HITACHI Installation & Maintenance Manual

Wired Remote Control Switch (Model:PC-AR)IMPORTANT:


READ AND UNDERSTAND THIS MANUAL BEFORE USING THIS WIRED REMOTE CONTROL SWITCH.
KEEP THIS MANUAL FOR FUTURE REFERENCE.

IMPORTANT NOTICE:
z No part of this manual may be reproduced without written permission.
z Signal words (DANGER, WARNING, and CAUTION) are used to identify levels of hazard seriousness. Definitions of
identifying hazard levels are provided below with their respective signal words.
DANGER : Immediate hazards which WILL result in severe personal injury or death.
WARNING : Hazards or unsafe practices which COULD result in severe personal injury or death.
CAUTION : Hazards or unsafe practices which COULD result in minor personal injury or product or property
damage
NOTE: Useful information for operation and/or maintenance.

1. SAFETY SUMMARY
DANGER
z DO NOT pour water into the remote control switch (hereafter called “controller”). This product is equipped
with electrical parts. If poured, it will cause a serious electrical shock.
WARNING
z DO NOT perform installation work and electrical wiring connection by yourself. Contact your distributor or
dealer of <25. and ask them for installation work and electrical wiring by service person.
CAUTION
z DO NOT install the indoor unit, outdoor unit, controller and cable at such places as;
1. Where there is oil vapor and the oil is dispersed
2. Where the hot springs are near (in a sulfuric environment)
3. Where generation, flowing, staying or leaking of flammable gas is detected
4. Where the sea is near (in the salty environment)
5. An acid or alkaline environment
z DO NOT install the indoor unit, outdoor unit, controller and cable within approximately 3 meters from strong
electromagnetic wave radiators such as medical equipment. In case that the controller is installed in a place
where there is electromagnetic wave direct-radiation, shield the controller and cables by covering with the
steel box and running the cable through the metal conduit tube.
z In case that there is electric noise at the power source for the indoor unit, provide a noise filter.
The box ‫ غ‬is for checking work .Check the box after checkig.

2. Installation Work
[2.1 Selection of Installation Place]
‫ غ‬1) Select a suitable place for handling and determine the installation place of the controller with the customer’s ac-
ceptance. Do not install the controller at such places as;
٨ where children can touch ٨ where the air from the air conditioner is directly discharged
[2.2 Before Installation]
‫ غ‬This packing contains the following parts.
[A] Remote Control Switch (Q’ty: 1, For Operation Control)
[B] Screw<M4x16L> (Q’ty: 2, For Fixing the Holding Bracket onto the Wall)
[2.3 Installation Space] More than
‫ غ‬1) In case of installing the controllers in vertical line, keep a distance more than 50mm be- 50mm
tween the controllers vertically. If the distance is insufficient, the front cover of the controller
can not be opened wide enough.
[2.4 Installation Procedures] Figure Seen from Bottom Side
‫ غ‬1) Insert the edge of the slotted screw- Groove Part for Removing Controller
driver into the groove at the bottom of
the holding bracket, push and turn the
slotted screwdriver and then remove Approx.
⚂ 㧢㨙㨙᏷ߩ 6mm
the controller from the holding bracket. ࡑࠗ࠽ࠬ
Slotted
࠼࡜ࠗࡃ࡯ Screw ࠷ࡔ
Groove Part
Driver
ਅ஥߆ࠄ⷗ࠆ Groove for Attaching
Controller
‫ غ‬2) Attach the controller to the holding bracket and connect the cable as follows.
A. In Case of Exposing Remote Control Cable

Cable
ࠤ࡯ࡉ࡞ Attach the stopper to the
࠽ࠗࡠࡦࡃࡦ࠼ߥߤࠍᏎ޿
cable at the inside of the
Band Stopper
࠽ࠗࡠࡦࡃࡦ࠼ ߡ‫߇࡞ࡉ࡯ࠤޔ‬಴ߥ޿ࠃ߁
(Field-Supplied) draw-out hole.
ߦߒߡߊߛߐ޿‫ޕ‬
㧔⃻࿾Ḱ஻ຠ㧕

ࠪ࡯ࠬࠍ߻޿ߚㇱಽࠍ
Lead the cable with its
sheath peeled through
Ḵߦᴪߞߡㅢߔ‫ޕ‬
the groove.
㩢㩝㩄㩧 㩢㩝㩄㩧
# $ Peel the insulation at
Fix the holding bracket 4'/1%10 4'/1%10 ࠤ࡯ࡉ࡞వ┵ߩⵍⷒ
onto the wall with screws the end of㧹㧟↪࿶⌕┵
ࠍ߻߈‫ޔ‬ the cable and
clamp the M3 solderless
ሶ㧔⃻࿾Ḱ஻ຠ㧕ࠍធ
(accessory). terminals (field-supplied).
⛯ߔࠆ‫ޕ‬

