Structural Standard Notes & Special Inspections: Structural Column Material Takeoff Structural Framing Material Takeoff
Structural Standard Notes & Special Inspections: Structural Column Material Takeoff Structural Framing Material Takeoff
DESIGN LOADS IN ACCORDANCE WITH THE 2015 INTERNATIONAL BUILDING CODE AND ASCE 7-10 "MINIMUM DESIGN LOADS FOR BUILDINGS AND
1. ALL STRUCTURAL STEEL WORK SHALL CONFORM TO THE AISC "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS (LRFD)" AND TO THE
OTHER STRUCTURES".
RISK CATEGORY = III
1. FOOTINGS SHALL REST ON SUITABLE UNDISTURBED SOIL OR COMPACTED STRUCTURAL FILL. BOTTOM-OF-FOOTING ELEVATIONS ARE SHOWN ON
THE PLANS BUT ARE SUBJECT TO REVISION WHEN ACTUAL SOIL CONDITIONS ARE UNCOVERED BY EXCAVATION. THE ENGINEER SHALL BE NOTIFIED REQUIREMENTS OF THE LOCAL BUILDING CODES. ALL WELDING SHALL CONFORM TO THE AWS "CODE FOR WELDING IN BUILDING STRUCTURAL COLUMN MATERIAL TAKEOFF STRUCTURAL FRAMING MATERIAL TAKEOFF
PROMPTLY OF ANY WEAK STRATA, EXCESSIVE WATER OR ANY OTHER CONDITION CONTRIBUTING TO POOR BEARING MATERIALS. CONSTRUCTION".
DEAD LOADS TYPE COUNT STEEL TONNAGE TYPE COUNT STEEL TONNAGE
2. THE PRESENCE/ABSENCE OF LEDGE AT ALL PROPOSED FOOTING LOCATIONS HAS NOT BEEN DETERMINED. PROMPTLY NOTIFY ENGINEER IF LEDGE IS 2. DIMENSIONAL TOLERANCES SHALL COMPLY WITH LATEST EDITION OF "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES".
• ROOF = 20 PSF HSS4.500X0.375 7 0.8 C9X13.4 12 1.0
ENCOUNTERED DURING FOUNDATION EXCAVATION AND AWAIT FURTHER INSTRUCTIONS BEFORE PROCEEDING. 3. CONNECTIONS NOT DETAILED, SHALL BE DESIGNED FOR THE LOADS INDICATED ON THE DRAWINGS (REDUCTIONS NOT PERMITTED), ONE-HALF
• FUTURE SOLAR ALLOCATION = 15 PSF HSS4x4x1/4 9 0.4 HSS4X4X3/8 14 0.6
3. THE MINIMUM FROST DEPTH FOR FOOTINGS SHALL BE 5'-0" BELOW FINISHED GRADE. THE UNIFORM LOAD CAPACITY OF THE MEMBER (THREE-FOURTHS FOR COMPOSITE MEMBERS) IN ACCORDANCE WITH AISC-LRFD REQUIREMENTS)
• HOLLOWCORE PLANK: = 85 PSF
4. DO NOT PLACE FOOTINGS, SLABS OR ANY OTHER CONCRETE SECTIONS ON FROZEN GROUND. REMOVE ALL FROZEN MATERIALS AND REPLACE OR 15 KIPS, WHICHEVER IS GREATER. BOLTED CONNECTIONS SHALL BE MADE WITH MIMUM 3/4" DIAMETER BOLTS OR LARGER UNLESS OTHERWISE HSS4x4x3/8 22 2.3 HSS5x5x3/8 37 7.5
• WALLS, FLOORING, MECH/ELEC/PLUMBING = 20 PSF
WITH COMPACTED STRUCTURAL FILL OR CONSOLIDATED CRUSHED STONE. INDICATED ( ASTM A325N OR A490N). HSS5x5x1/4 4 0.7 HSS6x6x1/2 10 2.1
LIVE LOAD
5. ALL EXTERIOR WALLS HAVE BEEN DESIGNED AS CANTILEVERED RETAINING WALLS SUCH THAT BACKFILLING OPERATIONS CAN BE COMPLETED 4. ALL ANCHOR BOLTS SHALL BE 3/4" DIAMETER BOLTS OR LARGER UNLESS OTHERWISE INDICATED. A MINIMUM OF 4-BOLTS IS REQUIRED FOR ALL HSS5x5x3/8 20 2.2 HSS6x6x3/8 15 3.6
• CLASSROOMS/CORRIDORS = 80 PSF
PRIOR TO HAVING THE FIRST FLOOR STEEL OR DECK IN PLACE. FOUNDATION WALLS MUST BE A MINIMUM OF 3-DAYS OLD AND THE CONCRETE COLUMN BASE PLATES.
