Thermal Insulation
Thermal Insulation
Thermal Insulation
It is important to know how heat is transferred in fish holds. Heat is transferred by conduction,
convection or radiation, or by a combination of all three. Heat always moves from warmer to colder
areas; it seeks a balance. If the interior of an insulated fish hold is colder than the outside air, the fish
hold draws heat from the outside. The greater the temperature difference, the faster the heat flows to
the colder area.
Conduction. By this mode, heat energy is passed through a solid, liquid or gas from molecule to
molecule in a material. In order for the heat to be conducted, there should be physical contact
between particles and some temperature difference. Therefore, thermal conductivity is the measure of
the speed of heat flow passed from particle to particle. The rate of heat flow through a specific
material will be influenced by the difference of temperature and by its thermal conductivity.
Convection. By this mode, heat is transferred when a heated air/gas or liquid moves from one place
to another, carrying its heat with it. The rate of heat flow will depend on the temperature of the moving
gas or liquid and on its rate of flow.
Radiation. Heat energy is transmitted in the form of light, as infrared radiation or another form of
electromagnetic waves. This energy emanates from a hot body and can travel freely only through
completely transparent media. The atmosphere, glass and translucent materials pass a significant
amount of radiant heat, which can be absorbed when it falls on a surface (e.g. the ship’s deck surface
on a sunny day absorbs radiant heat and becomes hot). It is a well known fact that light-coloured or
shiny surfaces reflect more radiant heat than black or dark surfaces, therefore the former will be
heated more slowly.
In practice, the entry of heat into fish holds/fish containers is the result of a mixture of the three modes
mentioned above, but the most significant mode is by conduction through walls and flooring.
5.1.2 Definitions
The thermal properties of insulating materials and other common fishing vessel construction materials
are known or can be accurately measured. The amount of heat transmission (flow) through any
combination of materials can be calculated. However, it is necessary to know and understand certain
technical terms to be able to calculate heat losses and understand the factors that are involved.
By convention, the ending -ity means the property of a material, regardless of its thickness and the
ending -ance refers to the property of a specific body of given thickness.
Heat energy
One kilocalorie (1 kcal or 1 000 calories) is the amount of heat (energy) needed to raise the
temperature of one kg of water by one degree Celsius (°C). The SI standard unit for energy is Joule
(J). One kcal is approximately 4.18 kJ (this varies slightly with temperature). Another unit is the Btu
(British thermal unit). One Btu corresponds roughly to 1 kJ.
Thermal conductivity
In simple terms this is a measure of the capacity of a material to conduct heat through its mass.
Different insulating materials and other types of material have specific thermal conductivity values that
can be used to measure their insulating effectiveness. It can be defined as the amount of heat/energy
(expressed in kcal, Btu or J) that can be conducted in unit time through unit area of unit thickness of
material, when there is a unit temperature difference. Thermal conductivity can be expressed in kcal
m-1 °C-1, Btu ft-1 °F-1 and in the SI system in watt (W) m-1 °C-1. Thermal conductivity is also known as the
k-value.
This is designated as l (the Greek letter lambda) and defined as the amount of heat (in kcal)
conducted in one hour through 1 m2 of material, with a thickness of 1 m, when the temperature drop
through the material under conditions of steady heat flow is 1 °C. The thermal conductance is
established by tests and is the basic rating for any material. l can also be expressed in Btu ft-2 h-1 °F-
1
(British thermal unit per square foot, hour, and degree Fahrenheit) or in SI units in W m-2 Kelvin (K)-1.
Thermal resistivity
The thermal resistance (R-value) is the reciprocal of l (1/l) and is used for calculating the thermal
resistance of any material or composite material. The R-value can be defined in simple terms as the
resistance that any specific material offers to the heat flow. A good insulation material will have a high
R-value. For thicknesses other than 1 m, the R-value increases in direct proportion to the increase in
thickness of the insulation material. This is x/l, where x stands for the thickness of the material in
metres.
The symbol U designates the overall coefficient of heat transmission for any section of a material or a
composite of materials. The SI units for U are kcal per square metre of section per hour per degree
Celsius, the difference between inside air temperature and outside air temperature. It can also be
expressed in other unit systems. The U coefficient includes the thermal resistances of both surfaces
of walls or flooring, as well as the thermal resistance of individual layers and air spaces that may be
contained within the wall or flooring itself.
This is defined as the quantity of water vapour that passes through the unit of area of a material of
unit thickness, when the difference of water pressure between both faces of the material is the unit. It
can be expressed as g cm mmHg-1 m-2 day-1 or in the SI system as g m MN-1 s-1 (grams metre per mega
Newton per second).