B. When Using Switch Box


1. Prepare field-supplied JIS Box (JIS C 8336-1988). 2. Lead the cable through the conduit tube in the wall.

JIS 㩘㩨㨹㩂㩇
, +5Box for JIS 㩘㩨㨹㩂㩇
, +5Box for
The following 5 types are available.
2 ୘↪ߩ႐ว
Controllers 1 Controllers
 ୘↪ߩ႐ว
1. Switch Box for 1 Controller(Without Cover)
2. Switch Box for 2 Controllers (Without Cover)
3. Switch Box for 1 Controller (With Cover)
4. Switch Box for 2 Controllers (With Cover)
5. Outlet Box (With Cover)

3. Peel the insulation at the end of the cable and


M4 Screws
㧹㧠ߥߴࡀࠫ
clamp the M3 solderless terminals (field-supplied).
(⃻࿾⺞㆐ຠ)
(Field-Supplied)

4'/1%10 # $ 4'/1%10

Remove the
protection
଻⼔ࠪ࡯࠻ film.
Connect the terminals.

‫ غ‬3) Attach the remote control switch to the holding bracket. Be careful not to pinch the cable
when attaching it.
‫ غ‬4) Remove the protection film from the liquid crystal display.

3. Electrical Wiring
Wiring Example (Using a twist pair cable with shield tube)
ATTENTION: Always make sure to turn off the power of the indoor unit when performing electrical wiring work. Performing
electrical wiring work with the power on can damage the circuit boards of the indoor unit and the remote control switch.

Max. 16 Indoor Units


●RemoteControl Cable <Option>
Remote Control
Remote Control Electrical Box Electrical Box Switch
Switch of Indoor Unit of Indoor Unit (Subsidiary)
Twist Pair Cable(1P-0.75mm2) Solderless Terminal
Terminal Board Terminal Board (X Type)
Diameter: Ǿ7
REMOCON REMOCON REMOCON REMOCON
A B
A B M3.5 A B M3.5 A B
Color: Ivory 1.25-3X
Screws Screws
50চ 100চ
M3 The number of ‫ غ‬indicates the length (m)
Screws
of the cable ( ‫غ‬㧩 5, 10, 15).
Twist Pair Cable with Shield Tube : 1P- 0.75চ2 or more

*for Australia
Connect the both ends of shield net of the shield tube to the earth as shown.
Electrcal Box
Indoor Unit
Control
Cable

Earth Screw

Power Source Cable


Remote Control Switch
TB2

TB1
CAUTION
A. Use a 0.3 to 0.75mm2 cable for connecting. The maximum total cable length is up 30m. If the total cable length
exceeds 30m, use a twist pair cable with shield tube(1P - 0.75mm2 or more). In that case, the maximum total cable
length is up to 500m. If using in combination with the control timer, the allowable total cable length is up to 100m.
The use of a cable other than that specified above can cause of malfunction due to the effects of noise.
B. Keep a distance more than 30cm between the transmission line (remote control switch cable and transmission
wires) and power source of the indoor units.
If not, the air-conditioner may not operate properly or malfunction may occur due to effect of power source noise.
C. In case of simultaneously controlling multiple indoor units, set the refrigerant cycle numbers and addresses of the
indoor units without overlapping.
D. Refer to the Tecnical Catalog Ⅱ provided with each indoor unit when performing electrical wiring work between the
remote control switch and indoor units for setting the refrigerant cycle number and the indoor unit address.
E. No gap shall exist between the remote control switch cable and hole of the remote cotrol switch case. If there is a
gap, cover the gap with vinyl tape.
If not, malfunction may occur due to entrance of water droplets or insects.
F. In case of operating with two remote control switches (Master and Slave), set the master and slave controllers by
selecting the appropriate function with the remote control switches according to the section 5. After setting it, turn
off the power supply of all the indoor unit connected to the remote control switches.

4. Checking Procedures
‫ غ‬1) Turn ON the power supply for all the indoor units.

NOTE:
Although a portion of the LCD (liquid crystal display) of the remote control switch may light immediately after the
power is turned on, this is not a malfunction.

‫ غ‬2) For the models with the auto-address function, wait for 3 minutes apporoximately. The addressing is automati-
cally performed. (There is a case that 5 minutes is required according to the setting condition.)

