Original instructions

LineStrong-series
Emergency Stop Grab Wire Safety Switch

ABB AB / Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden


www.abb.com/lowvoltage
Read and understand this document
Please read and understand this document before using the products. Please consult your ABB/JOKAB SAFETY
representative if you have any questions or comments.
WARRANTY
ABB/JOKAB SAFETY’s exclusive warranty is that the products are free from defects in materials and workmanship
for a period of one year (or other period if specified) from date of sale by ABB/JOKAB SAFETY.
ABB/JOKAB SAFETY MAKES NO WARRANTY OR REPRESENTATION, EXPRESSED OR IMPLIED,
REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF
THE PRODUCTS, ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OR THEIR INTENDED
USE. ABB/JOKAB SAFETY DISCLAIMS ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED.
LIMITATIONS OF LIABILITY
ABB/JOKAB SAFETY SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL
DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall responsibility of ABB/JOKAB SAFETY for any act exceed the individual price of the product on
which liability asserted.
IN NO EVENT SHALL ABB/JOKAB SAFETY BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER
CLAIMS REGARDING THE PRODUCTS UNLESS ABB/JOKAB SAFETY’S ANALYSIS CONFIRMS THAT THE
PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
SUITABILITY FOR USE
ABB/JOKAB SAFETY shall not be responsible for conformity with any standards, codes, or regulations that apply
to the combination of products in the customer’s application or use of the product. At the customer’s request,
ABB/JOKAB SAFETY will provide applicable third party certification documents identifying ratings and limitations of
use that apply to the products. This information by itself is not sufficient for a complete determination of the
suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended
to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be
suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not
described in this document.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment,
amusement machines, vehicles, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY
WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE ABB/JOKAB SAFETY PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE
INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PERFORMANCE DATA
While every effort has been taken to ensure the accuracy of the information contained in this manual ABB/JOKAB
SAFETY cannot accept responsibility for errors or omissions and reserves the right to make changes and
improvements without notice. Performance data given in this document is provided as a guide for the user in
determining suitability and does not constitute a warranty. It may represent the result of ABB/JOKAB SAFETY’S
test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to
the ABB/JOKAB SAFETY Warranty and Limitations of Liability.

2TLC172248M0201, rev. A 2 www.abb.com/lowvoltage


2012-11-27
Table of Contents
1 Introduction ......................................................................................................................................... 4
Scope ........................................................................................................................................................................ 4
Audience ................................................................................................................................................................... 4
Prerequisites ............................................................................................................................................................. 4
Special notes ............................................................................................................................................................ 4

2 Overview .............................................................................................................................................. 5
General description ................................................................................................................................................... 5
Safety regulations ..................................................................................................................................................... 5
Function description for the variants ......................................................................................................................... 6
3 Connections ...................................................................................................................................... 10
4 Installation and maintenance ........................................................................................................... 11
5 Application example.......................................................................................................................... 16
6 Model overview.................................................................................................................................. 17
Accessories............................................................................................................................................................. 19
7 Technical data ................................................................................................................................... 20
LineStrong1............................................................................................................................................................. 20
LineStrong2 series .................................................................................................................................................. 21
LineStrong3 series .................................................................................................................................................. 23
8 EC Declaration of conformity ........................................................................................................... 25

2TLC172248M0201, rev. A 3 www.abb.com/lowvoltage


2012-11-27
1 Introduction
Scope
The purpose of these instructions is to describe the Emergency Stop Grab Wire Safety Switch system LineStrong-
series, and to provide the necessary information required for assembly, installation, checks and adjustments after
installation, and maintenance. The instructions also include information necessary to connect LineStrong to a
safety circuit.

Audience
This document is intended for authorized installation personnel.

Prerequisites
It is assumed that the reader of this document has knowledge of the following:
• Basic knowledge of ABB/Jokab Safety products.
• Knowledge of machine safety.

Special notes
Pay attention to the following special notes in the document:

Danger of severe personal injury!


Warning! An instruction or procedure which, if not carried out correctly, may result in injury to the technician
or other personnel.

Danger of damage to the equipment!