This is the reciprocal of the permeance to water vapour and is defined as rv = 1/pv.
to prevent heat transmission entering from the surrounding warm air, the engine room and
heat leaks (fish hold walls, hatches, pipes and stanchions);
to optimize the useful capacity of the fish hold and fish-chilling operating costs;
to help reduce energy requirements for refrigeration systems if these are used.
Because hold space is often at a premium on small vessels and the costs of insulation can amount to
a significant proportion of the costs involved in construction, the choice of insulation material can be
very important.
Several thermal insulation materials are used commercially for fishing vessels, but few are completely
satisfactory for this purpose. The main problems are lack of sufficient mechanical strength and
moisture absorption. The latter is a particularly significant problem in fishing vessels, where melting
ice is used as a chilling medium. Thermal insulators work by trapping bubbles or pockets of gas inside
a foam structure. When these cells of gas are filled with moisture, there are significant losses in
insulating efficiency.
The thermal conductivity of water (at 10 °C) is 0.5 kcal m-1 h-1 °C-1 and that of ice (at 0 °C) is 2 kcal m-
1
h-1 °C-1 (about four times the value of water). In comparison, dry stagnant air is about 0.02 kcal m-1 h-
1
°C-1. Figure 5.1 shows the thermal conductivities of R-11, dry air, water vapour and ice within an
insulation material and illustrates the significant increase in thermal conductivity that can occur if
air/gas is replaced by water vapour in the insulation.
Absorption of moisture by the insulating materials can take place not only by direct contact with water
leaking into the hold walls, but also by condensation of water vapour in the walls where the dew point
is reached in the temperature gradient through the walls.
The proper design of water vapour barriers is therefore of utmost importance for protecting the
insulation from gaining moisture. In most climates the transmission of water vapour will tend to be
from the outside to the inside of the hold walls, as the external temperature is likely to be higher than
the internal temperature. This requires an impervious moisture-proof layer on the outside of the
insulation, as well as a waterproof barrier on the lining to prevent liquid melt water entering the
insulation. The vapour barrier can be achieved either through watertight surfaces of prefabricated
insulation panels (sandwich-type panels, with one face being the vapour barrier of light-gauge
galvanized steel sheets and the other face being the internal finish of plastic-coated aluminium or
galvanized iron sheets), reinforced plastic materials, polythene sheets, plastic films of minimum
thickness of 0.2 mm or aluminium foil of minimum thickness of 0.02 mm, laminated with a bitumen
membrane. The minimum thickness of aluminium or galvanized sheets should be 0.3 mm.
FIGURE 5.1 Comparison of thermal conductivities of R-11, dry air, water vapour, water and ice
within an insulation material
BOX 5.1
Desirable characteristics for insulation materials for fish holds
Thermal conductivity
Best insulation materials should have the lowest thermal conductivity, in order to
reduce the total coefficient of heat transmission. Thus, less insulating material
will be required. Dry stagnant gas is one of the best insulating materials. The
insulating properties of commercially available insulating materials are
determined by the amount of gas held inside the material and the number of gas
pockets. Therefore, the higher the number of cells (which can maintain the gas
stagnant) and the smaller their size, the lower the thermal conductivity of such
insulating material. These cells should not be interlinked, as this will allow
convection of heat.
Moisture-vapour permeability
Resistance/installation features
Safety features
Box 5.1 shows the main characteristics that a suitable insulation material should have.
TABLE 5.1
Density values and thermal conductivity at 20-25 °C of polyurethane insulation
One of the best commercially available choices of insulation material for fishing vessels is
polyurethane foam. It has good thermal insulating properties, low moisture-vapour permeability, high
resistance to water absorption, relatively high mechanical strength and low density. In addition, it is
relatively easy and economical to install. The main features of polyurethane foams are shown in Table
5.1.
Polyurethane foam is effective as an insulator because it has a high proportion (90 percent minimum)
of non-connected closed microcells, filled with inert gas. Until recently, the inert gas most commonly
used in polyurethane foams was R-11 (trichlorofluoromethane). However, the Montreal Protocol on
Substances that Deplete the Ozone Layer has called for the phasing out of the use of CFCs such as
R-11. Replacement foaming agents are being investigated at the present time, with hydrocarbons,
hydrofluorocarbons and inert gases such as carbon dioxide being developed as substitutes.
