Unidrive M Frame 7 To 10 Power Installation Guide Issue 11 en
Unidrive M Frame 7 To 10 Power Installation Guide Issue 11 en
Commander C200
& C300
Unidrive M / HS
Frame 7 to 10
Documentation
Manuals are available to download from the following locations: http://www.drive-setup.com/ctdownloads
The information contained in this manual is believed to be correct at the time of printing and does not form part of
any contract. The manufacturer reserves the right to change the specification of the product and its performance,
and the contents of the manual, without notice.
Environmental policy
Control Techniques Ltd operates an Environmental Management System (EMS) that conforms to the International
Standard ISO 14001.
When electronic products reach the end of their useful life, they must not be disposed of along
with domestic waste but should be recycled by a specialist recycler of electronic equipment.
Control Techniques products are designed to be easily dismantled into their major component
parts for efficient recycling. The majority of materials used in the product are suitable for
recycling.
Product packaging is of good quality and can be re-used. Large products are packed in wooden
crates. Smaller products are packaged in strong cardboard cartons which have a high recycled
fibre content. Cartons can be re-used and recycled. Polythene, used in protective film and bags
for wrapping the product, can be recycled. When preparing to recycle or dispose of any product
or packaging, please observe local legislation and best practice.
REACH legislation
EC Regulation 1907/2006 on the Registration, Evaluation, Authorisation and restriction of Chemicals (REACH)
requires the supplier of an article to inform the recipient if it contains more than a specified proportion of any
substance which is considered by the European Chemicals Agency (ECHA) to be a Substance of Very High
Concern (SVHC) and is therefore listed by them as a candidate for compulsory authorisation.
Further information on our compliance with REACH can be found at: http://www.drive-setup.com/reach
Registered Office
Nidec Control Techniques Ltd
The Gro
Newtown
Powys
SY16 3BE
UK
Registered in England and Wales. Company Reg. No. 01236886.
Copyright
The contents of this publication are believed to be correct at the time of printing. In the interests of a commitment to
a policy of continuous development and improvement, the manufacturer reserves the right to change the
specification of the product or its performance, or the contents of the guide, without notice.
All rights reserved. No parts of this guide may be reproduced or transmitted in any form or by any means, electrical
or mechanical including photocopying, recording or by an information storage or retrieval system, without
permission in writing from the publisher.
This declaration is issued under the sole responsibility of the manufacturer. The object of the declaration is in
conformity with the relevant European Union harmonization legislation. The declaration applies to the variable
speed drive products shown below:
Model
Interpretation Nomenclature aaaa - bbc ddddde
number
M100, M101, M200, M201, M300, M400, M600, M700, M701, M702, F300,
aaaa Basic series
H300, E200, E300, HS30, HS70, HS71, HS72, M000, RECT
bb Frame size 01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 11
c Voltage rating 1 = 100 V, 2 = 200 V, 4 = 400 V, 5 = 575 V, 6 = 690 V
ddddd Current rating Example 01000 = 100 A
A = 6P Rectifier + Inverter (internal choke), D = Inverter, E = 6P Rectifier +
e Drive format Inverter (external choke),
T = 12P Rectifier + Inverter (external choke)
The model number may be followed by additional characters that do not affect the ratings.The variable speed drive
products listed above have been designed and manufactured in accordance with the following European
harmonized standards:
Adjustable speed electrical power drive systems - Part 5-1: Safety requirements -
EN 61800-5-1:2007
Electrical, thermal and energy
Adjustable speed electrical power drive systems - Part 3: EMC requirements and
EN 61800-3: 2004+A1:2012
specific test methods
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for
EN 61000-6-2:2005
industrial environments
Electromagnetic compatibility (EMC) - Part 6-4: Generic standards - Emission
EN 61000-6-4: 2007+A1:2011
standard for industrial environments
Electromagnetic compatibility (EMC) - Part 3-2: Limits for harmonic current
EN 61000-3-2:2014
emissions (equipment input current ≤16 A per phase)
Electromagnetic compatibility (EMC) - Part 3-3: Limitation of voltage changes,
voltage fluctuations and flicker in public, low voltage supply systems, for
EN 61000-3-3:2013
equipment with rated current ≤16 A per phase and not subject to conditional
connection
EN 61000-3-2:2014 Applicable where input current < 16 A. No limits apply for professional equipment where input
power 1 kW.
These products comply with the Restriction of Hazardous Substances Directive (2011/65/EU), the Low Voltage
Directive (2014/35/EU) and the Electromagnetic Compatibility Directive (2014/30/EU).
G Williams
Vice President, Technology
Date: 17th March 2016
These electronic drive products are intended to be used with appropriate motors, controllers, electrical
protection components and other equipment to form complete end products or systems. Compliance with
safety and EMC regulations depends upon installing and configuring drives correctly, including using the
specified input filters.
The drives must be installed only by professional installers who are familiar with requirements for safety
and EMC. Refer to the Product Documentation. An EMC data sheet is available giving detailed information.
The assembler is responsible for ensuring that the end product or system complies with all the relevant
laws in the country where it is to be used.
Adjustable speed electrical power drive systems - Part 5-1: Safety requirements -
EN 61800-5-1:2007
Electrical, thermal and energy
Adjustable speed electrical power drive systems - Part 3: EMC requirements and
EN 61800-3: 2004+A1:2012
specific test methods
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for
EN 61000-6-2:2005
industrial environments
Electromagnetic compatibility (EMC) - Part 6-4: Generic standards - Emission
EN 61000-6-4: 2007+A1:2011
standard for industrial environments
Electromagnetic compatibility (EMC) - Part 3-2: Limits for harmonic current
EN 61000-3-2:2014
emissions (equipment input current ≤16 A per phase)
Electromagnetic compatibility (EMC) - Part 3-3: Limitation of voltage changes,
voltage fluctuations and flicker in public, low voltage supply systems, for
EN 61000-3-3:2013
equipment with rated current ≤16 A per phase and not subject to conditional
connection
EN 61000-3-2:2014 Applicable where input current < 16 A. No limits apply for professional equipment where input
power 1 kW.
These products comply with the Restriction of Hazardous Substances Directive (2011/65/EU), the Low Voltage
Directive (2014/35/EU) and the Electromagnetic Compatibility Directive (2014/30/EU).
Jon Holman-White
Director of Research and Development
Date: 9th October 2018
These electronic drive products are intended to be used with appropriate motors, controllers, electrical
protection components and other equipment to form complete end products or systems. Compliance with
safety and EMC regulations depends upon installing and configuring drives correctly, including using the
specified input filters.
The drives must be installed only by professional installers who are familiar with requirements for safety
and EMC. Refer to the Product Documentation. An EMC data sheet is available giving detailed information.
The assembler is responsible for ensuring that the end product or system complies with all the relevant
laws in the country where it is to be used.
This declaration is issued under the sole responsibility of the manufacturer. The object of the declaration is in
conformity with the relevant European Union harmonization legislation. The declaration applies to the variable
speed drive products shown below:
Model
Interpretation Nomenclature aaaa - bbc ddddde
number
M300, M400, M600, M700, M701, M702, F300, H300, E200, E300, HS30,
aaaa Basic series
HS70, HS71, HS72, M000, RECT
bb Frame size 01, 02, 03, 04, 05, 06, 07, 08, 09, 10, 11
c Voltage rating 1 = 100 V, 2 = 200 V, 4 = 400 V, 5 = 575 V, 6 = 690 V
ddddd Current rating Example 01000 = 100 A
A = 6P Rectifier + Inverter (internal choke), D = Inverter, E = 6P Rectifier +
e Drive format
Inverter (external choke), T = 12P Rectifier + Inverter (external choke)
The model number may be followed by additional characters that do not affect the ratings.
This declaration relates to these products when used as a safety component of a machine. Only the Safe
Torque Off function may be used for a safety function of a machine. None of the other functions of the drive
may be used to carry out a safety function.
These products fulfil all the relevant provisions of the Machinery Directive 2006/42/EC and the Electromagnetic
Compatibility Directive (2014/30/EU).
EC type examination has been carried out by the following notified body:
TUV Rheinland Industrie Service GmbH
Am Grauen Stein
D-51105 Köln
Germany
EC type-examination certificate numbers:
01/205/5270.01/14 dated 2014-11-11
01/205/5387.01/15 dated 2015-01-29
01/205/5383.02/15 dated 2015-04-21
Adjustable speed electrical power drive systems - Part 5-1: Safety requirements
EN 61800-5-1:2007
- Electrical, thermal and energy
Adjustable speed electrical power drive systems - Part 5-2: Safety requirements
EN 61800-5-2:2007
- Functional
Safety of Machinery, Safety-related parts of control systems, General principles
EN ISO 13849-1:2008
for design
EN ISO 13849-2:2008 Safety of machinery, Safety-related parts of control systems. Validation
Adjustable speed electrical power drive systems - Part 3: EMC requirements
EN 61800-3: 2004+A1:2012
and specific test methods
Safety of machinery, Functional safety of safety related electrical, electronic
EN 62061:2005
and programmable electronic control systems
G. Williams
Vice President, Technology
Date: 17th March 2016
Place: Newtown, Powys, UK
IMPORTANT NOTICE
These electronic drive products are intended to be used with appropriate motors, controllers, electrical
protection components and other equipment to form complete end products or systems. Compliance with
safety and EMC regulations depends upon installing and configuring drives correctly, including using the
specified input filters.
The drives must be installed only by professional installers who are familiar with requirements for safety
and EMC. Refer to the Product Documentation. An EMC data sheet is available giving detailed information.
The assembler is responsible for ensuring that the end product or system complies with all the relevant
laws in the country where it is to be used.
This declaration is issued under the sole responsibility of the manufacturer. The object of the declaration is in
conformity with the relevant European Union harmonization legislation. The declaration applies to the variable
speed drive products shown below:
Model
Interpretation Nomenclature aaaa - bbc ddddde
number
aaaa Basic series C300
bb Frame size 01, 02, 03, 04, 05, 06, 07, 08, 09
c Voltage rating 1 = 100 V, 2 = 200 V, 4 = 400 V
ddddd Current rating Example 01000 = 100 A
A = 6P Rectifier + Inverter with internal choke, E = 6P Rectifier + Inverter
e Drive format
(external choke)
The model number may be followed by additional characters that do not affect the ratings.
This declaration relates to these products when used as a safety component of a machine. Only the Safe
Torque Off function may be used for a safety function of a machine. None of the other functions of the drive
may be used to carry out a safety function.
These products fulfil all the relevant provisions of the Machinery Directive (2006/42/EC) and the Electromagnetic
Compatibility Directive (2014/30/EU).
EC type examination has been carried out by the following notified body:
TUV Rheinland Industrie Service GmbH
Am Grauen Stein
D-51105 Köln
Germany
Adjustable speed electrical power drive systems - Part 5-2: Safety requirements
EN 61800-5-2:2007
- Functional
EN 61800-5-1:2007 (in Adjustable speed electrical power drive systems - Part 5-1: Safety requirements
extracts) - Electrical, thermal and energy
Adjustable speed electrical power drive systems - Part 3: EMC requirements
EN 61800-3: 2004+A1:2012
and specific test methods
EN ISO 13849-1:2008 + Safety of Machinery, Safety-related parts of control systems, General principles
AC:2009 for design
EN 62061:2005 + AC:2010 Safety of machinery, Functional safety of safety related electrical, electronic
+ A1:2013 and programmable electronic control systems
Functional safety of electrical/ electronic/programmable electronic safety-
IEC 61508 Parts 1 - 7:2010
related systems
Jon Holman-White
Director of Research and Development
Date: 9th October 2018
Place: Newtown, Powys, UK
IMPORTANT NOTICE
These electronic drive products are intended to be used with appropriate motors, controllers, electrical
protection components and other equipment to form complete end products or systems. It is the
responsibility of the installer to ensure that the design of the complete machine, including its safety-related
control system, is carried out in accordance with the requirements of the Machinery Directive and any
other relevant legislation. The use of a safety-related drive in itself does not ensure the safety of the
machine. Compliance with safety and EMC regulations depends upon installing and configuring drives
correctly, including using the specified input filters. The drive must be installed only by professional
installers who are familiar with requirements for safety and EMC. The assembler is responsible for
ensuring that the end product or system complies with all relevant laws in the country where it is to be
used. For more information regarding Safe Torque Off, refer to the Product Documentation.
A Caution contains information which is necessary for avoiding a risk of damage to the
product or other equipment.
CAUTION
NOTE A Note contains information, which helps to ensure correct operation of the product.
1.3 Responsibility
It is the responsibility of the installer to ensure that the equipment is installed correctly with regard to
all instructions given in this guide. They must give due consideration to the safety of the complete
system, so as to avoid the risk of injury both in normal operation and in the event of a fault or of
reasonably foreseeable misuse.
The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or
incorrect installation of the equipment.
Safety information
Extreme care is necessary at all times when working with or adjacent to the drive. Hazardous voltage
may be present in any of the following locations:
• AC and DC supply cables and connections
• Output cables and connections
• Many internal parts of the drive, and external option units
Unless otherwise indicated, control terminals are single insulated and must not be touched.
The supply must be disconnected by an approved electrical isolation device before gaining access to
the electrical connections.
Product information
The STOP and Safe Torque Off functions of the drive do not isolate dangerous voltages from the
output of the drive or from any external option unit.
The drive must be installed in accordance with the instructions given in this guide. Failure to observe
the instructions could result in a fire hazard.
Mechanical installation
has been disconnected. If the drive has been energized, the AC supply must be isolated at least ten
minutes before work may continue.
Electrical installation
fail-safe mechanical brake in case of loss of motor braking.
With the sole exception of the Safe Torque Off function, none of the drive functions must be
used to ensure safety of personnel, i.e. they must not be used for safety-related functions.
