Idea or IdeaPLUS,
check the following:...........................................................................................................................206
11.1.4 If the Edison Idea or IdeaPLUS OK light is off, alarm light is on, and/or the LCD reports an
"Internal Alarm":...............................................................................................................................206
11.1.5 How do I use the two DC monitoring inputs on the back of the IdeaPlus? ....................................206
11.2 PROVIEW SOFTWARE.................................................................................................................................207
11.2.1 Scheme file takes several minutes to open........................................................................................207
11.2.2 When I press the Connect button, or select the Manage>Simulation or Manage>Oscillographic
Events menu items, a progress bar appears that takes several minutes to finish. ..........................207
11.2.3 When in Online-View mode, the following warning message appears: “Too many real-time
variables requested – exiting Online view.”.....................................................................................207
11.2.4 When I connect to the relay, none of the screens accessed from the Display menu, nor the IDEA
Workbenches, are updating...............................................................................................................207
11.2.5 When I connect to the relay, a message box appears telling me I have a different version of
firmware on my relay.........................................................................................................................208
11.2.6 Shortly after I power up my relay I get a Cold Load Pickup event in the Sequence of Events log.208
11.2.7 While downloading to the relay, power was inadvertently lost, and now the relay is either locked
up or behaving incorrectly. ...............................................................................................................208
12 GETTING HELP ....................................................................................................................................209
12.1 FREE, UNLIMITED TELEPHONE TECHNICAL SUPPORT ..............................................................................209
12.2 ONSITE SERVICE AND TRAINING ...............................................................................................................209
5
iDP-210 Feeder Relay Manual KA2048 520 REV07
13 APPENDICES .........................................................................................................................................210
13.1 SPECIFICATIONS .........................................................................................................................................210
13.2 CATALOG NUMBERS AND ORDERING INFORMATION ...............................................................................212
13.3 IDEA AND IDEAPLUS RELAY ACCESSORIES ............................................................................................213
13.4 FRONT PANEL COMMUNICATION PORT PINOUTS....................................................................214
13.5 REAR PANEL COMMUNICATION PORTS.......................................................................................215
13.5.1 Communication Board Accessories..................................................................................................215
13.5.2 RS485 Serial Communication Card..................................................................................................215
13.5.3 Fiber-Optic Based Serial Communication Card..............................................................................216
13.5.4 Ethernet Communication Cards .......................................................................................................216
13.6 BEHAVIOR OF FREQUENCY MEASURING ELEMENTS ................................................................................219
13.6.1 Comparison of iDP-210 Relay and Form 6 Recloser Control Frequency Measuring Elements..219
13.7 SEQUENCE OF EVENTS: EVENT DEFINITIONS............................................................................................219
13.8 MOUNTING THE IDEA OR IDEAPLUS RELAY WITH OPTIONAL MOUNTING KITS ......................................222
13.8.1 Idea/IdeaPlus Relay Double Rack Mount Connecting Plate and Handle Attachment Instructions
223
13.8.2 Idea/IdeaPlus Relay Single Rack-Mount Filler Plate Attachment Instructions .............................226
13.9 EXPLANATION OF RECLOSE READY LED BEHAVIOR ..............................................................................227
13.10 OPERATION OF RECLOSER BLOCKED LED .......................................................................................228
14 PROTECTIVE SETTINGS LIST........................................................................................................229
15 REVISION HISTORY...........................................................................................................................243
16 INDEX.......................................................................................................................................................244
6
iDP-210 Feeder Relay Manual KA2048 520 REV07
Table of FIGURES
FIGURE 1-1: EDISON IDEA RELAY ............................................................................................................................ 21
FIGURE 1-2: MAIN FEATURES OF THE IDEAPLUS FACEPLATE............................................................................... 22
FIGURE 2-1: IDEA RELAY, FRONT VIEW .................................................................................................................. 27
FIGURE 2-2: IDEA RELAY, SIDE VIEW...................................................................................................................... 27
FIGURE 2-3: IDEA RELAY, MOUNTING HOLE DETAIL ............................................................................................. 28
FIGURE 2-4: IDEA RELAY, PANEL CUTOUT DIMENSIONS........................................................................................ 28
FIGURE 2-5: IDEA RELAY, REAR PANEL DETAILS (BELOW S/N 2000) 4 VOLTAGE INPUTS, PR6DD10XXXXXX
ORDERING OPTION ............................................................................................................................ 29
FIGURE 2-6: IDEA RELAY, REAR PANEL DETAILS (BELOW S/N 2000) 6 VOLTAGE INPUTS, PR6DD16XXXXXX
ORDERING OPTION ............................................................................................................................ 29
FIGURE 2-7: IDEA RELAY, REAR PANEL DETAILS (ABOVE S/N 2000) 4 VOLTAGE INPUTS, PR6DD10XXXXXX
ORDERING OPT .................................................................................................................................. 30
FIGURE 2-8: IDEA RELAY, REAR PANEL DETAILS (ABOVE S/N 2000) 6 VOLTAGE INPUTS, PR6DD16XXXXXX
ORDERING OPTION ............................................................................................................................ 30
FIGURE 3-1: IDEA PLUS RELAY, FRONT VIEW ....................................................................................................... 35
FIGURE 3-2: IDEAPLUS RELAY, SIDE VIEW ........................................................................................................... 36
FIGURE 3-3: IDEA PLUS RELAY, MOUNTING HOLE DETAIL.................................................................................... 37
FIGURE 3-4: IDEA PLUS RELAY, PANEL CUTOUT DIMENSIONS .............................................................................. 37
FIGURE 3-5: IDEAPLUS RELAY, REAR PANEL DETAILS (BELOW S/N 2000) 4 VOLTAGE INPUTS,
PR6PD10XXXXXX ORDERING OPTION ............................................................................................ 38
FIGURE 3-6: IDEAPLUS RELAY, REAR PANEL DETAILS (BELOW S/N 2000) 6 VOLTAGE INPUTS,
PR6PD16XXXXXX ORDERING OPTION ............................................................................................ 39
FIGURE 3-7: IDEAPLUS RELAY, REAR PANEL DETAILS (ABOVE S/N 2000) 4 VOLTAGE INPUTS,
PR6PD10XXXXXX ORDERING OPTION ............................................................................................ 40
FIGURE 3-8: IDEAPLUS RELAY, REAR PANEL DETAILS (ABOVE S/N 2000) 6 VOLTAGE INPUTS,
PR6PD16XXXXXX ORDERING OPTION ............................................................................................ 41
FIGURE 5-1: FRONT PANEL OF THE IDP-210 RELAY ............................................................................................... 51
FIGURE 5-2: FRONT PANEL TARGETS....................................................................................................................... 53
FIGURE 5-3 : PASSWORD ENTRY DISPLAY ON RELAY LCD................................................................................ 59
FIGURE 5-4 : TYPICAL SETTING MENU ..................................................................................................................... 62
FIGURE 5-5: SAVE SETTINGS CONFIRMATION DISPLAY .......................................................................................... 63
FIGURE 5-6: FIRST FOUR LINES OF TARGETS LCD SUB-MENU ............................................................................. 64
FIGURE 5-7: RESET TARGETS LCD DISPLAY .......................................................................................................... 65
FIGURE 5-8: DEMAND METERS SUB-MENU DISPLAY ............................................................................................. 68
FIGURE 5-9: POWER/ENERGY METERS SUB-MENU DISPLAY ................................................................................. 68
FIGURE 5-10: RESET RECLOSER LCD DISPLAY ........................................................................................................ 70
FIGURE 5-11: SAMPLE FTYPE DISTANCE DUR DISPLAY.................................................................................... 70
FIGURE 5-12: SELF CLEAR FAULT SHOW STATISTICS LCD DISPLAY ...................................................................... 71
FIGURE 5-13: BREAKER TRIP/CLOSE DISPLAY WITH METERING ...................................................................... 72
FIGURE 5-14: BREAKER TRIP/CLOSE DISPLAY WITH METERING ...................................................................... 72
FIGURE 5-15: CONTACT INPUTS LCD DISPLAY ........................................................................................................ 72
FIGURE 5-16: CONTACT OUTPUTS LCD DISPLAY..................................................................................................... 73
FIGURE 5-17: BREAKER TRIP/CLOSE DISPLAY WITH METERING ...................................................................... 75
FIGURE 5-18: SCHEME IDENTITY LCD DISPLAY ....................................................................................................... 75
FIGURE 6-1: THE PROVIEW LOGIN DIALOG BOX .................................................................................................... 81
FIGURE 7-1: FILE OPEN DIALOG TO LOAD SCHEME ................................................................................................ 83
FIGURE 7-2: SCHEME LOADING MONITOR IN LOWER LEFT HAND CORNER OF PROVIEW SCREEN...................... 83
FIGURE 7-3: PROVIEW’S MENU-BAR SHOWING "CONNECT" BUTTON ............................................................... 84
FIGURE 7-4: MANAGE CONNECTIONS DIALOG BOX................................................................................................. 84
FIGURE 7-5: "COMPARING SCHEME…" PROGRESS INDICATOR.............................................................................. 85
FIGURE 7-6: OPENING THE "MANAGE CONNECTIONS" WINDOW ........................................................................... 85
FIGURE 7-7: MANAGE CONNECTIONS DIALOG BOX ............................................................................................... 86
FIGURE 7-8: EDIT DIALOG BOX FOR CONNECTIONS. LEFT - SERIAL CONNECTION (DIRECT/MODEM) OR RIGHT -
TCP/IP............................................................................................................................................... 86
FIGURE 7-9: CONNECTION ESTABLISHED MESSAGE BOX ....................................................................................... 87
7
iDP-210 Feeder Relay Manual KA2048 520 REV07
FIGURE 7-10: APPEARANCE OF COMPARE BUTTON WHEN RELAY CONTAINS DIFFERENT SETTINGS, MODES, OR
SCHEME (TYPICAL):........................................................................................................................... 88
FIGURE 7-11: APPEARANCE OF COMPARE BUTTON WHEN SCHEME AND SETTINGS ARE IDENTICAL BETWEEN
RELAY AND PC (IF NO CHANGES SINCE DOWNLOAD): ..................................................................... 88
FIGURE 7-12: APPEARANCE OF COMPARE BUTTON WHEN SETTINGS, MODES, SCHEME, AND VARIABLES ARE
IDENTICAL BETWEEN RELAY AND PC (ONLY AFTER UPLOAD OF ALL VARIABLES): ...................... 88
FIGURE 7-13: “SCHEME HAS BEEN MODIFIED…” MESSAGE DIALOG BOX.............................................................. 89
FIGURE 7-14: COMPARE DIALOG WINDOW ............................................................................................................... 89
FIGURE 7-15: SETTINGS DETAILS COMPARISON DIALOG BOX ................................................................................. 90
FIGURE 7-16: ACCESSING THE EVENT MANAGER ..................................................................................................... 92
FIGURE 7-17: OPEN EVENT MANAGER DIALOG ........................................................................................................ 93
FIGURE 7-18: OSCILLOGRAPHY SELECTION SCREEN................................................................................................. 94
FIGURE 7-19: OPEN OSCILLOGRAPHIC WINDOW WITH CURSOR CONTROL PANEL ................................................. 95
FIGURE 7-20: PHASOR DISPLAY SCREEN ................................................................................................................... 96
FIGURE 7-21: OPEN PHASOR DISPLAY WINDOW SHOWING VOLTAGE AND CURRENT PHASORS ........................... 96
FIGURE 7-22: TYPICAL SEQUENCE OF EVENTS SCREEN ............................................................................................ 97
FIGURE 7-23: STARTING THE "VIEW ONLINE" FEATURE ........................................................................................... 97
FIGURE 7-24: IDP-210 DISPLAY MENU ...................................................................................................................... 98
FIGURE 7-25: APPLICATION DIAGRAM WINDOW ....................................................................................................... 99
FIGURE 7-26: TARGETS DISPLAY ................................................................................................................................ 99
FIGURE 7-27: EXTERNAL ALARMS DISPLAY ............................................................................................................100
FIGURE 7-28: INTERNAL ALARMS DISPLAY .............................................................................................................100
FIGURE 7-29: VIEW CONTACT ITPUTS DISPLAY DIALOG ..........................................................................................101
FIGURE 7-30: RECLOSER STATUS DISPLAY .............................................................................................................102
FIGURE 7-31: TYPICAL SYNC-SCOPE DISPLAY.........................................................................................................103
FIGURE 7-32: BREAKER STATISTICS DISPLAY..........................................................................................................105
FIGURE 7-33: FAULT LOCATOR RESULTS DISPLAY DIALOG BOX ..........................................................................106
FIGURE 7-34: DATA PROFILER MENU PATH ............................................................................................................106
FIGURE 7-35: DATA PROFILER DIALOG ....................................................................................................................107
FIGURE 7-36: DATA PROFILER CONFIGURATION DIALOG. ......................................................................................108
FIGURE 7-37: IDP-210 METERING MENU ................................................................................................................109
FIGURE 7-38: ACCESSING THE MMI FORCING AND DIALOG ENABLES SETTINGS DIALOG ...................................109
FIGURE 7-39: MMI FORCING AND DIALOG ENABLES SETTINGS SCREEN ...............................................................110
FIGURE 7-40: ACCESSING THE CONTROL POWER CIRCUIT BREAKER DIALOG ......................................................111
FIGURE 7-41: CONTROL POWER CIRCUIT BREAKER DIALOG .................................................................................111
FIGURE 8-1: ACCESSING THE SETTINGS>SETTINGS FILES DIALOG BOX ..............................................................114
FIGURE 8-2: VIEW OF THE OPENED SETTINGS>SETTINGS FILES DIALOG ............................................................115
FIGURE 8-3: OPENING THE SETTING GROUP DIALOG BOX ...................................................................................116
FIGURE 8-4: SELECT SETTING GROUP DIALOG BOX .............................................................................................117
FIGURE 8-5: SELECT VIEW/MODIFY GROUP DIALOG BOX ...................................................................................118
FIGURE 8-6: COPY SETTING GROUP DIALOG BOX ................................................................................................119
FIGURE 8-7: OPENING THE GENERAL "SYSTEM SETTINGS" WINDOW..................................................................119
FIGURE 8-8: "GENERAL SYSTEM SETTINGS" WINDOW .........................................................................................120
FIGURE 8-9: THE DIRECTIONAL SETTINGS WINDOW ............................................................................................122
FIGURE 8-10: FAULT DETECTOR SETTINGS WINDOW .............................................................................................124
FIGURE 8-11: OPENING THE PHASE OVERCURRENT SETTING WINDOW ................................................................127
FIGURE 8-12: PHASE OVERCURRENT SETTING WINDOW ........................................................................................127
FIGURE 8-13: OPENING THE GROUND OVERCURRENT SETTING WINDOW.............................................................129
FIGURE 8-14: GROUND OVERCURRENT SETTING WINDOW ....................................................................................129
FIGURE 8-15: OPENING THE NEGATIVE SEQUENCE OVERCURRENT SETTING WINDOW .......................................131
FIGURE 8-16: NEGATIVE SEQUENCE OVERCURRENT SETTING WINDOW...............................................................132
FIGURE 8-17: CUSTOMED CURVE PARAMETER SETTINGS........................................................................................134
FIGURE 8-18: IEEE MEDIUM INVERSE TCC............................................................................................................135
FIGURE 8-19: IEEE VERY INVERSE TCC.................................................................................................................136
FIGURE 8-20: IEEE EXTREMELY INVERSE TCC .....................................................................................................137
FIGURE 8-21: IEC A CURVE TCC............................................................................................................................138
8
iDP-210 Feeder Relay Manual KA2048 520 REV07
9
iDP-210 Feeder Relay Manual KA2048 520 REV07
10
iDP-210 Feeder Relay Manual KA2048 520 REV07
Table of TABLES
TABLE 4-1: COMMON TERMINAL TYPES SUITABLE FOR CONNECTION TO THE IDEA AND IDEAPLUS RELAYS . 44
TABLE 5-1: MAIN LCD MENU FOR IDP-210.......................................................................................................... 58
TABLE 5-2: THE SETTINGS SUB-MENU............................................................................................................... 61
TABLE 5-3 : SUB-MENU OF THE PICK SETTING GROUPS SUB-MENU............................................................. 62
TABLE 5-4: SYSTEM SETTINGS SUB-MENU DISPLAY UNDER THE SETTINGS MENU ITEM......................... 62
TABLE 5-5 : INVERSE CURVE SELECTION FOR FRONT PANEL SETTING ................................................................. 63
TABLE 5-6 : EXTERNAL ALARM SUB-MENU .................................................................................................... 66
TABLE 5-7: INTERNAL ALARMS SUB-MENU................................................................................................... 67
TABLE 5-8: POSSIBLE DISPLAY STATES FOR RECLOSE/BKR STATUS MENU LINE................................................ 69
TABLE 5-9: RECLOSER/BREAKER STATUS SUB-MENU .......................................................................................... 69
TABLE 5-10: SELF-CLEARING FAULT SUB-MENU.................................................................................................... 70
TABLE 5-11: BREAKER STATISTICS SUB-MENU....................................................................................................... 71
TABLE 5-12: WORKBENCH SUB-MENU ............................................................................................................... 74
TABLE 5-13: WORKBENCH SWITCHES SUB-MENU ......................................................................................... 74
TABLE 6-1: PROVIEW OPERATING LEVEL DESCRIPTIONS ..................................................................................... 81
TABLE 7-1 : UPLOAD/DOWNLOAD OPTIONS FOR SCHEME STRUCTURE, IDEA WORKBENCH AND RELAY
SETTINGS ........................................................................................................................................... 91
TABLE 7-2 : DESCRIPTION OF THE SYNC-SCOPE STATUS DISPLAYS ....................................................................104
TABLE 8-1: RECLOSER/LOCKOUT ACTIONS SUMMARY.......................................................................................154
TABLE 13-1: PR6ADJK (IDEA) / PR6APJK (IDEAPLUS) DOUBLE RACK MOUNTING KIT PARTS LIST .............223
TABLE 13-2: PR6ADRP (IDEA) / PR6APRP (IDEAPLUS) SINGLE RACK MOUNTING KIT AND FILLER PLATE
PARTS LIST ......................................................................................................................................226
11
iDP-210 Feeder Relay Manual KA2048 520 REV07
Safety Information
Cooper Power Systems products meet of exceed all applicable industry standards relating to product
safety. We actively promote safe practices in the use and maintenance of our products through service
literature, instructional training programs and the continuous efforts of all Cooper Power Systems’
employees involved in product design, manufacture, marketing and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions
when working around high voltage lines and equipment and support our "Safety for Life” mission.
SAFETYINFORMATION
The instructions in this manual are not intended as a substitute for proper training or adequate
experience in the safe operation of the equipment described. Only competent technicians who are
familiar with the equipment should install, operate and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high- and low-voltage safe operating practices and procedures.
• Is trained and authorized to energize, de-energize, clear and ground power distribution equipment.
• Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face
shield, hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe installation and operation of this equipment be sure
to read and understand all cautions and warnings.
12
iDP-210 Feeder Relay Manual KA2048 520 REV07
Safety Instructions
The following general caution and warning statements apply to this equipment. Additional
statements, relating to specific tasks and procedures, are located throughout the manual.