The main ways polyurethane foams can be applied and used are as rigid boards/ slabs and pre-
formed pipes, which can be manufactured in various shapes and sizes. The main applications of
these types of foam are in chill rooms, ice stores and cold stores. Structural sandwich panels
incorporating slabs of foam can be produced for prefabricated refrigerated stores.
It can be poured in place. This involves mixing the chemicals either manually or by
mechanical means and pouring in open moulds or spaces where insulation is required. The
mixture creates a foam and solidifies. If necessary, the solidified foam can be cut to the
required size or shape.
It can be sprayed directly onto a solid surface using guns that mix and atomize the foam as it
is being applied. For example, fish holds or tanks can be sprayed directly on the outside
surface and inaccessible areas may be sprayed on and built up without the need of moulds.
The foam will adhere to itself and most metals, wood and other materials. It can also be
injected into a cavity (e.g. it can be used for moulded insulated boxes). Spray and injection
techniques are becoming the most widely used for the installation of rigid polyurethane foam
in ships and fishing vessels.
In frothing, the mixture of chemicals is dispensed partially pre-expanded, like an aerosol
cream. Appropriate equipment, including an extra blowing agent, is required for immediate
pre-expansion. The final phase of expansion takes place as the chemical reaction reaches
completion. This technique is used when rigid foams/panels with a high strength-weight ratio
are required.
BOX 5.2
Precautions against fire during the application of rigid polyurethane foam
in ships
Storage on site
Naked flames and sources of high radiant heat should be prohibited in areas
where board or slabstock are stored. Inflammable solvents and adhesives should
be stored under conditions where the usual precautions applicable to such
materials are observed.
Site application
General - Whenever possible all welding and other operations involving naked
flames or high temperatures in the proposed insulated area, or on external
surfaces of it, should be completed before the foam is applied. All these
operations, and smoking, must be prohibited while the application of the foam is
in progress to prevent ignition of exposed foam, solvents or adhesives.
Spraying - Immediately after spraying, the foam is left exposed. In this condition,
it constitutes a hazard if subjected to sources of heat or ignition. All welding or
other operations involving naked flames or high temperatures in the area must
be prohibited until the foam is suitably protected. Also, before the foam is
protected, naked flames or high temperatures must not be allowed to penetrate
the foam area from outside, e.g. by welding or cutting the plates behind the
insulation. Dust arising from sanding or buffing operations, which may be carried
out to produce a flat foam surface, may, in common with other dusts, constitute a
fire hazard. Suitable precautions should be taken by removing the dust as soon
as possible. The sprayed foam surface must be covered as soon as practicable,
by cladding approved by the competent authority.
Board or slabstock - Particular attention must be paid to the fire hazards arising
from the use of inflammable adhesives. Immediately after application the
insulation is exposed and therefore constitutes a fire hazard similar to that of
unprotected sprayed foam. The precautions detailed above for sprayed foam
must be taken before the foam is protected by cladding approved by the
competent authority.
Repair work
It may be found necessary to remove the cladding from the foam. If any welding
or other operation involving naked flames or high temperatures is to be carried
out, the foam must be cut back to at least 1 ft (0.33 m) from the site of operation.
All exposed foam must be protected (e.g. with an asbestos blanket) from the
naked flames or high temperatures.
Note: these guidelines only refer to those rigid polyurethane foams which
incorporate a fire-retardant additive and which are made from methane
diisocyanate.
Fire regulations require that fire-retarding agents should be incorporated into polyurethane insulation
foam. In addition, a protective lining should be incorporated so as to make the foam more difficult to
ignite from a small source of flame. Laboratory tests indicate that unprotected (rigid) polyurethane
foam containing a fire-retardant will not ignite from small flame sources such as matches, but will burn
rapidly when exposed to large sources of flame and heat. However, when the polyurethane foam is
protected from direct contact with flames and air is excluded, the burning of the foam is eliminated.
Also the type of resin and isocyanate used in the production of the foam can influence its performance
against fire. Foams produced with toluene diisocyanate show a tendency to soften and melt more
readily under the influence of heat than those foams made from methane diisocyanate. The
precautions against fire during the application of polyurethane foam in ships listed in Box 5.2 should
be taken into consideration.
Several grades of polyurethane foams are available, including grades that are particularly fire-
resistant. These foams, which contain isocyanurate, can survive for 10-25 minutes before burn-
through occurs, when exposed to a flame from a propane torch at 1 200 °C (standard polyurethane
foams under the same test conditions are penetrated in about 10 seconds), therefore offering high
resistance to actual penetration by fire. Commercially available isocyanurate foams have an average
density of 35 kg/m3, thermal conductivity of 0.022 kcal h-1 m-1 °C-1 and permeance to water vapour of
16.7 g cm m-2 day-1 mmHg-1. Figure 5.2 shows the relationship between the R-value and thickness of
commercial isocyanurate foams.
