Fault Indicators Sel Guide
Fault Indicators Sel Guide
Electrical Apparatus
2
320-05
3
Faulted Circuit Indicator Application Guide
Proximity Effect
Proximity effect is defined as the
current from an adjacent cable affect-
ing the operation of a fault ELBOW
indicator on the desired cable of oper- TIE-OFF
TAB
ation. Proximity effect has two differ-
ent modes in which it can affect fault ELBOW
indicator operation.
First, on multi-phase circuits, conduc-
tors of different phases can be in very TERMINATED
close proximity to one another. This is LOCATE
NEUTRAL
WIRES
especially true on underground appli- THE SENSOR
PORTION OF
cations. Due to the distance between THE FAULTED
the conductors, it becomes difficult for CIRCUIT
INDICATOR
the fault indicator to distinguish (in the outlined
area)
between the magnetic field of the
desired conductor and that of the
NEUTRAL
adjacent conductor. Therefore, a fault WIRES
on the adjacent conductor can cause a b c d
the fault indicator on another cable to
trip in error.
The second way proximity effect can Figure 5.
influence cause fault indicator opera- Recommended methods of concentric neutral primary cable preparation.
tion is when cables of the same
phase are in close proximity to one
another. For example, in a typical sin-
gle-phase transformer application, Proximity effect can be eliminated in Backfeed Voltages and
incoming and outgoing primary cables two ways. First, selecting a high trip Currents
are usually in close proximity to one rating can make the fault indicator less
sensitive to adjacent phases. The Automatic-resetting fault indicators
another. In this case, the fault current that use either voltage or current to
would be traveling in one direction second and most effective method for
eliminating proximity effect is by the reset the unit when system power is
through the incoming cable and going restored can be affected by the sys-
in nearly the opposite direction use of a current transformer (either
open or closed core) to concentrate tem connection. Typically on systems
through the outgoing cable. The cur- where delta connections exist, single-
rent in the outgoing cable can then the flux from the desired phase and
therefore reduce the sensitivity of the phase sectionalizing can cause volt-
generate a magnetic field that effec- age or current backfeed which may
tively cancels the magnetic field gen- sensor to adjacent phases.
cause tripped fault indicators to reset.
erated in the incoming cable. This is
especially true for low trip level fault It is difficult to quantify the exact mag-
indicators, because they are much nitude of the backfeed current without
more sensitive to the adjacent mag- doing an in-depth system study.
netic field. However, voltage backfeed can be
quantified. Due to typical transformer
connections, the maximum voltage
backfeed that a fault indicator may
see is 60% of the nominal system
voltage.
This fact provides a means by which
voltage backfeed can be eliminated
as a cause of FCI resetting. A reset
restraint circuit, with the threshold set
above the 60% level will prevent the
fault indicator from resetting in error.
Figure 4.
Proximity effect illustration.
4
320-05
Temperature Fault indicators can be used on tape This information suggests that since
Compensation shield conductor or drain wire cable. If the maximum line-to-ground fault cur-
the cable shielding does not provide rent will flow to the fault, selecting a
Temperature compensation is a fea- the return path for the indicator, the low trip rating on a fault indicator pro-
ture that allows the fault indicators to indicator can be installed directly to vides little added sensitivity over a
provide a more accurate and reliable the cable. If the cable shielding pro- fault indicator with a higher trip rating.
output between -40° C. and +85° C. vides the return path for the fault cur- As a matter of fact, due to phenome-
S.T.A.R. fault indicators use a current rent, the indicator will not reliably na like proximity effect, a lower trip
transformer design to implement the detect a fault, as described above, rating can make the fault indicator
low pass filter circuit and to minimize and will require the use of a tape less reliable than one with a higher
the affects of adjacent magnetic shield or a drain wire adapter. (An rating. Therefore it makes sense to
fields. These features provide a sig- adapter must be installed approxi- set the fault indicator trip rating based
nificant performance improvement mately four inches below the elbow to on the available fault current levels,
over the use of a reed switch sensing allow ample space to mount the fault not the load current level.