WARNING: This equipment is not intended to protect human life. Follow all
! locally approved procedures and safety practices when installing or
operating this equipment. Failure to comply can result in death,
severe personal injury and equipment damage.
G102.1
13
iDP-210 Feeder Relay Manual KA2048 520 REV07
1 Introduction
14
iDP-210 Feeder Relay Manual KA2048 520 REV07
15
iDP-210 Feeder Relay Manual KA2048 520 REV07
9. A CAUTION message will appear. Read the message and click OK.
10. The Open File box will appear. Do not open the default ProView 3.2.2 firmware.
Instead, navigate to the ProView 4.0.1 dll folder: Program Files \ Cooper \ Proview401
\ dll, select the Firmware_Form6_V401.o0 file, and click the Open button.
16
iDP-210 Feeder Relay Manual KA2048 520 REV07
11. A message will ask you to verify that you want to download the ProView 4.0.1
firmware. Click OK.
12. The blue progress bar will indicate the firmware is downloading.
13. A message will appear on the PC to indicate the firmware download is complete. Click
OK.
14. The relay will reboot and a message will appear on the LCD indicating that the
firmware installed is Version 4.0.1. All the LEDs will remain illuminated.
15. A message will appear on the PC indicating that the PC and relay are no longer
connected and communicating. Click OK.
17
iDP-210 Feeder Relay Manual KA2048 520 REV07
22. Wait until the screen message indicates that connection between ProView 4.0.1 on
the PC and the relay has been established. Click OK.
24. A screen will indicate the scheme comparison process is complete. Click Done.
18
iDP-210 Feeder Relay Manual KA2048 520 REV07
25. Select Manage>Device>Download structure and settings from the dropdown menu.
27. When the download is complete, the relay will reboot and the comparison status bar
will indicate that ProView 4.0.1 is equal between the PC and the relay.
19
iDP-210 Feeder Relay Manual KA2048 520 REV07
• Reverse Power.
• Breaker fail-to-trip and fail-to-open.
• Bus PT fuse fail detection (i.e., loss of potential). The user may individually set any
directional overcurrent elements to be blocked or made non-directional in the even of
a fuse fail condition.
CONTROL LOGIC
• Sync-check for breaker closing with configurable Hot Bus/Dead Bus, Hot Line/ Dead
Line control.
• Cold load pickup logic.
• Load encroachment logic.
• Eight setting groups with a setting group copy feature.
• User programmable LCD text messages.
• IDEA Workbench™ which provides for virtually unlimited logic customization.
NOTE:
See the “Workbench Programming Manual for the iDP-210” bulletin S165-210-2 for information on how to
configure the IDEA Workbench for the Idea relay.
MEASUREMENTS
• Instantaneous metering including volts, amps, watts, vars, pf and frequency
• Demand metering of amps, MW and Mvar
• Energy metering of amp-hours, MW-Hours and Mvar-Hours
• Harmonic voltage and current metering up to the 15th harmonic
MONITORING FUNCTIONS
• Fault location (distance to fault)
• Sequence of events recording
• Incipient Cable Splice Failure detection algorithm1 provides advance notice of pending
underground feeder cable splice faults.
• Breaker health monitoring including:
• Per phase interrupted current accumulation.
• Longest, average and last time to close.
• Longest, average and last time to trip.
• Breaker operation counter.
• Oscillographic event capture
COMMUNICATIONS
1
US patent 6,198,401.
20
iDP-210 Feeder Relay Manual KA2048 520 REV07
• The iDP-210 ships with DNP 3.0 (serial) protocol installed. Modbus RTU and DNP-
TCP-IP protocols are also included on the distribution CD-ROM. Other protocols can
be downloaded from www.cooperpower.com as they become available. Protocols are
configurable in the IDEA Workbench.
• Both native ProView and DNP3 protocols are TCP/IP enabled when the relay is
ordered with any of the available Ethernet options.
NOTE:
See the “Workbench Programming Manual for the iDP-210” bulletin S165-210-2 for information on how to
configure communications for the Idea relay.
ANALYSIS
• Interactive Oscillography: A set of pre-defined oscillographic views is provided for the
analysis of event records. The views group the various waveforms, protective
element statuses and contact I/O points together in a variety of combinations. A
number of other views, such as a SCADA-like Application Diagram, a synchro-scope,
and so forth, are also provided to assist in event analysis.
• View-Online: This feature allows the user to connect to the relay and to receive live
status indication of the relay’s protective elements, custom logic, targets and
measurement data.
• Relay-Replay: When used with a previously downloaded event record, this feature
allows the user to change the settings of the relay in the PC environment and observe
how the relay would have behaved for the event if it had been set differently.
• Virtual Test Set: This feature allows all of the relay’s settings to be tested in the PC
environment by providing the tools to create and simulate practically any type of fault
event. This eliminates the need for an expensive digital relay test set during the
engineering stage of setting development, and gives every user their own virtual test
set.
The iDP-210 Line Feeder Protection System runs on the Edison Idea or IdeaPLUS relay
hardware. These are shown in Figure 1-1 and Figure 1-2.
21
iDP-210 Feeder Relay Manual KA2048 520 REV07
The front panel of the IdeaPLUS hardware provides extensive user control over the relay
as well as front panel TRIP / CLOSE and Hot Line Tagging controls that replace the
separate conventional switches which must be mounted separately in a control panel. The
TRIP / CLOSE buttons operate even if the relay is failed or is not powered. CLOSE
functionality (inhibited or enabled) through a failed relay must be specified at time of order.
Refer to Section 13.2 for ordering information.
Programmable
Targets Hotkeys
(available with
Idea relay also)
Display with
Controls
Control Panel
(IdeaPlus Only)
See Figure 1-2 for a quick review of the main features of the IdeaPLUS front panel. The
Edison Idea relay and the top portion of the Edison IdeaPLUS relay front panel (that
portion in dark gray) are identical and offer the following
• 25 front panel LEDs for targeting. Note that the labels for the front panel targets may
be changed by the user to reflect utility specific or location specific terminology.
Twenty-three of these targets are programmable by the user.
• 8 programmable hot-keys for one button access to a variety of control and monitoring
functions without the need to negotiate the LCD menu. These hotkeys are
programmable in the Workbench.
• A 4 line by 20 character, wide temperature range LCD display with dedicated cursor
control and menu maneuvering buttons which provides user access to all settings,
targets and measurements. Most settings may be changed directly from the front
panel without need for a PC.
• Four LCD menu context sensitive buttons (marked F1 through F4) which provide
various control and information features.
The bottom portion of the IdeaPLUS is referred to as the control panel and is colored light
gray2. This panel provides:
• Large, self illuminated TRIP and CLOSE controls that operate even if the relay is not
powered or operating properly.
• A hot line tag control which, when enabled, blocks the ability of the relay to issue a
close command to the circuit breaker.
2
Many of the functions of the IdeaPLUS control panel are covered by US patent 6,271,759.
22
iDP-210 Feeder Relay Manual KA2048 520 REV07
• A Close Circuit Disable link. When removed, this link places a physical open in the
breaker’s close circuit making it impossible to close the breaker via the relay or its
CLOSE button under any condition. This is provided in addition to the hot line tag
control for those situations when extra security is required.
• Nine feature pushbuttons with integral indicating LEDs. These provide instant access
to ground trip block, reclose block, and supervisory block. All of the buttons are user
programmable in the IDEA Workbench.
Sample tasks which may be programmed to the pushbuttons include changing setting
groups, toggling operation modes and initiating custom control logic sequences.
23
iDP-210 Feeder Relay Manual KA2048 520 REV07
WARNING: This equipment is not intended to protect human life. Follow all
! locally approved procedures and safety practices when installing or
operating this equipment. Failure to comply can result in death,
severe personal injury and equipment damage.
G102.1
The Edison Idea is a Microprocessor Relay with unique control capabilities. As such, its installation may
be somewhat different than other relays you may have used. This section will provide the information
you need to install the Edison Idea relays.
24
iDP-210 Feeder Relay Manual KA2048 520 REV07
2.2 Edison Idea DC Connection Diagram Where Optional Contact I/O Board IS Present
DC Positive
52 a Trip Close
Note: CI6 is used as a Trip Coil monitor in
the Idea relay only.
TB3
1 7
5 9 13 3 5 11
Breaker 17 19 9 2 17
CI6 CO 15
Closed CI CI3
CI8 CI
CO5 4 SS1 CI1 CI2 CO3 CO1
Lamp 10 12 CO2 Power
18 10 Supply 16 12 13
2 18 14
6 10 14 4 6 8
1 TB1
3 7 11 15
19
CI CI
CI7 CI9 11 13 CO6 SEE NOTE BELOW
20 21 1 3 5 7 9 11
4 8 12 16
CO7 CO8 CO9 CO10 CO11 CO12
2 4 6 8 10 12 13
TB2
TB4
17 19
NOTE: CO9 through CO11 are configured as normally
CI4 CI5 open or normally closed per the Aux I/O ordering
option code (see Section 12.2) as follows:
18 20 Code 0: CO9, CO10 and CO11 all normally open
Code 1: CO9 NC, CO10 and CO11 NO
Code 2: CO9 and CO10 NC, CO11 NO
Code 3: CO9, CO10 and CO11 all normally closed
iDP-210 / idea
52 a
52b
DC Negative
25
iDP-210 Feeder Relay Manual KA2048 520 REV07
Edison Idea DC Connection Diagram Where Optional Contact I/O Board is NOT Present
DC Positive
Remote CLOSE
Remote TRIP
52 a
TB3
3 5 7 11
19 9 2 17
CO 15
SS1 CI1 CI2 CI3 CO3 CO1
4 CO2 Power
18 10 Supply 16 12 13
4 6 8 14
1 TB1
TB2
17 19
Breaker
Closed CI5
CI4
Lamp
18 20
iDP-210 / idea
Relay
Close Trip Alarm
52 a
52b
DC Negative
26
iDP-210 Feeder Relay Manual KA2048 520 REV07
27
iDP-210 Feeder Relay Manual KA2048 520 REV07
28
iDP-210 Feeder Relay Manual KA2048 520 REV07
TB3 TB4
2IN 4IN 6IN 8IN 10IN 12IN 13IN 16IN 18OUT 20N.O. 2OUT 4OUT 6OUT 8OUT 10OUT 12N.O.
CI6 CI7 CI8 CI9 CI10 CI11 CI12 CI13 CO5 CO6 CO7 CO8 CO9 CO10 CO11CO12
• • • • • • • • • •
TB2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Figure 2-5: Idea Relay, Rear Panel Details (below s/n 2000)
4 Voltage Inputs, PR6DD10xxxxxx Ordering Option
TB3 TB4
2IN 4IN 6IN 8IN 10IN 12IN 13IN 16IN 18OUT 20N.O. 2OUT 4OUT 6OUT 8OUT 10OUT 12N.O.
CI6 CI7 CI8 CI9 CI10 CI11 CI12 CI13 CO5 CO6 CO7 CO8 CO9 CO10 CO11CO12
• • • • • • • • • •
TB2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Figure 2-6: Idea Relay, Rear Panel Details (below s/n 2000)
6 Voltage Inputs, PR6DD16xxxxxx Ordering Option
29
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 2-7: Idea Relay, Rear Panel Details (above s/n 2000)
4 Voltage Inputs, PR6DD10xxxxxx Ordering Opt
Figure 2-8: Idea Relay, Rear Panel Details (above s/n 2000)
6 Voltage Inputs, PR6DD16xxxxxx Ordering Option
30
iDP-210 Feeder Relay Manual KA2048 520 REV07
2.4 Input/Output Description Summary
31
iDP-210 Feeder Relay Manual KA2048 520 REV07
WARNING: This equipment is not intended to protect human life. Follow all
! locally approved procedures and safety practices when installing or
operating this equipment. Failure to comply can result in death,
severe personal injury and equipment damage.
G102.1
3
Many of the functions of the IdeaPLUS control panel are covered by US patent 6,271,759.
32
iDP-210 Feeder Relay Manual KA2048 520 REV07
Remote
Close
Remote
52 a Trip
1 3 5 7 19 17 19
TB1
3 5 7 15 9 11
2
Trip Circuit
CI1 CI2 CI3 Power
3 Supply
2 4 6 8 20 21 12 13
4 6 8 14 10 1 16 18
9 11 13 15 17
TB4
SEE NOTE BELOW
CI10 CI11 CI12 CI13 CO5
1 3 5 7 9
10 12 14 16 18 CO CO CO
TB3 CO7 CO8 CO9
10 11 12
2 4 10 7
TB5
2 4 6 8 10 12 13
FROM
CLOSE FRONT
COIL FROM PANEL CCM TB2
GREEN TCM
MONITOR JUMPER
RELAY RED
MANUAL 17 19
[CCM] SWITCH CI4 and CI5 are
found on 4-voltage
HOT LINE TRIP FROM CI4 CI5 input versions only.
TAG COIL FROM FRONT
DC+ IN DC- IN Removable Front MONITOR RELAY PANEL
JUMPER
Panel Close Circuit [TCM] MANUAL 18 20
6 Fuse (See Note) SWITCH
5
1 3 9 8
iDP-210 / IdeaPlus
NOTE: CO9 through CO11 are configured as normally
NOTE: Dashed lines are open or normally closed per the Aux I/O ordering
symbolic breaker option code (see Section 12.2) as follows:
representations. Actual Code 0: CO9, CO10 and CO11 all normally open
Relay
NOTE: Front panel close circuit may vary CLOSE TRIP Alarm
Code 1: CO9 NC, CO10 and CO11 NO
circuit fuse is a 15A, COIL COIL Code 2: CO9 and CO10 NC, CO11 NO
depending upon exact
250V, TYPE MDA-15 breaker make and model. Code 3: CO9, CO10 and CO11 all normally closed
BUSSMAN # MDA-15. Modifications may be
required to accomodate 52 a
52b 52b
the unique characteristics
of the circuit breaker.
DC Negative
33
iDP-210 Feeder Relay Manual KA2048 520 REV07
3.3 DC Wiring Diagram of the IDP-210 with IdeaPLUS Hardware Implementing Operator Window Supervision of the Front Panel CLOSE Button
DC Positive
Remote
Close
Remote
52 a Trip
1 3 5 7 19 17 19
TB1
3 5 7 15 9 11
2
Trip Circuit
CI1 CI2 CI3 Power
3 Supply
2 4 6 8 20 21 12 13
4 6 8 14 10 1 16 18
9 11 13 15 17
TB4
SEE NOTE BELOW
CI10 CI11 CI12 CI13 CO5
1 3 5 7 9
10 12 14 16 18 CO CO CO
TB3 CO7 CO8 CO9
10 11 12
2 4 10 7
TB5
2 4 6 8 10 12 13
FROM
CLOSE FRONT
COIL FROM PANEL CCM TB2
GREEN TCM
MONITOR JUMPER
RELAY RED
MANUAL 17 19
[CCM] SWITCH CI4 and CI5 are
found on 4-voltage
HOT LINE TRIP FROM CI4 CI5 input versions only.
TAG COIL FROM FRONT
DC+ IN DC- IN Removable Front MONITOR RELAY PANEL
JUMPER
Panel Close Circuit [TCM] MANUAL 18 20
6 Fuse (See Note) SWITCH
5
1 3 9 8
iDP-210 / IdeaPlus
NOTE: CO9 through CO11 are configured as normally
NOTE: Dashed lines are open or normally closed per the Aux I/O ordering
symbolic breaker option code (see Section 12.2) as follows:
representations. Actual Code 0: CO9, CO10 and CO11 all normally open
Relay
NOTE: Front panel close circuit may vary CLOSE TRIP Alarm
Code 1: CO9 NC, CO10 and CO11 NO
circuit fuse is a 15A, COIL COIL Code 2: CO9 and CO10 NC, CO11 NO
depending upon exact
250V, TYPE MDA-15 breaker make and model. Code 3: CO9, CO10 and CO11 all normally closed
BUSSMAN # MDA-15. Modifications may be
required to accomodate 52 a
52b 52b
the unique characteristics
of the circuit breaker.
DC Negative
NOTE:Use of this diagram requires Idea Workbench programming. See Section 8.7.1.4 on page 159 for when to use this DC connection diagram.
34
iDP-210 Feeder Relay Manual KA2048 520 REV07
35
iDP-210 Feeder Relay Manual KA2048 520 REV07
36
iDP-210 Feeder Relay Manual KA2048 520 REV07
37
iDP-210 Feeder Relay Manual KA2048 520 REV07
TB3 TB4
2IN 4IN 6IN 8IN 10IN 12IN 13IN 16IN 18OUT 20N.O. 2OUT 4OUT 6OUT 8OUT 10OUT 12N.O.
CI6 CI7 CI8 CI9 CI10 CI11 CI12 CI13 CO5 CO6 CO7 CO8 CO9 CO10 CO11CO12
DC
CLOSE Monitor TRIP
CONTACT LAMP DC+ DC– LAMP CONTACT
1OUT 2OUT 3IN 4IN 5IN 6IN 7IN 8IN 9OUT 10OUT
TB5
• • • • • • • • • •
TB2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Figure 3-5: IdeaPLUS Relay, Rear Panel Details (below s/n 2000)
4 Voltage Inputs, PR6PD10xxxxxx Ordering Option
38
iDP-210 Feeder Relay Manual KA2048 520 REV07
TB3 TB4
2IN 4IN 6IN 8IN 10IN 12IN 13IN 16IN 18OUT 20N.O. 2OUT 4OUT 6OUT 8OUT 10OUT 12N.O.
CI6 CI7 CI8 CI9 CI10 CI11 CI12 CI13 CO5 CO6 CO7 CO8 CO9 CO10 CO11CO12
DC
CLOSE Monitor TRIP
CONTACT LAMP DC+ DC– LAMP CONTACT
1OUT 2OUT 3IN 4IN 5IN 6IN 7IN 8IN 9OUT 10OUT
TB5
• • • • • • • • • •
TB2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Figure 3-6: IdeaPLUS Relay, Rear Panel Details (below s/n 2000)
6 Voltage Inputs, PR6PD16xxxxxx Ordering Option
39
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 3-7: IdeaPLUS Relay, Rear Panel Details (above s/n 2000)
4 Voltage Inputs, PR6PD10xxxxxx Ordering Option
40
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 3-8: IdeaPLUS Relay, Rear Panel Details (above s/n 2000)
6 Voltage Inputs, PR6PD16xxxxxx Ordering Option
41
iDP-210 Feeder Relay Manual KA2048 520 REV07
4
CO9, CO10, and CO11 are configurable as being normally open or closed.
42
iDP-210 Feeder Relay Manual KA2048 520 REV07
43
iDP-210 Feeder Relay Manual KA2048 520 REV07
44
iDP-210 Feeder Relay Manual KA2048 520 REV07
4.2 Idea AC Connection Diagram - 4 Voltage Inputs, Normal ABC Phase Rotation
Idea PR6DD10xxxxxx and PR6DD20xxxxxx Ordering Options
IdeaPLUS PR6DP10xxxxxx and PR6DP20xxxxxx Ordering Options
A
Source
B 52
Line
9 10 11 12 13 14 1 2 3 4 5 6 7 8
TB2 IB IC IX
VA VB VC IA
VS
15 16
Note:
Terminals 7 and 8 are used for the In or Sensitive Ground Fault (SGF) elements only. The residual
overcurrent elements (Ir) derive their signals internally from the A, B and C phase current input signals.