Other grades of polyurethane are particularly strong, having quite high densities. For example,
standard rigid foam used as insulation in chill rooms can have densities of around 30-40 kg/m3 in
comparison with other grades of foam used as a structural core in boats with a density of 100
kg/m3 up to 300 kg/m3. Its resistance to compression varies according to the density of the foam, with
2-3 kg/cm2 for foams with densities of 35-40 kg/m3 and higher resistance for higher densities. Table
5.2 gives the main physical properties of some commercial grades of polyurethane foam. These
foams do not react with solvents used in the installation of fibreglass-reinforced plastic (such as
styrene formulated polyesters or acetone). Therefore, expanded polyurethane foams are widely used
as insulation in fish holds/fish containers together with a lining of fibreglassreinforced plastic, despite
the fact that they are significantly more expensive than expanded polystyrene. Their main technical
limitation is the fact that they are more likely to absorb water than expanded polystyrene, and can
burn and produce toxic substances during ignition. Figure 5.3 shows the permeability of different
insulation materials to water and water vapour.
FIGURE 5.2 Relationship between thermal resistance (R-value) and thickness of commercial
isocyanurate foam sheathing (data obtained from a Canadian manufacturer)
FIGURE 5.3 Comparison of permeability of different insulation materials to water and water
vapour at 20 °C and 65 percent relative humidity
Source: Prepared by authors based on data from ASHRAE, 1981 and Melgarejo, 1995.
TABLE 5.2
Physical properties of some grades of polyurethane foams
1
As specified by US Federal Specification HHI-I-00530.
2
1 PSI (pound/square inch) = 0.070307 kg/cm2.
Source: American Society for Testing and Materials (ASTM) Book of Standards and CPR Division.
The Upjohn Co., USA.
TABLE 5.3
Thermal conductivity and density values at 0 °C of polystyrene insulation
Through polymerization styrene can be made into white pearls/beads of polystyrene plastic. These
beads can then be expanded to form a foam known as expanded polystyrene. There are two main
ways of making of expanded polystyrene: by extrusion and by moulding of slabs.
Extruded foams are made by mixing the polystyrene with a solvent, adding a gas under pressure and
finally extruding the mixture to the required thickness. The extrusion process improves the
characteristics of the final foam, such as its mechanical resistance, producing non-interconnecting
pores and a more homogeneous material. The mechanical resistance of expanded polystyrene foams
can vary from 0.4 to 1.1 kg/cm2. There are several grades of foams available with densities from 10 to
33 kg/m3, with thermal conductivities that are lower with the increase in density, as shown in Table
5.3.
This last characteristic makes them unsuitable for use in fish holds/fish containers that have a lining of
fibreglass-reinforced plastic where the fibreglass is applied in situ directly onto the insulation material.
Rigid board panels can be made with expanded polystyrene of different densities, various thicknesses
and sizes.
Perlite is a volcanic rock containing from 2 to 5 percent bonded water. It is a chemically inert
substance composed basically of silica and aluminium, but some impurities, such as Na2O, CaO,
MgO and K2O, which are hygroscopic, can absorb moisture easily. Therefore, depending on the
storage conditions and the quality of the perlite, moisture absorption can be minimized. The average
density of expanded perlite is about 130 kg/m3 and its thermal conductivity is about 0.04 kcal m-1 h-1 °C-
1
(0.047 W m-1 °C-1). The perlite is expanded by means of rapid heating at a temperature between 800
and 1 200 °C. The vaporization of the bonded water and the formation of natural glass results in the
expansion of the perlite particles, which have a granular shape. Therefore, the main parameters that
define the characteristics of expanded perlite are:
the origin of the mineral perlite;
the granulometric characteristics of the mineral before the expansion process;
the temperature of expansion.
However, despite its good insulating efficiency, this is only effective when it is dry or in a loose
granular state. As these granules tend to absorb moisture and settle after installation, it becomes less
effective as an insulation material with time. The most common way of applying perlite is pouring the
granules and spreading them manually. It can fill small spaces more completely than fibrous insulation
materials. Loose-fill insulation, such as expanded perlite, may be used in combination with other types
of insulation material (e.g. slabs of cellular plastics) for filling awkwardly shaped areas of the fish hold
where cutting of slabs to the desired shape would be time-consuming and incomplete.
