Substation 9
Substation 9
300 MVA 69 KV 69 KV
230-69-13.8 kV ABS @ Ibaan ABS
SUBTRANSMISSION
LA
69 KV
PT
350:1
CT
100:5
ABS SUBSTATION 2
69 KV
1600 AMP.
Relaying CT 50 50N
CT Ratio: 100 : 5 51 51N Brand: GE
Overcurrent Numerical Relay
Model: MIF II
69 kV Live-Tank Gas Circuit Breaker
Rated Normal Current: 2000 A
BCT
LA
BCT 69 KV
SGB
20 MVA Power Transformer
67,000D/13,200Y
BCT
10 KV
LA
LA LA LA LA
10 KV 10 KV 10 KV 10 KV
15 kV Disconnecting Switch 15 kV Disconnecting Switch 15 kV Disconnecting Switch 15 kV Disconnecting Switch
Rated Cont. Current: 600 A Rated Cont. Current: 600 A Rated Cont. Current: 600 A Rated Cont. Current: 600 A
CT NOJA Recloser Cooper Recloser NOJA Recloser
TAVRIDA Recloser 200:5 15 kV, 800 Amps FXD 15 kV, 800 Amps
15.5 kV 630 A 15 kAIC 15 kAIC
PT 15 kV, 630 Amps PT
16 kAIC 70:1
70:1 12.5 kAIC
Landis + Gyr M M Landis + Gyr Landis + Gyr M M Landis + Gyr
CT CT
200:5 CT 200:5 CT
150:5 100:5
LA LA LA LA
10 KV 10 KV 10 KV 10 KV
15 kV Disconnecting Switch 15 kV Disconnecting Switch
Rated Cont. Current: 600 A Rated Cont. Current: 600 A
15 kV Disconnecting Switch 15 kV Disconnecting Switch
Rated Cont. Current: 600 A Rated Cont. Current: 600 A
FEEDER III- FEEDER IV
FEEDER 1 FEEDER II -
ITEMREF QUANTITY LOCATION:
Cadd by: Checked by: File Name Date SCALE
Engr. D. M. MARASIGAN SUBSTATION 9 NTS
Noted by
20 MVA
EE 414 SS DESIGN Sheet
1 of 1