45
iDP-210 Feeder Relay Manual KA2048 520 REV07
B 52 Line
9 10 11 12 13 14 1 2 3 4 5 6
TB2
IC
IB
VA
IA
VC
VB
VS
15 16
Note:
Terminals 7 and 8 are used for the In or Sensitive Ground Fault (SGF) elements only. The residual
overcurrent elements (Ir) derive their signals internally from the A, B and C phase current input signals.
46
iDP-210 Feeder Relay Manual KA2048 520 REV07
B 52
Line
AB Phase
connection shown
for synch-check. BC
or CA connection
allowed as
configured by the
software.
9 10 11 12 13 14 1 2 3 4 5 6 7 8
TB2
IC
IB
IX
VA
IA
VC
VB
VS
15 16
Note:
Terminals 7 and 8 are used for the In or Sensitive Ground Fault (SGF) elements only. The residual
overcurrent elements (Ir) derive their signals internally from the A, B and C phase current input signals.
47
iDP-210 Feeder Relay Manual KA2048 520 REV07
4.5 Idea AC Connection Diagram - 6 Voltage Inputs, Normal ABC Phase Rotation
Idea PR6DD16xxxxxx and PR6DD26xxxxxx Ordering Options
IdeaPLUS PR6PD16xxxxxx and PR6PD26xxxxxx Ordering Options
Note:
Terminals 7 and 8 are used for the In or Sensitive Ground Fault (SGF) element only. The residual
overcurrent elements (Ir) derive their signals internally from the A, B and C phase current input signals.
48
iDP-210 Feeder Relay Manual KA2048 520 REV07
Note:
Terminals 7 and 8 are used for the In or Sensitive Ground Fault (SGF) element only. The residual
overcurrent elements (Ir) derive their signals internally from the A, B and C phase current input signals.
49
iDP-210 Feeder Relay Manual KA2048 520 REV07
B 52
Line
AB Phase
connection shown
for synch-check. BC
or CA connection
allowed as
9 10 11 12 13 14 1 2 3 4 5 6 7 8 configured by the
TB2
VAx
VCx
VBx
software.
IC
IB
IX
IA
VCy
VAy
VBy
15 16 17 18 19 20
Note:
Terminals 7 and 8 are used for the In or Sensitive Ground Fault (SGF) element only. The residual
overcurrent elements (Ir) derive their signals internally from the A, B and C phase current input signals.
50
iDP-210 Feeder Relay Manual KA2048 520 REV07
5.1 Introduction
The iDP-210 offers extensive front panel operation capabilities including:
• View instantaneous and demand metering quantities
• View targets
• View fault locator results
• View and change most settings
• Force contact inputs and outputs
• Operate the circuit breaker
• Change setting groups
• View Sequence of Events log
This section of the manual is designed to familiarize the user with the structure of the front
panel MMI and how to interact with it.
51
iDP-210 Feeder Relay Manual KA2048 520 REV07
CAUTION: Equipment misoperation. In the event the Close Circuit disable link
! fuse must be replaced, replace only with a fuse of equal protective
rating and physical specification. Failure to use the proper fuse can
result in equipment damage and/or unintentional operation.
T291.0
• Nine dedicated feature pushbuttons with integral indicating LEDs. Three are assigned
in the default scheme to provide instant access to ground trip block, reclose block and
supervisory block, but all nine buttons are user configurable in the IDEA Workbench.
5
Many of the functions of the IdeaPLUS control panel are covered by US patent 6,271,759.
52
iDP-210 Feeder Relay Manual KA2048 520 REV07
53
iDP-210 Feeder Relay Manual KA2048 520 REV07
NOTE: The LED targets on the upper portion of the relay also operate to confirm the breaker’s position.
If the TRIP button is pressed when there is no trip circuit voltage a TRIP action will not
occur. But, when the TRIP circuit is re-energized the IdeaPlus relay will then issue a TRIP
signal because the relay stores the trip signal until it has trip circuit voltage.
The IdeaPlus relay does not require trip voltage to be confirmed before it asserts the TRIP
output contact. If any TRIP initiating event occurs - such as pressing the front panel trip
button - the relay will assert (and maintain asserted) its TRIP output contacts for at least
(79:62mtt) seconds as set in the Recloser Settings dialog box, and beyond that, until the
52a input un-asserts or the reclosing logic is reset. The TRIP contact output does not un-
assert even when fail-to-trip or slow-to-trip conditions are detected. If relay power is cycled,
TRIP will un-assert; but will, of course, re-assert upon power-up if there is a fault present.
5.5.1.2 CLOSE Button
The CLOSE contact output is held asserted for a minimum of (79:62mct) seconds, as set
in the Recloser Settings dialog. Thereafter, it will immediately un-assert if Tripping is
initiated for any reason. If Tripping is not initiated, the CLOSE contact output will nominally
remain closed until the 52a input asserts.
However, if Failure-to-Close is detected (79:62ftc) seconds after the CLOSE contact
output was asserted, then the CLOSE contact output could possibly un-assert at that
point. Whether or not the CLOSE contact output un-asserts for detection of Failure to
Close, depends upon what initiated the CLOSE operation, in conjunction with settings.
• For any closure due to a non-reclose operation (such as pressing the front panel
CLOSE button) detection of a Failure-to-Close condition always causes un-assertion
of the CLOSE contact output.
• But for any reclose operation, the detection of a Failure-to-Close condition will cause
un-assertion of the CLOSE contact output only if this behavior is expressly enabled
via the (79:ELO:ftc) setting found in the Recloser Settings dialog.
If relay power is cycled, CLOSE will un-assert.
54
iDP-210 Feeder Relay Manual KA2048 520 REV07
WARNING: Hazardous voltage. Do not use Hot Line Tag as a substitute for a
! visible disconnect. Always establish a visible disconnect prior to
performing any work requiring a de-energized line. Failure to comply
may cause death, severe personal injury or equipment damage.
T276.0
To apply Hot Line Tag (HLT), move the HLT toggle switch up to the ON position. The HLT
LED will illuminate indicating that the HLT feature is active. If the circuit breaker trips, the
HLT mode will ensure that the breaker will not be sent a close command from the Idea
relay via the relay’s CLOSE contacts located on terminals 7 and 8 on terminal Block 1
(TB1) or from terminals 1 and 2 on TB5 on the IdeaPlus relay. Hot Line Tag mode also
prevents remote operations through the contact inputs or the communication ports.
To disable the HLT mode, move the HLT toggle switch down to the OFF position. The
relay will now permit CLOSE commands to be issued to the circuit breaker.
Hot Line Tag mode can not be set or cleared by remote communications or contact input.
Hot Line Tag mode can only be set or cleared via the front panel HLT toggle switch.
55
iDP-210 Feeder Relay Manual KA2048 520 REV07
WARNING: Hazardous Voltage. Enabling Close Inhibit does not guarantee that
! the device being controlled by the relay cannot be closed by remote
command. This may result in the application of hazardous voltages
to the electrical circuit connected to the controlled device. Failure to
separately disable the remote communications, and to place a
physical break in the device’s close circuit may result in death,
severe personal injury and equipment damage.
T292.0
Close Inhibit acts only to inhibit the breaker from receiving a close command from the Idea
relay via the relay’s CLOSE contacts located on terminals 7 and 8 on terminal Block 1
(TB1) or from terminals 1 and 2 on TB5 on the IdeaPlus relay. To apply Close Inhibit,
press the Close Inhibit switch up so that the Close Inhibit LED starts flashing. The flashing
LED indicates that the supervisory control is still in operation and that Close Inhibit can be
turned off through supervisory control (contact inputs or communication command). TO
DISABLE SUPERVISORY CONTROL, press the Supervisory off switch so the
Supervisory OFF LED turns on. With supervisory control turned off, the Close Inhibit LED
will change from flashing to steady “ON”. When the Close Inhibit LED is steady “ON”, all
supervisory control (contact input and communication port) and auto reclosing is disabled.
To turn off Close Inhibit, press the Close Inhibit toggle switch to the off position, the Close
Inhibit LED will turn off. Press the Supervisory Off switch to enable supervisory control.
The Supervisory Off LED will turn off.
56
iDP-210 Feeder Relay Manual KA2048 520 REV07
57
iDP-210 Feeder Relay Manual KA2048 520 REV07
DISPLAY MEANING
> MODES Shorthand view of non-volatile operating mode
statuses.
4 line window
The current location on the menu is indicated by a cursor (>). To move up and down the
menu, use the up and down cursor keys and .
To choose one of the menu items, locate the cursor on the item and press the ENTER
button. This will then take you to the appropriate sub menu. These are described in the
following sections. To exit a sub-menu, press the MENU button. This will take you back
one menu level.
58
iDP-210 Feeder Relay Manual KA2048 520 REV07
VALUE: 0
VIEW CANCEL
ONLY
F1 F2 F3 F4
Figure 5-3 : PASSWORD Entry Display on Relay LCD
The password is a numeric value between 0 and 30,000. Use the blue + and - keys
increment or decrement the password value. The default password is numeric zero (0)
and can be changed via the Settings>Relay Behavior>MMI Forcing and Dialog Enables
dialog box. Press the blue ENTER key to enter the password and access the sub-menu.
If it is not desired to enter the password, press either the F4 key to Cancel the operation,
or the blue MENU key to exit the Password menu. If the password is unknown, press F1
to enter the SETTINGS sub-menus in a View-only mode.
Display Appearance
MODE If ON If OFF
Hot Line Tag H h
Ground Trip Blocked G g
Reclosing Blocked R r
Local Mode (i.e., Supervisory On or Off) S s
User Mode – W W w
User Mode – X X x
User Mode – Y Y y
User Mode – Z Z z
This menu provides full line descriptions of the status of each of the MODES. Moving the
cursor to a particular MODE and again pressing the ENTER key provides the ability to
change the MODE’s status. The exception to this is the Hot Line Tag function for the
IdeaPlus relay which requires Hot Line Tag to be enabled/disabled via the toggle switch.
The User Modes display may be changed using the Workbench>Workbench Non-Volatile
Modes dialog box within ProView. This allows the letter used (W, X, Y and Z) to be
changed, as well as the text string used in the MMI to describe the User Mode.
The Fixed Modes display may be changed using the Settings>Relay Behavior>Relay
Operating Modes menu path within ProView. This allows the designated letter to be
changed, as well as the text string used in the MMI to describe the User Mode. See
Section 8.17.2.
59
iDP-210 Feeder Relay Manual KA2048 520 REV07
60
iDP-210 Feeder Relay Manual KA2048 520 REV07
Meaning
> PICK SETTING GROUPS Select or modify a particular setting group
To select a setting group, move the cursor (>) to the “PICK SETTING GROUPS” line and
depress the blue ENTER button.
Two lines are now displayed as shown in Table 5-3. Selecting the appropriate line and
pressing the ENTER button provides access to the appropriate setting menu screen.
61
iDP-210 Feeder Relay Manual KA2048 520 REV07
Meaning
> Grp:Active #1 Setti The number (or text) indicates which setting
group is currently active in the relay.
Grp:Modify #1 Setti Indicates which setting group’s settings are
currently being displayed and capable of being
modified.
Table 5-3 : Sub-Menu of the PICK SETTING GROUPS Sub-Menu
Meaning
> Nom:Freq 50 or 60 Hz
4 line window
on Menu
Here we move the cursor to the Nom:IPsec setting and depress the ENTER key. This
brings up the display as shown in Figure 5-4, which is typical for all settings.
62
iDP-210 Feeder Relay Manual KA2048 520 REV07
The top line shows the setting name and unit of measure. The second line shows the
minimum and maximum setting range. The third line shows the current value of the
setting. To change the setting use the < and > to move the ^ cursor and the + and -
keys to increase or decrease the value where the ^cursor is positioned. Once the new
setting is set, press the ENTER button to store the setting in temporary memory. Use the
MENU key to go up one menu level to provide access to making additional setting
changes.
NOTE: For inverse time curves, the curve shapes are selected using the curve
descriptions as is done in the ProView software. The curve shapes are listed in Table 5-5.
Curve Shape
IEEE-MI ( Moderate Inverse)
IEEE-VI (Very Inverse)
IEEE-EI (Extremely Inverse)
IEC-A
IEC-B
IEC-C
IEC-D
IEC-E
SEL-U1
SEL-U2
SEL-U3
SEL-U4
SEL-U5
Custom (User-Defined)
Table 5-5 : Inverse Curve Selection for Front Panel Setting
NOTE: Setting changes from the front panel are not actually made in the relay until the
MENU button is pressed a second time in order to leave the overall SETTINGS sub-
menu. When leaving the SETTINGS sub-menu, if any setting changes have been made
the following screen Figure 5-5 appears:
63
iDP-210 Feeder Relay Manual KA2048 520 REV07
In this case we learn that the P was for a phase overcurrent trip and the M indicates a
medium-set trip condition. The 0 or 1 preceding the target indicates if the target is inactive
(0) or active (1).
Meaning
> Reset Targets Access Reset Targets menu
4 line window
on Menu
If the ENTER button is pressed while the cursor is on the Reset Targets line, a display is
shown which allows the targets to be reset. See Figure 5-7.
64
iDP-210 Feeder Relay Manual KA2048 520 REV07
NOTE: A target cannot be reset for which the condition is still valid.
> Push Fkey to reset
Targets, Ext Alarms
Push MENU to abort.
Targets ALARMS
F1 F2 F3 F4
Figure 5-7: Reset Targets LCD Display
If any external alarms are logged, the LCD menu display will show “EXTERNAL
ALARMS=1”. An external alarm is one that was caused by a condition external to the
relay. This is contrasted with internal alarms, which are caused by relay faults.
To view the alarms in more detail, place the cursor (>) next to the EXTERNAL ALARMS
line and press the ENTER key. This will result in the display as shown in Table 5-6.
If the ENTER button is pressed while the cursor is on the “Reset Ext Alarms” line, the
screen shown in Figure 5-7 is displayed which allows the targets to be reset. An alarm
cannot be reset for which the condition is still valid.
65
iDP-210 Feeder Relay Manual KA2048 520 REV07
Meaning
> Reset Ext. Alarms Access “Reset Ext. Alarms” screen. See Figure
4 line window
5-7.
66
iDP-210 Feeder Relay Manual KA2048 520 REV07
If any internal alarms are logged, the LCD display will show “INTERNAL ALARMS=1”. An
internal alarm is one that is the result of an internal relay fault. This is contrasted with
external alarms, which are caused by conditions external to the relay.
To view the alarms in more detail, place the cursor (>) next to the INTERNAL ALARM line
and press the ENTER key. This will result in the following display:
Meaning
> Reset Int. Alarms Access “Reset Int. Alarms” screen
4 line window
on Menu
Power Supplies ......0 If=1 indicates a power supply problem (If the
power supply fails the relay will not operate!)
RAM Failure ...........0 If=1 indicates a problem with the RAM
ROM Failures .........0 If=1 indicates a problem with the ROM
Calibrating…………0 If=1 indicates the relay is in a self-calibration
mode. Contact your Cooper Power Systems
representative for additional information.
Table 5-7: INTERNAL ALARMS Sub-Menu
If the ENTER button is pressed while the cursor is on the “Reset Int. Alarms” line, a display
similar to that in Figure 5-10 is shown which allows the targets to be reset. An alarm
cannot be reset for which the condition is still valid. With the exception of the first line, all
the lines of this sub-menu are for informational purposes only.
If the ENTER button is pressed while the cursor is on the “Power Supplies” line, a display
of the power supply voltage is shown. For instance, Plus Five…5.03 (nominal Volts). If the
measured Volts varies by +/- 0.3 Volts the Power Supplies alarm will assert.
All of these alarms are deemed Critical Self-Test Failures, in which subsequent operation
of the protective functions is indeterminate. When a Critical Self-Test Failure is detected,
the relay asserts Internal Alarm status points and its Alarm contact output, and then
disables all its contact output drivers. Thereafter, until the failure condition is corrected,
there is no programmed means by which the relay can further alter the status of any of its
contact outputs, whether by protective relay element operation, or by front panel, contact
input, or communicated control inputs.
Place the cursor on this line and press the ENTER button. The LCD will now display the
metered phase and ground currents and voltages in primary Amps and kV. The last line
of the display will briefly display the current and voltage legend for 1 second every 10
seconds.
67
iDP-210 Feeder Relay Manual KA2048 520 REV07
Place the cursor on this line and press the ENTER button. The LCD will now display the
metered phase and ground currents and voltages with phase angles in secondary amps
and volts. The last line of the display will briefly display the current and voltage legend for
1 second every 10 seconds.
5.7.7.3 DEMAND METER Sub-Menu
This menu gives access to the various demand meters. Placing the cursor on this line and
pressing he ENTER button will bring up the following menu:
Meaning
> Demand Amps per Pha Displays per phase demand and peak meters.
Press Enter for the time startup of the most
recent demands peaks.
Demand MW, MVAr Displays MW and MVAr import(-) and export(+)
demand and peak meters. Press Enter for the
time startup of the most recent demands peaks.
Reset Demand Peaks Access “Reset Demand Peaks” screen
Figure 5-8: Demand Meters Sub-Menu Display
This menu gives access to the various power and energy meters. Placing the cursor on
this line and pressing the blue ENTER button will bring up the following menu:
Meaning
> Power Meters Displays per phase and three phase power
meters.
W/VAr: Hour Meters Displays per phase and three phase watt- and
var-hour meters.
Amp:Hour Meters Displays per phase Amp-hour meters.
Reset X:Hour Meters Access “Reset Power/Energy Meters” screen.
Figure 5-9: Power/Energy Meters Sub-Menu Display
Place the cursor on this line and press the ENTER button. The LCD will now display the
metered line, bus, and line-bus slip (difference) frequency in Hertz.
68
iDP-210 Feeder Relay Manual KA2048 520 REV07
Meaning
> Reset Recloser Access Reset Recloser menu
4 line window
on Menu
69
iDP-210 Feeder Relay Manual KA2048 520 REV07
All of the lines of in this sub-menu are informational only except for the first line. While the
cursor (>) is on the Recloser/Breaker status line, pressing the ENTER key will take you to
the display shown in Figure 5-10. By pressing the F4 key the recloser will be reset. Press
the MENU key to move up back out of this display (each press of the MENU button takes
you back one menu level).
> Push RESET to reset
The recloser.
Push MENU to abort
RESET
F1 F2 F3 F4
Figure 5-10: Reset Recloser LCD Display
Meaning
> Distance(km) = 2.3 Distance to fault = 2.3km
I Flt(pri) = 1545 Fault current in Aprimary = 1545
Duration(cy) = 5.2 Duration of fault = 5.2 cycles
Fault Type = AG Fault involved phase A and Ground
Figure 5-11: Sample FTYPE DISTANCE DUR Display
Note the distance to fault will be in kilometers or miles, depending on which unit of
measure is selected in the relay.
