Danfoss KVC Capacity Regulating Valves
Danfoss KVC Capacity Regulating Valves
Data sheet
Features yy Accurate, adjustable pressure regulation yy Compact angle design for easy installation
yy Pulsation damping design yy Available with flare and ODF solder connections
Technical data
Refrigerants HCFC, HFC and HC
Ordering
Rated capacity 1) Flare Solder
Type [kW] connection 2) Code no. connection Code no.
R22 R134a R404A/R507 R407C [in.] [mm] [in.] [mm]
1)
Rated capacity is the regulator capacity at 2)
KVC is supplied without flare nut.
evaporating temperature te = -10 °C, Separate flare nuts can be ordered:
condensing temperature tc = 25 °C, 1
/2 in./12 mm, code no. 011L1103,
offset = 0.7 bar 5
/8 in./16 mm, code no. 011L1167
The connection dimensions chosen must not be If the discharge tube temperature becomes too
too small, since gas velocities in excess of 40 m/s high in relation to the compressor specification,
at the inlet of the regulator can give flow noise. the installation of an injection valve in a bypass
between liquid line and compressor suction line
is recommended.
Replacement capacity
Q 1) [kW] suction gas temperature ts after
Offset pressure/temperature reduction [°C]
Type
∆p [bar]
-45 -40 -30 -20 -10 0 10
R22
0.10 — 2.3 2.4 2.5 2.5 2.6 2.6
Correction factors
When selecting, the required regulator capacity The corrected capacity can then be found from
is to be multiplied by a correction factor the table. Correction factors for condensing
dependent on the condensing temperature. temperature can be found in section “selection”.
Replacement capacity
Q 1) [kW] suction gas temperature ts after
(continued) Offset
Type pressure/temperature reduction [°C]
∆p [bar]
-45 -40 -30 -20 -10 0 10
R134a
0.10 — — 1.4 1.4 1.5 1.7 1.7
Correction factors
When selecting, the required regulator capacity The corrected capacity can then be found from
is to be multiplied by a correction factor the table. Correction factors for condensing
dependent on the condensing temperature. temperature can be found in section “selection”.
Replacement capacity
Q 1) [kW] suction gas temperature ts after
(continued) Offset
Type pressure/temperature reduction [°C]
∆p [bar]
-45 -40 -30 -20 -10 0 10
R404A/R507
0.10 — 1.9 2.0 2.1 2.2 2.3 2.4
Correction factors
When selecting, the required regulator capacity The corrected capacity can then be found from
is to be multiplied by a correction factor the table. Correction factors for condensing
dependent on the condensing temperature. temperature can be found in section “selection”.
Replacement capacity
Q 1) [kW] suction gas temperature ts after
(continued) Offset
Type pressure/temperature reduction [°C]
∆p [bar]
-45 -40 -30 -20 -10 0 10
R407C
0.10 — 2.4 2.6 2.7 2.8 2.9 3.0
Correction factors
When selecting, the required regulator capacity The corrected capacity can then be found from
is to be multiplied by a correction factor the table. Correction factors for condensing
dependent on the condensing temperature. temperature can be found in section “selection”.
Sizing For optimum performance, it is important The following data must be used
to select a KVC valve according to system when sizing a KVC valve:
conditions and application. yy Refrigerant: HCFC, HFC and HC
yy Minimum suction temperature: ts in [°C]/[bar]
yy Compressor load in [kW]
yy Evaporator load in [kW]
yy Condensing temperature: tl in [°C]
yy Connection type: flare or solder
yy Connection size in [in.]
Valve selection Example The following example illustrates how this is done:
When selecting the appropriate valve it may be yy Refrigerant: R134a
necessary to convert the actual evaporator yy Minimum suction temperature:
capacity using a correction factor. This is ts = -12 °C ~ 0.9 bar
required when your system conditions are yy Compressor capacity at -12 °C = 15.4 kW
different than the table conditions. The selection yy Evaporator load at -12 °C = 10.0 kW
is also dependant on the acceptable pressure yy Condensing temperature: tl= 35 °C
drop across the valve. yy Connection type: solder
yy Connection size: 5/8 in.
Step 1
Determine the correction factor for condensing From the correction factors table (see below)
temperature tl. a condensing temperature of 35 °C, R134a
corresponds to a factor of 1.10.
tl [°C] 10 15 20 25 30 35 40 45 50
R134a 0.88 0.92 0.96 1.0 1.05 1.10 1.16 1.23 1.31
R22 0.90 0.93 0.96 1.0 1.05 1.10 1.13 1.18 1.24
R404A/R507 0.84 0.89 0.94 1.0 1.07 1.16 1.26 1.40 1.57
R407C 0.88 0.91 0.95 1.0 1.05 1.11 1.18 1.26 1.35
Step 2
Step 3
Now select the appropriate capacity table KVC 15 delivers 5.4 kW at an offset of 0.3 bar.
and choose the column for minimum suction Based on the required connection size of 5/8 in.
temperature ts = -20 °C. ODF, the KVC 15 is the proper selection for this
Using the corrected replacement capacity, example.
select a valve that provides an equivalent
or greater capacity than required.
Step 4
34L182.11
Danfoss
Setting
[bar]
Offset
P-band
Dimensions [mm]
and weights [kg]
Connection
C Net
Type Flare Solder ODF NV1 NV2 H1 H2 B1 øD
solder weight
[in.] [mm] [in.] [mm]
KVC 12 /2
1
12 /2
1
12 19 24 179 99 64 10 30 0.4
KVC 15 5
/8 16 5
/8 16 24 24 179 99 64 12 30 0.4
KVC 22 — — /8
7
22 — — 179 99 64 17 30 0.4