Catalog | April 2023

Modicon X80 modules


The common offer of modules for
Modicon M580 and M340 PLCs/PACs

www.se.com
Modicon
Discover Modicon
Edge control for Industrial IoT
Modicon IIoT-native edge controllers manage complex interfaces
across assets and devices or directly into the cloud, with embedded
functional safety and cybersecurity. Modicon provides performance
and scalability for a wide range of industrial applications up to high-
performance multi-axis machines and high-available redundant
processes.

Explore our offer


- Modicon HVAC Controllers
- Modicon PLC
- Modicon Motion Controllers
- Modicon PAC
- Modicon I/O
- Modicon Networking
- Modicon Power Supply
- Modicon Wiring
- Modicon Safety
Quick access to product information

Get technical information about your product

Each commercial reference presented in a catalog contains a hyperlink.


Click on it to obtain the technical information of the product:
– Characteristics, Dimensions and drawings, Mounting and clearance,
Connections and schemas, Performance curves
– Product image, Instruction sheet, User guide, Product certifications,
End of life manual

Find your catalog

• Up-to-date catalogs
• Embedded product selectors,360° pictures
> With just 3 clicks, you can access the Industrial Automation • Optimized search by commercial references
and Control catalogs, in both English and French
> Consult digital automation catalogs at Digi-Cat Online

Select your training

> Find the right Training for your needs on our Global website
> Locate the training center with the selector tool, using this link
General contents

Modicon X80 offer presentation . . . . . . . 1

Backplanes . . . . . . . . . . . . . . . . . . . . . . 2

Power supplies. . . . . . . . . . . . . . . . . . . . 3

I/O modules. . . . . . . . . . . . . . . . . . . . . . 4

Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Expert modules . . . . . . . . . . . . . . . . . . . 6

I/O expansion modules. . . . . . . . . . . . . . 7

Communication modules . . . . . . . . . . . . 8

Dedicated parts for severe environments. . . . 9

Standards and certifications, Services,


Index . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
In this catalog, all instances of words that refer to Safety without precision must be
understood as referring to “Functional Safety” according to IEC 61508 and IEC 61511.

1
Schneider Electric’s IoT-enabled, plug-and-play, open, se-
cure, interoperable architecture and platform, in Industries,
Infrastructures, Data Centers, and Buildings.
Innovation at every level Dedicated architectures and IoT Cybersecurity solutions Enhanced safety
EcoStruxure is based on a three-tiered techno- We tailor our solutions in the form of dedicated Robust cybersecurity protection is a must, and With the release of Modicon M580 Safety,
logy stack delivering innovation at every level, reference architectures for plants: Schneider Electric’s solutions can deliver it, Schneider Electric further expands the EcoS-
from connected products to edge control and b Management systems regardless of business type or industry. truxure platform.
apps, analytics, and services. The vendor-agnostic services provided by our This consolidates our position as one of the
b Power systems
Together with our hybrid segments approach, skilled professionals help to protect your entire most trusted industrial safety vendor, with
b Data center systems thousands of Modicon and Triconex safety
this enhances your value around safety, relia- critical infrastructure. We help to assess your
bility, operational efficiency, sustainability, and b Industrial plant and machine systems risk, implement cyber-specific solutions, and systems protecting the most critical industrial
connectivity across 6 domains of expertise: b Smart grid systems maintain your onsite defenses over time, while processes globally.
b Power b Plant integrating appropriate IT policies and require-
The Industrial Internet of Things (IIoT) gives an ments.
b IT b Grid additional boost to technologies. That's why we
provide our customers with an IoT-enabled ar- This is our difference and your advantage.
b Building
chitecture and platform offering simple, reliable,
b Machine productive, and cost-efficient solutions.

for Plant

EcoStruxure™Architecture

Apps,
Analytics & Field Services
Services
End-to-end Cybersecurity

Cloud and/or On Premise

Performance, Operations, Engineering EcoStruxure Plant Advisor

Harmony Modicon

Edge
Control
Advanced operator Industrial Edge EcoStruxure EcoStruxure EcoStruxure EcoStruxure EcoStruxure SCADA Systems
interface, Edge Box Control for IIoT Foxboro DCS Triconex Safety
Automation Expert Process Expert Control Expert
and industrial relays Systems

Connected
Products
Variable speed drives Innovative & connected Comprehensive, robust Process Pushbuttons and
and soft starters solutions for motor starters portfolio of power distribution Instrumentation Signalling
Sensors and RFID
and motor control centers

*The Schneider Electric industrial software business and AVEVA have merged to trade as AVEVA Group plc, a UK listed company. The
Schneider Electric and Life is On trademarks are owned by Schneider Electric and are being licensed to AVEVA by Schneider Electric.

2 www.se.com Life is On | Schneider Electric 3


Contents 1 - Presentation

Modicon X80 offer presentation


b Overview................................................................................................. page 1/2
b Composition........................................................................................... page 1/6 1
b Description.............................................................................................. page 1/7
b Modicon PAC offer for plant automation............................................... page 1/8
b Product compatibility according to network
architecture and platform.................................................................... page 1/10
2

10

1/1
Overview Modicon X80 modules
Compact, robust, sustainable

Modicon X80 modules Modicon X80 modules serve as the common in-rack I/O, experts, and
communication modules for Modicon M580 and Modicon M340 PAC platforms.
1 This range also includes power supplies, racks and accessories common to both
ranges.
A wide choice of modules is available to meet the needs of Hybrid industries and
critical infrastructures.
> Modicon X80 modules can be used in remote racks with an I/O expansion
module in Modicon M580 architectures. This forms a Modicon X80 RIO Drop.
> Modicon X80 modules can also be used in distributed architectures building
2 Modicon X80 DIO Drops.
Common in-rack modules for This single common offer helps customers to reduce their stocks of spare parts. It
Modicon M580 and Modicon M340 also decreases maintenance and training costs
Modicon X80 in-rack I/O modules provide a high level of services such as bit
forcing, device DDT, Change Configuration on the Fly and are natively integrated
into EcoStruxure Control Expert (1), the programming environment for
3 Modicon M580 and Modicon M340.
Compact
> The Modicon X80 modules feature the latest I/O technology, making them
extremely compact.
> It has smaller cabinet dimensions, with up to 64 discrete I/O for some modules.
> High density
4
M a i nt e

ce
le n

5
na
n ce Exc
el

Modicon X80 modules

6 Robust
> Offering more than required by the standards
Characteristics Modicon X80 modules IEC standards
Required by

7
Mechanical constraints Levels reached IEC 60068-2
Shock 30 g 15 g

Vibrations 3g 1g
Electrical immunity Levels reached IEC 61131-2
Radiated field 15 V/m 10 V/m
Electrostatic discharges

8
6 kV 4 kV
by contact
Inve

tio n

m Environmental immunity Working values IEC 61131-2


ec

e nt prot
st

Temperature 0…60 °C/32… 140 °F 5…55 °C/41… 131 °F


Modicon X80 ruggedized - 25…70 °C/32… 158 °F 5…55 °C/41… 131 °F
offer

Corrosive environments (coated versions) Class Gx, 3C4, Kb, 3S4, 3B2

9 Sustainable

> Common Modicon X80 modules reduce training and maintenance costs
> Hot swappable
> Existing solutions for migrating from legacy I/O to the Modicon X80 modules
> Green Premium Eco Label
10 (1) EcoStruxure Control Expert software continues the Unity Pro range of software and
corresponds to versions u 14 of Unity Pro.

Common platform
1/2
Overview (continued) Modicon X80 modules
Common safety

M580 Safety Regulatory requirements


Good practices dictate that control systems must be designed to keep process
control functions separate and operationally independent from safety functions. 1
This is usually achieved using a controller for the process and a separate system
for safety.

Our solution to combine safety and process management in one


application

> Dual processing capability to control safety and process functions independently 2
Clear distinction between > Unifying independent plant safety and process control to help protect the entire
operating environment
safety and process
> Minimized impact of standard process failure on plant safety, its people, and
assets
> No need to design, install, and maintain separate safety systems
> Same tools, wiring methods, and I/O structures as Modicon M580 controller
3
Sa

et
rit

y & S e cu
f

4
Operator
Engineering System clients
station servers
EcoStruxure
Control Expert P2P
5
HMI

Ethernet Extension
backplane rack

6
ERT
Device
network

Modbus + Proxy
NRP

7
CANopen

NOM Modbus SL

HMI

8
PROFIBUS DP
PROFIBUS PA

AS-i
Weighing

Typical common Safety architecture with Modicon M580 Safety 9

10

Combining standard process and safety in a single M580 project


1/3
Overview Modicon X80 modules
Certifications and standards

Certifications and standards


Depending on the model, Modicon X80 modules comply with the following
1 standards:
O
p ti m iz e d > International certifications: CE, UL, CSA, RCM, EAC, UKCA
> Certified for Hazardous Location Class I Division 2 Groups ABCD and for
ATEX/UKEX/IECEx zone 2/22 (depending on the model, see pages 10/2 to
10/3)
> Merchant navy: IACS E10 and agencies: ABS, BV, DNV, GL, LR, RINA,

2 >
RMRS, and CCS
Power generation market: IEC 61000-6-5, IEC 61850-3
> See pages 10/2 to 10/3 for more information.

International certifications

4 Merchant navy

6
Hazardous locations

7
Functional safety

10

Comprehensive certifications and standards


1/4
Overview Modicon X80 modules
Market segments

Market segments
> The Modicon PAC platforms (Modicon M340 and Modicon M580) supported by
common Modicon X80 modules are suited to fulfill the requirements of following 1
Ce
r t i fi e d
vertical segments:

Water & Mining, minerals & Consumer Packaged 2


waste water metals Goods

Oil & gas Power generation Discrete


manufacturing
3

Transportation
4
Tunnels Data centers

10

Simplified offer from small to large applications


1/5
Presentation Modicon X80 modules
Composition

Presentation

1
Modicon X80 modules serve as the common in-rack I/O, expert, and communication
modules for Modicon M580 and Modicon M340 PAC platforms (1). This range also
includes power supplies, racks and accessories common to both ranges.

Modicon M580 platform

3 Modicon M340 platform


Modicon X80 modules may also:
b Form part of a Modicon M580 Ethernet I/O architecture as an Ethernet RIO (EIO)
drop with X80 Remote I/O drop adapter;

Modicon PLC Configurator

4
Click on the pictogram to access
Modicon PLC Configurator on line

5 Modicon X80 RIO drop for Modicon M580 Ethernet I/O architecture

b Form an Ethernet Modbus/TCP DIO drop with X80 Peripheral remote I/O
adapter.

7
Modicon X80 DIO drop

Modicon X80 modules are available in single-rack or multi-rack configuration. One


Modicon X80 RIO drop may support two racks separated by a cumulative distance

8 of up to 30 m/98 ft.
These modules, common to several automation platforms, can reduce
maintenance and training costs as it comprises:
b a single range of spare parts in stock
b training common to several PLCs
Based on the latest I/O technology, Modicon X80 modules offer:

9 b high-quality ruggedness and compactness


b compliance with international certifications (ATEX, IEC, etc.)
b a wide selection of modules: discrete or analog I/O modules, expert modules,
In progress: all Modicon products in grey communication modules, etc.
Bit forcing simplifies simulation and structured data simplifies diagnostics.

10 (1) See the compatibility guide on page 1/10.

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 2
 /2 page 3/2 page 4
 /2 page 8/2 page 9
 /2

1/6
Description Modicon X80 modules
Description

Description
Modicon X80 modules
1  X-bus backplane with 4, 6, 8, or 12 slots or Ethernet + X-bus backplane with 4, 8, 1
or 12 slots for single power supply, and Ethernet + X-bus backplane with 6 or 10
slots for dual power supply
2  AC or DC power supply modules
3  Discrete and analog I/O modules
4  RIO drop adapter
1 4 2

3
2 3
Typical basic assembly with Modicon X80 I/O modules

Modicon X80 offer extends to:

4
b X80 I/O modules, including HART I/O
b X80 Expert modules such as counter, motion control, SSI encoder, time-
stamping, frequency input modules, and additional TPP (1) module for weighing
b X80 Communication modules for AS-Interface, Modbus, CANopen,
PROFIBUS DP communication, and additional devices such as fiber converter
modules and Ethernet network switch module
b X80 I/O expansion modules: Remote I/O drop and Peripheral remote I/O drop
adapters
Modicon M580 and Modicon M340 automation platforms also include specific 5
communication modules that are described in the related catalog:

7
DIA6ED2151012EN DIA6ED2110104EN

Treatment for severe environments


In their ruggedized version, the Modicon X80 modules may be used in harsh

8
environments or within a range of operating temperatures from -25 to +70 °C / -13 to
+158 °F (see page 9/2).

(1) Technology Partner Program

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 4
 /2 page 8
 /2 page 9
 /2

1/7
Modicon PAC offer for > Modicon X80
plant automation I/O modules
From 4 to 64 channels, discrete or
short form module long form module
(100mm) (131mm)

Standard and severe environments* analog (including temperature and


HART), Standard and Safety
1 1

> Modicon M580


ePAC (PLC)
2 Standard or Safety with coprocessor, Standalone or Redundant
2
Backplanes
From 4 to 12 slots, single bus (X-Bus) or
dual bus (X-Bus & Ethernet), for
Communication modules
3 Redundant or Standalone power supply AS-i, Modbus/ASCII Serial link,
CANopen, PROFIBUS DP, fiber 3
converter, Ethernet switch

4 Communication modules 4
OPC UA, IEC61850, IEC101/104,
DNP3, EtherNet/IP, Modbus/TCP
Expert modules
5 Counter, time-stamping, motion control,
frequency input,weighing, and 5
Communication modules diagnostics...
IEC101/104, DNP3, EtherNet/IP,
Modbus/TCP Power supplies
6 Standard or Safety, AC or DC, 6
> Modicon M340 Standalone or Redundant

I/O Expansion modules


PAC (PLC) Remote I/O adapter for Modicon M580
7 Standard or Performance 7
Modbus serial link, Modbus/TCP, or CANopen

8 8
* Most of Modicon products exist in hardened (H) or coated (C) versions to support severe environments

Configure with online tool: Pilot with EcoStruxure: > Modicon Networking
9 Ethernet Switches 9
Managed or Unmanaged
Modicon PLC Configurator
Click on the pictogram to access
Modicon PLC Configurator on line

10 10

More technical Information on www.se.com More technical Information on www.se.com

1/8 1/9
Compatibility Modicon M580/M340 platforms and Modicon X80 modules
Product compatibility according to network architecture and platform
For safety product compatibility, please refer to page 5/4

Product type Product main feature Commercial Module type Connection type Modicon M340 Modicon M580 Modicon M580 / M340
reference (1) Local rack with CPU Modicon X80 drops on Ethernet remote I/O Modicon X80 drops

1 1

preassembled cordset (3)


on distributed I/O
Standalone CPU Redundant CPU Standalone or redundant CPU N/A
X-bus backplane (4) X-bus + X-bus backplane (4) X-bus + X-bus backplane BMXXBPpppp X-bus + Ethernet X-bus backplane

Terminal block (2)


BMXXBPpppp Ethernet backplane BMXXBPpppp Ethernet backplane backplane BMXXBPpppp and

Connector with
BMEXBPpppp BMEXBPpppp BMEXBPpppp X-bus + Ethernet
backplane
BMEXBPpppp
BMXCRA31200 BMXCRA31210 BMECRA31210 BMXPRA0100
2 Modicon X80 Standalone Power
2
BMXCPS2000 100...240 V a, 20W
Power supplies supplies BMXCPS2010 24 V c, 17W
BMXCPS3020 (H) 24...48 V c, 32W
BMXCPS3500 (H) 100...240 V a, 36W
BMXCPS3540T 125 V c, 36W

3 Redundant Power
supplies
BMXCPS4002 (H)
BMXCPS4022 (H)
100...240 V a, 40W
24...48 V c, 40W
3
BMXCPS3522 (H) 125 V c, 40W
Modicon X80 X-bus Backplane BMXXBP0400 (H) 4 slots
Backplanes BMXXBP0600 (H) 6 slots
BMXXBP0800 (H) 8 slots

4 X-bus + Ethernet
BMXXBP1200 (H)
BMEXBP0400 (H)
12 slots
4 slots 4
Backplane BMEXBP0800 (H) 8 slots
BMEXBP1200 (H) 12 slots
X-bus + Ethernet, Dual BMEXBP0602 (H) (5) 6 slots
Power supply Backplane BMEXBP1002 (H) (5) 10 slots
Rack expansion
5 5
BMXXBE1000 (H) (6) Expansion module
BMXXBE2005 (7) Expansion kit
Accessories BMXXEM010 (8) Protective cover
Modicon X80 Discrete Input AC BMXDAI0805 8 inputs, 200…240 Va 20
Discrete modules BMXDAI0814 8 inputs, 100...120 Va 20
BMXDAI1602 (H) 16 inputs, 24 Va/ c 20
BMXDAI1603 (H) 16 inputs, 48 Va 20

6 BMXDAI1604 (H)
BMXDAI1614 (H)
16 inputs, 100...120 Va
16 inputs, 100...120 Va
20
40
6
BMXDAI16142 16 inputs, 100...120 Va 40
BMXDAI1615 (H) 16 inputs, 200…240 Va 40
Discrete Output AC BMXDAO1605 (H) 16 outputs, 100…240 Va 20
BMXDAO1615 (H) 16 outputs, 24…240 Va 40

7 Discrete Input DC BMXDDI1602 (H)


BMXDDI1603 (H)
16 inputs, 24 V c
16 inputs, 48 V c
20
20 7
BMXDDI1604T 16 inputs, 125 V c 20
BMXDDI3202K (H) 32 inputs, 24 V c 40
BMXDDI3203 (H) 32 inputs, 48 V c 40
BMXDDI3232 (H) 32 inputs, 12/24 V c 40

8 8
BMXDDI6402K (H) 64 inputs, 24 V c 2x40
Discrete Mixed I/O BMXDDM16022 (H) 8 inputs, 24 V c; 20
8 outputs, 24 V c
BMXDDM16025 (H) 8 inputs, 24 V c; 20
8 outputs, relay 24…240 Va/24 V c
BMXDDM3202K 16 inputs, 24 V c; 40
16 outputs, 24 V c
Discrete Output DC BMXDDO1602 (H) 16 outputs, 24 V c 20
9 BMXDDO1612 (H) 16 outputs, 24 V c negative 20 9
BMXDDO3202 (H) 32 outputs, 24 V c 40
BMXDDO3202K (C) 32 outputs, 24 V c 40
BMXDDO6402K (C) 64 outputs, 24 V c 2x40
Discrete Output Relay BMXDRA0804T 8 outputs, 100…150 Va 20
BMXDRA0815 (H) 8 outputs, 24…240 Va/24...125 V c 20

10 BMXDRA1605 (H)
BMXDRC0805 (H)
16 outputs, 24…240 Va/24 V c
8 outputs, 24…240 Va/24...125 V c
20
40
10
(1) Optional versions: (C) - “Coated”, (H) - “Hardened”, and (T) - “Extended Temperature” (3) 40: One 40-way connector (6) Extended rack can be on any type of backplane, but only X-bus
(2) 20: 20-way caged, screw clamp, or spring-type removable terminal block BMXFTB20p0 Compatible Not Compatible 2x40: Two 40-way connectors modules (BMX) can be used
28: 28-way caged or spring-type removable terminal block BMXFTB28p0 (4) BMXXBPpppp with PV02 or later required (7) Extended rack kit
40: 40-way caged or spring-type removable terminal block BMXFTB40p0 (5) Not compatible with single power supplies (8) Protective cover for unoccupied slots on backplane

1/10 1/10
1/11
Compatibility (continued) Modicon M580/M340 platforms and Modicon X80 modules
Product compatibility according to network architecture and platform
For safety product compatibility, please refer to page 5/4

Product type Product main feature Commercial Module type Connection type Modicon M340 Modicon M580 Modicon M580 / M340
reference (1)
Local rack with CPU Modicon X80 drops on Ethernet remote I/O Modicon X80 drops

1 1

preassembled cordset (3)


on distributed I/O
Standalone CPU Redundant CPU Standalone or redundant CPU N/A

Terminal block (2)


X-bus backplane (4) X-bus + X-bus backplane (4) X-bus + X-bus backplane BMXXBPpppp X-bus + Ethernet X-bus backplane

Connector with
BMXXBPpppp Ethernet backplane BMXXBPpppp Ethernet backplane backplane BMXXBPpppp and
BMEXBPpppp BMEXBPpppp BMEXBPpppp X-bus + Ethernet
backplane
BMEXBPpppp

2 2
BMXCRA31200 BMXCRA31210 BMECRA31210 BMXPRA0100

Modicon X80 Analog High-level Input BMXAMI0410 (H) 4 voltage/current inputs 20


Analog modules BMXAMI0800 8 voltage/current inputs 28
BMXAMI0810 (H) 8 voltage/current inputs 28
BMEAHI0812 (H) 8 current inputs, HART 20
Analog Low-level Input BMXART0414 (H) 4 RTD, thermocouple and voltage inputs 40

3 Analog Mixed I/O


BMXART0814 (H)
BMXAMM0600 (H)
8 RTD, thermocouple and voltage inputs
4 voltage/current inputs & 2 voltage/current outputs 20
40
3
Analog High-level Output BMXAMO0210 (H) 2 voltage/current outputs 20
BMXAMO0410 (H) 4 voltage/current outputs 20
BMXAMO0802 (H) 8 current outputs 20
BMEAHO0412 (C) 4 current outputs, HART 20

4 Modicon X80
Expert modules
SSI encoder interface
Counter
BMXEAE0300 (H)
BMXEHC0200 (H)
3 channels
2 channels
28
2x16,10 4
BMXEHC0800 (H) 8 channels 20
Time Stamping BMXERT1604T/H 16 inputs , 24...125 V c 28
Motion Control BMXMSP0200 2 channels 28
Frequency Input BMXETM0200H 2 channels 28

5 5
Weighing (5) PMESWT0100 1 channel
Communication Modicon X80 BMXNOM0200 (H) Serial link
modules (6) BMXEIA0100 AS-Interface
BMECXM0100 (H) CANopen
BMXNRP0200 (C) Fiber converter Multimode
BMXNRP0201 (C) Fiber converter Singlemode
PMEPXM0100 (H) PROFIBUS DP

6 Modicon M580
BMENOS0300 (C)
BMENOC0301 (C)
Ethernet switch
Ethernet
6
BMENOC0311 (C) Ethernet FactoryCast
BMENOC0321 (C) Ethernet control router
BMENOP0300 IEC 61850
BMXNGD0100 Ethernet Global Data

7 BMENUA0100 (H)
BMENOR2200H
OPC UA
Advanced RTU
7
Modicon M580/M340 BMXNOR0200H RTU
Modicon M340 BMXNOE0100 (H) Ethernet
BMXNOE0110 (H) Ethernet FactoryCast
BMXNOC0401 Ethernet

8 8
Modicon X80 I/O RIO drop adapter BMXCRA31200 X-bus, Standard
expansion BMXCRA31210 (C) X-bus, Performance
modules
BMECRA31210 (C) Ethernet, Performance
DIO drop adapter BMXPRA0100 Peripheral
(1) Optional versions: (C) - “Coated”, (H) - “Hardened”, and (T) - “Extended Temperature”
(2) 20: 20-way caged, screw clamp, or spring-type removable terminal block BMXFTB20p0
28: 28-way caged or spring-type removable terminal block BMXFTB28p0

9 40: 40-way caged or spring-type removable terminal block BMXFTB40p0


2x16,10: BMXXTSHSC20 kit, containing two 16-way connectors and one 10-way connector
(3) 40: One 40-way connector
9
2x40: Two 40-way connectors
(4) BMXXBPpppp with PV02 or later required
(5) Products by our Technology Partners; see more information on our partner website page
(6) According to the module type, communication module description is included within Modicon X80 catalog, Modicon M580 catalog, or Modicon M340 catalog.

Compatible Not compatible


10 10

1/11
1/12 1/11
1/13
Contents 2 - Backplanes

Single-rack configuration
b Presentation, description, references.................................................. page 2/2
b Accessories for single-rack configuration........................................... page 2/5 1
Multi-rack configuration
b Presentation, description...................................................................... page 2/6
b Accessories, references........................................................................ page 2/9
2

10

2/1
Presentation, Modicon X80 modules
description Modicon X80 backplanes
Single-rack configuration

Presentation
Modicon X80 offer includes three types of backplanes compatible with Modicon
1 automation products:
b Dual Ethernet and X-bus backplanes (BMEXBPpp00), with Ethernet connectivity
to some slots on the backplane.
b X-bus backplanes (BMXXBPpppp) (1), with X-bus functionality, conforming to
the legacy implementation and specification.
b Backplanes with power rendundancy (BMEXBPpp02), thanks to an additional
power supply slot.
2 Please refer to the Product compatibility table (page 1/10) for more information on
possible combinations with Modicon X80 modules.
Modicon PLC Configurator
All backplanes are available in both standard and ruggedized format for severe
environments (see page 9/2 for severe environment products).
X-bus backplane functionalities

3 Click on the pictogram to access


Modicon PLC Configurator on line
BMXXBPpp00 backplanes are basic elements in Modicon M580 single-rack and
multi-rack configurations, equipped with 4, 6, 8, or 12 slots. They perform the
following functions:
b They assign a rack number to X-bus slots
b Mechanical function: They are used to install modules in a PLC station (power
supply, processor, discrete, analog, and application-specific I/O). These racks can
be mounted on a panel or a plate, inside enclosures, on machine frames, etc.

4 b Electrical function: The racks incorporate X-bus (proprietary bus). They are used to:
v Distribute the power supply required for each module in the same rack
v Distribute data and service signals for the entire PLC station
v Hot swap modules during operation
Dual Ethernet and X-bus backplane functionalities
BMEXBPpppp backplanes provide electrical and mechanical functions for installing

5 modules in a PLC station (power supply, processor, discrete, analog, and application-
specific I/O), and feature additional functions:
b BMEXBPpp00 backplanes provide specific services to X-bus slots:
v Assign a rack number
v Supply the interconnection for the slots in the main and extended backplanes
b BMEXBPpp02 are dual power supply backplanes with two CPS slots for two
redundant power supplies. They feature:

6 v Compatibility only with redundant power supplies


v Security of power supply in high-availability applications
The Ethernet interface is the main communication medium in the Ethernet
backplane. The Ethernet modules on the Ethernet backplane are attached to one of
several ports and they connect to the Ethernet switch chip embedded in the Ethernet
backplane.
The Ethernet backplanes provide the following services to Ethernet slots:
7 b Ethernet connection
b Point-to-point connection
2 1 5 3

Description
X-bus backplanes

8 BMXXBPpp00 backplanes are available in 4, 6, 8, or 12-slot versions and comprise:


1 A metal frame with the following functions:
- Holds the X-bus electronic card and helps it withstand EMI and ESD type
interference
- Holds the modules
- Gives the rack mechanical rigidity
2 A ground terminal for grounding the rack

9
4 7 8 6 4 3 4 holes (big enough for M6 screws) for mounting the rack on a frame
4 2 fixing points for the shielding connection bar
BMXXBP0600 backplane with 6 slots
5 Tapped holes to take the locking screw on each module
6 A connector for a rack expansion module, marked XBE
7 40-way female ½ DIN connectors forming the electrical connection between the rack
and each module, marked CPS, 00…11 (the rack is delivered with each connector
protected by a cover, which needs to be removed before inserting the module)

10
8 Slots for anchoring the module pins

(1) Mandatory PV02 version or later.

2/2
Description (continued) Modicon X80 modules
Modicon X80 backplanes
Single-rack configuration

Description (continued)
8 7 2a
Dual Ethernet and X-bus backplanes
The number of X-bus and Ethernet slots found on a backplane depends on the
backplane size.
1
BMEXBP0400/BMEXBP0800 are 4/8-slot dual Ethernet and X-bus backplanes
with:
1  CPS slot for power supply
2  4 slots (BMEXBP0400) /8 slots (BMEXBP0800) with:

2
2a 4/8 Ethernet and X-bus connectors for mixed modules (1)
94 5 1 2 4 63 3  Extension: 1 connector for a X-bus backplane expansion
4  2 fixing points for the shielding connection bar
BMEXBP0400 backplane
5  Protective ground screw
6  Slots for anchoring the module pin
7  Tapped holes for the locking screw on each module
8  4 holes for M4, M5, M6, or UNC #6-32 screws (4.32 mm to 6.35 mm/0.17 to 0.25 in.)

3
9  Rack fastened to 35 mm/1.38 in. wide and 15 mm/0.59 in. deep DIN rails.
Mounting on a 35 mm/1.38 in. wide and 7.5 mm/0.295 in. deep DIN rail is also
possible (in this case, the product withstands less mechanical stress).

BMEXBP1200 is a 12-slot dual Ethernet and X-bus backplane with:


8 7 2a
1  CPS slot for power supply
2  12 slots with:
2a 8 Ethernet and X-bus connectors for mixed modules (1)
2b 4 X-bus connectors for X-bus modules
4
3  Extension: 1 connector for an X-bus backplane expansion
4  2 fixing points for the shielding connection bar
5  Protective ground screw
6  Slots for anchoring the module pin
2b 7  Tapped holes for the locking screw on each module

4 5 1 2 46 3
8  4 holes for M4, M5, M6, or UNC #6-32 screws (4.32 mm to 6.35 mm/0.17 to 0.25 in.) 5
BMEXBP1200 backplane
Backplanes with redundant power supply
BMEXBP0602 is a 6-slot dual Ethernet and X-bus backplane with:
1  2 CPS slots for BMXCPSppp2 redundant power supply only
8 7 2a
2  6 slots with:
2a 6 Ethernet and X-bus connectors for mixed modules (1)
3  Extension: 1 connector for an X-bus backplane expansion
6
4  2 fixing points for the shielding connection bar
5  Protective ground screw
6  Slots for anchoring the module pin
7  Tapped holes for the locking screw on each module
8  4 holes for M4, M5, M6, or UNC #6-32 screws (4.32 to 6.35 mm/0.17 to 0.25 in.)

4 5 1 1 2 46 3
9  Rack is fastened to 35 mm/1.38 in. wide and 15 mm/0.59 in. deep DIN rails.
Mounting on a 35 mm/1.38 in. wide and 7.5 mm/0.295 in. deep DIN rail is also
7
BMEXBP0602 backplane possible (in this case, the product withstands less mechanical stress).

BMEXBP1002 is a 10-slot dual Ethernet and X-bus backplane with:


8 7 2a 1  2 CPS slots for BMXCPSppp2 redundant power supply only
2  10 slots with:
2a 8 Ethernet and X-bus connectors for mixed modules (1)
8
2b 2 X-bus connectors for X-bus modules
3  Extension: 1 connector for an X-bus backplane expansion
4  2 fixing points for the shielding connection bar
5  Protective ground screw
2b 6  Slots for anchoring the module pin

4 5 1 1 2 46 3
7  Tapped holes for the locking screw on each module
8  4 holes for M4, M5, M6, or UNC #6-32 screws (4.32 to 6.35 mm/0.17 to 0.25 in.)
9
BMEXBP1002 backplane (1) Modules supporting both X-Bus and Ethernet. All Modicon X80 I/O modules,
except HART modules, are mixed modules. See compatibility table for more
details, page 1/10.

10

2/3
References Modicon X80 modules
Modicon X80 backplanes
Single-rack configuration

X-bus backplanes
PF122567A

Description Type of module No. of Power Reference Weight


1 to be inserted slots
(1)
consump-
tion (2)
kg/lb

X-bus BMXCPS power supply, 4 1W BMXXBP0400 0.630/


BMXXBP0400 backplanes BMXP34 or BMEP58 1.389
processor, 6 1.5 W BMXXBP0600 0.790/
I/O modules, communication 1.742
modules and application-
PF122568A

8 2W BMXXBP0800 0.950/
specific modules (counter,

2
2.094
motion control, and serial)
12 – BMXXBP1200 1.270/
2.780
BMXXBP0600
PF122569A

3
BMXXBP0800
PF122570A

4
BMXXBP1200

5 Ethernet + X-bus backplanes (3) (4)


Description Type of module Ethernet X-bus Power Reference (3) Weight
(5) to be inserted connectors connectors consump- kg/lb
PF122506

tion
(2)
4-slot BMXCPS power 4 4 2.8 W BMEXBP0400 0.719/
Ethernet + supply, BMEP58/ 1.500
BMEH58 processor,
6
BMEXBP0400 X-bus
backplane I/O modules,
communication
8-slot modules and 8 8 3.9 W BMEXBP0800 1.064/
2.350
PF122507

Ethernet + application-specific
X-bus modules (counter,
backplane motion control, and
serial) 8 12 3.9 W BMEXBP1200 1.398/
12-slot
BMEXBP0800 3.080

7
(8 Ethernet +
X-bus/4
X-bus)
backplane
PF122508

6-slot BMXCPSppp2 6 6 3.9 W BMEXBP0602 1.377/


Ethernet + redundant power 3.036
X-bus dual supply, BMEP58/
BMEXBP1200 power supply BMEH58 processor,
backplane I/O modules,
8 10-slot (8
Ethernet +
communication
modules and
8 10 3.9 W BMEXBP1002 1.377/
3.036
application-specific
PF122508

X-bus/2
X-bus) modules (counter,
dual power motion control, and
supply serial)
BMEXBP0602 backplane

9 (1) Number of slots taking the processor module, I/O modules, communication modules, and
application-specific modules (excluding power supply module).
PF122508

(2) Power consumption of anti-condensation resistor(s).


(3) In a Modicon M580 architecture, Ethernet backplanes can be used for Ethernet RIO drop
(EIO) and for expansion racks. Only the X-bus is extended across expansion racks
connected in a daisy chain. Modules that require connection to the Ethernet bus do not
BMEXBP1002 operate when installed in expansion racks (refer to compatibility table page 1/10).
(4) For multi-rack configuration, see page 2/6.

10 (5) Maximum number of slots for modules excluding power supply and rack expansion modules.

2/4
Description, Modicon X80 modules
references Modicon X80 backplanes
Accessories for single-rack configuration

Description
Dual Ethernet and X-bus backplanes
To be ordered separately:
A BMXXSPpp00 cable shielding connection kit, used to help protect against
1
electrostatic discharge when connecting the shielding on cordsets for connecting:
b Analog, counter, and motion control modules
b A Harmony HMI to the processor
The BMXXSPpp00 shielding system comprises:
9  A metal bar that takes the clamping rings and the grounding terminal
10  Two sub-bases to be mounted on the rack 2
11  A grounding terminal (not included)
12  Not included in the shielding connection kit, the STBXSP30p0 clamping rings (sold
in lots of 10, cross-section 1.5…6 mm2/16...10 AWG or 5…11 mm2/10...7 AWG)
10 9 12 11 10

BMXXSPpp00 cable shielding connection kit

3
Accessories
Description For use with Reference Weight
kg/lb
Shielding connection kits
comprising:
BMpXBP0400 backplanes BMXXSP0400 0.280/
0.617 4
- 1 metal bar BMXXBP0600 backplane BMXXSP0600 0.310/
- 2 support sub-bases 0.683
BMpXBP0800 backplanes BMXXSP0800 0.340/
BMEXBP0602 backplane 0.750
BMpXBP1200 backplanes BMXXSP1200 0.400/

Spring clamping rings


BMEXBP1002 backplane
Cables, cross-section STBXSP3010
0.882
0.050/ 5
Sold in lots of 10 1.5...6 mm2/16...10 AWG 0.110
(1) Cables, cross-section STBXSP3020 0.070/
5...11 mm2/10...7 AWG 0.154
STBXSP3000 + STBXSP30p0 Protective covers Unoccupied slots on BMXXEM010 0.005/
(replacement parts) BMpXBPpppp backplanes 0.011
Sold in lots of 5

(1) The grounding terminal is not included in the shielding connection kits.
6

10

2/5
Presentation, Modicon X80 modules
description Modicon X80 backplanes
Multi-rack configuration

Main rack
5 Composition of a multi-rack configuration
Multi-rack configurations are composed of one main rack, including a processor, and
1 expansion racks, which number depends on the CPU performance level:
b 1 expansion rack maximum for a station with a BMXP341000 processor
b 3 expansion racks maximum for a station with a BMXP3420ppp
b 3 expansion racks maximum for a station with a BMEP581020 or BMEP5820p0
processor
b 7 expansion racks maximum for a station with a BMEP5830p0, BMEP5840p0,
1 2 Modicon M340 3 BMEP585040, or BMEP586040 processor
2 4 Each rack is equipped with:
1  A BMpXBPpppp backplane (1)
2  A BMXCPSppp0 power supply or two BMXCPSppp2 redundant power supplies
(2)
3  A BMXXBE1000 rack expansion module. This module, inserted in the right-hand
end of the rack (XBE slot, see page 2/2) does not occupy backplane slots 00…11
(4, 6, 8, or 12 slots are still available).
3 Expansion rack 4  A BMXXBCpp0K X-bus extension cordset to connect the BMXXBE1000 rack
expansion modules
1 2 5 5  A TSXTLYEX line terminator on the unused 9-way SUB-D connector 6 or 7
Station with Modicon M340 in main rack + expansion rack
Configuration with X-bus racks
In a multi-rack configuration, the racks distributed on the X-bus include any of

4 Main rack 5 BMpXBPpppp backplanes. The racks are connected in a daisy chain using
BMXXBCpp0K (3) X-bus extension cordsets 4, connected at both ends to the
BMXXBE1000 rack expansion modules 3, via the 9-way SUB-D connectors 6 or
7.
The maximum total length between the main rack and last rack of the daisy chain
cannot exceed 30 m/98.42 ft.
Line terminators
5
3
Modicon M580
4 Both expansion modules at the ends of the daisy chain must have a line terminator
1 2 5 TSXTLYEX on the unused 9-way SUB-D connector.
Note: The processor is always positioned in the rack at address 0. In an X-bus daisy chain, the
order of the racks has no effect on operation. For example, the order of the daisy chain can be
Expansion rack 0-1-2-3, 2-0-3-1, or 3-1-2-0, etc.