The Safe Torque Off function may be used in a safety-related application. The system designer is
responsible for ensuring that the complete system is safe and designed correctly according to the
relevant safety standards.
The design of safety-related control systems must only be done by personnel with the required
training and experience. The Safe Torque Off function will only ensure the safety of a machine if it is
correctly incorporated into a complete safety system. The system must be subject to a risk
Technical data
assessment to confirm that the residual risk of an unsafe event is at an acceptable level for the
application.
Instructions in this guide regarding transport, storage, installation and use of the equipment must be
complied with, including the specified environmental limits. This includes temperature, humidity,
contamination, shock and vibration. Drives must not be subjected to excessive physical force.
Safety information
2.1 Introduction
This guide provides the information necessary to install the following drive models:
Unidrive M200 to M400 frame 7 to 9
Unidrive M600 to M702 frame 7 to 10
Unidrive HS70 to HS72 frame 7 to 10
Commander C200 to C300 frame 7 to 9
Product information
This guide focuses on the drive power section, for example: electrical installation of the supply /
motor cables and mechanical installation of the drive.
For information about the drive control section, for example: parameter set up information, control
and encoder connections, please refer to the Control User Guide.
2.2 Model number
The model numbers for the Unidrive M/HS and Commander product range are formed as illustrated
below:
Mechanical installation
Figure 2-1 Model number
Identification Label
Derivative Electrical Specifications Power Configuration* Documentation Customer Code Optional Build
Reserved
Format
M600 - 03 4 00078 A 1 0 1 01 A B 1 0 0
Electrical installation
Unidrive M700 IP / NEMA Rating:
Unidrive M701 1 = IP20 / NEMA 1
Unidrive M702
Unidrive HS70 Brake Transistor:
Unidrive HS71 B = Brake
Unidrive HS72 N = No
Commander C200
Commander C300 Cooling:
A = Air
Frame Size:
Customer Code:
00 = 50 Hz
Voltage Rating: 01 = 60 Hz
2 - 200 V (200 - 240 ± 10 %)
4 - 400 V (380 - 480 ± 10 %) Documentation:
5 - 575 V (500 - 575 ± 10 %) 0 - Supplied separately
6 - 690 V (500 - 690 ± 10 %) 1 - English
2 - French
3 - Italian
Current Rating: 4 - German
5 - Spanish
Technical data
Heavy Duty current rating x 10
Power Format:
A - AC in AC out (with internal choke)
D - DC in AC out (Inverter)
C - AC in DC out (Rectifier)
E - AC in AC out (without internal choke)
T - AC in AC out (12P rectifier plus inverter)
Configuration:
1 - Standard
U - No Control
M - Master
F - Follower
NOTE
For simplicity a Frame 9 drive with no internal choke (i.e. Model 09xxxxxxE) is referred to as a Frame
9E and a Frame 9 drive with an internal choke (i.e. Model 09xxxxxxA) is referred to as a Frame 9A.
Any reference to Frame 9 is applicable to both sizes 9E and 9A. All Frame size 10 drives are
supplied with no internal choke.
Refer to
User Guide M600-094 02240 E10
Key to approvals
Normal/Heavy 110/132kW 1710 Date code
Duty power rating CE approval Europe
Input phases & input current
Input voltage RCM regulatory
Output phases & Heavy Australia
Output voltage Duty/Normal Duty rating compliance mark
R
UL / cUL approval USA & Canada
Approvals
Serial number
Refer to Figure 2-1 Model number on page 15 for further information relating to the labels.
Safety information
Fuses
The AC supply to the drive must be installed with suitable protection against overload and
short-circuits. The following section shows recommended fuse ratings. Failure to observe
WARNING this requirement will cause risk of fire.
NOTE Nominal cables sizes below are based on the cable installation method B2 (ref: IEC60364-
5-52:2001) unless otherwise specified, and are provided as a guide only. Ensure cables
used suit local wiring regulations.
Product information
Table 2-1 200 V drive ratings, cable sizes and fuse ratings
Max. Nominal cable size
cont. Fuse Normal Duty Heavy Duty
European USA
input
current IEC UL Max. Nom Motor Max. Nom Motor
cont. power power cont. power power
Model Input Output Input Output
3ph Nom Nom output @ @ output @ @
current 230 V 230 V current 230 V 230 V
Class Class
AWG AWG
A A A mm2 mm2 or or A kW hp A kW hp
kcmil kcmil
Mechanical installation
07200610 67 80 80 35 35 2 2 75 18.5 25 61 15 20
CC,
07200750 84 100 gG 100 35 35 1 1 94 22 30 75 18.5 25
J or T*
07200830 105 125 125 70 70 1/0 1/0 117 30 40 83 22 30
08201160 137 200 200 95 95 3/0 3/0 149 37 50 116 30 40
gR HSJ
08201320 166 200 225 2 x 70 2 x 70 2 x 1 2 x 1 180 45 60 132 37 50
2 x 70 2 x 95
09201760 205 250 250 2 x 2/0 216 55 75 176 45 60
(B1) (B2)
gR HSJ
2 x 95 2 x 120
09202190 260 315 300 2 x 4/0 266 75 100 219 55 75
(B1) (B2)
2 x 120 2x
10202830 305 400 400 2 x 250 325 90 125 283 75 100
(B1) 2 x 120 300
gR HSJ
2 x 150 (C) 2x
10203000 361 450 450 2 x 300 360 110 150 300 90 125
Electrical installation
(C) 300
Table 2-2 400 V drive ratings, cable sizes and fuse ratings
Max. Nominal cable size
cont. Fuse Normal Duty Heavy Duty
European USA
input
current IEC UL Max. Nom Motor Max. Nom Motor
cont. power power cont. power power
Model Input Output Input Output
3ph Nom Nom output @ @ output @ @
current 400 V 460 V current 400 V 460 V
Class Class AWG AWG
A A A mm2 mm2 or or A kW hp A kW hp
kcmil kcmil Technical data
07400660 74 100 80 CC, 35 35 1 1 79 37 60 66 30 50
07400770 88 100 gG 100 J or 50 50 2 2 94 45 60 77 37 60
07401000 105 125 125 T* 70 70 1/0 1/0 112 55 75 100 45 75
08401340 155 250 225 2 x 50 2 x 50 2 x 1 2 x 1 155 75 100 134 55 100
gR HSJ
08401570 177 250 225 2 x 70 2 x 70 2 x 1/0 2 x 1/0 184 90 150 157 75 125
2 x 70 2 x 95
09402000 232 300 2 x 3/0 2 x 2/0 221 110 150 200** 90 150
(B1) (B2)
315 gR HSJ
2 x 95 2 x 120
09402240 267 350 2 x 4/0 2 x 4/0 266** 132 200 224** 110 150
(B1) (B2)
2 x 120 2 x 120
UL listing information
10402700 332 400 400 2 x 300 2 x 250 320 160 250 270 132 200
(C) (B2)
gR HSJ
2 x 150 2 x 150
10403200 397 450 450 2 x 350 2 x 300 361 200 300 320** 160 250
(C) (B2)
* These fuses are fast acting.
** These ratings are for 2 kHz switching frequency. For ratings at 3 kHz switching frequency refer to the Power and
current ratings in section 5.1.2 Power and current ratings (Derating for switching frequency and
temperature) on page 94.
Table 2-4 690 V drive ratings, cable sizes and fuse ratings
Max. Nominal cable size
cont. Fuse Normal Duty Heavy Duty
European USA
input
current IEC UL Max. Nom Motor Max. Nom Motor
Model cont. power power cont. power power
Input Output Input Output
3ph Nom Nom output @ @ output @ @
Class Class current 690 V 690 V current 690 V 690 V
A A A mm2 mm2 AWG AWG A kW hp A kW hp
07600190 20 25 25 10 10 8 8 23 18.5 25 19 15 20
07600240 26 32 30 10 10 6 6 30 22 30 24 18.5 25
CC,
07600290 31 40 35 10 10 6 6 36 30 40 29 22 30
gG J or
07600380 39 50 50 16 16 4 4 46 37 50 38 30 40
T*
07600440 44 50 50 16 16 4 4 52 45 60 44 37 50
07600540 62 80 80 25 25 3 3 73 55 75 54 45 60
08600630 83 125 100 50 50 2 2 86 75 100 63 55 75
gR HSJ
08600860 104 160 150 70 70 1/0 1/0 108 90 125 86 75 100
2 x 50 2 x 35
09601040 149 150 150 2x1 2x3 125 110 150 104 90 125
(B2) (B2)
gR HSJ
2 x 70 2 x 50
09601310 171 200 200 2 x 1/0 2 x 1 155 132 175 131 110 150
(B2) (B2)
2 x 70
10601500 202 225 gR 2 x 2/0 2 x 1/0 172 160 200 150 132 175
(B2) 2 x 70
250 HSJ
2 x 95 (B2)
10601780 225 250 gR 2 x 3/0 2 x 2/0 197 185 250 178 160 200
(B2)
NOTE Refer to Chapter 5.1 Drive technical data on page 92 for maximum fuse rating, maximum
cable size and peak currents.
2 Either 10 mm2 or two conductors of the same cross-sectional area as the input
≤ 10 mm
phase conductor
> 10 mm2 and ≤ 16 mm2 The same cross-sectional area as the input phase conductor
> 16 mm2 and ≤ 35 mm2 16 mm2
2 Half of the cross-sectional area of the input phase conductor
> 35 mm
Safety information
motor rated current, motor power factor and motor leakage inductance all result in changes in the
maximum possible overload. Typical values are shown in the table below:
Table 2-6 Typical overload limits
Open loop Open loop
Operating mode RFC from cold RFC from 100 %
from cold from 100 %
Normal Duty overload with motor rated
current = Maximum drive normal duty 110 % for 165 s 110 % for 9 s 110 % for 165 s 110 % for 9 s
rated current
Product information
Heavy Duty overload with motor rated
current = Maximum drive Heavy duty rated 200 % for 28 s 200 % for 3 s 150 % for 60 s 150 % for 7 s
current (size 8 and below)
Heavy Duty overload with motor rated
current = Maximum drive Heavy duty rated 175 % for 42 s 175 % for 5 s 136 % for 81 s 136 % for 11 s
current (size 9 and 10)
Generally the drive rated current is higher than the matching motor rated current allowing a higher
level of overload than the default setting.
Mechanical installation
The time allowed in the overload region is proportionally reduced at very low output frequency on
some drive ratings.
NOTE The maximum overload level which can be attained is independent of the speed.
Output current
The continuous output current ratings given on the rating label are for maximum 40 C (104 F),
1000 m altitude and 3 kHz switching frequency (except where shown). Derating is required for higher
switching frequencies, ambient temperatures >40 C (104 F) and higher altitude. For derating
information, refer to Chapter 5 Technical data on page 92
Electrical installation
Input current
The input current is affected by the supply voltage and impedance. The input current given on the
rating label is the typical input current and is stated for a balanced supply.
Technical data
UL listing information
1 3 4
1 2
5
2
1 3 4
2
1 3 4
5 5 5 5
7 8 9A 9E / 10E
1
1
3 6 3 6 1 3 6 3 6
1
7 7 7 7
Key
1. Ground connections 2. AC supply connections 3. DC bus + 4. DC bus -
5. Rating label 6. Braking terminal 7. Motor connections
Safety information
Started Guide / Quick Start Guide, a safety information booklet, the Certificate of Quality and an
accessory kit box including the items shown in Table 2-7.
Table 2-7 Parts supplied with the drive
Description Size 7 Size 8 Size 9A / 9E Size 10E
Control connectors
(1 to 11 and 21 to 31)
Product information
x 1* x 1*
Control connector
(1 to 13)
x 1**
Relay connector
Mechanical installation
x 1***
24 V power supply
connector
x 1***
Grounding bracket
Electrical installation
x1
Surface mounting
brackets
x2 x2
Stored charge
The drive contains capacitors that remain charged to a potentially lethal voltage after the
AC supply has been disconnected. If the drive has been energized, the AC supply must
WARNING be isolated at least ten minutes before work may continue.
Normally, the capacitors are discharged by an internal resistor. Under certain, unusual
fault conditions, it is possible that the capacitors may fail to discharge, or be prevented
from being discharged by a voltage applied to the output terminals. If the drive has failed
in a manner that causes the display to go blank immediately, it is possible the capacitors
will not be discharged. In this case, consult Nidec Industrial Automation or their authorized
distributor.
Enclosure
The drive is intended to be mounted in an enclosure which prevents access except by
trained and authorized personnel, and which prevents the ingress of contamination. It is
WARNING designed for use in an environment classified as pollution degree 2 in accordance with IEC
60664-1. This means that only dry, non-conducting contamination is acceptable.
Safety information
3.2.1 Access
Access must be restricted to authorized personnel only. Safety regulations which apply at the place
of use must be complied with.
The IP (Ingress Protection) rating of the drive is installation dependent. For further information, refer
to section 3.8 Enclosing standard drive for high environmental protection on page 39.
3.2.2 Environmental protection
The drive must be protected from:
Product information
• Moisture, including dripping water or spraying water and condensation. An anti-condensation
heater may be required, which must be switched off when the drive is running.
• Contamination with electrically conductive material
• Contamination with any form of dust which may restrict the fan, or impair airflow over various
components
• Temperature beyond the specified operating and storage ranges
• Corrosive gasses
Mechanical installation
NOTE During installation it is recommended that the vents on the drive are covered to prevent
debris (e.g. wire off-cuts) from entering the drive.
3.2.3 Cooling
The heat produced by the drive must be removed without its specified operating temperature being
exceeded. Note that a sealed enclosure gives much reduced cooling compared with a ventilated one,
and may need to be larger and/or use internal air circulating fans.
