Pro Series Datasheet 0
Pro Series Datasheet 0
Pro Series Datasheet 0
PM335 EM235
HIGHLIGHTED FEATURES
The PRO Series power analyzers are available
as the PM335 panel mount (4-inch round /
® Class 0.2S accuracy (IEC / ANSI)
92×92mm square cutouts) form factor design
and the EM235 DIN-rail form factor design. ® AC / DC metering
Specifications are subject to change without notice. Copyright © 2021-2022 SATEC Ltd. PRO SERIES Datasheet December 2022
1
PRO SERIES
3.5”(49x73mm) LCD
1.8”(28x35mm) LCD
Anti-tamper
50mm deep, 92×92 square sealed enclosure
Additional modules or 4” round cutout
compatible with all fits type-tested switchboards
PRO Series models with add-on modules
2
PRO SERIES
FEATURES
Modbus
I O 101/104
DNP3
DIGITAL OPEN
IN/OUT PROTOCOL
` Up to 26 external digital triggers from ` Class 0.2S IEC 62053-22 / Class 0.2 C12.20
protection relays; onboard zero-sequence four-quadrant active and reactive energy
currents and volts, current and voltage polyphase meter
unbalance; fault waveforms and fast RMS trace;
` Demand Meter: amps, volts, harmonic demands
cross triggering between multiple devices via
digital inputs for synchronous event capture and ` Precise Energy and Power Demand Meter: Time-
recording of-Use (TOU), 16 Summary (totalization) and
TOU energy and demand registers for substation
` Event recorder for logging internal diagnostics
energy management; accumulation of energy
events, control events and I/O operations.
pulses from external watt-meters; block and
` 8 Fast Waveform recorders: 7-channel (V1-V3, sliding demands; up to 64 energy sources
I1-I4) simultaneous recording; selectable AC
` Harmonic Analyzer: up to 63rd harmonic for volts
sampling rate of 32, 64, 128 or 256 samples
and amps; directional power harmonics and
per cycle; 20 pre-fault cycles; synchronized
power factor; phasor, symmetrical components
waveforms from multiple devices in a single plot;
exporting waveforms in COMTRADE and PQDIF ` 32 digital counters for counting pulses from
file formats is possible via PAS software external sources and internal events
` 3-phase Power meter: true RMS, volts, amps, ` 4 daisy-chain slots for plug-in I/O/COM modules
powers, power factors, unbalance, and neutral
` ExpertPower client for MODBUS/TCP
current
communication with either a Remote or Local
(Stand Alone) SATEC’s ExpertPower server
3
PRO SERIES
` Real Time Clock; Internal clock with battery UP TO 4 EXPANSION MODULES SIDE BY SIDE
backup for three years retention time
` Up to 2 expansion modules: self-energized.
4
PRO SERIES
APPLICATIONS
5
PRO SERIES
TECHNICAL SPECIFICATIONS
DIGITAL INPUTS (2 DI) 4 relays rated at 5A/250V AC; 5A/30V DC, 1 contact (SPST
Form A)
Dry Contacts, internally @ 24V DC
wetted Galvanic isolation:
Between contacts & coil 3000V AC @ 1mn
Galvanic isolation 4000V AC @ 1mn Between open contacts 750V AC
Internal power supply 24V DC Operate time 10 ms max.
Scan time 1 ms Release time 5 ms max.
Connector type removable, 5 pins Wire size 14 AWG (up to 1.5 mm2)
Wire size 14 AWG (up to 1.5 mm2)
Terminal pitch 5mm
6
PRO SERIES
ADDITIONAL SPECIFICATIONS
POWER SUPPLY REAL-TIME CLOCK
Rated input 57.7-277V AC @ 50/60 Hz, Accuracy Typical error ±15 seconds per
48-290V DC month / < 5 minutes/year @ 25˚C
Tolerance ±15%
Burden 11VA@V AC, 6VA@V DC LOG MEMORY
Isolation 4000V AC @ 1mn 16GB memory for long-term waveform and data recording
Wire size Up to 14 AWG (≤ 2.5 mm2)
MATERIALS
COM4
Case enclosure Plastic PC/ABS blend
InfraRed COM port, Front Panel access with magnetic head
Display body Plastic PC/ABS blend
Supported protocols MODBUS RTU & DNP3
IEC 62056-21 Front panel Plastic PC
(for local meter data exchange) PCB FR4 (UL94-V0)
Isolation 4000V AC @ 1mn Terminals PBT (UL94-V0)
Plug-in connectors Polyamide PA6.6 (UL94-V0)
Labels Polyester film (UL94-V0)
7
PRO SERIES
STANDARDS COMPLIANCE
8
PRO SERIES
ORDER STRING
MODELS
PM335 Panel Mount Power Meter PRO-PM335
EM235 DIN-rail Mount Power Meter PRO-EM235
Transducer Version PRO-RPM035
OPTIONS
CURRENT INPUTS
5 Ampere 5A
1 Ampere 1A
5A split core remote high accuracy current sensor (HACS), RS5
50/60Hz only
High Accuracy Current Sensors (HACS), 50/60Hz only HACS
Requires ordering of 3 HACS
GWP: dedicated low voltage interface for GWP sensors GWP
CALIBRATION AT FREQUENCY
50 Hz 50HZ
60 Hz 60HZ
POWER SUPPLY
88-320V AC / 40-290V DC ACDC
INTEGRATED I/Os
2 x digital inputs (dry contact), 1 x Solid State Relay IOS
output, 1 x Universal Analog Input (-1mA to 20mA)
DISPLAY LANGUAGE
English EN
TESTING AND CERTIFICATE
Full functional test, calibration at various work loads & -
detailed test report
Full functional test, calibration at various work loads & CC
detailed test report plus ISO 17025 and ILAC certified
calibration certificate
OPTIONAL PROTOCOLS
IEC 61850 Communication Protocol 850
OPTIONAL MODULES *
I/O (MAX. 3 MODULES PER DEVICE)
4 Relay Outputs - 250V / 5A AC EMR4
4 SSR Outputs - 250V / 0.1A AC SSR4
8 Digital Inputs - Dry Contact DI8-DRC
8 Digital Inputs - 24V DC DI8-24V
8 Digital Inputs - 48V DC DI8-48V
8 Digital Inputs - 125V DC DI8-125V
8 Digital Inputs - 250V DC DI8-250V
AUXILIARY POWER SUPPLY (MAX. 1 PER DEVICE)
AUX. P.S. AC/DC 88-264V AC / 125-300V DC AUX-ACDC
Specifications are subject to change without notice. Copyright © 2021-2022 SATEC Ltd. PRO SERIES Datasheet December 2022
9