If the cursor ( > ) is placed at the “View Statistics” line and the ENTER button is pressed,
the following information is displayed:
70
iDP-210 Feeder Relay Manual KA2048 520 REV07
Meaning
> Trip Count= Cumulative number of breaker operations
BkrDuty:A= Cumulative interrupted current in kA6 for phase A
BkrDuty:B= Cumulative interrupted current in kA6 for phase B
BkrDuty:C= Cumulative interrupted current in kA6 for phase C
Trip Tmax= Maximum time to trip
Trip Tavg= Average time to trip
Trip Tnew= Time to trip for last operation
Close Tmax= Maximum time to Close
Close Tavg= Average time to Close
Close Tnew= Time to Close for last operation
Init Values Provides access to a settings sub-menu for initial
breaker monitoring settings.
Reset to InitValues Permits resetting of breaker statistics to those
defined in the Init Values menu. Other statistics
set to zero.
Table 5-11: Breaker Statistics Sub-Menu
6 2
Depending on the exponent value chosen, this could be kA, kA , etc.
71
iDP-210 Feeder Relay Manual KA2048 520 REV07
Pressing the F1 button (View) and holding it will bring up the display as shown in Figure
5-14. This display permits the continuous monitoring of the breaker’s 52a contact, the
state of the 50DCB element as well as current trip and close statuses. As a reminder, the
50DCB element is a low set phase current sensing element used only to detect when
current is flowing through the breaker.
Note also that if the 52a contact status is “1” rather than the “0” as shown in the figures,
then the breaker is already closed, and the F4 softkey label text will be “open” rather than
“close” as shown.
> 52a=0 PermitClos=0
50DCB=0
Trip=0 Close=0
View Enab close
F1 F2 F3 F4
Figure 5-14: BREAKER TRIP/CLOSE Display with Metering
To actually operate the breaker, the F2 “Enab” button must first be depressed for 1 second
to enable this feature. Once enabled it will be possible to operate the breaker for up to two
minutes. After two minutes the F2 button must be pressed again.
72
iDP-210 Feeder Relay Manual KA2048 520 REV07
This is the screen for the first input contact. The input signal name is given in the first line.
The second line is a description of the input. The third line is the physical description of
the input on the back of the relay.
The last line gives the user four options depending upon which function key is pressed.
F1 Hold this button down for 1 second to move on to the next contact
F2 Hold this button down for 1 second to move to the previous contact
F3 Hold this button down for 1 second to enable the contact forcing feature
F4 After the contact forcing has been enabled, hold this button down to force the logic
state to a “1”. The logic state will be forced only for as long as the button is
depressed. This does not latch the contact.
To exit out of this menu, press the MENU key.
> 0=ss1
User ss1 Description
Contact Output
Next Prev Enab force
F1 F2 F3 F4
Figure 5-16: Contact Outputs LCD Display
This is the screen for the first output contact. The input signal name is given in the first
line. The second line is a description of the output. The third line is the physical
description of the output on the back of the relay.
The last line gives the user four options depending upon which function key is pressed.
F1 Hold this button down for 1 second to move on to the next contact
F2 Hold this button down for 1 second to move to the previous contact
F3 Hold this button down for 1 second to enable the contact forcing feature
F4 After the contact forcing has been enabled, hold this button down to force the logic
state to a “1”. The logic state will be forced only for as long as the button is
depressed. This does not latch the contact.
To exit out of this menu, press the MENU key.
NOTE:
73
iDP-210 Feeder Relay Manual KA2048 520 REV07
When a Critical Self-Test Failure occurs (power supply failure, RAM, failure, ROM failure,
etc.) in which subsequent operation of the protective functions is indeterminate, the relay
asserts Internal Alarm status points and its Alarm contact output, and then disables all its
contact output drivers. Thereafter, until the failure condition is corrected, there is no
programmed means by which the relay can further alter the status of any of its contact
outputs, whether by protective relay element operation, or by front panel, contact input, or
communicated control inputs.
Moving the cursor to the WORKBENCH ANALOGS and WORKBENCH STATUS menu
items and pressing the blue ENTER button brings up informational displays. The names
of the custom analog measurements may be defined using the Workbench>Workbench
Analog Outputs to MMI menu path. The names of the Workbench status outputs may be
defined using the Workbench>Workbench Status Outputs to MMI and SOE menu path.
See S165-210-2, Workbench Programming Manual, for information.
Moving the cursor to the WORKBENCH SWITCHES line of the sub-menu items and
pressing the blue ENTER button brings up the following menu (Switches #1-9; A, B, C):
74
iDP-210 Feeder Relay Manual KA2048 520 REV07
Note the display strings “Momentary Switch #x” may be replaced with custom text. This is
accomplished in ProView by utilizing the Workbench>Workbench Softkey Switches in
MMI dialog box. See Bulletin S165-210-2, Workbench Programming Manual, for
information on renaming the switches.
Moving the cursor to any of these lines and pressing the blue ENTER button brings up the
following display:
> Push YES to operate
Push MENU to abort.
Momentary Switch #1
YES
F1 F2 F3 F4
Figure 5-17: BREAKER TRIP/CLOSE Display with Metering
As previously noted, the display string “Momentary Switch #x” may be replaced with
custom text.
Pressing the gray F4 button will send a logic signal to the IDEA Workbench. This signal
may be used in the IDEA Workbench to accomplish any desired task.
75
iDP-210 Feeder Relay Manual KA2048 520 REV07
6.2 Requirements
ProView is a powerful program that utilizes the power of your PC to maximize the
usefulness of the Edison idea/IdeaPLUS Relays. The more powerful your computer, the
more enjoyable your experience with ProView and the Edison idea/IdeaPLUS Relays will
be. As a MINIMUM, we recommend:
• Pentium-Class PC
• Windows 95, 98, NT, 2000, or XP
• Processor speed at least 300MHz
• Minimum 128MB, recommended 512MB of RAM
• At least 130 MB of free Hard-Disk storage
Note: These are the minimum supported capabilities. ProView will not perform satisfactorily on computers
that do not meet all of the above requirements.
Hint: Running ProView on a computer with the following specifications will give optimal performance:
Pentium IV Class PC
Windows 2000 or XP Professional operating system
Processor speed 1.8GHz or greater
RAM 512MB or more
76
iDP-210 Feeder Relay Manual KA2048 520 REV07
Click OK.
77
iDP-210 Feeder Relay Manual KA2048 520 REV07
Read the Software License Agreement fully, and choose “Yes” if you agree or “No” if you
do not agree to the terms of the Agreement.:
Select the Scheme Files you wish to install. The contents of this list will vary depending on
what product(s) you have ordered:
78
iDP-210 Feeder Relay Manual KA2048 520 REV07
Once you have made your selections, press “Next” to begin the installation. A progress
indicator will show the progress of the installation:
ProView will check the HTML Help file version currently loaded. If the version on the PC is
older, the Help files will automatically be updated.
If the version on the PC is newer, the following message will appear: This computer
already has a newer version of HTML Help. Click OK.
79
iDP-210 Feeder Relay Manual KA2048 520 REV07
After the installation has successfully completed, you will be prompted to place a shortcut
to the iDP210 scheme on your desktop. If you choose to install this shortcut, then you will
be able to start ProView and automatically load the appropriate iDP-210 scheme by
double clicking on the desktop icon.
After the installation has successfully completed, you will see this screen. Press “Finish” to
exit the setup program. If you do not de-select the “Register Online” checkbox, you will be
linked to the online ProView registration form. ProView 4.0.1 does not require a software
authorization key, but registration is still recommended so you can easily access valuable
modifications.
80
iDP-210 Feeder Relay Manual KA2048 520 REV07
81
iDP-210 Feeder Relay Manual KA2048 520 REV07
IMPORTANT: The use of relays and recloser controls that use the ProView operating system may
result in the creation of many combinations of setting files, scheme files, and custom software files.
Many of these combinations can be downloaded into any relay or recloser using the ProView operating
system. The user must ensure that the proper combination of software modules is created and
downloaded to the correct device for the application.
82
iDP-210 Feeder Relay Manual KA2048 520 REV07
If you choose to launch the main ProView application instead by means of the Windows
Start menu or a shortcut icon on the desktop, and a successful login has been provided,
the user may open – or load – the desired scheme. Access the standard file open dialog
via the File – Open menu command to reveal the dialog similar to Figure 7-1 below.
Figure 7-2: Scheme Loading Monitor in Lower Left Hand Corner of ProView
Screen
If the loading process takes longer than 3 minutes, your system may not have enough
RAM to run ProView efficiently. This may be the result of too many open background
tasks or insufficient system memory. Upgrading your PCs RAM will improve the
performance of ProView. ProView works best on systems with 512MB or more of RAM.
83
iDP-210 Feeder Relay Manual KA2048 520 REV07
This will bring up the Select Connection dialog box. Here you can select the appropriate
connection. (Additional connections can be added to this list. See section on “Configuring
ProView Connection Profiles” below for details).
Select the desired connection method and press “OK”. You will be prompted for a
connection password. The default passwords are “View” (upload information from device
only) or “Modify” (upload information from device and download changes to device).
ProView will attempt to locate the Edison ιδεα or IdeaPLUS relay via the selected port.
The connect button’s appearance will change depending on the phase of connection
ProView is in:
Before connecting:
84
iDP-210 Feeder Relay Manual KA2048 520 REV07
HINT If you mistakenly attempt to connect via the wrong port, you can abort the connection
attempt by pressing the Connect button at any time it appears with the yellow question
mark (?) symbol. Pressing this button after communication has been established will
disconnect the PC from the relay.
NOTE After connecting, if a dialog appears indicating that a comparison is not possible because the
relay has a different version of firmware, see Section 11.2.5 on page 208 for the procedure on updating
firmware.
After successfully connecting to the relay, the progress indicator bar shown in Figure 7-5
may appear. This progress bar signifies that ProView is comparing the contents of the
RAM and EEPROM of the connected relay to the version of the IDP-210 scheme currently
loaded on the PC. Depending upon your computer’s speed and the amount of RAM, this
could take as long as 5 minutes. See Section 6.2 for the recommended minimum PC
hardware requirements.
To add a new connection, simply click on the Add button in the Manage Connections
dialog box as shown in Figure 7-7. Select type of connection: Serial connection
(Direct/Modem) or TCP/IP. A new connection labeled “(none)” will be added to the list.
Click on “(none)” to select it and then click the Edit button.
85
iDP-210 Feeder Relay Manual KA2048 520 REV07
In the Manage Connections dialog box you can select the computer’s serial
communication port that is used to connect to the relay as well as the baud rate. The
Edison Idea and IdeaPLUS relays auto baud up to 115200 bps.
Figure 7-8: Edit dialog box for connections. Left - Serial connection
(Direct/Modem) or Right - TCP/IP.
To change the name for the connection select the Name tab in the Edit dialog box.
It is possible to enter a phone number. If a phone number is entered, then when that
connection is selected, the phone number is automatically dialed. Upon connecting, a
ASCII terminal emulator window will open. This provides the opportunity to enter an ASCII
command string to an intermediate device, such as a communications port switcher.
When finished entering any required ASCII commands needed to finish connection to the
relay, close the terminal emulator. ProView will now automatically connect to the relay.
7.2.2.2 Configuring TCP/IP Connection Parameters
When setting up a TCP/IP connection, the dialog box has two tabs, as shown in Figure
7-8, the Name and Socket tabs. The window opens by default to the Socket tab. Here you
must enter a TCP/IP value that does not conflict with your network. If being used in a
corporate environment, this number should be verified with the Information Technology
(IT) department. If being used in a standalone network, the default value of 1024 may be
used. Any value up to 64000 may be used.
The Name field in the Socket tab is used for the relay’s TCP/IP address. The default
address of all Idea and IdeaPlus relays is 10.10.10.10.
86
iDP-210 Feeder Relay Manual KA2048 520 REV07
The Description field in the Name tab may be used as a textual name for the connection.
This is the name that will appear in the list of connections as shown in Figure 7-7.
7.2.2.3 Changing the Relay’s TCP/IP Connection Parameters
Changing the relay’s TCP/IP parameters must be accomplished via a serial connection to
the relay. This is done for security purposes. For the same reason, the relay does not
dynamically assign IP addresses (DHCP server). The IP address and subnet masks for
the relay must be made manually via the serial connection.
First establish communication with the relay through a serial communication port.
Second, follow the Manage>Device>Settings menu path to open the relay’s Setting’s
menu. Every relay ships from the factory with an IP address of 10.10.10.10 and a subnet
mask of 255.255.255.0. At least the IP address must be changed to be unique for each
relay on the TCP/IP network.
Change these values to those desired and up load these settings to the relay using the
normal setting upload process.
Once the relay automatically reboots after the setting upload, ProView communication
may be established with the relay directly via the network connection port using the new
addresses.
Note, when using only one Ethernet cabling connection use the communication port closet
to the edge of the back of the relay (port 1).
After connection is successfully established, the “Compare” button on the toolbar will
appear in one of several possible modes as shown in Figure 7-10 through Figure 7-12.
87
iDP-210 Feeder Relay Manual KA2048 520 REV07
Regardless of the state of the compare button, clicking on it will bring up the detailed
comparison window as shown in Figure 7-14.
NOTE: If any modifications to the scheme were made after it has been opened in ProView, the message
dialog box shown in Figure 7-13 will appear when the Compare button is clicked. Any setting changes,
including selecting a different setting group to be active or to view, will also result in this dialog box. The
default factory scheme files are read only. You must save your scheme with a new name. This ensures
you can always go back to the factory default scheme at any time.
88
iDP-210 Feeder Relay Manual KA2048 520 REV07
This window allows you to see what is different between the PC and the Relay, and either
upload (receive) information from the relay or download (send) information to the relay. It
is important that the information in the PC match the relay if you plan on going “Online”.
Where information is identical between the PC and the relay, the action button(s) will be
disabled (grayed out). If information differs (as do the structure and settings in the figure
above), the action button will be enabled.
Pressing the Details button will bring up a dialog that lets you compare the value of
settings on the relay to the settings on the PC and correct discrepancies by uploading or
downloading individual settings, selected settings, or all settings. When you press the
Details button, a dialog similar to that shown in Figure 7-15 will appear:
89
iDP-210 Feeder Relay Manual KA2048 520 REV07
This dialog shows the values of only the settings that are different between the relay and
the PC. The comma-delimited values represent the setting for each setting group. In this
example, the computer shows a value of 0 for the 67P:E element in the first setting group,
while the relay shows a value of 1 for the same setting. The 67P setting is the same for all
other setting groups.
If you wish to change the setting on the relay to a new value you have entered on your
PC, simply select the line(s) of interest and click Download selected settings to device to
send the revised setting(s) to the relay.
If the settings in the relay are correct, you should upload them from the relay to ensure that
your PC has the correct information. Do this by first pressing the Select all button, and
then pressing the Upload selected settings from device button.
After you correct any mismatches, the compare button should revert to the “Equal” mode.
NOTE:
Downloading settings to the relay will erase all oscillographic event records and reset all accumulators
and counters stored in volatile memory. Please ensure that all event data is retrieved and that
accumulator and counter values are recorded before downloading schemes.
90
iDP-210 Feeder Relay Manual KA2048 520 REV07
NOTE:
Downloading settings to the relay will erase all oscillographic event records and reset all accumulators
and counters stored in volatile memory. Please ensure that all event data is retrieved and that
accumulator and counter values are recorded before downloading schemes.
In addition to uploading and downloading settings, ProView also allows the entire
protection scheme logic to be downloaded from the PC to the Relay. This download is
done using the “Download” structure button in the compare dialog. This button is only
enabled if there are differences in the structure of the scheme on the relay as compared to
the scheme on the PC. The usual reason for a structural difference in the scheme is due
to a newer version of the scheme being loaded on the PC than on the relay.
If the scheme structure is identical except for the workbench logic, you will also have the
option of uploading the workbench from the relay to the PC using the “Upload” workbench
button.
The table below summarizes the possible combinations of scheme and workbench
differences, and the appropriate action(s) for each case:
If the relay and PC are not equal, proceed as follows:
1. Upload Idea Workbenches.
2. If you are still not equal, Upload the Settings.
3. If you are still not equal, Download the Structure.
91
iDP-210 Feeder Relay Manual KA2048 520 REV07
92
iDP-210 Feeder Relay Manual KA2048 520 REV07
Once the Event Manager has been opened, the screen will appear as in Figure 7-17.
The top portion of the Event Manager is titled PC Events and provides the ability to load
any event record that has previously been saved to disk, or created in the Virtual Test Set
(VTS) within ProView.
• The Generate report… button enables you to convert a PC event to the COMTRADE
format. This function is designed to meet the requirements of IEEE® Std C37.111-
1999TM Standard Common Format for Transient Data Exchange (COMTRADE) for
Power Systems.
The lower portion of the window, titled Device Events, will allow the uploading of events
from the relay when connected to the PC.
LOADING EVENTS FROM THE RELAY
To load an event from the relay:
1. Establish communication with the relay as indicated in Section 7.2.
2. From the Event Manger window as shown in Figure 7-17, click on the drop down box
under Device Events “Time/Length:” to bring up a list of events in the relay.
3. To load one event, choose the desired event and click on the Upload button or to load
all of the events, click on the Upload All button.
4. The .evt event file(s) must always be saved to the Proview401/iDP-210 folder.
• If you are only saving one event, the Save As dialog box will automatically open
allowing you to rename the event. Click OK to save the event file to disk. If you
are saving all the events (via the Upload All button), the event files will be named
according to the date/time stamp of each event.
• When saving events from the relay, the following file types will automatically be
created: .evt, .dat, .cfg, and .txt for each event.
93
iDP-210 Feeder Relay Manual KA2048 520 REV07
94
iDP-210 Feeder Relay Manual KA2048 520 REV07
Movable cursor
controlled by the
Cursor Control Panel
Magnitude of all
displayed waveforms
at the cursor location
shown here.
95
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 7-21: Open Phasor Display Window Showing Voltage and Current
Phasors
96
iDP-210 Feeder Relay Manual KA2048 520 REV07
From the buttons on the bottom of the SER windows, it is possible to write the data file.
Up to 250 events are recorded in a first in-first out buffer.
7.7 View-Online
The “View-Online” feature allows for live connection to the relay. The Workbench’s logic
and status of all the elements can be viewed when in the View-Online mode.
There are two ways to enter “View-Online” mode. The easiest way is to click on the
Go Online button in the Communication Toolbar as shown in Figure 7-23. Alternatively,
you can is to open the Application Diagram window (see Section 7.8.1) and click on the
Go Online button that appears on that display.
97
iDP-210 Feeder Relay Manual KA2048 520 REV07
98
iDP-210 Feeder Relay Manual KA2048 520 REV07
This display shows the status of all of the targets on the front of the relay. To access this
display, follow the Display>Targets menu path from the main menu. In the figure, four of
the targets are shown active. In View Online mode (see Section 7.7) these targets are
continuously updated. During event playback, these targets reflect the behavior of the
relay during the actual event. The meaning of each of these targets is described in
Section 5.4 on page 53.
