0% found this document useful (0 votes)
52 views4 pages

Control Panel HVAC BM

The document provides a cost estimation breakdown for an HVAC project. It lists two HVAC control panels with details on points, components, and specifications. The total cost is calculated based on unit price and quantity.

Uploaded by

Alif Firdaus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views4 pages

Control Panel HVAC BM

The document provides a cost estimation breakdown for an HVAC project. It lists two HVAC control panels with details on points, components, and specifications. The total cost is calculated based on unit price and quantity.

Uploaded by

Alif Firdaus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

COST ESTIMATION BREAK-DOWN

JOB NO : 210037(EARLY WORK SERVICE FOR CARIFLEX ASIA EXPANSION PHASE-1)


HVAC EQUIPMENT

Spec/Reference

ITEM ITEM
NO Rev SYSTEM UNIT TOTAL Q'TY Unit Price Amount Remark REMARKS
NAME NO.
CAPACITY MATERIAL Size Spec. DESCRIPTION

ADMINISTRATION & LABORATORY BUILDING


CONTROL PANEL : INDOOR INSTALLATION; FEEDER PROTECTION RELAYS, CIRCUIT BREATKERS, ALL
NECESSARY ELECTRICAL ACCESSORIES.
- PROGRAMMABLE MICROPROCESSOR BASED DDC MODULE(COMPACT TYPE)
- SINGLE CPU
- COMPATIBLE BAC NET TCP/IP COMMUNICATION WITH BTL CERTIFICATION
TIME SYNCRONIZATION
SELF STANDING FLOOR MOUNTED ENCLOSURE
ENCLOSURE THICKNESS : RITTAL STD
PANEL COLOR : RAL 7035 (HOLD)
N-1 A HVAC CONTROL PANEL HVAC CONTROL PANEL(DDC CONTROLLER) HCP-001 370 POINTS - - - PANEL VENTILATION FAN, DUST FILTER EA 1 522
PROTECTION CLASS : IP42
ENCLOSURE THICKNESS : FRONT / 2.0T, OTHERS / 1.5T
MANUAL SELECTOR SWITCH, ALARM INDICATOR LAMP & LOCAL DISPLAY (15" PANEL TOUCHVIEW)
MANDATORY SPARE RATE : I/O POINTS & TB 20% AND PANEL SPACE 20%
INCLUDED NETWORK DEVICE AND ACCESSARY
1) DIGITAL OUTPUT : 180 POINTS
2) DIGITAL INPUT : 171 POINTS
3) ANALOG OUTPUT : 3 POINTS
4) ANALOG INPUT : 16 POINTS
5) INCLUDING NECESSARY STANDARD ACCESSARIES

Maintenance Building
CONTROL PANEL : INDOOR INSTALLATION; FEEDER PROTECTION RELAYS, CIRCUIT BREATKERS, ALL
NECESSARY ELECTRICAL ACCESSORIES.
- PROGRAMMABLE MICROPROCESSOR BASED DDC MODULE(COMPACT TYPE)
- SINGLE CPU
- COMPATIBLE BAC NET TCP/IP COMMUNICATION WITH BTL CERTIFICATION
TIME SYNCRONIZATION
SELF STANDING FLOOR MOUNTED ENCLOSURE
ENCLOSURE THICKNESS : RITTAL STD
PANEL COLOR : RAL 7035 (HOLD)
N-2 A HVAC CONTROL PANEL HVAC CONTROL PANEL(DDC CONTROLLER) HCP-002 147 POINTS - - - PANEL VENTILATION FAN, DUST FILTER EA 1 522
PROTECTION CLASS : IP42
ENCLOSURE THICKNESS : FRONT / 2.0T, OTHERS / 1.5T
MANUAL SELECTOR SWITCH, ALARM INDICATOR LAMP & LOCAL DISPLAY (15" PANEL TOUCHVIEW)
MANDATORY SPARE RATE : I/O POINTS & TB 20% AND PANEL SPACE 20%
INCLUDED NETWORK DEVICE AND ACCESSARY
1) DIGITAL OUTPUT : 76 POINTS
2) DIGITAL INPUT : 63 POINTS
3) ANALOG OUTPUT : 3 POINTS
4) ANALOG INPUT : 5 POINTS
5) INCLUDING NECESSARY STANDARD ACCESSARIES
COST ESTIMATION BREAK-DOWN
JOB NO : 210037(EARLY WORK SERVICE FOR CARIFLEX ASIA EXPANSION PHASE-1)
HVAC EQUIPMENT

