System 20 Btu Meter Manual Doc 00035532
System 20 Btu Meter Manual Doc 00035532
System 20 Btu Meter Manual Doc 00035532
BTU METER
INSTALLATION AND OPERATION GUIDE
ONICON
Flow and Energy Measurement For Software Version 0.1.15 and Higher
DOC-0003557 Rev.F
SYSTEM-20 BTU METER
SAFETY This meter was calibrated at the factory before shipment. To ensure correct use of the
meter, please read this manual thoroughly. Regarding this Manual:
INFORMATION
• This manual should be passed on to the end user.
• Before use, read this manual thoroughly to comprehend its contents.
• The contents of this manual may be changed without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without
ONICON’s written permission.
• ONICON makes no warranty of any kind with regard to this material, including, but
not limited to, implied warranties of merchantability and suitability for a particular
purpose.
• All reasonable effort has been made to ensure the accuracy of the contents of this
manual. However, if any errors are found, please inform ONICON.
• ONICON assumes no responsibilities for this product except as stated in the
warranty.
• If the customer or any third party is harmed by the use of this product, ONICON
assumes no responsibility for any such harm owing to any defects in the product
which were not predictable, or for any indirect damages.
SAFETY PRECAUTIONS:
The following general safety precautions must be observed during all phases of
installation, operation, service, and repair of this product. Failure to comply with
these precautions or with specific WARNINGS given elsewhere in this manual violates
safety standards of design, manufacture, and intended use of the product. ONICON
Incorporated assumes no liability for the customer’s failure to comply with these
requirements. If this product is used in a manner not specified in this manual, the
protection provided by this product may be impaired. The following messages are used in
this manual:
WARNING (1)
Messages identified as “Warning” contain information regarding the personal safety
of individuals involved in the installation, operation or service of this product.
CAUTION (2)
Messages identified as “Caution” contain information regarding potential damage
to the product or other ancillary products.
See pages A-4 through A-6 for French Translations of all WARNINGS, CAUTIONS and
IMPORTANT NOTES.
IMPORTANT NOTES.
Voir page A-4 par A-6 pour les traductions en français de tous les AVERTISSEMENTS,
MISES EN GARDE ET REMARQUES IMPORTANTES.
TABLE OF CONTENTS
SECTION 1.0 INTRODUCTION............................................................................. 5
1.1 PURPOSE OF THIS GUIDE.............................................................................................................................................................5
1.2 TYPICAL SYSTEM-20 BTU METER..............................................................................................................................................5
1.3 STANDARD FEATURES AND SPECIFICATIONS...................................................................................................................5
1.4 ADDITIONAL REQUIRED HARDWARE....................................................................................................................................6
1.5 WORKING ENVIRONMENT..........................................................................................................................................................6
1.6 SERIAL NUMBER...............................................................................................................................................................................7
APPENDIX
CHANGING RS485 SETTINGS OR METER PROGRAMMING AFTER COMMISSIONING....................................A-1
1:1 SYSTEM-20 DRILLING TEMPLATE........................................................................................................................................A-2
OUTDOOR THERMOWELL ASSEMBLY IN WELDED PIPE.................................................................................................A-3
FRENCH TRANSLATION OF ALL WARNING, CAUTION AND IMPORTANT NOTES (TRADUCTIONS EN
FRANÇAIS DE TOUS LES AVERTISSEMENTS, MISES EN GARDE ET REMARQUES IMPORTANTES).............A-4
1.1 PURPOSE OF THIS GUIDE The purpose of this guide is to provide installation and commissioning procedures, and
basic operating and servicing instructions for the ONICON SYSTEM-20 BTU Meter.
WARNING (4)
Only qualified service personnel should attempt to install or service this product.
Serious injury may result from the improper installation or use of this product.
1.2 TYPICAL SYSTEM-20 ONICON’s System-20 is a true heat (Btu) computer, which accepts data from several
BTU METER sensors, performs a series of computations with that data, and displays and/or transmits
the results as an indication of the amount of heat (Btus) being transferred per unit time or
as a totalized amount.
4 FLOW
49.50 BTU/HR
SYSTEM-20
Made in USA BTU METER
1
2
5
3
RETURN
6
HEAT
EXCHANGER
SUPPLY
1. Class II Input Power 20-28 AC/DC, 50/60 Hz 4. ONICON Water Flow Meter (ordered separately)
2. Input and Output Signals - Three (3) pulse iinputs, 5. Return Temperature Sensor
three (3) pulse outputs, one (1) analog output 6. Supply Temperature Sensor
3. RS485 BACnet or MODBUS
1.3 STANDARD FEATURES • Single mode Btu calculations, in either the heating or cooling mode, are
AND SPECIFICATIONS totalized, and displayed.
• Two-pipe dual mode Btu calculations in both the heating mode and the
cooling modes, are totalized and displayed.
• A single isolated RS485 serial interface is provided for BACnet® MS/TP or
MODBUS® RTU.
• Three field configurable pulse outputs may be used for totalization, alarm
indication and mode status.
• Three auxiliary pulse inputs may be used to totalize data from external
devices. This data may also be transmitted via the network interface and
viewed on the local display.
• A single field configurable isolated analog output is provided for energy
rate, flow rate or temperature.
ONICON Incorporated 727-447-6140 Page 5 www.onicon.com
SYSTEM-20 BTU METER
1.4 ADDITIONAL REQUIRED The System-20 must be connected to a suitable volumetric flow meter and a
HARDWARE matched pair of temperature sensors in order to calculate and report heat data.
Please refer to ONICON’s flow meter literature, or contact ONICON for help in
selecting the flow meter that will best fit your requirements.
Straight Run
Flow Meter Model Line Sizes Notes
Required
F-1100 Single Turbine Insertion Flow Meter Can be used in 1"
1 ¼" and larger 25
copper lines
F-1200 Dual Turbine Insertion Flow Meter 2 ½" and larger 15
F-11XX Inline Turbine Flow Meter ¾" and 1" 25
F-3500 Insertion Electromagnetic Flow Meter 1 ¼" and larger See manual
FT-3100 and F-3200 Inline Electromagnetic Flow Meters ¼" and larger 5
F-4300 Clamp-on Ultrasonic Flow Meter 2" and larger See manual
F-4600 Inline Ultrasonic Flow Meter ½" - 2 ½" See manual
Temperature/Sensors
Pair of solid state temperature sensors with 0 – 20 mA outputs. Suitable for use
with fluid temperatures up to 200° F.
Pair of 4-wire 1000 Ω Platinum RTD temperature sensors. Suitable for use with
fluid temperatures up to 250° F.
1.5 WORKING ENVIRONMENT The System-20 was designed for installation and use in typical domestic and
commercial environments that are free of corrosive liquids and fumes, direct
liquid exposure, temperature extremes and vibrations.
The operating ambient air temperature range is -13°F to 140° F. The electrical
power should be relatively clean, free of high frequency noise, large voltage
transients, and protected from power surges and brown outs.
CAUTION (5)
The System-20 battery cannot be retrofitted or replaced. Risk of fire
explosion, and burns. DO NOT recharge, disassemble, crush, heat above
212°F (100°C) or incinerate. Please check your local ordinances for
information concerning battery disposal.
1.6 SERIAL NUMBER The serial number of your System-20 is located on the top and inside the
enclosure. The serial number is a unique identifier for the product. Please have
this number available when contacting ONICON for assistance.
SECTION 2.0 The System-20 is generally shipped in one package unless optional hardware or
equipment is ordered. (Thermowells may have been shipped in advance.)
UNPACKING
2.1 CHECKING THAT YOU HAVE Please notify ONICON immediately if any of these items are missing.
RECEIVED EVERYTHING
Standard Documentation Includes:
The System-20 BTU Meter Installation and Operation Guide
The System-20 Certificate of Calibration
The System-20
Remove the System-20 from the shipping carton and inspect it for physical
damage. Notify the freight carrier and ONICON immediately if any items are
damaged in transit. Save all packaging.