circuit. indicator on the cable.) A better method for selecting a trip rat-
The copper coil of the current trans- SIMPLIFY FAULT ing is to analyze the system parameters
former changes resistance as the INDICATOR APPLICATION and select a trip rating based on a
temperature varies, therefore, the out- generalized system. For example, a
put will also change due to variable Reliable fault indicator application can typical 200 A underground system
temperature ranges. Cooper Power be achieved by selecting the proper rarely carries more than 50 to 100 A,
Systems designed and integrated a faulted circuit indicator for the job, but but is designed to carry a maximum of
circuit that compensated for the tem- in addition, the fault indicator must be 200 A. While a trip rating just above
perature changes, therefore, provid- applied properly in the field. The best the 100 A level could be selected,
ing an accurate output. method to assure proper field applica- selecting a trip rating greater than the
tion is to make the application rules 200 A maximum continuous load cur-
Cable Preparation: URD simple for field personnel. rent will allow the load current to vary
Due to the characteristics of a typical anywhere in the acceptable current
Proper primary cable preparation is range. This trip setting can then be
necessary for fault indicators to work distribution system, it is possible to
achieve a high degree of fault used for any 200 A underground dis-
reliably. The unit cannot be installed tribution system. The only criteria that
directly over the concentric neutral, indicator reliability while using just
one or two trip ratings for the entire needs to be satisfied to make this phi-
because the unit monitors current. If losophy work is that the fault indicator
the current in the neutral (return path) system. The application of the fault
indicators then becomes a matter of must respond faster than any protec-
is high it could cancel the effects of tive device on the system.
the field from the fault current in the applying the right fault indicator for
conductor. The net result could be the given system type.
less than the trip rating; therefore, the In 1983, EPRI published a study
fault indicator would not trip. The line called “Distribution Fault Current
crew, upon investigation, would be Analysis.” This study showed typical
misled by the false indication. The fault current characteristics for a
unit can, however, be mounted over cross-section of distribution feeders
the neutral if the neutral is double throughout the United States. The
backed as shown in Figure 5 a and b. results of the study showed that faults
Doubling the neutral allows the FCI to typically have less than two ohms of
detect the field from the fault current impedance. Furthermore, it showed
in the conductor because it eliminates that system fault calculations were
a return path. Refer to Figure 5 for the relatively accurate when a zero fault
recommended methods of concentric impedance was used to calculate
neutral primary cable preparation. line-to-ground fault current magni-
tudes.
5
Faulted Circuit Indicator Application Guide
200
400
will allow the load current to vary within
the acceptable range without tripping. 10
The FCI will trip when fault current
reaches approximately 400 A, which
is beyond any expected continuous
load current, and less than the typical
expected minimum fault current. And,
because response time of the fault
1
indicator is faster than protective
equipment, the unit will indicate a
faulted condition before any protective
devices operate.
This philosophy will work for overhead
distribution as well. A system that is
.1
protected by fused cutouts, can have
fuse ratings from 1 A through 200 A. TIME IN SECONDS
Typical Range Typical
Since 200 A tin links can carry 150% of Continuous
rated load, the possible load currents Range
Current under of Fault
could vary anywhere from a few Normal Load Current
amperes up to a maximum of 300 A.
If a faulted circuit indicator with a trip .01 Response
rating of greater than 300 A is used, Curve
that trip rating could be used anywhere
on the overhead system, provided the
fault indicator is fast enough to beat
out the fuse for any fault occurrence.
When using this application philosophy, .001
one can also ignore any variations in
the fault indicator trip rating due to
changing cable dimensions, because
as long as the trip rating is substan-
tially larger than the maximum load
current, the exact trip rating does not
matter. The maximum line-to-ground .0001
fault current will flow to the fault, 1 10 100 1,000 10,000
effectively tripping a fault indicator CURRENT IN AMPERES
that is slightly higher in rating. This
further allows the fault indicator to be Figure 6.
applied generally to any system. Low Voltage Reset faulted circuit indicator (Low trip rating) response curve as
In general, a fault indicator applied to applied to a typical 200 A underground system.