Configuration with Ethernet racks


6 Dual Ethernet and X-bus backplanes support Ethernet ring or star architectures from
Modicon M580 CPUs Ethernet port:
1 2 5 b Modicon M580 BMEp58pp2p CPUs support Ethernet star or ring architectures
Station with Modicon M580 in main rack + expansion rack (RSTP loop is supported on ports 2 and 3). The embedded scanner allows
scanning of distributed equipment. The CPU directly drives these devices (“NOC”
embedded function).

7
b Modicon M580 BMEp58pp4p CPUs support an embedded scanner that allows
5 scanning of Modicon X80 drops on Ethernet RIO (EIO) and distributed equipment.
BMXXBE1000_main_image

PF108138_B_M

Modicon M580 CPUs have an additional third Ethernet port dedicated to the
6
connection of a service tool such as a PC, HMI, or network analyzer. This port,
labeled “ETH 1”, does not support RSTP.
7

Modicon M580 CPUs can communicate on the main Ethernet rack. They cannot be
8
BMXXBE1000 Rack TSXTLYEX line terminator
expansion module featuring installed in an expansion rack.
two 9-way SUB-D connectors It is necessary to use one of the following Ethernet backplanes:

Reference Description
BMEXBP0400 Standard 4-slot backplane
BMEXBP0800 Standard 8-slot backplane

9 BMEXBP1200
BMEXBP0602
Standard 12-slot backplane
Dual power supply 6-slot backplane
BMEXBP1002 Dual power supply 10-slot backplane

10

Compatibility: I/O modules: Communication modules: Modules for severe environments:


page 1/10 page 4/2 page 8/2 page 9/2

2/6
Presentation, Modicon X80 modules
description Modicon X80 backplanes
Multi-rack configuration

Combined configuration
An expansion rack can be connected to the main rack and the Modicon X80 drop
Modicon PLC Configurator
(EIO).
The rack address is assigned as follows:
1
b Each rack will be assigned a physical address using 4 microswitches located in
the bus extender module.
b The main rack containing the CPU will be assigned address 0.
b The other racks will be assigned addresses 1 to 7.
Click on the pictogram to access

2
Modicon PLC Configurator on line Each rack is equipped with:
1  A BMpXBPpp00 backplane (1)
2  A BMXCPSppp0 power supply or two BMXCPSppp2 redundant power supplies
(2)
Local rack 3  A BMXXBE1000 rack expansion module. This module, inserted in the right-hand
end of the rack (XBE slot) does not occupy backplane slots 00…11 (4, 6, 8, or 12
slots are still available).
4  A BMXXBCpppK X-bus cordset to connect to each other the expansion modules
5  Line terminators: Both expansion modules at the ends of the daisy chain must
have a line terminator 5 TSXTLYEX on the unused 9-way SUB-D connector.
3

Main rack 5

4
Modicon X80 1 2 3 4
Remote I/O drop

5
Expansion rack
1 2 5
Modicon M580 local rack + Modicon X80 remote drop +
expansion rack

(1) BMEXBPpppp are only supported on M580 processor based platforms.


6
(2) BMXCPSppp2 redundant power supplies are only compatible with the BMEXBPpp02 dual
power supply backplanes.
(3) BMXXBCpp0K extension cordsets, length 0.8 m/2.62 ft, 1.5 m/4.92 ft, 3 m/9.84 ft,
5 m/16.4 ft, or 12 m/39.4 ft, with angled connectors or TSXCBYp08K extension cordsets,
length 1 m/3.28 ft, 3 m/9.84 ft, 5 m/16.4 ft, 12 m/39.4 ft, 18 m/59 ft, or 28 m/92 ft, with straight

7
connectors.

10

Compatibility: I/O modules: Communication modules: Modules for severe environments:


page 1
 /10 page 4/2 page 8
 /2 page 9
 /2

2/7
Presentation, Modicon X80 modules
description Modicon X80 backplanes
Multi-rack configuration

Quantum Ethernet I/O migration


Modicon M580 Modicon M580
Modicon M580 CPUs level 4 and above (BMEP584040, BMEP585040, and
1
(Primary PLC) (Standby PLC)
BMEP586040) support Quantum I/O using the Quantum Ethernet remote drop
adapter 140CRA31200. The number of Remote I/O drops allowed (up to 31)
depends on the M580 processor model.
Ethernet The Quantum Ethernet drop is configured using EcoStruxure Control Expert (1)
software. Each Quantum I/O can be configured with the X80 I/O model (Device DDT)
Fiber optic or the Quantum model (“State ram” :%I, %IW, %M, %MW) to simplify the reuse of
legacy applications.
2
Quantum rack
The compatibilities of Quantum I/O in an Ethernet Quantum drop are identical in a
Quantum processor based architecture. See page 1/10 for more information.
In addition, the Modicon LL984 legacy language is supported by some CPU models;
please refer to the Modicon M580 product catalog for more information.

Quantum Ethernet I/O migration

3 Premium X-bus extension


Modicon M580 Modicon X80 expansion rack The Modicon M580 CPU supports revamping of an existing Premium installation by
replacing the Premium rack 0 (CPU and communication modules) with an M580
rack.
It is also possible to combine Premium racks TSXRKY4EX/6EX/8EX/12EX with
X-bus Modicon X80 I/O based on an X-bus rack. The majority of existing configurations are

4 Premium rack Premium rack supported.


The number of expanded racks allowed depends on which CPU is being used:
b The BMEP581020, BMEP582020, and BMEP582040 CPUs support a main local
rack and up to 3 expansion racks. If you are using 4, 6, or 8-slot Premium
Premium X-bus expansion example
expansion racks, you can install 2 physical racks at each assigned rack address,
allowing up to 6 Premium expansion racks (up to 6 backplanes and 100 m/328 ft
between 2 drops).
5 b The BMEP583020, BMEP583040, BMEP584020, and BMEP584040 CPUs
support a main local rack with up to 7 expansion racks. If you are using 4, 6, or
8-slot Premium expansion racks, you can install 2 physical racks at each assigned
rack address, allowing up to 14 Premium expansion racks.
The maximum number of supported X-bus drops is as follows:
b 4 for BMEP581ppp/2ppp
b 8 for BMEP583ppp/4ppp/5ppp/6ppp
6 The maximum number of X-bus drops is calculated as follows:
b Max number = 1 for CPU rack (BMXXBPpp00 or BMEXBPpp00)
+ ½ the number of TSXRKY4/6/8EX racks
+ the number of TSXRKY12EX racks
+ the number of BMXXBPpp00 racks

7 DIA6ED2151012EN

Description of the rack expansion module


The front panel of the BMXXBE1000 rack expansion module comprises:
5  A screw for locking the module in its slot (at the far right-hand end of the rack)
5 6  A display block with 5 LEDs:
BMXXBE1000_main_image

- RUN LED (green): Module running


8 6 - COL LED (red): Several racks have the same address, or rack address 0
does not contain any BMXP34ppp0 or BMXP58p0pp0 processor
- LEDs 0, 1, 2, and 3 (green): rack address 0, 1, 2, or 3
7
7  A 9-way female SUB-D connector, marked X-bus, for the incoming X-bus cordset
3 connected to the upstream rack, or if it is the first rack, for the A/ line terminator
included in the TSXTLYEX 4 pack
8  A 9-way female SUB-D connector, marked X-bus, for the outgoing X-bus cordset
9 8
3 to the downstream rack, or if it is the last rack, for the /B line terminator included
in the TSXTLYEX 4 pack
On the right-hand side panel
A flap for accessing the 3 rack addressing microswitches: 0…3
Installation rules for BMpXBPpppp racks
Rules for installing racks in enclosures (see our website).
4
10
PF108138

(1) EcoStruxure Control Expert software continues the Unity Pro range of software and
corresponds to versions u 14 of Unity Pro.

Compatibility: I/O modules: Communication modules: Modules for severe environments:


page 1/10 page 4/2 page 8/2 page 9/2

2/8
References Modicon X80 modules
Modicon X80 backplanes
Accessories for multi-rack configuration

Rack expansion
Description Use Reference Weight
1
BMXXBE1000_main_image

kg/lb
Modicon X80 I/O Standard module for mounting in each BMXXBE1000 0.178/
rack expansion module rack 0.392
(XBE slot) and used to interconnect:
- Up to 1 expansion rack with
BMXP341000 processor
- Up to 3 expansion racks with
BMXP342pppp processor
- Up to 3 expansion racks with
BMEP581020/20pp processor 2
- Up to 7expansion racks with
BMEP5830pp/40pp/50pp/60pp
processor
BMXXBE1000 - 1 rack with X80 drop (EIO)

Modicon X80 I/O Complete kit for 2-rack configuration BMXXBE2005 0.700/
rack expansion kit comprising:
- 2 BMXXBE1000 rack expansion
1.543
3
modules
BMXXBE2005_main_image

- 1 BMXXBC008K extension cordset,


length 0.8 m/2.62 ft
- 1 TSXTLYEX line terminator (set of 2)

Cordsets and connection accessories


4
Description Use Composition Type of Length Reference Weight
connector m/ft kg/lb
BMXXBE2005
X-bus Between 2 2 x 9-way Angled 0.8/ BMXXBC008K 0.165/
expansion BMXXBE1000 SUB-D 2.62 0.363
cordsets rack expansion connector
total length
30 m/98 ft
modules
1.5/ BMXXBC015K 0.250/ 5
PF108142_M

max (1). 4.92 0.551


3/ BMXXBC030K 0.420/
9.84 0.926
5/ BMXXBC050K 0.650/
16.4 1.433

6
12/ BMXXBC120K 1.440/
BMXXBCpppK
39.4 3.175

Description Use Composition Sold in Reference Weight


lots of kg/lb
Line Required on 2 x 9-way SUB-D 2 TSXTLYEX 0.050/
terminators both connectors marked A/ and /B 0.110
BMXXBPppp0
modules
located at either
end of the daisy
7
chain
PF108138_B_M

(1) Module and cordsets do not operate properly at temperatures lower than -25 °C/-13 °F.
TSXTLYEX

10

Compatibility: I/O modules: Communication modules: Modules for severe environments:


page 1
 /10 page 4/2 page 8
 /2 page 9
 /2

2/9
Contents 3 - Power supplies

Modicon X80 power supplies


b Presentation, description...................................................................... page 3/2
b Functions, references............................................................................ page 3/3 1

10

3/1
Presentation, Modicon X80 modules
description Modicon X80 Power supplies

Presentation
BMXCPSpppp power supplies provide the power supply for each BMEXBPpp00 or
1 BMXXBPpp00 Modicon X80 backplanes and the modules installed on it
(BMEXBPpp02 supports BMXCPSppp2 power supplies only).
The Modicon X80 power supplies offer comprises:
Modicon PLC Configurator
b Five power supplies for DC line supplies:
v 24 V c, 17 W isolated power supply, BMXCPS2010
v 24...48 V c, 32 W isolated power supply, BMXCPS3020

2 Click on the pictogram to access Modicon PLC


v 24...48 V c, 40 W redundant power supply, BMXCPS4022
v 125 V c, 36 W power supply, BMXCPS3540T (extended operating temperature
Configurator on line and calculate which power
-25 to +70 °C/-13 to +158 °F)
supply fits better to the power consumption v 125 V c, 40 W redundant power supply, BMXCPS3522
b Three power supplies for AC line supplies:
v 100...240 V a, 20 W power supply, BMXCPS2000
v 100...240 V a, 36 W power supply, BMXCPS3500

3
v 100...240 V a, 40 W redundant power supply, BMXCPS4002

Description
The power supply is selected according to:
b The electrical line supply: 24 V c, 48 V c, 125 V c, or 100...240 V a
b The required power (calculate the power consumption by the Modicon PLC
Configurator tool) (1)
BMXCPS2000_image

4 1 BMXCPSpppp power supplies have the following on the front panel:


1 A display block comprising:
- OK LED (green), lit if rack voltages are present and correct
- 24 V LED (green), lit when the sensor voltage is present (BMXCPS2000/
BMXCPS3500/BMXCPS3540T power supply modules only)
- RD LED (green), lit when all the internal power supply modules are functioning

5 2
normally (BMXCPS4002/BMXCPS4022/BMXCPS3522 redundant power
supply modules only)
3 - ACT LED (green), lit when the power supply is the primary power supply, off
when it acts as a secundary supply in redundant application
(BMXCPS4002/BMXCPS4022/BMXCPS3522 redundant power supply
4 modules only)
BMXCPS2000 2 A pencil-point RESET pushbutton for a cold restart of the application

6 3 A 2-way connector that can take a removable terminal block (caged or spring-
type) for connecting the alarm relay
4 A 5-way connector that can take a removable terminal block (caged or spring-
type) for connecting the following:
BMXCPS4002_main_image

- c or a line supply
1 - Protective ground
- Dedicated 24 V c power supply for the input sensors (for BMXCPS2000/

7 BMXCPS3500/BMXCPS3540T power supply modules only)


Included with each power supply module:
b Set of two BMXXTSCPS10 caged removable terminal blocks (5-way and 2-way)
To be ordered separately (if necessary):
2 b Set of two BMXXTSCPS20 spring-type removable terminal blocks (5-way and
2-way)

8
3
Compatibility of the power supply with the backplane
The redundant AC power supply can be used alone in a single power supply
backplane or as a pair in a dual power supply backplane. For high-availability
4 applications, two independent redundant power supplies can be used to increase
BMXCPS4002
the availability of power supply. In case the primary power supply fails to provide the
total current, the secundary power supply will change to primary mode and continue

9
to function.
Type Standalone power supply Redundant power supply
(BMXCPSppp0) (BMXCPSppp2)
Single power supply backplanes
(BMXXBPpp00, BMEXBPpp00)
Dual power supply backplanes
(BMEXBPpp02)

10 Compatible
Incompatible
(1) This power consumption calculation for the backplane can also be performed by EcoStruxure
Control Expert V14 (Unity Pro in earlier versions) programming software.
Compatibility: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 4/2 page 8
 /2 page 9
 /2

3/2
Functions, Modicon X80 modules
references Modicon X80 Power supplies

Functions
Alarm relay
The alarm relay incorporated in each power supply has a volt-free contact accessible on the front panel, on the 1
BMXCPS2010_image

2-way connector.
The operating principle is as follows:
In normal operation, with the PLC in RUN, the alarm relay is energized and its contact is closed (state 1).
The relay de-energizes and its associated contact opens (state 0) whenever the application stops, even partially,
due to any of the following:
b Detection of a blocking fault
b Incorrect rack output voltages
b Loss of supply voltage
2
RESET pushbutton
BMXCPS2010/3020
The power supply in each backplane has a RESET button on the front panel which, when pressed, triggers an
initialization sequence on the processor and the modules in the rack it supplies.
Pressing this pushbutton triggers a sequence of service signals, which is the same as that for:
b A power break, when the pushbutton is pressed
3
BMXCPS3500_image

b A power-up, when the pushbutton is released


b In terms of the application, these operations represent a cold start (forcing the I/O modules to state 0 and
initializing the processor).

Sensor power supply


BMXCPS2000/3500 AC power supplies and BMXCPS3540T DC power supplies have an integrated 24 V c
supply for powering the input sensors.
Connection to this 24 V c sensor power supply is via the 5-way connector on the front panel. The available power
4
depends on the power supply (0.45 A or 0.9 A).
BMXCPS2000/3500
References
Each BMEXBPpp00 or BMXXBPpp00 rack must be equipped with a power supply. BMEXBPpp02 must be
BMXCPS4002_main_image

equipped with 1 or 2 redundant power supplies. These power supplies are inserted in the leftmost power supply
slots of each rack (marked CPS).
The power required to supply each backplane depends on the type and number of modules installed in the
5
backplane. It is therefore necessary to draw up a power consumption table for each backplane in order to
determine which BMXCPSpppp power supply is the most suitable for each backplane (please use the Modicon
PLC Configurator tool).

X80 Power supplies (1)


Line supply Available power (2)
3.3 V c (3) 24 V c 24 V c Total
Nominal current
24 V c rack
Reference Weight

kg/lb
6
(3) sensors (4) (3)
BMXCPS4002 24 V c 8.3 W 17 W – 17 W 0.7 A BMXCPS2010 0.290/
isolated 0.639
BMXCPS4022_main_image

24...48 V c 15 W 32 W – 32 W 1.3 A BMXCPS3020 0.340/


isolated 0.750
24...48 V c 18 W 40 W – 40 W 1.67 A BMXCPS4022 0.810/

100...150 V c 15 W 31.2 W 21.6 W 36 W (5) 1.3 A BMXCPS3540T (5)


1.786
0.340/
7
0.750
18 W 40 W – 40 W 1.67 A BMXCPS3522 0.610/
1.345
100...240 V a 8.3 W 16.8 W 10.8 W 20 W 0.7 A BMXCPS2000 0.300/
0.661

8
15 W 31.2 W 21.6 W 36 W 1.3 A BMXCPS3500 0.360/
0.794
BMXCPS4022 18 W 40 W – 40 W 1.67 A BMXCPS4002 0.360/
0.794
Separate parts
BMXCPS3522_main_image

Description Type Composition Reference Weight


kg/lb
Set of 2 removable Spring-type One 5-way terminal block and BMXXTSCPS20 0.015/
connectors
Caged
one 2-way terminal block
One 5-way terminal block and BMXXTSCPS10
0.033
0.020/
9
one 2-way terminal block 0.044
(1) Include a set of 2 caged removable connectors. Spring-type connectors available separately under reference BMXXTSCPS20.
(2) The sum of the power consumed on each voltage (3.3 V c and 24 V c) must not exceed the total power of the module.
Calculate the power consumption with the Modicon PLC Configurator tool or with EcoStruxure Control Expert: see the power
supply and I/O budget available in the Power supply properties in EcoStruxure Control Expert.

BMXCPS3522
(3) 3.3 V c and 24 V c rack voltages for powering modules in the Modicon X80 I/O rack.
(4) 24 V c sensor voltage for powering the input sensors (voltage available via the 2-way removable connector on the front panel).
(5) Extended operating temperature -25 to +70 °C/-13 to +158 °F (with power derating at extreme temperatures: 27 W between
10
-25 and 0 °C/-13 and 0 °F and between 60 and 70 °C/140 and 158 °F).

Compatibility: I/O modules: Communication modules: Modules for severe environments:


page 1
 /10 page 4/2 page 8
 /2 page 9
 /2

3/3
Contents 4 - I/O modules

Modicon X80 Discrete I/O modules


Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4/2

b Presentation, description...................................................................... page 4/8


1
b Functions................................................................................................ page 4/9
b Connection devices.............................................................................. page 4/10
b Complementary characteristics.......................................................... page 4/12
b References............................................................................................ page 4/13 2
Modicon X80 Analog I/O modules
Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4/16

b Presentation.......................................................................................... page 4/20


b Description............................................................................................ page 4/21 3
b Connections, combinations ................................................................ page 4/22
b Complementary characteristics.......................................................... page 4/23
b References............................................................................................ page 4/24

Modicon X80 HART analog I/O modules


Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4/26
4
b Presentation, description.................................................................... page 4/28
b References............................................................................................ page 4/29

10

4/1
Selection guide Modicon X80 modules
Modicon X80 I/O modules
Discrete input modules

Applications 8-channel discrete input modules 16-channel discrete input modules

1 1

2 2

3 3
Type a c a or c a

Voltage 200…240 V 100...120 V 24 V 48 V 125 V 24 V (a or c) 48 V 100…120 V 200…240 V

Current per channel 10.4 mA 5 mA 3.5 mA 2.5 mA 2.4 mA 3 mA (a) 5 mA 10.1 mA (max) at 50 Hz 9.7 mA (max) at 50 Hz
(for U = 220 V at 50 Hz) 3.9 mA (c) 11.9 mA (max) at 60 Hz 11.5 mA (max) at 60 Hz

Modularity 8 inputs and 1 common 8 isolated inputs 16 inputs and 1 common 16 isolated inputs

4 4
(Number of channels and commons)
Connection Via BMXFTB20p0 Via BMXFTB40p0
20-way caged, screw clamp, or spring-type removable terminal block 40-way caged or spring-type removable terminal block
Inputs IEC/EN 61131-2 conformity Type 2 Type 3 Type 1 Non-type Type 1 (a) Type 3 Type 1 Non-type at 50 Hz Type 1
Non-type (c) Type 1 at 60 Hz
Logic – Positive (sink) Positive (sink) / Negative –
(source) (c)

5 Type of input Capacitive Current sink Resistive Capacitive


5
Sensor compatibility 2-wire a 2-wire c, 3-wire c PNP any type – 2-wire c/a, 2-wire a
IEC/EN 60947-5-2 3-wire c PNP/NPN
any type
Sensor power supply 170…264 V a 85...132 V a 19…30 V c 38…60 V c 88…150 V a 20…26 V a 40…52 V a 85…132 V a 100...120 V a 200...240 V a
(ripple included) (no sensor power 19...30 V c
monitoring)

6 Protection of inputs Use one 0.5 A fast-blow


fuse per group of
Use one 0.25 A fast-blow Use one 0.5 A fast-blow fuse per group of channels
fuse per channel
Use one 0.25 A fast-blow fuse per channel 6
channels
Maximum dissipated power 4.73 W 2.35 W 2.5 W 3.6 W 8.5 W 3W 4W 3.8 W 4.3 W
(at 40 °C/104 °F)
Operating temperature 0…60 °C/32…140 °F -25...70 °C/-13...158 °F 0…60 °C/32…140 °F
Dimension WxHxD 32 x 100 x 86 mm/1.25 x 3.93 x 3.38 in. 32 x 131 x 86 mm/1.25 x 5.15 x 3.38 in.

7 Compatibility with TeSys Quickfit installation system – 7


Compatibility with Passive connection –
Modicon ABE7 Telefast sub-bases
pre-wired system (1)
Adapter sub-bases with –
relays
References
BMXDAI0805 BMXDAI0814 BMXDDI1602 BMXDDI1603 BMXDDI1604T BMXDAI1602 BMXDAI1603 BMXDAI1604 BMXDAI1614 BMXDAI16142 BMXDAI1615
8 Page 4/13 8
(1) For more information, please refer to the “Telefast Pre-wired system -- Modicon ABE7 IP20 connection sub-bases” catalog or visit our website.

9 9

10 10

More technical Information on www.se.com More technical Information on www.se.com

4/2 4/2
4/3
Selection guide (continued) Modicon X80 modules
Modicon X80 I/O modules
Discrete input and mixed I/O modules

Applications 32-channel high-density 32-channel discrete input modules 64-channel high-density discrete 16-channel discrete mixed I/O modules 32-channel high-density discrete
discrete input module input module mixed I/O module

1 1

2 2

3 3
Type c c inputs and c/a relay outputs c

Voltage 24 V 12/24 V 48 V 24 V Inputs: 24 V Inputs: 24 V c Inputs: 24 V


Solid-state outputs: 24 V Relay outputs: 24 V c or 24…240 V a Solid-state outputs: 24 V
Current per channel Inputs 2.5 mA 3.3 mA 2.3 mA 0.6 mA 3.5 mA 3.5 mA 2.5 mA
Outputs – 0.5 A 2 A (c or a) 0.1 A
Modularity 32 inputs and 2 commons 64 inputs and 4 commons 8 inputs and 1 common, 16 inputs and 1 common,

4 4
(Number of channels and commons) 8 outputs and 1 common 16 outputs and 1 common
Connection Via one 40-way connector with Via BMXFTB40p0 Via two 40-way connectors with Via BMXFTB20p0 Via one 40-way connector with
preassembled cordsets 40-way caged or spring-type removable terminal block preassembled cordsets 20-way caged, screw clamp, or spring-type removable terminal block preassembled cordsets
Inputs IEC/EN 61131-2 conformity Type 1 Type 3 Non-type Type 3 Type 1
Logic Positive (sink) Positive (sink) / Negative (source) Positive (sink)
Type of input Current sink Current sink/source Current sink
Sensor compatibility IEC/EN 2-wire c, 3-wire c PNP any type 2-wire c, 3-wire c PNP/NPN any type 2-wire c, 3-wire c PNP any type – 2-wire c, 3-wire c PNP any type
5 Sensor power supply
60947-5-2
19…30 V c 10.8...30 V c 38...60 V c 19…30 V c
5
(ripple included)
Protection of inputs Use one 0.5 A fast-blow fuse per group of channels
Outputs Fallback – Configurable output fallback, continuous monitoring of output control, and resetting of outputs in case of internal detected fault
IEC/EN 61131-2 conformity – Yes

6 Protection
Logic


Protected
Positive
Not protected

Protected
Positive 6
Preactuator power supply – 19…30 V c 19...30 V c 19…30 V c
(ripple included) 24...240 V a
Output fuse protection – Use one 6.3 A fast-blow fuse per group Use one 12 A fast-blow fuse per group of Use one 2 A fast-blow fuse per group of
of channels channels channels
Maximum dissipated 3.9 W 4.7 W 6W 4.3 W 3.7 W 3.1 W 4W

7 power
Operating temperature 0…60 °C/32…140 °F 7
Dimension WxHxD 32 x 100 x 86 mm/1.25 x 3.93 x 3.38 in. 32 x 131 x 86 mm/1.25 x 5.15 x 3.38 in. 32 x 100 x 86 mm/1.25 x 3.93 x 3.38 in.
Compatibility with TeSys Quickfit installation system LU9G02 splitter boxes (8 motor starters) – LU9G02 splitter boxes (8 motor starters) – LU9G02 splitter boxes (8 motor starters)
and BMXFCCpp3 preassembled and BMXFCCpp3 preassembled and BMXFCCpp3 preassembled
cordsets (see pages 4/11 and 4/13) cordsets (see pages 4/11 and 4/13) cordsets (see pages 4/11 and 4/13)

8 Compatibility with
Modicon ABE7 Telefast
Passive connection sub-bases

Adapter sub-bases with relays


Depending on model (2)

Depending on model (3)



Depending on model (2)

Depending on model (3)


8
pre-wired system (1)

References BMXDDI3202K BMXDDI3232 BMXDDI3203 BMXDDI6402K BMXDDM16022 BMXDDM16025 BMXDDM3202K


Pages 4/13 4/8
(1) For more information, please refer to the “Telefast Pre-wired system -- Modicon ABE7 IP20 connection sub-bases” catalog or visit our website.

9 (2) 8- or 16-channel passive sub-bases, with or without LED, with common or 2 terminals per channel
(3) Active sub-bases with solid state or electromagnetic relays (fixed or removable), 16 channels, with common or 2 terminals per channel (caged or spring-type connection) 9

10 10

More technical Information on www.se.com More technical Information on www.se.com

4/3
4/4 4/3
4/5
Selection guide (continued) Modicon X80 modules
Modicon X80 I/O modules
Discrete output modules

Applications 16-channel discrete output modules 32-channel discrete 32-channel high- 64-channel high- 8-channel relay output modules 16-channel relay output
output module density discrete output density output module module

1 1
module

2 2

3 Type

Voltage
c transistor

24 V
a triac

100…240 V 24...240 V
c transistor

12...24 V 24 V
c relay

100…150 V
c/a relay

24…125 V c 24 V c
3
24…240 V a 24…240 V a
Current per channel 0.5 A 0.6 A 3A 0.5 A 0.1 A 0.3 A (Ith) 3 A (Ith) 4 A (Ith) 2 A (Ith)

Modularity 16 outputs and 16 outputs and 16 isolated outputs 32 outputs and 64 outputs and 8 normally open isolated relay outputs 8 normally open and 16 normally open relay
(Number of channels and commons) 1 common 4 commons 2 commons 4 commons normally close isolated outputs and
4 Connection Via BMXFTB20p0 Via BMXFTB40p0 Via one 40-way Via two 40-way Via BMXFTB20p0
relay outputs
Via BMXFTB40p0
2 commons
Via BMXFTB20p0
4
20-way caged, screw clamp, or spring-type removable terminal block 40-way caged or spring-type removable terminal connector with connectors with 20-way caged, screw clamp, or spring-type 40-way caged or 20-way caged, screw
block preassembled cordsets preassembled cordsets removable terminal block spring-type removable clamp, or spring-type
terminal block removable terminal block
Outputs Fallback Configurable output fallback, continuous monitoring Configurable output fallback Configurable output fallback, continuous monitoring of output control, and Configurable output fallback
of output control, and resetting of outputs in case of resetting of outputs in case of internal detected fault
internal detected fault
5 IEC/EN 61131-2 conformity Yes 5
Protection Yes – Yes –
Logic Positive (source) Negative (sink) – Positive (source) –
Preactuator power supply 19…30 V c 100…240 V a 24...240 V a 10.8...30 V c 19…30 V c 100…150 V c 5...150 V c 19...30 V c
(ripple included) 19...264 V a 24...240 V a
Output fuse protection Use one 6.3 A fast-blow fuse per group of channels Use one 3 A fast-blow Use one 4 A fast-blow Use one fast-blow fuse Use one 2 A fast-blow fuse per group of channels Use one 0.5 A fast-blow Use one fast-blow fuse per each channel Use one 12 A fast-blow

6 6
fuse per group of fuse per channel per group of channels fuse per each channel fuse per each group of
channels channels
Maximum dissipated power 4W 2.26 W – 4.8 W 3.6 W 6.85 W 3.17 W 5.76 W 6.84 W 3W
Operating temperature 0…60 °C/32…140 °F -25…70 °C/ 0…60 °C/32…140 °F
-13…158 °F
Dimension WxHxD 32 x 100 x 86 mm/1.25 x 3.93 x 3.38 in. 32 x 131 x 86 mm/1.25 x 5.15 x 3.38 in. 32 x 100 x 86 mm/1.25 x 3.93 x 3.38 in. 32 x 131 x 86 mm/ 32 x 100 x 86 mm/
1.25 x 5.15 x 3.38 in. 1.25 x 3.93 x 3.38 in.

7 7
Compatibility with TeSys Quickfit installation system – LU9G02 splitter boxes (8 motor starters) and –
BMXFCCpp3 preassembled cordsets (see pages
4/11 and 4/15)
Compatibility with Passive connection sub-bases – Depending on model (2) –
Modicon ABE7 Telefast Adapter sub-bases with relays – Depending on model (3) –
pre-wired system (1)
References BMXDDO1602 BMXDDO1612 BMXDAO1605 BMXDAO1615 BMXDDO3202 BMXDDO3202K BMXDDO6402K BMXDRA0804T BMXDRA0815 BMXDRC0805 BMXDRA1605

8 Page 4/14
(1) For more information, please refer to the “Telefast Pre-wired system -- Modicon ABE7 IP20 connection sub-bases” catalog or visit our website.
8
(2) 8- or 16-channel passive sub-bases, with or without LED, with common or 2 terminals per channel
(3) Active sub-bases with solid state or electromagnetic relays (fixed or removable), 16 channels, with common or 2 terminals per channel (caged or spring-type connection)

9 9

10 10

More technical Information on www.se.com More technical Information on www.se.com

4/4
4/6 4/4
4/7
Presentation, Modicon X80 modules
description Modicon X80 I/O modules
Discrete I/O modules

Presentation
Discrete I/O modules in the Modicon X80 offer are standard modules occupying a
1 single slot on the rack. These modules are equipped with one of the following:
b A connector for a 20-way caged, screw clamp, or spring-type removable terminal
block
b A connector for a 40-way caged or spring-type removable terminal block
b One or two 40-way connectors
This wide range of discrete I/O can be used to meet whatever requirements arise in

2 terms of:
b Functions: AC or DC I/O, positive or negative logic
b Modularity: 8, 16, 32, or 64 channels per module
The inputs receive signals from the sensors and perform the following functions:
b Acquisition
b Adaptation
b Electrical isolation

3 b Filtering
b Protection against interference signals
The outputs memorize commands issued by the processor to enable control of the
preactuators via the decoupling and amplification circuits.

Description
4 BMXDpI/DpO/DRA discrete I/O modules are standard format (1 slot). They have an
IP20 case to help protect the electronics, and are locked into position with a captive
screw.
I/O modules connected via 20-way removable terminal block
1
1  Rigid body providing support and protection for the electronic card
2
2  Module reference marking (a label is also visible on the right-hand side of the

5 3 module)
3  Channel status display block
4 4  Connector taking the 20-way removable terminal block for connection of sensors
or preactuators
5 To be ordered separately:
5  BMXFTB20p0 20-way removable terminal block (identification label supplied
with each I/O module) or a preassembled cordset with a 20-way removable
6 Module for connection via 20-way removable
terminal block
terminal block at one end and flying leads at the other (see page 4/15).

1 I/O modules connected via 40-way removable terminal block


2 1  Rigid body providing support and protection for the electronic card
3 2  Module reference marking (a label is also visible on the right-hand side of the
module)

7 4
3  Channel status display block
4  Connector taking the 40-way removable terminal block for connection of
sensors or preactuators

5 To be ordered separately:
5  BMXFTB40p0 40-way removable terminal block (identification label supplied
with each I/O module) or a preassembled cordset with a 40-way removable
terminal block at one end and flying leads at the other (see page 4/15)
8 Module for connection via 40-way removable
terminal block
I/O modules connected via 40-way connector(s)
1  Rigid body providing support and protection for the electronic card
2  Module reference marking (a label is also visible on the right-hand side of the
1
5 module)
2
3  Channel status display block
9 3 4  One or two 40-way connectors (32 or 64 channels) (1) for connection of sensors
or preactuators
5  With the 64-channel module, a pushbutton which, with successive presses,
displays the state of channels 0...31 or 32...63 on the display block 3
4 (see page 4/9)
To be ordered separately, depending on the type of module:

10 One or two preassembled cordset(s) with a 40-way connector (see page 4/15)

32- and 64-channel modules for connection


via one or two 40-way connector(s) (1) Fujitsu FCN 40-way connector
Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1/10 page 2/2 page 3/2 page 8/2 page 9/2

4/8
Functions Modicon X80 modules
Modicon X80 I/O modules
Discrete I/O modules

Functions (1)
The discrete I/O modules provide the following functions:
b Hot swapping: Due to their special integrated devices, I/O modules (including 1
application-specific modules) can be removed or added while the power is on.
b I/O assignment: The channels of discrete I/O modules are grouped into blocks
of 4, 8, or 16 consecutive channels depending on the type of module. Each group
of channels can be assigned to a specific application task, namely master or fast.
b Protection of DC inputs: The 24 V c and 48 V c inputs are constant-current
type. This characteristic limits the current consumed at the inputs. 2
b Protection of DC outputs: Active transistor outputs can withstand overloads,
short-circuits, reverse polarity, and inductive over-voltage.
b Reactivation of DC outputs: If a line fault has caused an output to trip, the
output can be reactivated using this parameter if no other terminal line fault is
present. Reactivation is controlled by means of a group of 8 channels. It can be
programmed or automatic. 3
b RUN/STOP command: An input can be configured to control the RUN/STOP
changeover for the PLC.
b Output fallback: This parameter defines the fallback mode used by the DC
transistor outputs when the PLC stops. It can assume the “fallback” value at state
0 or state 1 for the corresponding group of 8 channels or the “maintain” value
representing the state of the outputs before the PLC stops.
4
Display block for module b I/O module diagnostics: Each discrete I/O module is equipped with a display
BMXDDO3202K block on the front panel centralizing the information necessary for module
control, diagnostics, and maintenance.
v Diagnostics via EcoStruxure Control Expert (2): Using the integrated

5
diagnostics in EcoStruxure Control Expert (2), local diagnostics screens are
available at global hardware configuration level, module level, and channel level.
v Remote diagnostics using a Web browser on a «Thin Client» PC: In addition,
the diagnostics described above can be performed remotely using a simple Web
browser thanks to the standard Web server integrated in the Modicon X80
modules (processor with integrated Ethernet port or Ethernet module), using the
“ready-to-use” Rack Viewer function.
b Compatibility with 2-wire and 3-wire sensors: The discrete input modules can
be used in conjunction with OsiSense XS inductive proximity sensors and with
6
OsiSense XU photoelectric sensors (3).

(1) For further information, please consult our website.


(2) EcoStruxure Control Expert software continues the Unity Pro range of software and
corresponds to versions u 14 of Unity Pro.
7
(3) For further information, please consult Telemecanique Sensors website.

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8/2 page 9
 /2

4/9
Connections Modicon X80 modules
Modicon X80 I/O modules
Connection devices for discrete I/O modules

Connecting modules with 20-way removable terminal blocks


There are three types of 20-way removable terminal block:
1 b Screw clamp terminal block
b Caged terminal block
b Spring-type terminal block
Each removable terminal block can take:
b Bare wires
b Wires equipped with DZ5CE/AZ5DE cable ends

2 One version of the removable terminal block is equipped with 3, 5, or 10 m /4.92, 9.84,
or 16.4 ft cordsets with color-coded flying leads (BMXFTWpp1).

DIA3ED2160602EN
Caged terminal blocks

3 The capacity of each terminal is:


b Minimum: One 0.34 mm2 wire (AWG 22)
Caged Screw clamp Spring-type b Maximum: One 1 mm2 wire (AWG 18)
terminal block terminal block terminal block
BMXFTB2000 caged connectors are equipped with captive screws (maximum
tightening torque 0.5 N.m/0.37 lb-ft).

4 Screw clamp terminal blocks


The capacity of each terminal is:
b Minimum: One or two 0.34 mm2 wires (AWG 22)
b Maximum: Two 1.5 mm2 wires (AWG 16)
BMXFTB2010 screw clamp connectors are equipped with captive screws
(maximum tightening torque 0.5 N.m/0.37 lb-ft).
Terminal block with flying-lead
5 Spring-type terminal blocks
The capacity of each terminal in the BMXFTB2020 spring-type terminal blocks is:
Example of I/O module
with 20 pins b Minimum: One 0.34 mm2 wire (AWG 22)
b Maximum: One 1 mm2 wire (AWG 18)
Accessories for connecting 20-pin modules

6
Connecting modules with 40-way removable terminal blocks
There are two types of 40-way removable terminal block:
b Caged terminal block
b Spring-type terminal block
Caged terminal block Spring-type terminal block

7 Each removable terminal block can take:


b Bare wires
b Wires equipped with DZ5CE/DZ5CA cable ends
One version of the removable terminal block is equipped with 3 or 5 m /4.92 or 9.84 ft
cordsets with color-coded flying leads (BMXFTWpp5).