99
iDP-210 Feeder Relay Manual KA2048 520 REV07
This display shows the status of all of the relay’s external alarms. To access this display,
follow the Display>External Alarms menu path from the main menu. External alarms are
those caused by events external to the relay hardware itself. In the figure, none of the
targets are shown active. In View Online mode (see Section 7.7) these alarms are
continuously updated. The status of these alarms is also presented on the relay LCD
display. See Section 5.7.6.1
This display shows the status of all of the relay’s internal alarms. To access this display,
follow the Display>Internal Alarms menu path from the main menu. Internal alarms are
those caused by the relay hardware itself. In the figure all of the targets are shown
normal. In View Online mode (see Section 7.7) these targets are continuously updated.
The status of these alarms is also presented on the relay LCD display. See Section
5.7.6.2.
100
iDP-210 Feeder Relay Manual KA2048 520 REV07
101
iDP-210 Feeder Relay Manual KA2048 520 REV07
NOTE
For more complete descriptions of the Recloser Inputs and Recloser Outputs, see S165-210-2, Idea
Workbench Programming Guide.
102
iDP-210 Feeder Relay Manual KA2048 520 REV07
On the left is a phasor display that will show the phasors of the bus and line voltages used
to determine synchronization. On the right are a series of blocks that will show their
contents if appropriate. For example, either the “Sync Check is NOT running.” or the
“Sync Check IS running.” box will appear, but never both. From top to bottom, these
blocks are described in Table 7-2.
This display is useful only during event playback, when using the Virtual Test Set, or when
in Online-View mode. The display will appear as shown in Figure 8-31 when in Online
View mode.
103
iDP-210 Feeder Relay Manual KA2048 520 REV07
Synch Check is NOT running. Displayed when the sync-check element is NOT running.
Hot Bus Voltages The bus (phase side voltages) is hot as defined by the
29:59Hot7 setting.
Hot Line Voltage The line (synch side) voltage) is hot as defined by the
29:59Hot7 setting.
Dead Bus Voltages The bus (phase side voltages) is dead as defined by the
29:27Dead7 setting.
Dead Line Voltage The line (synch side) voltage) is hot as defined by the
29:27Dead7 setting.
Close Prohibited due to Anti-Motoring (Voltage The line and bus voltages are such that motoring will occur
level) when the breaker is closed.
Close Prohibited due to Anti-Motoring (Slip The slip between the line and bus frequencies is such that
Polarity) motoring will occur when the breaker is closed.
Close Prohibited due to Anti-Motoring (Angle The angle between the line and bus voltages are such that
Polarity) motoring will occur when the breaker is closed.
Static Angle Close Prohibited The angle between the bus and line voltages exceeds the
(Angle not in Limits) 25:SAngle7 setting.
Static Angle Close Prohibited The slip between the bus and line voltages exceeds the
(Slip not in Limits) 25:SSlip7 setting.
Close Prohibited (Bus frequency not in limits) The bus frequency is below the 25:81UFB7 or above the
25:81OFB settings.
Close Prohibited (Line frequency not in Limits) The line frequency is below the 25:81ULB7 or above the
25:81OLB7 settings.
Anticipatory Close Prohibited (Slip not in Limit) The expected slip when using the anticipatory close logic
is greater than the 25:ASlip7 setting.
Anticipatory Close Prohibited (Anticipated Angle The expected angle between the bus and line voltages
not in limits) when using the anticipatory close logic is greater than the
25:AAngle.
Breaker close is NOT permitted. Displayed when the sync element is running and the
synchronism conditions have not been met.
Breaker close IS permitted. Displayed when the sync element is running and the
synchronism conditions have been met.
Table 7-2 : Description of the Sync-Scope Status Displays
7
See Section 8.7 on page 155 for a detailed description of all settings pertaining to the sync-check function.
104
iDP-210 Feeder Relay Manual KA2048 520 REV07
105
iDP-210 Feeder Relay Manual KA2048 520 REV07
106
iDP-210 Feeder Relay Manual KA2048 520 REV07
By selecting the fewest and most appropriate metering forms at a high sample rate, a
large amount of metering data can be acquired to determine the cause of many line and
power quality issues.
1. Select Data Profiler dialog box from the Display menu as shown in Figure 7-34. The
Data Profiler dialog as shown in Figure 7-35 will appear.
2. Click the Configure button to display the Data Profiler Configuration dialog box.
Note: Seven metering options are already configured as the default.
The metering options are listed on the left of the screen. Use the scroll bar to view all
of the options.
The Selected metering options listed on the right side of the dialog are the active
options. A metering option must be listed in this field to be enabled.
Note: If WB Data Profiler (#01):(!) through #10 are selected, they must be configured
in the IDEA Workbench via the Workbench Outputs Tool box>Data Profiler menu.
Drive the output with any analog input from the Workbench Inputs menu. Refer to
S165-210-2, iDP-210 Workbench Programming Guide, for additional information.
Refer to Figure 7-36.
107
iDP-210 Feeder Relay Manual KA2048 520 REV07
3. Select metering options. Click the desired metering option in the Available list, then
click ADD >> or double-click the metering option in the Available list.
Note: To remove a metering option from the selected list, click on the metering
option, then click << Remove.
4. Set the date the recordings are to start.
A Trend Time will be given in days and hours when the Continuous feature is
enabled. If 0 Hrs. is displayed, the start/stop times are set before the current date.
Trend Time is the total amount of time the Data Profiler can record. This time will vary
and is dependent on the sample rate and the number of metering options selected.
Note: It is recommended to enable the Continuous feature and note the Trend Time
available.
A. Click the Continuous box if the recordings are not to be stopped. A check mark
appears when enabled.
B. Set the stop date if Continuous is not enabled. Make sure there is enough Trend
Time available.
5. Set the Starting Time of Day the recordings are to begin from the drop down menu.
6. Set the Duration of time the Profiler is to run each day, beginning at the Starting Time
of Day, from the drop down menu.
7. Set the Sampling Interval from the drop down menu. Frequent sampling rates
decrease the amount of Trend Time available.
8. Click OK to return to the Data Profiler screen.
The Data Profiler will display data only after the first sampling interval.
Note: Any altered settings must be downloaded to take effect.
9. Click the Write to File button to save the Data Profiler data.
108
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 7-38: Accessing the MMI Forcing and Dialog Enables Settings dialog
109
iDP-210 Feeder Relay Manual KA2048 520 REV07
7.10.1 Enabling Relay MMI for Control Actions and Setting the Relay Password
From the dialog box shown in Figure 7-39 it is possible to control whether the following
actions may be performed from the front panel of the relay:
• Operate the circuit breaker.
• Momentarily force the state of any contact input.
• Momentarily force the state of any contact output.
This dialog box also provides the ability to change the password which must be entered
through the relay’s MMI to make setting changes. The settings available in this dialog box
are described in the following table.
110
iDP-210 Feeder Relay Manual KA2048 520 REV07
7.10.2 Controlling the Operation of the Circuit Breaker from Within ProView
To enable ProView to operate the breaker, the 52E:Dialog setting box must be checked
(enabled). This checkbox is accessed from the Settings>Relay Behavior>MMI Force and
Dialog Enables menu path.
Once the 52E:Dialog setting is enabled, it is possible to operate the breaker via the
Control Power Circuit Breaker dialog. This is accessed from the Display>Power Circuit
Breaker menu path. See Figure 7-40. This brings up the dialog box shown in Figure
7-41.
111
iDP-210 Feeder Relay Manual KA2048 520 REV07
This dialog presents the user with important status information to assist in making the
decision whether or not to operate the breaker. This information includes phase currents,
breaker 52a or 52b status (as set in the Settings>General Systems Settings Dialog), key
relay output contact statuses, and whether or not Trip/Close is enabled.
In addition, a button in this dialog box provides direct Go Online/Go Offline functionality.
It is also possible to operate the breaker from the Application Diagram screen. See
Section 7.8.1.
112
iDP-210 Feeder Relay Manual KA2048 520 REV07
8.1 Introduction
The iDP-210 scheme provides comprehensive protection, control, and monitoring for
feeders.
The iDP-210 offers the following protection functions:
Three Phase Overcurrent Protection:
One inverse time overcurrent element plus three zones of instantaneous overcurrent
elements. Low and medium set elements are equipped with timers for definite-time
operation.
Residual Overcurrent Protection:
One inverse time overcurrent element plus three zones of instantaneous overcurrent
elements. Low and medium set elements are equipped with timers for definite-time
operation.
Negative Sequence Overcurrent Protection:
One inverse time overcurrent element plus three zones of instantaneous overcurrent
elements. Low and medium set elements are equipped with timers for definite-time
operation.
Directional Torque Control:
All overcurrent elements can individually be setup with torque control to trip for faults
in the forward or reverse direction.
Multiple-Shot Reclosing:
Four-shot programmable reclosing with individual timers is provided. The reclosing
logic allows for selective reclose initiate and cancel commands based on the tripping
element. Sequence coordination with downstream devices is also provided.
Sync-Check Element:
A sync-check element equipped with “Hot bus-Dead line”, “Dead bus-Hot Line”,
“Dead bus-Dead line” and “Hot bus-Hot line” logic is provided.
Frequency Based Load Shedding and Restoration:
Five levels of underfrequency load shedding with individual timers are provided. The
underfrequency elements can be setup with voltage and/or current supervision.
The restoration logic, if enabled, allows for restoration of the feeder when the voltage
and frequency come back within acceptable limits. A separate underfrequency alarm
level is also provided.
Voltage Elements:
Three levels of definite-time over/under voltage elements, one negative-sequence
overvoltage element, and one zero-sequence overvoltage element are provided.
Cold Load Pickup Detection:
Truncates the overcurrent elements below a set point during cold load pickup
conditions.
113
iDP-210 Feeder Relay Manual KA2048 520 REV07
114
iDP-210 Feeder Relay Manual KA2048 520 REV07
The dialog box provides access to Write, Read or View various file types.
• Write buttons: These write the appropriate settings to an ASCII text file. This allows a
group of settings to be created and distributed to a remote location by e-mail or floppy
diskette.
• Read buttons: These read the designated setting text file. This overwrites any
settings currently in the computer’s memory.
• View buttons: These will open the designated settings files using the default editor set
up in Windows to open files ending with the “.txt” extension. This is usually either
Microsoft Notepad or Wordpad.
The following file types may be written, read or viewed:
• Core Protection Settings: This file contains all the protection-related settings for the
relay.
• Idea Workbench Settings: This file contains all the settings relating to and created by
the user regarding custom logic in the IDEA Workbench.
• Comm Related Settings: This file contains all the settings relating to and created by
the user regarding communications in the Communications Workbench.
• Simulation Settings: This file contains all of the settings related to the Virtual Test Set.
See Section 9 for more information on the Virtual Test Set.
• All Settings: This file contains all of the above.
115
iDP-210 Feeder Relay Manual KA2048 520 REV07
116
iDP-210 Feeder Relay Manual KA2048 520 REV07
The lower section of the dialog shows the names of the eight available setting groups. If it
is desired to change the name of one or more setting groups, a button is provided at the
bottom of the dialog to take you directly to the Select Setting Group Names dialog. See
Section 9.3.3 for more information on this dialog.
117
iDP-210 Feeder Relay Manual KA2048 520 REV07
118
iDP-210 Feeder Relay Manual KA2048 520 REV07
119
iDP-210 Feeder Relay Manual KA2048 520 REV07
120
iDP-210 Feeder Relay Manual KA2048 520 REV07
121
iDP-210 Feeder Relay Manual KA2048 520 REV07
8
If the over-current elements use the 50/51 function naming convention, then when used as directional elements, the names are
misleading and the additional care taken when using directional elements may be more easily forgotten. The use of the 67
(directional overcurrent) naming convention is also misleading when the elements are used in a non-directional fashion, but since
67 elements generally require more attention to set properly, the use of the 67 naming convention is felt to be more conservative.
122
iDP-210 Feeder Relay Manual KA2048 520 REV07
123
iDP-210 Feeder Relay Manual KA2048 520 REV07
Follow the Settings>Overcurrent>Fault Detector Settings menu path to open the dialog
box as shown in Figure 8-10.
The iDP-210 relay has three instantaneous overcurrent elements that are used exclusively
to assist in determining the type of fault, if any, that is present on the power system, hence
the reason they are called “fault detector elements.” There is one element each for
positive, negative and zero sequence current. These pickup settings for these elements
are called 46PFD, 46QFD and 46NFD respectively.
Most importantly these elements are involved in:
determining which directional elements to enable during fault conditions;
supervision of the load encroachment logic since load encroachment is valid only for
balanced three phase conditions; and
enabling of the fault location algorithm.
Setting these elements improperly can result in variety of unexpected operations.
In previous releases of the iDP-210 software, these elements had to be set by hand. New
in this release of the iDP-210 is the option to have the relay automatically set them based
on the settings of the other overcurrent elements in the relay. This autoset option is
selected by default in the iDP-210.
NOTE: The autoset feature as described in the following section will only work if at least
one corresponding normal overcurrent element is enabled. For example, if none of the
negative sequence overcurrent elements are enabled, then the negative sequence fault
detector (46QFD) must still be set manually. This is also true for the positive and zero-
sequence fault detectors.
124
iDP-210 Feeder Relay Manual KA2048 520 REV07
The directional phase overcurrent elements, 67P, must be able to trip directionally for
either balanced or unbalanced faults. The 46PFD element must be set such that it picks
up for the lowest-current magnitude three-phase fault that is desired to be treated as a
three-phase fault by the 67P elements.
The 46NFD and 46QFD elements must be similarly set such that they pick up for the
lowest-current magnitude single-phase and phase-to-phase faults which are desired to be
treated as single-phase and phase-to-phase unbalanced faults by the 67P elements.
Additionally, the 46NFD and 46QFD settings must be high enough that they do not pick up
for system unbalance or for any actual three-phase fault for which the 67P elements are
required to trip. If not so coordinated, the 46NFD or 46QFD elements will pick up when
they shouldn't, resulting in possible erroneous directionality decisions.
8.5.1.2.2 Automatic Setting of Fault Detector Elements
By default, the Fault Detector elements will automatically be set to be equal to the
minimum pick-up value of any related enabled settings multiplied by the value of the
46FDRatio setting. This setting can be set from 0.8 to 1.0, with the default at 1.0.
Specifically:
The positive sequence fault detector 46PFD, will be set to be equal to the minimum of the
pickup values of these enabled elements, multiplied by the value of 46FDRatio:
• Phase time overcurrent pickup element, pickup value setting 67P:PU
• Phase low set definite overcurrent element, pickup value 67PL
• Phase medium set definite overcurrent element, pickup value 67PM
• Phase instantaneous (high set) overcurrent element, pickup value 67PH
The negative sequence fault detector 46QFD, will be set to be equal to the minimum of the
pickup values of these enabled elements, multiplied by the value of 46FDRatio:
• Negative sequence time overcurrent pickup element, pickup value setting
67Q:PU
• Negative sequence low set definite overcurrent element, pickup value 67QL
• Negative sequence medium set definite overcurrent element, pickup value 67QM
• Negative sequence instantaneous (high set) overcurrent element, pickup value
67QH
The zero sequence fault detector 46NFD, will be set to be equal to the minimum of the
pickup values of these enabled elements, multiplied by the value of 46FDRatio:
• Zero sequence time overcurrent pickup element, pickup value setting 67R:PU
• Zero sequence low set definite overcurrent element, pickup value 67RL
• Zero sequence medium set definite overcurrent element, pickup value 67RM
• Zero sequence instantaneous (high set) overcurrent element, pickup value 67RH
125
iDP-210 Feeder Relay Manual KA2048 520 REV07
126
iDP-210 Feeder Relay Manual KA2048 520 REV07
The “Details…” box at the bottom of the setting window displays the setting range for the
selected element. Place the cursor in a settings box to view the setting range for that
element.
The setting window also displays the selected setting group.
127
iDP-210 Feeder Relay Manual KA2048 520 REV07
The Definite Time Overcurrent settings available in this dialog box are:
The Inverse Time Overcurrent settings available in this dialog box are:
128
iDP-210 Feeder Relay Manual KA2048 520 REV07
129
iDP-210 Feeder Relay Manual KA2048 520 REV07
The Definite Time Overcurrent settings available in this dialog box are:
The Inverse Time Overcurrent settings available in this dialog box are:
130
iDP-210 Feeder Relay Manual KA2048 520 REV07
SEL-U5
User Defined
Pickup 0.025 to 90 sec. amperes
Time dial 0.1 to 10
Torque control: None, Forward, or Reverse
Reset mode: Instantaneous or Disk-like
Definite time knee (flat) 4 – 40 times pickup
131
iDP-210 Feeder Relay Manual KA2048 520 REV07
The Definite Time Overcurrent settings available in this dialog box are:
132
iDP-210 Feeder Relay Manual KA2048 520 REV07
The Inverse Time Overcurrent settings available in this dialog box are:
⎛ A ⎞
T t = TD × ⎜ P + B⎟
⎝M -1 ⎠
When Disk-like reset is selected for the IEEE curve shapes, the reset time is determined
by the following formula:
⎛ C ⎞
Tr = TD × ⎜ 2 ⎟
⎝ M -1 ⎠
Where:
M = Multiples of pickup
TD = Time dial setting
Curve Type A B P C
IEEE MI 0.0515 0.114 0.02 4.85
IEEE VI 19.61 0.491 2.0 21.6
IEEE EI 28.2 0.1217 2.0 29.1
IEC-A 0.14 0 0.02 --
133
iDP-210 Feeder Relay Manual KA2048 520 REV07
Curve Type A B P C
IEC-B 13.5 0 1.0 --
IEC-C 80.0 0 2.0 --
IEC-D (LI) 120.0 0 1.0 --
IEC-E (SI) 0.05 0 0.04 --
SEL-U1 0.0104 0.0226 0.02 1.08
SEL-U2 5.95 0.18 2 5.95
SEL-U3 3.88 0.0963 2 3.88
SEL-U4 5.67 .0352 2 5.67
SEL-U5 .00342 .00262 0.02 0.323
The inverse time characteristic curves follow the above equation until a user selectable
maximum multiple of pickup is reached, at which point the curves change to a definite time
characteristic. This multiple of pickup may be set between 4 and 40.
The user programmable curves are dependent on the Setting Group. The curves are
programmed within the appropriate Phase, Ground, or Negative Sequence settings
windows. Refer to Figure 8-17 for example of customized curve parameter settings.