‫ غ‬3) Set the “TEST RUN” mode by pressing the “MODE” and “CHECK” switch simultaneously for more than 3 sec-
onds.
NOTES:
A."TEST RUN" is displayed on the LCD. ← Example when 5 indoor Units are
unit connected.
B.The total number of the indoor units connected is
indicated on the LCD.
C. In case that the indicated number is not correct, the auto-address function is not performed correctly due to
incorrect wiring, the electric noise or etc.
Turn OFF the power supply and correct the wiring after checking the following points;
(Do not repeat turning ON and OFF within 10 seconds.)
1. Power Supply for Indoor Unit is Not Turned ON or Incorrect Wiring.
2. Incorrect Connection of Connecting Cable between Indoor Units or Incorrect Connection of Controller Cable
3. Incorrect Setting of Rotary Switch and Dip Swiach (The setting is overlapped.) on the Indoor Units PCB
D. Check to ensure that the “TEST RUN” mode is not set.

‫ غ‬4) Canceling “TEST RUN” Mode


1. When the unit is not operating, press the RESET switch.
2. When the unit is operating, press the RUN/STOP switch.

ATTENTION:
When "00" is indicated, the auto-address function may be performing.
Cancel the "TEST RUN" mode and set it again.
5.. Optional Setting and Input / Output Setting of Indoor Unit

Normal Mode (When unit is not operating) 3. Selection of Indoor Unit for Optional Setting
" 01" or "02" flashes.
1. Change to the optional setting mode. Select the indoor unit to set by
Press the “CHECK” switch and the ”RESET”
HIGH
pressing the “ щ ” or “ ш ” switch
C OOL

switch simultaneously for more than 3 seconds. ADDS RN and press the “CHECK” switch.
A / C SERVICE
The address of the indoor unit (ADDS)
2. Selection of Optional Setting Mode to set and the refrigerant cycle number
(RN) are indicated by 0 to 15. (The left
HIGH SET TEMP.
C OOL HIGH figure shows the No.1 cycle and No.2
C OOL indoor unit.)
A / C SERVICE
ADDS RN
<Example>
A / C SERVICE
When selecting No.2 cycle and No.3 indoor
unit (The address is indicated by 0 to 15.)
Press the "TEMP." щ QT ш switch
“SERVICE” is
and set “01” or “02”. Then press NOTES: (1) In case that the both indications of the “ADDS.” and “RN” show “AA”,
indicated and the the same setting is performed to all the indoor units.
mode number is the “CHECK” switch. (2) The address of indoor unit not connected is not indicated.
flashed.

Optional Setting Mode (Mode Number “01”) Input / Output Setting Mode (Mode Number “02”)
4. Selection of Optional Setting Items 4. Selection of Input / Output Number
Item Code of Input / Output Number
HIGH
Optional Setting HIGH
C OOL
C OOL
Select the input /
Select the item code output number by
A / C SERVICE
by pressing the A / C SERVICE pressing the “TIME”
“TIME”ٖorٌ ٖorٌ switch.

HIGH
switch.
C OOL HIGH
<Example> C OOL
<Example>
SERVICE
When selecting C5 When selecting o1
A / C
(Increasing Fan SERVICE (Output 1)
A / C
Speed)

* Refer to Table B (Page 8) for contents of the input / output


In Case of Setting Other Items
setting.
5. Change of Setting Conditions
Setting Condition In Case of Setting Other Items
HIGH
C OOL The optional setting 5. Change of Setting Conditions
condition is changed
Contents of Input / Output Setting
A / C SERVICE by pressing
HIGH
the “CHECK” switch. The optional setting
C OOL
condition is changed
<Example> When setting 01(Increasing Fan Speed 1)
A / C SERVICE (0→1→2→̖) by
̪ Refer to the contents of the setting codes for the Table A of “Optional pressing the “CHECK”
Setting Items”. switch.
<Example> When setting 04 (Output: Thermo-ON for Cooling)

̪ Refer to the Table C for the contents of the input / output setting.

Normal Mode
Press щ or ш switch in step 4 or 5 when selecting
Press the “RESET” switch in the condition of 4 or 5 to cancel the settings for another unit.
optional setting mode.
6. Initialization of Optional Setting and Input/Output Setting
The procedure for initialization of optional settings and input / output settings are as follows.
Normal mode (when unit is not operating) 3. Selection of Indoor Unit
1. Change to the optional setting mode. "07" flashes. Select the address of the indoor unit
to be returned to the optional setting-
Press the “CHECK” switch and the ”RESET” HIGH
input/output factory settings.
switch simultaneously for more than 3 seconds. C OOL
ADDS RN
Press the "TEMP." control ∨ or ∧
2. Selection of Optional Setting Mode A /C SERVICE
switch and select the address of the
indoor unit.
HIGH SET TEMP.
Press the "TEMP."
C OOL
"∨" or "∧" switch,
NOTES:
select "07" for
A / C SERVICE * In case of control by using two remote controllers (Master and Slave),
the optional input
settings shall be operated by the master controller.
/ output setting
“SERVICE” is indicated and the mode * In case of selecting the address of the indoor unit not to initialize the
number is flashed.
cancel mode, and
optional and input / output setting, "NO FUNCTION" is displayed.
then press the
* If selecting the indoor unit address "AA", the indoor units that do not
"CHECK" switch.
have these initialization function cannot be restore to the factory setting.

