PM210011 900 Es602 001

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

A B C D E F G H

NOTES

1. THIS SINGLE LINE DIAGRAM INDICATES THE CONCEPTUAL POWER DISTRIBUTION SCHEME FOR THE
BUILDING AREA.

2. POWER TO THE BUILDING AREA PDC SHALL BE SUPPLIED VIA 13.8kV CABLES FROM UNIT 600 UTILITY
PDC 600-P291.
3. RATINGS OF ALL ELECTRICAL EQUIPMENT ARE PRELIMINARY.

4. ACTUAL NUMBER OF MV SPARE FEEDERS ARE AS INDICATED IN THE SLD.

8 5. EMERGENCY POWER DISTRIBUTION PHILOSOPHY IS AS INDICATED BELOW-


8
5.1 EMERGENCY POWER SUPPLY SHALL BE RECEIVED VIA 13.8kV CABLES FROM CENTRAL GENERATION PDC.
5.2 LOSS OF NORMAL SUPPLY TO BUS A & BUS B OF 900-P220 WILL INITIATE TO CLOSE THE
EMERGENCY INCOMER AT BUS E.
5.3 EMERGENCY POWER SHALL BE DISTRIBUTED TO BUILDING LOADS AT 400V
5.4 ON RESUMPTION OF NORMAL POWER SUPPLY, EMERGENCY POWER SUPPLY SHALL BE DISCONNECTED
IN MAKE BEFORE BREAK SEQUENCE ALLOWING MOMENTARY PARALLELING WITH THE NORMAL POWER
SUPPLY.
5.5 DURATION OF MOMENTARY PARALLEL OPERATION WITH NORMAL POWER SUPPLY SHALL NOT EXCEED
3 SECOND. TIMER SHALL BE PROVIDED FOR AUTOMATIC DISCONNECTION OF EMERGENCY INCOMER TO
AVOID PROLONGED
PARALLEL OPERATION.
5.6 MOMENTARY PARALLEL OPERATION WITH NORMAL POWER SUPPLY SHALL NOT BE CONSIDERED IN
DECIDING SHORT CIRCUIT RATING OF MV AND LV SWITCHGEAR.

6. FOR 900-P410 LV FEEDER DETAILS REFER LOAD SUMMARY DOCUMENT No. PM210011-900-EL1-00002

7. REFER DWG. NO. PM210011-SCE900-ES601 FOR POWER DISTRIBUTION TO ALL UNIT-900


RC & STEEL FRAME BUILDINGS.

900-P290 - BUILDING AREA PDC

7 7

13.8kV FEEDER A
13.8kV FEEDER B 13.8kV FEEDER E
(FROM 600-P220 (H125)
(FROM 600-P220 (H129) (FROM 605-P220 H132
UTILITY PDC)
UTILITY PDC) CENTRAL GENERATION PDC)
HOLD 3

900-P220

630A 630A 630A


ATS ATS

V NC V NC V NO

HOLD 1 H101 H102 H103


H104 630A H105 630A 02
900-P220, 13.8kV, 60Hz, 630A, 31.5kA FOR 1s, 3PH, 3WIRE BUS A BUS B BUS B BUS E
6 6
NO NC
V V
H106 H107 H108 H109 H110 H111 H112 H113 H114 H115 H116 H117 H118

630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A

V V V V V V V V V V V V V

5 5
TO 900-P232 TO CONTRACTOR SPARE TO 900-P234 TO 900-P236 SPARE TO 900-P233 900-P235 900-P237 900-P238 HOLD 4 SPARE HOLDS
CENTRAL CONTROL ROOM AREA POWER FEEDER MAINT. WORKSHOP ADMIN BUILDING FEEDER CENTRAL CONTROL ROOM MAINTENANCE ADMIN BUILDING SECURITY BUILDING FEEDER
1. SHORT CIRCUIT RATING OF MV & LV SWITCHGEAR
900-B901 FEEDER 900-B906 900-B902 900-B901 WORKSHOP 900-B902 900-B908
2. TRANSFORMER %Z
900-B906
3. CENTRAL GENERATION PDC SWITCHGEAR TAG & FEEDER NO.
900-P230 900-P231 4. EMERGENCY FEEDER AND TRANSFORMER REQUIREMENT FOR SECURITY BUILDING FOR SECURITY BUILDING.
13.8/0.42kV 13.8/0.42kV 5. TEMPORARY GENERATOR RATING FOR CONTRUCTION/COMISSIONING POWER AND ITS DISTRIBUTION SCHEME.
750kVA ONAN 200kVA ONAN
Dyn11, Z=5% Dyn11, Z=5%
REFERENCE DRAWINGS
HOLD 2 HOLD 2

PM210011-600-ES6-00001 OVERALL KEY ONE LINE DIAGRAM


PM210011-900-EL1-00002 ELECTRICAL LOAD SUMMARY - 900-P290 BUILDING AREA PDC

LEGEND
of Air Products and must not be used, copied, reproduced, or disclosed to others in whole or in part, without proper authorization. This drawing may not be reproduced or used for purposes other than that for which it was supplied.

HOLD 5
This drawing is the property of Air Products and Chemicals, Inc. and/or subsidiaries, and must be accounted for and returned to the company upon request. Information on this drawing is confidential and proprietary information

400V
G DELTA/STAR DISTRIBUTION
TEMPORARY WITHDRAWABLE
4 TRANSFORMER WITH 4
GENERATOR CIRCUIT BREAKER
OFF-LOAD TAP CHANGER
V = VACUUM
AND SECONDARY NEUTRAL
A = AIR
SOLIDLY EARTHED

MCB WITH THERMAL EARTH


400A
OUTDOOR & MAGNETIC TRIP
3+N+E ISOLATOR
AND SOCKET
OUTLET

G DIESEL EARTH SWITCH


GENERATOR

AUTO TRANSFER
900-P410 ATS
SWITCH

1250A 630A
400A CABLE TERMINATION
ATS

A NC A NO
3 M101 M102
3
M104 3 PHASE HEATER
HOLD 1
630A
900-P410, 400V, 60Hz, 1250A, BUS A A BUS E

25kA FOR 1s, 3PH, 4WIRE NC


M104
NOTE 6

2 2
PROPRIETARY DATA:
CONFIDENTIAL AND

1 1
TITLE USED ON PM-21-0011

OWNER
OVERALL SINGLE LINE DIAGRAM GROUP
ELE

RELEASE
900-P290 BUILDING IFE
PURPOSE

02 ISSUED FOR DESIGN 06/06/23 YC/TT GB SB


c
Air Products and Chemicals, Inc. AREA PDC REFERENCE

01 ISSUED FOR DESIGN 23/05/23 RP TT/GB SB NEOM GREEN H2 PROJECT


DOC
00 ISSUED FOR ENGINEERING 18/07/22 HMP TT GB SAUDI ARABIA No PM210011-900-ES602-001
As of Dates in REVISIONS list
REV CN No REVISION DESCRIPTION DATE BY CHK'D APP'D All rights reserved SCALE SHEET
NTS 001

A B C D E F G H
\\Cad0\plants\PM210011\Elect\02 Users\Yash\U900-SLDs\PM210011-900-ES602-001.dgn

You might also like