For further information, refer to section 3.5 Enclosure for standard drives on page 32.
Electrical installation
3.2.4 Electrical safety
The installation must be safe under normal and fault conditions. Electrical installation instructions are
given in Chapter 4 Electrical installation on page 54.
3.2.5 Fire protection
The drive enclosure is not classified as a fire enclosure. A separate fire enclosure must be provided.
For installation in the USA, a NEMA 12 enclosure is suitable.
For installation outside the USA, the following (based on IEC 62109-1, standard for PV inverters) is
recommended. Technical data
Enclosure can be metal and/or polymeric, polymer must meet requirements which can be
summarized for larger enclosures as using materials meeting at least UL 94 class 5VB at the point of
minimum thickness.
Air filter assemblies to be at least class V-2.
The location and size of the bottom shall cover the area shown in Figure 3-1. Any part of the side
which is within the area traced out by the 5° angle is also considered to be part of the bottom of the
fire enclosure.
UL listing information
Drive
o
5
o
5
The bottom, including the part of the side considered to be part of the bottom, must be designed to
prevent escape of burning material - either by having no openings or by having a baffle construction.
This means that openings for cables etc. must be sealed with materials meeting the 5VB
requirement, or else have a baffle above. See Figure 3-2 for acceptable baffle construction. This
does not apply for mounting in an enclosed electrical operating area (restricted access) with concrete
floor.
Figure 3-2 Fire enclosure baffle construction
Not less
than 2
times ‘X’
N o t le s s
th a n 2 X
Baffle plates (may be above or
B a f f le p la t e s ( m a y b e
X
X
B o t t o m o f f ir e
Safety information
Isolation device
The AC and / or DC power supply must be disconnected from the drive using an approved
isolation device before any cover is removed from the drive or before any servicing work
WARNING is performed.
Stored charge
The drive contains capacitors that remain charged to a potentially lethal voltage after the
AC and / or DC power supply has been disconnected. If the drive has been energized,
Product information
WARNING the power supply must be isolated at least ten minutes before work may continue.
Normally, the capacitors are discharged by an internal resistor. Under certain, unusual
fault conditions, it is possible that the capacitors may fail to discharge, or be prevented
from being discharged by a voltage applied to the output terminals. If the drive has failed
in a manner that causes the display to go blank immediately, it is possible the capacitors
will not be discharged. In this case, consult Nidec Industrial Automation or their authorized
distributor.
Mechanical installation
3.3.1 Removing the terminal covers
Figure 3-3 Location and identification of terminal covers
AC
terminal cover
Electrical installation
AC / DC
terminal cover
AC / DC
terminal cover
Technical data
7 8 9A 9E 10E
UL listing information
When replacing the terminal covers, the screws should be tightened to a maximum torque of 1 N m
(0.7 lb ft).
3.3.2 Removing the finger-guard and DC terminal cover break-outs
Figure 3-5 Removing the finger-guard break-outs
All sizes:
Place the finger-guard on a flat solid surface and hit relevant break-outs with hammer as shown (1).
Pliers can be used to remove the breakouts, grasp the relevant break-out with pliers and twist it as
shown (3). Continue until all the required break-outs have been removed (2). Remove any flash /
sharp edges once the break-outs have been removed.
Grommet kits are available for size 7 to 10 finger guards. For size 8 to 10, two versions are available
allowing for either single or double cable entries.
Product information
Drive size Part number Picture
Mechanical installation
Size 8 - Kit of 8 x single entry grommets 3470-0089
Electrical installation
Size 9 and 10 - Kit of 8 x double entry
3470-0107
grommets
If the drive has been used at high load levels for a period of time, the heatsink can reach
Technical data
temperatures in excess of 70 °C (158 °F). Human contact with the heatsink should be
prevented.
WARNING
Many of the drives in this product range weigh in excess of 15 kg (33 lb). Use appropriate
safeguards when lifting these models.
A full list of drive weights can be found in Table 5-14 Overall drive weights on page 106.
UL listing information
WARNING
W
D
H2 H1
H1 H2 W D
Size
mm in mm in mm in mm in
7 557 21.93 508 20 270 10.63 280 11.02
8 804 31.65 753 29.65 310 12.21 290 11.42
9E and 10E 1069 42.09 1010 39.70 310 12.21 290 11.42
9A 1108 43.61 1049 41.30 310 12.21 290 11.42
Safety information
25 mm
(0.98 in) 220 mm (8.66 in) 259 mm (10.20 in)
10 mm
(0.39 in) 9.5 mm
538 mm (21.18) (0.37 in)
Product information
7
8 8
Mechanical installation
Æ 9mm (0.35 in)
Electrical installation
1051 mm (41.38 in)
9E / 10E
1090 mm (42.91 in)
9A
Technical data
UL listing information
166 mm
(5.75 in)
146 mm 8
Æ9 mm (0.35 in)
x 6 holes
32 mm
(1.26 in)
327 mm (12.87 in) 328 mm (12.90 in)
287±1 mm (11.3±0.04 in) Æ9 mm (0.35 in)
287±1 mm (11.3±0.04 in)
x 4 holes
Æ9.0 mm (0.35 in) 259 mm (10.20 in) 259 mm (10.18 in)
x 4 holes
31 mm
(1.22 in) 9E/10E
9A
32 mm
(1.24 in)
Safety information
Surface mounting kit Optional through-panel
Frame size Qty Qty
(supplied with drive) mounting kit
x2
7 x 2* Hole size: 9 mm (0.35 in)
Product information
x6
8 x 2* Hole size: 5.5 mm (0.22 in)
Mechanical installation
x8
9A / 9E and
x 2* Hole size: 5.5 mm (0.22 in)
10E
Hole size: 9 mm (0.35 in) x1
Electrical installation
The through panel mounting kit is not supplied with the drive and can be purchased separately, below
are the relevant part numbers:
Size CT part number
7 3470-0079
8 3470-0083
9A 3470-0119
9E/10E 3470-0105
Technical data
If the drive has been used at high load levels for a period of time, the heatsink can reach
temperatures in excess of 70 °C (158 °F). Human contact with the heatsink should be
prevented.
WARNING
UL listing information
Enclosure
* 50°C derating applies, refer to Table 5-6 Maximum permissible continuous output current @ 50 °C
(122 °F) on page 96.
When through-panel mounted, ideally drives should be spaced at least 45 mm (1.77 in) to
NOTE
maximize panel stiffness
Safety information
other devices / auxiliary equipment when planning the installation.
Locate
Locateasas
required
required
AC supply
contactor and
fuses or MCB
Product information
³ 100 mm
(4 in)
Mechanical installation
B B
Note
For EMC compliance:
1) When using an external EMC
filter, one filter is required for
each drive
2) Power cabling must be at
least 100mm (4in) from the
drive in all directions
7 8
Electrical installation
A = 60mm (2.37 in)
Signal cables
Plan for all signal cables
to be routed at least
300 mm (12 in) from the
drive and any power cable
Technical data
External
Locate optional braking controller
resistor external to
cubicle (preferably near
to or on top of the cubicle). ³ 100 mm
Locate the overload (4 in)
protection device as required
Optional braking
resistor and overload
UL listing information
Locate
Locateasas
required
required
Enclosure AC supply
contactor and
fuses or MCB
³100mm
(4in)
A = 60 mm (2.37 in)
B = 45 mm (1.77 in)
B B
Note
For EMC compliance:
9 10 1) When using an external EMC
filter, one filter is required for
each drive
2) Power cabling must be at
least 100mm (4in) from the
drive in all directions
Signal cables
Plan for all signal cables
to be routed at least
300 mm (12 in) from the
drive and any power cable
Locate optional braking
resistor external to
cubicle (preferably near
to or on top of the cubicle).
³100mm
Locate the overload
(4in)
protection device as required External
controller
Optional braking
resistor and overload
Safety information
to be installed in the enclosure.
2. If an external EMC filter is to be used with each drive, add the dissipation figures from section
3.9.2 EMC filter ratings on page 44 for each external EMC filter that is to be installed in the
enclosure.
3. If the braking resistor is to be mounted inside the enclosure, add the average power figures from
for each braking resistor that is to be installed in the enclosure.
4. Calculate the total heat dissipation (in Watts) of any other equipment to be installed in the
enclosure.
5. Add the heat dissipation figures obtained above. This gives a figure in Watts for the total heat that
Product information
will be dissipated inside the enclosure.
Calculating the size of a sealed enclosure
The enclosure transfers internally generated heat into the surrounding air by natural convection (or
external forced air flow); the greater the surface area of the enclosure walls, the better is the
dissipation capability. Only the surfaces of the enclosure that are unobstructed (not in contact with a
wall or floor) can dissipate heat.
Calculate the minimum required unobstructed surface area Ae for the enclosure from:
Mechanical installation
P
A e = -----------------------------------
k Tint – T ext
Where:
Ae Unobstructed surface area in m2 (1 m2 = 10.9 ft2)
T
ext Maximum expected temperature in oC outside the enclosure
Tint Maximum permissible temperature in oC inside the enclosure
P Power in Watts dissipated by all heat sources in the enclosure
Electrical installation
k Heat transmission coefficient of the enclosure material in W/m2/oC
Example
To calculate the size of an enclosure for the following:
• Two drives operating at the Normal Duty rating
• External EMC filter for each drive
• Braking resistors are to be mounted outside the enclosure
• Maximum ambient temperature inside the enclosure: 40 C
• Maximum ambient temperature outside the enclosure: 30 C Technical data
For example, if the power dissipation from each drive is 187 W and the power dissipation from each
external EMC filter is 9.2 W.
Total dissipation: 2 x (187 + 9.2) =392.4 W
NOTE Power dissipation for the drives and the external EMC filters can be obtained from
Chapter 5 Technical data on page 92.
The enclosure is to be made from painted 2 mm (0.079 in) sheet steel having a heat
UL listing information
transmission coefficient of 5.5 W/m2/oC. Only the top, front, and two sides of the
enclosure are free to dissipate heat.
The value of 5.5 W/m2/ºC can generally be used with a sheet steel enclosure (exact
values can be obtained by the supplier of the material). If in any doubt, allow for a greater
margin in the temperature rise.
D
W
Safety information
Text Maximum expected temperature in C outside the enclosure
Tint Maximum permissible temperature in C inside the enclosure
P Power in Watts dissipated by all heat sources in the enclosure
Po
k Ratio of -------
Pl
Where:
P0 is the air pressure at sea level
Product information
PI is the air pressure at the installation
Typically use a factor of 1.2 to 1.3, to allow also for pressure-drops in dirty air-filters.
Example
To calculate the size of an enclosure for the following:
• Three drives operating at the Normal Duty rating
• External EMC filter for each drive
• Braking resistors are to be mounted outside the enclosure
Mechanical installation
• Maximum ambient temperature inside the enclosure: 40 C
• Maximum ambient temperature outside the enclosure: 30 C
For example, dissipation of each drive: 101 W and dissipation of each external EMC filter: 6.9 W
(max).
Total dissipation: 3 x (101 + 6.9) = 323.7 W
Insert the following values:
Tint 40 C
Text 30 C
Electrical installation
k 1.3
P 323.7 W
Then:
3 1.3 323.7
V = ---------------------------------------
40 – 30
Safety information
page 102.
The standard drive is rated to IP20 pollution degree 2 (dry, non-conductive contamination only)
(NEMA 1). However, it is possible to configure the drive to achieve IP65 rating (size 7 and 8) or IP55
(size 9 and 10) (NEMA 12) at the rear of the heatsink for through-panel mounting.
This allows the front of the drive, along with various switchgear, to be housed in a high IP enclosure
with the heatsink protruding through the panel to the external environment. Thus, the majority of the
heat generated by the drive is dissipated outside the enclosure maintaining a reduced temperature
inside the enclosure. This also relies on a good seal being made between the heatsink and the rear
Product information
of the enclosure using the gasket and securing brackets provided.
The main gasket should be installed as shown in Figure 3-13.
Figure 3-13 Installing the gasket
Enclosure
rear wall
Mechanical installation
Drive Gasket
Electrical installation
Technical data
UL listing information
1 2
3 4
1) Remove screw shown using T20 torque driver
2) Bend EMC bracket 90 degrees as shown
3) Fit sealing gasket and place drive in panel cutout
4) Ensure EMC bracket is trapped under lower mounting bracket when fitting brackets
Safety information
IP55 (NEMA 12)
or IP65 enclosure
IP20
(NEMA1)
Product information
Mechanical installation
The Gasket seal provides
an IP65 (size 7 and 8) or
IP55 (size 9 and 10)
rated barrier to maintain
Electrical installation
enclosure rating after
drive is fitted.
The main gasket should be installed as shown in Figure 3-13. Any screws / bolts that are used for
mounting should be installed with M8 flat nylon washers to maintain a seal around the screw hole.
See Figure 3-16 on page 42, sealing clamps are supplied in the through panel mounting kit to aid
compression of the gasket.
NOTE The heatsink fans have conformal coated PCBs and have sealant at cable entry points.
Dripping, splashing or sprayed water can impede the operation of the fan, therefore if the Technical data
environment is such that the fan may be subjected to more than occasional dripping or
sprayed water while operational, then suitable drip protection covers should be employed.
UL listing information
Sealing
brackets
NOTE For detailed information regarding high IP through panel mounting see section
3.4.3 Through-panel mounting on page 30.
NOTE When designing a high IP enclosure, consideration should be given to the dissipation from
the front of the drive.
Table 3-4 Power losses from the front of the drive when through-panel mounted
Frame size Power loss
7 204 W
8 347 W
9A/9E/10E 480 W
Safety information
below.