8
Caged terminal blocks
The capacity of each terminal is:
b Minimum: One 0.34 mm2 wire (AWG 22)
Terminal block with flying-lead
b Maximum: One 1 mm2 wire (AWG 18)
BMXFTB4000 caged connectors are equipped with captive screws (maximum
tightening torque 0.4 N.m/0.30 lb-ft).

9 Example of I/O module


with 40 pins
Spring-type terminal blocks
The capacity of each terminal in the BMXFTB4020 spring-type terminal blocks is:
Accessories for connecting 40-pin modules b Minimum: One 0.34 mm2 wire (AWG 22)
b Maximum: One 1 mm2 wire (AWG 18)

10

4/10
Connections (continued) Modicon X80 modules
Modicon X80 I/O modules
Connection devices for discrete I/O modules

Connecting modules with 40-way connectors


Preassembled cordsets with 40-way connector at one end and flying leads at

1 2 3 4
the other
Preassembled cordsets can be used for easy direct wire-to-wire connection
1
between the I/O of modules with 40-way connectors 1 and the sensors,
preactuators, or intermediate terminal blocks.
These preassembled cordsets comprise:
b At one end, a 40-way connector 2 with two sheaths 3, each containing 20 wires
with a cross-section of 0.34 mm2 (AWG 22) (BMXFCWpp3)
b At the other end, color-coded flying leads 4 conforming to standard DIN47100 2
Preassembled cordset with 40-way
connector and two ends with flying leads

3
Preassembled cordsets with 40-way connector and HE 10 connector(s)
1 2 3 5 Two types of cordset can be used for connecting the I/O of modules 1 with 40‑way
connectors to Modicon ABE7 rapid wiring connection and adaptation interfaces (1).
These preassembled cordsets comprise:
b At one end, a 40-way connector 2 with two sheaths 3 each containing 20 wires
(BMXFCCpp3) 4
b At the other end, two HE 10 connectors 5

5
Preassembled cordset with 40-way connectors and HE10
connectors for Modicon ABE7 Telefast system

1 7 6
Connection to TeSys Quickfit system 6
BMXDDI3202K/6402K input modules, BMXDDO3202K/6402K output modules, and
BMXDDM3202K mixed I/O modules with 40-way connectors are designed,
amongst other things, for use in conjunction with the TeSys Quickfit mounting
system via the LU9G02 splitter module 6 (for 8 motor starters).
The splitter modules are easily connected using 7 BMXFCCpp3 preassembled
cordsets.

(1) For more information, please refer to the “ABE7 / ABE9 Telefast Pre-wired system» catalog
7
or visit our website.
Example of connection to the TeSys Quickfit
installation system

10

4/11
Characteristics Modicon X80 modules
Modicon X80 I/O modules
Discrete I/O modules

Complementary characteristics
The following characteristics complement those introduced in the selection guide on
1 pages 4/2 to 4/7.

DC input modules BMXDDI16pp/1604T/3202K/3232/3203/6402K and


BMXDAI1602
b Input impedance at nominal voltage: 6.4 to 19.2 kΩ, depending on model
b Reverse polarity: Protection for modules BMXDDI1602/1603/3202K/3203

2 b
b
Paralleling of inputs (1): Yes, for modules BMXDDI1602/1603/3232/3203
Dielectric strength between groups of channels: 500 V c for modules
BXDDI3202K/3203/3232/6402K
b Temperature derating for module BMXDDI1604T: No derating up to 40 °C/104 °F,
a maximum of 25% of inputs at state 1 at 70 °C/158 °F

AC input modules BMXDAI 08pp/16pp

3 b Input frequency: 47 to 63 Hz
b Current peak on activation at nominal voltage: 5 to 380 mA depending on model
b Input impedance at nominal voltage and F = 55 Hz: 6 to 28 kΩ, depending on
model

Triac output module BMXDAO1605


b Current via common: 2.4 A
4 b Current for the 4 commons together: 4.8 A

Isolated triac output module BMXDAO1615


b Current per module: 10 A maximum continuous

DC transistor output modules BMXDDO16pp/3202/3202K/6402K

5 b Dielectric strength between groups of channels: 500 V c for modules


BMXDDO3202K/6402K

Relay output modules BMXDRA08ppp/1605 and BMXDRC0805


b Protection against AC inductive overvoltage: Use an RC circuit or ZNO surge
limiter appropriate to the voltage in parallel on each output.
b Protection against DC inductive overvoltage: Use a discharge diode on each
6 output.

Mixed I/O relay module BMXDDM16025


b Input impedance at nominal voltage: 6.8 kΩ
b Dielectric strength between groups of inputs: 500 V c

DC mixed I/O modules BMXDDM16022/3202K


7 b Input impedance at nominal voltage: 6.8 to 9.6 kΩ, depending on model
b Reverse polarity on the inputs: Protection
b Paralleling of outputs: Yes, for a maximum of 2 outputs for module BMXDDM16022
and a maximum of 3 outputs for module BMXDDM3202K

8
(1) For further information, please consult our website.

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1/10 page 2/2 page 3/2 page 8/2 page 9/2

4/12
References Modicon X80 modules
Modicon X80 I/O modules
Discrete input modules

References
Modicon X80 Discrete input modules
Type Input voltage Connection via
(1)
IEC/EN 61131-2
conformity
No. of channels
(common x channels
Reference Weight 1
per group) kg/lb
c 24 V 20-way caged, screw clamp, or Type 3 16 inputs BMXDDI1602 0.115/
(positive logic) spring-type removable terminal (1 x 16)
BMXDDI1602_main_image

0.254
block
One 40-way connector Type 1 32 inputs BMXDDI3202K 0.110/

Two 40-way connectors Non-type


(2 x 16)
64 inputs BMXDDI6402K (1)
0.243
0.145/
2
(4 x 16) 0.320
24 V 20-way caged, screw clamp, or Non-type 16 inputs BMXDAI1602 0.115/
(positive/ spring-type removable terminal (1 x 16) 0.254
negative logic) block
BMXDDI160pp 12/24 V 40-way caged or spring-type Type 3 32 inputs BMXDDI3232 0.137/
BMXDAI08ppp/160p
3
(positive/ removable terminal block (2 x 16) 0.302
negative logic)
48 V 20-way caged, screw clamp, or Type 1 16 inputs BMXDDI1603 0.115/
BMXDDI3202K_main_image

(positive logic) spring-type removable terminal (1 x 16) 0.254


block
40-way caged or spring-type Type 3 32 inputs BMXDDI3203 0.137/
removable terminal block (2 x 16) 0.302
125 V 20-way caged, screw clamp, or Non-type 16 inputs BMXDDI1604T 0.144/
(positive logic) spring-type removable terminal
block
(1 x 16) 0.317
4
a 24 V 20-way caged, screw clamp, or Type 1 16 inputs BMXDAI1602 0.115/
spring-type removable terminal (1 x 16) 0.254
BMXDDI3202K
block

48 V 20-way caged, screw clamp, or Type 3 16 inputs BMXDAI1603 0.115/


BMXDDI6402K_main_image

spring-type removable terminal (1 x 16) 0.254

100…120 V
block
20-way caged, screw clamp, or Type 3 8 isolated inputs BMXDAI0814 0.115/
5
spring-type removable terminal (8 x 1) 0.254
block
20-way caged, screw clamp, or Type 3 16 inputs BMXDAI1604 0.115/
spring-type removable terminal (1 x 16) 0.254
block
BMXDDI6402K 40-way caged or spring-type
removable terminal block
Type 1 16 isolated inputs BMXDAI1614 0.157/
0.346 6
40-way caged or spring-type Non-type at 50 Hz 16 isolated inputs BMXDAI16142 (2) 0.157/
removable terminal block Type 1 at 60 Hz 0.346
BMXDAI16142 _main_image

200…240 V 20-way caged, screw clamp, or Type 2 8 inputs BMXDAI0805 0.120/


spring-type removable terminal (1 x 8) 0.265
block

7
40-way caged or spring-type Type 1 16 isolated inputs BMXDAI1615 0.157/
removable terminal block 0.346

BMXDAI161p
BMXDAI16142
(1) 64-channel modules have 2 connectors and therefore require 2 connection cables.
(2) BMXDAI16142 is optimized for 60Hz application, e.g. Quantum modules, while BMXDAI1614 is compatible for both 50Hz and
60 Hz.
8

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8
 /2 page 9/2

4/13
References (continued) Modicon X80 modules
Modicon X80 I/O modules
Discrete output and mixed I/O modules

References
Modicon X80 Discrete output modules
1 Type Output voltage Connection via
(1)
IEC/EN 61131-2 No. of channels
conformity (common x channels
Reference Weight

per group) kg/lb


c 24 V 20-way caged, screw Yes 16 outputs BMXDDO1602 0.120/
BMXDDO1602_main_image

transistor (positive logic) clamp, or spring-type (1 x 16) 0.265


removable terminal block
24 V 20-way caged, screw Yes 16 outputs BMXDDO1612 0.120/
2 (negative logic) clamp, or spring-type
removable terminal block
(1 x 16) 0.265

12...24 V 40-way caged or Yes 32 outputs BMXDDO3202 0.142/


(positive logic) spring-type removable (2 x 16) 0.313
BMXDDO16p2/BMXDAO1605
terminal block
BMXDRApppp
24 V One 40-way connector Yes 32 outputs BMXDDO3202K 0.110/
(positive logic) (2 x 16) 0.243
BMXDDO6402K_main_image
BMXDDO3202K_main_image

3 Two 40-way connectors Yes 64 outputs BMXDDO6402K (1) 0.150/


(4 x 16) 0.331

a triac 100…240 V 20-way caged, screw Yes 16 outputs BMXDAO1605 0.140/


clamp, or spring-type (4 x 4) 0.309
removable terminal block

4
BMXDDO3202K BMXDDO6402K
24…240 V 40-way caged or Yes 16 isolated BMXDAO1615 0.250/
spring-type removable outputs 0.551
terminal block
c relay 100…150 V c 20-way caged, screw Yes 8 normally open BMXDRA0804T 0.178/
clamp, or spring-type isolated relay outputs 0.392
removable terminal block

5
c/a 24...125 V c 20-way caged, screw Yes 8 normally open BMXDRA0815 0.210/
BMXDAO1615_main_image
BMXDRC0805_main_image

relay 24...240 V a clamp, or spring-type isolated relay outputs 0.463


removable terminal block
24 V c 20-way caged, screw Yes 16 normally open BMXDRA1605 0.150/
24…240 V a clamp, or spring-type relay outputs 0.331
removable terminal block (2 x 8)
5...125 V c 40-way caged or Yes 8 normally open and BMXDRC0805 0.189/

6
24…240 V a spring-type removable normally closed 0.417
BMXDDO3202 BMXDAO1615
BMXDRC0805 terminal block isolated relay outputs

Modicon X80 Discrete mixed I/O modules


Type Voltage Connection via IEC/EN 61131-2 No. of channels Reference Weight

7 conformity (common x channels


per group) kg/lb
Inputs Outputs Inputs Outputs Inputs Outputs
c 24 V c 24 V c 20-way caged, screw Type 3 Yes 8 (1 x 8) 8 (1 x 8) BMXDDM16022 0.115/
BMXDDM16022_main_image
BMXDDM3202K_main_image

transistor (positive logic) clamp, or spring-type 0.254


removable terminal block
c/a 24 V c 24…240 V 20-way caged, screw Type 3 Yes 8 (1 x 8) 8 (1 x 8) BMXDDM16025 0.135/

8 relay a
(positive logic)
clamp, or spring-type
removable terminal block
0.298

c 24 V c 24 V c One 40‑way connector Type 1 Yes 16 (1 x 16) 16 (1 x 16) BMXDDM3202K 0.110/


transistor (positive logic) 0.243
BMXDDM3202K BMXDDM1602p

9
(1) 64-channel modules have 2 connectors and therefore require 2 connection cables.

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8
 /2 page 9/2

4/14
References (continued) Modicon X80 modules
Modicon X80 I/O modules
Accessories for discrete I/O modules

References (continued)
Removable terminal blocks
Description For use with Type Reference Weight
kg/lb
1
20-way removable terminal For module with 20-way removable terminal Caged BMXFTB2000 0.093/
blocks block 0.205
BMXFTB2000_main_image

Screw clamp BMXFTB2010 0.075/


0.165
Spring BMXFTB2020 0.060/

40-way removable terminal For module with 40-way removable terminal block Caged
blocks
BMXFTB4000
0.132
0.166/
0.366
2
Spring BMXFTB4020 0.098/
0.216
Preassembled cordsets for 16- and 32-channel I/O modules with removable terminal block
Description Composition Cross- Length Reference Weight
section m/ft kg/lb
Preassembled cordsets
with one end with flying
One 20-way spring-type removable 0.324 mm2/ 3/9.84
terminal block (BMXFTB2020) and AWG 22
BMXFTW301 0.850/
1.874
3
leads one end with color-coded flying 5/16.4 BMXFTW501 1.400/
PF106144_M38

leads 3.086
10/32.8 BMXFTW1001 2.780/
6.129
One 40-way spring-type removable 0.324 mm2/ 3/9.84 BMXFTW305 0.940/

4
terminal block (BMXFTB4020) and AWG 22 2.072
BMXFTWp01
one end with color-coded flying 5/16.4 BMXFTW505 1.460/
leads 3.218

Preassembled cordsets for 16-, 32-, and 64-channel I/O modules with 40-way connectors
Description No. of Composition Cross- Length Reference Weight
sheaths section m/ft kg/lb
Preassembled cordsets 1 x 20 One 40-way 0.324 mm2/ 3/9.84 BMXFCW301 0.820/
5
PF106145_M38

with one end with flying wires (16 connector and AWG 22 1.808
leads channels) one end with color- 5/16.4 BMXFCW501 1.370/
coded flying leads 3.020
10/32.8 BMXFCW1001 2.770/
BMXFCWp01 6.107
2 x 20 One 40-way 0.324 mm2/ 3/9.84 BMXFCW303 0.900/
wires (32 connector and 1.984
PF106177_M38

AWG 22
channels) two ends with color- 5/16.4 BMXFCW503 1.490/
(1) coded flying leads
10/32.8 BMXFCW1003
3.285
2.960/
6
BMXFCWp03 6.526
Preassembled cordsets for 2 x 20 One 40-way connector 0.324 mm2/ 0.5/1.64 BMXFCC053 0.210/
BMXFCC_cable_FCN-2HE_image

Modicon ABE7 sub-bases wires (32 and two HE 10 connectors AWG 22 0.463
channels) 1/3.28 BMXFCC103 0.350/
(1) 0.772
2/6.56 BMXFCC203 0.630/

BMXFCCp03 3/9.84 BMXFCC303


1.389
0.940/
7
2.072
5/16.4 BMXFCC503 1.530/
3.373
10/32.8 BMXFCC1003 3.000/
6.614

(1) 64-channel modules have 2 connectors and therefore require 2 connection cables.
8

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8/2 page 9
 /2

4/15
Selection guide Modicon X80 modules
Modicon X80 I/O modules
Analog input modules

Applications Analog inputs

1 1

2 2

3 3
Type of input Isolated low-level inputs, voltage, thermocouples, temperature probes, resistors Isolated high-level inputs Non-isolated high-level inputs Isolated high-level inputs

Type Multirange Voltage/current

Range Voltage ± 40 mV, ± 80 mV, ± 160 mV, ± 320 mV, ± 640 mV, ± 1.28 V ± 10 V, 0…10 V, 0...5 V, 1..5 V, ± 5 V

Current – 0...20 mA, 4…20 mA, ± 20 mA

Thermocouple Thermocouples, type B, E, J, K, L, N, R, S, T, U –

4 Temperature probe 2-, 3- or 4-wire temperature probes, type Pt100, JPt100, Pt1000, JPt1000, Ni100, Ni1000
(in accordance with DIN43760), and Cu 10
– 4
Resistor 2-, 3- or 4-wire resistors, 400 Ω or 4000 Ω –

Modularity 4 inputs 8 inputs 4 inputs 8 inputs

Acquisition period 400 ms for the 4 inputs 400 ms for the 8 inputs Fast: 1 + (1 x no. of declared channels) ms Fast: 1 + (1 x no. of declared channels) ms
Default: 5 ms for the 4 channels Default: 9 ms for the 8 channels
5 Conversion time – 5
Resolution 15 bits + sign 16 bits

Dimension WxHxD 32 x 100 x 86 mm/1.25 x 3.93 x 3.38 in.

Isolation Between channels 750 V c 300 V c

6 Between channels and bus 1400 V c 6


Between channels and ground 750 V c 1400 V c

Connection Directly to the module Via one 40-way connector Via two 40-way connectors Via BMXFTB20p0 20-way caged, screw clamp, or Via BMXFTB28p0 28-way caged or spring-type removable terminal block
spring-type removable terminal block
Via preassembled cordsets BMXFCWp01S cordsets with one end with color-coded flying leads BMXFTWp01S cordsets with one end with color-coded BMXFTWp08S cordsets with one end with color-coded flying leads
(3 or 5 m/9.84 or 16.4 ft) flying leads (3 or 5 m/9.84 or 16.4 ft) (3 or 5 m/9.84 or 16.4 ft)

7 Compatibility with
Modicon ABE7 Telefast
Connection sub-base 4-channel sub-base for direct connection of 4 thermocouples plus connection and provision of
cold junction compensation
4-channel sub-base for direct connection of 4 inputs,
delivers and distributes 4 protected isolated power
8-channel sub-base for direct connection of 8 current/voltage inputs
7
pre-wired system (1) supplies
Type of connection sub-base ABE7CPA412 ABE7CPA410 ABE7CPA02/03/31/31E ABE7CPA02/31/31E

Type of preassembled cordsets BMXFCApp2 (1.5, 3, or 5 m/4.92, 9.84, or 16.4 ft) BMXFCApp0 (1.5, 3, or 5 m/4.92, 9.84, or 16.4 ft) BMXFTApp0 (1.5 or 3 m/4.92 or 9.84 ft)

References
BMXART0414 BMXART0814 BMXAMI0410 BMXAMI0800 BMXAMI0810
8 Page 4/24 8
(1) For more information, please refer to the “Telefast Pre-wired system -- Modicon ABE7 IP20 connection sub-bases” catalog or visit our website.

9 9

10 10

More technical Information on www.se.com More technical Information on www.se.com

4/16 4/16
4/17
Selection guide Modicon X80 modules
Modicon X80 I/O modules
Analog output modules and mixed I/O modules

Applications Analog outputs Analog mixed I/O

1 1

2 2

3 3
Type of I/O Isolated high-level outputs Non-isolated high-level outputs Non-isolated high-level inputs and outputs

Type Voltage/current Current Voltage/current

Range Voltage ± 10 V – Inputs: ± 10 V, 0…10 V, 0...5 V, 1..5 V


Outputs: ± 10 V
Current 0–20 mA, 4–20 mA Inputs: 0–20 mA, 4–20 mA
Outputs: 0–20 mA, 4–20 mA

4 Modularity

Acquisition period (inputs)


2 outputs


4 outputs 8 outputs 4 inputs and 2 outputs

Fast: 1 + (1 x no. of declared channels) ms


4
Default: 5 ms for the 4 channels
Conversion time (outputs) ≤ 1 ms ≤ 4 ms ≤ 1 ms

Resolution Inputs – 14…12-bit in U range


12-bit in I range

5 Outputs 15 bits + sign 12-bit in U range


11-bit in I range 5
Dimension WxHxD 32 x 100 x 86 mm/1.25 x 3.93 x 3.38 in.

Isolation Between groups of input or – 750 V c


output channels
Between channels 750 V c –

6 6
Between channels and bus 1400 V c
Between channels and ground 1400 V c

Connection Directly to the module Via BMXFTB20p0 20-way caged, screw clamp, or spring-type removable terminal block

Via preassembled cordsets BMXFTWp01S cordsets with one end with color-coded flying leads (3 or 5 m/9.84 or 16.4 ft)

Compatibility with Connection sub-base 4-channel sub-base for direct connection of 2/4 current/voltage outputs 8-channel sub-base for direct connection of 8 current/voltage inputs –
Modicon ABE7 Telefast

7 pre-wired system (1) Type of connection sub-base

Type of preassembled cordsets


ABE7CPA21

BMXFCApp0 (1.5, 3, or 5 m/4.92, 9.84, or 16.4 ft)


ABE7CPA02

BMXFTApp2 (1.5 or 3 m/4.92 or 9.84 ft)



7
References
BMXAMO0210 BMXAMO0410 BMXAMO0802 BMXAMM0600
Page 4/22
(1) For more information, please refer to the “Telefast Pre-wired system -- Modicon ABE7 IP20 connection sub-bases” catalog or visit our website.

8 8

9 9

10 10

More technical Information on www.se.com More technical Information on www.se.com

4/17
4/18 4/17
4/19
Presentation Modicon X80 modules
Modicon X80 I/O modules
Analog I/O modules

Presentation
The Modicon X80 analog I/O modules offer comprises:
1 b 5 analog input modules:
v 2 modules with 4 and 8 isolated channels, low-level voltage, thermocouples, Pt,
JPt, Ni, or Cu temperature probes and resistors, 15 bits + sign
BMXART0414/0814
v 1 module with 4 high-speed isolated analog channels, high-level voltage or
current, 16 bits BMXAMI0410
v 2 modules with 8 high-speed non-isolated analog channels, high-level voltage or
2 current, 15 bits + sign BMXAMI0800/0810
b 3 analog output modules:
v 1 module with 2 isolated analog channels, high-level voltage or current, 15 bits +
sign BMXAMO0210
v 1 module with 4 isolated analog channels, high-level voltage or current, 15 bits +
sign BMXAMO0410
v 1 module with 8 non-isolated analog channels, high-level current, 15 bits + sign
3 BMXAMO0802
b 1
 analog mixed I/O module with 4 input channels and 2 output channels
(non‑isolated), voltage or current, 12 to 14 bits according to type of channel and
range BMXAMM0600
Analog I/O modules are equipped with a connector for a 20 or 28-way removable
terminal block, except for BMXART0414/0814 analog input modules for
4 Modicon PLC Configurator
thermocouples/temperature probes, which are equipped with one or two 40-way
connector(s).
All analog modules occupy a single slot in BMEXBPpppp or BMXXBPpppp racks.
These modules can be installed in any slot in the rack, except the first two (PS and
00), which are reserved for the power supply module and the processor module
respectively.

5
Click on the pictogram to access
Modicon PLC Configurator on line and The power supply for the analog functions is supplied by the backplane bus (3.3 V
design your installation and 24 V). Analog I/O modules are hot-swappable (see page 4/9).

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8
 /2 page 9
 /2

4/20
Description Modicon X80 modules
Modicon X80 I/O modules
Analog I/O modules

Description
BMXAMp/ART analog I/O modules are standard format (1 slot). They have a case,
which provides IP20 protection of the electronics, and are locked into position by a
captive screw.
1
1
I/O modules connected via 20 or 28-way removable terminal block
BMXAMp analog I/O modules feature the following:
2 1  A rigid body providing support and protection for the electronic card
2  A module reference marking (a label is also visible on the right-hand side of the
3 module)
3  A module and channel status display block
2
4  A connector taking the 20 or 28-way removable screw clamp or spring-type
terminal block for directly connecting the sensors or preactuators to the module
4 To be ordered separately (see page 4/25):
5  BMXFTB20p0 or BMXFTB28p0 20 or 28-way removable terminal block
(referencing label supplied with each I/O module) or pre-wired cables with:
5 - A 20-way terminal block at one end and flying leads at the other
(BMXFTWp01S)
3
- A 28-way terminal block at one end and flying leads at the other
Module for connection via 20 or 28-way
(BMXFTWp08S)
removable terminal block - A 20 or 28-way terminal block and a 25-way SUB-D connector (BMXFCApp0
or BMXFTApp0), for connection to Modicon ABE7 sub-bases

I/O modules connected via 40-way connector


BMXART analog input modules have the following on the front panel:
4
1 1  A rigid body providing support and protection for the electronic card
2  A module reference marking (a label is also visible on the right-hand side of the
2
module)
3 3  A module and channel status display block
4  One (or two) 40-way connector(s) for connecting the sensors
To be ordered separately (see page 4/25):
5  Pre-wired cables with:
5
- A 40-way connector at one end and flying leads at the other (BMXFCWp01S)
4 5
- A 40-way connector and a 25-way SUB-D connector (BMXFCApp2) for direct
connection to Modicon ABE7 sub-bases
To be ordered separately (see page 2/5):
b A BMXXSPpp00 shielding connection kit to help protect against electrostatic
discharge, consisting of a metal bar and two sub-bases for mounting on the rack 6
supporting the analog modules
Module for connection via 40-way connector b A set of STBXSP3020 clamping rings for the shielding braids of analog signal
cables

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3
 /2 page 8
 /2 page 9/2

4/21
Connections, Modicon X80 modules
combinations Modicon X80 I/O modules
Connection devices for analog I/O modules

Connecting modules with removable terminal blocks


BMXAMI0410, BMXAMO, and BMXAMM modules with 20-way terminal block
1 The 20-way removable terminal blocks (BMXFTB20p0) are the same as those
used for discrete I/O modules (screw clamp, caged, or spring-type) (see page
4/25).
1 One version of the removable terminal block is equipped with a 3 or 5 m/9.84 or
16.4 ft cordset with color-coded flying leads (BMXFTWp01S). These preassembled
cordsets with reinforced shielding have color-coded flying leads at the other end 1.

2 BMXAMI0800/0810 modules with 28-way terminal block


The 28-way removable terminal blocks are caged (BMXFTB2800) or spring-type
(BMXFTB2820).
One version of the removable terminal block is equipped with a 3 or 5 m/9.84 or
16.4 ft cordset with color-coded flying leads (BMXFTWp08S). These preassembled
cordsets with reinforced shielding have color-coded flying leads at the other end 1.

3 BMXFTWp01S cordset (with 20-way removable


terminal block at one end and flying leads at the
Connecting modules with 40-way connectors
other) BMXART0p14 modules with 40-way connectors
Two types of cordset are available:
b Preassembled cordsets with reinforced shielding (BMXFCWp01S) which
have color-coded flying leads at the other end 2. Available in 3 or 5 m/9.84 or

4 16.4 ft lengths, they enable easy direct wire-to-wire connection of the analog
sensors via terminal blocks.
b Preassembled cordsets with reinforced shielding (BMXFCAp02) which have a
25-way SUB-D connector at the other end 3. Available in 1.5, 3, or 5 m/4.92,
9.84, or 16.4 ft lengths, they enable direct connection to the Modicon
ABE7CPA412 sub-base (see below).

5 2
Use with Modicon ABE7
Using the Modicon ABE7 Telefast pre-wired system makes it easier to install
the modules since the inputs (or outputs) can be accessed via screw clamp
terminals. Seven special sub-bases are available:
Modicon ABE7CPA410 sub-base
6 The Modicon ABE7CPA410 sub-base is mainly used in conjunction with the
BMXAMI0410 voltage/current analog 4-input module. This sub-base allows you to:
b Directly connect 4 sensors
b Remotely locate the input terminals in voltage mode
b Power the 4 to 20 mA conditioning units one channel at a time with a 24 V
BMXFCWp01S cordset (with 40-way connector at one end and
flying leads at the other) voltage, protected and limited to 25 mA, while maintaining isolation between
channels
7 b Help protect the current impedance matching resistors integrated in the
sub-base against overvoltages
Connection is via the BMXFCApp0 cordset (1.5, 3, or 5 m/4.92, 9.84, or 16.4 ft).

Modicon ABE7CPA412 sub-base


The Modicon ABE7CPA412 sub-base is specially designed as a wiring interface for
the BMXART0414 and BMXART0814 thermocouple modules. This sub-base
8 allows you to:
b Connect 4 thermocouple probes
b Provide external cold junction compensation with a temperature probe
integrated in the sub-base
b Provide continuity of the shielding
The BMXART0814 module requires two Modicon ABE7CPA412 sub‑bases. The
3
connection with each sub-base is made via a BMXFCApp2 cordset (1.5, 3, or
9 5 m/4.92, 9.84, or 16.4 ft).
Modicon ABE7CPA21 sub-base
The Modicon ABE7CPA21 sub-base is compatible with the BMXAMO0210 output
module. This sub-base allows you to:
b Directly connect 2 current/voltage outputs
BMXFCApp2 cordset, BMXART0414 4-channel module, b Provide continuity of the shielding

10 and ABE7CPA412 sub-base Connection is via the BMXFCApp0 cordset 3 (1.5, 3, or 5 m/4.92, 9.84, or 16.4 ft).

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8
 /2 page 9
 /2

4/22
Combinations (continued), Modicon X80 modules
characteristics Modicon X80 I/O modules
Connection devices for analog I/O modules

Use with Modicon ABE7 (continued)


Modicon ABE7CPA02 sub-base
The Modicon ABE7CPA02 sub-base can be used in combination with:
b BMXAMI0800/0810 analog current input modules with 8 inputs
1
b BMXAMO0802 analog current output modules with 8 outputs
This sub-base allows you to:
b Connect the 8 analog inputs or outputs point-to-point
b Provide continuity of the shielding
BMXAMI0800/0810 modules are connected via BMXFTApp0 1.5 or 3 m/4.92 or
9.84 ft cables.
The BMXAMO0802 module is connected via BMXFTApp2 1.5, 3, or 5 m/4.92, 9.84,
2
or 16.4 ft cables.

Modicon ABE7CPA03 sub-base


DIA3ED2160602EN
The Modicon ABE7CPA03 sub-base can be used in combination with the
BMXAMI0800 voltage/current analog 8-input module.
This sub-base allows you to: 3
b Directly connect 8 analog inputs
b Power the current inputs one channel at a time with a voltage of 24 V that is
protected and limited to 25 mA
b Provide continuity of the shielding
The BMXAMI0800 module is connected via BMXFTApp0 1.5 or 3 m/4.92 or 9.84 ft
cables.
4
Modicon ABE7CPA31/31E sub-bases
The Modicon ABE7CPA31/31E sub-bases can be used in combination with the
BMXAMI0800/0810 voltage/current analog 8-input modules.
These sub-bases allow you to:
b Directly connect 8 analog inputs
b Power the current inputs one channel at a time with 24 V converters
b Provide continuity of the shielding 5
BMXAMI0800/0810 modules are connected via BMXFTApp0 1.5 or 3 m/4.92 or
9.84 ft cables.

Complementary characteristics
BMXART0414/0814 analog input modules
BMXART0414/0814 modules are multirange input modules with 4 or 8 low-level 6
isolated inputs (15 bits + sign) respectively.
Depending on the choice made during configuration, the modules offer, for each of
the inputs, the following ranges:
b Temperature probe: Pt100, JPt100, Pt1000, JPt1000, Cu10, Ni100, or Ni1000 (in
accordance with DIN43760), with open-circuit detection

7
b Thermocouple: B, E, J, K, L, N, R, S, T, or U with broken wire detection
b Resistor: 0…400 or 0…4000 W, 2-, 3-, or 4-wire
b Voltage: ± 40 mV, ± 80 mV, ± 160 mV, ± 320 mV, ± 640 mV, ± 1.28 V

BMXAMI0410 analog input module


The BMXAMI0410 module is a high-level analog input module with 4 isolated inputs
(16 bits).
Used with sensors or transmitters, it performs monitoring, measurement, and
process control functions for continuous processes. 8
The module offers the following ranges for each of the inputs depending on the
choice made during configuration:
b Voltage ± 10 V, ± 5 V, 0…10 V, 0…5 V, and 1…5 V
b Current 0 – 20 mA, 4– 20 mA, and ± 20 mA

BMXAMI0800/0810 analog input modules


BMXAMI0800/0810 analog input modules have 8 high-level isolated/non-isolated
9
analog inputs (15 bits + sign).
The modules offer the following ranges for each of the inputs depending on the
choice made during configuration:
b Voltage: ± 10 V, 0…10 V, 0…5 V, 1…5 V, ± 5 V
b Current: 0 – 20 mA and 4– 20 mA
10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1/10 page 2/2 page 3/2 page 8/2 page 9/2

4/23
Characteristics (continued), Modicon X80 modules
references Modicon X80 I/O modules
Analog input, output, and mixed module

Complementary characteristics (continued)


BMXAMO0210 analog output module
1 The BMXAMO0210 module has 2 high-level isolated outputs (15 bits + sign).
The BMXAMO0210 module offers the following ranges for each of the inputs depending on the choice made
during configuration:
b Voltage: ± 10 V
b Current: 0 – 20 mA and 4– 20 mA
BMXAMO0410/0802 analog output modules
2 BMXAMO0410/0802 analog output modules have 4 or 8 high-level isolated/non-isolated analog outputs (16
bits/15 bits + sign).
The BMXAMO0410 module offers the following ranges for each of the outputs depending on the choice made
during configuration:
b Voltage: ± 10 V
b Current: 0 – 20 mA and 4– 20 mA
The BMXAMO0802 module offers the current ranges 0 – 20 mA and 4– 20 mA.
3 BMXAMM0600 analog mixed I/O module
The BMXAMM0600 mixed module is a non-isolated I/O module with 4 inputs (14/12 bits) and 2 outputs (12 bits).
The module offers the following ranges for each of the inputs or outputs depending on the choice made during
configuration:
b Voltage: ± 10 V, 0…10 V, 0…5 V, and 1…5 V
b Current: 0 – 20 mA and 4– 20 mA
4
References
X80 Analog input modules (1)
Type of input Input signal range Resolution Connection via No. of Reference Weight
channels kg/lb
Isolated high-level ± 10 V, 0…10 V, 16 bits 20-way caged, screw 4 channels BMXAMI0410 0.143/
BMXAMI0410_main_image

5
inputs 0…5 V, 1…5 V, ± 5 V, 0 – 20 clamp, or spring-type 0.315
mA, removable terminal block
4– 20 mA, ± 20 mA

Non-isolated ± 10 V, 0…10 V, 0…5 V, 15 bits 28-way caged or 8 channels BMXAMI0800 0.175/


high-level inputs 1…5 V, + sign spring-type removable 0.386
± 5 V, 0 – 20 mA terminal block

6 BMXAMI0pp0 Isolated high-level ± 10 V, 0…10 V, 0…5 V,


inputs 1…5 V,
15 bits + sign 28-way caged or
spring-type removable
8 channels BMXAMI0810 0.175/
0.386
± 5 V, 0 – 20 mA terminal block
BMXART0414_main_image

Isolated low-level Temperature probe, 15 bits + sign 40-way connector 4 channels BMXART0414 0.135/
inputs thermocouple, 0.298
± 40 mV, ± 80 mV, 8 channels BMXART0814 0.165/
± 160 mV, ± 320 mV,
7
0.364
± 640 mV, ± 1.28 V

BMXART0414
X80 Analog output modules (1)
Type of outputs Output signal range Resolution Connection via No. of Reference Weight
channels kg/lb
BMXAMO0210_main_image

Isolated high-level ± 10 V, 16 bits 20-way caged, screw 2 channels BMXAMO0210 0.144/

8
outputs 0 – 20 mA, clamp, or spring-type 0.317
4– 20 mA removable terminal block
High-level outputs ± 10 V, 15 bits 20-way caged, screw 4 channels BMXAMO0410 0.175/
isolated 0 – 20 mA, + sign clamp, or spring-type 0.386
4– 20 mA removable terminal block
Non-isolated 0 – 20 mA, 15 bits 20-way caged, screw 8 channels BMXAMO0802 0.175/
high-level inputs 4– 20 mA + sign clamp, or spring-type 0.386
removable terminal block

9
BMXAMO0210
X80 Analog mixed I/O module (1)
Type of I/O Signal range Resolution Connection via No. of Reference Weight
BMXAMM0600_main_image

channels kg/lb
Mixed I/O, ± 10 V, 0…10 V, 14 bits or 20-way caged, screw Inputs: BMXAMM0600 0.155/
non-isolated 0…5 V, 1…5 V, 12 bits clamp, or spring-type 4 channels 0.342
0 – 20 mA, depending removable terminal block Outputs:
4– 20 mA on the range 2 channels
10 (1) Calculate the power consumption by using the Modicon PLC configurator online tool.