Caution!
An instruction or procedure which, if not carried out correctly, may damage the equipment.

NB: Notes are used to provide important or explanatory information.

2TLC172248M0201, rev. A 4 www.abb.com/lowvoltage


2012-11-27
2 Overview
General description
All ABB Jokab Safety Emergency strop grab wire safety switches conform to European Standard EN ISO 13850
and IEC 60947-5-5. They have a positive mechanical linkage between the switch contacts and the wire as per
IEC 60947-5-1. The emergency stop switches are brought into the operational condition by pre-tensioning the wire
by use of a tensioner / gripper device which clamps the wire and then hooks to the switch eyebolts. Correct tension
can be observed by viewing the tension indicator on the switch housing. Once tensioned the switch contact blocks
can be set to the operational condition (safety contacts closed, auxiliary contacts open) by pressing a blue reset
button on the switch cover.
All of the grab wire safety switches have wire-breakage monitoring. On pulling or breakage (tension loss) of the
wire, the safety contacts are positively opened and the auxiliary contacts are closed. The switches are
mechanically latched and can then only be returned to the operational condition by a pressing the reset button as
required by EN ISO 13850.

Safety regulations
Warning!
Carefully read through this entire manual before using the device.
The devices shall be installed by a trained electrician following the Safety regulations, standards and the Machine
directive.
Failure to comply with instructions, operation that is not in accordance with the use prescribed in these instructions,
improper installation or handling of the device can affect the safety of people and the plant.
For installation and prescribed use of the product, the special notes in the instructions must be carefully observed
and the technical standards relevant to the application must be considered.
In case of failure to comply with the instructions or standards, especially when tampering with and/or modifying the
product, any liability is excluded.

2TLC172248M0201, rev. A 5 www.abb.com/lowvoltage


2012-11-27
Function description for the variants
LineStrong1

LineStrong1 is a compact and small, yet robust switch that can handle wires up to 30 meters on a single switch
(50 meters on two switches).
When someone pulls the wire of Linestrong1 or if the wire is broken, the switch goes to a safe state, e.g. the
machine is emergency-stopped. After a emergency stop the LineStrong1 needs to be reset to be able to run again
and this is made on the local reset button. LineStrong1 is equipped with an indication of how taut the wire is, which
make the installation or adjustment easy.
The LineStrong1 is made of a rugged die cast housing with a rating of IP67.
A positive forced connection provides a forced disconnect of the safety contacts when the wire is being pulled or
broken. The design of the LineStrong1 ensures that the contacts will not fail or be held in a normally closed
position, due to failure of the spring mechanism or that welding/sticking of the contacts can occur. The LineStrong1
switch has 2NC and 2NO contacts.

Up to 50 m
500 mm Every 3 meter Every 3 meter 500 mm

eyebolt

Up to 50 m

500 mm Every 3 meter Every 3 meter 500 mm

eyebolt Safety Spring

1) LineStrong1 with another LineStrong1


2) LineStrong1 with safety spring

2TLC172248M0201, rev. A 6 www.abb.com/lowvoltage


2012-11-27
LineStrong2

LineStrong2 is a robust switch that can handle wires up to 80 meters on a single switch (100 meters on two
switches). When someone pulls the wire of LineStrong2 or if the wire is broken, the switch goes to a safe state, e.g.
the machine is emergency-stopped. After a emergency stop the LineStrong2 needs to be reset to be able to run
again and this is made with the local reset button. Additional features on the LineStrong2 are a "normal" emergency
stop that is fitted on the side of the grab wire safety switch and also a two coloured LED for indication. LineStrong2
is equipped with an indication of how taut the wire is, which make the installation and adjustment easy.
Depending on the environment where the switch will be used, different material can be chosen for the LineStrong2.
The basic version has a rugged yellow die cast housing with a rating of IP67. In severe applications as for food
processing and chemical industry there is a LineStrong2Z with a total rugged stainless steel 316 body. This version
has IP69K enclosure protection (maintained by a double seal lid gasket and seals) and can be high pressure hosed
with detergent at high temperature.
LineStrong2 also exist in a version(LineStrong2ZX) with certified explosion proof contact block. LineStrong2ZX is in
stainless steel and can be used in European Zone 1, 2, 21,22 enviroments. (Gas and Dust)
A positive forced connection provides a forced disconnect of the safety contacts when the wire is being pulled or
broken. The design of the LineStrong2 ensures that the contacts will not fail or be held in a normally closed
position, due to failure of the spring mechanism or that welding/sticking of the contacts can occur. The LineStrong2
switch has 2NC and 2NO contacts.