• GYMNASIUM = 100 PSF HSS6.625X0.500 2 1.4 HSS8x8x1/2 23 10.6
STRENGTH MUST BE AT LEAST 80% (OR GREATER) OF THE 28-DAY DESIGN STRENGTH BEFORE BACKFILLING OPETAIONS MAY COMMENCE. 5. STRUCTURAL STEEL CONTRACTOR SHALL PROVIDE ALL NECESSARY GUYING AND BRACING REQUIRED TO ERECT AND HOLD THE STEEL FRAME
• ASSEMBLY AREAS = 100 PSF HSS6x6x1/4 6 1.6 HSS8x8x5/8 12 6.5
6. ALL FOUNDATION WALLS (INCLUDING FROST WALLS) SHALL BE BACKFILLED WITH SELECT BACKFILL AS SPECIFIED IN "STRUCTURAL MATERIALS" PLUMB AND SQUARE UNTIL THE ROOF DECK AND WALLS ARE INSTALLED.
• STAIRS = 100 PSF HSS6x6x3/8 38 5.5 HSS9X9X5/8 2 1.1
WITHIN 4'-0" OF THE EXTERIOR FACE OF WALL. REFER TO CIVIL DRAWINGS FOR BACKFILL MATERIAL OUTSIDE 4'-0" OF THE BUILDING. IT SHALL 6. NO FIELD BURNING CUTTING OR OTHER ALTERATIONS OF PRIMARY STRUCTURAL STEEL IS PERMITTED WITHOUT WRITTEN APPROVAL FROM THE
SNOW LOAD
NOT BE ASSUMED THAT EXISTING ON-SITE MATERIAL MAY BE USED FOR SELECT BACKFILL UNLESS THE MATERIAL IS PRE-APPROVED BY THE CIVIL OR ENGINEER. HSS7x7x3/16 1 0.1 HSS10X8X1/2 1 0.2
• GROUND SNOW (Pg) = 40 PSF (BURLINGTON, VT)
GEOTECHNICAL ENGINEER. BACKFILL MATERIAL ON THE INSIDE OF ALL FOUNDATION WALLS WHERE A SLAB-ON-GRADE WILL BE PRESENT SHALL 7. FULL CONTACT AREA OF BEARING PLATES AND COLUMN BASE PLATES SHALL BEAR ON NON-SHRINK GROUT. GROUT SHALL BE APPLIED AND HSS8.625X0.625 1 1.1 HSS10X10X1/2 6 4.4
• SITE ELEVATION = +/- 215'-0"
BE AN APPROVED STRUCTURAL FILL MATERIAL OR CRUSHED STONE MEETING THE SPECIFICATIONS PROVIDED IN "STRUCTURAL MATERIALS". CURED IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. HSS8x8x1/2 12 0.9 HSS10x10x5/8 4 3.0
• ADJUSTED GROUND SNOW LOAD = 40 PSF
7. COMPACTION: SELECT BACKFILL FOR FOUNDATION WALLS SHALL BE PLACED IN MAXIMUM 8" LEVEL LIFTS AND COMPACTED TO 90% MAXIMUM 8. NO MASONRY CONSTRUCTION SHALL BE ALLOWED IN AN AREA WHERE THE STRUCTURAL STEEL WORK IS NOT COMPLETE, SPECIFICALLY WHERE HSS8x8x3/8 4 0.8 HSS12x6x1/4 9 3.3 81 Maple Street ▪ Burlington VT 05401
• EXPOSURE FACTOR (Ce) = 1.0
DENSITY (MODIFIED PROCTOR) AT OPTIMUM MOISTURE CONTENT AND TO 95% MAXIMUM DENSITY (MODIFIED PROCTOR) (PER ASTM D-1557) STEEL HAS NOT YET BEEN PLUMBED OR ALIGNED. 802▪864▪6844 ▪ www.fffinc.com
• THERMAL FACTOR (Ct) = 1.10 HSS8x8x5/8 23 27.6 HSS12x6x3/8 11 3.4
BELOW ALL LOCATIONS WHERE A SLAB, SIDEWALK OR UPPER FROST WALL FOUNDATIONS WILL BE PLACED. WHERE STRUCTURAL FILL IS REQUIRED 9. ALL FIELD CONNECTIONS ARE TO BE BOLTED EXCEPT WHERE WELDING IS SPECIFIED. ALL WELDS (SHOP OR FIELD WELDS) EXPOSED-TO-VIEW IN THE Architecture ▪ Planning ▪ Interiors
• SNOW IMPORTANCE FACTOR (Is) = 1.10 HSS12x8x5/8 14 28.5 W8x10 1 0.1
ON INSIDE FACE OF FOUNDATION WALLS, COMPACT TO 95% MAXIMUM DENSITY (MODIFIED PROCTOR) (PER ASTM D-1557). FINAL PRODUCT ARE TO BE GROUND SMOOTH.