BMXAMM0600
Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8
 /2 page 9
 /2

4/24
References (continued) Modicon X80 modules
Modicon X80 I/O modules
Accessories for analog I/O modules

References (continued)
Connection accessories for analog modules (1)
Description For use with
modules
Type, composition Length Reference Weight
kg/lb
1
20-way removable BMXAMI0410 Caged – BMXFTB2000 0.093/
BMXFTB2020_main_image

terminal block BMXAMO0210 0.205


BMXAMO0410 BMXFTB2010
Screw clamp – 0.075/
BMXAMO0802
0.165
BMXAMM0600
Spring – BMXFTB2020 0.060/

BMXFTB20p0 28-way removable BMXAMI0800 Caged – BMXFTB2800


0.132
0.111/
2
terminal block BMXAMI0810 0.245
Spring – BMXFTB2820 0.080/
0.176
Preassembled BMXAMI0410 One 20-way terminal block 3 m/9.84 ft BMXFTW301S 0.470/
cordset BMXAMO0210 (BMXFTB2020) and one end with 1.036
BMXAMO0410
BMXAMO0802
color-coded flying leads 5 m/16.4 ft BMXFTW501S 0.700/
3
PF106144

1.543
BMXAMM0600
BMXAMI0800 One 28-way removable terminal 3 m/9.84 ft BMXFTW308S 0.435/
BMXFTWp01S BMXAMI0810 block (BMXFTB2820) and one end 0.959
with color-coded flying leads 5 m/16.4 ft BMXFTW508S 0.750/
1.653
BMXFCW301S
4
BMXART0414 One 40-way connector and one end 3 m/9.84 ft 0.480/
BMXART0814 with color-coded flying leads 1.058
5 m/16.4 ft BMXFCW501S 0.710/
1.565
Modicon ABE7 Telefast pre-wired system
Description For use with Type, composition Length or Reference Weight
modules connection kg/lb
technology
Modicon ABE7
sub-base
BMXAMI0410 Distribution of isolated power
supplies. Delivers 4 protected
Screws ABE7CPA410 0.180/
0.397
5
PF514132

isolated power supplies for 4 –20 mA


inputs. Direct connection of 4 inputs
BMXART0414 Connection and provision of Screws ABE7CPA412 0.180/
BMXART0814 (2) cold-junction compensation for 0.397
thermocouples
Direct connection of 4 inputs
ABE7CPA41p/21 BMXAMO0210
BMXAMO0410
Direct connection of 2/4 outputs Screws ABE7CPA21 0.210/
0.463
6
BMXAMI0800 Point-to-point connection of 8 I/O Screws ABE7CPA02 0.317/
BMXAMI0810 0.699
BMXAMO0802
BMXAMI0800 Direct connection of 8 inputs. Delivers Screws ABE7CPA03 0.307/
8x 24 V c power supplies limited to 0.677

BMXAMI0800
25 mA to the 8 current inputs
Direct connection of 8 inputs Screws ABE7CPA31 0.498/ 7
BMXAMI0810 Delivers 8x 24 V c power supplies 1.098
isolated and limited to 25 mA to the ABE7CPA31E
Spring 0.508/
8 current inputs
1.120
Preassembled BMXAMI0410 One 20-way removable terminal 1.5 m/4.92 ft BMXFCA150 0.320/
cordsets for BMXAMO0210 block and one 25-way SUB-D 0.705

8
Modicon ABE7 BMXAMO0410 connector for ABE7CPA410/CPA21 3 m/9.84 ft BMXFCA300 0.500/
sub-bases sub-base 1.102
5 m/16.4 ft BMXFCA500 0.730/
PF106175

1.609
BMXART0414 One 40-way connector and one 1.5 m/4.92 ft BMXFCA152 0.330/
BMXART0814 (2) 25-way SUB-D connector for 0.728
BMXFCApp0 ABE7CPA412 sub-base 3 m/9.84 ft BMXFCA302 0.510/
1.124
5 m/16.4 ft BMXFCA502 0.740/
1.631
9
BMXAMI0800 One 28-way removable terminal 1.5 m/4.92 ft BMXFTA150 0.374/
BMXAMI0810 block and one 25-way SUB-D 0.825
connector for sub-bases 3 m/9.84 ft BMXFTA300 0.500/
ABE7CPA02/03/31/31E 1.102
PF106176

BMXAMO0802 One 20-way removable terminal 1.5 m/4.92 ft BMXFTA152 0.374/

BMXFCApp2
block and one 25-way SUB-D
connector for ABE7CPA02 3 m/9.84 ft BMXFTA302
0.825
0.500/
10
sub-bases 1.102
(1) The shielding on the cordsets carrying the analog signals must always be connected to the BMXXSPpp00 shielding
connection kit mounted under the rack holding the analog modules (see page 2/5).
(2) The BMXART0814 8-channel module requires two ABE7CPA412 sub-bases and two BMXFCApp2 cordsets.

4/25
Selection guide Modicon X80 modules
Modicon X80 I/O modules
HART analog I/O modules

Applications HART analog inputs HART analog outputs

1 1

2 2

Type of I/O Isolated analog inputs with HART Isolated analog outputs with HART

3 Number of channels 8 4 3
Range Current 4-20 mA

Maximum load impedance – 600 Ω (0-20 mA)

Operating temperature 0…60°C/32…140°F

4 Dimensions WxHxD 32 x 100 x 86 mm/1.25 x 3.93 x 3.38 in. 4


Compatible devices BMEP58pppp processors BMEP58pppp processors
BMECRA31210 drop modules BMECRA31210 drop modules
BMEXBPpp00(H) Ethernet + X-bus backplanes BMEXBPpp00(H) Ethernet + X-bus backplanes
140NOC78000 Quantum Ethernet DIO module 140NOC78000 Quantum Ethernet DIO module
Resolution 15 bits + sign

5 Isolation Between channels 1000 V c for 1 minute 5


Between channels and bus 1400 V c for 1 minute

Between channels and ground 1400 V c for 1 minute

Connection Directly to the module Via BMXFTB20p0

6 6
20-way caged, screw clamp, or spring-type removable terminal block
Compatibility with Connection sub-base 8-channel sub-base for direct connection of 8 current/voltage inputs 4-channel sub-base for direct connection of 2/4 current/voltage outputs
Modicon ABE7 Telefast
pre-wired system Type of connection sub-base ABE7CPA02, ABE7CPA03, ABE7CPA31 ABE7CPA21

Type of preassembled cordsets BMXFTA1522, BMXFTA3022 (1,5 or 3 m/4.92 or 9.84 ft) BMXFCA150, BMXFCA300, BMXFCA500 (1,5, 3, or 5 m/4.92, 9.84, or 16.4 ft)

Field device support 2-wire/4-wire


7 HART specification HART field device compliance HART V5, V6, V7 7
HART field device connection Point-to-point

HART I/O mapping Yes

References
BMEAHI0812 BMEAHO0412
8 Page 4/29 8

9 9

10 10

More technical Information on www.se.com More technical Information on www.se.com

4/26 4/26
4/27
Presentation, Modicon X80 modules
description Modicon X80 I/O modules
HART analog I/O modules

1 Presentation
BMEAHO0412_main_image

BMEAHp0p12 HART analog I/O modules contain transceivers that control HART
1
2
3 devices and information through the module. They can be managed by the AMS
(Asset Management System) or by the automation platform CPU.
BMXFTB2020_main_image These modules require an Ethernet + X-bus backplane and can only be installed in
the main local rack with the CPU or in RIO drops with a Modicon X80 Performance
Remote I/O drop adapter BMECRA31210. They cannot be installed in expansion
racks.
4
2
5 Description
BMEAHp0p12 HART analog I/O modules are standard format (1 slot). They have a
Module for connection via 20-way removable case, which provides IP20 protection of the electronics, and are locked into position
terminal block by a captive screw. They are connected via a 20-way removable terminal block.
BMEAHp0p12 HART analog I/O modules feature the following:
3 1  A rigid body providing support and protection for the electronic card
2  A module reference marking (a label is also visible on the right-hand side of the
module)
3  A module and channel status display block
4  A connector taking the 20-way removable screw clamp or spring-type terminal
block for directly connecting the sensors or preactuators to the module

4 To be ordered separately (see page 4/25):


5  A BMXFTB20p0 20-way removable terminal block
(referencing label supplied with each I/O module) or pre-wired cables with:
- A 20-way terminal block at one end and flying leads at the other
(BMXFTWp01S)
- A 20-way terminal block and a 25-way SUB-D connector (BMXFCApp0 or
BMXFTApp22), for connection to Modicon ABE 7 sub-bases

5 Connecting modules using 20-way removable terminal blocks


DIA6ED2151012EN
The 20-way removable terminal blocks (BMXFTB20p0) are the same as those
used for discrete I/O modules (screw clamp, caged or spring-type) (see page 4/25).
One version of the removable terminal block is equipped with a 3 or 5 m/9.84 or
16.4 ft cordset with color-coded flying leads (BMXFTWp01S). These preassembled

6 cordsets with reinforced shielding have color-coded flying leads at the other end.

BMXFTWp01S Use with Modicon ABE7 sub-bases


Modicon ABE7CPA21 sub-base
The Modicon ABE7CPA21 sub-base is compatible with the BMEAHO0412

7
output module.
This sub-base allows you to:
b Directly connect two current/voltage outputs
b Ensure continuity of the shielding
Connection is via the BMXFCApp0 cordset (1.5, 3, or 5 m/4.92, 9.84, or 16.4 ft
BMXFCApp0 long).

8
Modicon ABE7CPA02 sub-base
The Modicon ABE7CPA02 sub-base can be used with the BMEAHI0812 HART
analog input module.
This sub-base allows you to:
b Connect the 8 analog inputs point-to-point
b Ensure continuity of the shielding

9 The BMEAHI0812 module is connected by means of the 1.5 or 3 m/4.92 or 9.84 ft


long BMXFTA1522/3022 cables

10

4/28
References Modicon X80 modules
Modicon X80 I/O modules
HART analog I/O modules

Use with Modicon ABE7 sub-bases


Modicon ABE7CPA03 sub-base
The Modicon ABE7CPA03 sub-base can be used with the BMEAHI0812 HART analog input module. 1
This sub-base allows you to:
b Directly connect the 8 analog inputs
b Power the current inputs one channel at a time with a voltage of 24 V that is protected and limited to 25 mA
b Ensure continuity of the shielding
The BMEAHI0812 module is connected by means of the 1.5 or 3 m/4.92 or 9.84 ft long BMXFTA1522/3022
cables (1). 2
Modicon ABE7CPA31 sub-base
The Modicon ABE7CPA31 sub-base can be used with the BMEAHI0812 HART analog input module.
DIA3ED2160602EN This sub-base allows you to:
b Directly connect the 8 analog inputs
b Power the current inputs one channel at a time with 24 V converters
b Ensure continuity of the shielding 3
The BMEAHI0812 module is connected by means of the 1.5 or 3 m/4.92 or 9.84 ft long BMXFTA1522/3022
cables.

Additional characteristics

4
BMEAHI0812 HART analog input module
The BMEAHI0812 module is a module with 8 high-level isolated inputs (15 bits + sign).
The BMEAHI0812 module offers the current range 4 - 20 mA for each of the inputs depending on the choice made
during configuration.

BMEAHO0412 HART analog output module


The BMEAHO0412 module is a module with 4 high-level isolated outputs (15 bits + sign).
The BMEAHO0412 module offers the current range 4 - 20 mA for each of the inputs depending on the choice
made during configuration.
5

References
BMEAHI0812_main_image

Modicon X80 HART analog input module

6
Type of input Input signal Resolution Connection via No. of Reference Weight
range channels kg/lb
Isolated 4 - 20 mA 15 bits 20-way caged, screw 8 channels BMEAHI0812 0.233/
high-level inputs + sign clamp, or spring-type 0.514
removable terminal block

Modicon X80 HART analog output module


Type of input Output signal Resolution Connection via No. of Reference Weight
7
range channels kg/lb
BMEAHI0812 Isolated 4 - 20 mA 15 bits 20-way caged, screw 4 channels BMEAHO0412 0.223/
high-level outputs + sign clamp, or spring-type 0.492
removable terminal block

8
(1) The BMEAHI0812 HART analog input module loses its isolation between channels when connected to the Modicon
ABE7CPA03 sub-base.

10

4/29
Contents 5 - Safety

Modicon X80 Safety products


Modicon Safety selection guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5/2
b Safety Product compatibility................................................................. page 5/4 1
Modicon X80 Safety power supplies
b Presentation, description...................................................................... page 5/6
b Functions, references............................................................................ page 5/7

Modicon X80 Safety discrete I/O modules


2
b Presentation............................................................................................ page 5/8
b Description, connections ...................................................................... page 5/9
b References............................................................................................ page 5/10

Modicon X80 Safety analog I/O module 3


b Presentation, description, connections............................................. page 5/11
b References.............................................................................................page 5/11

10

5/1
Selection guide Modicon X80 modules
Modicon X80 Safety
Safety I/O modules

Applications 16-channel Safety discrete input module 8-channel Safety discrete output module 4-channel Safety relay output module 4-channel Safety analog input module

1 1

2 2

3 Type

Voltage
DC

24 V
AC/DC relays

24 V c/24...230 V a
Current


3
Current per channel 3.5 mA 0.5 A –

Range Voltage – 6

Current – 4...20 mA

4 Modularity Number of channels

Number of groups
16

2
8

1
4 isolated outputs 4 isolated inputs
4
Number of channels per common 8 –

Acquisition period Hot-swap RAID HDD and battery backup – 5 ms for the 4 inputs

Resolution – 16 bits (12,500 counts)


5 Connection Via BMXFTB20p0 20-way caged, screw clamp, or spring-type removable terminal block 5
Isolated inputs IEC/EN 61131-2 conformity Type 3 –

Logic Positive –

Type of input – Resistive

6 Sensor compatibility IEC/EN 60947-5-2 2-wire/3-wire –


6
Isolated outputs Fallback – Configurable fallback setting for each channel –

IEC/EN 61131-2 conformity – Yes –

Protection – Yes –

Logic – Positive –

7 Isolation Between channels Non-isolated 3000 Vrms 500 Vrms 7


Between channels and bus 1500 Vrms 3000 Vrms 1500 Vrms

Between channels and ground 1500 Vrms 3000 Vrms 1500 Vrms

Dimension WxHxD 32 x 131 x 86 mm/1.25 x 5.15 x 3.38 in.

Sensor power supply (ripple included) 19…30 V –


8 Preactuator power supply (ripple included) – 19…30 V 10…264 V a/10…34 V c – 8
Protection of inputs Use a fast-blow fuse, max 0.5 A, depending on the module –
current load
Output fuse protection – Use a fast-blow fuse, max 6 A, depending on the module current Use a fast-blow fuse, max 6 A, depending on the relay contact –
load current load
Maximum dissipated power 3.57 W 4.40 W 3.90 W 3.98 W

9 Conformal coated Yes 9


Operating temperature -25…60 °C/-13…140 °F

References
BMXSDI1602 BMXSDO0802 BMXSRA0405 BMXSAI0410
Page 5/10 5/11

10 10

More technical Information on www.se.com More technical Information on www.se.com

5/2
2 5/3
Compatibility Modicon M580 platform and Modicon X80 modules
Safety product compatibility according to network architecture and platform
For non safety product compatibility, please refer to page 1/10

Product type Product main feature Commercial Module type Connection type Modicon M580 Safety
reference (1)

1 Local rack with Safety CPU and coprocessor Modicon X80 drops on Ethernet Remote I/O Modicon X80 drops on 1

preassembled cordset
(X-bus + Ethernet backplanes BMEXBP are mandatory for Safety distributed I/O
CPU and coprocessor)

Terminal Block (2)


Standalone CPU Redundant CPU (HSBY) Standalone or redundant CPU (HSBY) Standalone CPU

Connector with
X-bus + Ethernet backplane BMEXBPpppp X-bus backplane BMXXBPpppp X-bus + Ethernet backplane X-bus backplane BMXXBPpppp
BMEXBPpppp

2 BMXCRA31200 BMXCRA31210 BMECRA31210 BMXPRA0100


2
Modicon X80 Redundant Safety power BMXCPS4002S 100...240 V a, 40W
Safety power supply
supplies BMXCPS4022S 24...48 V c, 40W

BMXCPS3522S 100...150 V c, 40W

3 Modicon X80
Backplanes
X-bus backplane BMXXBP0400 (H) 4 slots
3
BMXXBP0600 (H) 6 slots

BMXXBP0800 (H) 8 slots

BMXXBP1200 (H) 12 slots

4 X-bus + Ethernet
backplane
BMEXBP0400 (H) 4 slots
4
BMEXBP0800 (H) 8 slots

BMEXBP1200 (H) 12 slots

X-bus + Ethernet, Dual BMEXBP0602 (H) (3) 6 slots


power supply backplane

5 BMEXBP1002 (H) (3) 10 slots


5
Rack expansion BMXXBE1000 (H)(4) Module

BMXXBE2005 (5) Kit

Accessories BMXXEM010 (65) Protective cover

6 Safety I/O Safety Analog Input BMXSAI0410 4 channels 20


6
Safety Discrete Input BMXSDI1602 16 channels 20

Safety Discrete Output BMXSDO0802 8 channels 20

Safety Output Relay BMXSRA0405 4 channels 20

7 I/O expansion RIO drop adapter BMXCRA31200 X-bus, Standard 7


BMXCRA31210 (C) X-bus, Performance

BMECRA31210 (C) Ethernet, Performance

DIO drop adapter BMXPRA0100 Peripheral

8 (1) Optional versions: (C) - “Coated”, (H) - “Hardened”


(2) 20-way caged, screw clamp, or spring-type removable terminal block BMXFTB20p0
8
(3) Not compatible with single power supplies
(4) Extended rack can be any type of rack, but only X-bus modules (BMX) can be used
(5) Extended rack kit
(6) Protective cover for unoccupied slots on backplane

Compatible Not compatible

9 Note: All X80 Safety modules are compatible with the Modicon M580 Safety ePAC only. 9

10 10

More technical Information on www.se.com More technical Information on www.se.com

5/4 5/4
5/5
Presentation, Modicon X80 modules
description Modicon X80 Safety
Safety power supplies

Presentation
The Safety power supply in the Modicon X80 module offer is the BMXCPSppp2S.
1 The BMXCPS4022S Safety power supply:
b Converts 24...48 V c power into two output voltages, 24 V c and 3.3 V c,
which are distributed over the backplane
b Detects overvoltage, overload, and short-circuit conditions on both the 3.3 V c
and 24 V c backplane lines
The BMXCPS3522S Safety power supply:
2 b Converts 100...150 V c power into two output voltages, 24 V c and 3.3 V c,
which are distributed over the backplane
b Detects overvoltage, overload, and short-circuit conditions on both the 3.3 V c
and 24 V c backplane lines
The BMXCPS4002S Safety power supply:
b Converts 110...240 V a power into two output voltages, 24 V c and 3.3 V c,

3 which are distributed over the backplane


b Detects overvoltage, overload, and short-circuit conditions on both the 3.3 V c
and 24 V c backplane lines, and allows a maximum voltage of 30 V c

6
M580_62098_CPSCT16005C

Description
The BMXCPSppp2S Safety power supply includes:
1 1 Display panel comprising LEDs with various combinations to provide quick
4 diagnostics of the power supply status:
- ACTIVE LED (green): On when the power supply is the primary power
supply, off when it acts as a secundary supply in a redundant application
- OK LED (green): On if the rack voltages are present and correct
- RD LED (green): On when all the internal power supplies function normally
2
2 Printed serial number and product version
3 Pencil-point Reset pushbutton for a cold restart of the application
5 3
4 2-way connector that can take a removable terminal block (caged or spring-type)
for connecting the alarm relay
4 5 A 5-way connector that can take a removable terminal block (caged or spring-
type) for connecting the following:
- AC or DC line supply
- Protective ground
6 1 hook and 1 screw for mechanical attachment and grounding connection to the
6
5
BMXCPSppp2S backplane
Included with each power supply: Set of two caged removable terminal blocks
(5-way and 2-way) BMXXTSCPS10
To be ordered separately (if necessary): Set of two spring-type removable
terminal blocks (5-way and 2-way) BMXXTSCPS20 (see page 5/7).

7 Compatibility of the power supply with the rack


The BMXCPSppp2S is a safety-certified power supply that can be used as:
b a main local rack
b an extended local rack
b a main remote rack
b an extended remote rack

8 The BMXCPSppp2S is a redundant power supply. It can be installed alone in single


power supply rack or dual power supply rack as a pair (primary and secundary).
For high-availability applications, two independent redundant power supplies can
be used to increase the security of the power supply. In case the primary power
supply fails to provide the whole current, the secundary power supply changes to
primary mode and continues to function.

9 The power supply has to be inserted in the leftmost power supply slots on each rack
(marked CPS).

Advanced diagnostics
The BMXCPSppp2S can provide advanced diagnostics such as current load,
temperatures, remaining life time, and undervoltage thresholds. These unique
values will help to simplify maintenance by predicting when to replace the power
10 supply before it fails.

Note: LED diagnostic display is provided for the module and for each input channel.

5/6
Functions, Modicon X80 modules
references Modicon X80 Safety
Safety power supplies

Functions
Alarm relay
The alarm relay incorporated in each power supply has a volt-free contact accessible on the front panel, on the
2-way connector.
1
The operating principle is as follows:
b The alarm relay is energized and its contact is closed (state 1) in normal operation, with the PLC in RUN.
b The relay de-energizes and its associated contact opens (state 0) whenever the application stops, even
partially, due to any of the following:
v Occurrence of a blocking fault (RAM detected error in memory check, Safety watchdog overrun detected on
CPU, etc.)
2
v Incorrect rack output voltages
v Loss of supply voltage

Reset pushbutton
The power supply in each rack has a Reset button on the front panel.
3
Pressing the Reset button on the power supply causes re-initialization of all modules in the same rack as the
power supply. If the BMXCPSppp2S power supply is in the main local rack, pressing the Reset button causes
re-initialization of the CPU.

In a redundant design, with two BMXCPSppp2S power supplies, you can press the Reset button on either, or

4
both, power supplies to execute the reset function.
Pressing this pushbutton triggers a sequence of service signals, which is the same as that for:
b A power break, when the pushbutton is pressed.
b A power-up, when the pushbutton is released
In terms of the application, these operations represent a cold start (forcing the I/O modules to state 0 and
initializing the processor).

References
Modicon X80 Safety power supply (1)
5
Line supply Available power (2) Nominal current Reference Weight
kg/lb
3.3 V c (3) 24 V c rack (3) Total 24 V c rack (3)
24...48 V c 18 W 40 W 40 W 1.67 A BMXCPS4022S 0.810/
1.786
100...150 V c 18 W 40 W 40 W 1.67 A BMXCPS3522S 0.610/
1.345
6
100...240 V c 18 W 40 W 40 W 1.67 A BMXCPS4002S 0.510/
1.124

Accessories for Modicon X80 Safety power supply


Description Type Composition Reference Weight
kg/lb 7
Removable connectors Spring-type One 5-way terminal block and BMXXTSCPS20 0.015/
one 2-way terminal block 0.033

Caged One 5-way terminal block and BMXXTSCPS10 0.020/


one 2-way terminal block 0.044

(1) Include a set of 2 caged removable connectors. Spring-type connectors available separately under reference
8
BMXXTSCPS20.
(2) The sum of the power consumed on each voltage (3.3 V c and 24 V c) must not exceed the total power of the module. See
the power supply and I/O budget available in EcoStruxure Control Expert in the Power supply properties.
(3) 3.3 V c and 24 V c rack voltages for powering modules in the Modicon X80 I/O rack.

10

5/7
Presentation Modicon X80 modules
Modicon X80 Safety
Safety discrete I/O modules

Presentation of Safety I/O modules


Modicon M580 Safety TB-IO_assembly

Modicon X80 is a powerful, proven solution for integrating an homogeneous


1 automation architecture with a unique process and safety modules.
In the Modicon X80 offer, a Safety project can include both Safety modules and non-
safety modules:
b Safety modules in the SAFE task
b Non-safety modules only for the non-safety tasks (MAST, FAST, AUX0, and
Modicon M580 Safety configuration with a mix of Modicon X80
standard and Safety I/O AUX1)

2 Only non-safety modules that do not interfere with the safety function can be added
to a Safety project.
Safety I/O modules can be used to connect the Safety PAC to sensors and
actuators that are not part of the safety function loop.
Modicon_Safety_Copro

Each Safety I/O module incorporates a dedicated Safety processor.

3
Safety I/O modules can be installed in the local backplane or in RIO drops.
All Safety I/O modules support SIL3 standards according to IEC 61508. The
assessment is indicated by the category (Cat) and performance level (PL).
Modicon Safety configuration with Modicon X80 Safety
modules only with removable terminal blocks Each Safety I/O module provides module and channel LED diagnostics on the front
face of the module:
b The top four LEDs (Run, Err, I/O, and Lck) indicate the module status.

4
b The bottom rows of LEDs combine with the top four LEDs to indicate the state
and health of each input or output channel.

Presentation of Safety discrete I/O modules


There are three Safety discrete I/O modules in the Modicon X80 offer:
b BMXSDI1602 Safety discrete input module
b BMXSDO0802 Safety discrete output module
5 b BMXSRA0405 Safety discrete relay output module
These modules can only be used with a Safety CPU.
BMXSDI1602
The BMXSDI1602 Safety discrete input module has the following features:
b 16 Type 3 (1) inputs, in two groups of 8 non-isolated inputs
b 24 V c nominal input voltage
6 b Achieves SIL3, Cat2/PLd assessment using 1 input channel and Cat4/PLe using
2 input channels
b Compatible with 2- or 3-wire proximity sensors
b Optional provision of two 24 V c outputs (VS1 and VS2) for short-circuit to
24 V c monitoring
b Monitoring of external 24 V c sensor supply voltage
BMXSDO0802
7 The BMXSDO0802 Safety discrete output module has the following features:
b 8 non-isolated 0.5 A outputs
b 24 V c nominal output voltage
b Achieves SIL3, Cat4/PLe assessment
b Monitoring of the external pre-actuator power supply
BMXSRA0405
8 The BMXSRA0405 Safety discrete relay output module has the following features:
b 4 relay outputs with 5 A current
b 24 V c and 24...230 V a nominal output voltage (overvoltage category II)
b Achieves SIL2, Cat2/PLc assessment using 1 relay and SIL3, Cat4/PLe using
2 relays
b Support for 8 pre-defined application wiring configuration selections
b Configurable automatic self-test monitoring of the relay capacity to execute the
9 commanded output state (depending on the selected application wiring
configuration)
b Configurable module settings for fallback mode and fallback timeout (in ms)
(1) According to IEC61131-2 standard

10

5/8
Description, Modicon X80 modules
connections Modicon X80 Safety
Safety discrete I/O modules

1 Description
Safety discrete I/O modules are standard format with one slot. They have an IP20
1
M580_62098_CPSCT16001D

2 housing to help protect the electronics, and are locked into position with a captive
3 screw.

4 To be ordered separately: A BMXFTB20p0 20-way removable terminal block


(identification label supplied with each I/O module) or a preassembled cordset with
a 20-way removable terminal block at one end and flying leads at the other (see
connections on page 5/10):
BMXSDI1602, BMXSDO0802, and BMXSRA0405, Safety discrete modules
include: 2
1 Lock/unlock configuration button
2 Rigid body providing support and protection for the electronic card
3 Module reference marking (a label is also visible on the right-hand side of the
5 module)
4 Display panel comprising LEDs with various combinations to provide quick
diagnostics of the status of the module and each channel:
- RUN LED (green): module in operation 3
- ERR LED (red): detected module error
- I/O LED (red): detected I/O error
- LCK LED (bi-color green/red): indicates the configuration status
- 1 LED per channel (bi-color green/red): indicates the channel status
5 Connector taking the 20-way removable terminal block for connecting sensors or

4
preactuators

Safety discrete I/O module


Connections
20-way removable terminal blocks are used to connect the three Safety discrete I/O
modules.
BMXFTB2000_main_image

There are three types of 20-way removable terminal block:


b caged terminal block BMXFTB2000 (1)
b screw clamp terminal block BMXFTB2010 (1)
5
b spring-type terminal block BMXFTB2020 (1)

Type of Minimum capacity Maximum capacity


terminal block

6
Caged (1) One 0.34 mm² wire (AWG 22) One 1 mm² wire (AWG 18)
Screw clamp (1) One or two 0.34 mm² wires (AWG 22) Two 1.5 mm² wires (AWG 15)
Spring-type One 0.34 mm² wire (AWG 22) One 1 mm² wire (AWG 18)
(1) Connectors are equipped with captive screws: max. tightening torque 0.5 N.m/0.37 lb-ft.

BMXFTB2000 Note: No cordset is provided for cabling Safety X80 I/O modules. Too many options are
possible according to the kind of:
- application: safety only, safety mixed with availability, etc.
- functional safety level: SIL3/Cat2, SIL3/Cat4, SIL2, etc.
For more information on the different cabling options, please refer to the detailed user manuals
7
published on our website.

10

5/9
References Modicon X80 modules
Modicon X80 Safety
Safety discrete I/O modules

References
M580_62098_CPSCT16001D

Modicon X80 Safety discrete input module


1 Type of Input
current voltage
Connnection
via
IEC/EN
61131-2
Number of
channels
Reference Weight
kg/lb
conformity (common)
DC 24 V (logic Caged, screw Type 3 16 BMXSDI1602 0.115/
positive) clamp, or non-isolated 0.254
spring-type inputs
20-way (1 x 16)
2 removable
terminal block

BMXSDI1602
Modicon X80 Safety discrete output module
Type of Input Connnection IEC/EN Number of Reference Weight
M580_62098_CPSCT16002A

3
current voltage via 61131-2 channels kg/lb
conformity (common)
DC 24 V (logic Caged, screw Yes 8 BMXSDO0802 0.120/
positive) clamp, or non-isolated 0.264
spring-type outputs
20-way (1 x 8)
removable
terminal block

4
Modicon X80 Safety relay output module
Type of Input Connnection IEC/EN Number of Reference Weight
BMXSDO0802 current voltage via 61131-2 channels kg/lb
conformity (common)

5 AC/DC 24 Vc/ Caged, screw Yes 4 isolated BMXSRA0405 0.145/


M580_62098_CPSCT16004A

relay 24...230 V a clamp, or outputs 0.320


spring-type (1 x 4)
20-way
removable
terminal block

6 Removable terminal blocks


Description For use with Type composition Reference Weight
modules kg/lb

20-way removable BMXSDI1602 Caged BMXFTB2000 0.093/


terminal blocks 0.205

7
BMXSRA0405

BMXSDO0802 Screw clamp BMXFTB2010 0.075/


0.165

BMXSRA0405 Spring BMXFTB2020 0.062/


0.132

10

5/10
Presentation, Modicon X80 modules
description, Modicon X80 Safety
Safety analog input module
connections,
references

Presentation
1
The Safety analog input module in the Modicon X80 offer is the BMXSAI0410:

2
The BMXSAI0410 Safety analog input module has the following features:
b 4 isolated analog 4...20 mA current input channels
1
M580_62098_CPSCT16001D

b 16-bit resolution (12,500 counts), spanning the data range 0...25 mA


3 b Current out of range detection, for current values less than 3.75 mA or greater
4 than 20.75 mA
b Achieves SIL3, Cat2/PLd assessment using 1 input channel and SIL3, Cat4/PLe
using 2 input channels
This module can only be used with a Safety CPU. 2
Description
The BMXSAI0410 Safety analog input module includes:
1 Lock/unlock configuration button
5 2 Rigid body providing support and protection for the electronic card
3 Module reference marking (a label is also visible on the right-hand side of the
module)
4 Display pannel comprising LEDs with various combinations to provide quick
3
diagnostics of the status of the module and each channel (1):
- RUN LED (green): module in operation
- ERR LED (red): detected module error
- I/O LED (red): detected I/O error
- LCK LED (bi-color green/red): indicates the configuration status

BMXSAI0410
- 1 LED per channel (bi-color green/red): indicates the channel status
5 Connector taking the 20-way removable terminal block for connecting sensors or
4
preactuators
Connections
20-way removable terminal blocks are used to connect the analog input module. (2)
M580_62098_OPFJR17001A

5
There are three types of 20-way removable terminal block:
b caged terminal block BMXFTB2000 (3)
b screw clamp terminal block BMXFTB2010 (3)
b spring-type terminal block BMXFTB2020

Type of terminal Minimum capacity Maximum capacity


block
Caged (3) One 0.34 mm² wire (AWG 22) One 1 mm² wire (AWG 18)
6
Screw clamp (3) One or two 0.34 mm² wires (AWG 22) Two 1.5 mm² wires (AWG 15)

Spring-type One 0.34 mm² wire (AWG 22) One 1 mm² wire (AWG 18)

SDI1602 red label Red labels are provided for Safety I/O modules.

References 7
Modicon X80 Safety analog input modules
Type of Input signal Resolution Connection Nb of Reference Weight
input range channels kg/lb
BMXFTB2000_main_image

Isolated 4–20 mA 16 bits Removable 4 BMXSAI0410 0.143/


high- terminal block, 0.315
level
input
20-way caged,
screw clamp,
or spring-type
8
Connection accessories for Modicon X80 Safety analog input module
Description For use with Type Reference Weight
modules composition kg/lb
20-way removable
terminal blocks
BMXSAI0410 Caged BMXFTB2000 0.093/
0.205 9
Screw clamp BMXFTB2010 0.075/
0.165
Spring BMXFTB2020 0.060/
0.132
BMXFTB2000 (1) LEDs in positions 5…7 are not used because the input module only has four channels.

10
(2) No cordset is provided for cabling safety Modicon X80 I/O modules. Too many options are
possible according to the kind of:
- applications: safety only, safety mixed with availability, etc.
- functional safety level: SIL3/Cat2, SIL3/Cat4, SIL2, etc.
For more information on the different cabling options, please refer to the detailed user
manuals published on our website.
(3) Connectors are equipped with captive screws: max. tightening torque 0.5 N.m/0.37 lb-ft.

5/11
Contents 6 - Expert modules

Modicon X80 Counter modules


b Presentation, description...................................................................... page 6/2
b Functions................................................................................................ page 6/3 1
b References.............................................................................................. page 6/5

Modicon X80 Time-stamping module


b Presentation, description...................................................................... page 6/6
b Performance, references....................................................................... page 6/7 2
Modicon X80 SSI encoder interface module
b Presentation, description...................................................................... page 6/8
b Functions, references............................................................................ page 6/9

Modicon X80 Motion control module 3


b Presentation, description.................................................................... page 6/10
b Operation, references...........................................................................page 6/11
b MFB library presentation, functions................................................... page 6/12
b Motion tree manager, programming, maintenance............................ page 6/13
4
Modicon X80 Frequency input module
b Presentation, description.................................................................... page 6/14
b Module specifications, references...................................................... page 6/15

Modicon X80 Weighing module


b Presentation, description.................................................................... page 6/16
5
b References............................................................................................ page 6/17

10

6/1
Presentation, Modicon X80 modules
description Modicon X80 Expert modules
Counter modules

Presentation

1
In the Modicon X80 module offer, BMXEHC0200 and BMXEHC0800 counter
modules are used to count the pulses generated by a sensor or to process the
signals from an incremental encoder.
The two modules differ in their number of counter channels, maximum input
frequencies, functions, and auxiliary input and output interfaces:
Counter No. of Maximum Integrated No. of No. of
module channels frequency functions physical physical
2 Modicon PLC Configurator BMXEHC0200 2 60 KHz Upcounting
inputs
6
outputs
2
Downcounting
Period meter
Frequency meter
Frequency generator
Axis control

3
Click on the pictogram to access BMXEHC0800 8 10 KHz Upcounting 2 –
Modicon PLC Configurator on line and Downcounting
design your installation Measurement
The sensors used on each channel can be:
b 2-wire 24 V proximity sensors
b 3-wire 24 V proximity sensors
b 10/30 V output signal incremental encoders with push-pull outputs

4
BMXEHC0200/0800 counter modules can be used to meet the demands of
applications such as:
b Alarm generation on empty unwinder status using the ratio
b Sorting small parts using the period meter
b Single electronic cam using the dynamic setting thresholds
b Speed control using the period meter
These standard format modules can be installed in any available slot on a

5 EcoStruxure Control Expert


monitor
Modicon X80 backplane. They are hot-swappable.
In a Modicon X80 PLC configuration, the number of BMXEHC0200/0800 counter
modules should be added to the number of application-specific modules
(communication). The function parameters are set by configuration using
EcoStruxure Control Expert (1) software.

Description
6 BMXEHC0200/0800 counter modules are standard format. They occupy a single
BMXEHC0200_main_image

slot in BMpXBPppp backplanes. They come in a plastic case, which provides IP20
protection of the electronics, and are locked into position by a captive screw.
1
BMXEHC0200 module, 2 channels, 60 KHz
2 The front panel of the BMXEHC0200 counter module features:
7 1  Module and channel status display block
2  16-way connector for connecting the sensors of counter 0
3 3  16-way connector for connecting the sensors of counter 1
4  10-way connector for connecting:
4
- Auxiliary outputs
- Sensor power supplies
To be ordered separately:
8
BMXEHC0200
b A BMXXTSHSC20 kit containing two 16-way connectors and one 10-way
connector (see page 6/5)
b A BMXXSPpp00 shielding connection kit if the backplane is not already equipped
with one (see page 2/5)
BMXEHC0800_main_image

BMXEHC0800 module, 8 channels, 10 KHz


1
The front panel of the BMXEHC0800 counter module features:
9 1  Module and channel status display block
2  Connector taking the BMXFTB20p0 20-way removable terminal block 3 (same
as that of I/O modules)
2 To be ordered separately:
b A 20-way removable terminal block 3 (caged, screw clamp, or spring-type)
(see page 4/15)
3
b A BMXXSPpp00 shielding connection kit if the backplane is not already equipped
10 with one (see page 2/5)

BMXEHC0800 BMXFTB20p0 (1) EcoStruxure Control Expert software continues the Unity Pro range of software and
corresponds to versions u 14 of Unity Pro.

6/2
Functions Modicon X80 modules
ModiconX80 Expert modules
Counter modules

Operating modes for module BMXEHC0200


8 configurable modes Frequency meter This mode measures a frequency, speed, data rate, or an event stream.
As standard, this mode measures the frequency received on the IN A input.
This frequency is expressed in Hz (number of pulses/second), with a precision of 1 Hz. 1
The maximum frequency on the IN A input is 60 kHz.
The maximum cyclic ratio at 60 kHz is 60%.
Event counting This mode is used to determine the number of events received.
In this mode, the counter calculates the number of pulses applied to the IN_A input at time
intervals defined by the user.
The module counts the pulses applied to the IN_A input each time the pulse for this input lasts
longer than 5 μs (without anti-bounce filter). 2
Period measurement This mode is used to:
b Determine the duration of an event
b Determine the time between 2 events
b Time and measure the execution time of a process
It measures the time elapsed during an event or between 2 events (IN_A input) according to a
selectable time base of 1 μs, 100 μs, or 1 ms.
The IN_SYNC input can be used to enable or stop a measurement.
The module can carry out a maximum of 1 measurement every 5 ms. 3
The shortest measurable pulse is 100 μs, even if the unit defined by the user is 1 μs.
The maximum measurable duration is 4,294,967,295 units (unit to be defined).