Up to 80 m LineStrong2
Up to 100 m LineStrong2Z

500 mm Every 3 meter Every 3 meter 500 mm

eyebolt

Up to 60 m LineStrong2
Up to 80 m LineStrong2Z

500 mm Every 3 meter Every 3 meter 500 mm

eyebolt Safety Spring

1) LineStrong2 with another LineStrong2


2) LineStrong2 with safety spring

2TLC172248M0201, rev. A 7 www.abb.com/lowvoltage


2012-11-27
LineStrong3

LineStrong3 is a quite robust switch that can handle long wires, up to 200 meters on a single switch. When
someone pulls the wire of LineStrong3 or if the wire is broken, the switch goes to a safe state, e.g. the machine is
emergency-stopped. After a emergency stop the LineStrong3 needs to be reset to be able to run again and this is
made on the local reset button. Additional features on the LineStrong3 is a "normal" emergency stop fitted on the
top of the grab wire safety switch and also a two coloured LED for indication. LineStrong3 is equipped with an
indication of how taut the wire is, which makes the installation and adjustment easy.
Depending on the environment where the switch will be used, different materials can be chosen for the
LineStrong3. The basic version has a rugged yellow die cast housing with a rating of IP67. In severe applications
as for food processing and chemical industry, there is a LineStrong3Z with a total rugged stainless steel 316 body.
This version has IP69K enclosure protection (maintained by a double seal lid gasket and seals) and can be high
pressure hosed with detergent at high temperature.
LineStrong3 also exist in versions with certified explosion proof contact block(X-versions).
LineStrong3LZX/RZX/DZX are in stainless steel and can be used in European Zone 1, 2, 21,22 enviroments. (Gas
and Dust)
A positive forced connection provides a forced disconnect of the safety contacts when the wire is being pulled or
broken. The design of the LineStrong3 ensures that the contacts will not fail or be held in a normally closed
position, due to failure of the spring mechanism or that welding/sticking of the contacts can occur. The LineStrong3
switch has 4NC and 2NO contacts.
Single wire - LineStrong3L/3R and LineStrong3LZ/3RZ
The Linestrong3L/3R are two different versions depending on installation.
L - "Left hand" - is the version of LineStrong3 where the placement of the grab wire switch is to the left in the
installation.
R - "Right hand" - is the version of LineStrong3 where the placement of the grab wire switch is to the right in the
installation.
LineStrong3L/3R have die-cast housings and are robust to manage severe indoor or outdoor use.
LineStrong3L/3R are designed to protect a length up to 100 meters on a single switch. If two switches are used
together, up to 125 meters.
LineStrong3LZ/3RZ are in stainless steel 316 housings and are designed specifically to withstand the tough
environments found in the food and pharmaceutical industries. LineStrong3LZ/3RZ are designed to protect a length
up to 100 meters on a single switch. If two switches are used together, the wire can go up to 125 meters.

NB! The picture shows the left hand version NB! The picture shows the right hand version

Up to 125 m

500 mm Every 3 meter Every 3 meter 500 mm

eyebolt
Up to 100 m

500 mm Every 3 meter Every 3 meter 500 mm


1) LineStrong3L with a Linstrong3R
eyebolt Safety Spring 2) LineStrong3L with safety spring

2TLC172248M0201, rev. A 8 www.abb.com/lowvoltage


2012-11-27
Double wire – LineStrong3D and 3DZ
With wire entries from both sides of the grab wire switch, LineStrong3D can be used for a long protection length.
LineStrong3D has a die-cast housing and is robust to manage severe indoor or outdoor use. LineStrong3D is
designed to protect a length up to 200 meters on a single switch. If several switches are used together, it will be
possible with a length up to 125 meters between the switches. A two colour LED ensures switch status can be
seen easily from a distance.
LineStrong3DZ has stainless steel 316 housing and is designed specifically to withstand the tough environments
found in the food and pharmaceutical industries. LineStrong3DZ is designed to protect a length up to 200 meters
on a single switch. If several switches are used together it will be possible with a length up to 125 meters between
the switches.