Figure 3-17 Size 7 to 10 mounting of the EMC filter
Product information
Mechanical installation
3.9.1 Optional external EMC filters
Table 3-5 EMC filter cross reference
Electrical installation
09201760 to 09202190 (9E) 4200-4460
10202830 to 10203000 4200-4460
400 V
07400660 to 07401000 4200-1132
08401340 to 08401570 4200-1972
09402000 to 09402240 (9A) 4200-3021
09402000 to 09402240 (9E) 4200-4460
10402700 to 10403200 4200-4460 Technical data
575 V
07500440 to 07500550 4200-0672
08500630 to 08500860 4200-1662
09501040 to 09501310 (9A) 4200-1660
09501040 to 09501310 (9E) 4200-2210
10501520 to 10501900 4200-2210
690 V
UL listing information
Safety information
V
Product information
A
H
B
Z V Load Line
Mechanical installation
W C
L1 L2 L3 L1 L2 L3
Electrical installation
4200-1132 240 mm 255 mm 55 mm 150 mm 205 mm 270 mm 90 mm 6.5 mm
M10
4200-0672 (9.45 in) (10.04 in) (2.17 in) (5.90 in) (8.07 in) (10.63 in) (3.54 in) (0.26 in)
Technical data
UL listing information
Safety information
Product information
Mechanical installation
V: Ground stud - M10
Z: O 11 mm
Electrical installation
4200-4460 280 mm 180 mm 57 mm 245 mm 225 mm 40 mm 105 mm 360 mm 11 mm
4200-2210 (11.02) (7.09) (2.24 mm) (9.65 in) (8.86 in) (1.57 in) (4.13 in) (14.7 in) (0.43 in)
4200-2210 11 mm
Safety information
with the drive should be prevented.
Regular checks of the following should be carried out to ensure drive / installation reliability are
maximized:
Environment
Ambient temperature Ensure the enclosure temperature remains at or below maximum specified
Ensure the drive remains dust free – check that the heatsink and drive fan
Dust are not gathering dust. The lifetime of the fan is reduced in dusty
Product information
environments.
Moisture Ensure the drive enclosure shows no signs of condensation
Enclosure
Enclosure door filters Ensure filters are not blocked and that air is free to flow
Electrical
Screw connections Ensure all screw terminals remain tight
Ensure all crimp terminals remains tight – check for any discoloration which
Mechanical installation
Crimp terminals
could indicate overheating
Cables Check all cables for signs of damage
Electrical installation
Technical data
UL listing information
2 5
Safety information
Product information
5
Mechanical installation
3
Electrical installation
3) Disconnect fan cables from drive (making a note of the order) and push grommet down prior to
attempting fan removal
4) Remove the mounting screws using a T20 torque driver
5) Withdraw fan housing from the drive
After fan(s) have been replaced, reverse the above steps to refit.
Size 8 3251-8240
UL listing information
Safety information
2
Product information
3
Mechanical installation
Auxiliary fan removal procedure
1) Disconnect fan wiring connector shown
2) Slide fan housing in the direction shown using tongue shown in enlarged diagram of fan
Electrical installation
3) Withdraw fan housing from the drive
After fan has been replaced, reverse the above steps to refit.
Isolation device
The AC and / or DC power supply must be disconnected from the drive using an approved
isolation device before any cover is removed from the drive or before any servicing work
WARNING is performed.
STOP function
The STOP function does not remove dangerous voltages from the drive, the motor or any
WARNING
external option units.
Stored charge
The drive contains capacitors that remain charged to a potentially lethal voltage after the
AC and / or DC power supply has been disconnected. If the drive has been energized,
WARNING the AC and / or DC power supply must be isolated at least ten minutes before work may
continue. Normally, the capacitors are discharged by an internal resistor. Under certain,
unusual fault conditions, it is possible that the capacitors may fail to discharge, or be
prevented from being discharged by a voltage applied to the output terminals. If the drive
has failed in a manner that causes the display to go blank immediately, it is possible the
capacitors will not be discharged. In this case, consult Nidec Industrial Automation or
their authorized distributor.
Safety information
Input connections
Supply Mains
ground Supply
L1 L2 L3
Fuses
Product information
Optional
line reactor
Optional
EMC filter
L1 L2 L3
PE +DC -DC
Mechanical installation
Electrical installation
8
+DC BR
Thermal
Optional
overload
braking
UL listing information
protection
resistor
device
Motor
Optional ground
connection
On size 7 and 8, the supply and motor ground connections are made using the M8 studs located by
the supply and motor connection terminals. Refer to Figure 4-1.
Fuses
Optional
EMC filter
L1 L2 L3
PE +DC -DC
Internal EMC
filter
9A
Output connections
U V W
*
+DC BR
Thermal
overload
protection
device
Motor
Optional ground
connection
On size 9A, the supply and motor ground connections are made using the M10 studs located by the
supply and motor connection terminals. Refer to Figure 4-2.
Safety information
Supply Mains
ground Supply
L1 L2 L3
Fuses
Line reactor
Product information
Optional
EMC filter
L1 L2 L3
PE
Mechanical installation
9E/10E
Electrical installation
Output connections
U V W
Technical data
+DC BR
Thermal
overload
protection
device
UL listing information
Motor
Optional ground
connection
A separate line reactor (INLXXX) must be used for size 9E and 10E. Failure to provide
sufficient reactance could damage or reduce the service life of the drive. Refer to
CAUTION
Table 4-4 Size 7 to 10 Model and Line reactor part number on page 61.
The drive must be connected to the system ground of the AC supply. The ground wiring must
conform to local regulations and codes of practice.
On size 9E and 10E, the supply and motor ground connections are made using the M10 studs
located by the supply and motor connection terminals. Refer to Figure 4-3.
The ground loop impedance must conform to the requirements of local safety regulations.
The drive must be grounded by a connection capable of carrying the prospective fault
current until the protective device (fuse, etc.) disconnects the AC supply.
WARNING
The ground connections must be inspected and tested at appropriate intervals.
Safety information
Supplies with voltage up to 600 V may have grounding at any potential, i.e. neutral, centre or corner
(“grounded delta”) Supplies with voltage above 600 V may not have corner grounding
If an SI-Applications Plus module is installed in the drive, then the drive must not be used
on a corner-grounded or centre-grounded delta supply if the supply voltage is above 300
V. If this is required, please contact the supplier of the drive for more information.
WARNING
Drives are suitable for use on supplies of installation category III and lower, according to IEC 60664-1.
Product information
This means they may be connected permanently to the supply at its origin in a building, but for outdoor
installation additional over-voltage suppression (transient voltage surge suppression) must be
provided to reduce category IV to category III.
Mechanical installation
to Table 4-3 . For details of ground fault protection contact the supplier of the drive.
A ground fault in the supply has no effect in any case. If the motor must continue to run with a ground
fault in its own circuit then an input isolating transformer must be provided and if an EMC filter is
required it must be located in the primary circuit.
Unusual hazards can occur on ungrounded supplies with more than one source, for example on ships. Contact
the supplier of the drive for more information.
Table 4-3 Behavior of the drive in the event of a ground (earth) fault with an IT supply
Electrical installation
Drive size Internal filter only External filter (with internal)
May not trip – precautions required: May not trip – precautions required:
(All sizes) • Remove the EMC filter* • Do not use EMC filter
• Use ground leakage relay • Use ground leakage relay
* Please note that the internal filter is not removable on size 9E and 10E.
Technical data
UL listing information
A separate line reactor (INLXXX) of at least the value shown in Table 4-4 and Table 4-5
must be used with size 9E and 10E. Failure to provide sufficient reactance could damage
or reduce the service life of the drive.
CAUTION
Safety information
Size Drive model Inductor model
number
07200610 INL 2009 4401-0227
07200750 INL 2010 4401-0228
07200830 INL 2011 4401-0229
07400660 INL 4014 4401-0237
07400770 INL 4015 4401-0238
07401000 INL 4016 4401-0239
Product information
07500440 INL 5006 4401-0223
7
07500550 INL 5010 4401-0245
07600190 INL 6001 4401-0248
07600240 INL 6002 4401-0249
07600290 INL 6003 4401-0250
07600380 INL 6004 4401-0251
07600440 INL 6005 4401-0252
Mechanical installation
07600540 INL 6006 4401-0253
08201160 INL 2012 4401-0230
08201320 INL 2013 4401-0231
08401340 INL 4017 4401-0240
08401570 INL 4018 4401-0241
8
08500630 INL 5011 4401-0246
08500860 INL 5012 4401-0247
Electrical installation
08600630 INL 6007 4401-0254
08600860 INL 6008 4401-0255
09201760, 09202190, 09402000, 09402240 INL 401 4401-0181
9
09501040, 09501310, 09601040, 09601310 INL 601 4401-0183
10202830, 10203000, 10402700, 10403200 INL 402 4401-0182
10
10501520, 10501900, 10601500, 10601780 INL 602 4401-0184
D
W
UL listing information
Safety information
The drive may be supplied with DC instead of 3 phase AC.
The connecting of the DC bus between several drives is typically used to:
1. Return energy from a drive which is being overhauled by the load to a second motoring drive.
2. Allow the use of one braking resistor to dissipate regenerative energy from several drives.
There are limitations to the combinations of drives which can be used in this configuration.
For further information, contact the supplier of the drive.
Product information
NOTE Unidrive M/Unidrive HS size 9E and 10E drives do not have an accessible negative DC
terminal. It is recommended that 9D and 10D drives are used as an alternative when this
is needed, please refer to the Modular Installation Guide for further details.
Mechanical installation
are being used and the current drawn by these module is greater than the drive can supply.
• It can be used as a back-up power supply to keep the control circuits of the drive powered up
when the line power supply is removed. This allows any fieldbus modules, application modules,
encoders or serial communications to continue to operate.
• It can be used to commission the drive when the line power supply is not available, as the display
operates correctly. However, the drive will be in the Under voltage state unless either line power
supply or low voltage DC operation is enabled, therefore diagnostics may not be possible.
(Power down save parameters are not saved when using the 24 V back-up power supply input).
Electrical installation
• If the DC bus voltage is too low to run the main SMPS in the drive, then the 24 V supply can be
used to supply all the low voltage power requirements of the drive. Low Under Voltage Threshold
Select (06.067)** must also be enabled for this to happen.
** Not available on Unidrive M200 to M400.
NOTE The power 24 Vdc supply (terminals 51, 52) must be connected to enable the 24 V dc
supply to be used as a backup supply, when the line power supply is removed. If the power
24 Vdc supply is not connected none of the above mentioned functions can be used,
"Waiting For Power System" will be displayed on the keypad and no drive operations are Technical data
possible. The location of the power 24 Vdc can be identified from Figure 4-5 and Figure
4-6 Location of the 24 Vdc power supply connection on size 8 to 10 on page 65.
Terminal
Back-up supply for the control circuit 1, 2*
51, 52
* Terminal 9 on Unidrive M702 and HS72 (24 Vdc control supply on Unidrive M200 to M400 is
supplied via AI-Backup Adaptor)
51 52
Safety information
Product information
51 52
Mechanical installation
4.5 Low voltage operation
With the addition of a 24 Vdc power supply to supply the control circuits, the drive is able to operate
from a low voltage DC supply with a range from 24 Vdc to the maximum DC volts. It is possible for
the drive to go from operating on a normal line power supply voltage to operating on a much lower
supply voltage without interruption (not available with Unidrive M200 to M400).
Going from low voltage operation to normal mains operation requires the inrush current to be
Electrical installation
controlled. This may be provided externally. If not, the drive supply can be interrupted to utilise the
normal soft starting method in the drive.
To fully exploit the new low voltage mode of operation, the under voltage level is now user
programmable. For application data, contact the supplier of the drive.
The working voltage range of the low voltage DC power supply is as follows:
Size 9 to 10
Minimum continuous operating voltage: 26 V
Minimum start up voltage: 32 V Technical data
NOTE Unidrive M/Unidrive HS size 9E and 10E drives do not have an accessible negative DC
terminal. It is recommended that 9D and 10D drives are used as an alternative when this
UL listing information
is needed, please refer to the Modular Installation Guide for further details.
61 62
4.7 Ratings
See section 2.4 Ratings on page 17.
Maximum continuous input current
The values of maximum continuous input current are given to aid the selection of cables and fuses.
These values are stated for the worst case condition with the unusual combination of stiff supply with
high imbalance. The value stated for the maximum continuous input current would only be seen in
one of the input phases. The current in the other two phases would be significantly lower.
The values of maximum input current are stated for a supply with a 2 % negative phase-sequence
imbalance and rated at the maximum supply fault current given in section 2.4 Ratings on page 17.
The nominal cable sizes given in section 2.4 Ratings on page 17 are only a guide. Refer to local
wiring regulations for the correct size of cables. In some cases a larger cable is required to avoid
excessive voltage drop.
Safety information
cable rating may be chosen to match that of the motor. To ensure that the motor and cable
are protected against over-load, the drive must be programmed with the correct motor
rated current.
Fuses
The AC supply to the drive must be installed with suitable protection against overload and
short-circuits. Nominal fuse ratings are shown in section 2.4 Ratings on page 17. Failure
WARNING to observe this requirement will cause risk of fire.
Product information
A fuse or other protection must be included in all live connections to the AC supply.
Fuse types
The fuse voltage rating must be suitable for the drive supply voltage.
Mechanical installation
The output circuit has fast-acting electronic short-circuit protection which limits the fault current to
typically no more than five times the rated output current, and interrupts the current in approximately
20 µs. No additional short-circuit protection devices are required.
The drive provides overload protection for the motor and its cable. For this to be effective, Pr 00.046
(Pr 00.006 on Unidrive M200 to M400) Motor rated current must be set to suit the motor.
Electrical installation
Pr 00.046 (Pr 00.006 on Unidrive M200 to M400) Motor rated current must be set correctly
to avoid a risk of fire in the event of motor overload.