Ratio counting Ratio counting mode only uses the IN_A and IN_B inputs. There are 2 possible modes:
b Ratio 1: Used to divide 2 frequencies. This is intended for applications such as flowmeters,
mixers, etc.

4
b Ratio 2: Used to subtract 2 frequencies. This is intended for the same applications, but for
those requiring more precise regulation (more similar frequencies).
Ratio 1 mode gives the results in thousandths for better accuracy (a display of 2,000 corresponds
to a value of 2) and ratio 2 mode gives the results in Hz.
The maximum frequency that the module can measure on the IN_A and IN_B inputs is 60 kHz.
Downcounting This mode is used to list a group of operations. In this mode, activating the synchronization
function starts the counter which, starting from a user-defined preset value, decreases with
each pulse applied to the IN_A input, until it reaches 0. This downcounting is made possible
when the enable function has been activated. The counting register is thus updated at 1 ms
intervals. 5
One basic use of this mode is to signal, using an output, the end of a group of operations (when
the counter reaches 0).
The shortest pulse applied to the IN_SYNC input is 100 μs.
The maximum frequency applied to the IN_SYNC input is 1 pulse every 5 ms.
The maximum user-defined preset value is 4,294,967,295.
The maximum count value is 4,294,967,295 units.
Loop (modulo) counting This mode is used in packaging and labeling applications where actions are repeated on sets of
moving objects:
6
b In upcounting, the counter increases until it reaches the user-defined “modulo - 1” value. On
the next pulse, the counter is reset to 0 and upcounting restarts.
b In downcounting, the counter decreases until it reaches 0. On the next pulse, the counter is
reset to the user-defined “modulo - 1” value. Downcounting can then restart.
The maximum frequency applied to the IN_A and IN_B inputs is 60 kHz.

7
The maximum frequency of the modulo event is 1 event every 5 ms.
The maximum modulo value is 4,294,967,296 (possible by declaring 0 in the modulo adjust
value).
32-bit counter counting This mode is mainly used in axis following.
The maximum frequency applied simultaneously to the IN_A and IN_B inputs is 60 kHz.
The maximum frequency of the referencing event is 1 event every 5 ms.
The counter value is between -2,147,483,648 and +2,147,483,647.

8
Width modulation In this operating mode, the module uses an internal clock generator to supply a periodic signal
on the module's O0 output. Only the O0 output is affected by this mode, as the O1 output is
independent of it.
The maximum output frequency is 4 kHz.
As O0 is a source output, a load resistor is necessary for the O0 output signal to change to 0 at
the correct frequency.
The cyclic ratio adjustment range varies according to the frequency of the O0 output.

10

6/3
Functions (continued) Modicon X80 modules
Modicon X80 Expert modules
Counter modules

Operating modes for module BMXEHC0800


5 configurable 16-bit Frequency meter This mode measures a frequency, speed, rate, or data stream control.
1 modes As standard, this mode measures the frequency received on the IN A input.
This frequency is expressed in Hz (number of pulses per second), with a precision of 1 Hz.
The maximum frequency on the IN A input is 10 kHz.
The maximum cyclic ratio at 10 kHz is 60%.
Event counting This mode is used to determine the number of events received.
In this mode, the counter calculates the number of pulses applied to the IN_A input at time
intervals defined by the user.

2
As an option, it is possible to use the IN_AUX input during a period of time, provided that the
enable bit has been configured.
The module counts the pulses applied to the IN_A input each time the pulse for this input lasts
longer than 50 μs (without anti-bounce filter).
Pulses with less than 100 ms synchronization are lost.
Downcounting This mode is used to list a group of operations. In this mode, when counting is enabled
(software validation via the valid_sync command), a rising or falling edge on the IN_AUX input
causes a value, defined by the user, to be loaded in the counter. The latter decreases with each
3 pulse applied to the IN_A input until it reaches the value 0. Downcounting is made possible
when the force_enable command is high (software positioning).
The smallest pulse applied to the IN_AUX input varies according to the selected filter level.
The maximum frequency applied to the IN_AUX input is 1 pulse every 25 ms.
Loop (modulo) counting This mode is used in packaging and labeling applications where actions are repeated on sets of
moving objects.
The counter increases with each pulse applied to the IN_A input until it reaches the user-

4
defined “modulo - 1” value. On the next pulse in the upcounting direction, the counter is reset to
0 and upcounting restarts.
The maximum frequency applied to the IN_A input is 10 kHz.
The smallest pulse applied to the IN_AUX input varies according to the selected filter level.
The maximum frequency of the modulo event is 1 event every 25 ms.
The maximum modulo value is 65,536 units.
Up/down counter This mode is used for an accumulation, upcounting, or downcounting operation on a single
input.
5 Each pulse applied to the IN_A input produces:
b Upcounting of pulses if the IN_AUX input is high
b Downcounting of pulses if the IN_AUX input is low
The counter values vary between the limits -65,536 and +65,535.
The maximum frequency applied to the IN_A input is 10 kHz.
Pulses applied to the IN_A input after a change of direction are only upcounted or downcounted
after a period corresponding to the delay for taking account of the state of the IN_AUX input due
to the programmable filter level on this input.

6 One 32-bit mode 32-bit counter counting 32-bit counter counting mode is available for channels 0, 2, 4, and 6 (channels 1, 3, 5, and 7 are
now inactive). It behaves in the same way as the up/down counting mode using up to 3 physical
inputs. It enables simultaneous upcounting and downcounting.

The counter values vary between the limits -2,147,483,648 and +2,147,483,647 (31 bits +
sign).
The maximum frequency applied to the IN_A and IN_B inputs is 10 kHz.

7
The smallest pulse applied to the IN_AUX input is defined according to the filtering applied to
this input.
The maximum frequency of loading the preset value is 1 every 25 ms.

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 2/2 page 8
 /2 page 9
 /2

6/4
References Modicon X80 modules
Modicon X80 Expert modules
Counter modules

References
Modicon X80 counter modules (1)
Description No. of Characteristics Reference Weight 1
BMXEHC0200_main_image

BMXEHC0800_main_image channels kg/lb


Counter modules 2 60 kHz counting BMXEHC0200 0.112/
for 24 V c 0.247
2 and 3-wire sensors and 8 10 kHz counting BMXEHC0800 0.113/
10/30 V c incremental 0.249
encoders with push-pull
outputs
2

BMXEHC0200 BMXEHC0800

Connection accessories (2)


Description Composition Unit reference Weight 3
BMXFTB0200_main_image

kg/lb
Pack of connectors Two 16-way connectors and BMXXTSHSC20 0.021/
for BMXEHC0200 module one 10-way connector 0.046

20-way removable Caged BMXFTB2000 0.093/


terminal blocks 0.205

4
for BMXEHC0800 module Screw clamp BMXFTB2010 0.075/
0.165
Spring BMXFTB2020 0.060/
0.132
BMXFTB20p0
Shielding connection kit Comprising a metal bar and two See page 2/5 –
for X80 counter modules support bases for mounting on
backplane

(1) Calculate the power consumption by using the Modicon PLC Configurator online tool.
(2) The shielding on the cordsets carrying the counter signals must always be connected to the
5
BMXXSPpp00 shielding connection kit mounted under the backplane that holds the
BMXEHC0200 module (see page 2/5).

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1/10 page 2/2 page 2/2 page 8
 /2 page 9
 /2

6/5
Presentation Modicon X80 modules
Modicon X80 Expert modules
Time-stamping module

Presentation
The BMXERT1604T/H time-stamping module is a complete solution providing a
1 SCADA with a sequence of events that are time-stamped at source, enabling the
BMXERT1604T_main_image

user to analyze the source of any abnormal behavior in an automated system.


The SOE (sequence of events) is displayed in the alarms log or in the list of events
for a client such as a SCADA.
Each event in the SOE is a change of value (transition) of a discrete I/O detected by
a time-stamping module.

2 Advantages
Using the time-stamping system has the following advantages:
b No PLC programming
b Direct communication between the time-stamping modules and the client; if the
BMXERT1604T/BMXERT1604H time-stamping modules are in a Quantum Ethernet I/O drop, the bandwidth of the
PLC communication is not used
3 b Consistency of the I/O values between the process (time-stamping modules) and
the client
b Consistency is maintained irrespective of the operating mode
b No loss of events under normal operating conditions
b Management of Hot Standby configurations on the PLC and/or SCADA
redundancy

4 Composition of a time-stamping architecture


Modicon X80 Remote I/O drop adapter
The BMXERT1604T/H module can be at the source of any discrete I/O signal located
in the drop with a resolution of 10 ms. To help ensure no event is lost, all events are
stored and kept in a buffer located in the product until OFS takes them.

5
The NTP protocol is used to synchronize the Modicon X80 Remote I/O drop adapter
(BMpCRA312p0).

Modicon X80 Time-stamping module


The BMXERT1604T/H time-stamping module has 16 discrete inputs which carry out
the time-stamping at source outputs with a resolution of 1 ms.

6
To help ensure no event is lost, all events are stored and kept in a buffer located in
the product until OFS takes them.
This module can be placed either in an RIO drop or in a local rack equipped with a
Modicon X80 Remote I/O drop adapter which is synchronized via the DCF 77 or
IRIG-B standards.

OFS V3.6 software

7 OFS V3.6 software is used to access events stored in the various buffers in the
architecture and to place them in the SCADA via the standard OPC DA protocol. For
further information, consult our website.

AVEVA Plant SCADA


AVEVA Plant SCADA receives events transmitted by OFS and displays them in the
SOE or in the list of alarms. For further information, consult our TPP partner website.
8

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8
 /2 page 9
 /2

6/6
Performance, Modicon X80 modules
references Modicon X80 Expert modules
Time-stamping module

Performance
Performance Event source module Value
Between two identical source
modules in the same rack
BMXERT1604T
BMXERT1604H
1.6 < resolution < 3.3 ms 1
BMpCRA31p10 10 ms

Between two different inputs in the BMXERT1604T 1 ms


same source module BMXERT1604H

2
BMpCRA31p10 1 scan

Maximum buffer BMXERT1604T 255 groups (1)


BMXERT1604H
Maximum number of discrete BMXERT1604T 400 discrete inputs (2)
inputs/outputs monitored by the BMXERT1604H
PLC for the entire time-stamping BMpCRA31p10 2,048 discrete I/Os (2)
module

Maximum number of I/O and BMXERT1604T 16 discrete inputs on module


3
memory available BMXERT1604H 255 groups (3)
BMpCRA31p10 256 discrete I/O configured
4,000 events in internal buffer

Maximum number of source


modules in an Ethernet remote
BMpCRA31p10
BMXERT1604T
1 per drop
9 per drop
4
drop BMXERT1604H

Maximum number of sources of BMXERT1604T 500 sources per second (2)


events polled by OFS BMXERT1604H

References
Modicon X80 Time-stamping modules 5
Description Input type Reference Weight
kg/lb
Multifunction time-stamping input 16 discrete inputs BMXERT1604T 0.119/
module 0.262
Multifunction time-stamping input BMXERT1604H

6
module for severe environments

Connection accessories for time-stamping modules


Description For use with Type, Length Reference Weight
modules composition kg/lb
28-way BMXERT1604T Caged – BMXFTB2800 0.111/
removable BMXERT1604H 0.245
terminal blocks
7
Spring – BMXFTB2820 0.080/
0.176

(1) A group is a set of 1 to 16 events detected in the same cycle.


(2) This maximum value is not an absolute value. It depends on the overall system dynamics
(total number of scanned items and number of events generated by the system).
(3) The event number contained in one group varies within 1..16. It depends on how many
channels get the events occured within same sampling window (0.5ms).

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8/2 page 9
 /2

6/7
Presentation, Modicon X80 modules
description Modicon X80 Expert modules
SSI encoder interface module

Presentation
The BMXEAE0300 SSI encoder interface module 1 for the Modicon automation
1 platform (1) is a 3-channel standard synchronous serial interface module designed
for use with SSI absolute encoders 2.
1
The BMXEAE0300 module enables SSI encoder values to be processed on PAC
platforms for applications requiring accurate position/angular control, such as:
b Hydro power, e.g. dam inlet gate position control
b Wind power, e.g. wind turbine blade pitch control
2 b Complex motion loop control, e.g. ship elevator, blast furnace, flame cutting, etc.
The BMXEAE0300 module provides a migration path from Premium (with
TSXCTY2C measurement and counter module) to the Modicon X80 modules SSI
solution to compete in the above market segments.

2 Like any other application-specific module, the BMXEAE0300 module is installed in


the rack slots (01 to 11). The number of modules is limited by the maximum number
3 of application-specific channels permitted according to the CPU type (consult
our website).
Dam inlet gate control
Inlet gate control enables the water level in a dam to be monitored and controlled:
b The SSI encoder provides the PLC with accurate feedback of the gate position
Modicon X80 modules with Modicon M340 processor for precise monitoring of gate opening, adjustment, and positioning.

4 b The SSI interface converts the signals from the SSI encoders and transmits them
to the CPU.
Wind turbine blade pitch control
Pitch control is required for adjusting the angle of the wind turbine blades in relation
to the wind direction and strength, in order to achieve optimum energy conversion
efficiency.

5
b The SSI absolute encoder is frequently used to feed back the position of the
blade due to its reliability and robustness.
b Typically, the position of each of the three blades is read by the SSI encoders and
then transmitted to the CPU via the SSI interface for motion loop control.
Sometimes, 3 additional SSI inputs act as backup. Therefore, this new offer is
adequately sized for the channel density.

6 Description
The BMXEAE0300 SSI encoder interface module is standard format (1 slot). Its
housing provides IP20 protection of the electronics and it is locked in each slot (01 to
11) by a captive screw.

1 The front panel of the BMXEAE0300 module features:


1  A rigid housing providing support and protection for the electronic card
7
BMXEAE0300_main_image

2 2  The module reference marking (a label is also visible on the right-hand side of the
module)
3 3  A display block indicating:
BMXFTB2800_main_image

v Module status via 4 LEDs:


- RUN (green): module operating status
- ERR (red): internal fault detected in the module or a fault detected between
the module and the rest of the configuration
8 4
5
- I/O (red): external fault detected
- DL (green): firmware download status
v Status of the 3 SSI channels via 8 LEDs:
- Sx (green): channel x input (x = 0, 1, or 2)
- Qx (green): reflex output for channel x (x = 0, 1, or 2)
- I0/1 (green): capture inputs for the 3 SSI channels
BMXEAE0300 BMXFTB28p0
4  A connector for a 28-way terminal block, for connecting to a removable caged or
9 spring terminal block on sensors and preactuators
To be ordered separately:
5  A BMXFTB2800 28-way removable caged terminal block or BMXFTB2820 spring
terminal block, supplied with a channel identification label (see page 6/11)
v A shielding connection kit to help protect against electrostatic discharge,
consisting of a metal bar and two sub-bases for mounting on the rack:

10
BMXXSPpp00 (reference dependent on the number of slots in the rack) (see
page 2/5)
v A set of clamping rings STBXSP30p0 for the connection cable shielding braids
(reference dependent on the cable diameter) (see page 2/5)
(1) Only for the Modicon automation platforms compatible with Modicon X80 modules

6/8
Functions, Modicon X80 modules
references Modicon X80 Expert modules
SSI encoder interface module

Module specifications and functions


Specifications
The BMXEAE0300 SSI encoder interface module is a 3-channel, synchronous serial interface,
absolute encoder interface for Modicon PLCs. It supports:
1
b 3 channels of SSI inputs (DATA pair, CLK pair, 24 VDC field power supply to encoder)
b 1 reflex output for each SSI channel (Q)
b 2 capture inputs for the 3 SSI channels (CAP_IN0, CAP_IN1)
b 8 to 31 bits data width
b 4 baud rates (100 kHz, 200 kHz, 500 kHz, and 1 MHz)
b Capture and compare functions 2
Basic and optional functions
The following table presents the main functions of the BMXEAE0300 module:
Function Basic/ Description
optional
Absolute SSI encoder Basic The position values of the SSI channel are automatically read by the 3
value acquisition module within 1 ms, unless the channel is disabled.
Modulo Optional The modulo function limits the dynamics of the position value to within the
for motion power of 2. An event (if enabled) detects the passing of the modulo. The
reflex output can also be detected when the modulo is passed (if configured).
Reduction Optional This function reduces the intrinsic resolution of the encoder by a value
for motion defined by the “reduction” parameter. This reduction is carried out by a shift
in the bit field provided by the encoder. 4
Offset Optional The correction function of the encoder offset systematically corrects the
for motion offset produced by the encoder at mechanical position “0”. The user enters
the absolute encoder offset parameter.
Capture Optional The two capture input registers (per channel) enable the PLC program to
for events carry out a dynamic measurement function between two points. The
capture action can be triggered by two capture inputs. The event will be
triggered at each capture. 5
Compare Optional Two independent comparators (per channel), with thresholds that can be
for events modified by adjustment (explicit exchange), are able to generate an event
or reflex output when the threshold is crossed.

Main features
b Supported by EcoStruxure Control Expert (1).
b Supports absolute encoder 24 V model with standard SSI interface, including Telemecanique
6
Sensors OsiSense SSI encoders. For further information, consult Telemecanique Sensors
website.
b Standards and approvals: e, UL, CSA, C-Tick, GOST, etc.
EcoStruxure Control Expert monitor

References
Modicon X80 SSI encoder interface module (2)
7
BMXEAE0300_main_image

Description Number Description Reference Weight


of channels per channel kg/lb
SSI encoder 3 SSI 1 reflex output for each SSI channel BMXEAE0300 0.138/
interface module channels 2 capture inputs for the 3 SSI channels 0.304
8 to 31 bits data width

8
4 baud rates:100 kHz, 200 kHz,
500 kHz, 1 MHz
Capture and compare functions

Cabling accessories
Description Description, use Reference Weight
kg/lb
28-way removable Caged BMXFTB2800 0.111/
BMXEAE0300
terminal block
Spring BMXFTB2820
0.245
0.080/
9
0.176
BMXFTB2800_main_image

Shielding Comprising a metal bar and two support bases See page 2/5 –
connection kit for mounting on rack
for BMXEAE0300
module
(3)

(1) EcoStruxure Control Expert software continues the range of Unity Pro software and corresponds to
10
versions u 14 of Unity Pro.
(2) Calculate the power consumption by using the Modicon PLC Configurator online tool.
(3) The shielding on the cables carrying the power supply to the module, each SSI channel, the capture inputs, and
BMXFTB28p0 the reflex outputs (if any of them is wired) must always be connected to the BMXXSPpp00 shielding connection
kit mounted under the rack holding the BMXEAE0300 module (see page 2/5).

6/9
Presentation, Modicon X80 modules
description Modicon X80 Expert modules
Motion control module

1 Presentation
The 1 BMXMSP0200 motion control pulse train output (PTO) module for the
1 Modicon automation platform is used for controlling third-party variable speed
drives 2, which have an integrated position loop and inputs that are compatible with
open collector outputs.
The BMXMSP0200 Motion control module is also directly compatible with the
Lexium 32C and 32M 3 servo drive ranges, which have an integrated pulse control
interface.

2 The BMXMSP0200 motion control PTO module has two independent PTO
channels. Like any other application-specific module, it is installed in the rack slots
(labeled 01 to 11). The number of modules is limited by the maximum number of
application-specific channels permitted according to the CPU type:
b Standard BMXP341000: Maximum of 20 application-specific channels (1)
b Performance BMXP3420p0: Maximum of 36 application-specific channels (1)
3 2 b BMEP5810: Maximum of 24 application-specific channels (1)
3 b BMEP5820: Maximum of 32 application-specific channels (1)
b BMEP5830 and BMEP5840: Maximum of 64 application-specific channels (1)
b BMEP585040: Maximum of 180 application-specific channels (1)
b BMEP586040: Maximum of 216 application-specific channels (1)

4 4 Description
The BMXMSP0200 motion control module is standard format (1 slot). Its housing
provides IP20 protection of the electronics and it is locked in each slot (01 to 11) by
a captive screw.

5 The front panel of the BMXMSP0200 motion control module features:


4  A rigid body providing support and protection for the electronic card
5 6 5  A module reference marking (a label is also visible on the right-hand side of the
module)
6  A display block indicating:
- Module status via 4 LEDs (RUN, ERR, I/O, and DL)
- Status of the auxiliary inputs, 4 per channel
7 - Status of the PTO outputs, 2 per channel
- Status of the auxiliary outputs, 2 per channel
6 8
7  A connector for a 28-way terminal block, for connecting to a removable spring
terminal block on sensors and preactuators

BMXMSP0200 To be ordered separately:


BMXFTB28p0 8  A BMXFTB2800 28-way removable caged terminal block or BMXFTB2820
spring terminal block, supplied with a channel identification label (see page 6/11)
b A shielding connection kit to help protect against electrostatic discharge,

7 consisting of a metal bar and two sub-bases for mounting on the rack:
BMXXSPpp00 (reference dependent on the number of slots in the rack) (see
page 2/5)
b A set of clamping rings STBXSP30p0 for the connection cable shielding braids
(reference dependent on the cable diameter) (see page 2/5)

8 (1) Application-specific channels: BMXEHC0200 (2-channel) and BMXEHC0800 (8‑channel)


counter modules, BMXMSP0200 (2-channel) motion control module, BMXNOM0200
(2-channel) and BMXNOR0200H (1-channel) serial communication modules, BMEAHI0812
(8-channel) analog input module and BMEAHO0412 (4-channel) analog output module,
BMXEAE0300 (3-channel) SSI module and BMXERT1604T/H (16-channel) discrete input
module.

9 DIA6ED2151012EN

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8
 /2 page 9/2

6/10
Operation, Modicon X80 modules
references Modicon X80 Expert modules
Motion control module

Operation
Block diagram of a BMXMSP0200 module channel
Inputs/outputs per channel 1
PTO output CWp Speed Servo drive

Servo
Integrator
PTO output CCWp motor
Pulses

24 V c output D_Enable Position Velocity Torque


loop loop loop

24 V c output C_Clear
2
C_Position Wait position

D_Ready Servo ready

Homing
Origin

Proximity
Proximity sensor
Position switch 3
References
Modicon X80 Motion control module (1)
BMXMSP0200_main_image

Description Number of Description per channel Reference Weight

PTO module
channels
2 2 x 200 kHz max. PTO outputs BMXMSP0200
kg/lb
0.145/ 4
2 x 24 V c/50 mA auxiliary outputs 0.320
4 x 24 V c auxiliary inputs

Cabling accessories
Description Description, use Length Reference Weight
kg/lb 5
28-way Caged – BMXFTB2800 0.111/
removable 0.245
BMXMSP0200 terminal block Spring – BMXFTB2820 0.080/
0.176

Connection From BMXMSP0200 (screw clamp 3 m/9.84 VW3M8223R30 –


BMXFTB2800_main_image

6
cable terminal block) module to Lexium ft
for daisy chain 32C or 32M (RJ45 connector)
or pulse control (cable with flying leads at one end and
an RJ45 connector at the other)
(2)
Shielding Comprising a metal bar and two – See page 2/5 –
connection kit support bases for mounting on rack
for module
BMXMSP0200
7
(1) Calculate the power consumption by using the Modicon PLC Configurator online tool.
BMXFTB28p0
(2) The shielding on the cordsets carrying the motion control signals must always be connected
to the BMXXSPpp00 shielding connection kit mounted under the rack holding the
BMXMSP0200 module (see page 2/5).

10

Compatibility: Backplanes: Power supplies: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 8/2 page 9
 /2

6/11
Presentation, Modicon X80 modules
functions Modicon X80 Expert modules
MFB motion control library

Modicon Quantum EIO


Presentation
MFB (Motion Function Blocks) is a library of function blocks integrated in
1 Modicon M580 EcoStruxure Control Expert (1) used to set up motion control in the architectures of
drives and servo drives on CANopen buses:
Modicon M340 b Altivar 312: For asynchronous motors from 0.18 to 15 kW/0.25 to 20 HP
b Altivar 71: For synchronous or asynchronous motors from 0.37 to 500 kW/0.5 to
700 HP
b Lexium 32: For servo motors from 0.15 to 7 kW/0.20 to 10 HP
b Lexium ILA/ILE/ILS: Integrated motor drives from 0.10 to 0.35 kW/0.13 to 0.47 HP
2 b Lexium SD328A: For 3-phase stepper motors from 0.35 to 0.75 kW/0.47 to 1 HP

In compliance with PLCopen specifications, the MFB library allows both easy and
Altivar 312
Altivar 71
flexible motion programming with EcoStruxure Control Expert (1), as well as axis
diagnosis.
CANopen

In maintenance operations, drives can be replaced quickly thanks to drive parameter


download blocks.

3 Setting up drives on the CANopen network is facilitated through Motion Tree


Manager organization in the EcoStruxure Control Expert (1) browser, making it easy
for users to access the application drives.
Lexium SD328A
Applications
Lexium 32 The features of the Motion Function Blocks library are particularly suitable for
machines with independent axes. In the case of these modular/special machines,
MFB function blocks are an ideal solution for controlling single axes. The following
4 Lexium ILA/ILE/ILS are typical applications for this type of architecture:
b Automatic storage/removal
b Material handling
MFB: Motion control distributed over CANopen b Palletizers/depalletizers
b Conveyors
b Packaging, simple labeling application
b Grouping/ungrouping

5 b Adjustment axes in flexible machines, etc.

Functions
The table below lists the function blocks of the MFB library and the compatible
drives. The prefix indicates the block family:
b MC: Function block defined by the Motion Function Blocks PLC Open standard
b TE: Function block specific to Schneider Electric products
6 b Lxm: Function block specific to Lexium servo drives

Type Function Function block Altivar 312 Altivar 71 Lexium 32 Lexium ILA/ Lexium
ILE/ILS SD328A
Management Read an internal parameter MC_ReadParameter
and motion Write an internal parameter MC_WriteParameter

7
Read the current position MC_ReadActualPosition
Read the instantaneous speed MC_ReadActualVelocity
Acknowledge detected error MC_Reset
messages
Stop any active movement MC_Stop
Axis coming to standstill MC_Power
Movement to absolute position MC_MoveAbsolute

8
Relative movement MC_MoveRelative
Additional movement MC_MoveAdditive
Homing MC_Home
Movement at given speed MC_MoveVelocity
Read diagnostic data MC_ReadAxisError
Read servo drive status MC_ReadStatus
Torque control MC_TorqueControl

9 Read actual torque value


Manual control
MC_ReadActualTorque
MC_Jog
Save and Read drive parameters and store TE_UploadDriveParam
restore in PLC memory
parameters Write drive parameters TE_DownloadDriveParam
(FDR) from PLC memory
Advanced Read a motion task Lxm_UploadMTask
Lexium
10
Write a motion task Lxm_DownloadMTask
functions
Start a motion task Lxm_StartMTask (1)
Set the reduction ratio, signed Lxm_GearPosS (1)
System Communication with the servo drive TE_CAN_Handler

Compatible (1) The Lxm_StartMTask and Lxm_GearPosS function blocks are only compatible with Lexium 32
(LXM32M) servo drives.

6/12
Setup Modicon X80 modules
Modicon X80 Expert modules
MFB motion control library

Motion Tree Manager


Motion Tree Manager is associated with MFB library of EcoStruxure Control
Expert (1) and integrated in its browser. It provides specific assistance for:
b Axis object management
1
b Axis variable definition
b Drive parameter management
Motion Tree Manager automatically creates links between the CANopen bus
configuration and the MFB function block data using a limited amount of

2
configuration data.

General axis parameters


In this tab, the designer is prompted to define:
b The name of the axis that will identify it in the browser for the entire application
b The address of the drive on the CANopen bus

Axis parameters
3
The drop-down lists in this tab are used to determine the exact type of drive: family,
version.

Variable names
This last tab is used to identify data structures:
b Axis_Reference: Used by the function block instances for the axis in question
4
b CAN_Handler: Used to manage communication with the drive via the CANopen
Motion Tree Manager integrated in the EcoSruxure Control network
Expert browser

Recipe definition
The recipes attached to the axis are the data structures containing the adjustment
parameters of a given drive. This data is used when:
5
b Changing the drive with restoration of the context during “Faulty Device
Replacement” (FDR) maintenance
b Changing the manufacturing program of the machine and calling up an
appropriate set of parameters: servo control gains, limitations, etc. adapted to
the weight and size of the moving parts
b Saving parameters in the initial values of the PLC application
6

Programming, diagnostics, and maintenance


Communication between the PLC and drive is automatically set up by the system
as soon as a TE_CAN_Handler instance is declared in the EcoStruxure Control
Expert (1) task with which the axis is associated. Movements are then programmed 7
by sequencing function blocks from the library in the user’s chosen EcoStruxure
Control Expert (1) editor (LD, ST, FBD).
General parameters: Axis name and address
The two function blocks, MC_ReadStatus, and in some cases MC_ReadAxisError,
are useful for determining the overall status of the axis, as well as the code of the

8
active detected errors.
The function blocks TE_UploadDriveParam and TE_DownloadDriveParam allow
the application to save the drive parameters (recipe) and to then quickly reload them
into another drive when it is necessary to change the original one.

(1) EcoStruxure Control Expert software continues the Unity Pro range of software and

9
corresponds to versions u 14 of Unity Pro.
MFB: Programming a movement in absolute mode

10

6/13
Presentation, Modicon X80 modules
description Modicon X80 Expert modules
Frequency input module

Presentation
The BMXETM0200H frequency input module offers turbine shaft and engine speed
1 monitoring functionality for general purpose turbomachinery control (TMC)
applications. It can be integrated into Modicon M340 and M580 standard and
high-availability systems.
TMC applications include prime movers, driven equipment, auxiliaries, mechanical
retrofits, and protection. With the Modicon Package solution, the frequency input and
measurement function is available for the following general purpose TMC application
types:
2 b Large hydro turbines
b Small steam turbine generators
b Small hydro turbines
b Small mechanical drive gas turbines
b Diesel generators
b Reciprocating compressors
b Packaged air compressors
3 b Single-stage mechanical drive turbines: pumps

Integration

Sampling

4
Inlet steam
Shaft speed

TTV
To DO card (turbine trip)
M340 local rack
To AI card (inlet pressure)

CV
To AO card (turbine control)

BMXETM0200H

5 Speed probe Turbine Generator

M580 local and remote racks To AI card (exhaust pressure)

Exhaust steam
TMC governor control system architecture

Functionality
BMXETM0200H_main_image

6
The purpose of the BMXETM0200H module is to monitor the turbine shaft or engine
speed. It is designed to receive electrical pulses generated by the gear tooth sensing
probe, cam, and crank etc. and convert these pulses into a numerical value. The
measured value of the turbine shaft rotating velocity is highly accurate with a fast
refresh rate.

With the BMXETM0200H module providing frequency input and measurement,

7
Modicon PACs build up a closed loop control system as part of the turbomachinery
governor. This control mechanism will automatically track and direct the speed of
driven equipment (such as a generator or compressor) and a prime mover (such as a
turbine or engine) under varying load conditions with the aim of:
b maintaining the selected speed
BMXETM0200H b limiting slow and fast speeds
b helping to protect mechanical parts and customer investment by anticipating
overspeeds by means of its acceleration and jerk detection capability
8

10

6/14
References Modicon X80 modules
Modicon X80 Expert modules
Frequency input module

Module specifications
Availability and compatibility
Available for Modicon M340 and M580 standalone and HSBY platforms, on local
rack or RIO rack with hot swapping supported.
1
Ambient operating temperature
Hardened with extended temperature range from -25…70 °C/-13…158 °F and
conformal coating.

Measurement performance 2
Two frequency input channels for 1 V and 1 Hz signal up to a maximum of 500 KHz
with 100 KHz, 10 KHz, and 1 KHz input filters.

Supported signal source device type

3
Speed sensor inputs support passive pickup, active speed sensor (output OC, TTL,
ST), potential transformer, and incremental encoder.

Digital reflex outputs


1 positive 24 VDC reflex digital output per channel controlled from an embedded
comparator.

Error detection
Detects broken wire and probe health status.
4
Dedicated TMC functions
A set of dedicated TMC functions for turbine shaft monitoring, including:
b Frequency pattern recognition up to 512 pulses per pattern

5
b Acceleration and jerk detection
b Phase angle and ratio detection between channels
b Scaling factor for RPM measurement up to 1,024 teeth per revolution
b Alarm bits that can be time-stamped by the Modicon M580 controller

Software configuration
Configurable using EcoStruxure Control Expert (1) or Unity Pro ≥ V11 (S, L, and XL)
with TMC Hotfix integrated.
6
Reference
Modicon X80 Frequency input module
Description Composition Reference Weight
kg/lb
Turbomachinery 1 ms cycle time
7
BMXETM0200H 0.124/
frequency input module 0.273
2 digital reflex outputs
(2 channels) for severe
environments 2 discrete inputs (for
frequency measurement
functions)

8
(1) EcoStruxure Control Expert software continues the Unity Pro range of software and
corresponds to versions u 14 of Unity Pro.

10

6/15
Presentation, Modicon X80 modules
description Modicon X80 Expert modules
Weighing module

Technology Presentation
Partner

1
The PMESWT0100 Scaime partner weighing module can be installed in :
™ b a Modicon automation platform including a dual Ethernet and X-bus BMEXBPpp00(H)
backplane and a Modicon M580 BMEP58p0p0 PLC, or
PMESWT0100 Scaime partner b a Modicon X80 RIO drop including a dual Ethernet and X-bus BMEXBPpp00(H)
weighing module
backplane and a BMECRA31210 adapter.
With this module, it is possible to go beyond the scope a of simple weighing
application: it is suitable for static weighing applications such as silo level

2
measurement and scale weighing; it is also well suited to low-speed dynamic
weighing applications such as filling, dosing, and material transfer.
The Modicon PLC can manage the whole weighing environment as well as the whole
machine or industrial process associated with the weighing system: weighing data is
accessible by the PLC via implicit exchanges or explicit commands. Once the
weighing signal is received, it is processed and transferred by the weighing module
to the Modicon M580 PLC via the Ethernet backbone.
This Ethernet weighing transmitter offline configuration, online calibration,
3 monitoring, and weighing diagnostics are achieved using EcoStruxure Control
Expert (1) software via FDT/DTM.
The Scaime partner weighing module has been developed to comply with the general
standards and certifications of the Modicon X80 modules. For more information, see
page 10/2 or consult our website.

1 Description
4
PMESWT0100_main_image

2 The PMESWT0100 weighing module features the following:


1  A rigid body providing support and protection for the electronic card
3 2  A module reference marking (a label is also visible on the right-hand side of the
module)
4
3  A module and channel status display block
4  Screw clamp terminals for connecting an external HMI output
5 5  Screw clamp terminals for connecting discrete reflex inputs
5 6
6  Screw clamp terminals for connecting discrete reflex outputs
7  Screw clamp terminals for connecting input load cells

7 Main characteristics
Measurement input
1 weighing channel per module, comprising up to 8 load cells connected via junction
box
6 PMESWT0100 Input load cell supply voltage
5Vc
Internal resolution
24-bit converter
User resolution
Up to 1,000,000, factory-calibrated 500,000 at 2 mV/V

7 Internal measurement rate


6 to 400 measurements per second
External measurement rate
100 measurements per second
Discrete reflex outputs
Number of applications
4 positive logic outputs, 2 for dosing and 2 for threshold monitoring
8 Maximum voltage
55 V c
Nominal current
400 mA
Response time
2 ms discrimination

9 Discrete inputs
Number of applications
2 positive logic inputs, weighing functions
Low voltage range
0…3 V c
High voltage range
9…28 V c
10 High current
20 mA at 24 V c
(1) EcoStruxure Control Expert software continues the Unity Pro range of software and
corresponds to versions u 14 of Unity Pro.

6/16
References Modicon X80 modules
Modicon X80 Expert modules
Weighing module

References
PMESWT0100_main_image

Modicon X80 Weighing module


Description Composition Reference Weight
kg/lb
1
Scaime partner - Load cell input 100 measurements/s PMESWT0100 (2) 0.233/
weighing module (1) (for 1 to 8 load cells) 0.514
(1 weighing channel per - 4 discrete reflex outputs (for threshold
module) monitoring and dosing)
- 2 discrete inputs (for weighing

2
Technology functions)
Partner - 1 output for an external HMI

(1) Partner Product, sold by SE and Scaime. Supported by Scaime, see our website.
(2) To order this product, please contact our Customer Care Center.
PMESWT0100

10

6/17
Contents 7 - I/O expansion modules

Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7/2

Modicon X80 Remote I/O drop adapters


b Modicon X80 Offer presentation............................................................ page 7/4
1
b Characteristics....................................................................................... page 7/4
b Performance and Standard adapters.................................................... page 7/5

Modicon X80 Peripheral Remote I/O drop adapter


b Presentation ........................................................................................... page 7/7
2
b Description, references ......................................................................... page 7/7

10

7/1
Selection guide Modicon X80 modules
Modicon X80 I/O expansion modules

Applications RIO drop adapter RIO drop adapter RIO drop adapter

1 1
Type of device Standard Performance Performance

2 2
Network protocols EtherNet/IP
Racks Maximum number per drop Up to 2
Structure Physical interface 10BASE-T/100BASE-TX
Type of connector 2xRJ45: 3xRJ45: 3xRJ45:
b 2 connectors for RIO network (RSTP ring topology) b 1 connector for service b 1 connector for service

3 Ethernet backplane connection No


b 2 connectors for RIO network (RSTP ring topology) b 2 connectors for RIO network (RSTP ring topology)
Yes 3
Access method CSMA-CD
Data rate 10/100 Mbps
Medium Double shielded twisted pair copper cable, category CAT 5E
Dimension WxHxD 32 x 100 x 86 mm/1.25 x 3.93 x 3.38 in.