Up to 125 m Up to 125 m
500 mm 500 mm 500 mm 500 mm
500 mm Every 3 meter Every 3 meter

eyebolt

Up to 100 m Up to 100 m

500 mm Every 3 meter 500 mm 500 mm Every 3 meter 500 mm

Safety Spring eyebolt Safety Spring

1) Several LineStrong3D
2) LineStrong3D with safety springs

2TLC172248M0201, rev. A 9 www.abb.com/lowvoltage


2012-11-27
3 Connections
See Chapter Installation and Maintenance for more information regarding installation

Connections

LineStrong1 & LineStrong2 LineStrong3

LED wiring example

LineStrong2, explosion proof LineStrong3, explosion proof

2NC 2NC 2NO

Contact blocks

2TLC172248M0201, rev. A 10 www.abb.com/lowvoltage


2012-11-27
4 Installation and maintenance
Installation of the Safety Switch

1. The installation of all Emergency Stop Grab Wire Safety Switch systems must be in accordance with a risk
assessment for the individual application. Installation must only be carried out by competent personnel and
in accordance with these instructions.

2. According to ISO 13850, corner pulleys may only be mounted such that a complete length of the wire can
be observed.

3. Wire support eyebolts must be fitted at 2.5 m. min. to 3m. max.intervals along all wire lengths between
switches. The wire must be supported no more than 500mm from the switch eyebolt or Safety Spring (if
used). It is important that this first 500mm is not used as part of the active protection coverage.

4. M5 mounting bolts must be used to fix the switches. Tightening torque for mounting bolts to ensure reliable
fixing is 4 Nm. Tightening torque for the lid screws,conduit entry plugs and cable glands must be 1.5 Nm to
ensure IP seal. Only use the correct size gland for the conduit entry and cable outside diameter.

5. Tensioning of wire is achieved by use of ABB tensioner / gripper assemblies.


Upon installation, tension to mid position as indicated by the green arrows in the viewing window of each
switch. Check operation of all switches and the control circuits by pulling the wire at various locations along
the active protection area and resetting each switch by pressing the blue Reset button. Ensure each time
that the switches latch off, and require manual resetting by pressing the Reset button. Increase the system
tension further, if required, depending upon the checks along the active length of coverage.
If safety switch is fitted with a Mushroom type E-Stop button (Red) then test and reset this part of the
switch to ensure correct function of the safety control circuits. Typical operational conditions for successful
operation of system is less than 75N pulling force and less than 150mm deflection of rope between eyebolt
supports.

6. Recommended wire span options and fittings - (subject to an individual risk assessment for the installation)
See Function description for correct wire span for each variant.

7. Wiring LED (Not on LineStrong1): 1) Terminal 1 – red


2) Terminal 2 – black
Black or Terminal 2 is 0VDC. 3) Terminal 3 – green
When 24VDC is applied to the Red wire or Terminal 1, the lamp will illuminate Red.
When 24VDC is applied to the Green wire or Terminal 3, the lamp will illuminate Green.
If the LED is fitted but is not used ensure the conductors remain coiled and fixed away from the internal
mechanism.
8. To fit Mushroom type Emergency Stop button (Not on LineStrong1):
a) Remove M12 threaded plug from the mounting port.
b) Apply thread locking solution to the threads of the E Stop
mechanism.
c) Insert the Emergency Stop Mechanism into the mounting port
and tighten to 1.5 Nm.
d) After installation test and reset to ensure all safety circuits are
functioning correctly.

Warning! All the safety functions must be tested before starting up the system.

