Module-2 Testing and Parallel Operation
Module-2 Testing and Parallel Operation
The secondary winding of the transformer is kept open, and the voltmeter is connected to their
terminal. This voltmeter measures the secondary induced voltage. As the secondary of the
transformer is open, thus no-load current flows through the primary winding.
The value of no-load current is very small as compared to the full rated current. The copper
loss occurs only on the primary winding of the transformer because the secondary winding is
open. The reading of the wattmeter only represents the core and iron losses. The core loss of
the transformer is the same for all types of loads.
Calculation of open-circuit test
Let,
• W0 – wattmeter reading
• V1 – voltmeter reading
• I0 – ammeter reading
Then the iron loss of the transformer Pi = W0 and
Working component Iw is
Putting the value of W0 from the equation (1) in equation (2) you will get the value of the
working component as
Magnetizing component is
1
Module-2 Testing and Parallel Operation
The phasor diagram of the transformer at no load or when an open circuit test is performed is
shown below,
The iron losses measured by the open circuit test is used for calculating the efficiency of the
transformer.
2
Module-2 Testing and Parallel Operation
The low voltage source is applied across the secondary winding, which is approximately 5 to
10% of the normal rated voltage. The flux is set up in the core of the transformer. The
magnitude of the flux is small as compared to the normal flux.
The iron loss of the transformer depends on the flux. It is less occurred in the short circuit test
because of the low value of flux. The reading of the wattmeter only determines the copper loss
occurred, in their windings. The voltmeter measures the voltage applied to their high voltage
winding. The secondary current induces in the transformer because of the applied voltage.
The phasor diagram of the short circuit test of the transformer is shown below
3
Module-2 Testing and Parallel Operation
Definition: The full load test on a small transformer is very convenient, but on the large
transformer, it is very difficult. The maximum temperature rise in a large transformer is
determined by the full load test. This test is called, back-to-back test, regenerative test or
Sumpner’s test.
The suitable load which absorbs the full load power of a large transformer will not easily be
available. Hence a large amount of energy will be wasted. The back-to-back test determines
the maximum temperature rise in a transformer, and hence the load is chosen according to the
capability of the transformer.
Back-to-Back Test Circuit
The two identical transformer is used for the back-to-back test. Consider the Tr1 and Tr2 are the
primary windings of the transformer connects parallel to each other. The nominal rated voltage
and frequency is supplied to their primary winding. The voltmeter and ammeter are connected
on their primary side for the measurement of the input voltage and current.
The secondary winding of the transformer is connected in series with the each other but with
opposite polarity. The voltmeter V2 is connected to the terminal of the secondary winding for
the measurement of the voltage.
The series opposition of the secondary winding is determined by connecting there any two
terminals; the voltmeter is connected across their remaining terminals. If it is connected in
series opposition, the voltmeter gives the zero reading. The open terminal is used for measuring
the parameter of the transformer.
4
Module-2 Testing and Parallel Operation
The above figure shows that the terminal B and C are connected to each other, and the voltage
is measured across the terminal A and D.
Determination of Temperature Rise
The temperature rise of the transformer is determined by measuring the temperature of their oil
after every particular interval of time. The transformer is operating back-to-back for the long
time which increases their oil temperature. By measuring the temperature of their oil, the
withstand capacity of the transformer under high temperature is determined.
Determination of Iron Loss
The wattmeter W1 measures the power loss which is equal to the iron loss of the transformer.
For determining the iron loss, the primary circuit of the transformer is kept closed. Because of
the primary closed circuit, no current flows through the secondary windings of the transformer.
The secondary winding behaves like an open circuit. The wattmeter is connected to
their secondary terminal for the measurement of iron loss.
Determination of Copper Loss
The copper loss of the transformer is determined when the full load current flows through their
primary and secondary windings. The additional regulating transformer is used for exciting the
secondary windings. The full load current flows from the secondary to the primary winding.
The wattmeter W2 measures the full load copper loss of the two transformers.
5
Module-2 Testing and Parallel Operation
Additive Polarity: In additive polarity, the same terminals of the primary and the secondary
windings of the transformer are connected
Subtractive Polarity: In subtractive polarity, different terminals of the primary and secondary
side of the transformer is connected.
