Am8000 Eng
Am8000 Eng
BB-8000 LCD-8000-A
AM-8000
Fire Detection Control Panel
32 loop addressed control panel
HARDWARE FEATURES
2.0 USB port to firmware upgrade, history log saving and file
exchange with a PC or PK-8000 Configuration Tool software.
SOFTWARE FEATURES
AM-8000 is a RISC high speed microprocessor fire detec-
tion control panel, is compliant to the European EN 54-2 e
- 4 Passwords access levels EN 54-2 compliant
EN54-4.
- Programmable text for Devices/Zones: 32 characters
- 500 zones and 400 Logic Groups per system
The control panel AM-8000.2 can drive 2 analog loops
- Control-By-Event Equations (CBE) to program activations
and it’s expandable to 4 using an additional LIB-8000 card
using logic operators (AND. OR. DEL, etc.)
installed inside the panel.
- 2000 events History Log file per system
- The History Log File and the Event List are duplicated on
Using the high speed CAN-bus line it’s possible to expand
every Panel to be fault tolerant for Network Fails.
the control panel AM-8000 from 4 to 32 loops through
- Real time clock
the connection with max 7 BB-8000 (expandable from 2
- Self programming utility on fire detection loops with
to 4 loops).
Type-ID self recognition of connected devices
- Self recognition for double address settings
Each loop, using the new Advanced protocol, can manage
- Algorithm to activate alarms and faults
and supervise 159 detectors and 159 modules up to max
- Possibility to separate control of strobes / sounders in Day
5088 detectors and 5088 modules.
/Night mode or different alarm conditions
- Automatic warning of Clean-up detectors
On the CAN-bus, that links AM-8000 with BB-8000, it’s
- Automatic warning of detectors low speed
possible to connect up to 7 LCD-8000-L displays in order
- Programmable alarm threshold on detectors
to manage and supervise all the fire detection system. The
- Programmable software function for all different field devi-
display can be installed on the field or on the BB-8000.
ces
- Walk-Test function for each area
WWW.NOTIFIER.IT
AM-8000 LCD-8000-L LCD-8000 LIB-8000 PK-8000
BB-8000 LCD-8000-A
AM-8000
Fire Detection Control Panel
32 loop addressed control panel
333 mm
CERTIFICATE
CPD: 1293 - CPD - 0316
WWW.NOTIFIER.IT
AM-8000 LCD-8000-L LCD-8000 LIB-8000
000 PK-8000
BB-8000 LCD-8000-A
WWW.NOTIFIER.IT
AM-8000 LCD-8000-L LCD-8000 LIB-8000 PK-8000
BB-8000 LCD-8000-A
LCD-8000-L
Touch screen terminal
To manage and supervise the fire system
GENERAL FEATURES
Touch screen display 7” TFT
800x480 pixel
65.000 colours
Controlled backlit LED
Keys for specific functions
15 LED to report events
TECHNICAL FEATURES
Power supply: 24Vdc
Stand-by current: 125mA @24Vdc
Alarm current: 230mA @24Vdc
Working temperature: -5°C/+40°C
Stock temperature: -10°C/+50°C
Relative Humidity no condensation: 10-95%
Possible wall installation or on the BB-8000
This terminal has a CAN-bus output to manage and supervise
Dimensions: 187Hx247Lx31P
all the fire detection system. IP20
SIRENE
TA C I TAT E
A L LA R M E
R E M O T O ATT I V O
The terminal has two USB ports 1.1/2.0 (one internal and one
R I TA R D I ATT I V I
ESCLUSIONI
187 mm
TEST
GUASTI
SISTEMA
DISPERSIONE
A TERRA
ESCLUSIONI/
GUASTI
SIRENA
TRASMISSIONE
GUASTI
TA C I TA Z I O N E TA C I TA Z I O N E
AZZERA
TRASMISSIONE E VA C U A Z I O N E RIPRISTINO RESET
R I TA R D I A L LA R M I / G UA S T I
SIRENE
A L LA R M I
COMANDO
ANTINCENDIO
31 mm
LCD -8F
A L LA R
ME
SIREN
TA C I TA E
TE
ALL
REMO ARME
T O AT
TIVO
R I TA R
D I ATT
IVI
ESCLU
SIONI
TEST
247 mm
TENSIO
PRESE NE
NTE
GUAS
TI
SISTE
MA
ALIME
N TA Z I
ONI
CONNECTIONS
DISPE
RSI
A TER ONE
RA
ESCLU
SIO
GUAS NI/
TI
SIREN
A
TRASM
ISSI
GUAS ONE
TI
TRASM
ISS
A L LA R I O N E
MI
E VA C U
COMA AZION
E
ANTIN NDO AZZER
CEND R I TA R
A
IO DI TA C I T
A L LA R A Z I O N E
WWW.NOTIFIER.IT
AM8000 LCD-8000 PK-8000
BB-8000 LCD-8000-L LIB-8000
LCD-8000-A
LCD-8000 / LCD-8000-A
Repeaters
Remote repeater terminals for AM-8000 control panels
LCD-8000
It reports all the signalling of the control panel AM-8000
and it also has these functions:
- Events Acknowledgment and System Reset (ACK)
- Display history events
- Download on USB key the history events of the control
panel AM-8000.