• FLAT ROOF SNOW LOAD (Pf) = 40 PSF (VT MINIMUM) W10x33 36 16.8 W8x15 74 5.2
8. UNLESS OTHERWISE NOTED, ALL FOOTINGS AND PIERS SHALL BE CENTERED UNDER SUPPORTED MEMBERS. 10. DECKING: FLOOR & ROOF DECK SHALL BE OF DEPTH, GAGE AND TYPE INDICATED IN THE "SLAB-ON-DECK SCHEDULE" ON THE PLANS AND AS
• SLOPED ROOF SNOW LOAD (Ps) = N/A
9. CONTRACTOR TO DESIGN, FURNISH AND INSTALL ALL TEMPORARY SHEETING, SHORING AND BRACING NECESSARY TO SAFELY COMPLETE THE MANUFACTURED BY VULCRAFT, CANAM, OR APPROVED EQUAL (UNLESS OTHERWISE NOTED ON THE DRAWINGS AND SHALL BE INSTALLED IN W10x39 10 7.3 W8x21 2 0.1
WIND LOAD
CONSTRUCTION. STRICT ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND WITH RECOMMENDATIONS BY THE STEEL DECK INSTITUTE (S.D.I.). ALL W10x49 34 28.7 W8x35 10 1.9
• ULTIMATE WIND SPEED (Vult) = 120 MPH
10. THE CONTRACTOR SHALL PROVIDE THE NECESSARY EQUIPMENT TO CONTINUOUSLY DEWATER THE SITE TO FACILITATE CONSTRUCTION AND SAFE COMPOSITE DECK SHALL BE CLEARED OF ALL DEBRIS PRIOR TO PLACING CONCRETE. ALL FERRULES FROM STEEL STUDS SHALL BE REMOVED AND W12x65 50 68.0 W8x40 3 0.7
• WIND IMPORTANCE FACTOR (Iw) = 1.0
WORKING CONDITIONS. DISCARDED PRIOR TO PLACING CONCRETE. W12x79 5 4.6 W10x22 1 0.3
• EXPOSURE CATEGORY =D
11. PROVIDE FOUNDATION PERIMETER DRAIN SYSTEM WHERE INDICATED ON THE DRAWINGS. FOUNDATION (PERIMETER) DRAINS SHALL BE ENCASED 11. DECKING UNITS SHALL BE INSTALLED IN MINIMUM WIDTHS OF 24" AND SHALL SPAN OVER A MINIMUM OF 2-SUPPORTS (UNLESS OTHERWISE
• INTERNAL PRESSURE COEFF.(GCpi) = +0.18, -0.18 W14x90 13 22.4 W10x26 15 2.5
IN 3/4" TO 1" CRUSHED STONE (2'-0" SQUARE MINIMUM WITH 6" COVER ON ALL SIDES OF PIPE) WRAPPED IN MIRAFI 140N FILTER FABRIC. DETAILED ON THE DRAWINGS). PROPERLY SUPPORT ALL EDGES OF THE DECKING. PROVIDE MINIMUM END BEARING LENGTHS OF 2" OVER STEEL
SEISMIC LOAD W14x120 6 19.8 W10x30 11 3.8
12. REFER TO THE BORING LOGS FOR EXISTING SOIL CONDITIONS. CONTACT THE ENGINEER WITH ANY QUESTIONS. SUPPORTS AND 4" ON CONCRETE OR MASONRY SUPPORTS, UNLESS GREATER END BEARING IS REQUIRED BY THE DECK MANUFACTURER. END LAPS
• DESIGN PROCEDURE = EQUIVALENT LATERAL FORCE PROCEDURE Grand total 317 241.5 W10x33 26 1.0
(2"MINIMUM) ARE PERMITTED AT SUPPORT LOCATIONS ONLY. Colin Lindberg Architects
• SEISMIC IMPORTANCE FACTOR = 1.25
12. REFER TO SLAB-ON-DECK SCHEDULE FOR FASTENING SPECIFICATIONS AND PATTERNS OF FLOOR & ROOF DECK. W10x39 8 1.7
• SITE CLASS =C
• SITE COEFFICIENT (FA) = 1.2