WARNING
There is also provision for the use of a motor thermistor to prevent over-heating of the motor, e.g. due
to loss of cooling.
4.8.1 Motor cable types
Since capacitance in the motor cable causes loading on the output of the drive, ensure the cable
length does not exceed the values given in Table 5-23 Maximum motor cable lengths on page 111.
Use 105 °C (221 °F) (UL 60/75 °C temp rise) PVC-insulated cable with copper conductors having a
Technical data
The maximum motor cable lengths specified in section 5.1.21 Maximum motor cable lengths on
page 111 is shielded and contains four cores. Typical capacitance for this type of cable is 130 pF/m
(i.e. from one core to all others and the shield connected together).
Safety information
If the drive is to control more than one motor, one of the fixed V/F modes should be selected
(Pr 05.014 = Fixed or Squared). Make the motor connections as shown in Figure 4-9 and Figure 4-
10. The maximum motor cable lengths specified in section 5.1.21 Maximum motor cable lengths on
page 111 apply to the sum of the total cable lengths from the drive to each motor.
It is recommended that each motor is connected through a protection relay since the drive cannot
protect each motor individually. For connection, a sinusoidal filter or an output inductor must be
connected as shown in Figure 4-10, even when the cable lengths are less than the maximum
permissible. For high DC voltages or when supplied by a regen system, a sinusoidal filter is
Product information
recommended. For details of filter or inductor sizes refer to the supplier of the drive.
Figure 4-9 Preferred chain connection for multiple motors
Motor protection
relay
Mechanical installation
9E/10E
Electrical installation
Figure 4-10 Alternative connection for multiple motors
Motor
9E/10E
protection
relay
Technical data
Star connection
Inductor
UL listing information
A contactor is sometimes required to be installed between the drive and motor for safety purposes.
The recommended motor contactor is the AC3 type.
Switching of an output contactor should only occur when the output of the drive is disabled.
Opening or closing of the contactor with the drive enabled will lead to:
1. OI ac trips (which cannot be reset for 10 seconds)
2. High levels of radio frequency noise emission
3. Increased contactor wear and tear
The Drive Enable terminal when opened provides a Safe Torque Off* function. This can in many
cases replace output contactors.
For further information see the Control User Guide.
*There is no Safe Torque Off function on the Unidrive M200/201
4.9 Braking
Braking occurs when the drive is decelerating the motor, or is preventing the motor from gaining
speed due to mechanical influences. During braking, energy is returned to the drive from the motor.
When the motor is being braked by the drive, the maximum regenerated power that the drive can
absorb is equal to the power dissipation (losses) of the drive.
When the regenerated power is likely to exceed these losses, the DC bus voltage of the drive
increases. Under default conditions, the drive brakes the motor under PI control, which extends the
deceleration time as necessary in order to prevent the DC bus voltage from rising above a user
defined set-point.
If the drive is expected to rapidly decelerate a load, or to hold back an overhauling load, a braking
resistor must be installed.
Table 4-7 shows the default DC voltage level at which the drive turns on the braking transistor.
However the braking resistor turn on and the turn off voltages are programmable with Braking IGBT
Lower Threshold (06.073) and Braking IGBT Upper Threshold (06.074).
Safety information
200 V 390 V
400 V 780 V
575 V 930 V
690 V 1120 V
NOTE When a braking resistor is used, Pr 00.015 (Pr 00.028 on Unidrive M200 to M400) should
be set to FASt ramp mode.
Product information
4.9.1 External braking resistor
Overload protection
When an external braking resistor is used, it is essential that an overload protection device
is incorporated in the braking resistor circuit; this is described in Figure 4-11 on page 73.
WARNING
When a braking resistor is to be mounted outside the enclosure, ensure that it is mounted in a
Mechanical installation
ventilated metal housing that will perform the following functions:
• Prevent inadvertent contact with the resistor
• Allow adequate ventilation for the resistor
When compliance with EMC emission standards is required, external connection requires the cable
to be armored or shielded, since it is not fully contained in a metal enclosure. See section
4.11.6 Compliance with generic emission standards on page 85 for further details.
Internal connection does not require the cable to be armored or shielded.
Table 4-8 Minimum resistance values and peak power rating for the braking resistor at 40 °C (104 °F)
Electrical installation
Minimum resistance* Instantaneous power rating Continuous power rating
Model
Ω kW kW
200 V
07200610 4.5 37.6 15
07200750 4.5 37.6 18.5
07200830 4.5 37.6 22
08201160 2.3 73.5 30
08201320 2.3 73.5 37 Technical data
09201760 (9A) 2 84.5 45
09202190 (9A) 2 84.5 45
09201760 (9E) 1.4 120.8 45
09202190 (9E) 1.4 120.8 55
10202830 1.7 99.5 75
10203000 1.7 99.5 90
400 V
07400660 7.5 90.2 30
UL listing information
Safety information
to trip during braking if the value chosen is too large.
Thermal protection circuit for the braking resistor
The thermal protection circuit must disconnect the AC supply from the drive if the resistor becomes
overloaded due to a fault. Figure 4-11 shows a typical circuit arrangement.
Figure 4-11 Typical protection circuit for a braking resistor
Optional
RFI filter
Product information
Main contactor
power supply
Drive
Stop
Start / Thermal
Reset protection
device
+DC
Mechanical installation
BR
Braking resistor
See Figure 4-1 on page 55, Figure 4-2 on page 56 and Figure 4-3 on page 57 for the location of the
+DC and braking resistor connections.
4.9.2 Braking resistor software overload protection
The drive software contains an overload protection function for a braking resistor. In order to enable
and set-up this function, it is necessary to enter three values into the drive:
Electrical installation
• Braking Resistor Rated Power (10.030)
• Braking Resistor Thermal Time Constant (10.031)
• Braking Resistor Resistance (10.061)
This data should be obtained from the manufacturer of the braking resistors. The braking resistor
thermal time constant can be calculated from resistor data sheet values using the following equation:
withstand. A ‘Brake Resistor’ alarm is given if this parameter is above 75 % and the braking IGBT is
active. A Brake R Too Hot trip will occur if Pr 10.039 reaches 100 %, when Pr 10.037 is set to 0
(default value) or 1.
If Pr 10.037 is equal to 2 or 3, a Brake R Too Hot trip will not occur when Pr 10.039 reaches 100 %,
but instead the braking IGBT will be disabled until Pr 10.039 falls below 95 %. This option is intended
for applications with parallel connected DC buses where there are several braking resistors, each of
which cannot withstand full DC bus voltage continuously. With this type of application it is unlikely the
UL listing information
braking energy will be shared equally between the resistors because of voltage measurement
tolerances within the individual drives. Therefore with Pr 10.037 set to 2 or 3, then as soon as a
resistor has reached its maximum temperature the drive will disable the braking IGBT, and another
resistor on another drive will take up the braking energy. Once Pr 10.039 has fallen below 95 % the
drive will allow the braking IGBT to operate again.
See the Parameter Reference Guide for more information on Pr 10.030, Pr 10.031, Pr 10.037 and
Pr 10.039.
When the internal filter is installed the leakage current is high. In this case a permanent
fixed ground connection must be provided, or other suitable measures taken to prevent a
safety hazard occurring if the connection is lost.
WARNING
Only type B ELCB / RCD are suitable for use with 3 phase inverter drives.
WARNING
If an external EMC filter is used with an ELCB / RCD, a delay of at least 50 ms should be
incorporated to ensure spurious trips are not seen. The leakage current is likely to exceed the trip
level if all of the phases are not energized simultaneously.
Safety information
• section 4.11.4, General requirements for EMC this is for all applications, to ensure reliable
operation of the drive and minimise the risk of disturbing nearby equipment. The immunity
standards specified in section 5.1.24 Electromagnetic compatibility (EMC) on page 114 will be
met, but no specific emission standards are applied.
• section 4.11.5, Requirements for meeting the EMC standard for power drive systems, IEC
61800-3 (EN 61800-3:2004+A1:2012).
• section 4.11.6, Requirements for meeting the generic emission standards for the industrial
environment, IEC 61000-6-4, EN 61000-6-4:2007+A1:2011.
Product information
The recommendations of section 4.11.4 will usually be sufficient to avoid causing disturbance to
adjacent equipment of industrial quality. If particularly sensitive equipment is to be used nearby, or in
a non-industrial environment, then the recommendations of section 4.11.5 or section 4.11.6 should
be followed to give reduced radio-frequency emission.
In order to ensure the installation meets the various emission standards described in:
• The EMC data sheet available from the supplier of the drive
• The Declaration of Conformity at the front of this manual
• Chapter 5 Technical data on page 92
Mechanical installation
The correct external EMC filter must be used and all of the guidelines in section 4.11.4 General
requirements for EMC on page 80 and section 4.11.6 Compliance with generic emission
standards on page 85 must be followed.
Electrical installation
Technical data
UL listing information
200 V
07200610 to 07200830 4200-1132
08201160 to 08201320 4200-1972
09201760 to 09202190 (9A) 4200-3021
09201760 to 09202190 (9E) 4200-4460
10202830 to 10203000 4200-4460
400 V
07400660 to 07401000 4200-1132
08401340 to 08401570 4200-1972
09402000 to 09402240 (9A) 4200-3021
09402000 to 09402240 (9E) 4200-4460
10402700 to 10403200 4200-4460
575 V
07500440 to 07500550 4200-0672
08500630 to 08500860 4200-1662
09501040 to 09501310 (9A) 4200-1660
09501040 to 09501310 (9E) 4200-2210
10501520 to 10501900 4200-2210
690 V
07600190 to 07600540 4200-0672
08600630 to 08600860 4200-1662
09601040 to 09601310 (9A) 4200-1660
09601040 to 09601310 (9E) 4200-2210
10601500 to 10601780 4200-2210
The installer of the drive is responsible for ensuring compliance with the EMC regulations
NOTE
that apply where the drive is to be used.
Safety information
Product information
Mechanical installation
Loosen the ground connection nuts and slide the grounding bracket in the direction shown. Once in
place, the ground connection nuts should be tightened with a maximum torque of 2 N m (1.47 lb ft).
Electrical installation
A faston tab is located on the grounding bracket for the purpose of connecting the drive 0V to ground
should the user require to do so.
When the drive is used with ungrounded (IT) supplies the internal EMC filter must be
removed unless additional motor ground fault protection is installed.
For instructions on removal, refer to Figure . Please note that the internal filter is not
Technical data
WARNING removable on size 9E and 10E. For details of ground fault protection contact the supplier
of the drive.
If the drive is part of a regen system or it is connected to an IT supply then the internal EMC filter
must be removed.
The internal EMC filter reduces radio-frequency emission into the line power supply. Where the
motor cable is short, it permits the requirements of EN 61800-3:2004 to be met for the second
environment - see section 4.11.5 and section 5.1.24. For longer motor cables the filter continues to
UL listing information
provide a useful reduction in emission level, and when used with any length of shielded motor cable
up to the limit for the drive, it is unlikely that nearby industrial equipment will be disturbed. It is
recommended that the filter be used in all applications unless the instructions given above require it
to be removed or the ground leakage current of the drive is unacceptable.
Figure 4-13 Removal of the size 7, 8 and 9A internal EMC filter and line to ground varistors (size 7
shown)
To electrically disconnect the Internal EMC filter, remove the screw as highlighted above (1).
To electrically disconnect the line to ground varistors, remove the screw as highlighted above (2).
NOTE
Safety information
ungrounded supplies with more than one source, for example on ships. Where the line to
ground varistors are removed, ensure that line to ground transients are limited to values
WARNING of category II. This is to ensure that line to ground transients do not exceed 4 kV as the
drive insulation system from power to ground is designed to category II.Contact the
supplier of the drive for more information.
Product information
Mechanical installation
1
Electrical installation
To electrically disconnect the line to ground varistors, remove the screw as highlighted above (1).
Technical data
UL listing information
Optional EMC
filter
3 phase AC supply ~
PE
Grounding bar
The incoming supply ground
should be connected to a
single power ground bus bar
or low impedance earth
terminal inside the cubicle.
This should be used as a Metal backplate
common 'clean' ground for all safety bonded to
Use four core cable to
components inside the cubicle. power ground busbar
connect the motor to the drive.
The ground conductor in the
motor cable must be connected
directly to the earth terminal of
the drive and motor.
It must not be connected directly
to the power earth busbar.
Optional
ground
connection
Safety information
power cables by all sensitive control signals / equipment.
Figure 4-16 Drive cable clearances
INL 1
Product information
Mechanical installation
Do not place sensitive
(unscreened) signal circuits
in a zone extending
300mm (12”) all around the
Drive, motor cable, input
cable from EMC filter and
unscreened braking resistor
Electrical installation
cable (if used)
300mm
(12in)
Technical data
Optional braking
resistor and overload
UL listing information
NOTE Any signal cables which are carried inside the motor cable (i.e. motor thermistor, motor
brake) will pick up large pulse currents via the cable capacitance. The shield of these
signal cables must be connected to ground close to the motor cable, to avoid this noise
current spreading through the control system.
NOTE The recommendations of the encoder manufacturer must also be adhered to for the
encoder connections.
NOTE In order to guarantee maximum noise immunity for any application double shielded cable
as shown should be used.
In some cases single shielding of each pair of differential signals cables, or a single overall shield
with individual shield on the thermistor connections is sufficient. In these cases all the shields should
be connected to ground and 0V at both ends.
If the 0V is required to be left floating a cable with individual shields and an overall shield must be
used.
Safety information
installed. The shield must not be broken or opened at this point. The clamps should be installed close
to the drive or feedback device, with the ground connections made to a ground plate or similar
metallic ground surface.