134
iDP-210 Feeder Relay Manual KA2048 520 REV07
IEEE MI (Curve 1)
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
the contact output operation delay as follows:
100
Solid state outputs (SS) contact operation delay: 1 msec maximum
All mechanical outputs (CO) contact operation delay: 5 msec maximum
Pickup delay (non-directional): 1 cycle maximum
Pickup delay (directional): 1 ½ cycle maximum
Time in Seconds (T)
10
10
7
5
Time Dial
1
1
0.5
0.1
0.1
0.01
1 10 100
Multiples of Pickup (M)
135
iDP-210 Feeder Relay Manual KA2048 520 REV07
IEEE VI (Curve 2)
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
the contact output operation delay as follows:
100
Solid state outputs (SS) contact operation delay: 1 msec maximum
All mechanical outputs (CO) contact operation delay: 5 msec maximum
Pickup delay (non-directional): 1 cycle maximum
Pickup delay (directional): 1 ½ cycle maximum
Time in Seconds (T)
10
10
Time Dial
1
0.5
0.1
0.1
0.01
1 10 100
Multiples of Pickup (M)
136
iDP-210 Feeder Relay Manual KA2048 520 REV07
IEEE EI (Curve 3)
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
the contact output operation delay as follows:
100
Solid state outputs (SS) contact operation delay: 1 msec maximum
All mechanical outputs (CO) contact operation delay: 5 msec maximum
Pickup delay (non-directional): 1 cycle maximum
Pickup delay (directional): 1 ½ cycle maximum
Time in Seconds (T)
10
10
1 7
5
Time Dial
1
0.1
0.5
0.1
0.01
1 10 100
Multiples of Pickup (M)
137
iDP-210 Feeder Relay Manual KA2048 520 REV07
IEC A (Curve 4)
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
100
10.0
7.0
10
Time in Seconds (T)
5.0
3.0
2.0
Time Dial
1.0
1 0.5
0.3
0.2
0.1
0.1 The TCC curves represent the protection element timing only. The timing tolerance
on the TCC curves is ±10% and ±1 cycle. The total response time of relay includes
this timing plus the pick up delay and the contact output operation delay as follows:
0.01
1 10 100
Multiples of Pickup (M)
138
iDP-210 Feeder Relay Manual KA2048 520 REV07
IEC B (Curve 5)
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
the contact output operation delay as follows:
100 Solid state outputs (SS) contact operation delay: 1 msec maximum
All mechanical outputs (CO) contact operation delay: 5 msec maximum
Pickup delay (non-directional): 1 cycle maximum
Pickup delay (directional): 1 ½ cycle maximum
Time in Seconds (T)
10
10.0
7.0
5.0
1
2.0
Time Dial
1.0
0.7
0.5
0.1 0.3
0.2
0.1
0.01
1 10 100
Multiples of Pickup (M)
139
iDP-210 Feeder Relay Manual KA2048 520 REV07
IEC C (Curve 6)
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The timing
tolerance on the TCC curves is ±10% and ±1 cycle. The total response
time of relay includes this timing plus the pick up delay and the contact
output operation delay as follows:
100 Solid state outputs (SS) contact operation delay: 1 msec maximum
All mechanical outputs (CO) contact operation delay: 5 msec maximum
Pickup delay (non-directional): 1 cycle maximum
Pickup delay (directional): 1 ½ cycle maximum
Time in Seconds (T)
10
10.0
7.0
5.0
1.0
0.7
0.1 0.2 0.5
0.3
0.01
1 10 100
Multiples of Pickup (M)
140
iDP-210 Feeder Relay Manual KA2048 520 REV07
IEC LI
10000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and the
contact output operation delay as follows:
100
10.0
7.0
5.0
10 3.0
2.0
Time Dial
1.0
0.7
0.5
1 0.3
0.2
0.1
0.1
1 10 100
Multiples of Pickup (M)
141
iDP-210 Feeder Relay Manual KA2048 520 REV07
IEC SI
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
100
10.0
7.0
5.0
3.0
Time in Seconds (T)
10
2.0
Time Dial
1.0
0.7
0.5
1 0.3
0.2
0.1
The TCC curves represent the protection element timing only. The
0.1 timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
the contact output operation delay as follows:
0.01
1 10 100
Multiples of Pickup (M)
142
iDP-210 Feeder Relay Manual KA2048 520 REV07
SEL U1
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
100 the contact output operation delay as follows:
10
10
7
1
5
1
Time Dial
0.1
0.5
0.1
0.01
1 10 100
Multiples of Pickup (M)
143
iDP-210 Feeder Relay Manual KA2048 520 REV07
SEL U2
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
the contact output operation delay as follows:
100
Solid state outputs (SS) contact operation delay: 1 msec maximum
All mechanical outputs (CO) contact operation delay: 5 msec maximum
Pickup delay (non-directional): 1 cycle maximum
Pickup delay (directional): 1 ½ cycle maximum
Time in Seconds (T)
10
10
7
1 5
Time Dial
1
0.1 0.5
0.1
0.01
1 10 100
Multiples of Pickup (M)
144
iDP-210 Feeder Relay Manual KA2048 520 REV07
SEL U3
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
the contact output operation delay as follows:
100
Solid state outputs (SS) contact operation delay: 1 msec maximum
All mechanical outputs (CO) contact operation delay: 5 msec maximum
Pickup delay (non-directional): 1 cycle maximum
Pickup delay (directional): 1 ½ cycle maximum
Time in Seconds (T)
10
1 10
7
5
Time Dial
0.1 1
0.5
0.01 0.1
1 10 100
Multiples of Pickup (M)
145
iDP-210 Feeder Relay Manual KA2048 520 REV07
SEL U4
1000
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
the contact output operation delay as follows:
100
Solid state outputs (SS) contact operation delay: 1 msec maximum
All mechanical outputs (CO) contact operation delay: 5 msec maximum
Pickup delay (non-directional): 1 cycle maximum
Pickup delay (directional): 1 ½ cycle maximum
Time in Seconds (T)
10
1
Time
10.0
Dial
7.0
5.0
3.0
0.1
0.5 1.0
0.1
0.01
1 10 100
Multiples of Pickup (M)
146
iDP-210 Feeder Relay Manual KA2048 520 REV07
SEL U5 Curve
100
Curves shown flat at 40 times pickup.
(Adjustable from 4 to 40 times).
The TCC curves represent the protection element timing only. The
timing tolerance on the TCC curves is ±10% and ±1 cycle. The total
response time of relay includes this timing plus the pick up delay and
the contact output operation delay as follows:
10
Solid state outputs (SS) contact operation delay: 1 msec maximum
All mechanical outputs (CO) contact operation delay: 5 msec maximum
Pickup delay (non-directional): 1 cycle maximum
Pickup delay (directional): 1 ½ cycle maximum
1
Time in Seconds (T)
10.0
7.0
5.0
3.0
0.1 2.0
Time Dial
1.0
0.7
0.5
0.3
0.01 0.2
0.1
0.001
1 10 100
Multiples of Pickup (M)
Figure 8-30: SEL U5 Curve TCC
147
iDP-210 Feeder Relay Manual KA2048 520 REV07
8.6 Reclosing
iDP-210 is equipped with a four-shot programmable reclosing element complete with
sequence coordination and synch-check. There are three dialog boxes that control the
action of the recloser. These dialogs and their menu paths are:
• Synch Check (Settings>Sync Check): This controls the functionality of the synch-
check elements.
• Recloser Settings (Settings>Recloser>Recloser Settings): This controls the basic
setup of the reclosing logic, such as the number of shots, sequence coordination, etc.
• Recloser Lockout Action (Settings>Recloser>Recloser/Lockout Action): This dialog
provides the ability to define how each protective element affects the reclose actions.
148
iDP-210 Feeder Relay Manual KA2048 520 REV07
The upper left-hand corner of the Recloser Settings dialog contains a sub-group called
“Reclose Shot Settings”. The variables in this sub-group are described in the following
table.
The “Recloser Miscellaneous” sub-group in the Recloser Settings dialog provides access
to various timers associated with the reclose process. This setting window contains the
following settings:
149
iDP-210 Feeder Relay Manual KA2048 520 REV07
9
A Non-Reclose Close event is anytime a close command is issued through any path other than the reclose logic, regardless of
where it comes from. This specifically includes underfrequency load-shedding restoration, any front panel issued close command,
a close issued via communication with the relay by ProView while in View-Online mode, the IDEA Workbench OR:Non-Reclose
Close, AND:Non-Reclose Close, OR:Control Close and AND:Control Close outputs.
10
Any external close operation not initiated via the front panel or communications should either be initiated via the ci3 input
(designated as the "Close" input), or should at least be indicated to the relay via this input, if the reset timer is desired to be
bypassed.
If the 52a contact input is asserted without indicating that it is an external close operation by assertion of the ci3 input, then the
iDP-210 scheme will run the reset timer before the recloser is reset.
It is intended that the user close the breaker via the front panel MMI or pushbuttons, or otherwise pass any external close initiation
to the contact inputs which are factory-configured for that purpose.
Note the definition of "external close." An "external close" is any close which is commanded to the relay from outside the relay,
whether by contact input, pushbutton, or communications. A closure which occurs without the scheme's ability to observe the
outside command, and without the scheme having initiated it, is not an "external close" by this definition. Thus when it is said that
the relay instantly resets for any "external close," it is implicit that the relay be able to detect the outside command. If the relay
cannot detect the outside command, then this is an anomalous event, and the reset timer will run to completion before the recloser
resets.
150
iDP-210 Feeder Relay Manual KA2048 520 REV07
The iDP-210 reclosing logic provides for fast reclose shots. If fast reclosing is enabled,
then it nominally occurs for all faults for which the High-Set three-phase overcurrent
elements do not trip. Or, alternatively, the conditions for which “fast reclosing” occurs can
be user-programmed from the Idea Workbench by driving the <AND: Enable Fast
Reclose> and <OR: Enable Fast Reclose> Workbench Outputs. See S165-210-2,
Workbench Programming Guide iDP-210 Feeder Protection Control and Monitoring
System for more information.
These settings are found in the “Fast Operations” sub-group of the Recloser Settings
dialog as shown in Figure 8-32. The applicable settings are:
The iDP-210 provides the ability for the user to control how the reclose logic responds in
the presence of various alarm conditions. These settings are found in the “Alarm Condition
Enables” section of the dialog box shown in Figure 8-32.
• Lock Out Reclosing and Inhibit Control Closes when Failure-to-Trip is detected.
• Lock out Reclosing and Inhibit Control Closes when Failure-to-Close is detected.
The applicable settings are:
151
iDP-210 Feeder Relay Manual KA2048 520 REV07
By default, the duration of each open interval during a trip/reclose sequence is pre-
determined according to each reclose shot number. However, you can flexibly extend the
open intervals by driving the <AND:Enable OI Timer> and/or <OR:Enable OI Timer>
outputs in the IDEA Workbench. For more information on the IDEA Workbench, see
Service Manual S165-210-2.
In the default scheme, the open interval timer (79oix) is always enabled. So the open
interval times (79oi1, 79oi2 and 79oi3) will run once the breaker has opened, clearing a
fault in a Trip/Reclose sequence. To alter this behavior, you must first override the default
“enabled” status of the open interval timer, by driving the <AND:Enable OI Timer> outputs
with a logical “zero” signal. Then, drive the <OR:Enable OI Timer> with the logic and
timing functions you require, using a logical “one” when you want the 79oi timer to run, and
a logical “zero” when you want it to reset, or simply pause.
When the <AND:Enable OI Timer> and <OR:Enable OI Timer> outputs are both driven
with a logical zero signal, the open interval timer is always halted, but is thereafter either
reset or simply paused, depending upon the setting of the 79oir variable as is set in the
“Reset or Pause Open Interval Timer” drop down box found in the Recloser Settings
dialog box. Then, once the <OR:Enable OI Timer> output is once again driven with a
logical “one” signal, the 79oix timer’s behavior is as follows, per the 79:oir setting:
79:oir = Pause: The 79oix timer resumes timing from where it was originally paused.
79:oir = Reset: The 79oix timer resets and begins to count from zero.
A common reason for pausing the reclose sequence is when two breakers can operate for
a given fault, and it is desired that one of them always recloses first. In this case, a 52a
contact from the first breaker could drive a contact input on the second breaker’s relay (or,
of course, equivalent information could be exchanged between the two relays via
communications means). In the IDEA Workbench of the second relay, the contact input
could be connected to drive both the <AND:Enable OI Timer> and <OR:Enable OI Timer>
outputs with a logical “zero” while the first breaker is open, forcing a pause in the second
breaker’s reclose sequence. After the first breaker recloses, its 52a contact would assert,
resulting in turn in the assertion of the <AND:…> and <OR:…> Workbench output signals,
thereby allowing continuation of the reclose sequence on the second breaker.
152
iDP-210 Feeder Relay Manual KA2048 520 REV07
153
iDP-210 Feeder Relay Manual KA2048 520 REV07
11
The Setting Code column indicates the value of the setting in the ASCII settings file. For example, if the value for a particular
Recloser/Lockout Action setting is set to 4, then the when the element operates, it will always result in a lockout (the action
programmed is “L L L L”).
154
iDP-210 Feeder Relay Manual KA2048 520 REV07
8.7 Sync-check12
The Sync-Check function in the iDP-210 is quite sophisticated and provides the following
features:
A programmable Operator Window govern the time window after a front panel or
ProView-based Control Close is initiated during which the iDP will look for a closing
opportunity. This requires the user to be aware of synch—conditions (e.g., by using
the Synch-Scope view, see page 103) for those applications like distributed
generation, where extra security against out-of-synch close is especially valued
Anticipatory Close accounts for the time it takes the circuit breaker mechanism to
actually close once sent a CLOSE command.
12
For more information on the behavior of the frequency element algorithms used for sync-check, see Section 13.6, “Behavior of
Frequency Measuring Elements” on page 219.
155
iDP-210 Feeder Relay Manual KA2048 520 REV07
Anti-motoring control assures that sync-check will be declared only when the resulting
power flow will be in the specified direction.
Sync against voltages of different PT ratios and different nominal phase angle
displacements (delta vs. wye).
Anti-pump logic
To access the synch-check element settings, follow the Settings>Sync Check menu path
as shown in Figure 8-36. This will open the Sync Check settings dialog as shown in
Figure 8-37.
156
iDP-210 Feeder Relay Manual KA2048 520 REV07
The sync-check element is provided with Hot Bus-Dead Line, Dead Bus-Hot Line, Dead
Bus-Dead Line and Hot Line-Hot Bus logic. In most relays, the Bus side is defined as the
side where three phase voltage inputs are provided. The Line side has a single-phase
voltage signal. In the iDP-210 it is possible to define if the three-phase voltage input side
should be referred to as the Bus or the Line side using the 25:V3P:Loc setting.
It is possible to select which phase of the three-phase voltage side is compared against
the single-phase voltage side. Note the following definitions of hot and dead buses.
• Dead 3-phase side = ALL “3-phase-side” voltages are equal to or below the
25:27Dead setting.
• Hot 3-phase side = ANY of the “3-phase-side” voltages are equal to or above the
25:27Hot setting.
• Dead 1-phase side = The “1-phase-side” voltage is equal to or below the 25:27Dead
setting.
• Hot 1-phase side = The “3-phase-side” voltage is equal to or above the 25:27Hot
setting.
If the bus voltage is above the 25:27Dead setting, then Dead-Line-Dead Bus and Hot-
Line-Dead Bus closes will be inhibited. If the bus voltage is below the 25:59Hot setting,
then Dead-Line-Hot Bus and Hot-Line-Hot-Bus closes will be inhibited. So if the bus
voltage is in between the 25:27Dead and 25:59Hot settings, all closes will be inhibited.
All settings are made in reference to the voltages on the side of the breaker having the 3-
phase PTs.
Normally, having the bus voltage in between the 25:27Dead and 25:59Hot settings defines
an abnormal bus voltage or measurement. In this case of a “not-hot and not-dead” bus
condition, the iDP-210 is designed to avoid closing the breaker. If this precautionary
behavior is not desired, then set 25:27Dead = 25:59Hot at some compromise mid-nominal
value. This will ensure that the bus is always either strictly dead or strictly hot and never in
an indeterminate state.
8.7.1.2 Voltage Phase Determination
Depending upon the location of PTs on the power system, it may be possible that the
single phase PT used for synch-check may have a different turns ratio that the bus PTs, or
may even be connected differently (delta for the line side compared to wye for the bus). To
accommodate such variations, the synch-check function provides two additional settings.
The nominal turns ratio of the VS PT input is determined by the Nom:VSSec setting. Any
phase angle difference that may be desired to be entered is made via the 25:VS:Rotate
setting. Note that all other synch-check settings are made in reference to the voltages on
the side of the breaker having the 3-phase PTs.
157
iDP-210 Feeder Relay Manual KA2048 520 REV07
The iDP sync-check system has two key logic subsystems for supervising synchronous
closure; one for static angle closure and another for anticipatory angle closure. The
subsystems are not mutually exclusive, but operate in parallel instead. The static angle
subsystem runs when the measured slip rate is less than (25:SSlip) Hz/sec, while the
anticipatory angle subsystem runs when the measured slip rate is less than (25:ASlip)
Hz/sec. Either subsystem can grant permission for breaker closure, providing the
measured slip rate (and other voltage-related measurements, as described below) are
within their respective set limits.
If the slip is less than the 25:Aslip setting, the relay checks if the anticipated angle
upon closing of the breaker will be less than or equal to the Max Anticipated Angle
setting, (25:AAngle). The Synch-check function takes in to account the frequency slip
rate and the Breaker Closure Time as defined by the 25:BCT setting. The Close
output contact will assert (25:BCT) seconds before the breaker angle passes most
closely to zero based upon the currently measured slip rate, assuming zero slip
acceleration.14
4. Assuming bus/line voltages are hot, and bus/line frequencies are within the 25:81
OFB, OFL, UFB, and UFL setting limits, then the relay checks to see if the anticipated
and real-time measured angles stay less than 25:SAngle degrees and the slip rate
remains below 25:Sslip Hz, all for 25:62 setup seconds. If these conditions are met,
then closure is permitted via the Static Angle Closure logic.
5. If anti-motoring is enabled through the 25:E:AMotor setting, the sync-check system
verifies that either the bus or line voltage frequency is higher (as appropriate) than the
other side upon closure initiation, and that the corresponding anticipated angle upon
closure is zero+, to ensure that incoming generation will not motor upon closure.
13
Frequency and Slip measurement functions employ an approximation of the positive sequence on the 3-phase voltage side.
14
In any event, the synch-check function does not allow an anticipatory close initiation when the angle of the voltage across the
open breaker is increasing. Effectively, this means that an anticipatory closure cannot be initiated when leading the zero angle
condition by more than 180 degrees.
158
iDP-210 Feeder Relay Manual KA2048 520 REV07
If the same Operator Window functionality as described in this section is desired for the
CLOSE button on the front of the IdeaPLUS hardware, then a separate output contact of
the IdeaPLUS relay hardware should be wired electrically in series with the CLOSE output
of the IDEA PLUS hardware. This additional contact should be programmed in the Idea
Workbench to be controlled by the <79:Close Breaker> signal. See the Idea Workbench
manual for the IDP-210 relay, publication S165-210-2, Appendix C, for more information.
The proper DC wiring diagram for this configuration is shown on page 34 of this manual.
8.7.1.4.1 General Description
The (25:62OWmax) and (25:62OWmin) settings govern the maximum and minimum time
windows after a Control Close is initiated during which the IDP-210 will look for a closing
opportunity. These settings have no affect on automatic close attempts made by the
reclose logic. Control Close events are:
The user pressing the front-panel Close button (not the CLOSE button on the
IdeaPLUS – see Caution note above).
The user clicking on the Close button in ProView while the relay is connected to a
PC.