REINFORCED MASONRY CONSTRUCTION 13. POWDER ACTUATED OR PNEUMATICALLY-DRIVEN FASTENERS, WITH CAPACITIES EQUAL TO SPECIFIED WELDS, WILL BE CONSIDERED PROVIDED W12x16 190 18.0
208 Flynn Ave # 2B
Burlington, VT 05401
1. CONCRETE MASONRY SHALL COMPLY WITH THE APPLICABLE SECTIONS OF THE NATIONAL CONCRETE MASONRY ASSOCIATION, PORTLAND COMPLETE DOCUMENTATION IS SUBMITTED FOR REVIEW AND APPROVAL BY THE ENGINEER. WHERE POWDER ACTUATED FASTENERS ARE W12x19 14 2.8
• SITE COEFFICIENT (Fv) = 1.693 (802) 864-4950
CEMENT ASSOCIATION AND AMERICAN CONCRETE INSTITUTE CODES. PERMITTED, USE EXTREME CAUTION TO INSURE THAT FASTENERS ARE NOT DRIVEN COMPLETELY THROUGH THE DECK. PLEASE NOTE THAT MATERIAL TAKE OFF HAS BEEN PROVIDED IN THE
• SHORT PERIOD RESPONSE (SS) = 0.362g W12x22 12 3.0
2. WHERE CELLS ARE TO BE GROUTED USE LOW-LIFT GROUTING PROCEDURES (4'-0" MAXIMUM HEIGHT). 14. REINFORCE SMALL OPENINGS (OPENINGS WITH A MAXIMUM DIMENSION IN ANY DIRECTION OF 24") IN FLOOR DECK WITH (2) #4 BARS ON ALL SCHEDULES FROM REVIT TO AID IN BIDDING THE PROJECT. THESE
• 1 SECOND PERIOD RESPONSE (S1) = 0.107g W12x26 45 12.9
3. VERTICAL REINFORCEMENT TO BE OF TYPE, SIZE AND SPACING INDICATED ON THE DRAWINGS. HORIZONTAL REINFORCEMENT TO BE SIDES OF OPENING (CNTR'D IN SLAB DEPTH). EXTEND BARS 24" MIN. BEYOND EDGE OF OPENING. FLOOR DECK SHALL BE CONTINUOUS THROUGH VALUES SHALL BE USED AS A QUANTITY CHECK ONLY. CONTRACTOR IS
• SHORT PERIOD SPECTRAL RESPONSE (SMS) = 0.434g W12x30 13 4.5
CONTINUOUS 9 GAGE DUR-O-WAL, TRUSS TYPE, JOINT REINFORCEMENT AT 16" o/c VERTICALLY, UNLESS NOTED OTHERWISE. OPENING WITH THE OPENING FORMED OUT. CUT & REMOVE THE DECK WITHIN THE OPENING AFTER THE CONCRETE HAS REACHED 80% OF ITS RESPONSIBLE FOR PROVIDING ALL MATERIAL QUANTITIES REQUIRED BY
• 1 SECOND PERIOD SPECTRAL RESPONSE (SM1) = 0.182g
DESIGN STRENGTH. FOR OPENINGS LARGER THAN THE ABOVE PROVIDE L3x3x1/4 FRAME (BEARING ON STRUCTURAL SUPPORTS) UNLESS THE DRAWINGS AND SPECIFICATIONS. W12x35 11 5.6
• 5% DAMPED SHORT SPECTRAL RESPONE (SDS) = 0.29g 4. PRIOR TO CONSTRUCTION, SUBMIT A DESIGN MIX FOR THE MORTAR AND GROUT FOR ENGINEER'S REVIEW. THEY SHALL BE IN ACCORDANCE
WITH THE APPROPRIATE ASTM SPECIFICATIONS AND INCLUDE ACTUAL 28 DAY COMPRESSIVE STRENGTH TESTS. OTHERWISE DETAILED ON THE DRAWINGS. REINFORCE SMALL OPENINGS (OPENINGS WITH A MAXIMUM DIMENSION IN ANY DIRECTION OF 24") W12x40 21 4.5
• 5% DAMPED 1 SECOND SPECTRAL RESPONSE (SD1) = 0.121g
5. PRIOR TO CONSTRUCTION, SUBMIT TEST DATA ON THE PROPOSED MASONRY UNITS FOR ENGINEER'S REVIEW. DATA SHALL BE IN ACCORDANCE IN ROOF DECK WITH AN 1/8" THICK PLATE (12" LARGER THAN OPENING, ALL SIDES) WELDED OR SCREWED (MAX 6" SPACING) TO THE TOP OF THE W12x45 2 1.1