2TLC172248M0201, rev. A 11 www.abb.com/lowvoltage


2012-11-27
Installation of the wire

When setting up an Emergency stop grab wire system from ABB Jokab Safety it is recommended to do the
tensioning of the wire by using of ABB Jokab Safety Tensioner / Gripper accessory. The installation of the
tensioner accessory reduces the installation time. The eyehook, tensioner thimble and the wire strength gripper are
in one assembly which enables rapid connection to the switch eyebolts and fast and accurate tensioning of the
wire. Thanks to the switch viewing window, systems can be accurately and quickly tensioned. The double clamp
mechanism prevents wire slippage.
The end of the safety wire is fed through a central hole in a cone shaped guide which protrudes from the main
housing. After being fed through the guide hole, the wire enters the main housing by going through a feed hole and
then is looped back through 180 degrees and is fed through a second feed hole on the opposite side of the
mechanism. The wire is then pulled for maximum tension and is locked in position by a locking bar inside the main
housing which is moved by turning an Allen type locking bolt.
Because of the added friction on the eyebolts and wire when navigating corners, a corner pulley can be used to
navigate inside or outside corners without causing damage to the wire.

1. Tension to mid position as indicated by the green arrows in the viewing window of each switch
2. The tensioner thimble allows immediate accurate and final tensioning of the wire, whilst viewing the tension
marker through the viewing window on the switch
3. For systems up to 50 meter Quick Link termination is provided for easy connection to either a Safety spring
or Switch eyebolt. (Note for systems above 50 meter a Tensioner / Gripper is required each side).

Outside Outside
corners corners

Inside
corners

Examples of using the corner pulley 1) Machine

2TLC172248M0201, rev. A 12 www.abb.com/lowvoltage


2012-11-27
Tensioner/Gripper

1. 2.

3. 4.

5. 6.

7. 8.

2TLC172248M0201, rev. A 13 www.abb.com/lowvoltage


2012-11-27
9. 10.

11.

12. 13.

14.

2TLC172248M0201, rev. A 14 www.abb.com/lowvoltage


2012-11-27
Maintenance
Every week: Check correct operation of system at locations along all coverage length and also the switch latching
mechanism. Check for nominal tension setting, re-tension wire if necessary.
Every 6 months: Isolate power and remove cover. Check screw terminal tightness and check for signs of moisture
ingress.

Warning! The safety functions and the mechanics shall be tested regularly.

Warning! In case of breakdown or damage to the product, contact the nearest ABB/Jokab Safety Service Office or
reseller. Do not try to repair the product yourself since it may accidentally cause permanent damage to the product,
impairing the safety of the device which in turn could lead to serious injury to personnel.
Caution! ABB/Jokab Safety will not accept responsibility for failure of the switch functions if the installation and
maintenance requirements shown in this sheet are not implemented. These requirements form part of the product
warranty.

2TLC172248M0201, rev. A 15 www.abb.com/lowvoltage


2012-11-27
5 Application example

2TLC172248M0201, rev. A 16 www.abb.com/lowvoltage


2012-11-27
6 Model overview
Type Article number Description
LineStrong1 2TLA050200R0030 2NC/2NO, M20
LineStrong2 2TLA050202R0332 2NC/2NO, M20, E-Stop, LED
LineStrong2Z 2TLA050202R0322 2NC/2NO, M20, E-Stop, LED, stainless steel
LineStrong2ZX 2TLA050202R7125 2NC, 3m cable, E-Stop, Stainless steel, Explosion proof
LineStrong3L 2TLA050206R0332 4NC/2NO, M20, E-Stop, LED, left
LineStrong3R 2TLA050208R0332 4NC/2NO, M20, E-Stop, LED, right
LineStrong3LZ 2TLA050206R0322 4NC/2NO, M20, E-Stop, LED, left, stainless steel
LineStrong3RZ 2TLA05008R0322 4NC/2NO, M20, E-Stop, LED, right, stainless steel
LineStrong3LZX 2TLA050204R7125 2NC/2NO, 3m cable, E-Stop, Stainless steel, Explosion proof
LineStrong3RZX 2TLA050206R7125 2NC/2NO, 3m cable, E-Stop, Stainless steel, Explosion proof
LineStrong3D 2TLA050204R0332 4NC/2NO, M20, E-Stop, LED, double
LineStrong3DZ 2TLA050204R0322 4NC/2NO, M20, E-Stop, LED, double, stainless steel
LineStrong3DZX 2TLA050208R7125 2NC/2NO, 3m cable, E-stop, Stainless steel, Explosion proof