4. Optional Setting and Input/Output Setting Initialization


HIGH HIGH
When displayed "CL",
C OOL
ADDS RN
C OOL
ADDS RN
the optional and input
A/C SERVICE A/ C SERVICE / output settings are
Press "CHECK" switch and the initialized. (restore to
Check to ensure that there are no problems initialization is performed. factory settings.)
to restore the factory settings, and perform It takes approximately 15 to 30 In case of performing to initialize the other indoor units, repeat
to initialize. seconds. the procedure from step 3.
In this case, the indoor unit address is completed to initialize,
the indication "CL" is displayed.

Normal mode In case that initialization is not required, press the “RESET” switch in step 4.

● Table A Optional Setting Items


Individual Setting
No. Items Optional Function Contents
Setting Condition
Removal of Heating 00 Standard (Set Temp. +4oC)
1 b1 Temperature Compensation ٤ 01 Removal (Set Temp.)
due to Uneven Heat Load 02 Set Temp. +2oC (*1)
Circulator Function at 00 Not Available
2 b2 ٤
Heating Thermo-OFF 01 Available
Enforced 3 Minutes
00 Not Available
3 b3 Minimum Operation Time of ٤
01 Available
Compressor
00 Standard
01 100 hours
4 b4 Change of Filter Cleaning Time ٤ 02 1,200 hours
03 2,500 hours
04 No Indication
00 Not Available
5 b5 Fixing of Operation Mode ˜ 01 Available
00 Not Available
6 b6 Fixing of Setting Temperature ˜ 01 Available
Fixing of Operation as 00 Not Available
7 b7
Exclusive Cooling Unit ˜ 01 Available
00 Not Available
8 b8 Automatic COOL/HEAT Operation ˜ 01 Available
00 Not Available
9 b9 Fixing of Fan Speed ˜ 01 Available
10 bA Not Prepared ˜ “- -” Fixed Not Used
00 Standard (No Compensation)
Cooling Temperature Compensation
11 bb ٤ 01 Set Temp. –1oC
due to Uneven Heat Load
02 Set Temp. –2oC
00 Not Used
12 bC Not Prepared -
01 (Use as 00 conditions)
00 Not Used
13 bd Not Prepared -
01 (Use as 00 conditions)
00 Not Used
14 bE Not Prepared -
01 (Use as 00 conditions)
Individual Setting
No. Items Optional Function Contents
Setting Condition
00 Not Used
15 C1 Not Prepared -
01 (Use as 00 conditions)
16 C2 Not Prepared - “- -” Fixed Not Used
00 Not Used
17 C3 Not Prepared ٤
01 (Use as 00 conditions)
00 Not Used
18 C4 Not Prepared ٤
01 (Use as 00 conditions)
00 Not Available
19 C5 Hi Speed ٤ 01 Hi Speed 1 (*2)
02 Hi Speed 2 (*2)
00 Not Available
20 C6 Hi Speed at Heating Thermo-OFF ٤
01 Available
Canceling of Enforced 3 Minutes
00 Available
21 C7 Minimum Operation Time of ٤
01 Not Available
Compressor
00 Control by Indoor Suction Thermistor
01 Control by Thermistor of
Remote Control Switch
22 C8 Thermistor of Remote Control Switch ٤
02 Control by Average Value of
Indoor Suction Thermistor and
Thermistor of Remote Control Switch
23 C9 Not Prepared - “- -“ Fixed Not Used
24 CA Not Prepared - “- -“ Fixed Not Used
00 Forced Stoppage Input: A Contact
25 Cb Selection of Forced Stoppage Logic ˜ 01 Forced Stoppage Input: B Contact
00 Not Used
26 CC Not Prepared ˜ 01 (Use as 00 conditions)
00 Not Used
27 Cd Not Prepared ٤
01 (Use as 00 conditions)
00 Not Used
28 CE Not Prepared -
01 (Use as 00 conditions)
00 Standard (7 Steps)
29 CF Change of Louver Swing Angle ٤ 01 Draft Prevention (5 Steps)
02 High Ceiling (5 Steps) (*3)
00 Not Used
30 d1 Not Prepared ٤
01 (Use as 00 conditions)
31 d2 Not Prepared - “- -“ Fixed Not Used
00 Not Available
32 d3 Power Supply ON/OFF 2 ٤
01 Available
Prevention for Cooling Discharge Air 00 Not Available
33 d4 ٤
Temp. Decrease 01 Available
Prevention for Heating Discharge Air 00 Not Available
34 d5 ٤
Temp. Decrease 01 Available
Room Temp. Control for Energy 00 Not Available
35 d6 ٤
Saving 01 Available
00
01
02
03
36 d7 Not Prepared ٤ Not Used(Use as 00 conditions)