Btu meters ordered with a flow meter and temperature sensors will be delivered
configured and programmed for use together as a system. The System-20 and
the temperature sensor serial numbers will match. The flow meter serial number
will be shown on the certificate of calibration and on the System-20 display.
Temperature Sensors
If ordered, temperature sensors will generally be packed in the same carton with
the System-20. Inspect the sensors and cables for damage. Each sensor will have
a label attached with a serial number.
Flow Meter
If ordered, the flow meter will be packaged in a separate carton. The flow meter
ordered with this Btu meter came complete with an instruction manual. Please
refer to it for detailed information regarding its installation, commissioning, and
operation.
SECTION 3.0 The System-20 BTU Meter should be installed by personnel with related
INSTALLATION knowledge and experience in the heating, cooling, and fluid metering fields.
ONICON is available to assist with technical recommendations and to provide
guidance by telephone and/or e-mail during the installation and commissioning
process. On-site field engineering, installation, and service are also available at an
additional cost. The installer should use good trade practices and must adhere to
all state and local building codes.
Before you begin, clean the external surfaces of all pipes at the installation
sites so that they are free of debris, foreign matter, solids, leak inhibitors, and
chemically aggressive substances. Flush the entire system so that it is free of flux,
solder, pipe and tube cuttings and any other debris.
3.1 SITE SELECTION Careful attention to the site selection for the system components will help ensure
an accurate energy measurement, help the installers with the initial installation,
reduce start-up problems, and make future maintenance easier. For example,
do not install the flow meter where it will be difficult for personnel to perform
periodic maintenance. When selecting a site for mounting the components, refer
to Section 1.5: WORKING ENVIRONMENT, as well as the following:
The System-20
Find an easily accessible location where field wiring connections can be made and
meter readings can be taken from floor level. Mount the enclosure on a vibration
free surface. Avoid locations such as the plenum of a fan coil, heat exchanger or
any housing that may contain electric motors or other strong sources of electrical
interference.
If possible, find an easily accessible location where field wiring connections can
be made from floor level. This will facilitate future service. Place the temperature
sensors away from strong sources of electrical noise that might affect the
performance of the sensors.
One temperature sensor thermowell will need to be placed in the same pipe with
the flow meter. It must be located at least five pipe diameters downstream of
the flow meter leaving enough clearance to remove either sensor from the pipe
without interference from the other sensor.
Mount the Btu meter on a vibration-free surface. Avoid sites such as the
plenum of a fan coil, heat exchanger, or other housings containing motors.
5 1/2"
5 1/2"
5 1/2"
SYSTEM-20 SYSTEM-20
BTU METER
BTU METER
SYSTEM-20
BTU METER
7 5/8" 7 5/8"
7 5/8" 5"
5"
∅ 0.200" 4pl
∅ 0.200" 4pl
∅ 0.875" 5pl
∅ 0.875" 5pl ∅ 0.875" 5pl
CAUTION (9)
DO NOT drill holes in the enclosure. Use only the openings that are provided.
Use four screws for mounting the Btu meter. The mounting surface must be
structurally sound and capable of withstanding a minimum weight of 40 lbs (18 kg).
Four mounting holes have been provided in the base of the enclosure shown
below. Push out the rubber seals by inserting the mounting screws. Use the
drilling template provided in Appendix 5 of this manual to drill the 4 holes
required to mount the enclosure.
CAUTION (11)
DO NOT USE THE ENCLOSURE AS A TEMPLATE FOR DRILLING HOLES. Do not
drill holes in the enclosure. Use only the openings that are provided.
5/8" Minimum
Hole Size
ONICON Furnished
Copper Tee With
1" Outlet
Customer supplied
threaded tee
(outlet size = line size)
Hot tap thermowells are designed for retrofit applications where it is not
practical to isolate and drain the pipe section prior to installation. The
thermowell is installed through a 1” full port ball valve as shown in the
drawing on next page. A wet tap drilling machine equipped with a 7/8”
drill is required to perform this type of installation.
Install the valve assembly as shown in the drawing on the next page
and then drill the 7/8” hole using the wet tap drilling machine. Once
the valve assembly has been installed and the hole has been drilled,
the thermowell can be inserted into the flow stream without a system
shutdown.
WARNING (13)
SYSTEM MAY BE UNDER HIGH PRESSURE. Hold the conduit box firmly by hand
before slowly loosening the position clamping nut when installing, adjusting
or removing the thermowell. Failure to do this will allow the pressure to
suddenly and rapidly force the thermowell from the pipe, potentially causing
serious injury. The thermowell could also be damaged or break apart causing
a break in the water seal resulting in the loss of large amounts of water.
ONICON Incorporated 727-447-6140 Page 11 www.onicon.com
SYSTEM-20 BTU METER
1. Calculate the insertion force (lbs) required by multiplying the system pressure
(psig) by 0.11. The person inserting the thermowell should ensure adequate
footing for the force required prior to opening the valve.
2. After applying thread seal tape, thread the hot tap adapter into the valve.
Firmly grasp the wiring enclosure, loosen the position clamping nut, open
the valve, and carefully push the thermowell into the flow stream. Use the
attached gauge to set the insertion depth.
CAUTION (14)
Excessive vibration can damage the thermowell. Insert the thermowell to the
proper depth using gauge supplied as shown. Reduce the insertion depth as
necessary if strong vibrations are felt during insertion, making certain that
the tip of the thermowell remains fully in the flow stream.
Carefully tighten the position clamping nut that is located at the top of the 1"
NPT hot tap adapter fitting. Do not release the wiring enclosure until the position
clamping nut has been tightened.
CAUTION (15)
DO NOT OVER TIGHTEN THE POSITION CLAMPING NUT. If fluid leaks, do
not attempt to correct by tightening this nut further. An internal o-ring seals
the fluid. Contact ONICON for assistance in the event of a leak.
WITHDRAWAL 5-1/2”
STOP
NON-REMOVABLE
CONDUIT BOX
1. System pressure will try to push the thermowell out of the flow stream
when the clamping nut is released. Be sure to establish safe footing prior to
loosening the clamping nut. The force pushing out against the thermowell is
the same as the insertion force.
2. Grasp the wiring enclosure firmly, holding the thermowell in the pipe and
then loosen the position clamping nut. Slowly withdraw the thermowell from
the pipe.
When ordered with the System-20, temperature sensors are factory matched and
tagged by serial number to a specific Btu meter. ONICON standard temperature
sensors are also designated and labeled as the SUPPLY or RETURN sensor and
must be installed per these labels.
TEMPERATURE SENSOR
SUPPLY
TEMPERATURE PLASTIC SPACER SLEEVE ELECTRONICS SIGNAL (RED)
PLACE ELECTRONICS
MODULE IN BOX AFTER
CONNECTING WIRES
REFERENCE (BLACK)
S/N 123456
SUPPLY
SIGNAL (RED)
5/8” MINIMUM
HOLE SIZE
CAUTION (18)
DO NOT OVERTIGHTEN. The thermowell completely seals the plumbing
system. Screwing in the sensor just ensures that the sensor tip will remain in
contact with the bottom of the thermowell.
3.3 ELECTRICAL INSTALLATION The System-20 is provided with three ¾" conduit openings along the bottom
of the enclosure for power and signal cables. Two openings are provided with
knockout seals. The power cable should enter the enclosure through the right
hand opening. Do not remove the seals from unused openings. To access the
wiring connections, remove the two cover screws shown below.
TERMINATED UNTERMINATED
JMP1 RS485 LOAD
RS485+
RS485-
RS485COM
IN 1 (+)
IN 1 (-)
IN 2 (+)
IN 2 (-)
IN 3 (+)
IN 3 (-)
SHIELD
OUT 1 (+)
OUT 1 (-)
OUT 2 (+)
OUT 2 (-)
OUT 3 (+)
OUT 3 (-)
COVER SCREWS
1 2 3 4 5 1 2 3 4 1 2 3 4 1 2 3 1 2 3 4 5
RETTEMP (+)
RETTEMP (-)
SUPTEMP (+)
SUPTEMP (-)
SHIELD
(A)
(A)
(B)
(B)
(A)
(A)
(B)
(B)
FREQ IN
24VTURB
TURB FREQ
TURBCOM
24 VDC (+)
4-20mA IN
SIG COMM
24 VDC (-)
2 4 2 4 2 4 2 4
WIRE WIRE WIRE WIRE
J2
TB10
!