Dimensions

LineStrong1

2 Mounting Holes Clearance


for M5 Screws

LineStrong2 / LineStrong2Z(X)

4 Mounting
Holes for M5
screws

2TLC172248M0201, rev. A 17 www.abb.com/lowvoltage


2012-11-27
LineStrong 3L/R and LineStrong3LZ(X)/3RZ(X)

LineStrong3D and LineStrong3DZ(X)

NB! All measurements are in mm

2TLC172248M0201, rev. A 18 www.abb.com/lowvoltage


2012-11-27
Accessories
Type Article number Description
Galvanized wire pull kits:
Wire pull kit includes:
10 m wire kit 2TLA050210R0130
Wire
20 m wire kit 2TLA050210R0330
Eyebolts
80 m wire kit 2TLA050210R0630
Tensioner / Gripper
100 m wire kit 2TLA050210R0730
Allan key
Stainless steel wire pull kits:
50 m wire kit 2TLA050210R0520
100 m wire kit 2TLA050210R0720
Wire only:
10 m wire 2TLA050210R2120
80 m wire 2TLA050210R2520
100 m wire 2TLA050210R2620
1 m wire (order by length) 2TLA020034R0500
Wire Tensioner:
Wire Tensioner, stainless steel 2TLA050210R4020
Wire Tensioner, galvanized 2TLA050210R4030
Corner pulley:
Corner pulley, stainless steel 2TLA050210R6020
Corner pulley, galvanized 2TLA050210R6030
Eyebolt:
Eyebolt, M8 x 1.25, stainless steel 2TLA050210R8020
Eyebolt, M8 x 1.25, galvanized 2TLA050210R8030
General wire pull accessories
Safety spring, 220 mm long, stainless 2TLA050211R0004
steel
Screw driver, Anti-Tamper, Torx T20 2TLA050211R0006
M20 x 1.5 gland 2TLA050040R0002
M20 x 1.5 conduit plug 2TLA050040R0004
LED Green/Red 24VDC 2TLA050211R0001

2TLC172248M0201, rev. A 19 www.abb.com/lowvoltage


2012-11-27
7 Technical data
LineStrong1
Manufacturer
Address ABB AB / JOKAB SAFETY
Varlabergsvägen 11
SE-434 39 Kungsbacka
Sweden
Electrical characteristics
Contact type IEC/EN60947-5-1 double break Typ Zb
Contact material Silver
2
Termination Clamp up to 2.5 mm conductors
Utilisation category AC15 A300 3A 240VAC 3A/120VAC 6A/24VDC 2.5A inductive
Thermal current (lth) 10 A
Rated insulation/withstand voltages 500VAC / 2500VAC
Short circuit overload protection Fuse externally 10 A (FF)
General
Wire span Up to 50 m
Wire tension devise ABB Jokab Safety Wire Tensioner
Wire type PVC sheath steel wire 4.0 mm outside diameter
Torque settings Mounting M5 4.0Nm
Lid T20 Torx M4 1.5Nm
Terminals 1.0Nm
Tension force (typical mid setting) 130 N
Tension operating force (wire pulled) < 125N < 300 mm deflection
Vibration resistance 10-500 Hz 0.35 mm
Shock resistance 15 g 11 ms
Conduit entries 3 x M20
Enclosure classification IP67
Operating temperature -25°C to +80°C