04
05
06
07
00 Automatic Ventilation
01 Ventilation by Total Heat Exchanger
37 E1 Ventilation Mode ٤
02 Bypass Ventilation
(No Total Heat Exchanging)
00 Not Available
38 E2 Increasing Supply Air Volume ٤
01 Available
00 Not Used
39 E3 Not Prepared ٤
01 (Use as 00 conditions)
00 Standard
40 E4 Precooling / Preheating Period ٤ 01 30 min.
02 60 min.
00 Not Used
41 E5 Not Prepared ٤
01 (Use as 00 conditions)
00 Not Available
Indoor Fan Operation Time After
42 E6 ٤ 01 60 min.
Cooling Operation Stoppage
02 120 min.
Individual Setting
No. Items Optional Function Contents
Setting Condition
00 Not Used
43 E7 Not Prepared -
01 (Use as 00 conditions)
Fan Operation Control at Heating 00 Not Available
44 E8 ٤
Thermo-OFF 01 Available
00 Not Used
45 E9 Not Prepared -
01 (Use as 00 conditions)
00
Not Used
46 EA Not Prepared ٤ 01
(Use as 00 conditions)
02
00 Not Available
Fan Operation Control at Cooling
47 Eb ٤ 01 LOW
Thermo-OFF
02 SLOW
Forced Thermo-ON Stoppage at 00 Not Available
48 EC ٤
Cooling 01 Available
00 Not Used
49 Ed Not Prepared ٤
01 (Use as 00 conditions)
00 Not Available
50 EE Automatic Fan Speed Control ٤
01 Available
00 No Function
01 OFF Timer by 1 hour
02 OFF Timer by 2 hours
• •
51 F1 Automatic OFF Timer Setting ˜ • •
23 OFF Timer by 23 hours
24 OFF Timer by 24 hours
0A OFF Timer by 0.5 hour
0B OFF Timer by 1.5 hours
00 Main
52 F2 Remote Control Main-Sub Setting ˜ 01 Sub
Automatic Reset of Setting 00 Not Available
53 F3
Temperature (*4) ˜ 01 Available
00 30 min. (Factory-Setting)
01 15 min.
54 F4 Automatic Reset Time ˜ 02 60 min.
03 90 min.
19 19oC
20 20oC
• •
• •
Automatic Reset Temperature
55 F5
for Cooling (*5) ˜ 25 25oC (Factory-Setting)
• •
• •
29 29oC
30 30oC
17 17oC
18 18oC
• •
• •
Automatic Reset Temperature
56 F6
for Heating (*6) ˜ 21 21oC (Factory-Setting)
• •
• •
29 29oC
30 30oC
Operation Stoppage Prevention by
00 Not Available
57 F7 Remote Control Switch Operational ˜ 01 Available
Error (*7)
Lock Function for Operation Mode 00 Not Available
58 F8
Selection ˜ 01 Available (Factory-Setting)
Lock Function for Temperature 00 Not Available
59 F9
Setting ˜ 01 Available (Factory-Setting)
Lock Function for Fan Speed 00 Not Available
60 FA
Selection ˜ 01 Available (Factory-Setting)
Lock Function for Swing Louver 00 Not Available
61 Fb
Operation ˜ 01 Available (Factory-Setting)
Individual Setting
No. Items Optional Function Contents
Setting Condition
00 Standard
01 Lower Limit +1oC
02 Lower Limit +2oC
Cooling Lower Limit for Setting
62 FC
Temperature (*5) ˜ • •
• •
09 Lower Limit +9oC
10 Lower Limit +10oC
00 Standard
01 Upper Limit –1oC
02 Upper Limit –2oC
Heating Upper Limit for Setting
63 Fd
Temperature (*6) ˜ • •
• •
09 Upper Limit –9oC
10 Upper Limit –10oC
00
64 FE Not Prepared - 01 Not Used (Use as 00 condition)
02
00 Not Available
65 FF Lock Function for ON / OFF Timer ˜ 01 Available (Factory-setting)
*1: The "02" setting may not be available according to the type of indoor unit.
*2: In case of 'XFW models, 00: Increasing fan speed 1 (standard), 01: Increasing fan speed 2 (high static pressure),
02: Standard (low static pressure)
*3: 00: Standard (7-step operation), 01: Draft Prevention (lower 2 steps cutoff), 02: High ceiling (upper 2 steps cut off)
*4: In case that the set temperature is changed and kept within the set time at "F4", the temperature is automatically changed to "F5"
and "F6". (In case that the set temperature is out of range at "F5" and "F6", it is applied within upper and lower limit for the set
temperature.)
*5: Applicable to fan, cooling and dry operation modes.
*6: Applicable to heating operation mode.
*7: Operation is stopped by pressing the "RUN/STOP" switch for 3 seconds.