• SEISMIC DESIGN CATEGORY =B
WITH THE APPROPRIATE ASTM SPECIFICATIONS AND INCLUDE ACTUAL COMPRESSIVE STRENGTH, ABSORPTION, WEIGHT, MOISTURE CONTENT DECK. FOR OPENINGS LARGER THAN THE ABOVE, PROVIDE L3x3x1/4 FRAME (BEARING ON STRUCTURAL SUPPORTS) UNLESS OTHERWISE DETAILED W12x50 1 0.7
BASIC SEISMIC FORCE RESISTING SYSTEMS = STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE
AND DIMENSIONS. ON THE DRAWINGS.
• RESPONSE MODIFICATION COEFF. (R) = 3.0 W12x53 9 4.4
6. NORMAL MASONRY CONSTRUCTION WEATHER CONDITIONS ASSUMES THAT AIR TEMPERATURES WILL BE BETWEEN 40 AND 90 DEGREES 15. STEEL FINISH: ALL STRUCTURAL STEEL SHALL BE BARE (I.E. NO PAINT) FOR FIREPROOFING , UNLESS NOTED OTHERWISE.
• SYSTEM OVERSTRENGTH FACTOR (ΩO) = 3.0 W12x65 4 3.1
FAHRENHEIT WITH MINIMUM EXPOSURE TO WIND AND RAIN. IF CONDITIONS OTHER THAN THESE OCCUR, MODIFY CONSTRUCTION 16. GALVANIZE FINISH: WHERE NOTED, GALVANIZE STEEL SECTIONS, SHAPES, PLATES AND BARS IN ACCORDANCE WITH ASTM A123. WEIGHT OF
• DEFLECTION AMPLIFICATION FACTOR (CD) = 3.0 W12x72 1 0.9
PROCEDURES IN ACCORDANCE WITH GOOD CONSTRUCTION PRACTICES AND CODES NOTED ABOVE. ZINC COATING SHALL CONFORM TO SPECIFIED REQUIREMENTS UNDER "WEIGHT OF COATING". SAFEGUARD AGAINST EMBRITTLEMENT IN
ALLOWABLE SOIL BEARING PRESSURE = 3000 PSF (BASED ON GEOTECH REPORT)
7. ALL BOND BEAMS, LINTELS AND JAM BLOCKS, UNLESS OTHERWISE NOTED, SHALL BE REINFORCED WITH 2-#4 REBAR. ACCORDANCE WITH ASTM A 143 AND AGAINST WARPAGE IN CONFORMANCE WITH ASTM A 384 AND A 385. BEFORE PROCEEDING WITH W14x22 25 5.6
LATERAL EARTH PRESSURE
8. FILL ALL VOIDS AND BLOCK CELLS SOLIDLY WITH GROUT FOR A DISTANCE OF 24" BENEATH AND 12" EACH SIDE OF ALL BEAM REACTIONS OR FABRICATION, NOTIFY ENGINEER OF ANY POTENTIAL WARPAGE PROBLEMS THAT MAY REQUIRE DESIGN MODIFICATIONS. GALVANIZE BOLTS, W14x26 7 1.6
• ACTIVE = 45 PSF/FT DEPTH
OTHER CONCENTRATED LOADS. NUTS IN ACCORDANCE WITH ASTM A 153. W14x30 3 1.2
• AT REST = 68 PSF/FT DEPTH
9. NO SPLICES IN REINFORCING BARS SHALL BE MADE EXCEPT AS DETAILED OR APPROVED BY THE ENGINEER. WHERE PERMITTED, ALL SPLICES SHALL 17. PRIOR TO PREPARATION OF STEEL SHOP DRAWINGS, STEEL CONTRACTOR SHALL FIELD VERIFY DIMENSIONS TO EXISTING OR INSTALLED W14x34 7 1.5
• PASSIVE = 405 PSF/FT DEPTH
BE LAPPED 50 BAR DIAMETERS (UNO). CONSTRUCTION AS NOTED ON THESE DRAWINGS. DIMENSIONS NOT SHOWN SHALL BE DETERMINED IN THE FIELD BY SAME.