4 4
Remote X80 I/O Maximum number of discrete I/O modules Up to 128 Up to 1024
Maximum number of analog I/O modules Up to 16 Up to 256
I/O modules supported Analog I/O All BMXApppppp
Discrete I/O All BMXDppppppp
HART integrated analog I/O modules – BMEAHI0812/BMEAHO0412
Communication modules supported Serial link – BMXNOM0200 BMXNOM0200

5 5
AS-i – BMXEIA0100 BMXEIA0100
PROFIBUS DP – PMEPXM0100 (1)
CANopen – BMECXM0100 (1)
Network Option switch – BMENOS0300
Expert modules supported Counter – BMXEHC0200/BMXEHC0800 BMXEHC0200/BMXEHC0800
Time-and date-stamping – BMXERT1604T/H BMXERT1604T/H
SSI encoder interface module – BMXEAE0300 BMXEAE0300

6 Frequency input
Weighing


BMXETM0200H BMXETM0200H
PMESWT0100
6
Standard services CCOTF (Change Configuration on the Fly) No Yes
Diagnostics for remote I/O devices (DDT) Yes
Port mirroring No Yes
System Time Stampig No 10 ms

7 7
Non-interfering Type 1 No Yes
Network redundancy Yes (logical, 50ms recovery time)
Module redundancy No
I/O service b Input data is collected and published to the remote I/O head adaptor
b Output modules are updated with the data received from remote I/O head adaptor
Communication services EtherNet/IP Adapter Yes
QoS (Quality of Service) Yes
RSTP media redundancy Yes
8 NTP/SNTP time synchronization
FDR Service
SNTP (Client)
Yes (Client)
8
SNMP Network management SNMPV1 (Agent)
Syslog Yes (Client)
CIP Explicit messaging (Server) Yes
Modbus/TCP server for module diagnostics Yes

9 Compatibility with processor Modicon M580 BMEP58pp40(S)


Modicon M580 BMEH58pp40(S)
Modicon Quantum
Modicon M580 BMEP58pp40(S)
Modicon M580 BMEH58pp40(S) 9
References
BMXCRA31200 BMXCRA31210 BMECRA31210
Page 7/6
(1) Not supported in a distant rack in a hot standby configuration

10 10

More technical Information on www.se.com More technical Information on www.se.com

7/2 7/2
7/3
Presentation Modicon X80 modules
Modicon X80 I/O expansion modules
Remote I/O drop adapter

Modicon X80 Remote I/O drop adapters


BMECRA31210_main_image

Offer presentation
1 A Modicon M580 Ethernet RIO (EIO) architecture with Modicon X80 I/O drops
requires the use of Modicon X80 remote I/O drop adapters in each remote rack to
connect Modicon X80 I/O, communication, and expert modules.
The remote I/O drop adapter connects to the RIO network to ensure network
determinism on a dedicated private network connected to the Modicon M580 CPU.
The Modicon X80 modules are integrated and seen by the EcoStruxure Control
2 Expert engineering software as if they were local I/Os, with a high-level of
integration in terms of configuration and diagnostics.
Modicon X80 offer comprises three I/O drop adapters:
b Performance drop adapters BMECRA31210 and BMXCRA31210
BMECRA31210 b Standard drop adapter BMXCRA31200
For severe environments, BMpCRA31210 adapters are also available in a

3
conformal coating version (suffix «C»): see page 9/3 for more details.

Adapter compared suitability


According to the considered RIO architecture, each I/O drop adapter presents the
most suitable features as shown in the table below:
Modicon X80 I/O Communication Safety Controllers
drop adapter Ethernet X-Bus Safety Non-Safety Quantum M580
4 BMXCRA31210 (C) U U U U U
BMXCRA31200 U U U U
BMECRA31210 (C) U U U U U

Characteristics

5 Connecting I/O drop adapters


Each adapter uses one slot in the Modicon X80 rack and is connected by Ethernet
cordsets equipped with RJ45 connectors.
Depending on the distance between the main local rack and remote drops, RIO
drop adapters are connected via copper cable (up to 100m) or fiber optic cable (up
to 15 km). A DRS switch may be used to extend the distance betwen devices
connected through fiber optic.
6 DIA6ED2151012EN
Supported modules
Depending on model, Modicon X80 Remote I/O drop adapters support various
types of modules (1):
b All Modicon X80 I/O modules (HART I/O modules only supported by
BMECRA31210)
b Modicon X80 communication modules (except for BMXCRA31200), like Serial
7 link, AS-Interface, PROFIBUS DP, CANopen, and Network option swtich
modules.
b Modicon X80 expert modules (except for BMXCRA31200), like counter,
time-stamping, SSI encoder, Frequency input, and weighing modules.
Redundancy
Redundancy brings service continuity by preventing process downtime and by
8 facilitating repairability and maintenance.
With BMpCRA312p0 adapters, the dual Ethernet network connection port allows
daisy chain loop connections using the RSTP protocol (Rapid Spanning Tree
Protocol), in a ring topology.

(1) Please refer to Selection guide page 7/2 for details.

10

7/4
Presentation, Modicon X80 modules
description Modicon X80 I/O expansion modules
Remote I/O drop adapter – Performance and Standard

Modicon X80 Remote I/O drop adapters (continued)

1
Performance Remote I/O drop adapter BMECRA31210
BMECRA31210_main_image

Presentation

1 BMECRA31210 Performance RIO drop adapter is designed to be installed on an


Ethernet backplane in the main remote rack (only one BMECRA31210 module
2 installed per Modicon X80 RIO drop). This module can also support a
BMXXBPpp00 expansion rack. BMECRA31210 adapter features:
3 b Supports both Ethernet and X-bus communications across the remote
backplane.
b Supports Modicon X80 I/Os and TPP partner modules with both Ethernet and
2
4
X-bus connections (1).
b Supports all expert modules (e.g. counter and weighing modules) and
5
communication modules (e.g. Serial, PROFIBUS)
b Time-stamping can be managed with a resolution of 10 ms for Modicon X80 RIO
drops on Ethernet backplane
3
BMECRA31210
b Supports Change Configuration on the Fly (CCOTF).

Description
1  LED display block indicating the module status
2  Rotary switches for setting the address of an EIO drop (00…159)
3  Dedicated RJ45 service port (ETH 1) for remote service tools such as a PC, HMI
terminal module, or Ethernet DIO devices
4  RJ45 device network port (ETH 2) for connection to the Ethernet network
5  RJ45 device network port (ETH 3) for connection to the Ethernet network 4
Note: The keying pin on the rear side of the module prevents BMECRA31210 from
being installed on unsupported backplanes.

Performance Remote I/O drop adapter BMXCRA31210 (2)


BMXCRA31210_main_image

Presentation

1
BMXCRA31210 Performance RIO drop adapter is designed to be installed on an
Ethernet backplane in the main remote rack (only one BMXCRA31210 module
5
2 installed per Modicon X80 RIO drop). This module can also support a BMXXBPpp00
expansion rack.
3 BMXCRA31210 adapter features:
b Support of X-bus communications only across the remote backplane.
b Support of Modicon X80 I/O and partner modules only with X-bus connections.
6
4
b Supports of several expert modules such as counter modules, as well as Change
5 Configuration on the Fly (CCOTF).
b Time-stamping can be managed with a resolution of 10 ms for Modicon X80 RIO
drops on an Ethernet backplane
BMXCRA31210
Description
1  Display block indicating the module status
2  Rotary switches for addressing EIO drops (00…159)
3  Dedicated RJ45 SERVICE port for remote service tools such as a PC, an HMI
7
terminal, or Ethernet DIO devices (identical to the SERVICE port on Quantum
CRP/CRA modules, see page 2/6)
4  RJ45 DEVICE NETWORK port for connection to the Ethernet network
5  RJ45 DEVICE NETWORK port for connection to the Ethernet network

8
(1) This module is also compatible with X-bus backplanes. In this case it has the same
functionality as a BMXCRA31210 Performance Ethernet drop adapter. For more details,
see our website.
(2) Also compatible with Quantum PLC

10

7/5
Presentation, Modicon X80 modules
description Modicon X80 I/O expansion modules
Remote I/O drop adapter – Performance and Standard

Modicon X80 Remote I/O drop adapters (continued)


Standard Remote I/O drop adapter BMXCRA31200 (1)
1
BMXCRA31200_main_image

Presentation
1 BMXCRA31200 Standard RIO drop adapter is a basic adapter designed to be
installed on an Ethernet backplane in the main remote rack (only one
2 BMXCRA31200 module installed per Modicon X80 RIO drop and no expansion
rack allowed).
BMXCRA31200 Standard adapter features:

2 4
b Supports X-bus communications only across the remote backplane.
b Supports only Modicon X80 I/O discrete and analog modules (except for HART
I/O modules). Neither expert nor communication modules are supported.
5 b No time-stamping, no Change Configuration on the Fly (CCOTF).

BMXCRA31200
Description
1  Display block indicating the module status
3 2  Rotary switches for addressing EIO drops (00…159)
4  RJ45 DEVICE NETWORK port for connection to the Ethernet network
5  RJ45 DEVICE NETWORK port for connection to the Ethernet network

References
Modicon X80 Remote I/O drop adapters

4
Description SERVICE Device ports Height Reference Weight
port mm/in kg/lb
Modicon X80 RIO drop 1 2 (RSTP) 100/ BMXCRA31200 0.225/
adapter (Standard) RIO Network 3.93 0.496
Modicon X80 RIO drop 1 2 (RSTP) 100/ BMECRA31210 0.225/
adapters (Performance) RIO Network 3.93 0.496
2 (RSTP) 100/ BMXCRA31210 0.225/
RIO Network 3.93 0.496
5 (1) Also compatible with Quantum PLC

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 4/2 page 8
 /2 page 9
 /2

7/6
Presentation, Modicon X80 modules
characteristics, Modicon X80 I/O expansion modules
Peripheral remote I/O adapter
description,
reference

Presentation
The BMXPRA0100 Peripheral remote I/O adapter is dedicated to Modicon X80 DIO
M340
M580
drops in a Modicon M340 or Modicon M580 I/O architecture using Ethernet
Modbus/TCP.
1
Ethernet Modbus/TCP The BMXPRA0100 module manages a remote X80 I/O rack on Ethernet Modbus/
TCP which includes:
b discrete I/O modules
b analog I/O modules
Modicon X80 Modicon X80 Modicon X80

2
DIO drop DIO drop DIO drop It communicates by I/O scanning with the master PAC (Modicon M340 or
Modicon X80 DIO drops in an Ethernet Modbus/TCP network Modicon M580).
In case of a redundant Ethernet link, the use of a BMXNOE0100 Ethernet module is
required.

Main characteristics

3
Primary racks per drop
Up to 4
Discrete I/O modules
Up to 1,024
Analog I/O modules
Up to 256
Internal memory 4
Up to 448 Kbits
Memory card capacity
Up to 96 Kbits
Average consumption
95 mA
Dissipated power
5
2.3 W
Real time clock with battery backup
Yes

Description 6
1 1  Module reference
BMXPRA0100_main_image

2 2  Display block indicating the module status


3  Memory card port with protective cover
3 4  RJ45 Ethernet port
4
Reference (1) 7
Description Reference Weight
kg/lb
Modicon X80 Peripheral remote I/O adapter BMXPRA0100 –
Provides 1 module per Ethernet
Modbus/TCP DIO drop

Modicon X80 Peripheral


remote I/O adapter 8
(1) Requires Unity Pro software u V4.1 or EcoStruxure Control Expert.

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 3/2 page 4
 /2 page 8
 /2 page 9/2

7/7
Contents 8 - Communication modules *

Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8/2

Modicon X80 AS-Interface module


b Presentation, description...................................................................... page 8/4
1
b Diagnostics, references......................................................................... page 8/5

Modicon X80 Modbus and Character mode serial link module


b Presentation, description...................................................................... page 8/6
b Characteristics, references................................................................... page 8/7 2
Modicon X80 CANopen module
b Presentation, description...................................................................... page 8/8
b Diagnostics, references......................................................................... page 8/9

Modicon X80 PROFIBUS DP module 3


b Presentation, description, architecture.............................................. page 8/10
b Software configuration, diagnostics, references................................page 8/11

Modbus Plus Proxy


b Presentation, description.................................................................... page 8/12 4
b References............................................................................................ page 8/13

Modicon X80 Fiber converter modules


b Presentation, description.................................................................... page 8/14
b References............................................................................................ page 8/14
5
Modicon X80 Ethernet switch module
b Presentation, description.................................................................... page 8/15
b References............................................................................................ page 8/15

6
* Communication modules specific to Modicon M580 ePAC or Modicon M340 PAC
are not described in this chapter, please refer to Modicon M580 and Modicon M340
catalogs.

10

8/1
Selection guide Modicon X80 modules
Modicon X80 communication modules

Applications AS-Interface communication Serial link communication CANopen communication PROFIBUS communication Modbus Plus communication

1 Type of device AS-Interface module Modbus and Character mode serial link module CANopen module PROFIBUS DP module Modbus plus Proxy
1

2 2

Network protocols

3 3
AS-Interface Modbus and Character mode CANopen PROFIBUS DP Ethernet Modbus/TCP Modbus Plus

Structure Physical interface AS-Interface V3 standard b Non-isolated: RS-232, 8-wire ISO 11898 RS-485 10/100BASE-TX RS-485
b Isolated: RS-485, 2-wire
Type of connector 3-way SUB-D 1xRJ45 and 2XRJ45 9-way SUB-D male 9-way SUB-D female 2 x RJ45 2 x 9-way female SUB-D
Access method Server/Client – Server/Client Server/Client, Token passing CSMA/CD HDLC -Token passing
Data rate 167 Kbps 0.3...115.2 Kbps in RS 232 500 Kbps at 100 m/328 ft 9.6 kbit/s at 1200 m/3.937 ft 10/100 Mbps 1 Mbps
0.3...57.6 Kbps in RS 485 1 Mbps at 20 m/65.62 ft 12 Mbit/s at 100 m/328 ft

4 Medium 2-wire AS-Interface cable Shielded twisted pair copper cable Shielded twisted pair copper cable Shielded twisted pair copper cable Double shielded twisted pair copper cable,
category CAT 5E (direct or crossover)
Shielded twisted pair copper cable
4
Configuration Maximum number of devices 62 clients 2 per drop, 16 per Ethernet remote I/O (RIO) network 63 clients 10 maîtres, 125 clients 128 32 per segment
max. 64 for all segments
Maximum length 100 m/328 ft, 15 m/49.21 ft with non-isolated RS 232, 100 m/328 ft 1200 m/3.937 ft per segment 100 m/328 ft 450 m/1.476 ft per segment
500 m/1640 ft max. with 2 repeaters 1000 m/3280 ft with non-isolated RS 485 2,5 m/8.202 ft with repeater 1,8 m/5.905 ft with 3 repeaters
Number of links of the same type per BMXP341000 processor: 20/36 application-specific channels with Limitation depends on number of available Up to 10 PMEPXM0100 modules in total with a 1 TCSEGDB23F24FA max.

5 5
station 2 AS‑Interface modules BMXP341000/BMXP342ppp (1 application-specific Ethernet slots in Modicon M580 Local and Modicon M580 BMEP586040 processor
channel = 1 counter, motion control, or serial link Remote Racks
module channel)
BMXP3420p0 or BMEP58 processor: 36 application specific channels max. Each BMECXM0100 counts as a DIO device.
4 AS‑Interface modules 6 BMXNOM0200 modules per BMpCRA31p10 Number of DIO devices depends on CPU/NOC
Ethernet drop adapter capacity and IO scanner memory
BMpCRA31210 Ethernet drop adapter: All M580 processors: 36 application-specific –
2 AS-Interface modules channels
6 Standard services Transparent exchanges with sensors/actuators Read/write bits and words, Transparent exchanges with CANopen clients Cyclic data exchange (master class1) Modbus/TCP messaging Modbus Plus messaging
6
Diagnostics in Modbus mode and Ethernet-based processors Acyclic data exchange (master class2)
Conformity class M4 profile – EDS description files of the clients PI International certified – –

Communication Gateway DTM No No Yes Yes No No


services
7 7
FDR Service No No Yes Yes Yes No
SNMP Network Management No No Yes (Agent) Yes (Agent) Yes (Agent) No
Syslog No No Yes (Client) Yes (Client) No No
Modbus Plus server No No No No Yes (scanned by the PLC) No
Read/Write variables No No No No No Yes
Global Data No No No No No Yes

8 8
Peer Cop service No No No No No Yes
Compatibility with processor Modicon M340, Modicon M580 Modicon M580 only Modicon M340, Modicon M580

References
BMXEIA0100 BMXNOM0200 BMECXM0100 PMEPXM0100 TCSEGDB23F24FA
Page 8/5 8/7 8/9 8/11 8/13

9 9

10 10

More technical Information on www.se.com More technical Information on www.se.com

8/2 8/2
8/3
Presentation, Modicon X80 modules
description 4 Modicon X80 Communication modules
AS-Interface module

Presentation
The BMXEIA0100 server module for AS-Interface cabling system provides the
1 AS-Interface system server function for the Modicon automation platform.
Modicon M340/ Modicon M580 / X80 RIO drop
Third-party AS-Interface device

3
Third-party AS-Interface device
Third-party AS-Interface device Tesys U

The AS-Interface cabling system consists of a server station and client stations.
The server supporting the AS-Interface profile interrogates the devices connected
on the AS-Interface line one-by-one and stores the information (actuator/sensor
status, device operating status) in the PLC memory. Communication on the
AS-Interface line is managed totally transparently in relation to the application PLC
4 program.
The BMXEIA0100 module supports the latest management profile for
AS-Interface devices (AS-Interface V3), which is able to manage level V1, V2, and
V3 AS-Interface clients:
b Discrete client devices (up to 62 devices of 4 inputs/4 outputs organized in
2 banks (A/B) of 31 addresses each)
b Analog devices (up to 31 devices (4 channels) in bank A)
5 b Safety interfaces (up to 31 devices in bank A)
An AS-Interface power supply is essential for powering the various devices on the
line. Ideally it should be placed near stations that consume a great deal of energy.
Please refer to the “Phaseo AS-i ABL Single phase power supplies 2.4 and 4.8 A for
AS-Interface wiring system” catalog.
A Modicon M340 Performance configuration with a BMXP3420p0/20p02 processor
or a Modicon M580 configuration with a BMEP58pppp processor can take 4
6 BMXEIA0100 modules. A Standard configuration with BMXP341000 processor
can take 2 BMXEIA0100 modules.

Description
The BMXEIA0100 AS-Interface module is standard format (1 slot). Its housing
provides IP20 protection of the electronics and it is locked into each rack slot (01

7 1
….11) by a captive screw.
The front panel of the BMXEIA0100 AS-Interface module features:
BMXEIA0100_main_image

2 1 A rigid body providing support and protection for the electronic card
2 A module reference marking
3
3 A display block with 5 LEDs indicating the module operating modes:
4 - RUN (green): Module running
- ERR (red): Detected module fault
8 5
- A/B (green): Displays the group of 31 clients
- I/O (red): Detected I/O fault on AS-Interface line
- 32 LEDs for diagnostics of the AS-Interface line and each client connected
on the line depending on the A/B pushbutton selection (1)
6 4 2 LEDs marked ASI POWER and FAULT: AS-Interface external power supply
present and detected AS-Interface line fault (see diagnostics on page 8/5)
5 Two pushbuttons marked A/B and MODE (see diagnostics on page 8/5)
9 BMXEIA0100 6 A 3-way male SUB-D connector for the AS-Interface cable (female screw clamp
connector supplied)

___________________________________________________________________________
(1) Depending on whether A or B is selected, this displays either the first 31 clients (standard
addressing) or the last 31 clients (extended addressing).

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 2
 /2 page 2/6 page 4
 /2 page 8
 /2 page 9
 /2

8/4
Diagnostics, Modicon X80 modules
references Modicon X80 Communication modules
AS-Interface module

Diagnostics
The two LEDs 4 on the module front panel are used in conjunction with the two
pushbuttons 5 for module diagnostics: 1
LEDs Pushbuttons
4 ASI PWR: 4 FAULT: Detected 5 A/B: Selects the 5 MODE: Module
AS-Interface AS-Interface line fault group of clients on the Offline/Online
power supply present display block 3

The display block on the front panel of the BMXEIA0100 server module can be
used to perform simplified local diagnostics by displaying the client devices present 2
on the AS-Interface line.
Detailed diagnostics of each client device is also possible using:
b An adjustment terminal (1)
b A Web browser using the Rack Viewer function in the standard Web server on
the Modicon X80 modules. For further information, please consult our website.
Rack function display in Web browser
3
References
Modicon X80 AS-Interface module
Description Usage Reference Weight
kg/lb
AS-Interface module M4 AS-Interface profile BMXEIA0100 0.340/
supplied with 3-way male
SUB-D connector
for level V1, V2, and V3
clients
0.750
4
(1) For instance, see our Bihl+Wiedemann partner offer.

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 2/6 page 4
 /2 page 8
 /2 page 9
 /2

8/5
Presentation, Modicon X80 Modules
description Modicon X80 Communication modules
Modbus and Character mode serial link module

Presentation
The Modbus serial link is used for client/server architectures (it is necessary,
1 however, to check that the Modbus services used by the application have been
implemented on all relevant devices).
Harmony

Modicon M340/Modicon M580/ Modicon X80 RIO drop

2
Modbus
splitter block
Modbus

Foxboro

4
Power Logic Third-party Modbus device Altivar

The bus consists of a client station and server stations. Only the client station can
initiate the exchange (direct communication between server stations is not
possible). Two exchange mechanisms are available:
b Question/response, where requests from the client are addressed to a given
server.The client then waits for the response from the server that has been

5 interrogated.
b Broadcasting, where the client broadcasts a message to all server stations on the
bus. The latter execute the order without transmitting a reply.
b It is necessary to use BMpCRA31p10 modules as drop adapters. On one drop it
is possible to plug a maximum of two BMXNOM0200 modules.
The following services are not available in the server stations:
v Modbus server
6 v Modem services
Although most processors have a serial link that can support modems, the
BMXNOM0200 2-channel serial link module is particularly recommended for this
type of use.
Its performance and numerous parameter-setting options make it ideal for any type
of configuration, especially when using radio modems.

7 1 Description
BMXNOM0200_main_image

Modicon X80 serial link module


2 The front panel of the BMXNOM0200 serial link module features :
1 A screw for locking the module in a slot in the rack.
2 A display block with 4 LEDs:
- RUN (green) and ERR (red): Module status
8 3a - For each of the two channels: SER COM (green): Activity on the serial link
- (lit)/ detected fault on a device present on the serial link (flashing)
3b 3  Two RJ45 connectors (exclusive use) for connection of channel 0 (with black
indicator):
4 v 3a A connector for RS 232C connection, marked “COM Port 0 RS232”.
v 3b A connector for RS 485 connection, marked “COM Port 0 RS485”.
4  An RJ45 connector for RS 485 connection of channel 1, marked “COM Port 1
9 BMXNOM0200 RS485”, with black indicator.
To be ordered separately:
RS 485 cordsets (refer to the “Modicon M580 automation platform” catalog available
on our website) or RS 232 cordsets for DCE terminal (see page 8/7).

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 2
 /2 page 2/6 page 4
 /2 page 8
 /2 page 9
 /2

8/6
Characteristics, Modicon X80 Modules
references Modicon X80 Communication modules
Modbus and Character mode serial link module

Complementary characteristics
The following characteristics complement those indicated in the selection guide on
page 8/2. 1
BMXNOM0200 module serial links
b Physical interface:
v Port 0 RS 232 : RS 232 8-wire, non-isolated
v Port 0 and port 1 RS 485 : RS 485 2 wire, isolated

2
b Frame:
v Modbus : RTU/ASCII, full duplex in RS 232, half duplex in RS 485
v Character mode: full duplex in RS 232, half duplex in RS 485
b Data rate:
v Port 0 RS 232 : 0,3...115 kbit/s (Modbus/mode caractères)
v Port 0 et port 1 RS 485 : 0,3...57,6 kbit/s (Modbus/Character mode)
b Line polarization:

3
v Modbus RS 485 : automatic
v RS 485 Character mode: configurable with EcoStruxure Control Expert (1)
software
EcoStruxure Control Expert b Maximum length of a tap link in RS 485 2-wire:
Monitor v 15 m/49 ft in a non-isolated link
v 40 m/131 ft in an isolated link.
b Expert mode (from version V1.2 of the module and version V5 of Unity Pro (1): used to
configure the time out links individually from the application and thus adapt to the
specific characteristics of certain modems. 4
References (2)
BMXNOM0200_main_image

Modicon X80 serial link module


Description Protocol Physical layer Reference Weight
kg/lb
2-channel serial link Modbus client/
module (3) server RTU/ASCII,
Character mode
1 non-isolated RS
232 channel (Port
0)
BMXNOM0200 0,230/
0,507 5
GSM/GPRS modem 2 isolated RS 485
channels (Port 0
and Port 1)
Cordons pour liaison série RS 232 (4)
Description Connection Number of Length Reference Weight

Cordset for Data RJ45


wires m/ft
3/9,84 TCSMCN3M4F3C2
kg/lb
0,150/
6
BMXNOM0200 Terminal connector 0,331
Equipment (DTE) and 9-way
(printer) female
SUB-D
connector
Cordset for Data RJ45 4-wire 3/9,84 TCSMCN3M4M3S2 0,150/
Communication
Equipment (DCE)
connector
and 9-way
(RX, TX, RTS,
CTS)
0,331
7
(modem, etc.) female 8-wire 3/9,84 TCSXCN3M4F3S4 0,165/
SUB-D (excluding RI 0,364
connector signal)

(1) EcoStruxure Control Expert software continues the Unity Pro range of software and
corresponds to versions ≥ 14 of Unity Pro.
8
(2) Requires Unity Pro software ≥ V4.1 or EcoStruxure Control Expert
(3) For the ruggedized version, BMXNOM0200H, see characteristics on page 9/9.
(4) RS 485 serial link connection (refer to the “Modicon M580 automation platform” catalog
available on our website).

DIA6ED2151012EN
9

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1/10 page 2/2 page 2/6 page 4/2 page 8/2 page 9/2

8/7
Presentation, Modicon X80 modules
description Modicon X80 Communication modules
CANopen module

Presentation
CANopen is an open network supported by more than 600 companies worldwide,
1 and promoted by CAN in Automation (CiA). With the general acceptance of
CANopen, Schneider Electric has the accumulated and proven experience of
applying CANopen in machine solution platforms.
CANopen helps to ensure reliable and deterministic access to real-time data in field
devices. As a consequence, products using CANopen are increasingly used in
control system architectures. The BMECXM0100 CANopen module provides

2
powerful access to the CANopen clients from the Modicon M580 local rack or a
remote Modicon X80 drop.
Engineering System Operator
station servers Clients Advantages
BMECXM0100 is designed to fulfill customer needs by offering the following
advantages:
b Operational intelligence:
CXM
v Complete software integration into EcoStruxure Control Expert or Unity Pro with
3 M580 a predefined catalog of preferred devices and numerous automated operations
such as device variable creation, IP/DHCP settings, and IO scanner
configuration
Device network CXM v Simple integration of third-party devices
b Maintenance excellence:
v Robust and well-designed with a long life cycle following Modicon X80
standards
4 RIO
v Built to withstand extreme temperatures (-25 ºC to +70 ºC/-13 ºF to +158 ºF),
ATEX certified
sub-ring v Easy diagnostics by maintenance engineers via a simple Web browser (no need
for Unity) and the FDR (Fast Device Replacement) service
CXM b Investment protection: Totally flexible topologies with the possibility of using
several BMECXM0100 modules in a single Modicon M580, or in a remote I/O
drop closest to the process
5 Typical topology to connect CANopen devices to Modicon
b Time-to-market: Simple, compact size, all in one, which reduces installation time
b Enhanced protection and security: Integrated cybersecurity design helps to
M580 platforms or Modicon X80 drops with BMECXM0100 protect plant operations

Description
The BMECXM0100 CANopen module is standard format (1 slot) and supports one

6
CANopen port (SUB-D9 male connector).
The BMECXM0100 supports up to 63 clients with a maximum process image size
of 4 Kbytes IN/4 Kbytes OUT.
Standardized baudrates between 20 Kbd and 1 Mbd (20 Kbd, 50 Kbd, 125 Kbd,
250 Kbd, 500 Kbd, 1 Mbd) are supported.
Depending on the performance level required by the process, the BMECXM0100
module can be scanned by the RIO or the DIO scanner of the Modicon M580 CPU.
7 RIO scanning helps to ensure optimum performance, in sync with the PLC task
(MAST, FAST or AUX).
Configuring CANopen with EcoStruxure Control Expert
Several BMECXM0100 modules can be connected to the same or different I/O
scanners in the same Modicon M580 PAC.
BMECXM0100 modules are not compatible with redundant Modicon M580
architectures and cannot be scanned by an Ethernet module including

8 BMENOC03p1 and BMXNOC0402.


Third-party CANopen clients can only be configured in BMECXM0100 modules
from their EDS description files and via the hardware catalog manager. They
cannot be configured from their DTM. Communication between the device and its
DTM over Ethernet IO is also not supported.

10

8/8
Diagnostics, Modicon X80 modules
references Modicon X80 Communication modules
CANopen module

Diagnostics
BMECXM0100_main_image

The 5 LEDs 1 on the module front panel are used for quick CANopen communication
1 diagnostics:
LED Color Description
1
I/O Red Indicates the exchange status with CANopen
devices
BS (Bus Status) Red /Green Indicates the EtherNet/IP connection status
Yellow Firmware upgrade in progress
CAN RUN Green Indicates the status of the CANopen fieldbus 2
2 CAN ERR Red Indicates the status of the CANopen physical layer
and indicates detected errors due to missing CAN
messages (SYNC, node-guarding, or heartbeat)
BMECXM0100 CAN COM Yellow Dedicated to SDO transmission

References 3
Modicon X80 CANopen module
Description Reference Weight
kg/lb
Communication module used in Modicon M580 platform; BMECXM0100 –
supplied with male 9-way SUB-D connector 2 (1)

4
(1) For the ruggedized version BMECXM0100H, see page 9/9.

10

8/9
Presentation, Modicon X80 modules
description, Modicon X80 Communication modules
architecture PROFIBUS DP module

Presentation
Overview
1 The Modicon X80 PROFIBUS DP module allows the user to integrate
PROFIBUS DP client devices into Schneider Electric Modicon M580 control system
PMEPXM0100 PROSOFT
partner PROFIBUS module to exchange process, alarming, and diagnostic data with PROFIBUS DP devices as
well as to provide configuration and asset management of client devices using
Device Type Managers (DTMs).
This is an advanced in-rack solution for your PROFIBUS system compliant with

2 High-availability (HSBY system) and Standalone common Safety architectures.


Latest versions of Modicon M580 CPU and BMECRA31210 Modicon X80 Remote
I/O drop adapter firmware and software are necessary to operate the module:
EcoStruxure ProSoft
Configurator for b CPU version u V2.80
Control Expert
Modicon tool b BMECRA31210 version u V2.40 if the module is used in a remote drop
(PCM)
b EcoStruxure Control Expert u V14
b ProSoft Configurator for Modicon tool (PCM)

3 Advantages
The Modicon X80 PROFIBUS DP module is designed to meet customer needs by
offering the following advantages:
b High performance, with up to 125 client devices behind one module
(2 Kb IN/2 Kb OUT), and up to 10 PROFIBUS servers in one Modicon M580
CPS 0
PSS 2 3
configuration
4
XM
4002 4040 0100

ProSoft
b Real-time PROFIBUS network analyzer with packet capture tool: accelerates
the troubleshooting phase, fine tunes network options, and anticipates any
maintenance needs
b Simple and ergonomic ProSoft Configurator for Modicon (PCM) with easy import
Interaction between EcoStruxure Control Expert, Prosoft
Configurator for Modicon (PCM tool), and Modicon X80 into EcoStruxure Control Expert to efficiently build the PROFIBUS architecture
PROFIBUS DP module b Easy modernization from Quantum PTQ, user-friendly interface
b Achilles Level 2, HTTP, SNMP, Access control & Sys Log

5 EcoStruxure
Description
Control Expert Modicon X80 PROFIBUS DP module is a PROFIBUS DP V1 server class 2 module
that can be plugged in the Modicon M580 local rack or in any remote drop
supporting the Modicon M580 Ethernet backplane depending on the architecture. It
has an Autoscan feature to automatically poll and configure all the active clients
connected to the bus.

6 PROFIBUS DP
The PROFIBUS Communication DTM library is provided to enable the module
interface by PROFIBUS Asset Management Tools.
PROFIBUS PA
“On the flyˮ operations, such as changing parameters or adding a new device
online, are allowed.
The module is refreshed based on the RPI values, asynchronous to the periodic
tasks. This refreshment is achieved via the Mast task with limited impact on the task

7
duration, which is proportional to the device number.
The Modicon X80 PROFIBUS DP module can be scanned by the Modicon M580
CPU as well as by any Ethernet module (BMENOCpppp). Nevertheless, the CPU
capacity (mainly memory) is designed to be capable of managing all Modicon X80
PROFIBUS DP modules installed in the configuration. This simplifies the
architecture and the process of modifying client parameters via the “on the flyˮ
Standalone topology to connect Modicon X80 PROFIBUS DP
module to Modicon M580 or Modicon X80 drop with
feature, as well as that of adding new devices.

8 PMEPXM0100 An advanced operating mode provides the option to stop the module while
the PLC is in RUN in order to manage any modification without stopping the
process.
EcoStruxure
Control Expert Architecture
The Modicon X80 PROFIBUS DP module can be integrated into two types of
architecture:

9 b Standalone:
v Local racks and remote racks
v Up to 6 modules in one configuration for high-end Modicon M580 CPU
v Common Safety
PROFIBUS DP
b High availability (HSBY system):
v Local rack only
PROFIBUS PA v Up to 6 modules in each rack for high-end Modicon M580 CPU

10
Redundant (HSBY) topology to connect the Modicon X80
PROFIBUS DP module to Modicon M580 platform or
Modicon X80 drop with PMEPXM0100

8/10
Software configuration, Modicon X80 modules
diagnostics, Modicon X80 Communication modules
references PROFIBUS DP module

ProSoft Configurator for Modicon tool (PCM)


The following are required to configure the PMEPXM0100 Modicon X80 PROFIBUS
DP module:
b EcoStruxure Control Expert V14 and higher
1
b ControlExpert_V140_HF_PMEPXM0100
b ProSoft Configurator for Modicon tool (PCM)

There is a strong interaction between EcoStruxure Control Expert and the Prosoft
Configurator for Modicon (PCM). The ProSoft Configurator for Modicon tool (PCM)
also provides the finest level of information and diagnostics on the module, on
the bus, and on all the clients. This tool is available at no additional cost on the
2
Schneider Electric website in the product page section.

The PROFIBUS DP module is integrated from EcoStruxure Control Expert with


ProSoft Configurator for Modicon tool (PCM) high-level services:
b It is included natively in the EcoStruxure Control Expert (1) hardware catalog
b Exhaustive Device DDT for advanced control and diagnostics
3

Diagnostics and monitoring


The 7 LEDs on the module front panel are used for quick PROFIBUS DP fieldbus 6
communication diagnostics.

The Modicon X80 PROFIBUS DP module provides a range of statistics that can
assist with module operation, maintenance, and fault finding. The statistics can be
accessed by the Prosoft Configurator for Modicon or via the Web server embedded
in the module.
7
PMEPXM0100 status monitoring - Live List

References
Modicon X80 PROFIBUS DP module
8
PMEPXM0100_main_image

Description Reference Weight


kg/lb
Used for Modicon M580 platform PMEPXM0100 0.270/
fieldbus communication 0.595

9
PMEPXM0100 (1) EcoStruxure Control Expert software continues the Unity Pro range of software and
corresponds to versions u 14 of Unity Pro.

10

8/11
Presentation Modicon X80 modules
Modicon X80 Communication modules
Modbus Plus Proxy

Presentation
The TCSEGDB23F24FA Modbus Plus Proxy module is a network gateway that
1 allows Modicon M340 and Modicon M580 PLCs to communicate with existing
Modbus Plus devices.
It is not necessary to modify the applications for these devices to communicate with
the Modicon M340 and Modicon M580 PLCs, since the module automatically
addresses the platforms and the various communication functions between the
Modicon M340/ Modicon M580 and other PLC platforms (especially 984LL).

2 The Modbus Plus Proxy offers Modbus Plus PLC users the chance to integrate
Modicon M340 and Modicon M580 PLCs easily into their Modbus Plus network and
thus to access advanced communications via Ethernet, or to migrate gradually from
other PLC models to Modicon M340/Modicon M580 and EcoStruxure Control
Expert (1).

3 SCADA Web
configuration
interface

Compact 984

5
Distributed
I/O Modbus Plus Modicon M340
Proxy

Modicon M580

6 Modbus Plus Ethernet

Key benefits
Reduced startup time
b Online configuration of the proxy via a simple Web browser

7 b Web page setup similar to the screens of the Modbus Plus Peer Cop utility,
accessible under Concept/EcoStruxure Control Expert (1) for the Global Data
transaction
b Simpler data exchange with Global Data transactions performed on all network
nodes
b Point-to-point communication without programming with Peer Cop

8 Increased network reliability and maintainability


b Standard diagnostics provide data on all network nodes for easy troubleshooting
b Dual Modbus Plus ports provide Modbus Plus network redundancy
Reduced total cost of ownership
b Helps protect your investment in Modbus Plus while migrating to Ethernet
b Dual Ethernet ports allow connection of both the Modicon M340 or Modicon M580
PLC and the configuration PC to the proxy, without any additional switches
9
(1) Unity Pro software in earlier versions.