EARTH
EARTH
24V L (+)
24V N (-)
24V L (+)
24V N (-)
24V ONLY
WARNING (19)
Disconnect main power before proceeding.
1 2 3
TB8 TURB
TERMINATED UNTERMINATED
3. (-) SUPPLY COMMON (BLACK)
2. (+) FREQUENCY (GREEN)
JMP1 RS485 LOAD
TB1 RS-485 TB2 PULSE IN TB3 PULSE OUT TB4 ANA OUT
1
1. (+) 24 VDC SUPPLY (RED)
1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4
RS485+
RS485-
RS485COM
IN 1 (+)
IN 1 (-)
IN 2 (+)
IN 2 (-)
IN 3 (+)
IN 3 (-)
SHIELD
OUT 1 (+)
OUT 1 (-)
OUT 2 (+)
OUT 2 (-)
OUT 3 (+)
OUT 3 (-)
TB5 TEMPERATURE TB6 RTD SUP TB7 RTD RET TB8 TURB TB9 FLOWMETER
1 2 3 4 5 1 2 3 4 1 2 3 4 1 2 3 1 2 3 4 5
SUPTEMP (+)
SUPTEMP (-)
SHIELD
RETTEMP (+)
RETTEMP (-)
(A)
(A)
(B)
(B)
(A)
(A)
(B)
(B)
FREQ IN
24VTURB
TURB FREQ
TURBCOM
24 VDC (+)
SIG COMM
24 VDC (-)
4-20mA IN
2 4 2 4 2 4 2 4
WIRE WIRE WIRE WIRE
TB10
TB9
!
EARTH
EARTH
24V L (+)
24V N (-)
24V L (+)
24V N (-)
TB10
POWER INPUT
6. EARTH GROUND
5. (-) N
5
SYS-20 AC/DC 4. (+) L
POWER IN
3. EARTH GROUND
2. (-) N 4
1. (+) L
1. This terminal block is ONLY for use with ONICON F-1000 Series Turbine
Flow Meters.
2. Voltage output for use with non-ONICON Flow Meters - 24VDC @ 50 mA
maximum.
3. See meters installation & operation guide for additional information on
properly wiring & grounding the meter.
4. Class II power supply requirements:
20 - 28 V AC/DC, 50 / 60 Hz
500 mA DC or 1A AC total input current.
5. 24 VAC aux power output connection for all flow meters except the F-1000
Series.
WARNING (20)
The System-20 must be connected to earth ground for proper operation.
Failure to do so may result in erratic operation.
CAUTION (21)
Minimum temperature rating of the cable to be connected to the field wiring
terminals, 140°F (60°C).
TERMINATED UNTERMINATED
TB1 RS-485 TB2 PULSE IN TB3 PULSE OUT TB4 ANA OUT
1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4
1 2 3 4 5 6
RS485+
RS485-
RS485COM
IN 1 (+)
IN 1 (-)
IN 2 (+)
IN 2 (-)
IN 3 (+)
IN 3 (-)
SHIELD
OUT 1 (+)
OUT 1 (-)
OUT 2 (+)
OUT 2 (-)
OUT 3 (+)
OUT 3 (-)
TB5 TEMPERATURE
1 2 3 4 5 1
TB6 RTD SUP
2 3 4 1
TB7 RTD RET
2 3 4 1
TB8 TURB
2 3 1
TB9 FLOWMETER
2 3 4 5
PULSE OUTPUT
RETTEMP (-)
SUPTEMP (+)
SUPTEMP (-)
SHIELD
(A)
(B)
(B)
(A)
(B)
(B)
(A)
(A)
FREQ IN
SIG COMM
24VTURB
TURB FREQ
TURBCOM
24 VDC (+)
4-20mA IN
24 VDC (-)
2 4 2 4 2 4 2 4
5 - (+) PULSE OUT 3
WIRE WIRE WIRE WIRE
TB10
24V N (-)
EARTH
24V L (+)
24V N (-)
EARTH
24V ONLY
2 - (-) PULSE OUT 1
1 - (+) PULSE OUT 1
TB2
PULSE INPUT
1 2 3 4 5 6
6 - (-) PULSE IN 3
5 - (+) PULSE IN 3
4 - (-) PULSE IN 2 2
3 - (+) PULSE IN 2
2 - (-) PULSE IN 1
1 - (+) PULSE IN 1
1 - 2 = 120 Ω
JMP1 2 - 3 = NON TERMINATED
RS485 TERMINATION
1 2 3 4
TB1
RS485 OUTPUT
TERMINATED UNTERMINATED
1. (+) RS485
JMP1 RS485 LOAD
TB1 RS-485 TB2 PULSE IN TB3 PULSE OUT TB4 ANA OUT
2. (-) RS485
1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4
1 2 3 4
3. RS485 COMMON
RS485+
RS485-
RS485COM
IN 1 (+)
IN 1 (-)
IN 2 (+)
IN 2 (-)
IN 3 (+)
IN 3 (-)
SHIELD
OUT 1 (+)
OUT 1 (-)
OUT 2 (+)
OUT 2 (-)
OUT 3 (+)
OUT 3 (-)
TB4
JP3
RETTEMP (-)
SUPTEMP (+)
SUPTEMP (-)
SHIELD
(A)
(B)
(B)
(A)
(B)
(B)
(A)
(A)
FREQ IN
SIG COMM
TURB FREQ
TURBCOM
24 VDC (+)
4-20mA IN
24 VDC (-)
TB10
!
1. (+) 4-20 mA OUT
24V L (+)
24V N (-)
EARTH
24V L (+)
24V N (-)
EARTH
24V ONLY
1 2 3 4 5
TB5
ONICON FIXED RANGE OR
SCALED INPUT ANALOG
TEMPERATURE SENSORS
5. (-) RETURN TEMP
4. (+) RETURN TEMP
3. SHIELD 1
2. (-) SUPPLY TEMP
1. (+) SUPPLY TEMP
1 2 3 4
TB6
RTDs SUPPLY
TERMINATED UNTERMINATED
2. (A) COMPENSATION LEAD (not used w/ 2 wire RTD)
1. (A) RTD SIGNAL LEAD
JMP1 RS485 LOAD
TB1 RS-485 TB2 PULSE IN TB3 PULSE OUT TB4 ANA OUT
1 2 3 4 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4
RS485+
RS485-
RS485COM
IN 1 (+)
IN 1 (-)
IN 2 (+)
IN 2 (-)
IN 3 (+)
IN 3 (-)
OUT 1 (+)
OUT 1 (-)
OUT 2 (+)
OUT 2 (-)
OUT 3 (+)
OUT 3 (-)
SHIELD
TB5 TEMPERATURE TB6 RTD SUP TB7 RTD RET TB8 TURB TB9 FLOWMETER
1 2 3 4 5 1 2 3 4 1 2 3 4 1 2 3 1 2 3 4 5
1 2 3 4
SUPTEMP (+)
SUPTEMP (-)
SHIELD
RETTEMP (+)
RETTEMP (-)
(A)
(A)
(B)
(B)
(A)
(A)
(B)
(B)
FREQ IN
24VTURB
TURB FREQ
TURBCOM
24 VDC (+)
4-20mA IN
SIG COMM
24 VDC (-)
TB7
2 4
WIRE
2 4
WIRE
2 4
WIRE
2 4
WIRE
RTDs RETURN
AC/DC POWER IN AUX POWER OUT
1 2 3 4 5 6
J2
TB10
EARTH
24V L (+)
24V N (-)
24V L (+)
24V N (-)
24V ONLY
3. (B) RTD SIGNAL LEAD 2
2. (A) COMPENSATION LEAD (not used w/ 2 wire RTD)
1. (A) RTD SIGNAL LEAD
1 - 2 = 2-WIRE RTD
3
RTD SELECTION
2 - 3 = 4-WIRE RTD
JUMPERS
1. This terminal block for use with an ONICON fixed range (O1 & O2) or loop
powered 4-20mA scalable range temperature sensors. See Temperature
Inputs Wiring Diagram on page 20 for additional information.