GENERAL FEATURES
213 mm 27 mm
Display TFT 7” (800x480 pixel) with Touchpad and
backlit LED
WWW.NOTIFIER.IT
AM-8000 LCD-8000-L LCD-8000 LIB-8000
000 PK-8000
BB-8000 LCD-8000-A
LIB-8000 PK-8000
Expansion board Software for AM-8000
2 loops expansion Programming the control panel AM-8000
FEATURES
WWW.NOTIFIER.IT
AM-8000 LCD-8000-L LCD-8000 000
LIB-8000 PK-8000
BB-8000 LCD-8000-A
CODE
CEI 800 AM-8000.2 2 LOOPS Fire Alarm Control Panel with display.
CEI 801 BB-8000.2 2 LOOP Black Box Without display.
CEI 800L LCD-8000-L Touch Screen Terminal.
CEI 803 LIB-8000 Expansion Board.
CABLE
CVCAVO-CAN2X0,34 C.CANBUS 2X0,34 CB627-06272341
CVCAVO-CAN2X0,75 C.CANBUS 2X0,75 CB627-06272751
Compatible Devices
DETECTORS CALL POINT
NFXI Series M700 Series
NFXI detectors are designed to offer an improved detec- Addressable manual break glass call point. Equipped
tion across multiple fire types. All detectors have isola- with a red LED to signal local alarm. Addressing through
tor, LED to indicate the device status and rotary switch rotary switches and provided with double insulation
to address the control panel. There are different types: protection for the communication line. CPD certified for
- Smoke detector (optical) EN 54-11. Different types:
- Optical and rate of rise - Indoor call point
- Rate of rise detector - Outdoor call point
- Maximum temperature heat detector (58°C)
- Maximum temperature heat detector (78°C)
- Multicriteria detector: smoke optical, heat and IR flame SOUNDER
NFXI Series
NFXI sounders have isolator and rotary switch. Certifi-
cated according to CPD-EN54.3. Different types:
NFXI BEAM SMOKE DETECTOR
Beam smoke detector uses an optical - Electronic sounder
transmitter/receiver unit (TRX) and a reflector to place
- Sounder and strobe
on the opposite side. Sensitivity is adjustable on 6 levels
with 2 adjustable levels related to environment. Auto-
- Strobe
matic gain dusty compensation for loss of signal. Easy
alignment due to the adjustment knobs, the sight align-
ment and the digital readout of signal strength. Alarm MODULES
and fault relays. Thanks to special integrated interface Input Series 700 and MA
can communicate with the control panel and the
Output Series 700 and MA
addressing is achieved through rotary switches (from 01
to 159).
BASES
INTELLIGENT AIR DUCT SMOKE DETECTOR
The addressed duct detection system DNRE senses 500 Series
airflow in order to detect the possible presence of
smoke particles (caused by a fire). Directly connected to
the loop of the control panel.
WWW.NOTIFIER.IT
D-161.1-8000-ENG REV. A.1 07/2013