Spec/Reference

ITEM ITEM
NO Rev SYSTEM UNIT TOTAL Q'TY Unit Price Amount Remark REMARKS
NAME NO.
CAPACITY MATERIAL Size Spec. DESCRIPTION

Main Control Building


CONTROL PANEL : INDOOR INSTALLATION; FEEDER PROTECTION RELAYS, CIRCUIT BREATKERS, ALL
NECESSARY ELECTRICAL ACCESSORIES.
- PROGRAMMABLE MICROPROCESSOR BASED DDC MODULE(COMPACT TYPE)
- SINGLE CPU
- COMPATIBLE BAC NET TCP/IP COMMUNICATION WITH BTL CERTIFICATION
TIME SYNCRONIZATION
SELF STANDING FLOOR MOUNTED ENCLOSURE
ENCLOSURE THICKNESS : RITTAL STD
PANEL COLOR : RAL 7035 (HOLD)
N-3 A HVAC CONTROL PANEL HVAC CONTROL PANEL(DDC CONTROLLER) HCP-003 217 POINTS - - - PANEL VENTILATION FAN, DUST FILTER EA 1 522
PROTECTION CLASS : IP42
ENCLOSURE THICKNESS : FRONT / 2.0T, OTHERS / 1.5T
MANUAL SELECTOR SWITCH, ALARM INDICATOR LAMP & LOCAL DISPLAY (15" PANEL TOUCHVIEW)
MANDATORY SPARE RATE : I/O POINTS & TB 20% AND PANEL SPACE 20%
INCLUDED NETWORK DEVICE AND ACCESSARY
1) DIGITAL OUTPUT : 87 POINTS
2) DIGITAL INPUT : 117 POINTS
3) ANALOG OUTPUT : 3 POINTS
4) ANALOG INPUT : 10 POINTS
5) INCLUDING NECESSARY STANDARD ACCESSARIES

Substation
CONTROL PANEL : INDOOR INSTALLATION; FEEDER PROTECTION RELAYS, CIRCUIT BREATKERS, ALL
NECESSARY ELECTRICAL ACCESSORIES.
- PROGRAMMABLE MICROPROCESSOR BASED DDC MODULE(COMPACT TYPE)
- SINGLE CPU
- COMPATIBLE BAC NET TCP/IP COMMUNICATION WITH BTL CERTIFICATION
TIME SYNCRONIZATION
SELF STANDING FLOOR MOUNTED ENCLOSURE
ENCLOSURE THICKNESS : RITTAL STD
PANEL COLOR : RAL 7035 (HOLD)
N-4 A HVAC CONTROL PANEL HVAC CONTROL PANEL(DDC CONTROLLER) HCP-004 218 POINTS - - - PANEL VENTILATION FAN, DUST FILTER EA 1 522
PROTECTION CLASS : IP42
ENCLOSURE THICKNESS : FRONT / 2.0T, OTHERS / 1.5T
MANUAL SELECTOR SWITCH, ALARM INDICATOR LAMP & LOCAL DISPLAY (15" PANEL TOUCHVIEW)
MANDATORY SPARE RATE : I/O POINTS & TB 20% AND PANEL SPACE 20%
INCLUDED NETWORK DEVICE AND ACCESSARY
1) DIGITAL OUTPUT : 93 POINTS
2) DIGITAL INPUT : 114 POINTS
3) ANALOG OUTPUT : 3 POINTS
4) ANALOG INPUT : 8 POINTS
5) INCLUDING NECESSARY STANDARD ACCESSARIES
COST ESTIMATION BREAK-DOWN
JOB NO : 210037(EARLY WORK SERVICE FOR CARIFLEX ASIA EXPANSION PHASE-1)
HVAC EQUIPMENT