NOTES:
* After at least 3 minutes from the power ON, change the optional setting.
* When changing "CF" setting (change of louver swing range), restore the power supply or allow the louver to make one complete
swing fully in the auto swing mode to apply the optional setting.
* The optoinal settings are different according to the indoor and outdoor unit models. Check to ensure that the unit has the optional
setting or not.
* Record the setting conditions for each optional setting in the "Setting" column of the table.

●Table B Input and Output Number Display and Connectors ●Table C Input and Output Settings and Display Codes
Input number Port Factory Setting Setting Indication Input Output
display 00 Not set Not set
Input / Output Indication Setting Item Indiicaton 01 Room Thermostat (for Cooling) Operation
02 Room Thermostat (for Heating) Alarm
Input1 CN3 1-2 Remote ON/OFF 1 (level) 03 03 Remote ON/OFF 1 (level) Cooling
Input2 CN3 2-3 Forbidding Remote Control 06 04 Remote ON/OFF 2 (Operation) Thermo-ON for
after Manual Stoppage Cooling
Output1 CN7 1-2 Operation 01 05 Remote ON/OFF 2 (Stoppage) Heating
06 Forbidding Remote Control Thermo-ON for
Output2 CN7 1-3 Alarm 02 after Manual Stoppage Heating
07 Remote Cooling / Heating Total Heat Exchanger
Output3 CN8 1-2 Thermo-ON for Heating 06
Change
08 Elevating grille input Elevating Grille output
NOTES:
* After at least 3 minutes from the power ON, change the optional setting.
* The elevating grille input can be set to Input 2 only " ".
The elevating grille cannot be set to Input 1.
* The elevating grille output can be set to Output 1 or Output 2 only " " or " ".
The elevating grille output cannot be set to Output 3.
* Do not set the elevating grille for the total heat exchanger.
* Record the setting conditions for each input and output in the "Setting" column of the table.
7. Changing Indoor Unit Address from Remote Control Switch
The address (unit number) of the indoor unit can be changed by using the remote control switch ( CWH-01QE ).
NOTES:
* In case of operating with two remote control switches (master and slave), the address of the indoor units cannot be
changed or checked.
* The address may not be able to be changed depending on the type of indoor unit.
* Do not operate the central controller when in the address check mode or address change mode.
(1) Check the Indoor Unit for which the address to be changed.
Address of Indoor Unit to be Changed is not known (check) . . . Proceed to (2) Address Check Mode.
Address of Indoor Unit to be Changed is known . . . Proceed to (3) Address Change Mode.
Initialize address set with the automatic address function or initialize address that has been changed with the
address change mode. . . Proceed to (4) Address Initialization Mode.

(2) Address Check Mode


This function is for two or more the indoor units are connected to the remote control switch.
The indoor unit address can be checked by the indoor unit individual operation with selecting the indoor address.
Normal Mode (when unit is not operating)
1. Change to the optional setting mode. 3. Selection of Indoor Unit
Press the “CHECK” switch and the ”RESET”
"05" Indicates. Select the address of the indoor
switch simultaneously for more than 3 seconds.
HIGH
unit to be operated.
2. Selection of Optional Setting Mode C OOL
ADDS RN
Press the "TEMP." щ or ш
HIGH SET TEMP.
A / C SERVICE
switch and select the address of
C OOL
the indoor unit.
A / C SERVICE
"CHECK" The address and refrigerant cycle
Switch number of the indoor unit to be set are
“SERVICE” is Press the "TEMP" щ or ш switch, displayed (the diagram at left shows the
indicated and the select "05" for the address check No. 2 cycle and the No. 3 indoor unit).
mode number is NOTES:
flashed.
mode, and then press the "CHECK"
switch. * Unconnected indoor unit address is not displayed.
* In case of control by using two remote control switches (Master and
Slave), the indoor unit addresses cannot be checked.