A Close request arriving via communications (DNP 3.0, Modbus, etc.)
A Close request made by asserting the dedicated CLOSE contact input on the
relay rear panel.
A Close request made in the Idea Workbench using the <AND:Control Trip> or
<OR:Control Trip> Workbench Output signals.
If sync-check is enabled, then the iDP-210 will wait during this window for synchronism to
occur. If synchronism is not detected during the window, then the user must re-initiate a
Control Close to try again (for example, release and then press the Close pushbutton
again).
Example:
Say that (25:62OWmax) is 5 seconds, and (25:62OWmin) is 2 seconds. Then...
If the operator presses the Close button for only 1 second, then the relay will look for a
closing opportunity (waiting for sync-check permission if sync-check is enabled) for 2
seconds - not 1 second only.
If the operator presses the Close button for 3 seconds, then the relay will look for a
closing opportunity for exactly 3 seconds.
If the operator presses the Close button for 10 seconds, then the relay will look for a
closing opportunity for 5 seconds only - not 10 seconds.
159
iDP-210 Feeder Relay Manual KA2048 520 REV07
This synch-check setting dialog box shown in Figure 8-37 contains the following settings:
160
iDP-210 Feeder Relay Manual KA2048 520 REV07
161
iDP-210 Feeder Relay Manual KA2048 520 REV07
162
iDP-210 Feeder Relay Manual KA2048 520 REV07
163
iDP-210 Feeder Relay Manual KA2048 520 REV07
164
iDP-210 Feeder Relay Manual KA2048 520 REV07
The Reverse Power Element dialog box contains the following settings:
165
iDP-210 Feeder Relay Manual KA2048 520 REV07
• One or more phase voltages are below the 27FF setting for at least 27FF:62P
seconds AND…
• Current is flowing in one or more phases OR voltage above the 59FFR setting level is
present on one or more phases.
Once declared, a fuse fail condition is only reset once all three phase voltages remain
above the 59FFR setting for at least 59FFR:3P:62P seconds.
166
iDP-210 Feeder Relay Manual KA2048 520 REV07
167
iDP-210 Feeder Relay Manual KA2048 520 REV07
168
iDP-210 Feeder Relay Manual KA2048 520 REV07
15
For more information on the behavior of the frequency element algorithms, see Section 13.6, “Behavior of Frequency Measuring
Elements” on page 219.
169
iDP-210 Feeder Relay Manual KA2048 520 REV07
170
iDP-210 Feeder Relay Manual KA2048 520 REV07
171
iDP-210 Feeder Relay Manual KA2048 520 REV07
172
iDP-210 Feeder Relay Manual KA2048 520 REV07
173
iDP-210 Feeder Relay Manual KA2048 520 REV07
16
Note the subtle difference between the 79:62ftt and 79:62stt settings. The former stops timing on the cessation of current flow
through the breaker, and the latter stops when the mechanism says it is open. The 79:62ftt is designed to properly indicate a fail to
clear regardless of what the 52 circuit indicates, making it immune to a bad mechanism or defective 52 circuit. The 79:62stt is better
used for early warning of mechanism or wiring problems.
174
iDP-210 Feeder Relay Manual KA2048 520 REV07
17
US Patent 6,198,401
175
iDP-210 Feeder Relay Manual KA2048 520 REV07
Note that current limiting fuse operations may occasionally generate a waveform that will
be counted by the ICSF detector. However, these events will be very limited in number
compared to the number of counts that will occur prior to an actual cable splice failure.
6
August 06, 1995 at 09:38:33
5
4
Current [kA ]
3
2
1
0
-1
Phase B
-2
0 20 40 60 80 100
Time [mS]
35
30
Fault Occurances
25
20
15
10
5
0
Time (pu)
To access the Incipient Cable Splice Fault settings, follow the Settings>Incipient Cable
Splice Fault Logic menu path as shown in Figure 8-50. This will open the settings window
shown in Figure 8-51.
Figure 8-50: Opening the Incipient Cable Splice Fault Detection Setting Window
176
iDP-210 Feeder Relay Manual KA2048 520 REV07
The settings available in this dialog box are described in the table below.
177
iDP-210 Feeder Relay Manual KA2048 520 REV07
The load encroachment elements are plotted on a power plane. As shown in the figure,
the following reference points are defined as:
• FS = the maximum MVA level which is supplied to the feeder.
• FQP1 = the maximum positive reactive power at the minimum forward load, in
per unit of FS.
• FQP2 = the maximum positive reactive power at the maximum forward load, in
per unit of FS.
• FQN1 = the maximum negative reactive power at the minimum forward load, in
per unit of FS.
178
iDP-210 Feeder Relay Manual KA2048 520 REV07
• FQN2 = the maximum negative reactive power at the maximum forward load, in
per unit of FS.
As the maximum allowable MVA level to serve the feeder is increased, the radius of the
right-sided semi-circle is increased to the right.
• RS = the maximum MVA level which is ‘received’, being sent from the other ends
of the feeder to the local breaker. Examples would be for a looped feeder circuit,
or a feeder with attached co-generation.
• RQP1 = the maximum positive reactive power at the minimum reverse load, in
per unit of RS.
• RQP2 = the maximum positive reactive power at the maximum reverse load, in
per unit of RS.
• RQN1 = the maximum negative reactive power at the minimum reverse load, in
per unit of RS.
• RQN2 = the maximum negative reactive power at the maximum reverse load, in
per unit of RS.
As the maximum allowable MVA level to serve local loads is increased, the radius of the
left-sided semi-circle is increased to the left.
The load encroachment settings are accessed from Settings>Load Encroachment menu
path shown in Figure 8-53 The Load Encroachment settings window is shown in Figure
8-54.
179
iDP-210 Feeder Relay Manual KA2048 520 REV07
180
iDP-210 Feeder Relay Manual KA2048 520 REV07
181
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 8-55: Menu path to access Cold Load Pickup Setting Window
The pickup setting of all low set definite time elements, 67PL, 67NL and 67QL, are
multiplied by the CL:Multiplier setting. The settings of the medium and high set definite
time elements (67PM, 67PH, 67NM, 67NH, 67QN and 67QH) are not affected by the cold
load logic.
Note: Cold load pickup logic may be disabled by setting the CL:Duration:62D timer to zero
(0). This explicitly disables the logic. See Figure 8-57.
182
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 8-57: Cold Load Pickup Logic for Time Overcurrent Elements
Trip Time
100
Thin Curve is the
portion of the curve
for which operation
is restrained.
10 Tripping
Time (seconds)
Figure 8-58: Effect of Cold Load Pickup Setting CL:Multiplier on Time Overcurrent
Elements
183
iDP-210 Feeder Relay Manual KA2048 520 REV07
I Demand = I Peak (1 − e −t / τ )
Where the time constant τ is defined by the value of the demand interval setting, Dmd-Int,
such that, starting from t=0 and IDemand = 0, at a time equal to the Dmd-Int setting, IDemand
reads 90% IPeak.
Thus;
Dmd _ Int * 60
τ =− = 26.0577 * Dmd _ Int
ln (0.1)
To access these settings follow the Settings>Demand Meter Settings menu path as
shown in Figure 8-59. This will open the dialog box shown in Figure 8-60.
184
iDP-210 Feeder Relay Manual KA2048 520 REV07
185
iDP-210 Feeder Relay Manual KA2048 520 REV07
NOTE:
If the mode status is changed from within ProView when not in View Online mode, the change will occur
immediately. If the mode status is changed from within ProView when View Online mode is active, the
status change may take as long as 20 seconds to occur and be confirmed in the dialog. This delay is the
result of the amount of data traffic occurring between the relay and ProView when in View Online mode.
Figure 8-61: Menu Path for Accessing the Status of Non-Volatile Modes Dialog
186
iDP-210 Feeder Relay Manual KA2048 520 REV07
0 in a green
field is
displayed if
status is
NOT set.
1 in a red
field is
displayed if
the status IS
set.
187
iDP-210 Feeder Relay Manual KA2048 520 REV07
188
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 8-64: Menu Path to Control External Alarm Output Contact Behavior
189
iDP-210 Feeder Relay Manual KA2048 520 REV07
190
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 9-1: Accessing the Fixed Fault Setup Dialog for the VTS
191
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 9-2: The Fixed Fault Setup Dialog for the VTS
The drop down box at the top of the dialog permits the user to select whether the fixed
phasors as defined in the dialog box, or the computed phasors resulting from the model
method, will be used during the VTS event. In this figure, the dialog indicates the model
derived phasors will be used.
The settings are divided in to three sections. From left to right they are the voltage and
currents during the pre-fault, fault, and post fault periods. Note that there are no currents
to define for the post fault period as it is assumed the breaker has cleared the fault. The
time duration of the pre-fault period is defined in the Fault Dynamics Settings dialog box.
See Section Error! Reference source not found.
The voltage VAy is the single phase voltage appearing on the opposite side of the breaker
and is usually used for synch-check applications.
The control of the timing of when the VTS switches from the pre-fault, fault, and post-fault
periods is provided in the Fault Dynamics dialog. See Section Error! Reference source
not found..
192
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 9-4: The Model Fault Setup Dialog for the VTS
193
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 9-5: The Fault Model Results Dialog for the VTS
Vs Vr
ZS0 ZL0 ZR0
ZS1 ZL1 ZF ZR1
ZS2 ZL2=ZL1 ZR2 Vs
Power Angle
Relay Vr
The Model Fault Setup dialog box has a group of variables gathered in the Fault Setup
sub-group. The variables are:
18
All impedances entered in Ohms secondary.
194
iDP-210 Feeder Relay Manual KA2048 520 REV07
“System Setup” is the next sub-group down the dialog. This section contains all of the
settings necessary to define the system impedance characteristics. Note that all
impedances are specified as being in per unit. The actual base unit is not important, just
that all quantities are on the same base.
19
All impedance values are in Ohms-secondary.
195
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 9-7: Accessing the Fault Dynamics Setup Dialog for the VTS
196
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 9-8: The Fault Dynamics Setup Dialog for the VTS
The settings available in this dialog are used for two purposes. The first is to control the
pre-fault, fault and post fault transitions. The second is to simulate system frequency shifts.
This is used primarily to test load shedding schemes or other schemes that utilize the iDP-
210’s frequency elements. These settings are:
197
iDP-210 Feeder Relay Manual KA2048 520 REV07
198
iDP-210 Feeder Relay Manual KA2048 520 REV07
199
iDP-210 Feeder Relay Manual KA2048 520 REV07
To Read a Simulation Settings file, click on the Read Simulation Settings from Disk
button. This brings up a standard Windows Open File dialog box. Select the file desired
to read. At this point the file will be opened with the settings in this file will overwrite any
settings in the existing Fixed Fault Setup, Model Fault Setup, and Fault Dynamics settings
dialogs.
To prepare the PC for the simulation, click on the initialize button marked Init . If the
scheme is not ready, a progress bar will appear advising the status of the preparation
process. When ready, the Simulation Toolbar will re-appear.
At this time the simulation may be run. It is best to run the simulation while viewing a
screen displaying oscillography, the Application Diagram, the synch-scope, the IDEA
Workbench, target displays, etc. The entire system becomes “live” during event playback
just as if the PC were connected to a relay in View Online mode.
As an example, and to better demonstrate the manner in which the VTS operates, open
an oscillography window that shows the analog parameters. Each click on the Step button
will play into the system one data point for each voltage and current. The data points
represent simulated output from the relay’s analog input channels. After opening one of
these windows, LEFT CLICKING on the Step button a few times will result in a screen
similar to that shown in Figure 9-11 in which we have opened the Waveforms and
Symmetrical Components window.
Pressing the FreeRun button will result in the VTS to continuously generate signals until
an event record is generated. At this time a PC Event will have been created which can be
saved to disk and reloaded at any time. All event playback features will be available. See
Section 7.5 for more information on loading event records and event playback.
200
iDP-210 Feeder Relay Manual KA2048 520 REV07
201
iDP-210 Feeder Relay Manual KA2048 520 REV07
10 Test Procedure
The intent of this test procedure is to verify that the relay hardware is properly functioning.
These tests are to be run on the relay with the factory default scheme and settings.
1.1. Apply power to the relay in accordance with its auxiliary power supply rating.
1.2. Verify the relay briefly flashes all front panel LEDs.
1.3. Verify that after approximately 5 seconds the LCD displays the root menu.
2.1. Apply balanced 3-phase voltage and 3-phase current inputs, at nominal system frequency, to
the phase and voltage inputs. Apply an AC current signal to the IN (4th current0 input channel.
2.3. Scroll down to the Metering line and press the ENTER button.
2.4. Scroll down to the SEC AMPS, VOLTS, DEG line and press the ENTER button.
2.5. Verify the measured current and voltage signal magnitude and phase angles match those
applied.
3. Verify Contact Output Operation: Verify all contact outputs properly show as being in their “default”
open or closed states and operate properly when closed as follows:
3.2. Scroll down to the Contact Outputs line and press ENTER. This will now show the status of
contact output ss1 as being equal to 0. The display will look like the following:
> 0=ss1
User ss1 Description
Contact Output
Next Prev Enab forc
F1 F2 F3 F4
3.3. Apply an ohm-meter to contact output SS1. This is a normally open contact and the ohm-
meter should display a value close to infinity ohms.
202
iDP-210 Feeder Relay Manual KA2048 520 REV07
3.5. Press the F4 button and hold it down. This will toggle the state of the ss1 contact. Verify the
ohm-meter now reads near 0 ohms.
3.6. Press the F1 and F2 keys to move to the next contact output of co2 and repeat steps 3.3.1
through 3.3.6. Note the normal condition of the contact outputs as follows:
4.1.1. Press the METERING hotkey and verify the LCD displays voltages and currents.
4.1.2. Press the RESET TARGETS hotkey and verify the LCD brings up the reset target
screen.
4.1.3. Press the EVENTS hotkey and verify the LCD displays the last event summary.
4.1.4. Press the LAMP TEST hotkey and verify all LEDs illuminate.
4.1.5. Press the SETTINGS hotkey, enter the password, and verify the settings menu is
displayed.
4.1.6. Press the BREAKER STATUS hotkey and verify the breaker status display is displayed.
4.1.7. Press the ALARMS hotkey and verify the Alarms menu is displayed.
4.1.8. Press the TEXT MESSAGES hotkey and verify the message screen is displayed.
203
iDP-210 Feeder Relay Manual KA2048 520 REV07
4.2.1.1. Press the GND TRIP BLOCKED button and verify the status of integral LED
changes state. Press the button again and verify the LED again changes state.
4.2.1.2. Press the NON RECLOSING button and verify the status of integral LED changes
state. Press the button again and verify the LED again changes state.
4.2.1.3. Press the LOCAL MODE button and verify the status of integral LED changes
state. Press the button again and verify the LED again changes state.
4.2.1.4. USER OPTION #1, 2, 3, 4, 5, and 6 will only be active and illuminate if they have
been programmed in the IDEA WORKBENCH.
4.2.2. Verify Operation of the Hot Line Tag or Close Inhibit Switch
4.2.2.1. For IdeaPLUS relays with Hot Line Tag Switch, move the toggle level to the up
position and verify the associated LED illuminates. Return the toggle switch to the
down position and verify the LED extinguishes.
4.2.2.2. For IdeaPLUS relays with the Close Inhibit switch, move the toggle switch to the
up position and allow the spring loaded toggle lever to return to the center position.
The behavior of the associated triple LED lamp assembly varies depending upon
the state of the Supervisory Off feature:
4.2.3.1. Apply an ohm-meter to the rear contact terminals of the TRIP button contacts
(labeled as “TRIP contact” on the back of the relay). This is normally open contact
and the ohm-meter should display a value close to infinity. Press the TRIP
pushbutton and verify the ohm-meter now should display a value close to zero.
204
iDP-210 Feeder Relay Manual KA2048 520 REV07
4.2.3.2. Apply an ohm-meter to the rear contact terminals of the CLOSE button contacts
(labeled as “CLOSE contact” on the back of the relay). This is normally open
contact and the ohm-meter should display a value close to infinity. Press the
CLOSE pushbutton and verify the ohm-meter now should display a value close to
zero.
4.2.4.1. Apply a voltage equal to the rating of the lamps ordered across the “Green Lamp”
and “Red Lamp” terminals on the back of the relay and verify the lamps illuminate.
205
iDP-210 Feeder Relay Manual KA2048 520 REV07
11 Troubleshooting
If you receive an alarm from the relay, or some other indication of improper operation, here
is a brief troubleshooting guide. For more detailed troubleshooting assistance, contact
Cooper Power Systems Relay Technical Support as described in the next chapter.
11.1 Hardware
11.1.1 If the Edison Idea or IdeaPLUS fails to operate, no lamps are illuminated and
the LCD display is blank-
• Verify that supply voltage is present at terminals 1 and 2 of J1, and that the voltage is
correct.
• If correct voltage is applied and problem persists, a failure of the Edison IdeaPLUS is
possible. Contact Cooper Power Systems Technical Support as described in 12.1.
11.1.2 If the Edison Idea or IdeaPLUS fails to operate, most or all LEDs are
illuminated, and the LCD display shows all “A” characters only-
• Using ProView, first download firmware and then download a scheme file to the relay
• If the scheme or firmware cannot be downloaded, or if the problem persists after
download, a failure of the relay is possible. Contact Cooper Power Systems Technical
Support as described in 12.1.
11.1.3 If you cannot establish a communication link between ProView and the Edison
Idea or IdeaPLUS, check the following:
• There is an entry in the "Phone Book" for the relay
• The entry in the "Phone Book" refers to the proper COM port on the PC
• The communications cable is connected to one of the RS-232 ports (NOT to the RS-485
port, unless a special adapter is used). A straight DB-9 RS232 cable is required to
communicate through the front RS232 port on the relay.
• The cable is a 1:1 direct patch wired cable for the front port, or a null-modem cable for the
rear port when connecting the relay directly to a computer. A 1:1 cable is used on the
rear port if the relay is connected to a modem.
11.1.4 If the Edison Idea or IdeaPLUS OK light is off, alarm light is on, and/or the LCD
reports an "Internal Alarm":
• Use the front panel menus to determine the specific alarm(s), and then contact Cooper
Power Systems Relay Technical Support for more specific troubleshooting information.
11.1.5 How do I use the two DC monitoring inputs on the back of the IdeaPlus?
These are currently non-functional in the present release of the IDP software.
206
iDP-210 Feeder Relay Manual KA2048 520 REV07
11.2.4 When I connect to the relay, none of the screens accessed from the Display
menu, nor the IDEA Workbenches, are updating.
You are not in Online-View mode. After connecting to the relay, click on the Go Online button.
This button is located both next to the Connect button at the top of the screen, and in many of
the Display menu dialog boxes, including the Application Diagram display.
207
iDP-210 Feeder Relay Manual KA2048 520 REV07
11.2.5 When I connect to the relay, a message box appears telling me I have a
different version of firmware on my relay.
The scheme file loaded in ProView was developed for a different firmware version than what
resides in the relay.