Explanation With Connection Diagram
Each of the terminals of the primary, as well as the secondary winding of a transformer, is
alternatively positive and negative with respect to each other as shown in the figure below. Let,
A1 and A2 be the positive and negative terminal, respectively of the primary side of the
transformer and a1, a2 are the positive and negative terminal of the secondary side of the
transformer.
If A1 is connected to a1 and A2 is connected to a2 that means similar terminals of the
transformer are connected, then the polarity is said to be additive. If A1 is connected to a2 and
A2 to a1, that means the opposite terminals are connected to each other, and thus the voltmeter
will read the subtractive polarity.
It is essential to know the relative polarities at any instant of the primary and the secondary
terminals for making the correct connections if the transformers are to be connected in parallel
or they are used in a three-phase circuit.
In the primary side, the terminals are marked as A1 and A2 and from the secondary side, the
terminals are named as a1 and a2. The terminal A1 is connected to one end of the secondary
winding, and a voltmeter is connected between A2 and the other end of the secondary winding.
When the voltmeter reads the difference that is (V1 – V2), the transformer is said to be
connected with opposite polarity know as subtractive polarity and when the voltmeter reads
(V1 + V2), the transformer is said to have additive polarity.
6
Module-2 Testing and Parallel Operation
Iron losses in a transformer has two components: Hysteresis loss and Eddy current loss
Hysteresis loss: Hysteresis loss is due to reversal of the magnetising force. This loss is due to
the retentive property of material used for the magnetic core.
Eddy current loss: The alternating flux in the core induces a voltage in the core which in turn
sets up a current in the laminations. This current is called eddy current. The loss due to the
eddy current is called eddy current loss.
For a given value of volume of iron in the core, we have, Hysteresis loss 𝑾𝒉 ∝ 𝑲𝒉 𝑩𝟏.𝟔
𝒎𝒂𝒙 𝒇
Where,
7
Module-2 Testing and Parallel Operation
For a given thickness of lamination and volume of iron, we have, Eddy Current loss
𝑾𝒆 ∝ 𝑲𝒆 𝑩𝟐𝒎𝒂𝒙 𝒇𝟐
Where,
Ke – co-efficient of eddy current. Its value depends upon the nature of magnetic material
Bmax – maximum value of flux density in wb/m2
t – thickness of lamination in meters
f – frequency of reversal of the magnetic field in Hz
To separate the iron losses, we need to supply the primary of the transformer with a variable
voltage, variable frequency source
We need to maintain the voltage to frequency ratio a constant to make the flux density in the
core constant.
𝑊𝑖
Iron loss 𝑊𝑖 = 𝐴𝑓 + 𝐵𝑓 2 or = 𝐴 + 𝐵𝑓
𝑓
If we know iron loss at two different frequencies, we can calculate the constants A and B, then
for any given frequency we can determine the hysteresis loss and eddy current loss.
Transformer primary is connected to a source whose frequency and the induced emf can be
varied and the secondary is kept open. This can be achieved by using an alternator driven by a
prime mover such as a DC shunt motor. By adjusting the field and armature rheostats of the
Ns P
DC motor the speed can be varied there by the frequency varies, as f = and by varying the
120
field rheostat of the alternator we can vary the magnitude of the induced emf E which is applied
to the primary of the transformer.
8
Module-2 Testing and Parallel Operation
As the supply frequency is 50 Hz and taking the rated voltage is 230 V the ratio of V to f will
be 230/50 = 4.6 is to be maintained constant for various different frequencies such as 40 Hz,
42 Hz, 45 Hz, 50 Hz, and 55 Hz and the corresponding voltage is calculated and adjusted by
adjusting the excitation of the alternator. For each application of this V and f the input watt
meter readings are noted against the frequency. [V/f = 4.6]
Ns = (120f/P)
f Hz rpm = (30f) for 4- V = (4.6f) Pi Watts
pole alternator volts Pi/f
40 1200 184 ... ...
42 1260 193.2 ... ...
45 1350 207 ... ...
50 1500 230 ... ...
55 1650 253 ... ...
A graph between the frequency f and (Pi/f) is plotted as shown. The intercept represents the
value of the hysteresis coefficient Kh in watts per Hertz. The slope of the slant line represents
the eddy current coefficient Ke in Watts per Hz2.