"RUN/STOP" switch "RESET" switch

4. Run and Stop Indoor Unit. 5. Ending Address Checking


HIGH After selecting the indoor unit, press the "RUN/ HIGH SET TEMP.
C OOL
ADDS RN
STOP" switch to operate the indoor unit of the C OOL

A / C SERVICE
displayed address.
A / C

Pressing the "RUN/STOP" switch during the


indoor unit operation, returns to the indoor unit Press the "RESET" switch during the indoor
selection procedure of step (3). unit operation OFF to return to the normal
Repeat steps (3) and (4) until the address number of the indoor unit for which the address mode.
is to be changed is able to be checked. When selecting another indoor unit, first stop the Once the address of the indoor unit to be
operation of the indoor unit currently being checked. changed has been checked, change the
NOTES: address of the indoor unit by proceeding to
* All operations other than operation of the "RUN/STOP" switch are not available during step (3) Address Change Mode.
the address checking.
* Do not operate from the central station during the address checking.
(3) Address Change Mode
Change the address (unit number) of the indoor unit.
Normal Mode (when unit is not operating) 3. Selection of Indoor Unit
1. Change to the optional setting mode. "04" indicated. Select the address of the indoor
unit to be changed.
Press the “CHECK” switch and the ”RESET” HIGH

switch simultaneously for more than 3 seconds. C OOL Press the "TEMP." щor ш
switch to select the address of
ADDS RN

2. Selection of Optional Setting Mode A / C SERVICE


the indoor unit and then press the
HIGH SET TEMP. "CHECK" switch.
C OOL
The address and refrigerant cycle
"CHECK"
SERVICE number of the indoor unit to be set
A / C
switch change from flashing to remaining lit.
NOTE:
“SERVICE” is Press the temperature controlщ or
indicated and the * In case of selecting the address not to change, "NO FUNKTION" is
mode number is
ш switch, select "04" for the address displayed.
flashed. change mode, and then press the
"CHECK" switch.

4. Change the address of the indoor unit.


HIGH Select the new address to be used after
C OOL
changing the address.
ADDS RN
NOTE:
The refrigerant cycle number display can be
A refrigerant cycle number of "99" is used in case
A / C SERVICE

changed from 00 to 63 by pressing the "TIME" Ш


of temporarily avoiding setting an address when
or ٌ switch, and the unit number display can be
"CHECK" switch all indoor unit refrigerant cycle numbers or unit
changed from 00 to 63 by pressing the "TEMP."
numbers are in use. If an address has been set
control щ orш switch.
HIGH to "99", make sure to subsequently change the
C OOL
ADDS RN The address display changes from flashing to address to an address within the normal address
A / C SERVICE remaining lit when the "CHECK" switch is pressed range.
after selecting an address.

The result of changing the address is displayed several seconds after the "CHECK" switch has been pressed. "AH" is temporarily
displayed if address change processing has been completely succeeded, while "EE" is temporarily displayed if the address was unable
to be changed. If this happens, repeat the procedure for changing the address.

5. Changing the address of another indoor unit.


HIGH Select the address of the indoor unit to be changed.
C OOL
ADDS RN Pressing the "TEMP." control ∨ or ∧ switch after the result of an address change is displayed in step 4 for
A/ C SERVICE changing the address of an indoor unit, returns to the selection of an indoor unit of step 3.
Repeat steps 3 and 4 until all indoor unit address changes have been completed.

6. Ending Address Change. 7. Turning ON Power of Indoor Unit.


HIGH
Press the "RESET" switch Once turn OFF the power of the indoor unit 3 to 5 minutes after
C OOL
during selection of an indoor completing step 6. After the display on the remote control switch
ADDS RN

SERVICE unit of step 3return to the is no longer displayed, turn ON the power of the indoor unit.
A / C

normal mode.
NOTE:
Once the address of the indoor
After ending address change in step 6, make sure to turn off the
"AC" flashes while connections are unit has been successfully
power of the indoor unit. If this procedure is not performed, the
being checked. changed, processing for
automatic address function may not be performed properly.
checking connections begins.

NOTE:
In the case of having changed the address of the indoor unit with
the remote control switch, make sure to record the new refrigerant
cycle number and unit number of the indoor unit that has been
changed in the entry column on the printed board. Entry column
⸥౉ᰣ
(4) Address Initialization
This is used to initialize an address that has been changed in the address change mode or to initialize an indoor unit
address that has been set with the automatic address function. When set this function, the address of the indoor unit
is returned to the dip switch setting. (Repeat automatic address setting if the dip switch setting is to the automatic
address setting.)
Normal mode (when unit is not operating)
1. Change to the optional setting mode.
3. Select an indoor unit.
Press the “CHECK” switch and the ”RESET”
switch simultaneously for more than 3 seconds. "06" Indicates. Select the address of the indoor unit for
HIGH which the address is to be initialized.
2. Selection of Optional Setting Mode C OOL
ADDS RN
Press the "TEMP." щor ш switch
HIGH SET TEMP.
A / C SERVICE
and select the address of the indoor
C OOL
unit.
A / C SERVICE
"CHECK"
switch NOTES:
* In case of control by two remote control switches (Master ayd Slave),
“SERVICE” is settings shall be operated by the master controller.
Press the "TEMP."щor ш
indicated and the
mode number is switch, select either "06" for the * In case of selecting the address not to change "NO FUNCTION" is
flickered. address initialization mode, and displayed .
then press the "CHECK" switch. * When selecting indoor address "AA", the indoor unit address that does
not have an address initialization cannot be cleared.

