QuickStart Data Sheets - Doble ProtectionSuite 3.

0
All User Levels

These data sheets include these topics:

User Level Topic

BASIC Spreadsheet Step


BASIC Copy Grids
BASIC Bulk Edits
CALIBRATION Calibration (2 sheets)
PRO/ADMIN Database Conversion
PRO/ADMIN Sample Value Support

ProtectionSuite is Doble Engineering Company’s software for protection (802.3 LAN, R


S232 serial,
relays and protection systems. These pages highlight some of the new SerialOverUSB
)
features for the Basic edition of Version 3.0. LAN ProtectionSuite 2.2
02.3
a l, 8
seri
2 32
RS

Relay
Copyright 2014, Doble Engineering Company
Part 72A-3280-01 Rev. B
012414
Spreadsheet Test Step Doble ProtectionSuite 3.0
This is a new kind of test step. This is similar to a document step in that, All Levels
when it runs, the tester can enter data that gets recorded in the .psx file, as with Configure the Spreadsheet Protection Suite will import Excel spreadsheets
any other test. It even shows multiple test runs in history, as with any other test. (and .cvs files) directly into the spreadsheet test.
This step is for measuring and tracking regulatory compliance.

Instead of a series of steps, the test runs with all cells that are not locked.
You can put formulas in cells, and can freeze rows or columns, so they retain
position when you add more.

Add Spreadsheet Step You can build the spreadsheet by hand, or can:
Import a .csv file
Cut and paste data from another spreadsheet
Bring the data in from Excel
This example shows importing an Excel spreadsheet.
Result After Importing Data

Right-click to modify test format


(font, color, and so on).

Select from the drop-down menu for new test steps,


under Data Entry & Information / Spreadsheet Step tabs

The Spreadsheet has an option, “Request PassFail status”, like the Document step.
The spreadsheet supports embedding standard formulas, so the test designer Cells can be merged, text centered, and given background colors.
can have fields that get updated with values, as the tester inputs values. There is an Autofit option for labels that are too big for a cell.
The spreadsheet test designer can lock down cells, making them
unchangeable. Select the cells, then click Lock Cells. A small ball icon
in the corner of the cell shows that it is locked.
Copyright 2014, Doble Engineering Company
Part 72A-3280-01 Rev. B
01xx14
Copying Grids, Bulk Edits Doble ProtectionSuite 3.0
Basic

Copying Grids
You can use a right mouse click to copy a grid to the clipboard,
then paste the grid into Excel.

Bulk Edits
You can now select a column in the ProtectionWeb relay browser
(column editors). Select multiple files, right-click, edit the column.

Copyright 2014, Doble Engineering Company


Part 72A-3280-01 Rev. B
012414
F6080 Calibration Sheet 1 of 2
Doble ProtectionSuite 3.0 Calibration, Pro, Admin
Press the “...” button.
You can use the F6080 instrument to calibrate your F6150’s amplifiers.
Protection Suite tells the F6150 what to output, then the F6080 checks that signal
and adjusts the calibration, as needed. The process runs inside Protection Suite,
under the Instrument / Calibration tabs.
You will need an F-series test instrument, such as an F6150 or F6350, as well
as F6080 instrument.

Verify the Protection Suite connection with the F610 or


1 similar instrument under the Connect/Verify tab.

For amplifiers previously


calibrated, the Serial number and
Last Calibration Date are now
2 Verify the Protection Suite connection with filled in automatically.
the F6080 under the Connect/Calibration tab.

4
Click Next.
3 Click to begin calibration.
Set Comm Channel.

Select the tests you want performed.

Click here to save time by not


testing what you don’t need.

Copyright 2014, Doble Engineering Company


Part 72A-3280-01 Rev. B
01xx14
F6080 Calibration Sheet 2 of 2
Doble ProtectionSuite 3.0
Calibration, Pro, Admin

This window shows how to connect the test leads.

Click Continue to start the tests.

The test being run is displayed.

After the last test completes, click Finish.

A progress bar for that test is shown. At the end of the


test, the instrument is automatically rebooted and the
next test starts. Copyright 2014, Doble Engineering Company
Part 72A-3280-01 Rev. B
01xx14
ProTesT to Protection Suite (.psx) Conversion Doble ProtectionSuite 3.0
Pro or Admin

Can now convert a large number of ProTesT databases at one time.


Specify either a folder or a folder with all sub-folders.

PS 3.0 has a “one click option” for importing all the ProTesT databases in a
specified folder and, optionally, to descend all subdirectories of that folder and
convert those databases also. The resulting .psx files are placed in a folder
structure that mimics the nesting of the original databases.

If location-mapping is specified, it applies to all the databases that are converted.

Copyright 2014, Doble Engineering Company


Part 72A-3280-01 Rev. B
012414
Sample Value Support Doble ProtectionSuite 3.0
In the substation, instead of relays monitoring voltage Pro or Admin
and current directly, the digital monitoring device monitors
voltages and currents, using an IEC61850 protocol.

Sample Value Sources Set

The Sample Value Setup


tab is new in V 3.0.
Select the instrument type from the
pull-down menu. [a number of F6150
types are shown] Pick a configuration.
Click to add SV source sets. Although can have many Note: The Source panel (on the Sources
source sets, you can only use 2 conventional sources, tab) only allows you to select
or a total of 3 sets for a given test. configurations you can use.
Can add 5V to conventional sources,
but that’s unusual. [???]
All test types are supported.
Add as standard configurations:
2V/2I, 0V/0I

Click ellipse button to set quality flags.

In the IEC61850 environment, we are driving Sample Value sources, instead of


conventional sources. Each set has 4 Vs and 4 Is.
Add SV sources through the drop-down menu.

You can have as many SV source sets as you want. You are limited to two SV sets
if you are also using conventional sources. Otherwise, you can have three sets.

Copyright 2014, Doble Engineering Company


Part 72A-3280-01 Rev. B
012414