2. These terminal blocks for use with an 1000 ohms platinum RTD temperature
sensors (R2 & R3). See Temperature Inputs Wiring Diagram on page 20 for
additional information.
3. Select jumper position 1 & 2 for 2-wire RTD or 2 & 3 for 4-wire RTD.
1 2 3 4 5
1 2 3 4
1 2 3 4
4.1 START-UP When power is first applied to the meter the display will be illuminated and the
following start screen will appear. Momentarily press SEL (select) to access the
operating mode (User Screens) display pages.
User Screens !
Commissioning
NEXT
SEL
Verify that the meter is functional by stepping through the display pages and
confirming the flow rate and temperature data is within expected norms.
Momentarily press NEXT or BACK to change the displayed page. A complete list
of the display pages is provided on the following pages.
When reviewing the Supply and Return temperature display pages, note
which one has the word “FLOW” in the lower left corner of the page. This is an
indication of the flow sensor location in the piping system. Verify the actual
location of the flow sensor in the piping system. It is critical that the correct
location (supply or return) be programmed into the meter.
CAUTION (23)
During start-up and commissioning, the FLOW location must be properly
identified as being in the supply or return pipe of the heat exchange circuit.
The sensor’s position must then be programmed into the meter. Failure to do
so will result in significant errors in both the flow and energy measurements.
To return to the commissioning mode from the user screens, momentarily press
MENU. The following page will appear. Momentarily press EXIT to return to the
start screen.
BACK Run hours ! BACK Volume Total ! BACK Run hours ! BACK Energy Total !
NEXT 0 NEXT 0 NEXT 0 NEXT 0
MENU hours MENU gallons x 1 MENU hours MENU Mode 2 kBtu
BACK Auxiliary Input 2 ! BACK Volume Rate ! BACK Auxiliary Input 2 ! BACK Volume Total !
NEXT 0 NEXT 0 0 0
NEXT NEXT
Counts
MENU gpm x 1
MENU MENU
Counts MENU Mode 2 gallons x 1
BACK Auxiliary Input 1 ! BACK Supply ! BACK Auxiliary Input 1 ! BACK Energy Rate !
Temperature
0 0 0
NEXT NEXT
0.0 NEXT NEXT
MENU
Counts MENU Deg F MENU
Counts MENU kBtu/h x 1
BACK Delta Temperature ! BACK Return ! BACK Mode Status ! BACK Volume Rate !
Temperature
0.0 Mode 2 0
NEXT NEXT 0.0 NEXT NEXT
BACK Return !
Temperature
NEXT 0.0
MENU Deg F
EXIT User Energy Total EXIT YTD Volume EXIT User Energy Total EXIT YTD Energy
BACK BACK BACK BACK
NEXT 0 NEXT 0 NEXT 0 NEXT 0
MENU KBtu MENU gallons MENU Mode 2 kBtu MENU Mode 2 kBtu
EXIT Prev. Yr Volume EXIT Prev. Yr Energy EXIT User Energy Total EXIT YTD Volume
BACK BACK
0
BACK BACK
NEXT 0 NEXT 0
Versions Flow Meter
Max 200
EXIT EXIT MENU
MENU
BACK App: BACK Serial Number
NEXT Boot: NEXT
MENU MENU
MENU
MENU
4.2 COMMISSIONING The last step in the installation process is commissioning the meter.
Commissioning is a two-step process. The first step is to review the mechanical
installation to confirm that the flow sensor and temperature sensor(s) are
properly located in the piping system. The second step is a review of the
meter program settings. Both steps must be completed in order to finish the
installation. A simple commissioning checklist is shown below. A copy of this may
be found online at www.onicon.com/system20.html.
During initial power-up, the display pages will appear when the commissioning option EXIT Flow Meter
Serial Number
is selected. The settings shown below allow the installer to set MODBUS® or BACnet®
BACK
NEXT XXXXXX
parameters, the flow sensor location (supply or return pipe) and the date and time. If the
EDIT
factory pre-programmed engineering units for flow, energy and temperature are correct, EXIT Location Tag
press SAVE to exit commissioning once the correct date has been set. Momentarily press BACK
Text
NEXT if you wish access the remaining commissioning mode display pages shown on the
NEXT
EDIT
following pages.
EXIT Set Meter
BACK
NEXT edits units of
measure
NEXT
SAVE completes install
SAVE with current settings
EDIT
EXIT Flow Input Source EXIT Flow Input Source EXIT Energy Rate
BACK
EXIT BACnet Address BACK
4-20Ma
BACK
Frequency NEXT
kBtu/h x 1
NEXT NEXT
BACK
1 EDIT EDIT EDIT Select Units
NEXT
EDIT 0 - 127
EXIT Flow Damping EXIT Flow Damping EXIT Energy Rate Multiplier
BACK
EXIT Instance Number BACK
NEXT
1
BACK
NEXT
1 NEXT kBtu/h x 1
BACK
NEXT
57017 EDIT 1 - 32 EDIT 1 - 32 EDIT
EDIT 0 - 4194302
EXIT Flow Rate Units EXIT Meter Volume Units EXIT Energy Damping EXIT Temperature Sensor
BACK
Type
EXIT Baud Rate BACK
gpm x 1
BACK
gallons NEXT
1 BACK
1k Ohm RTD
NEXT NEXT NEXT
BACK
NEXT
38400 EDIT Select Units EDIT Select Units EDIT 1 - 32 EDIT
EDIT
NEXT
kBtu x 1 BACK
XXXXXX
BACK
Volume Total
NEXT NEXT
EDIT EDIT EDIT Select Type
EXIT Energy Rate EXIT Temperature Sensor EXIT Temperature Sensor EXIT Pulse Output 3
BACK Type Type
NEXT
kBtu/h x 1 BACK
Scalable
BACK
ONICON
BACK
Alarm
NEXT NEXT NEXT
EDIT Select Units EDIT EDIT EDIT Select Type
EXIT Energy Rate Multiplier EXIT Supply Temperature EXIT Supply Temperature EXIT Pulse Duration
BACK 4mA Offset
X
BACK
kBtu/h x 1
BACK BACK
NEXT NEXT NEXT
+0.000 NEXT
500 ms
EDIT EDIT EDIT EDIT
Return Temperature
EXIT EXIT Return Temperature EXIT Analog Output
4mA Offset
BACK BACK BACK
NEXT
X
NEXT
+0.000 NEXT Energy Rate
EDIT EDIT EDIT Select Type
Return Temperature
EXIT EXIT Return Temperature EXIT Analog Volts Signal
20mA Slope
XXX
BACK BACK BACK
NEXT NEXT 10.000 NEXT 0 - 10V
EDIT EDIT EDIT Select Signal
EXIT
Configure Auxiliary
Input 3
BACK
NEXT
Pulse
EDIT
Initial Security
Seal Here
SECTION 5.0 The ONICON System-20 has self diagnostic functions that continually monitor
DIAGNOSTIC key operating parameters. A list of the alarm messages is shown below.
FUNCTIONS
Displayed
Description
Message
System Fault This message indicates a hardware malfunction. The meter
will not calculate energy in this state.
Dt< Minimum This is a warning message that the delta temperature is low.
Empty Pipe The pipe is empty.
Flow RTD Open The SUPPLY temperature sensor in the flow body is reading
open. The meter will not calculate energy in this state.
Flow RTD Short The SUPPLY temperature sensor in the flow body is reading
as a short circuit. The meter will not calculate energy in this
state.
Remote RTD The remote RETURN temperature sensor is reading open. The
Open meter will not calculate energy in this state.
Remote RTD The remote RETURN temperature sensor is reading as a short
Short circuit. The meter will not calculate energy in this state.