4. Address Initialization

HIGH The displayed address is initialized. Check that there is no problem with initializing the address.
C OOL
ADDS RN

SERVIC
Automatic address initialization starts when the "CHECK" switch is pressed.
A / C

● Once the address has been successfully initialized, processing for checking connections starts.
● If the address has already been initialized or the indoor unit does not have an address initialization
function, the address and refrigerant cycle number to be set change from flashing to remaining lit.
The address and refrigerant cycle Repeat the setting procedure from step 3 when initializing the addresses of other indoor units.
number of the indoor unit to be set
flash temporarily. Press the "RESET" switch to end address initialization.
8. Elevating Grille Group Setting and Cancellation
Group setting of the elevating grille refers to a function that allows all settings for the elevating grille (setting of elevating
functions for input 2 and outputs 1 and 2) to be made all at once for all indoor units connected to the remote control
switch. Settings are made by following the procedure as follows.
●Elevating Grille Group Setting Procedure
Normal mode (when unit is not operating)

1. Switch to the elevating grille group setting mode.


Press the “CHECK” switch and the ”RESET”
switch simultaneously for more than 3 seconds.

2. Elevating grille Group Setting Procedure "RESET" 3. Display Following Elevating Grille Group Setting Procedure
Switch
HIGH "GRL" is SET
HIGH
C OOL displayed. "SET" flashes
C OOL
for 3 seconds.
A/ C
A/C
"RUN/STOP"
Press the "RUN/STOP" switch when making group Switch
The elevating grille settings are made for all indoor units
settings. (Press the "RESET" switch to return to the connected to the remote control switch. "SET" flashes for 3
normal mode without making group settings.) seconds after settings have been made, and then automatically
returns to the normal mode.

NOTES:
* In case of using by two remote control switches (Master and Slave), the settings shall be operated by the master controller.
* Group settings are made to all indoor units connected to the remote control switch regardless of whether or not these are actually
provided with the elevating grille. The indoor unit to be set cannot be selected. (In this case, refer to section 5, "Optional Setting
and Input/Output Setting from Remote Control Switch".)
* Please note that when functions other than the elevating grille have been set for input 2 and output 1 and 2, those settings are
cleared (namely, there are overwritten by the elevating grille function).

Elevating grille settings can be canceled all at once by following the procedure as follows.
●Elevating Grille Group Cancellation Procedure
3. Select the unit to be set.
Normal mode (when unit is not operating)
"02" Indicates. Press the "TEMP." ∨ or ∧ switch,
1. Change to the optional setting mode. HIGH
select the address of the indoor
Press the “CHECK” switch and the ”RESET” C OOL
unit to be set and then press the
switch simultaneously for more than 3 seconds. ADDS RN "CHECK" switch.
A/ C SERVICE
The address and refrigerant cycle
2. Select the input/output setting mode.
number of the indoor unit to be
HIGH SET TEMP.
set are displayed (the diagram at
C OOL left shows the No. 1 cycle and the
HIGH
No. 2 indoor unit). All units are
C OOL
A/ C SERVICE
ADDS RN
displayed at once when "AA" is
A/ C SERVICE
set for both the refrigerant cycle
number and address.
“SERVICE” is Press the "TEMP." ∨ or ∧ switch,
indicated and the select "02" for the input/output Example: Display in case of
mode number is group cancellation of all units.
flashed. setting mode, and then press the
"CHECK" switch.
When canceling elevating grille settings for
other units, repeat selection of the indoor units
4. Group cancellation procedure by pressing the "TEMP." щorш switch.
HIGH Press the " ɪɫ "
C OOL
ADDS RN
switch.
NO FUNCTION Press the "RESET" switch to cancel the
A/C SERVICE
The elevating grille settings for the selected cancellation procedure.
units are canceled all at once and input
"NO FUNCTION" flashes for 2 1 and output 1 and 2 are returned to the Normal mode
seconds factory settings. "NO FUNCTION" flashes
for 2 seconds following this procedure.

317B39060, 2007