To update the firmware you must be logged in at the Modify password level. Then follow these
steps:
1. Connect to the relay.
2. Follow the Manage>Device>Download Firmware menu path from the main menu.
3. Wait for the firmware to download. When this is complete the relay will have stopped
functioning as a relay. See above Warning.
4. Click on the Compare button as described in Section 7.3 Comparing PC Schemes and
Settings to Relay on page 87.
5. Choose “Download Structure” from the Compare dialog box. This will load the new
scheme to the relay.
6. Reload your settings to the relay.
7. The relay will now be ready for testing.
11.2.6 Shortly after I power up my relay I get a Cold Load Pickup event in the
Sequence of Events log.
When the relay is first powered up, the 52A opens and the Cold Load Pickup timer
(CLEnable:62P) starts timing. Once that timer expires, a Cold Load Pickup event is
recorded.
11.2.7 While downloading to the relay, power was inadvertently lost, and now the
relay is either locked up or behaving incorrectly.
If power is lost during a structure or setting download to the relay, it is possible that the
incomplete download will result in erratic relay behavior. The following procedure will
rectify this situation.
1. Power down the relay.
2. Power up the relay with the MENU softkey pressed and held in until the relay LEDs
illuminate. This process clears the partially loaded scheme.
3. Connect to the relay and down the desired scheme and settings.
208
iDP-210 Feeder Relay Manual KA2048 520 REV07
12 Getting Help
Call 1 (800) 497-5953 from 8:30 AM to 4:00PM Central Time (USA) (GMT – 6 hours)
Outside the USA, call 1-414-768-8203 from 8:30 AM to 4:00PM Central Time (USA) (GMT – 6 hours)
Or e-mail: [email protected]
Call 1 (800) 497-5953 from 8:30 AM to 4:00 PM Central Time (GMT – 6 hours)
209
iDP-210 Feeder Relay Manual KA2048 520 REV07
13 Appendices
13.1 Specifications
Frequency 50/60 Hz
210
iDP-210 Feeder Relay Manual KA2048 520 REV07
211
iDP-210 Feeder Relay Manual KA2048 520 REV07
CommOption
Lamp Style.
Input Range
Language
Enclosure
TermBlk
Scheme
Tagging
Product
Aux I/O
Construct Catalog Number
Power
from this table.
PR6
Sample Catalog Number: PR6 P2 D10 E 1 5 1 N S T 3
TYPE Edison Idea/IdeaPlus Relay PR6
Edison Idea Chassis D2
Edison IdeaPlus Chassis P2
Scheme/ iDP-210 Feeder Relay D10
Model iDP-210 Feeder Relay w/2 sets of 3-phase voltage inputs D16 Requires Aux I/O Board
iDP-210 Feeder Relay with SEF D20
iDP-210 Feeder Relay with SEF and 2, 3-phase VT inputs D26 Requires Aux I/O Board
Inserts English E
Language Portuguese P
Spanish S
Other O
Power 48VDC Power Supply 4
125VDC/120VAC Power Supply 1
250VDC/240VAC Power Supply 2
24VDC Power Supply 3
Input 5 Amp CT Inputs, 67/120V PT Inputs 5
Ranges 1 Amp CT Inputs, 67/120V PT Inputs 1
Comm. RS485 1
Options Fiber serial 3
Ethernet Fiber Optic:Fiber Optic MTRJ/MTRJ 4
Ethernet Fiber Optic:Wire MTRJ/RJ45 5
Ethernet Wire:Wire RJ45/RJ45 6
Standard: None 7
Ethernet Single Mode Fiber LC/LC 8
Aux I/O No additional Contact I/O N
Add 8 Contact Inputs and 8 Contact Outputs, all N.O 0
Add 8 Contact Inputs and 8 Contact Outputs, 1 NC, 7NO 1
Add 8 Contact Inputs and 8 Contact Outputs, 2 NC, 6NO 2
Add 8 Contact Inputs and 8 Contact Outputs, 3 NC, 5NO 3
Term. All Barrier S
All Compression C
Tag Type Mechanical Hot-Line Tag, CLOSE inhibited on relay fail T
Mechanical Hot-Line Tag, CLOSE enabled on relay fail A
Software based Close-inhibit, CLOSE inhibited on relay fail C
Software based Close-inhibit, CLOSE enabled on relay fail R
Trip/Close 125VDC/120VAC LED Lamps for Trip and Close Status 3
Lamp 48 VDC LED Lamps for Trip and Close Status 2
Type 24VDC LED Lamps for Trip and Close Status 1
48VDC Incandescent Lamps for Trip and Close Status 7
24 VDC Incandescent Lamps for Trip and Close Status 6
212
iDP-210 Feeder Relay Manual KA2048 520 REV07
Other X
No Bulbs 0
213
iDP-210 Feeder Relay Manual KA2048 520 REV07
Pinouts
1 DCD Carrier Detect Output
2 TXD Transmit Data Output
3 RXD Receive Data Input
4 DSR Data Set Ready Not Connected
5 GND Ground Ground
6 DTR Data Terminal Ready (same as RTS) Output
7 CTS Clear to Send Input
8 RTS Request to Send (same as DTR) Output
9 NC Not Used Not Connected
214
iDP-210 Feeder Relay Manual KA2048 520 REV07
Figure 13-1: Back panel Ethernet and Communication options (above s/n 2000)
215
iDP-210 Feeder Relay Manual KA2048 520 REV07
216
iDP-210 Feeder Relay Manual KA2048 520 REV07
Maximum link length is determined by the use of the particular physical layer
implementation, and can be further constrained by the actual network configuration. In
case of the 100Base-FX MT-RJ connector based implementation, maximum link length in
excess of 2000m can be achieved with 62.5/125µm multi mode fiber. The fiber-optic link
uses 1300nm wavelength, and can easily be interfaced to other 100Base-FX solutions
(ST connector patch cord solution).
The Ethernet communication accessory card is equipped with two physical ports
configured to act as primary and standby LAN connections. Availability of the backup
communication port enables creation of highly redundant Ethernet networks thus
increasing the overall system reliability.
• Under normal network conditions, all communications will be channeled through
the primary port (#1, Figure 13-1), with the standby port either logically disabled,
or configured for fast automatic throw-over in case of the primary Ethernet link
failure.
Ethernet Communication Card Configurations
Card Output Communication
Type Configurations Connectors Speed
1 10/100 Base-T 2 * RJ-45 10 / 100MBps
(auto switching)
2 100 Base-FX 2 * MT-RJ 100MBps
(fiber) (full duplex)
3 10/100 Base-T, RJ-45 + MT-RJ 10/100MBps
100 Base-FX and 100MBps
217
iDP-210 Feeder Relay Manual KA2048 520 REV07
J1 J2 J3
Recommended Cable: Twisted pair with 3rd conductor for Signal Ground
218
iDP-210 Feeder Relay Manual KA2048 520 REV07
The following discussion provides a description of the behavior of the frequency measuring algorithms
used in the iDP-210 for both the frequency elements 81O and 81U and the synch-check element and
for certain signals in the IDEA Workbench. Note that the terminology “asserts” means the logic
produces a logical 1 output, and “unasserts” indicates the logic returns to a logical 0 output.
Assuming sinusoidal single-frequency voltages, then on the three-phase side of the breaker, if the
positive sequence voltage estimate falls below 2% of full scale, the frequency elements latch and
maintain their prior status, asserted or unasserted.
If the positive sequence voltage remains below 2% of full scale for longer than 4 cycles, then the
frequency elements are unlatched and unasserted (all 81U's drop out, and all 81O's drop out) and the
Workbench signal <X Freq Not Measurable> asserts, where "X" stands for either "Bus" or "Line",
depending upon which side of the breaker the three-phase PT's are located.
One and one-half (1.5) cycles after the positive sequence voltage rises above 2% of full scale, the
<X Freq Not Measurable> signal unasserts and the frequency elements commence reporting their
actual realtime status.
On the single-phase side of the breaker, all of the above logic applies equally except:
• The signal <Y Freq Not Measurable> is asserted when voltage is inadequate for frequency
determination, where "Y" stands for either "Line" or "Bus", depending upon which side of the
breaker the single-phase PT is located.
Also available to the IDEA Workbench for the iDP-210 is a third signal, <Slip Not Measurable>, which
asserts simply when either of the <Bus Freq Not Measurable> or <Line Freq Not Measurable>
signals assert.
The only substantive difference between the iDP-210 relay and the Form 6 recloser control is that in the
Form 6, the <Phase Freq, Slip Unstable> and <Sync Freq, Slip Unstable> signals assert 4 cycles
sooner than the similar <Bus Freq Not Measurable> and <Line Freq Not Measurable> signals in the
iDP-210. The vast majority of frequency functionality is identical between the Form 6 and iDP-210. The
practical effect will be that the Form 6 will provide an earlier warning to frequency measurement
problems, while the iDP-210 will provide fewer false warnings due to switching transients.
The relay with iDP-210 scheme contains capabilities to perform Sequence of Events (SOE) time-
stamping for more than 74 event types (binary inputs).
Sixteen additional event types can be user-defined through the ProView™ Idea Workbench™. The
status of the 16 user-defined events types are displayed on the relay front panel LCD in the
Workbench> Workbench Status menu display. These 16 event types are displayed as USER SOE #01
ON, USER SOE #02 ON, etc. (through USER SOE #16 ON) as the default. Refer to the Workbench
Status Outputs to MMI and SOE section in S165-210-2 iDP-210 Workbench Programming Guide for
additional user-defined event information.
219
iDP-210 Feeder Relay Manual KA2048 520 REV07
A minimum of 250 events will be available in the event recorder. The most recent event appears at the
top of the event recorder. The event recorder uses a first in, first out protocol.
220
iDP-210 Feeder Relay Manual KA2048 520 REV07
221
iDP-210 Feeder Relay Manual KA2048 520 REV07
13.8 Mounting the Idea or IdeaPlus Relay with optional Mounting Kits
The Idea and IdeaPlus relays are designed to be mounted in a standard 19” rack. These are the
mounting options:
• Double Rack Mounting Kit
• Single Mount with Filler Plate Mounting Kit
222
iDP-210 Feeder Relay Manual KA2048 520 REV07
13.8.1 Idea/IdeaPlus Relay Double Rack Mount Connecting Plate and Handle
Attachment Instructions
These instructions apply to the attachment of the handles and connecting plate for two Idea or
IdeaPlus relays mounted side-by-side in a standard 19” rack. Follow these procedures to
attach the handles and connecting plate.
Item Description Part Number Quantity
1 Idea Relay (for reference) 2
IdeaPlus Connecting Plate 6A00169501
2 or or 1
Idea Connecting Plate 6A00185101
3 #10-24 Screw 813315110100A 2
Table 13-1: PR6ADJK (Idea) / PR6APJK (IdeaPlus) Double Rack Mounting Kit Parts List
1. Remove the relay from service.
2. Carefully transport the relay to a suitable service facility.
Note: The entire kit assembly/installation process should be conducted in a clean environment, such as a
repair shop.
223
iDP-210 Feeder Relay Manual KA2048 520 REV07
4. Remove one handle from each relay so they fit together as shown in front view.
5. Remove the middle screws from the back of each relay with a Phillips head screwdriver.
6. Place the connecting plate over the screw holes in the relays.
7. Secure the connecting plate with the previously removed screws.
8. Completely tighten hardware. Do not torque.
9. Secure the relays together.
10. Connecting two relays requires removing the front panel from the relay (right-side) as
shown in Figure 13-5.
11. Unscrew the six screws from the relay front panel until they detach from the relay box.
12. Pull the right side of the right relay front panel out towards the left Figure 13-5.
224
iDP-210 Feeder Relay Manual KA2048 520 REV07
Note: Various connecting wires will keep the panel attached to the relay. It is not necessary to disconnect
any wires.
13. Use a long flathead screwdriver to screw each #10-24 screw (Item 3, Table 13-1) right to
left into the pre-threaded holes.
Note: It is not necessary to remove the front cover panel of the left relay.
Figure 13-5: Double Rack—Single Mount Handle and Filler Plate Attachment
Instructions
225
iDP-210 Feeder Relay Manual KA2048 520 REV07
Note: The filler plate can be mounted on either side of the relay.
Note: This procedure is required prior to mounting one relay in a standard 19” rack.
Note: The entire kit assembly/installation process should be conducted in a clean environment, such as a
repair shop.
3. Remove the screws from the handle on the side the filler plate will be mounted to. Retain the
screws.
4. Align the holes of the loose handle over the pre-drilled holes on the side of the relay.
5. Align the filler plate over the handle holes as shown in Figure 13-6.
6. Attach the handle and filler plate (Item 2) to the relay with the two new #10-32 Pan Head
Screws (Item 3) and the screws retained in Step 3 as shown in Figure 13-6.
7. Tighten all hardware completely. Do not torque.
8. Return the relay to service.
226
iDP-210 Feeder Relay Manual KA2048 520 REV07
227
iDP-210 Feeder Relay Manual KA2048 520 REV07
When the fault condition is no longer detected (the 46NFD drops out) then some time
must elapse before the user can be assured that the associated trip/reclose sequence
(either local or downstream) is complete. The (79:62res) timer setting (Recloser Reset
Time) is employed for this purpose. This is the reset timer setting which would normally be
employed when resetting from a local trip/reclose sequence. But, as described above, the
46NFD pickup is used to alert the reclosure module of just such a condition (either local or
downstream). So pickup/dropout of the 46NFD has the same effect as pickup/dropout of
any enabled residual overcurrent element, as far as the reset of the recloser module is
concerned.
228
iDP-210 Feeder Relay Manual KA2048 520 REV07
Location:
Name:
Other Identifier:
Scheme Scheme Revision Date:
Filename:
Setting Group:
Settings Prepared By: On Date:
Settings Set By: On Date:
NOTE: Variables whose settings are shown as a series of comma delimited values are variables
whose settings can change with the selected Setting Group. The first number in the series
represents the setting for the first setting group, and so forth. Variables with a single entry are
global variables whose settings do not change with the setting group.
229
iDP-210 Feeder Relay Manual KA2048 520 REV07
230
iDP-210 Feeder Relay Manual KA2048 520 REV07
231
iDP-210 Feeder Relay Manual KA2048 520 REV07
232
iDP-210 Feeder Relay Manual KA2048 520 REV07
233
iDP-210 Feeder Relay Manual KA2048 520 REV07
234
iDP-210 Feeder Relay Manual KA2048 520 REV07
235
iDP-210 Feeder Relay Manual KA2048 520 REV07
236
iDP-210 Feeder Relay Manual KA2048 520 REV07
237
iDP-210 Feeder Relay Manual KA2048 520 REV07
238
iDP-210 Feeder Relay Manual KA2048 520 REV07
239
iDP-210 Feeder Relay Manual KA2048 520 REV07
240
iDP-210 Feeder Relay Manual KA2048 520 REV07
241
iDP-210 Feeder Relay Manual KA2048 520 REV07
242
iDP-210 Feeder Relay Manual KA2048 520 REV07
15 Revision History
Rev 1.27 March 2002
• All revision notes prior to Rev 1.27 deleted from this section. For details on revision
notes prior to Rev 1.27, see manual Revision 1.26.
• Corrected setting range minimum values for 50PH, 50RH and 50QH in Section 8.5.2.
• Corrected the IEEE MI TCC curve.
• Added additional documentation about self test failures in Section 5.7.6.2.
Rev 1.28 March 2002 (REV 02)
• Added Section 8.16, Demand Meter Settings and Section 8.17.1, Setting Non-
Volatile Modes When Connected to the Relay
KA2048 520 REV 03 October 2002
• Updated Section 3.2, IdeaPLUS DC Connection Diagram.
• Adding Warning G140.0 to Section 7.
KA2048 520 REV 04 July 2004: Manual release for iDP-210 release in ProView 4.0.1
• Updated delta PT AC wiring diagrams. The connections to the C phase PTs were
reversed.
• Added ProView 4.0.1-specific documentation.
• Added new DC wiring diagram for front panel synch-check operation with IdeaPLUS
(see page 34).
KA2048 520 REV 05 September 2004:
• Added descriptions of the Generate Report and Copy to Clipboard buttons in the
Event Manager dialog.
KA2048 520 REV 06 November 2004:
• Updated IdeaPLUS DC Wiring diagrams to correct indicate terminal numbers for SS1,
C01, CO3 and CO4.
• Section 8.5.1.2: Added note regarding need to manually set fault detectors where
matching overcurrent elements are not enabled.
KA2048 520 REV 07 January 2005
• Section 8.5.2.4: Added the following statement to each published TCC Curve: The
timing tolerance on the TCC curves is ±10% and ±1 cycle.
243
iDP-210 Feeder Relay Manual KA2048 520 REV07
16 INDEX
Adjusting, 52
Control Close events, 159
A Control logic, 20
AC Wiring Diagram Control Panel (IdeaPlus Only), 21
ABC rotation, 4 voltage inputs, 45
ABC rotation, 6 voltage inputs, 48
ACB rotation, 4 voltage inputs, 46
D
ACB Rotation, 6 voltage inputs, 49 DC Connection Diagram
Delta PT, 4 voltage inputs, 47 Idea, 25, 26
Delta PT, 6 voltage inputs, 50 Idea Plus, 33
Alarms, 65, 67 Definite-time overcurrent elements, 126
ALARMS Demand Meter
External, 65 Alarm display on LCD, 66
External, display, 100 Displaying metering values, 109
Internal, display, 100 HMI Submenu, 68
ANALYSIS, 21 Hotkey, 57
Interactive oscillography, 21 Settings, 184
Relay-replay, 21 Dialog box
View-online, 21 External alarm output contact, 191
Virtual test set, 21 Dialog window
Anti-Pump Timer. See Operator Window Compare, 89
Application diagram, display, 98 Directional fault detectors
Automatic restoration, 172 Setting, 124
Directional parameters
Setting, 122
B Disconnecting from the relay, 87
Baud rate, 86 Display with controls, 21
Breaker Displaying relay data, 98
Failure functions, 174 Downloading settings, 90, 91
Moniotoring functions, 175 Downloading the scheme structure, IDEA Workbench
Settings, 173 and settings, 91
Breaker statistics, display, 105
E
C Equipment mis-operation
Catalog numbers, 212 Warning, 208
Circuit breaker Event record, loading, 92
Operation of, from ProView, 111 Event records, 92
Circuit Breaker, trip and close, 98 External alarm, 188
Close circuit External alarms, 65
Disable link, 52 External Alarms, 65
Close circuit break
IdeaPlus, 55
Cold load pickup, 181
F
Communicating with the Relay, 84 Fail to trip timer, 174
Communications, 20 Fault locator results, display, 105
Compare button, 88 Firmware
Comparing PC Schemes and Settings to Relay, 87 Updating, 208
Configuring ProView Connection Profiles, 85 Frequency elements, 169, 219
Connecting to the Relay, 84 Front panel communication port pinouts, 214
Contact inputs and outputs, display, 101 Front panel elements, 52
Contact output bvehavior Front panel targets, 53
External alarms, 188 Fuse fail logic, 165
Contrast of the LCD Fuse failure settings, 166
244
iDP-210 Feeder Relay Manual KA2048 520 REV07
245
iDP-210 Feeder Relay Manual KA2048 520 REV07
246