Low Flow The flow reading is below the minimum flow threshold of
the meter (e.g. 0.03 gpm for ½” meter). The meter will not
calculate energy in this state.
High Flow This is a warning message that the flow reading is above the
maximum flow rate of the meter (e.g. 15 gpm for ½” meter).
SECTION 6.0 BACnet MS/TP, serial interface connections are connected at terminal block TB1.
BACNET® MS/TP
Transceiver: 2-wire, half-duplex (1/4 unit load)
BACnet® address (MAC address) range: 1 - 255 (Default: 017)
Device Instance: 0 - 4,194,303 (Default: 57017)
Baud rate: 9600, 19200, 38400 or 76800 (Default: 38400)
Termination: 120 Ω or none (Default: none)
Biasing: None
Flow control: None
6.1 BACNET OBJECT TYPES BACnet Object Type and Number of Objects Implemented
Device 1
Analog Input 10
Analog Value 34
Binary Value 12
Multi-State Object 1
Trend Log Multiple 1
Objects List
Object Identifier Function
Analog input 1 Energy rate BACnet Engineering Units for Analog Inputs (Defaults)
Analog input 2 Volume rate Energy rate: kBtu/h, tons, kW or MW
Analog input 3 Supply temperature
Volume rate: gpm, l/s, ft3/m or m3/h
Analog input 4 Return temperature
Analog input 5 Delta temperature Temperature: °F or °C
Analog input 6* Peak energy rate
Analog input 7* Average delta temp
* Time interval set by Trend Log Object
Analog value 33 Aux pulse input 3 total Volume: gallons, liters, ft3 or m3
Auxiliary pulse inputs: No units (counts)
Analog value 34 Run hours
Run hours: Hours
* Time interval set by Trend Log Object
Multi-state Object
Object Identifier Description Notes
Multi-state value 1 Reports the operating status of the meter Numeric values indicate meter
status.
1 = Normal
9 = Comm error
SECTION 7.0 MODBUS, serial interface connections are connected at terminal block TB1.
MODBUS Transceiver: 2-wire, half-duplex (1/4 unit load)
MODBUS address range: 1 - 247 (Default: 017)
Data format: 8 bit
Stop Bits: 1
Parity: None (Default), Odd, or Even
Byte Order: ABCD
Baud rate: 4800, 9600, 19200, 38400, 57600, 76800 or 115200 (Default: 9600)
Termination: Jumper selectable 120Ω resistor (See page 18)
Biasing: None
30017 Flow Temperature - °F Input Register Floating Point Register (1 of 2) Temperature measured by RTD in flow
meter location
30018 Flow Temperature - °F Input Register Floating Point Register (2 of 2) Temperature measured by RTD in flow
meter location
30019 Flow Temperature - °C Input Register Floating Point Register (1 of 2) Temperature measured by RTD in flow
meter location
30020 Flow Temperature - °C Input Register Floating Point Register (2 of 2) Temperature measured by RTD in flow
meter location
30021 Remote Temperature - °F Input Register Floating Point Register (1 of 2) Temperature measured by remote RTD
30022 Remote Temperature - °F Input Register Floating Point Register (2 of 2) Temperature measured by remote RTD
30023 Remote Temperature - °C Input Register Floating Point Register (1 of 2) Temperature measured by remote RTD
30024 Remote Temperature - °C Input Register Floating Point Register (2 of 2) Temperature measured by remote RTD
30025 Delta Temperature - °F Input Register Floating Point Register (1 of 2)
30026 Delta Temperature - °F Input Register Floating Point Register (2 of 2)
30027 Delta Temperature - °C Input Register Floating Point Register (1 of 2)
30028 Delta Temperature - °C Input Register Floating Point Register (2 of 2)
30029 Energy Total - Single Mode - kBtu Input Register Floating Point Register (1 of 2)
30030 Energy Total - Single Mode - kBtu Input Register Floating Point Register (2 of 2)
30031 Energy Total - Single Mode - MBtu Input Register Floating Point Register (1 of 2)
30032 Energy Total - Single Mode - MBtu Input Register Floating Point Register (2 of 2)
30033 Energy Total - Single Mode - TonHr Input Register Floating Point Register (1 of 2)
30034 Energy Total - Single Mode - TonHr Input Register Floating Point Register (2 of 2)
30035 Energy Total - Single Mode - MJ Input Register Floating Point Register (1 of 2)
30036 Energy Total - Single Mode - MJ Input Register Floating Point Register (2 of 2)
30037 Energy Total - Single Mode - kWHr Input Register Floating Point Register (1 of 2)
30038 Energy Total - Single Mode - kWHr Input Register Floating Point Register (2 of 2)
30039 Energy Total - Mode 1 - kBtu Input Register Floating Point Register (1 of 2)
30040 Energy Total - Mode 1 - kBtu Input Register Floating Point Register (2 of 2)
30041 Energy Total - Mode 1 - MBtu Input Register Floating Point Register (1 of 2)
30042 Energy Total - Mode 1 - MBtu Input Register Floating Point Register (2 of 2)
30043 Energy Total - Mode 1 - TonHr Input Register Floating Point Register (1 of 2)
30044 Energy Total - Mode 1 - TonHr Input Register Floating Point Register (2 of 2)
30045 Energy Total - Mode 1 - MJ Input Register Floating Point Register (1 of 2)
30046 Energy Total - Mode 1 - MJ Input Register Floating Point Register (2 of 2)
30047 Energy Total - Mode 1 - kWHr Input Register Floating Point Register (1 of 2)
30048 Energy Total - Mode 1 - kWHr Input Register Floating Point Register (2 of 2)
30049 Energy Total - Mode 2 - kBtu Input Register Floating Point Register (1 of 2)
30050 Energy Total - Mode 2 - kBtu Input Register Floating Point Register (2 of 2)
30051 Energy Total - Mode 2 - MBtu Input Register Floating Point Register (1 of 2)
30052 Energy Total - Mode 2 - MBtu Input Register Floating Point Register (2 of 2)
30053 Energy Total - Mode 2 - TonHr Input Register Floating Point Register (1 of 2)
30054 Energy Total - Mode 2 - TonHr Input Register Floating Point Register (2 of 2)
30106 Previous Year Energy Total - Mode 1 - MJ Input Register Floating Point Register (2 of 2)
30107 Previous Year Energy Total - Mode 1 - kWHr Input Register Floating Point Register (1 of 2)
30108 Previous Year Energy Total - Mode 1 - kWHr Input Register Floating Point Register (2 of 2)
30109 Previous Year Energy Total - Mode 2 - kBtu Input Register Floating Point Register (1 of 2)
30110 Previous Year Energy Total - Mode 2 - kBtu Input Register Floating Point Register (2 of 2)
30111 Previous Year Energy Total - Mode 2 - MBtu Input Register Floating Point Register (1 of 2)
30112 Previous Year Energy Total - Mode 2 - MBtu Input Register Floating Point Register (2 of 2)
30113 Previous Year Energy Total - Mode 2 - TonHr Input Register Floating Point Register (1 of 2)
30114 Previous Year Energy Total - Mode 2 - TonHr Input Register Floating Point Register (2 of 2)
30115 Previous Year Energy Total - Mode 2 - MJ Input Register Floating Point Register (1 of 2)
30116 Previous Year Energy Total - Mode 2 - MJ Input Register Floating Point Register (2 of 2)
30117 Previous Year Energy Total - Mode 2 - kWHr Input Register Floating Point Register (1 of 2)
30118 Previous Year Energy Total - Mode 2 - kWHr Input Register Floating Point Register (2 of 2)
30119 User Defined Energy Total - Single Mode - kBtu Input Register Floating Point Register (1 of 2)
30120 User Defined Energy Total - Single Mode - kBtu Input Register Floating Point Register (2 of 2)
30121 User Defined Energy Total - Single Mode - MBtu Input Register Floating Point Register (1 of 2)
30122 User Defined Energy Total - Single Mode - MBtu Input Register Floating Point Register (2 of 2)
30123 User Defined Energy Total - Single Mode - TonHr Input Register Floating Point Register (1 of 2)
30124 User Defined Energy Total - Single Mode - TonHr Input Register Floating Point Register (2 of 2)
30125 User Defined Energy Total - Single Mode - MJ Input Register Floating Point Register (1 of 2)
30126 User Defined Energy Total - Single Mode - MJ Input Register Floating Point Register (2 of 2)