Spec/Reference

ITEM ITEM
NO Rev SYSTEM UNIT TOTAL Q'TY Unit Price Amount Remark REMARKS
NAME NO.
CAPACITY MATERIAL Size Spec. DESCRIPTION

Product Warehouse-1
CONTROL PANEL : INDOOR INSTALLATION; FEEDER PROTECTION RELAYS, CIRCUIT BREATKERS, ALL
NECESSARY ELECTRICAL ACCESSORIES.
- PROGRAMMABLE MICROPROCESSOR BASED DDC MODULE(COMPACT TYPE)
- SINGLE CPU
- COMPATIBLE BAC NET TCP/IP COMMUNICATION WITH BTL CERTIFICATION
TIME SYNCRONIZATION
SELF STANDING FLOOR MOUNTED ENCLOSURE
ENCLOSURE THICKNESS : RITTAL STD
PANEL COLOR : RAL 7035 (HOLD)
N-5 A HVAC CONTROL PANEL HVAC CONTROL PANEL(DDC CONTROLLER) HCP-005 158 POINTS - - - PANEL VENTILATION FAN, DUST FILTER EA 1 522
PROTECTION CLASS : IP42
ENCLOSURE THICKNESS : FRONT / 2.0T, OTHERS / 1.5T
MANUAL SELECTOR SWITCH, ALARM INDICATOR LAMP & LOCAL DISPLAY (15" PANEL TOUCHVIEW)
MANDATORY SPARE RATE : I/O POINTS & TB 20% AND PANEL SPACE 20%
INCLUDED NETWORK DEVICE AND ACCESSARY
1) DIGITAL OUTPUT : 89 POINTS
2) DIGITAL INPUT : 62 POINTS
3) ANALOG OUTPUT : 2 POINTS
4) ANALOG INPUT : 5 POINTS
5) INCLUDING NECESSARY STANDARD ACCESSARIES

PRESSURE DIFFERENTIAL SWITCH (FOR FAN)


- MEASURING RANGE : 0~1000 Pa
- OPERATING VOLTAGE : AC/DC 24V
N-10 A HVAC CONTROL DEVICE PRESSURE DIFFERENTIAL SWITCH(FOR FILTER) - - - - - EA 29 522
- OUTPUT SIGNAL : SPDT
- PROTECTION CLASS : IP54 (INDOOR)
- MOUNTING BRACKET AND ACCESSARY

PRESSURE DIFFERENTIAL SWITCH (FOR FAN)


- MEASURING RANGE : 0~1000 Pa
- OPERATING VOLTAGE : AC/DC 24V
N-11 A HVAC CONTROL DEVICE PRESSURE DIFFERENTIAL SWITCH(FOR FILTER) - - - - - EA 16 522
- OUTPUT SIGNAL : SPDT
- PROTECTION CLASS : IP65/66 (OUTDOOR)
- MOUNTING BRACKET AND ACCESSARY

PRESSURE DIFFERENTIAL SWITCH (FOR FAN)


- MEASURING RANGE : 0~1000 Pa
- OPERATING VOLTAGE : AC/DC 24V
N-12 A HVAC CONTROL DEVICE PRESSURE DIFFERENTIAL SWITCH(FOR FILTER) - - - - - EA 4 522
- OUTPUT SIGNAL : SPDT
- PROTECTION CLASS : Exd IIC T6 (EXPROSION PROOF)
- MOUNTING BRACKET AND ACCESSARY

PRESSURE DIFFERENTIAL INDICATING SWITCH (FOR FILTER)