Enclosure material/cover Die cast painted yellow

Mounting position Any


Mounting bolts 4 x M5
Weight (approx.) 0.675 kg

2TLC172248M0201, rev. A 20 www.abb.com/lowvoltage


2012-11-27
Safety-related characteristic data and Conformity
Conformity European Machinery Directive 2006/42/EC
EN ISO 12100:2010, EN ISO 13850:2008, EN 60204-1:2006+A1:2009
EN 60947-1:2007+A1:2011, EN 60947-5-1:2004+A1:2009, EN 60947-5-
5:1997+A1:2005
EN ISO13849-1 Up to PL e, Cat. 4 depending upon system architecture
EN 62061 Up to SIL3 depending upon system architecture
Safety data
6
Mechanical reliability B10d 1.5 x 10 operations at 100mA load
-7
PFHD <1.0x10
Proof test interval (life) 21 years
MTTFd 214 years (8 cycles per hour/24 hours per day/365 days)
Certifications TÜV, cULus
Information with regard to UL 508 Use 12AWG copper conductors only
Electrical Rating: A300 48W5
Type 1 Enclosure
Max. Switching Current / Volt / Amp: 120V 6A (720VA break) PF 0.38,
240V 3A (720VA break) PF 0.38

LineStrong2 series
Manufacturer
Address ABB AB / JOKAB SAFETY
Varlabergsvägen 11
SE-434 39 Kungsbacka
Sweden
Electrical characteristics
Contact type IEC/EN60947-5-1 double break Typ Zb
Contact material Silver
2
Termination Clamp up to 2.5 mm conductors
Utilisation category AC15 A300 3A 240VAC 3A/120VAC 6A/24VDC 2.5A inductive
Thermal current (lth) 10 A
Rated insulation/withstand voltages 500VAC / 2500VAC
Short circuit overload protection Fuse externally 10 A (FF)
Explosion Proof version (X)
Classification Ex d IIC T6 (-20°C ≤ Ta ≤ +60°C) Gb
Ex tb IIIC T85°C (-20°C ≤ Ta ≤ +60°C) Db
Rated Voltage 250V AC/DC
Rated Current 2 pole 4A
4 pole 2.5A
General
Wire span
LineStrong2 Up to 80 m
LineStrong2Z(X) Up to 100 m
Wire tension devise ABB Jokab Safety Wire Tensioner
Wire type PVC sheath steel wire 4.0 mm outside diameter
Torque settings Mounting M5 4.0Nm
Lid T20 Torx M4 1.5Nm
Terminals 1.0Nm
Tension force (typical mid setting) 130 N
Tension operating force (wire pulled) < 125N < 300 mm deflection

2TLC172248M0201, rev. A 21 www.abb.com/lowvoltage


2012-11-27
Vibration resistance 10-500 Hz 0.35 mm
Shock resistance 15 g 11 ms
Conduit entries 3 x M20
Enclosure classification
LineStrong2 IP67
LineStrong2Z(X) IP69K
Operating temperature
LineStrong2 -25°C to +80°C
LineStrong2Z(X) -25°C to +80°C (100°C cleaning)
Enclosure material/cover
LineStrong2 Die cast painted yellow
LineStrong2Z Stainless steel 316
Mounting position Any
Mounting bolts 4 x M5
Weight (approx.)
LineStrong2 0.880 kg
LineStrong2Z(X) 1.635 kg
Safety-related characteristic data and Conformity
Conformity European Machinery Directive 2006/42/EC
EN ISO 12100:2010, EN ISO 13850:2008, EN 60204-1:2006+A1:2009
EN 60947-1:2007+A1:2011, EN 60947-5-1:2004+A1:2009,
EN 60947-5-5:1997+A1:2005
EN ISO13849-1 Up to PL e, Cat. 4 depending upon system architecture
EN 62061 Up to SIL3 depending upon system architecture
Safety data
6
Mechanical reliability B10d 1.5 x 10 operations at 100mA load
-7
PFHD <1.0x10
Proof test interval (life) 21 years
MTTFd 214 years (8 cycles per hour/24 hours per day/365 days)
Certifications TÜV, cULus
Information with regard to UL 508 Use 12AWG copper conductors only
Electrical Rating: A300 48W5
Type 1 Enclosure
Max. Switching Current / Volt / Amp: 120V 6A (720VA break) PF 0.38,
240V 3A (720VA break) PF 0.38