Figure 4-17 Feedback cable, twisted pair
Cable overall shield
Twisted
Product information
pair Cable
cable
Mechanical installation
Shield
connection
to 0V
Twisted
Cable pair
shield shield
Electrical installation
Ground clamp Cable
on shield
Technical data
Cable Twisted
shield pair
shield
Shield
connection
to 0V
UL listing information
Connection
at motor
To ensure suppression of radio frequency emission, observe the following:
• Use a cable with an overall shield
• Clamp the overall shield to grounded metallic surfaces at both the
encoder and the drive, as illustrated in section 4-18
The second environment typically includes an industrial low-voltage power supply network
which does not supply buildings used for residential purposes. Operating the drive in this
environment without an external EMC filter may cause interference to nearby electronic
CAUTION equipment whose sensitivity has not been appreciated. The user must take remedial
measures if this situation arises. If the consequences of unexpected disturbances are
severe, it is recommended that the guidelines in section 4.11.6 Compliance with generic
emission standards be adhered to.
Safety information
Detailed instructions and EMC information are given in the Unidrive M / Unidrive HS EMC Data
Sheet which is available from the supplier of the drive.
Product information
³100mm (4in)
Mechanical installation
³100mm
(4in)
Electrical installation
9E
Technical data
³100mm (4in)
UL listing information
³300mm
(12in)
Sensitive
signal
cable
Safety information
Ensure direct
metal contact
at drive and
Product information
filter (not shown)
mounting
points (any
paint must be
removed).
Mechanical installation
(unbroken) physically
fixed to the backplate.
Connect the shield of the motor cable to the ground terminal of the motor frame using a link that is as
short as possible and not exceeding 50 mm (2 in) long. A full 360° termination of the shield to the
terminal housing of the motor is beneficial.
It is unimportant for EMC purposes whether the motor cable contains an internal (safety) ground
core, or there is a separate external ground conductor, or grounding is through the shield alone. An
Electrical installation
internal ground core will carry a high noise current and therefore it must be terminated as close as
possible to the shield termination.
Figure 4-22 Grounding the motor cable shield
Technical data
UL listing information
Unshielded wiring to the optional braking resistor(s) may be used, provided the wiring does not run
external to the enclosure. Ensure a minimum spacing of 300 mm (12 in) from signal wiring and the
AC supply wiring to the external EMC filter. Otherwise this wiring must be shielded.
OR
+DC BR +DC BR
Optional external
braking resistor
Optional external
braking resistor
If the control wiring is to leave the enclosure, it must be shielded and the shield(s) clamped to the
drive using the grounding bracket as shown in Figure 4-24. Remove the outer insulating cover of the
cable to ensure the shield(s) make contact with the bracket, but keep the shield(s) intact until as
close as possible to the terminals
Alternatively, wiring may be passed through a ferrite ring, part no. 3225-1004.
Safety information
Product information
Mechanical installation
4.11.8 Variations in the EMC wiring
Interruptions to the motor cable
The motor cable should ideally be a single length of shielded or armored cable having no
interruptions. In some situations it may be necessary to interrupt the cable, as in the following
examples:
• Connecting the motor cable to a terminal block in the drive enclosure
• Installing a motor isolator/disconnect switch for safety when work is done on the motor
Electrical installation
In these cases the following guidelines should be followed.
Back-plate
Enclosure
To the motor
Isolator
Surge immunity of control circuits - long cables and connections outside a building
The input/output ports for the control circuits are designed for general use within machines and small
systems without any special precautions.
These circuits meet the requirements of EN 61000-6-2:2005 (1 kV surge) provided the 0V connection
is not grounded.
In applications where they may be exposed to high-energy voltage surges, some special measures
may be required to prevent malfunction or damage. Surges may be caused by lightning or severe
power faults in association with grounding arrangements which permit high transient voltages
between nominally grounded points. This is a particular risk where the circuits extend outside the
protection of a building.
As a general rule, if the circuits are to pass outside the building where the drive is located, or if cable
runs within a building exceed 30 m, some additional precautions are advisable. One of the following
techniques should be used:
1. Galvanic isolation, i.e. do not connect the control 0V terminal to ground. Avoid loops in the
control wiring, i.e. ensure every control wire is accompanied by its return (0V) wire.
2. Shielded cable with additional power ground bonding. The cable shield may be connected to
ground at both ends, but in addition the ground conductors at both ends of the cable must be
bonded together by a power ground cable (equipotential bonding cable) with cross-sectional
area of at least 10 mm2, or 10 times the area of the signal cable shield, or to suit the electrical
safety requirements of the plant. This ensures that fault or surge current passes mainly through
the ground cable and not in the signal cable shield. If the building or plant has a well-designed
common bonded network this precaution is not necessary.
3. Additional over-voltage suppression - for the analog and digital inputs and outputs, a zener diode
network or a commercially available surge suppressor may be connected in parallel with the
input circuit as shown in Figure 4-27 and Figure 4-28.
If a digital port experiences a severe surge its protective trip may operate (I/O Overload trip code 26).
For continued operation after such an event, the trip can be reset automatically by setting Pr 10.034
to 5.
Safety information
30V zener diode
e.g. 2xBZW50-15
0V 0V
Figure 4-28 Surge suppression for analog and bipolar inputs and outputs
Signal from plant Signal to drive
Product information
2 x 15V zener diode
e.g. 2xBZW50-15
0V 0V
Mechanical installation
Surge suppression devices are available as rail-mounting modules, e.g. from Phoenix Contact:
Unipolar TT-UKK5-D/24 DC
Bipolar TT-UKK5-D/24 AC
These devices are not suitable for encoder signals or fast digital data networks because the
capacitance of the diodes adversely affects the signal. Most encoders have galvanic isolation of the
signal circuit from the motor frame, in which case no precautions are required. For data networks,
follow the specific recommendations for the particular network.
Electrical installation
Technical data
UL listing information
* These ratings are for 2 kHz switching frequency. For ratings at 3 kHz switching frequency refer to
section 5.1.2 Power and current ratings (Derating for switching frequency and temperature) on
page 94.
Safety information
Normal Duty Heavy Duty
Max Max Open
Nominal Motor RFC Nominal Motor
cont Peak cont loop
Model power at power at peak power at power at
output current output peak
575 V 575 V current 575 V 575 V
current current current
A kW hp A A A A kW hp
07500440 53 45 50 58.3 44 66 88 30 40
07500550 73 55 60 80.3 55 82.5 110 37 50
08500630 86 75 75 94.6 63 94.5 126 45 60
Product information
08500860 108 90 100 118.8 86 129 172 55 75
09501040 125 110 125 137.5 104 156 182 75 100
09501310 150 110 150 165 131 196.5 229.25 90 125
10501520 200 130 200 220 152 228 266 110 150
10501900 200 150 200 220 190 285 332.5 132 200
Mechanical installation
Normal Duty Heavy Duty
Max Max Open
Nominal Motor RFC Nominal Motor
cont Peak cont loop
Model power at power at peak power at power at
output current output peak
690 V 690 V current 690 V 690 V
current current current
A kW hp A A A A kW hp
07600190 23 18.5 25 25.3 19 28.5 38 15 20
07600240 30 22 30 33 24 36 48 18.5 25
Electrical installation
07600290 36 30 40 39.6 29 43.5 58 22 30
07600380 46 37 50 50.6 38 57 76 30 40
07600440 52 45 60 57.2 44 66 88 37 50
07600540 73 55 75 80.3 54 81 108 45 60
08600630 86 75 100 94.6 63 94.5 126 55 75
08600860 108 90 125 118.8 86 129 172 75 100
09601040 125 110 150 137.5 104 156 182 90 125
09601310 155 132 175 170.5 131 196.5 229.25 110 150
10601500 172 160 200 189.2 150 225 262.5 132 175
Technical data
10601780 197 185 250 216.7 178 267 311.5 160 200
UL listing information
2 3 4 6 8 12 16 2 3 4 6 8 12 16
kW hp kW hp
kHz* kHz kHz kHz kHz kHz kHz kHz* kHz kHz kHz kHz kHz kHz
200 V
08201320 45 60 180 160.2 148.8 126 93 37 50 132 126.7 114 103 89.8 80.5
09202190 75 100 266 258 218 184 128 93 55 75 219 212 180 153 110 81
10202830 90 125 325 313 266 194 144 75 100 283 264 228 170 127
10203000 110 150 360 313 266 194 144 90 125 300 264 228 171 129
400 V
07400660 37 60 79 63 53.6 30 50 66 57 48 41 34
08401570 90 150 184 169 142 106.7 77 75 125 157 143 121 104 80.1 65
09402000 110 150 221 192 159 108 77 90 150 200 180 157 130 92 65
09402240 132 200 266 255 231 192 160 109 77 110 150 224 211 190 157 130 92 65
10402700 160 250 320 285 238 173 124 132 200 270 237 200 147 108
10403200 200 300 361 339 285 238 173 126 160 250 320 307 282 237 202 147 109
575 V
07500550 55 60 73 71.5 51.8 40.2 27.7 21.2 37 50 55 52.8 39.2 30.8 21.6 17.1
08500860 90 100 108 91.8 73.1 49.7 37.8 55 75 86 67.1 53.3 37.8 28.4
10501520 130 200 200 168 126 100 70 54 110 150 152 138 106 85 61 47
Safety information
Maximum permissible continuous Maximum permissible continuous
Nominal Nominal
Model output current (A) for the following output current (A) for the following
rating rating
switching frequencies switching frequencies
2 3 4 6 8 12 16 2 3 4 6 8 12 16
kW hp kW hp
kHz* kHz kHz kHz kHz kHz kHz kHz* kHz kHz kHz kHz kHz kHz
10501900 150 200 200 152 116 76 54 132 200 190 190 186 137 106 70 51
690 V
Product information
07600190 18.5 25 23 21.2 15 20 19 16.7
Mechanical installation
08600630 75 100 86 72.2 49.7 37.8 55 75 63 53.3 37 28.4
08600860 90 125 108 91.8 72.4 49.7 37.8 75 100 86 67.1 53.3 37 28.4
09601310 132 175 155 126 100 71 54 110 150 131 105 85 62 47
10601500 160 200 172 169 126 100 71 55 132 175 150 138 105 86 62 47
10601780 185 250 197 154 114 75 55 160 200 178 137 105 69 52
Electrical installation
* For Unidrive M200 to M400 the 0.667 and 1 kHz value is the same as the 2 kHz value.
Technical data
UL listing information
07200830 117 112 92.4 80 59.7 49.1 83 81.3 69.7 53.1 43.2
08201320 180 167 148 133 113 84 132 125 117 104 95.1 81.8 72
09202190 253 237 221 197 168 117 85 219 210 195 166 140 101 72
10202830 325 320 302 266 241 176 130 283 279 241 207 153 114
10203000 346 320 302 266 241 176 130 300 279 243 207 153 114
400 V
08401570 184 180 146 123 93.8 69 157 146 132 110 94.2 73.8 58
09402000 221 213 175 144 97 69 200 180 174 143 119 83 58
09402240 253 237 213 176 144 98 69 213 193 175 143 119 83 58
10402700 320 300 259 217 154 112 270 259 214 182 131 97
10403200 343 321 300 260 217 155 112 307 282 259 214 182 131 99
575 V
08500860 104 97.2 90.7 76.7 64.8 44.3 31.3 86 80.8 61.1 49 33.4 24.9
Safety information
Maximum permissible continuous output Maximum permissible continuous output
Model current (A) for the following current (A) for the following
switching frequencies switching frequencies
2 3 4 6 8 12 16 2 3 4 6 8 12 16
kHz* kHz kHz kHz kHz kHz kHz kHz* kHz kHz kHz kHz kHz kHz
690 V
07600190 23 19 19 14.5
Product information
07600290 36 35.8 24.8 19 29 27.7 19.4 14.5
08600860 104 97.2 90.7 76.7 64.8 44.3 31.3 86 80.8 61.1 48.2 33.5 24.9
Mechanical installation
09601040 125 114 90 62 48 104 97 77 55 42
* For Unidrive M200 to M400 the 0.667 and 1 kHz value is the same as the 2 kHz value.