- MEASURING RANGE : 0~1000 Pa
- OPERATING VOLTAGE : AC/DC 24V
N-13 A HVAC CONTROL DEVICE PRESSURE DIFFERENTIAL SWITCH(FOR FILTER) - - - - - EA 14 522
- OUTPUT SIGNAL : SPDT
- PROTECTION CLASS : IP54 (INDOOR)
- MOUNTING BRACKET AND ACCESSARY

PRESSURE DIFFERENTIAL INDICATING SWITCH (FOR FILTER)


- MEASURING RANGE : 0~1000 Pa
- OPERATING VOLTAGE : AC/DC 24V
N-14 A HVAC CONTROL DEVICE PRESSURE DIFFERENTIAL SWITCH(FOR FILTER) - - - - - EA 2 522
- OUTPUT SIGNAL : SPDT
- PROTECTION CLASS : IP 65/66 (OUTDOOR)
- MOUNTING BRACKET AND ACCESSARY

TEMPERATURE TRANSMITTER (FOR DUCT)


- OPERATING VOLTAGE : DC 24V
- OUTPUT SIGNAL : 4~20mA
N-15 A HVAC CONTROL DEVICE TEMPERATURE TRANSMITTER - - - - - EA 8 522
- PROTECTION CLASS : IP54
- CALRIBRATION CERTIFICATE
- MOUNTING BRACKET AND ACCESSARY

TEMPERATURE TRANSMITTER (FOR DUCT)


- OPERATING VOLTAGE : DC 24V
- OUTPUT SIGNAL : 4~20mA
N-16 A HVAC CONTROL DEVICE TEMPERATURE TRANSMITTER - - - - - EA 2 522
- PROTECTION CLASS : IP65/66
- CALRIBRATION CERTIFICATE
- MOUNTING BRACKET AND ACCESSARY
COST ESTIMATION BREAK-DOWN
JOB NO : 210037(EARLY WORK SERVICE FOR CARIFLEX ASIA EXPANSION PHASE-1)
HVAC EQUIPMENT

Spec/Reference

ITEM ITEM
NO Rev SYSTEM UNIT TOTAL Q'TY Unit Price Amount Remark REMARKS
NAME NO.
CAPACITY MATERIAL Size Spec. DESCRIPTION

TEMPERATURE TRANSMITTER (FOR ROOM)


- OPERATING VOLTAGE : DC 24V
- OUTPUT SIGNAL : 4~20mA
N-17 A HVAC CONTROL DEVICE TEMPERATURE TRANSMITTER - - - - - EA 15 522
- PROTECTION CLASS : IP54
- CALRIBRATION CERTIFICATE
- MOUNTING BRACKET AND ACCESSARY

HUMIDITY TRANSMITTER (FOR DUCT)


- OPERATING VOLTAGE : DC/AC 24V
- OUTPUT SIGNAL : 4..20mA
N-18 A HVAC CONTROL DEVICE HUMIDITY TRANSMITTER - - - - - EA 8 522
- PROTECTION CLASS : IP54
- CALRIBRATION CERTIFICATE
- MOUNTING BRACKET AND ACCESSARY

HUMIDITY TRANSMITTER (FOR DUCT)


- OPERATING VOLTAGE : DC/AC 24V
- OUTPUT SIGNAL : 4..20mA
N-19 A HVAC CONTROL DEVICE HUMIDITY TRANSMITTER - - - - - EA 2 522
- PROTECTION CLASS : IP65/66
- CALRIBRATION CERTIFICATE
- MOUNTING BRACKET AND ACCESSARY

PRESSURE DIFFERENTIAL INDICATING TRANSMITTER (FOR ROOM)


- OPERATING VOLTAGE : DC/AC 24V
- OUTPUT SIGNAL : 4..20mA
N-20 A HVAC CONTROL DEVICE PRESSURE DIFFERENTIAL TRANSMITTER - - - - - EA 15 522
- PROTECTION CLASS : IP54
- CALRIBRATION CERTIFICATE
- MOUNTING BRACKET AND ACCESSARY