ALLOWABLE LIVE LOAD DEFLECTION W14x38 11 5.2
10. ALL REINFORCING IN MASONRY SHALL BE FULLY GROUTED IN PLACE USING LOW LIFT (ONLY) GROUTING TECHNIQUES. 18. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS (IN ELECTRONIC PDF FORMAT) TO THE ENGINEER FOR REVIEW PRIOR TO FABRICATION FOR
• ROOFS = L/360 W14x43 8 3.9
THE FOLLOWING ITEMS. DRAWINGS SHALL INCLUDE ERECTION PLANS, ELEVATIONS, SECTIONS DETAILS (CONNECTIONS AND ANCHORAGE) AND
• FLOORS = L/480 W14x48 7 3.6
"PIECE" DRAWINGS SUITABLE FOR FABRICATION AND INSTALLATION.
• WALLS = L/240 (L/600 AT BRICK)
CONCRETE • CONCRETE EMBEDS AND ANCHOR BOLTS W14x53 6 4.5
1. ALL BAR REINFORCEMENT SHALL BE DEFORMED BARS. ALL WELDED WIRE FABRIC SHALL BE SUPPLIED AND INSTALLED IN FLAT SHEETS AND SHALL BE • STRUCTURAL STEEL W14x61 3 2.3
LAPPED ONE FULL MESH AT SPLICE LOCATIONS. REINFORCEMENT SHALL BE SECURELY TIED IN ITS PROPER PLACE BEFORE AND DURING PLACING • FLOOR DECKING W14x68 3 3.0
• ROOF DECKING
STRUCTURAL MATERIALS OPERATIONS. USE APPROVED CHAIRS AND SPACERS AS REQUIRED. NO CONCRETE BARS SHALL BE CUT OR OMITTED IN THE FIELD WITHOUT THE W14x82 3 4.6
APPROVAL OF THE ENGINEER. USE PLASTIC TIPPED ACCESSORIES IN CONCRETE EXPOSED TO WEATHER, WATER OR VIEW. W14x90 3 4.6
1. STRUCTURAL FILL (SLABS): REFER TO GEOTECHNICAL REPORT PREPARED BY JOHN TURNER CONSULTING DATED FEBRUARY 9, 2023.
2. STRUCTURAL FILL (UNDER BUILDING EXCAVATIONS): REFER TO GEOTECHNICAL REPORT PREPARED BY JOHN TURNER CONSULTING DATED
2. WHERE CONTINUOUS BARS ARE INDICATED TO BE RUN CONTINUOUSLY AROUND CORNERS, DOWEL INTO INTERSECTING WALLS AND LAP AT SPLICE FIELD TESTING FOR QUALITY CONTROL W14x109 1 1.6
LOCATIONS.
1. THE OWNER SHALL EMPLOY A QUALIFIED MATERIALS TESTING/INSPECTION AGENCY TO TAKE FIELD DENSITY TESTS ON COMPACTED FILL IN W16x26 56 16.4
FEBRUARY 9, 2023. 3. LAP ALL BARS 50 DIAMETERS MINIMUM AT SPLICE LOCATIONS UNLESS INDICATED OTHERWISE ON THE DRAWINGS. SPLICES ARE TO BE STAGGERED
ACCORDANCE WITH ASTM D1557. TESTING FREQUENCY SHALL BE AS FOLLOWS: COMPACTED FILL: (1) TEST FOR EACH COMPACTED LAYER BELOW W16x31 26 10.0
3. CRUSHED STONE: REFER TO GEOTECHNICAL REPORT PREPARED BY JOHN TURNER CONSULTING DATED FEBRUARY 9, 2023. WHEREVER POSSIBLE.