10

8/12
References Modicon X80 modules
Modicon X80 Communication modules
Modbus Plus Proxy

Embedded Web server


Web server functions
The Modbus Plus Proxy includes an embedded Web server that can be used to 1
perform diagnostics and configure the module connection. Data is presented in the
form of standard web pages in HTML format. To access a web page, you need
Internet Explorer (version 6.0 or later) and Java (version 1.5 or later).
Embedded Web server functions
1 - Setup: The Setup pages allow you to define the parameters for several different
module services, including security, IP, SNMP, Global Data, Peer Cop, and Ethernet
ports.
2
2 - Diagnostics: These network diagnostic pages contain Ethernet, TCP, and SNMP
statistics, as well as a log of the diagnostics performed.

Complementary characteristics
The following characteristics complement those introduced in the communication
selection guide on page 0552Q/5
3
b External power supply voltage: 19.2...31.2 V c
b Consumption: 300 mA max.
b Dissipated power: 6.2 W

References
System and network requirements
4
b EcoStruxure Control Expert or Unity Pro XL programming software (version 3.x or
later) (1)
b Internet Explorer (version 6.0 or later)
b Java (version 1.5 or later)
b Microsoft Windows XP or Vista
Modicon M340 processors: 5
b BMXP342020 (Modbus and Ethernet version)
b BMXP3420302 (CANopen and Ethernet version)
Modicon M580 processors:
b BMEP581020
b BMEP582020/BMEP582040(S)
b BMEP583020/BMEP583040
b BMEP584020/BMEP584040(S) 6
b BMEP585040
b BMEP586040(S)
Modicon M340 Ethernet modules:
b BMXNOE0100
b BMXNOE0110
TCSEGDB23F24FA b BMXNOC0401 7
Modicon M580 Ethernet modules:
b BMENOC0301
b BMENOC0311
b BMENOC0321

Modicon Modbus Plus Proxy (2) 8


Description Supplied with Reference Weight
kg/lb
Modbus Plus Proxy module 2 front-mounted power TCSEGDB23F24FA –
for Modicon M340 and supply connectors
Modicon M580 PLCs
(2 positions)

(1) Unity Pro V8.0 or later with Modicon M580


9
(2) For Modicon Modbus Plus Proxy with conformal coating, see page 9/9.

10

8/13
Presentation, Modicon X80 modules
description, Modicon X80 Communication modules
references Fiber converter modules

Modicon X80 Fiber converter module (1) (2)


Presentation
1 BMXNRP0200/0201 module offers an alternative to the use of Modicon managed
BMXNRP0201_main_image

dual ring switches (DRS), for fiber optic communications over long distances in
1 Ethernet I/O systems (RIO or DIO).
2 When inserted in Modicon X80 EIO drops, BMXNRP0200/0201 modules make it
possible to:
3 b Extend the total distance of the EIO network when EIO drops are located in areas
of the factory above 100 m/328 ft
2 b Enhance immunity to noise
b Resolve grounding incompatibilities between sites with different grounding
methods
4 BMXNRP0200/0201 modules can be installed on the primary or secondary rings.
These modules cannot, however, be used to connect secondary rings to the primary
ring.

3 BMXNRP020p
Following the distance of the remote location, you may select:
b The BMXNRP0200 module for multimode optical fiber which allows remote
location up to 2 km/1.25 mi., or
b The BMXNRP0201 module for single-mode optical fiber which allows remote
location up to 16 km/9.94 mi.

Depending on the configuration, the X80 Fiber converter module may be linked to
4 the X80 Remote I/O drop adapter of the drop where it is installed, via 1 or 2 Ethernet
Interlink cables.

Description
1  Module reference
2  Display block indicating the module status

5
3  RJ45 Ethernet ports (2 LEDs, LNK and ACT, indicate the status of each port)
4  Fiber optic ports with SFP transceiver for LC type connector
Instead of an embedded switch, you may also use our external Modicon switches
described in the Modicon Networking catalog. They are all delivered with predefined
parameters in order to opitimize your architecture performances such as dual ring
switch, management of main ring RIO, sub-ring or loop with DIO.

6 References (1)
Modicon X80 Fiber converter modules (2)
Description Optical fiber Reference Weight
kg/lb
Modules for fiber optic Multimode BMXNRP0200 –

7
DIA6ED2140903EN communications over long
distances Single-mode BMXNRP0201 –

(1) For additional characteristics, see our website.


(2) R
 equires Unity Pro Extra Large software u V7.0 or EcoStruxure Control Expert:
see our website.

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 2
 /2 page 2/6 page 4/2 page 8/2 page 9/2

8/14
Presentation, Modicon X80 modules
description, Modicon X80 Communication modules
references Ethernet switch module

Ethernet switch module


Presentation
The BMENOS0300 Ethernet switch module offers an economic alternative to the 1
BMENOS0300_main_image

use of Modicon managed dual ring switches (DRS) for copper Ethernet
1 communication over short distances in Ethernet I/O systems (RIO or DIO). Based on
2 the rotary switches on the front panel, the application of the 2 device network ports
can be configured intuitively as:
4 b RIO ring
b DIO ring
2
3
5 b DIO ports
Depending on the architecture, the BMENOS0300 switch can be used to
6 communicate with the distributed I/O by simply inserting it in the local main rack or
remote drops.

Description

BMENOS0300
1  Module reference
2  Display block indicating the module status 3
3  Rotary switch for configuring the ETH 1 service port
4  Rotary switch for configuring the 2 device network ports (ETH 2 and ETH 3)
5  ETH 1: Service port (Ethernet)
6  ETH 2/ ETH 3: Device network port (Ethernet)

Instead of an embedded switch, you may also use our external Modicon switches 4
described in the Modicon Networking catalog. They are all delivered with predefined
parameters in order to opitimize your architecture performances such as dual ring
switch, management of main ring RIO, sub-ring or loop with DIO.

References (1) 5
Modicon X80 Ethernet switch module
Description SERVICE Device network Reference Weight
port port (Ethernet) kg/lb
DIA6ED2140903EN Switch for copper Ethernet 1 2 BMENOS0300 –
communication over short
distances

(1) For additional characteristics, see our website.


6

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules: Modules for severe environments:
page 1
 /10 page 2/2 page 2/6 page 4
 /2 page 8
 /2 page 9
 /2

8/15
Contents 9 - Dedicated parts for severe
environments

Treatment for severe environments


b Presentation............................................................................................ page 9/2
v Protective treatment for Modicon X80 modules........................................ page 9/2 1
v Treatment for severe environments.......................................................... page 9/2
- Harsh chemical environments............................................................. page 9/2
- Extreme climate environments............................................................ page 9/2
v Specific characteristics for Safety modules............................................... page 9/2 2
v Composition of Modicon X80 offer for severe environments..................... page 9/3

Dedicated parts for severe environments


b Modicon X80 Racks and rack expansion module for severe environments
3
v References............................................................................................... page 9/4
b Modicon X80 Power supplies for severe environments
v References............................................................................................... page 9/5
b Modicon X80 I/O modules for severe environments
v Modicon X80 Discrete I/O modules........................................................... page 9/6 4
v Modicon X80 Analog I/O modules............................................................. page 9/7
b Modicon X80 Expert modules for severe environments
v Modicon X80 Counter modules................................................................. page 9/8
v Modicon X80 Time-stamping module........................................................ page 9/8 5
v Modicon X80 SSI encoder interface module............................................. page 9/8
v Modicon X80 Frequency input module...................................................... page 9/8
b Modicon X80 I/O expansion modules for severe environments

6
v Modicon X80 Remote I/O drop adapter with conformal coating ................ page 9/9
b Modicon X80 Communication modules for severe environments
v Modicon X80 Modbus and Character mode serial link module.................. page 9/9
v Modicon X80 CANopen master module.................................................... page 9/9
v Modicon X80 PROFIBUS DP module....................................................... page 9/9
v Modicon X80 PROFIBUS DP network gateway........................................ page 9/9 7
v Modicon X80 Fiber converter modules..................................................... page 9/9
v Modicon X80 Ethernet switch module....................................................... page 9/9

10

9/1
Presentation Modicon X80 modules
Treatment for severe environments

Presentation
Protective treatment for Modicon X80 modules
1 The Modicon X80 modules comply with “TC” treatment requirements (treatment for
all climates). It is designed as standard to operate in temperatures ranging from 0 to
+60 °C/32 to 140 °F.
For installations in industrial environments corresponding to “TH” (treatment for hot
and humid environments), devices must be housed in enclosures providing at least
IP54 protection as specified by standard IEC/EN 60529, or an equivalent level of
protection according to NEMA 250.
2 The Modicon X80 modules offer IP20 protection (1). It can therefore be installed
without an enclosure in reserved access areas that do not exceed pollution level 2
(control room with no conductive dust). Pollution level 2 does not take account of
harsher environments, such as those where the air is polluted with conductive dust,
fumes, corrosive or radioactive particles, vapors or salts, molds, insects, etc. All the
safety hardware in-rack modules colored red (processor, coprocessor, Modicon X80

3 I/O) are conformal coated for use in severe environments.

Treatment for severe environments


If the Modicon X80 modules have to be used in more severe environments or are
required to start and operate in an extended temperature range, from -25 °C
to +70 °C/-13 °F to 158 °F (only H or T version), the “ruggedized ” offer features
industrially hardened processor and power supply modules, X-bus and Ethernet I/O
4 modules and backplanes that have a protective coating on their circuit boards.
Note: Capable of starting within an extended temperature range (from -25 °C to +70 °C/-13 °F
to 158 °F, a single-rack configuration is also able to operate at extremely low temperatures
(as low as -40 °C/-40 °F) if placed in an appropriate enclosure. Please contact our Customer
Care Center.
The coated/harsh offer provides the Safety CPU/coprocessor and Safety I/O

5
modules with “AVR 80” coating on their electronic cards.This treatment increases the
isolation capability of the circuit boards and their resistance to:
b Condensation
b Dusty atmospheres (conducting foreign particles)
b Chemical corrosion, in particular during use in sulfurous atmospheres (oil
refinery, purification plant, etc.) or atmospheres containing halogens (chlorine, etc.)
or chemical vapors

6 This protection, combined with appropriate installation and maintenance, enables


Modicon X80 products to be used in the following environments:

Harsh chemical environments (products with suffix ‘H’ and ‘C’)


The use of contact grease protection on connectors, removal blocks is mandatory to
meet these requirements.
The lubricant protection seals electrical contacts from oxygen, moisture, aggressive

7 gasses, and other hostile elements.


v IEC/EN 60721-3-3 class 3C1, 3C2, 3C3, 3C4:
- 7 days; 25 °C/77 °F relative humidity 75%
- Concentrations (ppb): H2S: 9,900/SO2: 4,800/Cl2: 200
v ISA S71.04 classes G1, G2, G3, Gx:
- 14 days; 25 °C/77 °F relative humidity 75%
- Concentrations (ppb): H2S: 60/SO2: 350/Cl2: 1,450/NO2: 12
8 v IEC/EN 60068-2-52 salt mist, Kb test severity level 2:
- 3 x 24-hour cycles
- 5% NaCI
- 40 °C/104 °F relative humidity 93%
Extreme climate environments (products with suffix ‘H’ and ‘T’)
v Temperatures ranging from -25 to +70 °C/-13 to 158 °F

9 v
v
Relative humidity levels up to 93% from -25 °C/-13 °F to +60 °C/140 °F
Formation of ice
v Altitudes from 0 to 5,000 m/0 to 16,404 ft
Note: Some products with the suffix 'C' also operate in an extended temperature range (from
-25 °C to +60 °C/-13 °F to 140 °F). Please contact our Customer Care Center.

(1) Each slot in a BMpXBPpp00 backplane is equipped as standard with a protective cover that

10 should only be removed when inserting a module. If any covers are subsequently misplaced,
replacements can be ordered under reference BMXXEM010 (sold in lots of 5).

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules:


page 1
 /10 page 2/2 page 3/2 page 4
 /2 page 8
 /2

9/2
Presentation (continued) Modicon X80 modules
Treament for severe environments

Presentation (continued)
Specific characteristics for Safety modules
All Safety modules are coated and only exist with this surface treatment. There is no
T, C, or H extension in the product references. Safety modules are compatible with:
1
b a temperature range from -25...+60 °C/-13...140 °F
b corrosive environments using common H components
A protective gel is needed to cover all electrical connections on Modicon X80
products used in corrosive environments.
This gel comes in a 25 g tube and can be ordered separately under the reference
BMXGEL0025.
2
Protective gel BMXGEL0025

Modicon X80 offer composition for severe environments


To order ruggedized modules and backplanes, see the reference tables from page 9/4 to
page 9/9 :
b References of available ruggedized products include the suffix “H”
b References of available conformal coated products include the suffix “C”. 3
The majority of operating and electrical characteristics of ruggedized modules are
identical to those of their equivalent standard versions. However, some
characteristics are subject to either derating or limitation. Please consult
our website.

In this chapter, note that only Modicon X80 products are described.
4
b For M580 or M340 products, please refer to related catalog:

6
DIA6ED2151012EN DIA6ED2110104EN

b For additional accessories, please refer to:


v
v
Standard accessories for backplanes, page 2/5 and page 2/9
Standard accessories for power supplies, page 3/3 7
v Standard accessories for I/O modules, page 4/15
v Standard accessories for expert modules, page 4/15

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules:


page 1/10 page 2/2 page 3/2 page 4/2 page 8/2

9/3
References Modicon X80 modules
Dedicated parts for severe environments
Modicon X80 backplanes and rack expansion module
for severe environments

Modicon X80 backplanes and rack expansion module for severe


environments
1 Description Type of module to be
inserted
No. of Power
slots consumption
Reference Weight
kg/lb
PF122567A

(1) (2)
X-bus BMXCPS power supply, 4 1W BMXXBP0400H 0.630/
backplanes BMXP34 or BMEP58 1.389
for severe processor, BMEH58 6 1.5 W BMXXBP0600H 0.790/
BMXXBP0400H environments processor, I/O modules, 1.742

2
and application-specific
(counter and communication) 8 2W BMXXBP0800H 0.950/
modules 2.094
12 0.74 W BMXXBP1200H 1.270/
2.800
Ethernet + BMXCPS power supply, 4 2.8 W BMEXBP0400H 0.715/
PF122507B

X-bus BMEP58 processor, 1.576


backplanes BMEH58 processor, 8 3.9 W BMEXBP0800H 1.070/
for severe I/O modules, and application-
3
2.359
environments specific (counter and
communication) modules 12 3.9 W BMEXBP1200H 1.387/
BMEXBP0800H
3.058
Ethernet + BMEP58 processor, 6 3.9 W BMEXBP0602H 1.387/
X-bus dual BMEH58 processor, 3.058
power supply BMXCPS400p redundant 10 3.9 W BMEXBP1002H 1.387/
backplanes power supply, I/O modules, 3.058
for severe and application-specific

4
environments (counter and communication)
modules
BMXXBE1000H_main_image

Description Use Reference Weight


kg/lb
Rack Standard module to be installed in each rack (XBE BMXXBE1000H 0.178/
expansion slot) 0.392
module (3) for Used to daisy chain 2, 4, or 8 racks depending on the
severe types of Modicon M340 or Modicon M580 processor

5 environments

BMXXBE1000H (1) Number of slots taking the processor module, I/O modules, and application-specific modules
(excluding power supply module).
(2) Power consumption of anti-condensation resistor(s).
(3) Module and cordsets do not operate properly at temperatures lower than -25 °C/-13 °F.

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules:


page 1
 /10 page 2/2 page 3/2 page 4
 /2 page 8
 /2

9/4
References (continued) Modicon X80 modules
Dedicated parts for severe environments
Modicon X80 Power supplies for severe environments

Modicon X80 Power supplies for severe environments


Each BMpXBPpp00H backplane must be equipped with a power supply.
BMEXBPpp02H must be equipped with 1 or 2 redundant power supplies. These
modules are inserted in the leftmost power supply slots of each backplane (marked
1
Modicon PLC Configurator CPS).

The available power values given below in bold italic correspond to operation at
-25 °C/-13 °F and +70 °C/+158 °F (see temperature derating curves on
our website).
Click on the pictogram to access Modicon PLC
Configurator on line and calculate which power
supply fits better to the power consumption
The power required to supply each rack depends on the type and number of
modules installed in the backplane. It is therefore necessary to draw up a power
2
consumption table for each rack in order to determine which is the most appropriate
BMXCPSppppH power supply for your requirements : calculate the power
consumption by using the Modicon PLC Configurator online tool.

Modicon X80 Power supplies for severe environments(1)


Line supply Available power (2) Reference Weight
kg/lb
3
3.3 V c 24 V c rack 24 V c Total
(3) (3) sensors (4)
24...48 V c 15 W 32 W – 32 W BMXCPS3020H 0.340/
isolated
BMXCPS3020H_image

BMXCPS3500H_image

11.3 W 23.4 W 23.4 W 0.750

4
100...240 V a 15 W 31.2 W 21.6 W 36 W BMXCPS3500H 0.360/
11.3 W 23.4 W 16.2 W 27 W 0.794
BMXCPS3020H BMXCPS3500H

5
BMXCPS4002H_main_image

BMXCPS4022H_main_image

18 W 40 W – 40 W BMXCPS4002H 0.360/
18 W 40 W 40 W 0.794

24...48 V c 18 W 40 W – 40 W BMXCPS4022H 0.810/


6
18 W 40 W 40 W 1.786

BMXCPS4002H BMXCPS4022H

125 V c 18 W 40 W – 40 W BMXCPS3522H 0.610/


7
BMXCPS3522H_main_image

18 W 40 W 40 W 1.345

(1) Includes a set of 2 removable caged connectors BMXXTSCPS10.


(2) The total power consumed on each voltage (3.3 V c and 24 V c) must not exceed the total
power of the module. 8
(3) 3.3 V c and 24 V c rack voltages for powering Modicon M340 and Modicon M580 PLCs.
BMXCPS3522H (4) 24 V c sensor voltage for powering the input sensors (voltage available via the 2-way
removable connector on the front panel).

10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules:


page 1/10 page 2/2 page 3/2 page 4/2 page 8/2

9/5
References (continued) Modicon X80 modules
Dedicated parts for severe environments
Modicon X80 Discrete I/O modules for severe
environments

References
Modicon X80 Discrete input modules for severe environments
1 Type of
current
Input voltage Connection via IEC/EN 61131-2 No. of channels
conformity (common x channels
Reference Weight
kg/lb
per group)
c 24 V (positive logic) 20-way caged, screw Type 3 16 inputs BMXDDI1602H 0.115/
BMXDDI1602H_main_image

clamp, or spring-type (1 x 16) 0.254


removable terminal block
One 40-way connector Type 1 32 inputs BMXDDI3202KH 0.110/

2
(2 x 16) 0.243

Two 40-way connectors Non-type 64 inputs BMXDDI6402KH 0.145/


(4 x 16) 0.320

24 V (positive/ 20-way caged, screw Non-type 16 inputs BMXDAI1602H 0.115/


BMXDDI160pH negative logic) clamp, or spring-type (1 x 16) 0.254
BMXDAI160pH removable terminal block

3
12/24 V (positive/ 40-way caged or Type 3 32 inputs BMXDDI3232H 0.138/
negative logic) spring-type removable (2 x 16) 0.30
BMXDAI1615H_main_image

terminal block
48 V 20-way caged, screw Type 1 16 inputs BMXDDI1603H 0.115/
clamp, or spring-type (1 x 16) 0.254
removable terminal block
40-way caged or Type 3 32 inputs BMXDDI3203H 0.138/
spring-type removable (2 x 16) 0.304

4
terminal block
a 24 V 20-way caged, screw Type 1 16 inputs BMXDAI1602H 0.115/
clamp, or spring-type (1 x 16) 0.254
BMXDAI161pH
removable terminal block
BMXDDO3202H
48 V 20-way caged, screw Type 3 16 inputs BMXDAI1603H 0.115/
clamp, or spring-type (1 x 16) 0.254
BMXDDI3202KH _main_image

BMXDDI6402KH _main_image

removable terminal block


100…120 V 20-way caged, screw Type 3 16 inputs BMXDAI1604H 0.115/

5
clamp, or spring-type (1 x 16) 0.254
removable terminal block
40-way caged or Type 1 16 isolated inputs BMXDAI1614H 0.150/
spring-type removable 0.331
terminal block
200…240 V 40-way caged or Type 1 16 isolated inputs BMXDAI1615H 0.156/
spring-type removable 0.344
BMXDDI3202KH (left) terminal block
BMXDDI6402KH (right)
6 Modicon X80 Discrete output modules for severe environments
Type of Output voltage Connection via IEC/EN 61131-2 No. of channels Reference Weight
current conformity (common x channels kg/lb
per group)
c 24 V 20-way caged, screw Yes 16 outputs BMXDDO1602H 0.120/
transistor (positive logic)
BMXDDO1612H_main_image

BMXDDO3202K_main_image

clamp, or spring-type (1 x 16) 0.265


removable terminal block

7 24 V
(negative logic)
20-way caged, screw
clamp, or spring-type
Yes 16 outputs
(1 x 16)
BMXDDO1612H 0.120/
0.265
removable terminal block
12...24 V 40-way caged or Yes 32 outputs BMXDDO3202H 0.144/
(positive logic) spring-type removable (2 x 16) 0.317
terminal block
BMXDDO16p2H BMXDDO3202KC
24 V One 40-way connector Yes 32 outputs BMXDDO3202KC 0.110/
BMXDAO1605H

8
(positive logic) (2 x 16) 0.243
BMXDRAppppH

Two 40-way connectors Yes 64 outputs BMXDDO6402KC 0.150/


(4 x 16) 0.331
BMXDDO6402KC_main_image

BMXDAO1615H_main_image

a triac 100…240 V 20-way caged, screw Yes 16 outputs BMXDAO1605H 0.140/


clamp, or spring-type (4 x 4) 0.309
removable terminal block

9 24…240 V 40-way caged or


spring-type removable
Yes 16 isolated outputs BMXDAO1615H 0.250/
0.551
terminal block
BMXDDO6402KC BMXDDO3202H c / a 24...125 V c 20-way caged, screw Yes 8 normally open BMXDRA0815H 0.210/
BMXDAO1615H relay 24...240 V a clamp, or spring-type isolated relay outputs 0.463
BMXDRC0805H removable terminal block
24 V c 20-way caged, screw Yes 16 normally open relay BMXDRA1605H 0.150/
240 V a clamp, or spring-type outputs 0.331
10 24...125 V c
removable terminal block
40-way caged or Yes
(2 x 8)
8 normally open and BMXDRC0805H 0.189/
24…240 V a spring-type removable normally closed 0.417
terminal block isolated relay outputs

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules:


page 1
 /10 page 2/2 page 3/2 page 4
 /2 page 8
 /2

9/6
References (continued) Modicon X80 modules
Dedicated parts for severe environments
Modicon X80 Analog I/O modules for severe
environments

References
Modicon X80 Discrete mixed I/O modules for severe environments
1
BMXDDM16022H_main_image

Type Voltage Connection via IEC/EN 61131-2 No. of channels Reference Weight
conformity (common x kg/lb
channels per
group)
Inputs Outputs Inputs Outputs Inputs Outputs
c 24 V c 24 V c 20-way caged, screw Type 3 Yes 8 8 BMXDDM16022H 0.115/
transistor clamp, or spring-type (1 x 8) (1 x 8) 0.254
(positive logic) removable terminal
block 2
BMXDDM1602pH c/a 24 V c 24…240 V a 20-way caged, screw Type 3 Yes 8 8 BMXDDM16025H 0.135/
relay clamp, or spring-type (1 x 8) (1 x 8) 0.298
(positive logic) removable terminal
block
BMXART0414H_main_image

BMXART0814H_main_image

Modicon X80 Analog input modules for severe environments


Type of
inputs
Input signal range Resolution Connection No. of
channels
Reference Weight
kg/lb 3
Isolated ± 10 V, 0…10 V, 16 bits 20-way caged, screw clamp, 4 inputs BMXAMI0410H 0.143/
high-level 0…5 V, 1…5 V, ± 5 V or spring-type removable 0.315
inputs 0…20 mA, terminal block
4…20 mA,
± 20 mA 28-way caged, screw clamp, 8 inputs BMXAMI0810H 0.175/
or spring-type removable 0.386

4
terminal block
BMXART0414H (left)
BMXART0814H (right) Isolated Temperature probe, 15 bits 40-way connector 4 inputs BMXART0414H 0.135/
low-level thermocouple + sign 0.298
inputs ± 40 mV, ± 80 mV, 8 inputs BMXART0814H 0.165/
± 160 mV, 0.364
± 320 mV,
BMEAHI0812H_main_image

± 640 mV,
± 1.28 V

Modicon X80 HART analog input module for severe environments


Type of Input signal range Resolution Connection No. of Reference Weight
5
inputs channels kg/lb
Isolated 4...20 mA 15 bits 20-way caged, screw clamp, 8 inputs BMEAHI0812H 0.233/
high-level + sign or spring-type removable 0.514
inputs terminal block
BMEAHI0812H
Modicon X80 Analog output modules for severe environments 6
BMXAMO0210H_main_image

Type of Output signal range Resolution Connection No. of Reference Weight


outputs channels kg/lb
Isolated ± 10 V, 16 bits 20-way caged, screw clamp, 2 outputs BMXAMO0210H 0.144/
high-level 0…20 mA, 4…20 mA or spring-type removable 0.317
outputs terminal block
4 outputs BMXAMO0410H 0.175/

7
0.386
Non-isolated 0…20 mA, 15 bits 20-way caged, screw clamp, 8 outputs BMXAMO0802H 0.150/
high-level 4…20 mA + sign or spring-type removable 0.331
outputs terminal block
BMXAMp0pp0H

Modicon X80 HART analog output module for severe environments


BMEAHO0412C_main_image

Type of Output signal range Resolution Connection No. of Reference Weight

8
outputs channels kg/lb
Isolated 4...20 mA 15 bits 20-way caged, screw clamp, 4 outputs BMEAHO0412C 0.223/
high-level + sign or spring-type removable 0.492
outputs terminal block

Modicon X80 Analog mixed I/O module for severe environments

BMEAHO0412C
Type of
outputs
Signal range Resolution Connection No. of
channels
Reference Weight
kg/lb 9
Inputs Outputs Inputs Outputs
Mixed I/O, ± 10 V, ± 10 V, 14 or 12 bits 20-way caged, screw 4 2 BMXAMM0600H 0.155/
non-isolated 0…10 V, 0…20 depending clamp, or spring-type inputs outputs 0.342
0…5 V, mA, on the range removable terminal block
1…5 V, 4…20
0…20 mA, mA
4…20 mA
10

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules:


page 1
 /10 page 2/2 page 3
 /2 page 4
 /2 page 8
 /2

9/7
References (continued) Modicon X80 modules
Dedicated parts for severe environments
Modicon X80 Expert modules for severe environments

References
Modicon X80 Counter modules for severe environments
1
BMXEHC0200H_main_image

BMXEHC0800H_main_image
Description Characteristics Connection No. of Reference Weight
via channels kg/lb
Counter modules 60 kHz counting 2 x 16-way 2 BMXEHC0200H 0.112
for 24 V c 2- and connector 0.247
3-wire sensors and and 1 10-way
10/30 V c incremental connector
encoders with

2
push-pull outputs 10 kHz counting 20-way 8 BMXEHC0800H 0.113
caged, screw 0.249
clamp, or
spring-type
BMXEHC0200H BMXEHC0800H removable
terminal
block

3
Modicon X80 Time-stamping module for severe environments
BMXERT1604H_main_image

Description Characteristics Connection No. of Reference Weight


via channels kg/lb
Multifunction Time- and 28-way 16 BMXERT1604H 0.119/
time-stamping input date-stamping at 1 caged or 0.262

4
module ms spring-type
1.6 < resolution < 3.3 removable
ms terminal
store up to local 4000 block
events (255 groups,
each group 16
channel) (1)
BMXERT1604H
16 discrete inputs on
module

5 Modicon X80 SSI encoder interface module for severe environments


BMXEAE0300H_main_image

Description Characteristics Connection No. of Reference Weight


via channels kg/lb
SSI encoder 8- to 31-bit data 28-way 3 BMXEAE0300H 0.138/
interface module width caged or 0.304
4 baud rates: spring-type
100 kHz, 200 kHz, removable

6 500 kHz, 1 MHz terminal


block

BMXEAE0300H

Modicon X80 Frequency input module for severe environments


BMXETM0200H_main_image

7
Description Characteristics Connection No. of Reference Weight
via channels kg/lb
Speed and frequency Input frequency: 28-way 2 BMXETM0200H 0.124/
control module for 0…500Hz, reflex caged or 0.273
turbomachinery digital output spring-type
application removable
terminal
block

8
BMXETM0200H

Removable terminal blocks for severe environments (3)


BMXFTB4000H_main_image

BMXFTB4020H_main_image

Description Type Reference Weight


kg/lb
9 40-way removable terminal block Caged BMXFTB4000H 0.166/
0.366
Spring BMXFTB4020H 0.098/
0.216
(1) This maximum value is not an absolute value. It depends on the overall system dynamics
(total number of scanned items and number of events generated by the system).
(2) The shielding on the cordsets carrying the counter signals must always be connected to the

10
BMXFTB4000H BMXFTB4020H BMXXSPpp00 shielding connection kit mounted under the rack holding the BMXEHC0200H
module (see page 2/5).
(3) Both standard and hardened terminal blocks are applicable for severe environment.
However, hardened terminal blocks can provide a better protection in a severe environment
due to their gold plating.

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules:


page 1
 /10 page 2/2 page 3/2 page 4
 /2 page 8
 /2

9/8
References (continued) Modicon X80 modules
Dedicated parts for severe environments
Modicon X80 I/O expansion modules, communication
modules, and gateway for severe environments

References
Modicon X80 Remote I/O drop adapters for severe environments
1
BMECRA31210C_main_image

BMXCRA31210C_main_image
Description Protocol SERVICE port Reference Weight
kg/lb
Remote I/O drop RSTP 1 BMECRA31210C 0.225/
adapter 0.496
Remote I/O drop RSTP 1 BMXCRA31210C 0.225/
adapter 0.496

Modicon X80 Serial link module for severe environments


Description Physical layer Reference Weight
2
kg/lb
Serial link module Modbus client/server 1 non-isolated BMXNOM0200H 0.230/
BMECRA31210C BMXCRA31210C (2 channels) RTU/ASCII, RS 232 channel 0.507
Character mode, (SL0)
GSM/GPRS modem 2 isolated RS 485
channels
(SL0 and SL1)
3
Modicon X80 CANopen client module for severe environments
BMECXM0100H_main_image

PMEPXM0100H_main_image

Description Protocols Physical Reference Weight


layer kg/lb
CANopen CiA 301 V4.2 ISO 11898 (9-way BMECXM0100H 0.200/
communication standard (client or SUB-D connector) 0.441
module server); Ethernet/IP

Modicon X80 PROFIBUS DP module for severe environments 4


Description Protocols Physical Reference Weight
layer kg/lb
X80 PROFIBUS DP Implicit exchange of EIA-485 PMEPXM0100H 0.270/
Master module process data (optical, MBP) 0.595

BMECXM0100H PMEPXM0100H Modicon X80 PROFIBUS DP network gateway for severe environments
Description Protocols Physical
layer
Reference Weight
kg/lb 5
PROFIBUS Modbus/TCP 1 Ethernet switch, TCSEGPA23F14FK 0,62/
PF516164

Remote Master 2 ports 1,36


(PRM) module 10BASE-T/
100BASE-TX
PROFIBUS DP V1 1 isolated RS 485
and PROFIBUS PA PROFIBUS DP
(via gateway) port
Modbus Plus Proxy module for severe environments
6
Description Supplied with Reference Weight
kg/lb
Modbus Plus Proxy module 2 front-mounted TCSEGDB23F24FK −
power supply
TCSEGPA23F14FK connectors

7
(2 positions)

Modicon X80 Fiber converter modules for severe environments (1) (2)
Description Optical fiber Reference Weight
BMENOS0300C_main_image
BMXNRP0200C_main_image

kg/lb
Modules for fiber optic communications Multimode BMXNRP0200C 0,203/
over long distances 0,447
Single-mode BMXNRP0201C 0,203/

Modicon X80 Ethernet switch module for severe environments


0,447
8
Description SERVICE port Device network Reference Weight
port(Ethernet) kg/lb
Ethernet switch 1 2 BMENOS0300C –
module

9
BMXNRP020pC BMENOS0300C Connection accessories
Designation Description RS 232 Reference Weight
interface kg/lb
Cordset for Equipped with 1 x Simplified 4-wire TCSMCN3M4M3S2 0.150/
DCE terminal RJ45 connector and (RX, TX, RTS, and 0.331
(modem, etc.) 1 x 9-way male CTS)
SUB-D connector Full 8-wire TCSXCN3M4F3S4 0.165/
Length 3 m/9.84 ft (except RI signal) 0.364

(1) Requires Unity Pro Extra Large software u V7.0 or EcoStruxure Control Expert;
see our website.
10
(2) Supports operation at -25 to 60°C / -13 to 140°F.

Compatibility: Backplanes: Power supplies: I/O modules: Communication modules:


page 1/10 page 2/2 page 3
 /2 page 4/2 page 8
 /2

9/9
Contents 10 - Standards and certifications,
Services, Index

Technical appendices
b Standards, certifications, and environmental conditions................. page 10/2
v Per region............................................................................................... page 10/2 1
v Per application........................................................................................ page 10/2
v Functional safety.................................................................................... page 10/3
b Environmental characteristics............................................................ page 10/4
b Protective treatment of Modicon X80 modules.................................. page 10/4
b Installation restrictions and recommendations................................. page 10/4 2
b Environment tests................................................................................ page 10/5
b Certifications and EC regulations for automation products............. page 10/8

Dedicated service offers for your installed base


b Maintenance and support services................................................... page 10/10
3
b Consultancy services..........................................................................page 10/11
b Modernization solutions.....................................................................page 10/11
b Customization services......................................................................page 10/11

Index
4
b Product reference index..................................................................... page 10/14

10

10/1
Standards and Modicon X80 modules
certifications Standards, certifications, and environment
conditions

Standards and certifications


Per region
1 The Modicon X80 modules and X80 Safety modules have been developed to
comply with the principal national and international standards concerning electronic
equipment for industrial automation systems. Up-to-date information on which
certifications have been obtained is available on our website: consult commercial
references directly.
b Compliance with European Directives for CE marking:

2
v WEEE: 2012/19/EU
v Low voltage: 2014/35/EU
v Electromagnetic compatibility: 2014/30/EU
v Machinery: 2006/42/EC (check EU DoC on our website)
v ATEX: 2014/34/EU (check EU DoC on our website)
b Requirements specific to programmable controllers (functional characteristics,
immunity, resistance, safety, etc.):
v IEC/EN 61131-2
3 v IEC/EN/UL/CSA 61010-2-201
b Country specific passport:
v RCM
v EAC
v UKCA
For other country certifications, please refer to the technical appendix page 10/10.

4 Modicon X80 modules are considered as open equipment and are designed for use
in industrial environments, in pollution degree 2, overvoltage category II (IEC
60664-1), and in low-voltage installations, where the main power branch is protected
on both wires by devices such as fuses or circuit breakers limiting the current to 15A
for North America and 16A for the rest of the world.