Caution is needed during handling and installation of expanded perlite, as perlite dust can cause
chronic poisoning.
5.3.4 Fibreglass
Fibreglass matting is also used as insulating material and offers the following advantages:
Fibreglass insulation is available in rolls of different thickness, also called blankets and mats. The
width of the blankets and mats will depend on the way they are to be installed and some come faced
on one side with foil or Kraft paper, which serve as vapour barriers.
Rigid board panels can be made with compressed fibreglass. These lightweight insulation boards
have relatively high R-values for their thickness.
5.3.5 Cork
Cork is probably one of the oldest insulation materials used commercially, and in the past it was the
most widely used insulation material in the refrigeration industry. At present, due to the scarcity of
cork-producing trees, its price is relatively high in comparison with other insulating materials.
Therefore, its use is very limited, with the exception of some machine foundations to reduce the
transmission of vibrations. It is available as expanded slabs or boards as well as in granular form, its
density varies from 110 to 130 kg/m3 and it has an average mechanical resistance of 2.2 kg/m2. It can
only be used up to temperatures of 65 °C. It has good thermal insulating effectiveness, is fairly
resistant to compression and is difficult to burn. Its main technical limitation is the tendency to absorb
moisture with an average permeance to water vapour of 12.5 g cm m-2 day-1 mmHg-1. Table 5.5 gives
some typical characteristics of cork.
TABLE 5.4
Thermal conductivity and density values at 0 °C of fibreglass insulation
TABLE 5.5
Thermal conductivity and density values at 20-25 °C of cork insulation
Some of the more common materials used for insulation are compared in Table 5.6 with their relative
insulating values and the advantages and disadvantages of particular types. In general, the more
expensive materials, such as the polyurethane foams are more efficient insulators for given
thicknesses. Using the “R” system of grading (see definitions in paragraph 5.1.2), it is possible to
arrive at equivalent “R values” for a variety of insulating material types.
Figure 5.4 shows the comparison of typical thicknesses of different insulation materials used for chill
rooms and ice stores, operating on shore, in temperate and tropical areas, at average ambient air
temperatures of 20, 30 and 40 °C. Some designers indicate that the thermal conductance coefficient
(l) for shore-based chill and ice stores should not exceed 0.26 kcal m-2 h-1 °C-1 (equivalent to an R-
value = 18.8 ft2 h °F Btu-1). However, the setting of this value depends basically on the energy costs,
therefore it may be reduced if, in the future, energy costs increase.
TABLE 5.6
Common insulating materials, “R” values, advantages and disadvantages
The selection of the optimum insulation thickness for fish holds will depend on factors such as the
insulation costs (materials and installation), ice costs (or power and equipment costs according to the
refrigeration requirements), annual cost savings in refrigeration due to improved insulation efficiency,
and local conditions (type of fishing operations and vessel, species caught, fish prices, borrowing
costs). Therefore, the optimum thickness of insulation should be selected on an individual basis.
However, taking into account the local environmental conditions in which the fishing vessel is likely to
operate, which do not depend on economic calculations, a minimum recommended thickness of
insulation should be determined. In practice, a compromise should be reached between the optimum
economic insulation thickness and the ice/refrigeration costs.
It is also important, for planning purposes, to take into consideration the heat gains from radiation and
conduction, to select the optimum insulation thickness.
FIGURE 5.4 Comparison of typical insulation thickness for shore-based chilled and ice stores
operating at average ambient air temperatures of 20 °C, 30 °C and 40 °C (thickness rounded up
to nearest 5 mm)
A commonly used lining material for fish holds, in particular for wooden hull vessels, is fibreglass-
reinforced plastic (FRP), which can be applied directly to some expanded cellular plastic insulation
materials (such as polyurethane foams). In commercial practice, two or three layers of fibreglass (450
g/m2 density mat) and resin, or two layers of 450 g/m2 mat and a finishing layer of 300 g/m2 mat and
resin, are applied over the insulation material; the polyester resins are applied (with a roller) until a
lining about 4-5 mm thick is obtained. An alternative method for the use of expanded polystyrene
foam in conjunction with an FRP lining is to protect the insulation with marine plywood sheets not less
than 8 mm thick and a layer of tar, then cover the marine plywood with a layer of FRP no less than 4
mm thick. Adequate provisions should be made to ensure proper ventilation between the marine
plywood and the hull planking, to prevent fungal rot in the wooden hull and moisture absorption by the
insulation material.