30127 User Defined Energy Total - Single Mode - kWHr Input Register Floating Point Register (1 of 2)
30128 User Defined Energy Total - Single Mode - kWHr Input Register Floating Point Register (2 of 2)
30129 User Defined Energy Total - Mode 1 - kBtu Input Register Floating Point Register (1 of 2)
30130 User Defined Energy Total - Mode 1 - kBtu Input Register Floating Point Register (2 of 2)
30131 User Defined Energy Total - Mode 1 - MBtu Input Register Floating Point Register (1 of 2)
30132 User Defined Energy Total - Mode 1 - MBtu Input Register Floating Point Register (2 of 2)
30133 User Defined Energy Total - Mode 1 - TonHr Input Register Floating Point Register (1 of 2)
30134 User Defined Energy Total - Mode 1 - TonHr Input Register Floating Point Register (2 of 2)
30135 User Defined Energy Total - Mode 1 - MJ Input Register Floating Point Register (1 of 2)
30136 User Defined Energy Total - Mode 1 - MJ Input Register Floating Point Register (2 of 2)
30137 User Defined Energy Total - Mode 1 - kWHr Input Register Floating Point Register (1 of 2)
30138 User Defined Energy Total - Mode 1 - kWHr Input Register Floating Point Register (2 of 2)
30139 User Defined Energy Total - Mode 2 - kBtu Input Register Floating Point Register (1 of 2)
30140 User Defined Energy Total - Mode 2 - kBtu Input Register Floating Point Register (2 of 2)
30141 User Defined Energy Total - Mode 2 - MBtu Input Register Floating Point Register (1 of 2)
30142 User Defined Energy Total - Mode 2 - MBtu Input Register Floating Point Register (2 of 2)
30143 User Defined Energy Total - Mode 2 - TonHr Input Register Floating Point Register (1 of 2)
30144 User Defined Energy Total - Mode 2 - TonHr Input Register Floating Point Register (2 of 2)
30145 User Defined Energy Total - Mode 2 - MJ Input Register Floating Point Register (1 of 2)
30146 User Defined Energy Total - Mode 2 - MJ Input Register Floating Point Register (2 of 2)
30147 User Defined Energy Total - Mode 2 - kWHr Input Register Floating Point Register (1 of 2)
30148 User Defined Energy Total - Mode 2 - kWHr Input Register Floating Point Register (2 of 2)
30149 Volume Total - Single Mode - Gal Input Register Floating Point Register (1 of 2)
30150 Volume Total - Single Mode - Gal Input Register Floating Point Register (2 of 2)
30151 Volume Total - Single Mode - Liters Input Register Floating Point Register (1 of 2)
30152 Volume Total - Single Mode - Liters Input Register Floating Point Register (2 of 2)
30153 Volume Total - Single Mode - ft3 Input Register Floating Point Register (1 of 2)
30154 Volume Total - Single Mode - ft3 Input Register Floating Point Register (2 of 2)
30155 Volume Total - Single Mode - m3 Input Register Floating Point Register (1 of 2)
30156 Volume Total - Single Mode - m3 Input Register Floating Point Register (2 of 2)
30157 Volume Total - Mode 1 - Gal Input Register Floating Point Register (1 of 2)
30158 Volume Total - Mode 1 - Gal Input Register Floating Point Register (2 of 2)
30159 Volume Total - Mode 1 - Liters Input Register Floating Point Register (1 of 2)
30160 Volume Total - Mode 1 - Liters Input Register Floating Point Register (2 of 2)
30161 Volume Total - Mode 1 - ft3 Input Register Floating Point Register (1 of 2)
30162 Volume Total - Mode 1 - ft3 Input Register Floating Point Register (2 of 2)
30163 Volume Total - Mode 1 - m3 Input Register Floating Point Register (1 of 2)
30164 Volume Total - Mode 1 - m3 Input Register Floating Point Register (2 of 2)
30165 Volume Total - Mode 2 - Gal Input Register Floating Point Register (1 of 2)
30166 Volume Total - Mode 2 - Gal Input Register Floating Point Register (2 of 2)
30167 Volume Total - Mode 2 - Liters Input Register Floating Point Register (1 of 2)
30168 Volume Total - Mode 2 - Liters Input Register Floating Point Register (2 of 2)
30169 Volume Total - Mode 2 - ft3 Input Register Floating Point Register (1 of 2)
30170 Volume Total - Mode 2 - ft3 Input Register Floating Point Register (2 of 2)
30171 Volume Total - Mode 2 - m3 Input Register Floating Point Register (1 of 2)
30172 Volume Total - Mode 2 - m3 Input Register Floating Point Register (2 of 2)
30173 Year to Date Volume Total - Single Mode - Gal Input Register Floating Point Register (1 of 2)
30174 Year to Date Volume Total - Single Mode - Gal Input Register Floating Point Register (2 of 2)
30175 Year to Date Volume Total - Single Mode - Liters Input Register Floating Point Register (1 of 2)
30176 Year to Date Volume Total - Single Mode - Liters Input Register Floating Point Register (2 of 2)
30177 Year to Date Volume Total - Single Mode - ft3 Input Register Floating Point Register (1 of 2)
30178 Year to Date Volume Total - Single Mode - ft3 Input Register Floating Point Register (2 of 2)
30179 Year to Date Volume Total - Single Mode - m3 Input Register Floating Point Register (1 of 2)
30180 Year to Date Volume Total - Single Mode - m3 Input Register Floating Point Register (2 of 2)
30181 Year to Date Volume Total - Mode 1 - Gal Input Register Floating Point Register (1 of 2)
30182 Year to Date Volume Total - Mode 1 - Gal Input Register Floating Point Register (2 of 2)
30183 Year to Date Volume Total - Mode 1 - Liters Input Register Floating Point Register (1 of 2)
30184 Year to Date Volume Total - Mode 1 - Liters Input Register Floating Point Register (2 of 2)
30185 Year to Date Volume Total - Mode 1 - ft3 Input Register Floating Point Register (1 of 2)
30186 Year to Date Volume Total - Mode 1 - ft3 Input Register Floating Point Register (2 of 2)
30187 Year to Date Volume Total - Mode 1 - m3 Input Register Floating Point Register (1 of 2)
30188 Year to Date Volume Total - Mode 1 - m3 Input Register Floating Point Register (2 of 2)
30189 Year to Date Volume Total - Mode 2 - Gal Input Register Floating Point Register (1 of 2)
30190 Year to Date Volume Total - Mode 2 - Gal Input Register Floating Point Register (2 of 2)
30191 Year to Date Volume Total - Mode 2 - Liters Input Register Floating Point Register (1 of 2)
30192 Year to Date Volume Total - Mode 2 - Liters Input Register Floating Point Register (2 of 2)
30193 Year to Date Volume Total - Mode 2 - ft3 Input Register Floating Point Register (1 of 2)
30194 Year to Date Volume Total - Mode 2 - ft3 Input Register Floating Point Register (2 of 2)
30195 Year to Date Volume Total - Mode 2 - m3 Input Register Floating Point Register (1 of 2)
30196 Year to Date Volume Total - Mode 2 - m3 Input Register Floating Point Register (2 of 2)
30197 Previous Year Volume Total - Single Mode - Gal Input Register Floating Point Register (1 of 2)
30198 Previous Year Volume Total - Single Mode - Gal Input Register Floating Point Register (2 of 2)
30199 Previous Year Volume Total - Single Mode - Liters Input Register Floating Point Register (1 of 2)
30200 Previous Year Volume Total - Single Mode - Liters Input Register Floating Point Register (2 of 2)
30201 Previous Year Volume Total - Single Mode - ft3 Input Register Floating Point Register (1 of 2)
30202 Previous Year Volume Total - Single Mode - ft3 Input Register Floating Point Register (2 of 2)
30203 Previous Year Volume Total - Single Mode - m3 Input Register Floating Point Register (1 of 2)
30204 Previous Year Volume Total - Single Mode - m3 Input Register Floating Point Register (2 of 2)
30205 Previous Year Volume Total - Mode 1 - Gal Input Register Floating Point Register (1 of 2)
30206 Previous Year Volume Total - Mode 1 - Gal Input Register Floating Point Register (2 of 2)
30207 Previous Year Volume Total - Mode 1 - Liters Input Register Floating Point Register (1 of 2)
30208 Previous Year Volume Total - Mode 1 - Liters Input Register Floating Point Register (2 of 2)