a 200 A URD loop should have a
LOW trip rating (around 400 A) and a
600 A system should utilize a HIGH Three-Phase System
trip rating (around 800 A). AØ BØ CØ
(Refer to Figure 7)
The last step to making the application #3 #6 #9
of the faulted circuit indicator simpler ■ Fault occurs on Phase A. Fault
is to make all the features that may current levels exceed trip rating of FAULT
be needed in any application standard indicators and, thus, all indicators
on the fault indicator specified. For (#1 and #2) between recloser and #2 #5 #8
example, it is recommended that all fault trip.
fault indicators have inrush restraint. ■ Recloser opens. Indicators, with #1 #4 #7
This means that this fault indicator can inrush restraint, on Phase B and C
be applied anywhere on the system, detect loss of power. Deadtime is AUTO RECLOSER
even where a recloser is not being sufficient to fully discharge the trip OR BREAKER
used. Therefore, the line personnel capacitors.
won’t have to decide between a unit THREE-PHASE
without inrush restraint and one with SYSTEM
inrush restraint.
Figure 7.
FAULT INDICATOR Typical Three-Phase Application of
Fault Indicators with the Inrush
INRUSH OPERATION Restraint Option.
The following is a description of how
a system operates during inrush
when fault indicators equipped with
inrush restraint are applied.
6
320-05
■ Recloser closes back in. Phase A Time E - Recloser closes back-in. ■ The recloser cycles until recloser
sees fault current again. #1 and #2 A-phase (or A-leg) current lock-out occurs. The only tripped
indicators remain tripped while B rises to fault level. Previously indicators are #1 and #2, thus,
and C phases experience inrush. tripped indicators on A-phase locating the fault between #2 and
Trip circuits for indicators on B (or A-leg) remain tripped. B #3 on the A-leg.
and C phases have already been and C-phase (or B-leg and Current trace: Same as Figure 8.
inhibited and, thus, will not trip. C-leg) indicators experience
■ inrush, but do not respond
The recloser cycles until recloser due to disabled trip function A-LEG B-LEG
lock-out occurs. The only tripped at time D.
indicators are #1 and #2, thus, #3 #6
locating the fault between #2 and Time F - Recloser cycles until it locks FAULT
#3 on the A-phase. open or until the fault is
isolated by the operation of #2 #5
Current Trace a fuse link or sectionalizer.
#1
(Refer to Figure 8) The only tripped indicators #4
are on A-phase (or A-leg)
Time A - Normal Load Current All between the recloser and
indicators in normal state. the fault. AUTO RECLOSER
Time B - Fault occurs on Phase A (or OR BREAKER
A-leg of bifurcated feeder). Single-Phase System
All indicators on Phase A with Laterals SINGLE-PHASE SYSTEM
(or A-leg) between recloser WITH LATERALS
(Refer to Figure 9) (b)
and the fault trip.
■ Fault occurs on A-leg of bifurcated
Time C - Recloser opens. feeder. Fault current levels exceed Figure 9.
Indicators with inrush trip rating of indicators and, thus, Typical Single-Phase Application of
restraint on B and C-phases all indicators (#1 and #2) between Fault Indicators with the Inrush
(or B-leg and C-leg) detect recloser and fault trip. Restraint Option.
loss of power.
■ Recloser opens. Indicators, with
Time D - Deadtime exceeds time inrush restraint, on B-leg detect
necessary to trigger inrush loss of power. Deadtime is sufficient
restraint circuitry. (i.e. 300 to fully discharge the trip capacitors.
milliseconds, but in some
■ Recloser closes back in. A-leg
cases 100 milliseconds).
Indicators on B and sees fault current again. #1 and #2
C-phases (or B-leg and indicators remain tripped while B-
C-leg) inhibit their trip leg experiences inrush. Trip
function in anticipation of circuits for indicators in B-leg
inrush current. have already been inhibited and,
thus, will not trip.
FAULT CURRENT
TRIP RATING
NORMAL LOAD
ZERO CURRENT TIME
A B C D E F
FAULT CURRENT
TRIP RATING
NORMAL LOAD
ZERO CURRENT A B C D E F TIME
Figure 8.
Current Trace for Three-Phase Application of Fault Indicators with the Inrush
Restraint.
7
P.O. Box 1640
Waukesha, WI 53187
© 1998 Cooper Power Systems, Inc. www.cooperpower.com
MI
Printed on Recycled Paper 10/98