5
Per application
Power generation
b IEC/EN 61000-6-5 for interfaces type 1 and 2
b IEC/EN 61850-3 for locations G
Merchant navy
Merchant navy requirements of the major international organizations are unified in

6
IACS (International Association of Classification Societies) IACS E10 rules: BV,
DNV, ABS, LR, RINA (refer to page 10/11).
Railway
b EN 50155/IEC 60571: Railway applications - Rolling stock - Electronic
equipment
b EN 45545-2: Railway applications - Fire protection on railway vehicles - Part 2 :
requirements for fire behavior of materials and components
7 b EN 50121-3-2/IEC 62236-3-2: Railway applications - Electromagnetic
compatibility - Part 3-2: Rolling stock - Apparatus
b EN 50121-4/IEC 62236-4: Railway applications - Electromagnetic compatibility
- Part 4: Emission and immunity of the signalling and telecommunications
apparatus
b EN 50121-5/IEC 62236-5: Railway applications - Electromagnetic compatibility
- Part 5: Emission and immunity of fixed power supply installations and
apparatus
8 b EN 50124-1/IEC 62947-1: Railway - Insulation coordination - Part 1: Basic
requirements - Clearances and creepage distances for all electrical and
electronic equipment
b EN 50125-1/IEC 62498-1: Railway - Environmental conditions for equipment -
Part 1 : Rolling stock and on-board equipment
b EN 50125-3/IEC 62498-3: Railway - Environmental conditions for equipment -
Part 3: Equipment for signaling and telecommunications

9 Hazardous areas
b For USA and Canada: Hazardous location class I, division 2, groups A,B,C, and D
b For European Union: ATEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
b For United Kingdom: UKEX for atmosphere Zone 2 (gas) and Zone 22 (dust)
b For other countries: IECEx for atmosphere Zone 2 (gas) and/or Zone 22 (dust)

10

10/2
Standards and Modicon X80 modules
certifications Standards, certifications, and environment
(continued) conditions

Standards and certifications (continued)


Functional safety
All Safety modules are certified by TÜV Rheinland.
The certificate reviews the following standards:
1
b Generic safety
v IEC/EN 61508: Functional safety of electrical/electronic/programmable
electronic safety-related systems
- IEC/EN 61508-1 - Part 1: General requirements

2
- IEC/EN 61508-2 - Part 2: Requirements for electrical/electronic/
programmable electronic safety-related systems
- IEC/EN 61508-3 - Part 3: Software requirements
b Safety for Process
v IEC/EN 61511: Functional safety - Safety instrumented systems for the process
industry sector
- IEC/EN 61511-1 - Part 1: Framework, definitions, system, hardware and
software requirements
- IEC/EN 61511-2 - Part 2: Guidelines for the application of IEC 61511-1
3
- IEC/EN 61511-3 - Part 3: Guidance for the determination of the required
safety integrity levels
b Safety for Machine
v IEC/EN 62061: Safety of machinery - Functional safety of safety-related

4
electrical, electronic and programmable electronic control systems
v ISO/EN 13849-1: Safety of machinery - Safety-related parts of control systems
- Part 1: General principles for design
v ISO/EN 13849-2: Safety-related parts of control systems - Part 2: Validation
b Safety for Railway
v EN 50126/IEC 62278: Railway Applications - The Specification and
demonstration of reliability, availability, maintainability and safety (RAMS)
v EN 50128/IEC 62279: Railway Applications - Communication, signaling and
processing systems. Software for railway control and protection systems
5
v EN 50129/IEC 62425: Railway applications -Communication, signaling and
processing systems - Safety-related electronic systems for signaling

Fire & Gas


b EN 54.2 Fire detection and fire alarms systems – Part 2: Control and indicating
equipment
b EN 50156-1 Electrical equipment for furnaces and ancillary equipment - Part 1: 6
Requirements for application design and installation
b EN 50130-4 Immunity requirements components of fire, intruder, holdup, CCTV,
access control and social alarms systems
b EN 298 Automatic burner control systems for burners and appliances burning
gaseous or liquid fuels
b NFPA 85 Boiler and Combustion Systems Hazards Code
b NFPA 86 Standard for Ovens and Furnaces
b NFPA 72 National Fire Alarm and Signaling Code 7

10

10/3
Standards and Modicon X80 modules
certifications Standards, certifications, and environment
(continued) conditions

Environmental characteristics
Service conditions and recommendations relating to the environment
1 Modicon X80 modules Modicon X80 Safety modules Modicon X80 modules for
severe environments
Temperature Operation °C/°F 0...+60/32...140 -25...+60/-13...+140 -25...+70/-13...+158

Storage °C/°F -40...+85/-40...+185 -40...+85/-40...+185 -40...+85/-40...+185

Relative humidity Cyclical humidity % +5 ... +95 up to 55 °C/131 °F +5...+95 up to 55 °C/131 °F +5 ... +95 up to 55 °C/131 °F

2 (without condensation)
Continuous humidity % +5 ... +93 up to 55 °C/131 °F +5...+93 up to 60 °C/140 °F +5 ... +93 up to 60 °C/140 °F

Altitude Operation m/ft 0…2,000/0...6,562 (full specification: temperature and isolation)


2,000...5,000/6,562...16,404 (temperature derating: approx. 1 °C/400 m (33.8 °F/1,312 ft),
isolation 150 V/1,000 m/3,281 ft
For accurate temperature derating calculation, refer to IEC 61131-2 Ed4.0 Annex A
Modicon X80 power supplies

3
Supply voltage BMXCPS2010 BMXCPS3020 BMXCPS3540T BMXCPS2000 BMXCPS3500
BMXCPS3020H BMXCP3522 BMXCPS3500H
BMXCP3522S BMXCPS4002
BMXCPS4002S
BMXCPS4002H
BMXCPS4022S
Nominal voltage V 24 c 24...48 c 125 c 100...240 a 100...240 a

Limit voltages V 18...31.2 c 18...62.4 c 100…150 c 85...264 a 85...264 a


4 Nominal frequencies Hz – – – 50/60 50/60

Limit frequencies Hz – – – 47/63 47/63

Protective treatment of Modicon X80 modules

5 The Modicon X80 modules and X80 Safety modules meet the requirements of
“TC” treatment (treatment for all climates).
For installations in industrial production workshops or environments correspon-
ding to “TH” treatment (treatment for hot and humid environments), Modicon X80
modules must be embedded in enclosures with minimum IP54 protection.
The Modicon X80 modules and X80 Safety modules offer protection to IP20 le-
vel and protection against access to terminals (enclosed equipment) (1). They
6 can therefore be installed without an enclosure in reserved-access areas that do
not exceed pollution level 2 (control room with no dust-producing machine or
activity). Pollution level 2 does not take account of more severe environmental
conditions: air pollution by dust, smoke, corrosive or radioactive particles, vapors
or salts, molds, insects, etc.

7 Installation restrictions and recommendations


Please note that in order to fulfill the international certification conditions:
b Devices must be installed, wired, and maintained in accordance with the
instructions provided in the manual “Grounding and Electromagnetic
Compatibility of PLC Systems”;
b Installation restrictions are provided in “Modicon M580, M340, X80 Platforms,
Standards and Certifications“ and “Modicon M580 Safety, Standards and
8 Certificationsˮ manuals.
Download manuals for further details:

10 33002439KO1000 EIO0000002726 EIO0000002750

(1) In cases where a slot is not occupied by a module, a BMXXEM010 protective cover must be
installed (see catalog Modicon X80 modules).
(e): Tests required by European directives (e) and based on IEC/EN 61131-2 standards.

10/4
Environment tests Modicon X80 modules
Standards, certifications, and environment
conditions

Environment tests
The table below (pages 10/5 to 10/9) provides test values for Industry; for Power generation, Merchant navy, and Railway application
related tests, please refer to “Modicon M580, M340, and X80 platforms, Standards and Certifications - Installation & User guide” (see page
10/4).
1
Name of test Standards Levels
Immunity to LF interference (e) (1) (2)
Voltage and frequency variations IEC/EN 61131-2; IEC/EN 61000-6-2; 0.85...1.10 Un - 0.94...1.04 Fn; 4 steps t = 30 min
IEC 61000-4-11

2
Direct voltage variations IEC/EN 61131-2; 0.85...1.2 Un + ripple: 5% peak; 2 steps t = 30 min
IEC 61000-4-29
Third harmonic IEC/EN 61131-2 H3 (10% Un), 0°/180°; 2 steps t = 5 min

Voltage interruptions IEC/EN 61131-2; IEC/EN 61000-6-2; Power supply immunity:


IEC 61000-4-11; IEC 61000-4-29 b 1 ms for c PS1/10 ms for a PS2 (20 ms DS criteria),
For functional safety (DS criteria): 85% Un
b Check operating mode for longer interruptions
IEC 61000-6-7; IEC 61326-3-1
b up to 5s, 85% Un
IEC/EN 61131-2; IEC/EN 61000-6-2;
IEC 61000-4-11
For a PS2:
b 20% Un, t0: ½ period
b 40% Un, cycle 10/12
3
b 70% Un, cycle: 25/30
b 0% Un, cycle 250/300
Voltage shut-down and start-up IEC/EN 61131-2 b Un…0…Un; t = Un/60 s
b Umin…0…Umin; t = Umin/5 s
b Umin…0.9 Udl…Umin; t = Umin/60 s
Magnetic field IEC/EN 61131-2; Power frequency: 50/60 Hz, 100 A/m continuous
IEC 61000-4-8
For functional safety (DS criteria):
...1000 A/m; t = 3 s; 3 axes
4
IEC 61000-6-7; IEC 61326-3-1
IEC 61000-4-10 Oscillatory: 100 kHz...1 MHz, 100 A/m; t = 9 s; 3 axes

Conducted common mode disturbances IEC 61000-4-16 For remote systems:


range 0 Hz …150 kHz For functional safety (DS criteria): b 50/60 Hz and c, 300 V, t = 1s
b 50/60 Hz and c, 30 V, t = 1 min
IEC 61000-6-7; IEC 61326-3-1
5
b 5 Hz…150 kHz, sweep 3 V…30 V
b For AC: 10 V
b For DC: 10 V cont. or 100 V, t = 1 s
Where:
b PS1 applies to PLC supplied by battery, PS2 applies to PLC energized from a or c supplies
b Un: nominal voltage, Fn: nominal frequency, Udl: detection level when powered

(1) Devices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of
PLC Systems” (see page 10/4).
(2) These tests are performed without an enclosure, with devices fixed on a metal grid and wired as per the recommendations in the manual “Grounding and
Electromagnetic Compatibility of PLC systems” (see page 10/4). 6
(e): Tests required by European e directives and based on IEC/EN 61131-2.

10

10/5
Environment tests Modicon X80 modules
(continued) Standards, certifications, and environment
conditions

Environment tests (continued)


Name of test Standards Levels
1 Immunity to HF interference (e) (1) (2)
Electrostatic discharges IEC/EN 61131-2; IEC/EN 61000-6-2; 6 kV contact; 8 kV air; 6 kV indirect contact
IEC 61000-4-2
For functional safety (DS criteria):
IEC 61000-6-7; IEC 61326-3-1
Radiated radio frequency electromagnetic IEC/EN 61131-2; IEC/EN 61000-6-2; 80MHz…1GHz: 10/15 V/m (20 V/m DS criteria); 3 V/m,
field IEC 61000-4-3 1.4 GHz...2 GHz: 3V/m (10 V/m DS criteria)

2 For functional safety (DS criteria):


IEC 61000-6-7; IEC 61326-3-1
2 GHz...6 GHz: 3V/m
Sinus amplitude modulated 80%,1 kHz + internal clock
frequencies
Electrical fast transient bursts IEC/EN 61131-2; IEC/EN 61000-6-2; For a or c main supplies:
IEC 61000-4-4 b 2 kV in common mode/2 kV in wire mode (4 kV DS
criteria with external protection)
For functional safety (DS criteria):
IEC 61000-6-7; IEC 61326-3-1 For a or c auxiliary supplies, a unshielded I/O:
b 2 kV in common mode

3
For analog, c unshielded I/O, communication and
shielded lines:
b 1 kV in common mode (3 kV DS criteria)
Surge IEC/EN 61131-2; IEC/EN 61000-6-2; For a/c main and auxiliary supplies, a unshielded I/O:
IEC 61000-4-5 b 2 kV in common mode/1 kV in differential mode (4 kV
DS criteria with external protection)
For functional safety (DS criteria):
IEC 61000-6-7; IEC 61326-3-1 For analog, c unshielded I/O:
b 2 kV in common mode/2 kV in differential mode

4
For communication and shielded lines:
b 1 kV in common mode (3 kV DS criteria)
Conducted disturbances induced by IEC/EN 61131-2; IEC/EN 61000-6-2; 10 V; 0.15 MHz...80 MHz (20 V DS criteria)
radiated electromagnetic fields IEC 61000-4-6 Sinus amplitude 80%, 1 kHz + spot frequencies
For functional safety (DS criteria):
IEC 61000-6-7; IEC 61326-3-1
Damped oscillatory wave IEC/EN 61131-2; For a/c main supplies and a auxiliary supplies,
IEC 61000-4-18 a unshielded I/O:

5
b 2.5 kV in common mode/1 kV in differential mode
For c auxiliary supplies, analog, c unshielded I/O:
b 1 kV in common mode/0.5 kV in differential mode
For communication and shielded lines:
b 0.5 kV in common mode
(1) Devices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of
PLC Systems” (see page 10/4).
(2) These tests are performed without an enclosure, with devices fixed on a metal grid and wired as per the recommendations in the manual “Grounding and

6 Electromagnetic Compatibility of PLC systems” (see page 10/4).


(e): Tests required by European e directives and based on IEC/EN 61131-2.

10

10/6
Environment tests Modicon X80 modules
(continued) Standards, certifications, and environment
conditions

Environment tests (continued)


Name of test Standards Levels
Electromagnetic emissions (e) (1) 1
Conducted emissions IEC/EN 61131-2; 150 kHz … 500 kHz: quasi-peak 79 dB (µV/m); average
IEC/EN 61000-6-4; CISPR 11 & 22, Class A, 66 dB (µV/m)
Group 1 500 kHz … 30 MHz: quasi-peak 73 dB (µV/m); average
60 dB (µV/m)
Radiated emissions IEC/EN 61131-2; 30 MHz ... 230 MHz: quasi-peak 40 dB (µV/m) (at 10 m/33 ft)
IEC/EN 61000-6-4; CISPR 11 & 22, Class A, 230 MHz ... 1 GHz: quasi-peak 47 dB (µV/m) (at 10 m/33 ft)
Group 1 1 GHz ... 3 GHz: quasi-peak 76 dB (µV/m) (at 3 m/9.84 ft)
3 GHz ... 6 GHz: quasi-peak 80 dB (µV/m) (at 3 m/9.84 ft) 2
Name of test Standards Levels
Immunity to climatic variations (1) (power on)
Dry heat IEC 60068-2-2 (Bb & Bd) 60 °C/140 °F, t = 16 hrs
[for ruggedized range: 70 °C/158 °F, t = 16 hrs] (2)
Cold IEC 60068-2-1 (Ab & Ad) 0 °C…- 25 °C/32 °F...-13 °F, t = 16 hrs + power on at 0 °C/
32 °F
[for ruggedized range: power on at -25 °C/-13 °F ] (2) 3
Damp heat, steady state IEC 60068-2-78 (Cab) 55 °C/131 °F, 93% relative humidity, t = 96 hrs
(continuous humidity) [for ruggedized range: 60 °C/140 °F ] (2)
Damp heat, cyclic IEC 60068-2-30 (Db) 55 °C…25 °C/131 °F...77 °F, 93…95% relative humidity,
(cyclical humidity) 2 cycles t = 12 hrs +12 hrs
Change of temperature IEC 60068-2-14 (Nb) 0 °C … 60 °C/32 °F...140 °F, 5 cycles t = 6 hrs + 6 hrs
[for ruggedized range: - 25 °C…70 °C/-13 °F...158 °F ] (2)
Name of test Standards Levels 4
Withstand to climatic variations (1) (power off)
Dry heat IEC/EN 61131-2; IEC 60068-2-2 (Bb & Bd) 85 °C/185 °F, t = 96 hrs
Cold IEC/EN 61131-2; IEC 60068-2-1 (Ab & Ad) -40 °C/-40 °F, t = 96 hrs
Damp heat, cyclic IEC/EN 61131-2; IEC 60068-2-30 (Db) 55 °C…25 °C/77 °F...131 °F, 93…95% relative humidity,
(cyclical humidity) 2 cycles t = 12 hrs + 12 hrs
Change of temperature
(thermal shocks)
IEC/EN 61131-2; IEC 60068-2-14 (Na) -40 °C...85 °C/-40 °F...185 °F, 5 cycles t = 3 hrs + 3 hrs
5
(1) Devices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of
PLC Systems” (see page 10/4).
(2) Refer also to the section “Treatment for severe environments”.
(e): Tests required by European e directives and based on IEC/EN 61131-2 standards.

10

10/7
Environment tests Modicon X80 modules
(continued) Standards, certifications, and environment
conditions

Environment tests (continued)


Name of test Standards Levels
1 Immunity to mechanical constraints (1) (power on)
Sinusoidal vibrations IEC/EN 61131-2; Basic IEC/EN 61131-2: 5 Hz ... 150 Hz, ± 3.5 mm/0.14 in.
IEC 60068-2-6 (Fc) amplitude (5 Hz …. 8.4 Hz), 1 g (8.4 Hz …. 150 Hz)
Specific profile: 5 Hz ... 150 Hz, ± 10.4 mm/0.41 in.
amplitude (5 Hz …. 8.4 Hz), 3 g (8.4 Hz …. 150 Hz)
For basic and specific: endurance: 10 sweep cycles for
each axis

2 IEC 60870-2-2;
IEC 60068-2-6 (Class Cm)
2 Hz ... 500 Hz, 7 mm/0.28 in. amplitude (2 Hz … 9 Hz),
2 g (9 Hz … 200 Hz), 1.5 g (200 Hz … 500 Hz)
endurance: 10 sweep cycles for each axis
IEC 60068-2-6 Seismic analysis: 3 Hz ... 35 Hz, 22.5 mm/0.89 in.
amplitude (3 Hz …. 8.1 Hz), 6 g (8.1 Hz …. 35 Hz)
Shock IEC/EN 61131-2; 30 g, 11 ms; 3 shocks/direction/axis (2)
IEC 60068-2-27 (Ea) For M580 Safety: 15 g, 11 ms; 3 shocks/direction/axis
25 g, 6 ms; 100 bumps/direction/axis (bumps) (3)

3 Free fall during operation IEC/EN 61131-2;


IEC 60068-2-32 (Ed Method 1)
1 m/3.28 ft, 2 falls

Name of test Standards Levels


Withstand to mechanical constraints (power off)
Random free fall with packaging IEC/EN 61131-2; 1 m/3.28 ft, 5 falls
IEC 60068-2-32 (Method 1)
Flat free fall IEC/EN 61131-2; 10 cm/0.33 ft, 2 falls

4 Controlled free fall


IEC 60068-2-32 (Ed Method 1)
IEC/EN 61131-2; 30° or 10 cm/0.33 ft, 2 falls
IEC 60068-2-31 (Ec)
Plugging/Unplugging IEC/EN 61131-2 For modules and connectors:
Operations: 50 for permanent connections, 500 for
non-permanent connections
(1) Devices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of
PLC Systems” (see page 10/4).
5 (2) When using fast actuators (response time y 5 ms) driven by relay outputs: 15 g, 11 ms; 3 shocks/direction/axis.
(3) When using fast actuators (response time y 15 ms) driven by relay outputs: 15 g, 6 ms; 100 bumps/direction/axis.
(e): Tests required by European e directives and based on IEC/EN 61131-2 standards.

10

10/8
Environment tests Modicon X80 modules
(continued) Standards, certifications, and environment
conditions

Environment tests (continued)


Name of test Standards Levels
Equipment and personnel safety (1) (e)
Dielectric strength and insulation IEC/EN 61131-2; Dielectric: 2 Un + 1000 V; t = 1 min
1
resistance IEC 61010-2-201; UL; CSA Insulation: Un y 50 V: 10 MΩ, 50 V y Un y 250 V :
100 MΩ
Ground continuity IEC/EN 61131-2; 30A, R y 0,1Ω; t = 2 min
IEC 61010-2-201; UL; CSA
Leakage current IEC/EN 61131-2; y 0.5 mA in normal condition

Protection offered by enclosures


IEC 61010-2-201; UL; CSA
IEC/EN 61131-2;
y 3.5 mA in single fault condition
IP20 and protection against standardized pins 2
IEC61010-2-201
Impact withstand IEC/EN 61131-2; Sphere of 500 g, fall from 1.3 m/4.27 ft (energy 6.8 J
IEC 61010-2-201; UL; CSA minimum)
Overload IEC/EN 61131-2; 50 cycles, Un, 1.5 In; t = 1 s ON + 9 s OFF
IEC 61010-2-201; UL; CSA

3
Endurance IEC/EN 61131-2; In, Un; 6,000 cycles: t = 1 s ON + 9 s OFF
IEC 61010-2-201; UL; CSA
Temperature rise IEC/EN 61131-2; UL; CSA; ATEX; IECEx Ambient temperature 60 °C/140 °F
[for ruggedized range: 70 °C/158 °F ] (2)
(1) Devices must be installed, wired, and maintained in accordance with the instructions provided in the manual “Grounding and Electromagnetic Compatibility of
PLC Systems” (see page 10/4).
(2) Refer also to the section “Treatment for severe environments”.
(e): Tests required by European e directives and based on IEC/EN 61131-2 standards.
4

10

10/9
Technical appendices
Modicon automation product certifications and
EC regulations

Some countries require certain electrical components to undergo certification by law. This certification takes the form of a certificate of
conformity to the relevant standards and is issued by the official body in question. Where applicable, certified devices must be labeled

1
accordingly. Use of electrical equipment on board merchant vessels generally implies that it has gained prior approval (i.e. certification) by
certain shipping classification societies.

Abbreviation Certification body / authority Country


CE European Community European Union
UL Underwriters Laboratories USA
CSA Canadian Standards Association Canada

2 RCM
EAC
Australian Communications and Media Authority
Eurasian conformity
Australia, New Zealand
Russia and Eurasian Economic Union
UKCA United Kingdom Central Authority United Kingdom
cULus Underwriters Laboratories USA, Canada
cCSAus Canadian Standards Association Canada, USA
IECEx International Electrotechnical Commission Explosive International

3 ATEX
TÜV Rheinland (Functional Safety)
ATmosphères EXplosives
Technischer Überwachungsverein Rheinland
International
International
ABS American Bureau of Shipping USA
BV Bureau Veritas France
DNV Det Norske Veritas Norway, Germany
LR Lloyd’s Register UK

4 RINA
RMRS
Registro Italiano Navale
Russian Maritime Register of Shipping
Italy
Russia
RRR Russian River Register Russia
CCS China Classification Society China
KRS Korean Register of Shipping Korea
Class NK Nippon Kaiji Kyokai Japan

5 Note: Although DNV GL rebranded to DNV as of March 1st, 2021, all certificates with DNV GL name and logo keep their initial validity date. Only rules in force on or
after March 1st, 2021, are rebranded to DNV.

The following tables provide an overview of the situation as of April 2023, in terms of which certifications (listed next to their respective bodies)
have been granted or are pending for our automation products.
Up-to-date information on which certifications have been obtained by products bearing the Schneider Electric brand can be viewed on
6 our website.

Product certifications
Certifications

Certified
Certification pending

7 CE UL CSA RCM EAC UKCA UL - CSA


Hazardous locations (1)
ATEX - IECEx TÜV Rheinland

EU USA Canada Australia Russia UK USA, Canada International Germany


Modicon STB Cl. I, Div. 2, Grps ABCD Zone 2 (2) (4)
Modicon Telefast ABE 7
Modicon Switch (3) Cl. I, Div. 2, Grps ABCD (2) Zone 2 (2)
Modicon MC80 Cl. I, Div. 2, Grps ABCD

8 Modicon M340
Modicon M580
Cl. I, Div. 2, Grps ABCD
Cl. I, Div. 2, Grps ABCD
Zone 2/22 (2) (5)
Zone 2/22 (2) (5)
Modicon M580 Safety Cl. I, Div. 2, Grps ABCD Zone 2/22 (2) (5) SIL3, SILCL3, SIL4,
Cat.4/PLe (6)
Modicon X80 Cl. I, Div. 2, Grps ABCD Zone 2/22 (2) (5)
Modicon Momentum Cl. I, Div. 2, Grps ABCD
Modicon Quantum (2) Cl. I, Div. 2, Grps ABCD Zone 2/22 (2) (5)

9
(1)Refer to user manual for installation in hazardous locations.
(2) Depends on product; Refer to the product certificates on our website.
(3) North American certification cULus (Canada and USA).
(4) For zones not covered by this specification, Schneider Electric offers a solution as part of the TPP (Technology Partner Program). Please contact our Customer
Care Center.
(5) Certified by INERIS. Refer to the instructions supplied with each ATEX and/or IECEx certified product.
(6) Certified by TÜV Rheinland for integration into a Safety function:
- up to SIL2 or SIL3 regarding IEC61508/61511 for Process,
- up to SILCL3 regarding IEC62061 and up to Cat.4/PLe regarding ISO13849 for Machine,
10 - up to SIL4 regarding EN50126/50128/50129 for Railway.

10/10
Technical appendices
Modicon automation product certifications and
EC regulations

Merchant navy certifications


Shipping classification societies
1
Certified
Certification pending
Only part of range certified
ABS BV DNV LR RINA RMRS RRR CCS KRS Class NK
USA France Norway/
Germany
Great Britain Italy Russia Russia China Korea Japan
2
Modicon STB
Modicon Telefast ABE 7
Modicon Switch (1) (1) (1)
Modicon MC80
Modicon M340
Modicon M580
Modicon M580 Safety
3
Modicon X80
Modicon Momentum
Modicon Quantum

EC regulations
European Directives 4
The open nature of the European markets assumes harmonization between the regulations set by the member states of the European Union.
European Directives are texts intended to remove restrictions on free circulation of goods and must be applied within all European Union
states.
Member states are obligated to incorporate each Directive into their national legislation, and to simultaneously withdraw any regulations that
contradict it.
Directives - and particularly those of a technical nature with which we are concerned - merely set out the objectives to be fulfilled (referred to as
“essential requirements”). Manufacturers are responsible for taking the necessary measures to establish that their products conform to the
5
requirements of each Directive applicable to their equipment.
As a general rule, manufacturers certify compliance with the essential requirements of the Directive(s) that apply to their products by applying a
e mark. The e mark is affixed to our products where applicable.

Significance of the e mark


The e mark on a product indicates the manufacturer's certification that the product conforms to the relevant European Directives; this is a
6
prerequisite for placing a product that is subject to the requirements of one or more Directives on the market and allowing its free circulation
within European Union countries. The e mark is intended for use by those responsible for regulating national markets.
Where electrical equipment is concerned, conformity to standards indicates that the product is fit for use. Only a warranty by a well-known
manufacturer can provide reassurance of a high level of quality.
As far as our products are concerned, one or more Directives are likely to apply in each case, in particular:
b The Low Voltage Directive (2014/35/EU)
b The Electromagnetic Compatibility Directive (2014/30/EU) 7
b The ATEX e Directive (2014/34/EU)
b The Machinery Directive (2006/42/EU)

Hazardous substances
These products are compatible with:
b The WEEE Directive (2012/19/EU) 8
b The RoHS Directive (2011/65/EU)
b The China RoHS Directive (Standard GB/T 26572-2011)
b REACH regulations (EC No. 1907/2006)
Note: Documentation on sustainable development is available on our website (product environmental profiles and instructions for use, RoHS and REACH
directives).

9
End of life (WEEE)
End of life products containing electronic cards must be dealt with by specific treatment processes.
When products containing backup batteries are unusable or at end of life they must be collected and treated separately. Batteries do not contain
a percentage by weight of heavy metals above the limit specified by European Directive 2013/56/EU.

10
(1) Please refer to Modicon Networking catalog for more details.

10/11
Presentation Dedicated service offers for your
installed base

Schneider Electric, with its experts, products, and dedicated tools, provides services
such as system design, consultancy, maintenance contracts, modernization of

1
facilities, and project delivery.
The Schneider Electric services offer is structured around several key areas:
b Maintenance and support services:
v A set of services to help maintain reliability and availability of automated control
systems. These services may be the subject of a bespoke maintenance contract
to meet your requirements more closely.
b Consultancy services:
2 v Diagnostics of the installed base
b Modernization solutions:
v Migration solutions including consultancy, expertise, tools, and technical support
to help ensure a smooth transition to newer technology while retaining the wiring
and encoding in most cases.
Customization services are also available to accommodate specific requirements.

3 For more information, please consult the specific pages on our website.

Maintenance and support services


Spare parts, exchanges, and repairs Everything you need to get equipment working again as quickly as possible
4 Solutions to respond very quickly to requests for spare parts, exchanges, and repairs
to your installed automation equipment (automation platforms, Human Machine
Interfaces, drives, distributed I/O):
b Spare parts management:
v Identification of critical parts
v Stock of spare parts: a Schneider Electric owned stock of spare parts, on your
site or in one of our warehouses, with immediate availability on site or a
5 contractually agreed delivery time if stored off site
v Testing of spare parts stored on site
v Automatic stock filling
b Repairs:
v Products that have broken down are repaired in a network of worldwide repair
centers. For each repaired product, our experts provide a detailed report.

6 b On-site repair:
v Our experts’ knowledge and expertise
v Monitoring of specific repair procedures
v Availability of our teams to respond 24/7
b Exchanges:
DIA6ED2171102EN v With standard replacements, receive a new or reconditioned product before the
product that has broken down has even been sent back

7 v Fast exchanges offer the option to receive the replacement product within
24 hours (in Europe)
Preventive maintenance Improving and helping to ensure the long-term reliability and performance of your
installations
Schneider Electric’s preventive maintenance expert assesses your site and the
equipment to be managed and sets up a maintenance program to accommodate
your specific requirements. A list is provided of the tasks to be performed and their
8 frequency, including site-specific tasks, describing how preventive maintenance is to
be managed.
Extended warranty An additional manufacturer warranty covering replacement or repair of the
equipment
The extended warranty offers the option to take out a 3-year warranty. The warranty
period can vary according to the geographical area (please contact our Customer

9 Online support
Care Center for more information).
Access to dedicated experts
Priority access to experts who can answer technical questions promptly concerning
equipment and software both on sale and no longer commercially available.
Software subscription Access to software upgrades and new features

10
By subscribing to software updates, users are able to:
b Purchase licences
b Receive updates, upgrades, software migrations, and transitions
b Download software from Schneider Electric’s software library

10/12
Presentation (continued) Dedicated service offers for your
installed base

Consultancy services
M2C (Maintenance and Modernization Professional tools and methods, proven experience of managing obsolescence and
Consultancy) updating installed bases, helping to reduce downtime and improve performance
With our maintenance and modernization consultancy offer, Schneider Electric will
1
help you check the state of your installed base by:
b Defining the scope and depth of the analysis in collaboration with you
b Collecting the technical data without shutting down production
b Analyzing and identifying avenues for improvement
b Producing a recommendation plan
Customer benefits: 2
b Learning about the components that make up the installed base and what their
life cycle state is (i.e. commercialized or obsolete)
b Better downtime anticipation
b Expert advice designed to improve performance
Modernization solutions
Migration to EcoStruxure Proven expertise, tools, and methods to give you a clear vision of the improvement
opportunities and guide you towards a successful modernization project
3
Schneider Electric offers gradual solutions of modernization through a set of
products, tools, and services that allow you to upgrade your installations with our
latest technologies. Our solutions offer you the choice to plan your modernization:
b Partial modernization: replacement of an old set of components with a new one

4
b Step-by-step modernization: gradual incorporation of new solutions or offers in
Find out more about EcoStruxure architectures on our website
www.se.com
the system
b Complete modernization: total renovation of the system

The table below lists our various migration offers:


Wide range of migration offers Moving to Modicon M580/M340 platforms and Modicon X80 station
Solution Solution type
Change the Change the Change the
Tools
SoftWare
Solution services
Modernization/ Manage Execute 5
CPU and CPU and the CPU, the I/O application migration your your
retain the I/O I/O racks and racks, and conversion service project project
racks and retain I/O field the I/O tool
wiring wiring with wiring
wiring system
Platform Premium
TSX47 to TSX107 6
Quantum
Modicon 984 & 800 Series I/O
Modicon Compact
Symax (1)
April Series 1000
April SMC
(2)
7
Merlin Gerin PB
AEG (1)
Rockwell SLC500
Rockwell PLC 5
Siemens S5 and S7 8
Service available

(1) Consult Schneider Services - project-specific solution is possible


(2) For April Series 1000 (April 5000-7000 and April 2000-3000)

Customization services
Consult Schneider Services - project-specific solution is possible
9
Schneider Electric is able to meet your specific requirements and provide you with
adapted products:
b Protective coating for HMIs, automation platforms, and distributed I/O modules
for use in harsh environments

10
b Customized cable lengths to match your specific needs
b Customized front panels for HMIs
b The multi-use flying lead I/O adapter can be prepared in the factory before use on
request.

Note: To check availability of services required, please contact our Customer Care Center.

10/13
Index Modicon X80 modules
Product reference index

A BMXCRA31200 7/6 BMXEIA0100 8/5 BMXMSP0200 6/11


ABE7CPA02 4/25 BMXCRA31210 7/6 BMXERT1604H 9/8 BMXNOM0200 8/7

1 ABE7CPA03
ABE7CPA21
4/25
4/25
BMXCRA31210C
BMXDAI0805
9/9
4/13
BMXERT1604T
BMXETM0200H
6/7
6/15
BMXNOM0200H
BMXNRP0200
9/9
8/14
ABE7CPA31 4/25 BMXDAI0814 4/13 9/8 BMXNRP0200C 9/9
ABE7CPA31E 4/25 BMXFCA150 4/25 BMXNRP0201 8/14
BMXDAI1602 4/13
ABE7CPA410 4/25 BMXFCA152 4/25
BMXDAI1602 4/13 BMXNRP0201C 9/9
ABE7CPA412 4/25
BMXDAI1602H 9/6 BMXFCA300 4/25 BMXPRA0100 7/7

2 B
BMXDAI1602H
BMXDAI1603
9/6
4/13
BMXFCA302
BMXFCA500
4/25
4/25
BMXSAI0410
BMXSDI1602
5/11
5/10
BMEAHI0812 4/29
BMXDAI1603H 9/6 BMXFCA502 4/25 BMXSDO0802 5/10
BMEAHI0812H 9/7
BMXDAI1604 4/13 BMXFCC053 4/15 BMXSRA0405 5/10
BMEAHO0412 4/29
BMXDAI1604H 9/6 BMXFCC1003 4/15 BMXXBC008K 2/9
BMEAHO0412C 9/7
BMXDAI1614 4/13 BMXFCC103 4/15 BMXXBC015K 2/9
BMECRA31210 7/6
BMXXBC030K
3
BMXDAI16142 4/13 BMXFCC203 4/15 2/9
BMECRA31210C 9/9
BMXDAI1614H 9/6 BMXFCC303 4/15 BMXXBC050K 2/9
BMECXM0100 8/9 BMXXBC120K 2/9
BMXDAI1615 4/13 BMXFCC503 4/15
BMECXM0100H 9/9 BMXXBE1000 2/9
BMXDAI1615H 9/6 BMXFCW1001 4/15
BMENOS0300 8/15 BMXXBE1000H 9/4
BMXDAO1605 4/14 BMXFCW1003 4/15
BMENOS0300C 9/9 BMXXBE2005 2/9
BMXDAO1605H 9/6 BMXFCW301 4/15
BMEXBP0400 2/4 BMXXBP0400 2/4
BMXDAO1615 4/14
4
BMXFCW301S 4/25
BMEXBP0400H 9/4 BMXXBP0400H 9/4
BMXDAO1615H 9/6 BMXFCW303 4/15
BMEXBP0602 2/4 BMXXBP0600 2/4
BMXDDI1602 4/13 BMXFCW501 4/15
BMEXBP0602H 9/4 BMXXBP0600H 9/4
BMXDDI1602H 9/6 BMXFCW501S 4/25
BMEXBP0800 2/4 BMXXBP0800 2/4
BMXDDI1603 4/13 BMXFCW503 4/15
BMEXBP0800H 9/4 BMXXBP0800H 9/4
BMXDDI1603H 9/6
BMEXBP1002 2/4 BMXFTA150 4/25
BMXDDI1604T 4/13 BMXXBP1200 2/4
BMXFTA152 4/25
5
BMEXBP1002H 9/4 BMXXBP1200H 9/4
BMXDDI3202K 4/13
BMEXBP1200 2/4 BMXFTA300 4/25
BMXDDI3202KH 9/6 BMXXEM010 2/5
BMEXBP1200H 9/4 BMXFTA302 4/25
BMXDDI3203 4/13 BMXXSP0400 2/5
BMXAMI0410 4/24 BMXFTB2000 4/15 BMXXSP0600 2/5
BMXDDI3203H 9/6 4/25
BMXAMI0410H 9/7 BMXXSP0800 2/5
BMXDDI3232 4/13 5/10
BMXAMI0800 4/24 5/11 BMXXSP1200 2/5
BMXDDI3232H 9/6
BMXAMI0810 4/24 6/5 BMXXTSCPS10 3/3
6
BMXDDI6402K 4/13
BMXAMI0810H 9/7 BMXFTB2010 4/15 5/7
BMXDDI6402KH 9/6
BMXAMM0600 4/24 4/25 BMXXTSCPS20 3/3
BMXDDM16022 4/14
BMXAMM0600H 9/7 5/10 5/7
BMXDDM16022H 9/7 5/11 BMXXTSHSC20 6/5
BMXAMO0210 4/24
BMXDDM16025 4/14 6/5
BMXAMO0210H 9/7 BMXDDM16025H 9/7 BMXFTB2020 4/15
P
BMXAMO0410 4/24 BMXDDM3202K 4/14 4/25

7 5/10 PMEPXM0100 8/11


BMXAMO0410H 9/7 BMXDDO1602 4/14
5/11 PMEPXM0100H 9/9
BMXAMO0802 4/24 BMXDDO1602H 9/6 6/5 PMESWT0100 6/17
BMXAMO0802H 9/7 BMXDDO1612 4/14 BMXFTB2800 4/25
BMXART0414 4/24 BMXDDO1612H 9/6 6/7 S
BMXART0414H 9/7 BMXDDO3202 4/14 6/11
STBXSP3010 2/5
BMXART0814 4/24 BMXDDO3202H 9/6 BMXFTB2800 6/9
STBXSP3020 2/5
8 BMXART0814H
BMXCPS2000
9/7
3/3
BMXDDO3202K
BMXDDO3202KC
4/14
9/6
BMXFTB2820 4/25
6/7
T
BMXCPS2010 3/3 6/9
BMXDDO6402K 4/14 TCSEGDB23F24FA 8/13
BMXCPS3020 3/3 BMXFTB2820 6/11
BMXDDO6402KC 9/6 TCSEGDB23F24FK 9/9
BMXCPS3020H 9/5 BMXFTB4000 4/15
BMXDRA0804T 4/14 TCSEGPA23F14FK 9/9
BMXCPS3500 9/5 BMXFTB4000H 9/8
BMXDRA0815 4/14 TCSMCN3M4F3C2 8/7
BMXFTB4020 4/15
9
BMXCPS3500H 9/5 BMXDRA0815H 9/6
BMXFTB4020H 9/8 TCSMCN3M4M3S2 8/7
BMXCPS3522 3/3 BMXDRA1605 4/14 9/9
BMXCPS3522H 9/5 BMXFTW1001 4/15
BMXDRA1605H 9/6 TCSXCN3M4F3S4 8/7
BMXCPS3522S 5/7 BMXFTW301 4/15 9/9
BMXDRC0805 4/14
BMXFTW301S 4/25 TSXTLYEX
BMXCPS3540T 3/3 BMXDRC0805H 9/6 2/9
BMXFTW305 4/15
BMXCPS4002 3/3 BMXEAE0300 6/9
BMXFTW308S 4/25 V
BMXCPS4002H 9/5 BMXEAE0300H
10
9/8 VW3M8223R30 6/11
BMXFTW501 4/15
BMXCPS4002S 5/7 BMXEHC0200 6/5
BMXFTW501S 4/25
BMXCPS4022 3/3 BMXEHC0200H 9/8
BMXFTW505 4/15
BMXCPS4022H 9/5 BMXEHC0800 6/5
BMXFTW508S 4/25
BMXCPS4022S 5/7 BMXEHC0800H 9/8

10/14
Learn more about our products at
www.se.com

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability
of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric
nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Design: Schneider Electric


Photos: Schneider Electric