After evaluating the values of Kh and Ke we evaluate the hysteresis loss at power frequency f
= 50 Hz as Ph = Kh × f = 50 f Watts, and the eddy current loss at 50 Hz = Pe = Ke × f2 = 2500
Ke Watts.
So that the iron loss at 50 Hz Pi = (Ph + Pe), which should tally with the watt meter reading
obtained at f = 50 Hz.
9
Module-2 Testing and Parallel Operation
• In substations, the total load required may be supplied by an appropriate number of the
transformer of standard size. As a result, this reduces the spare capacity of the
substation.
• If the transformers are connected in parallel, so there will be scope in future, for
expansion of a substation to supply a load beyond the capacity of the transformer
already installed.
• If there will be any breakdown of a transformer in a system of transformers connected
in parallel, there will be no interruption of power supply, for essential services.
• If any of the transformer from the system is taken out of service for its maintenance and
inspection, the continuity of the supply will not get disturbed.
10
Module-2 Testing and Parallel Operation
The circuit diagram shown in figure explains to know the load sharing of two dissimilar
single-phase transformers A and B when connected in parallel and sharing a common load.
a1 is the turn ratio of the transformer A
a2 is the turn ratio of transformer B
ZA is the equivalent impedance of the transformer A referred to secondary
ZB is the equivalent impedance of the transformer B referred to secondary
ZL is the load impedance across the secondary
IA is the current supplied to the load by the secondary of the transformer A
IB is the current supplied to the load by the secondary of the transformer B
VL is the secondary load voltage
IL is the load current
11
Module-2 Testing and Parallel Operation
The current IA and IB have two components. The first component represents the transformers
share of the load currents and the second component is a circulating current in the secondary
windings of the single-phase transformer.
• In order to eliminate circulating currents, the voltage ratios must be identical. That is a1=a2
• Under this condition:
12
Module-2 Testing and Parallel Operation
From the above equation (9), it is clear that the transformer currents
are inversely proportional to the transformer impedance. Thus, for the efficient parallel
operation of the two single-phase transformers, the potential differences at full load across the
transformer internal impedance should be equal.
This condition ensures that the load sharing between the two single-phase transformer is
according to the rating of each transformer. If the per-unit equivalent impedance is not equal,
then the transformer will not share the load in proportion to their kVA ratings. As a result, the
overall rating of the transformer bank will be reduced.
The current in the equations (7) and (8) is changed into volt-amperes by multiplying the two
equations by the common load voltage VL.
Equation (13) tells that the volt-ampere load on each single-phase transformer is inversely
proportional to its impedance.
13
Module-2 Testing and Parallel Operation
Hence, to share the load in proportion to their ratings, the transformers should have the
impedance which is inversely proportional to their ratings.
Let E2A and E2B be the no-load secondary emfs of the two transformers A and B connected in
parallel.
By KVL and KCL, V2 = (E2A – IAZA) and V2 = (E2B – IBZB) also V2 = ILZL, IL = (IA + IB).
V2 = (IA + IB) ZL
−(E2A − E2B )+ IA ZA
from this equation, IB =
ZB
−(E2A − E2B )+ IA ZA
also, V2 = (IA + IB) ZL = (E2A - IAZA) = IAZL + ZL { }
ZB
ZL
= {IA ZA − −(E2A − E2B )}
ZB
ZL ZA Z
Grouping, IA {ZA + ZL + } = {E2A + (E2A − E2B ) Z L }
ZB B
14
Module-2 Testing and Parallel Operation
𝐸2𝐴 − 𝐸2𝐵
Circulating current = IC = [ ]
𝑍𝐴 + 𝑍𝐵
15
Module-2 Testing and Parallel Operation
Conclusion
Loading considerations for paralleling transformers are simple unless kVA, percent
impedances, or ratios are different. When paralleled transformer turn ratios and percent
impedances are the same, equal load division will exist on each transformer. When paralleled
transformer kVA ratings are the same, but the percent impedances are different, then unequal
load division will occur. The same is true for unequal percent impedances and unequal kVA.
Circulating currents only exist if the turn ratios do not match on each transformer. The
magnitude of the circulating currents will also depend on the X/R ratios of the transformers.
Delta-delta to delta-wye transformer paralleling should not be attempted.
16