30209 Previous Year Volume Total - Mode 1 - ft3 Input Register Floating Point Register (1 of 2)
30210 Previous Year Volume Total - Mode 1 - ft3 Input Register Floating Point Register (2 of 2)
30211 Previous Year Volume Total - Mode 1 - m3 Input Register Floating Point Register (1 of 2)
30212 Previous Year Volume Total - Mode 1 - m3 Input Register Floating Point Register (2 of 2)
30213 Previous Year Volume Total - Mode 2 - Gal Input Register Floating Point Register (1 of 2)
30214 Previous Year Volume Total - Mode 2 - Gal Input Register Floating Point Register (2 of 2)
30215 Previous Year Volume Total - Mode 2 - Liters Input Register Floating Point Register (1 of 2)
30216 Previous Year Volume Total - Mode 2 - Liters Input Register Floating Point Register (2 of 2)
30217 Previous Year Volume Total - Mode 2 - ft3 Input Register Floating Point Register (1 of 2)
30218 Previous Year Volume Total - Mode 2 - ft3 Input Register Floating Point Register (2 of 2)
30219 Previous Year Volume Total - Mode 2 - m3 Input Register Floating Point Register (1 of 2)
30220 Previous Year Volume Total - Mode 2 - m3 Input Register Floating Point Register (2 of 2)
30221 User Defined Volume Total - Single Mode - Gal Input Register Floating Point Register (1 of 2)
30222 User Defined Volume Total - Single Mode - Gal Input Register Floating Point Register (2 of 2)
30223 User Defined Volume Total - Single Mode - Liters Input Register Floating Point Register (1 of 2)
30224 User Defined Volume Total - Single Mode - Liters Input Register Floating Point Register (2 of 2)
30225 User Defined Volume Total - Single Mode - ft3 Input Register Floating Point Register (1 of 2)
30226 User Defined Volume Total - Single Mode - ft3 Input Register Floating Point Register (2 of 2)
30227 User Defined Volume Total - Single Mode - m3 Input Register Floating Point Register (1 of 2)
30228 User Defined Volume Total - Single Mode - m3 Input Register Floating Point Register (2 of 2)
30229 User Defined Volume Total - Mode 1 - Gal Input Register Floating Point Register (1 of 2)
30230 User Defined Volume Total - Mode 1 - Gal Input Register Floating Point Register (2 of 2)
30231 User Defined Volume Total - Mode 1 - Liters Input Register Floating Point Register (1 of 2)
30232 User Defined Volume Total - Mode 1 - Liters Input Register Floating Point Register (2 of 2)
30233 User Defined Volume Total - Mode 1 - ft3 Input Register Floating Point Register (1 of 2)
30234 User Defined Volume Total - Mode 1 - ft3 Input Register Floating Point Register (2 of 2)
30235 User Defined Volume Total - Mode 1 - m3 Input Register Floating Point Register (1 of 2)
30236 User Defined Volume Total - Mode 1 - m3 Input Register Floating Point Register (2 of 2)
30237 User Defined Volume Total - Mode 2 - Gal Input Register Floating Point Register (1 of 2)
30238 User Defined Volume Total - Mode 2 - Gal Input Register Floating Point Register (2 of 2)
30239 User Defined Volume Total - Mode 2 - Liters Input Register Floating Point Register (1 of 2)
30240 User Defined Volume Total - Mode 2 - Liters Input Register Floating Point Register (2 of 2)
30241 User Defined Volume Total - Mode 2 - ft3 Input Register Floating Point Register (1 of 2)
30242 User Defined Volume Total - Mode 2 - ft3 Input Register Floating Point Register (2 of 2)
30243 User Defined Volume Total - Mode 2 - m3 Input Register Floating Point Register (1 of 2)
30244 User Defined Volume Total - Mode 2 - m3 Input Register Floating Point Register (2 of 2)
30245 Auxiliary Pulse Input Count- Input 1 Input Register Floating Point Register (1 of 2) Unitless count. Value is representative
of the total number of pulses received
on input.
30246 Auxiliary Pulse Input Count- Input 1 Input Register Floating Point Register (2 of 2) Unitless count. Value is representative
of the total number of pulses received
on input.
30247 Auxiliary Pulse Input Count- Input 2 Input Register Floating Point Register (1 of 2) Unitless count. Value is representative
of the total number of pulses received
on input.
30248 Auxiliary Pulse Input Count- Input 2 Input Register Floating Point Register (2 of 2) Unitless count. Value is representative
of the total number of pulses received
on input.
30249 Auxiliary Pulse Input Count- Input 3 Input Register Floating Point Register (1 of 2) Unitless count. Value is representative
of the total number of pulses received
on input.
30250 Auxiliary Pulse Input Count- Input 3 Input Register Floating Point Register (2 of 2) Unitless count. Value is representative
of the total number of pulses received
on input.
7.2 DIAGNOSTIC FUNCTION CODE The MODBUS implementation of the System-20 supports the use of function
code 08, Diagnostic.
When using function code 08, you must also specify the “sub-function” code
when sending the message to the System-20.
Description of Sub-functions:
The data passed to the System-20 in the request data field is to be returned
(looped back) in the response. The entire response message should be identical
to the request.
The System-20 serial line port will be initialized and restarted, and all of its
communications event counters are cleared. If the port is currently in Listen Only
Mode, no response is returned. This function is the only one that brings the port
out of Listen Only Mode. If the port is not currently in Listen Only Mode, a normal
response is returned. This occurs before the restart is executed.
Forces the System-20 to its Listen Only Mode for MODBUS communications.
This isolates it from the other devices on the network, allowing them to continue
communicating without interruption from the addressed System-20. No response
is returned. When the remote device enters its Listen Only Mode, all active
communication controls are turned off. The Ready watchdog timer is allowed to
expire, locking the controls off. While the device is in this mode, any MODBUS
messages addressed to it or broadcast are monitored, but no actions will be
taken and no responses will be sent.
The only function that will be processed after the mode is entered will be the
Restart Communications Option function (function code 8, sub-function 1).
The response data field from the System-20 returns the quantity of messages
that it has detected on the communications system since its last restart, restart
communications option, or power-up.
The response data field returns the quantity of CRC errors encountered by the
System-20 since its last restart, restart communications option, or power-up.
The response data field returns the quantity of MODBUS exception responses
returned by the System-20 since its last restart, restart communications option, or
power-up.
The response data field returns the quantity of messages addressed to the
System-20, or broadcast, that the System-20 has processed since its last restart,
restart communications option, or power-up.
The response data field returns the quantity of messages addressed to the
System-20 for which it has returned no response (neither a normal response nor
an exception response), since its last restart, restart communications option, or
power-up.
The response data field returns the quantity of messages addressed to the
System-20 for which it returned a Server Device Busy exception response, since
its last restart, restart communications option, or power-up.
The response data field returns the quantity of messages addressed to the
System-20 that it could not handle due to a character overrun condition, since its
last restart, restart communications option, or power-up. A character overrun is
caused by data characters arriving at the port faster than they can be stored, or
by the loss of a character due to a hardware malfunction.