Electrical installation
Technical data
UL listing information
Nominal Drive losses (W) taking into account any Nominal Drive losses (W) taking into account any
Model rating current derating for the given conditions rating current derating for the given conditions
2 3 4 6 8 12 16 2 3 4 6 8 12 16
kW hp kW hp
kHz* kHz kHz kHz kHz kHz kHz kHz* kHz kHz kHz kHz kHz kHz
200 V
07200610 18.5 25 533 570 597 650 703 885 894 15 20 433 466 488 532 575 666 715
07200750 22 30 671 718 751 815 881 890 899 18.5 25 529 570 597 650 703 710 717
07200830 30 40 851 911 951 1004 911 920 929 22 30 589 634 663 720 755 763 770
08201160 37 50 1339 1433 1536 1765 1943 1962 1982 30 40 1026 1105 1193 1343 1373 1387 1401
08201320 45 60 1638 1753 1894 1914 1985 2005 2025 37 50 1260 1269 1306 1349 1372 1386 1400
09201760 (9A) 55 75 2028 2170 2312 2596 2448 2160 2031 45 60 1580 1701 1822 2065 2022 1881 1820
09202190 (9A) 75 100 2585 2754 2822 2623 2448 2156 2034 55 75 2016 2160 2227 2107 2025 1874 1821
09201760 (9E) 55 75 1889 2031 2174 2458 2348 2112 2006 45 60 1488 1609 1730 1973 1952 1845 1801
09202190 (9E) 75 100 2375 2554 2625 2482 2348 2108 2009 55 75 1874 2017 2093 2011 1956 1839 1802
10202830 90 125 2478 2672 2867 3123 2952 2701 2554 75 100 2068 2240 2413 2561 2494 2376 2303
10203000 110 150 2802 3016 3230 3126 2957 2706 2554 90 125 2213 2394 2576 2561 2494 2389 2323
400 V
07400660 37 60 745 830 907 1062 1218 1230 1242 30 50 616 692 758 773 763 771 778
07400770 45 60 896 999 1088 1264 1241 1253 1266 37 60 723 812 802 800 811 819 827
07401000 55 75 1033 1152 1247 1218 1170 1182 1194 45 75 906 1017 968 936 907 916 925
08401340 75 100 1482 1652 1817 2154 2121 2142 2164 55 100 1224 1374 1509 1521 1510 1525 1540
08401570 90 150 1798 2004 2191 2333 2279 2302 2325 75 125 1373 1541 1670 1674 1673 1690 1707
09402000 (9A) 110 150 2431 2710 2989 3075 2992 2842 2833 90 150 2132 2136 2370 2492 2475 2501 2538
09402240 (9A) 132 200 3016 3191 3143 3063 3000 2856 2828 110 150 2424 2532 2511 2489 2474 2498 2537
09402000 (9E) 110 150 2286 2565 2844 2966 2917 2807 2815 90 150 2014 2039 2274 2418 2425 2476 2526
09402240 (9E) 132 200 2806 2998 2984 2955 2925 2821 2811 110 150 2275 2400 2403 2416 2424 2473 2525
10402700 160 250 3210 3582 3954 4148 4034 3939 3843 132 200 2604 2923 3242 3401 3391 3438 3469
10403200 200 300 3703 4121 4226 4154 4038 3947 3874 160 250 3166 3376 3393 3398 3419 3442 3485
575 V
07500440 45 50 867 1004 1139 1358 1262 1275 1287 30 40 700 817 929 1028 967 977 986
07500550 55 60 1078 1248 1375 1209 1122 1133 1145 37 50 759 886 1002 914 863 872 880
08500630 75 75 1607 1861 2180 2814 2982 3012 3042 45 60 1153 1345 1585 2136 2284 2307 2330
08500860 90 100 2050 2374 2753 2947 2963 2993 3023 55 75 1554 1813 2174 2212 2218 2240 2263
Safety information
Nominal Drive losses (W) taking into account any Nominal Drive losses (W) taking into account any
Model rating current derating for the given conditions rating current derating for the given conditions
2 3 4 6 8 12 16 2 3 4 6 8 12 16
kW hp kW hp
kHz* kHz kHz kHz kHz kHz kHz kHz* kHz kHz kHz kHz kHz kHz
09501040 (9A) 110 125 1707 1977 2247 2787 2723 2731 2859 75 100 1372 1601 1830 2288 2305 2422 2603
09501310 (9A) 110 150 2087 2410 2734 2810 2692 2697 2859 90 125 1752 2034 2316 2332 2302 2412 2607
09501040 (9E) 110 125 1595 1865 2135 2675 2644 2687 2831 75 100 1290 1519 1748 2206 2246 2387 2580
09501310 (9E) 110 150 1933 2256 2580 2696 2616 2654 2831 90 125 1630 1913 2195 2247 2244 2378 2584
Product information
10501520 130 200 2692 3137 2923 2696 2616 2654 2831 110 150 1917 2245 2324 2253 2243 2373 2583
10501900 150 200 2384 2797 3209 3072 2946 2990 3189 132 200 2213 2605 2933 2750 2713 2818 3076
690 V
07600190 18.5 25 363 428 491 617 743 793 970 15 20 303 360 413 519 625 683 790
07600240 22 30 468 551 631 791 952 962 971 18.5 25 375 446 513 644 776 784 792
Mechanical installation
07600290 30 40 560 660 754 941 1129 1140 1152 22 30 449 533 610 765 920 929 938
07600380 37 50 725 854 971 1206 1271 1284 1297 30 40 587 697 796 993 966 976 985
07600440 45 60 836 985 1117 1350 1275 1288 1301 37 50 687 817 929 1015 967 977 986
07600540 55 75 1059 1248 1375 1209 1122 1133 1145 45 60 747 888 1004 909 869 878 886
08600630 75 100 1579 1861 2180 2814 2945 2974 3004 55 75 1132 1345 1585 2136 2284 2307 2330
08600860 90 125 2015 2374 2753 2947 2935 2964 2994 75 100 1526 1813 2174 2212 2218 2240 2263
Electrical installation
09601040 (9A) 110 150 1878 2213 2548 3218 3155 3266 3465 90 125 1513 1798 2083 2653 2714 2910 3161
09601310 (9A) 132 175 2384 2797 3211 3232 3155 3267 3474 110 150 1931 2281 2631 2677 2711 2917 3174
09601040 (9E) 110 150 1730 2065 2400 3070 3058 3215 3434 90 125 1409 1694 1979 2549 2643 2872 3138
09601310 (9E) 132 175 2160 2573 2986 3083 3058 3216 3443 110 150 1769 2119 2469 2571 2639 2878 3150
10601500 160 200 2420 2882 3270 3083 3052 3192 3472 132 175 2042 2441 2604 2571 2648 2876 3128
10601780 185 250 2614 3132 3649 3667 3495 3633 3993 160 200 2305 2774 3242 3265 3237 3442 3839
Technical data
UL listing information
Drive losses (W) taking into account any Drive losses (W) taking into account any current
Model current derating for the given conditions derating for the given conditions
2 3 4 6 8 12 16 2 3 4 6 8 12 16
kHz* kHz kHz kHz kHz kHz kHz kHz* kHz kHz kHz kHz kHz kHz
200 V
07200610 538 570 597 650 703 710 717 430 466 488 532 575 581 587
07200750 678 718 751 799 750 758 765 526 570 597 650 654 661 667
07200830 848 898 898 805 751 759 766 585 634 663 705 653 660 666
08201160 1353 1433 1536 1741 1770 1788 1806 1020 1105 1193 1228 1277 1290 1303
08201320 1640 1737 1740 1759 1771 1789 1807 1110 1202 1206 1228 1278 1291 1304
09201760 (9A) 2028 2170 2312 2354 2256 2010 1910 1580 1701 1822 1943 1867 1757 1700
09202190 (9A) 2431 2405 2368 2358 2245 2015 1922 2016 2063 2029 1954 1868 1763 1701
09201760 (9E) 1889 2031 2174 2240 2172 1970 1889 1488 1609 1730 1862 1808 1728 1684
09202190 (9E) 2241 2239 2223 2243 2161 1975 1900 1874 1932 1916 1872 1810 1733 1686
10202830 2478 2625 2641 2625 2671 2490 2379 2068 2240 2375 2326 2271 2185 2141
10203000 2666 2629 2643 2629 2678 2495 2374 2213 2394 2375 2350 2275 2187 2141
400 V
07400660 744 830 907 1062 1141 1152 1164 616 692 758 751 725 732 740
07400770 895 999 1087 1163 1138 1149 1161 720 808 804 779 773 781 789
07401000 1018 1136 1200 1118 1074 1085 1096 821 922 878 838 828 836 845
08401340 1480 1652 1815 2016 1970 1990 2010 1256 1410 1392 1391 1432 1446 1461
08401570 1754 1957 2114 1998 1979 1999 2019 1393 1564 1539 1518 1531 1546 1562
09402000 (9A) 2431 2710 2872 2799 2737 2639 2652 2132 2136 2290 2289 2305 2342 2399
09402240 (9A) 2837 2926 2870 2814 2737 2660 2665 2286 2294 2300 2294 2300 2340 2404
09402000 (9E) 2286 2565 2738 2709 2675 2611 2638 2014 2039 2200 2228 2262 2322 2389
09402240 (9E) 2648 2760 2735 2723 2675 2632 2651 2152 2184 2209 2233 2258 2320 2394
10402700 3210 3582 3681 3765 3700 3597 3591 2604 2923 3105 3081 3125 3165 3262
10403200 3482 3598 3676 3776 3694 3625 3589 3018 3062 3105 3087 3131 3168 3300
575 V
07500440 936 988 1115 1225 1144 1155 1167 705 817 923 923 898 907 916
07500550 1161 1225 1228 1098 1030 1040 1051 797 923 914 828 809 817 825
08500630 1753 1850 2172 2540 2672 2699 2726 1161 1345 1585 2292 2242 2264 2287
08500860 1980 2090 2291 2540 2684 2711 2738 1593 1845 2029 2039 2047 2067 2088
09501040 (9A) 1707 1977 2247 2538 2456 2495 2699 1372 1601 1830 2139 2122 2258 2455
09501310 (9A) 2087 2410 2734 2544 2456 2482 2676 1752 2034 2222 2143 2128 2258 2453
Safety information
Drive losses (W) taking into account any Drive losses (W) taking into account any current
Model current derating for the given conditions derating for the given conditions
2 3 4 6 8 12 16 2 3 4 6 8 12 16
kHz* kHz kHz kHz kHz kHz kHz kHz* kHz kHz kHz kHz kHz kHz
09501040 (9E) 1595 1865 2135 2443 2392 2460 2674 1290 1519 1748 2067 2072 2229 2436
09501310 (9E) 1933 2256 2580 2448 2392 2447 2652 1630 1913 2109 2071 2078 2229 2434
10501520 2692 2841 2654 2448 2392 2447 2652 1917 2220 2112 2077 2083 2222 2452
Product information
10501900 2384 2797 3141 2743 2672 2766 3036 2213 2605 2686 2516 2496 2651 2933
690 V
07600190 359 428 491 617 743 750 758 301 360 413 519 625 631 638
07600240 463 551 631 791 958 968 977 373 446 513 644 776 784 792
07600290 554 660 754 944 1144 1155 1167 446 533 610 765 809 817 825
07600380 717 854 965 1206 1144 1155 1167 583 697 796 926 885 894 903
Mechanical installation
07600440 814 969 1094 1225 1144 1155 1167 683 817 923 933 885 894 903
07600540 1029 1225 1228 1098 1030 1040 1051 758 906 908 837 797 805 813
08600630 1553 1850 2172 2540 2672 2699 2726 1125 1345 1585 2292 2229 2251 2274
08600860 1755 2090 2291 2540 2684 2711 2738 1543 1845 2029 2039 2014 2034 2054
09601040 (9A) 1878 2213 2548 2933 2882 2974 3248 1513 1798 2083 2483 2502 2721 2994
09601310 (9A) 2384 2797 3175 2918 2855 2974 3249 1931 2281 2548 2488 2509 2718 2991
Electrical installation
09601040 (9E) 1730 2065 2400 2810 2803 2934 3223 1409 1694 1979 2392 2443 2690 2974
09601310 (9E) 2160 2573 2955 2796 2778 2934 3225 1769 2119 2395 2397 2450 2687 2972
10601500 2420 2882 2947 2805 2789 2932 3229 2042 2441 2403 2377 2467 2701 2974
10601780 2614 3132 3610 3243 3221 3420 3771 2305 2774 3111 3007 2996 3253 3621
* For Unidrive M200 to M400 the 0.667 and 1 kHz value is the same as the 2 kHz value.
Table 5-9 Power losses from the front of the drive when through-panel mounted
Technical data
Frame size Power loss
7 204 W
8 347 W
9 480 W
10 480 W
Safety information
First digit Second digit
Protection against foreign bodies and access to
Protection against ingress of water
hazardous parts
0 Non-protected 0 Non-protected
Protected against solid foreign objects of 50
1 mm and greater 1 Protected against vertically falling water drops
(back of a hand)
Protected against solid foreign objects of
Protected against vertically falling water drops
2 12.5mm and greater 2
Product information
when enclosure tilted up to 15 °
(finger)
Protected against solid foreign objects of 2.5
3 3 Protected against spraying water
mm and greater (tool)
Protected against solid foreign objects of
4 4 Protected against splashing water
1.0mm and greater (wire)
5 Dust-protected (wire) 5 Protected against water jets
6 Dust-tight (wire) 6 Protected against powerful water jets
Protected against the effects of temporary
Mechanical installation
7 - 7
immersion in water
Protected against the effects of continuous
8 - 8
immersion in water
Electrical installation
Enclosures are intended for indoor use, primarily to provide a degree
Type 12 of protection against dust, falling dirt and dripping non-corrosive
liquids.
Safety information
normally be found on the motor data sheet in V/k rpm (volts per 1,000 rpm).
It is recommended that a minimum ratio of 12:1 is maintained between the switching frequency and
the maximum output frequency to maintain the quality of the output waveform. If this minimum ratio is
exceeded, extra motor losses will result due to the increased harmonic content of the output
waveform.
5.1.16 Accuracy and resolution
Unidrive M600 to M702:
Speed:
Product information
The absolute frequency and speed accuracy depends on the accuracy of the crystal used with the
drive microprocessor. The accuracy of the crystal is 100 ppm, and so the absolute frequency/speed
accuracy is 100 ppm (0.01 %) of the reference, when a preset speed is used. If an analog input is
used the absolute accuracy is further limited by the absolute accuracy of the analog input.
The following data applies to the drive only; it does not include the performance of the source of the
control signals.
Open loop resolution:
Mechanical installation
Preset frequency reference: 0.1 Hz
Precision frequency reference: 0.001 Hz
Closed loop resolution
Preset speed reference: 0.1 rpm
Precision speed reference: 0.001 rpm
Analog input 1: 11 bit plus sign (not applicable to Unidrive M702)
Analog input 2: 11 bit plus sign (not applicable to Unidrive M702)
Current:
The resolution of the current feedback is 10 bit plus sign.
Electrical installation
Accuracy: typical 2 %
worst case 5 %
Unidrive M200 to M400:
Frequency:
The absolute frequency accuracy depends on the accuracy of the oscillator used with the drive
microprocessor. The accuracy of the oscillator is ± 0.02 %, and so the absolute frequency accuracy
is ± 0.02 % of the reference, when a preset frequency is used. If an analog input is used, the absolute
accuracy is further limited by the absolute accuracy of the analog input. Technical data
The following data applies to the drive only; it does not include the performance of the source of the
control signals.