2TLC172248M0201, rev. A 22 www.abb.com/lowvoltage


2012-11-27
LineStrong3 series
Manufacturer
Address ABB AB / JOKAB SAFETY
Varlabergsvägen 11
SE-434 39 Kungsbacka
Sweden
Electrical characteristics
Contact type IEC/EN60947-5-1 double break Typ Zb
Contact material Silver
2
Termination Clamp up to 2.5 mm conductors
Utilisation category AC15 A300 3A 240VAC 3A/120VAC 6A/24VDC 2.5A inductive
Thermal current (lth) 10 A
Rated insulation/withstand voltages 500VAC / 2500VAC
Short circuit overload protection Fuse externally 10 A (FF)
Explosion Proof version (X)
Classification Ex d IIC T6 (-20°C ≤ Ta ≤ +60°C) Gb
Ex tb IIIC T85°C (-20°C ≤ Ta ≤ +60°C) Db
Rated Voltage 250V AC/DC
Rated Current 2 pole 4A
4 pole 2.5A
General
Wire span
LineStrong3L/R/LZ(X)/RZ(X) Up to 125 m
LineStrong3D/DZ(X) Up to 250 m
Wire tension devise ABB Jokab Safety Wire Tensioner
Wire type PVC sheath steel wire 4.0 mm outside diameter
Torque settings Mounting M5 4.0Nm
Lid T20 Torx M4 1.5Nm
Terminals 1.0Nm
Tension force (typical mid setting) 130 N
Tension operating force (wire pulled) < 125N < 300 mm deflection
Vibration resistance 10-500 Hz 0.35 mm
Shock resistance 15 g 11 ms
Conduit entries 4 x M20
Enclosure classification
LineStrong3D/L/R IP67
LineStrong3LZ(X)/RZ(X)/DZ(X) IP69K
Operating temperature
LineStrong3D/L/R -25°C to +80°C
LineStrong3LZ(X)/RZ(X)/DZ(X) -25°C to +80°C (100°C cleaning)
Enclosure material/cover
LineStrong3D/L/R Die cast painted yellow
LineStrong3LZ(X)/RZ(X)/DZ(X) Stainless steel 316
Mounting position Any
Mounting bolts 4 x M5
Weight (approx.)
LineStrong3D 1.320 kg
LineStrong3DZ(X) 2.200 kg
LineStrong3L/R 1.100 kg
LineStrong3LZ(X)/RZ(X) 2.000 kg

2TLC172248M0201, rev. A 23 www.abb.com/lowvoltage


2012-11-27
Safety-related characteristic data and Conformity
Conformity European Machinery Directive 2006/42/EC
EN ISO 12100:2010, EN ISO 13850:2008, EN 60204-1:2006+A1:2009
EN 60947-1:2007+A1:2011, EN 60947-5-1:2004+A1:2009,
EN 60947-5-5:1997+A1:2005
EN ISO13849-1 Up to PL e, Cat. 4 depending upon system architecture
EN 62061 Up to SIL3 depending upon system architecture
Safety data
6
Mechanical reliability B10d 1.5 x 10 operations at 100mA load
-7
PFHD <1.0x10
Proof test interval (life) 21 years
MTTFd 214 years (8 cycles per hour/24 hours per day/365 days)
Certifications TÜV, cULus
Information with regard to UL 508 Use 12AWG copper conductors only
Electrical Rating: A300 48W5
Type 1 Enclosure
Max. Switching Current / Volt / Amp: 120V 6A (720VA break) PF 0.38,
240V 3A (720VA break) PF 0.38

The Jokab Safety branded product with articlenumber beginning with 2TLJ is fully compatible with the ABB
branded product with articlenumber beginning with 2TLA.

2TLC172248M0201, rev. A 24 www.abb.com/lowvoltage


2012-11-27
8 EC Declaration of conformity

2TLC172248M0201, rev. A 25 www.abb.com/lowvoltage


2012-11-27
ABB AB / JOKAB SAFETY Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden

www.abb.com/lowvoltage

2TLC172248M0201, rev. A 26 www.abb.com/lowvoltage


2012-11-27