7.3 REPORT SLAVE ID The MODBUS implementation of the System-20 supports the use of function
FUNCTION CODE code 17, Report Slave ID. When a message is sent to the System-20 requesting to
report the slave ID, the following information is returned:
The System-20 will report data in decimal or HEX, depending on the control
system settings. The data must be converted from decimal/HEX to ASCII in order
to form the string.
APPENDIX
CHANGING RS485 SETTINGS OR METER PROGRAMMING AFTER
COMMISSIONING
RS485 settings and meter programming, including date and time settings, can be
changed after commissioning is complete. In order to accomplish this it will be
necessary to re-open the enclosure (Refer to section 3.3). Once the cover is open
locate the reset and commissioning push-button shown in the drawing below.
Once the cover is open locate the commissioning button shown in the diagram
below. It is immediately to the left of the button marked R. You will need a small
diameter probe (1/16”) to break the seal and press the button. A straightened
paperclip can be used for this. Briefly pressing commissioning once will allow you
to re-enter the commissioning mode. Follow the instructions starting in section
4.1 and re-commission the meter. Once the meter is re-commissioned, install a
new tamper seal over the commissioning button opening.
IMPORTANT NOTE:
It will be necessary to break the seal covering the commissioning push-
button when reentering the commissioning mode. The seal should be
replaced when changes are complete.
Use this drilling template to drill the 4 holes required to mount the
enclosure. The mounting surface must be structurally sound and
capable of withstanding a minimum weight of 40lbs (18kg).
A-2
• (4) Concrete screws - 3/16” X 1.5” with ¼ maximum
hex, Phillips or slot heads
www.onicon.com
SYSTEM-20 BTU METER
2066-1 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 03-18
www.onicon.com • [email protected]
Thermowell Installation
In Welded Pipe
THERMAL INSULATOR
GASKET
COVER
A-3
ensure weathertight seal.
1/2" CONDUIT
PORTS (PLUGGED)
INTEGRAL
JUNCTION BOX
0195-1 11451 South Belcher Road, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 Fax (727) 442-5699 04-14
www.onicon.com E-mail: [email protected]
www.onicon.com
SYSTEM-20 BTU METER
SYSTEM-20 BTU METER
FRENCH TRANSLATION OF ALL WARNING, CAUTION AND IMPORTANT NOTES (Traductions en français de
tous les AVERTISSEMENTS, MISES EN GARDE ET REMARQUES IMPORTANTES)
AVERTISSEMENT 1
Les messages identifiés comme étant des « Avertissements » comportent de l'information
concernant la sécurité personnelle des personnes impliquées dans l'installation, le
fonctionnement et l'entretien de ce produit.
MISE EN GARDE 2
Les messages identifiés comme étant des « Mises en garde » comportent de l'information
concernant les dommages potentiels qui pourraient affecter le produit ou tout autre produit
connexe.
REMARQUE IMPORTANTE 3
Les messages identifiés comme étant des « Remarques importantes » comportent de
l'information essentielle au bon fonctionnement du produit.
AVERTISSEMENT 4
Seul un technicien qualifié devrait tenter d'installer ou d'effectuer l'entretien de ce produit. Des
blessures graves peuvent découler de la mauvaise installation ou utilisation de ce produit.
ATTENTION 5
La batterie du System-20 ne peut pas être ajoutée ou remplacée. Risque d'explosion d'incendie
et de brûlures. NE PAS recharger, désassembler, écraser, chauffer à une température supérieure
à 212 ° F (100 ° C) ou incinérer. Veuillez vérifier vos ordonnances locales pour des informations
concernant la mise au rebut de la batterie.
REMARQUE IMPORTANTE 6
Le System-20 peut être installé à l'extérieur dans des espaces protégés à l'abri de la lumière
directe du soleil, de la pluie, du grésil ou de la neige.
REMARQUE IMPORTANTE 7
Une sélection appropriée du site est essentielle pour garantir la performance de ce compteur
BTU. Le capteur de débit et les capteurs de température doivent être bien placés dans le système
de canalisation afin de garantir la précision de la mesure énergétique.
REMARQUE IMPORTANTE 8
Les composantes du Système de mesure en BTU du Système-20 ONICON doivent être
configurées, programmées et installées ensemble pour créer un système. Mélanger des
composantes provenant de systèmes différents peut conduire à d'importantes erreurs
de mesure.
MISE EN GARDE 9
La liaison des raccords de conduits n'est pas automatique et devrait être fournie dans le cadre de
l'installation.
MISE EN GARDE 10
NE PAS percer de trous dans le boîtier. N'utilisez que les orifices fournis.
MISE EN GARDE 11
NE PAS UTILISER LE BOÎTIER À TITRE DE MODÈLE POUR PERCER DES TROUS. Ne pas percer de
trous dans le boîtier. N'utilisez que les orifices fournis.
REMARQUE IMPORTANTE 12
Il est important de veiller à ce qu'aucune saleté ni autre corps étranger ne pénètre les puits
thermométriques car ceci pourrait avoir un impact sur la réponse thermique du système.
MISE EN GARDE 13
LE SYSTÈME PEUT ÊTRE SOUS HAUTE PRESSION. Assurez-vous de maintenir fermement à la
main la boîte de jonction avant de desserrer lentement l'écrou de serrage de la position lors
de l'installation, du réglage ou du retrait du puits thermométrique. Le non respect de cette
instruction laissera la pression expulser soudainement et rapidement le puits thermométrique
du tuyau, ce qui pourrait entraîner des blessures graves. Le puits thermométrique pourrait
également être endommagé ou brisé, provoquant ainsi une rupture dans le joint hydraulique et
par conséquent la perte de grandes quantités d'eau.
MISE EN GARDE 14
Des vibrations excessives risquent d'endommager le puits thermométrique. Insérez le puits
thermométrique à la profondeur adéquate en utilisant la jauge fournie tel qu'indiqué. Diminuez
la profondeur d'insertion au besoin si des fortes vibrations sont ressenties lors de l'insertion, en
vous assurant que l'extrémité du puits thermométrique reste entièrement dans le flux.
MISE EN GARDE 15
NE PAS TROP SERRER L'ÉCROU DE SERRAGE DE LA POSITION. En cas de fuites de liquide, ne pas
tenter d'y remédier en serrant encore plus l'écrou. Un joint torique d'étanchéité interne retient le
liquide. Veuillez communiquer avec ONICON pour obtenir de l'aide en cas de fuite.
AVERTISSEMENT 16
Maintenez un contrôle ferme sur le boîtier de câblage jusqu'à ce que le puits thermométrique soit
complètement retiré et la vanne complètement fermée.
REMARQUE IMPORTANTE 17
Le fait de faire pivoter le puits thermométrique pendant que vous le retirez délicatement à
travers la vanne permettra d'assurer que l'extrémité inférieure est complètement retirée et
détachée de la vanne. Si vous sentez une résistance en fermant la vanne, ouvrez entièrement la
vanne et faites pivoter le puits pendant que vous le retirez du tuyau.
REMARQUE IMPORTANTE 18
NE PAS TROP SERRER. Le puits thermométrique scelle complètement le système de plomberie. Le
vissage du capteur permet d'assurer que l'extrémité du capteur reste en contact avec le fond du
puits thermométrique.
AVERTISSEMENT 19
Débranchez l'alimentation principale avant de continuer
AVERTISSEMENT 20
Le System-20 doit être connecté à la terre pour un fonctionnement correctement. Ne pas le faire
peut entraîner un fonctionnement erratique
ATTENTION 21
Température nominale minimum du câble à connecter aux bornes de câblage, 140F (60C)
REMARQUE IMPORTANTE 22
Le System-20 doit être utilisé avec une alimentation externe de Classe II. AC/DC
MISE EN GARDE 23
Lors du démarrage et de la mise en service, l'emplacement associé au DÉBIT doit être
correctement identifié dans le tuyau d'alimentation ou de retour du circuit d'échange
thermique. L'emplacement du capteur doit être ensuite programmé dans le compteur. Le non
respect de cette instruction provoquera d'importantes erreurs de mesures du flux et de l'énergie.
ONICON
Flow and Energy Measurement
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699
www.onicon.com • [email protected]