Open & closed loop resolution:
Preset frequency reference: 0.01 Hz
Analog input 1: 11 bit plus sign
Analog input 2: 11 bit
UL listing information
Current:
The resolution of the current feedback is 10 bit plus sign.
Accuracy: typical 2 %
worst case 5 %
Safety information
Typical input current
The values of typical input current are given to aid calculations for power flow and power loss.
The values of typical input current are stated for a balanced supply.
Maximum continuous input current
The values of maximum continuous input current are given to aid the selection of cables and fuses.
These values are stated for the worst case condition with the unusual combination of stiff supply with
bad balance. The value stated for the maximum continuous input current would only be seen in one
of the input phases. The current in the other two phases would be significantly lower.
Product information
The values of maximum input current are stated for a supply with a 2 % negative phase-sequence
imbalance and rated at the maximum supply fault current of 100kA.
Table 5-15 AC Input current and fuse ratings (200 V)
Maximum Maximum Fuse rating
Typical
continuous overload
input IEC UL / USA
Model input input
current
current current Nominal Max Nominal Max
Mechanical installation
Class Class
A A A A A A A
07200610 58 67 109 80 80 80 80
07200750 73 84 135 100 100 gG 100 100 CC, J or T*
07200830 91 105 149 125 125 125 125
08201160 123 137 213 200 200
200 200 gR HSJ
08201320 149 166 243 225 225
09201760 172 205 270 250 250 250 250
gR HSJ
09202190 228 260 319 315 315 300 300
Electrical installation
10202830 277 305 421 400 400 400 400
gR HSJ
10203000 333 361 494 450 450 450 450
07400660 67 74 124 80 80
100 100
07400770 80 88 145 gG 100 100 CC, J or T*
07401000 96 105 188 125 125 125 125
08401340 137 155 267
250 250 gR 225 225 HSJ
08401570 164 177 303
09402000 211 232 306 300 300
315 315 gR HSJ
09402240 245 267 359 350 350
UL listing information
Safety information
affects their current-carrying capacity, in some cases smaller cables may be acceptable
but in other cases a larger cable is required to avoid excessive temperature or voltage
CAUTION
drop. Refer to local wiring regulations for the correct size of cables.
Product information
Input Output Input Output
Install Install
Nominal Max Nominal Max Nominal Max Nominal Max
method method
07200610 2 2
35 35
07200750 70 B2 70 B2 1 1/0 1 1/0
07200830 70 70 1/0 1/0
08201160 95 95 3/0 3/0
2 x 70 B2 2 x 70 B2 2x1 2x1
08201320 2 x 70 2 x 70 2x1 2x1
Mechanical installation
09201760 2 x 70 2 x 185 2 x 95 2 x 150 2 x 2/0 2 x 500 2 x 2/0 2 x 350
B1 B2
09202190 2 x 95 2 x 185 2 x 120 2 x 150 2 x 4/0 2 x 500 2 x 4/0 2 x 350
10202830 2 x 120 2 x 185 B1 2 x 120 2 x 150 2 x 250 2 x 500 2 x 250 2 x 350
C
10203000 2 x 150 2 x 185 C 2 x 120 2 x 150 2 x 300 2 x 500 2 x 250 2 x 350
Electrical installation
mm2 AWG or Kcmil
Model Input Output Input Output
Install Install
Nominal Max Nominal Max Nominal Max Nominal Max
method method
07400660 35 35 1 1
07400770 50 70 B2 50 70 B2 2 1/0 2 1/0
07401000 70 70 1/0 1/0
08401340 2 x 50 2 x 50 2x1 2x1
2 x 70 B2 2 x 70 B2 2 x 1/0 2 x 1/0
08401570 2 x 70 2 x 70 2 x 1/0 2 x 1/0 Technical data
09402000 2 x 70 2 x 185 2 x 95 2 x 150 2 x 3/0 2 x 500 2 x 2/0 2 x 350
B1 B2
09402240 2 x 95 2 x 185 2 x 120 2 x 150 2 x 4/0 2 x 500 2 x 4/0 2 x 350
10402700 2 x 120 2 x 185 2 x 120 2 x 150 2 x 300 2 x 500 2 x 250 2 x 350
C C
10403200 2 x 150 2 x 185 2 x 150 2 x 150 2 x 350 2 x 500 2 x 300 2 x 350
UL listing information
Safety information
length does not exceed the values given in Table 5-23.
Use 105 °C (221 °F) (UL 60/75 °C temp rise) PVC-insulated cable with copper conductors having a
suitable voltage rating, for the following power connections:
• AC supply to external EMC filter (when used)
• AC supply (or external EMC filter) to drive
• Drive to motor
• Drive to braking resistor
Table 5-23 Maximum motor cable lengths
Product information
Maximum permissible motor cable length for each of the following switching
frequencies
Model
2 3 4 6 8 12 16
kHz* kHz kHz kHz kHz kHz kHz
All size 7 to 187 m 125 m 93 m 62 m 46 m
250 m (820 ft)
10 models (614 ft) (410 ft) (305 ft) (203 ft) (151 ft)
Mechanical installation
* For the Unidrive M200 to M400, the cables lengths at 0.667 and 1kHz switching frequency are the
same as cable lengths at 2 kHz.
• Cable lengths in excess of the specified values may be used only when special techniques are
adopted; refer to the supplier of the drive.
• The default switching frequency is 3 kHz for Open-loop and RFC-A and 6 kHz for RFC-S mode.
The maximum cable length is reduced from that shown in Table 5-23 if high capacitance or reduced
diameter motor cables are used, refer to section 4.8.2 High-capacitance / reduced diameter
cables on page 68.
5.1.22 Braking resistor values
Electrical installation
Table 5-24 Minimum resistance values and peak power rating for the braking resistor at 40 °C (104 °F)
Minimum resistance* Instantaneous power rating Continuous power rating
Model
Ω kW kW
200 V
07200610 4.5 37.6 15
07200750 4.5 37.6 18.5
07200830 4.5 37.6 22
08201160 2.3 73.5 30 Technical data
08201320 2.3 73.5 37
09201760 (9A) 2 84.5 45
09202190 (9A) 2 84.5 45
09201760 (9E) 1.4 120.8 45
09202190 (9E) 1.4 120.8 55
10202830 1.7 99.5 75
10203000 1.7 99.5 90
UL listing information
400 V
07400660 7.5 90.2 30
07400770 7.5 90.2 37
07401000 7.5 90.2 45
08401340 6.3 107.4 55
08401570 6.3 107.4 75
09402000 (9A) 3.6 187.8 90
Safety information
Model Connection type Torque setting
M200 to M400 Screw terminals 0.2 N m (0.15 lb ft)
M600 to M702 Plug-in terminal block 0.5 N m (0.4 lb ft)
Product information
0.5 N m (0.4 lb ft)
M600 to M702 Plug-in terminal block
Table 5-27 Terminal block maximimum cable sizes
Model Size Terminal block description Maximum cable size
All All Control connector 1.5 mm2 (16 AWG)
All All 2 way relay connector
2.5 mm2 (14 AWG)
M300 to M400 7 to 9 STO connector
Mechanical installation
2 way low voltage power 24V supply
M600 to M702 All
connector 1.5 mm2 (16 AWG)
Electrical installation
Brake connection 2 x 150 2 x 350
1 See section 4.11.8 Variations in the EMC wiring on page 89 for possible requirements regarding
grounding and external surge protection of control ports.
Safety information
provides further reduction of emission. The requirements of the following standards are met,
depending on the motor cable length and switching frequency.
Table 5-31 Size 7 emission compliance (200 V drives)
Switching Frequency (kHz)
Motor cable length (m)
2 3 4 6 8 12 16
Using internal filter:
0 – 100 C4 C4 C4 C4 C4 C4 C4
Product information
Using external filter:
0 – 20 C2 C2 C2 C2 C2 C2 C2
20 – 100 C2 C2 C3 C3 C3 C3 C3
Mechanical installation
Using internal filter:
0 – 100 C4 C4 C4 C4 C4 C4 C4
Using external filter:
0 – 20 C2 C2 C2 C2 C2 C2 C2
20 – 100 C2 C2 C3 C3 C3 C3 C3
Electrical installation
2 3 4 6 8 12 16
Using internal filter:
0 – 100 C4 C4 C4 C4 C4 C4 C4
Using external filter:
0 – 20 C2 C2 C2 C2 C2 C2 C2
20 – 100 C2 C2 C3 C3 C3 C3 C3
Table 5-39 Size 9 and 10 emission compliance (575 V and 690 V drives)
Switching Frequency (kHz)
Motor cable length (m)
2 3 4 6 8 12 16
Using internal filter:
0 - 50 C3 C3 C3 C3 C3 C3 C3
Using external filter:
0 – 20 C2 C2 C2 C2 C2 C2 C2
20 – 100 C2 C2 C3 C3 C3 C3 C3
Safety information
required to prevent interference)
E2U EN 61800-3 second environment, unrestricted distribution
I Industrial generic standard EN 61000-6-4
EN 61800-3 first environment restricted distribution (The following caution is required by EN
61800-3)
Product information
residential environment this product may cause radio interference in which case the user
CAUTION
may be required to take adequate measures.
Mechanical installation
which supplies buildings used for residential purposes.
• The second environment is one that includes all establishments other than those directly
connected to a low-voltage power supply network which supplies buildings used for residential
purposes.
• Restricted distribution is defined as a mode of sales distribution in which the manufacturer
restricts the supply of equipment to suppliers, customers or users who separately or jointly have
technical competence in the EMC requirements of the application of drives.
EN 61800-3:2004+A1:2012
Electrical installation
The 2004 revision of the standard uses different terminology to align the requirements of the
standard better with the EC EMC Directive.
Power drive systems are categorized C1 to C4:
Corresponding code
Category Definition
used previously
C1 Intended for use in the first or second environments R
Not a plug-in or movable device, and intended for use in
C2 the first environment only when installed by a I Technical data
professional, or in the second environment
Intended for use in the second environment, not the first
C3 E2U
environment
Intended for use in the second environment in a system
C4 E2R
rated at over 400 A or in a complex system
Note that category 4 is more restrictive than E2R, since the rated current of the PDS must exceed
400 A or the supply voltage exceed 1000 V, for the complete PDS.
UL listing information
Safety information
Dimensions (mm)
Weight
Part Number H W D
mm inch mm inch mm inch kg lb
4200-1132 270 10.63 90 3.54 150 5.90 6 13.2
4200-0672 270 10.63 90 3.54 150 5.90 6.2 13.7
4200-1972 300 11.81 120 4.72 170 6.69 9.6 21.2
4200-1662 300 11.81 120 4.72 170 6.69 9.4 20.7
4200-3021 339 13.3 230 9.06 120 4.72 11 24.3
Product information
4200-1660 360 14.2 245 9.6 105 4.13 5.2 11.5
4200-4460 105 4.13 360 14.2 245 9.6 12 26.5
4200-2210 105 4.13 360 14.2 245 9.6 10.3 22.7
Mechanical installation
CT part connections connections
number Ground stud
Bar hole diameter Max cable size Max torque Max torque
size
4200-1132 50 mm 2 8.0 N m
4200-0672 (1/0 AWG) (6.0lb ft)
N/A
4200-1972 95 mm2 20 N m
4200-1662 (3/0 AWG) (14.8 lb ft) 18 N m
M10
4200-3021 10.8 mm (13.3 lb ft)
4200-1660 10.8 mm 30 N m
N/A
Electrical installation
4200-4460 11 mm (22.1 lb ft)
4200-2210 11 mm
Technical data
UL listing information
6.4 Mounting
Drives may be surface, through-panel or tile mounted using the appropriate brackets. Drives may be
mounted singly or side by side with suitable space between them (bookcase mounting).
6.5 Environment
Drives must be installed in a Pollution Degree 2 environment or better (dry, non-conductive pollution
only).
The drives have been evaluated for use at ambient temperatures up to 40 °C. The drives have
additionally been evaluated for 50 °C and 55 °C ambient air temperatures with a derated output.
Safety information
Drives have been evaluated for OVC III.
Supply
The drives are suitable for use on a circuit capable of delivering not more than 100,000 RMS
symmetrical amperes, 480 Vac Maximum.
Terminal Torque
Terminals must be tightened to the rated torque as specified in the Installation Instructions.
Product information
Wiring Terminals
Drives must be installed using cables rated for 75 °C operation, copper wire only.
Where possible, UL Listed closed-loop connectors sized according to the field wiring shall be used
for all field power wiring connections.
Ground connection instructions
UL Listed closed-loop connectors sized according to the field wiring shall be used for grounding
connections.
Mechanical installation
Branch circuit protection
The fuses and circuit breakers required for branch circuit protection are specified in the Installation
Instructions.
Opening of branch circuit
Opening of the branch-circuit protective device may be an indication that a fault has been
interrupted. To reduce the risk of fire or electric shock, the equipment should be examined and
replaced if damaged. If burnout of the current element of an overload relay occurs, the complete
overload relay must be replaced.
Electrical installation
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electrical Code (NEC), The Canadian
Electrical Code, and any additional local codes.
Dynamic braking
M100, M101, M200, M201, M300 or M400, frame sizes 1 to 4 have been evaluated for dynamic
braking applications. Other drive models have not been evaluated for dynamic braking.
expressed as a percentage of full-load current. Refer to the Control User Guide for further
information.
In order for the motor protection to work properly, the motor rated current must be entered into Pr 06
or Pr 05.007.
The protection level may be adjusted below 150 % if required. Refer to the Control User Guide for
further information.
UL listing information