ISOLATED FOOTINGS, (1) TEST FOR EACH COMPACTED LAYER FOR EVERY 25'-0" (MAX) BELOW WALL FOOTINGS, AND (1) TEST FOR EVERY 500
4. SELECT BACKFILL FOR STRUCTURES: REFER TO GEOTECHNICAL REPORT PREPARED BY JOHN TURNER CONSULTING DATED FEBRUARY 9, 2023. 4. WHERE SPECIFIED OR REQUIRED, BEND REINFORCEMENT IN THE SHOP ONLY. ONLY COLD BENDING WILL BE PERMITTED. W16x36 34 16.1
SQUARE FEET OF SLAB AREA (3 TESTS MINIMUM FOR EACH COMPACTED LAYER BELOW SLABS). IF MATERIAL TESTS LESS THAN 95% COMPACTION,
5. LIGHTWEIGHT FILL: REFER TO GEOTECHNICAL REPORT PREPARED BY JOHN TURNER CONSULTING DATED FEBRUARY 9, 2023. 5. CONCRETE COVER OVER REINFORCEMENT SHALL AS FOLLOWS (UNLESS OTHERWISE NOTED ON DRAWINGS): W16x40 14 7.7
THEN CORRECTIVE ACTION AND ADDITIONAL TESTS WILL BE REQUIRED. OWNER RESERVES THE RIGHT TO CHARGE CONTRACTOR FOR ANY
6. FILTER FABRIC: MIRAFI FILTER FABRIC AS FOLLOWS: • CONCRETE PLACED AGAINST AND PERMANENTLY EXPOSED TO EARTH: = 3"
ADDITIONAL TESTS AND CORRECTIVE ACTION REQUIRED TO MEET THE SPECIFICATIONS. W16x45 27 17.0
• TYPE 140N FOR FOUNDATION DRAIN WRAPS (WHERE INDICATED ON DWGS) • CONCRETE EXPOSED TO EARTH & WEATHER:
2. THE OWNER SHALL EMPLOY A QUALIFIED MATERIALS TESTING/INSPECTION AGENCY TO PERFORM STANDARD FIELD TESTS FOR CONCRETE WORK W16x57 2 1.8
• TYPE RS280i FOR BELOW BUILDING FOUNDATION APPLICATIONS (WHERE INDICATED ON DWGS OR IN GEOTECHNICAL REPORT) • #6 THROUGH #18 BARS: = 2"
IN ACCORDANCE WITH ASTM C172. THE SAMPLING/TESTING FREQUENCY SHALL BE AS FOLLOWS: W16x67 18 19.8
7. RIGID INSULATION: ASTM C578, (TYPE & THICKNESS AS INDICATED ON DRAWINGS) • #5 BAR OR SMALLER = 1.5"
• ONCE EACH DAY FOR EACH DESIGN MIX OF CONCRETE PLACED, NOR LESS THAN W18x35 40 17.2
8. CONCRETE (CIP): NORMAL WEIGHT CONCRETE (NWC) OR LIGHTWEIGHT CONCRETE (LWC) AS SPECIFIED ON THE DRAWINGS WITH THE • CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
• ONCE FOR EACH 150 CUBIC YARDS OF EACH CLASS PLACED EACH DAY, NOR LESS THAN
FOLLOWING REQUIREMENTS: • SLABS, WALLS, JOISTS W18x40 26 13.4
• ONCE FOR EACH 2500 S.F. OF SLAB OR WALL AREA PLACED EACH DAY, (IN CALCULATING THE SURFACE AREA OF A SLAB OR WALL, ONLY
• 28-DAY CONCRETE STRENGTH = REFER TO SCHEDULES ON DRAWINGS • #14 AND #18 BARS = 1.5" W18x46 7 3.9
ONE SIDE OF THE SLAB OR WALL SHOULD BE CONSIDERED).
• DESIGN MIX SPECIFICATIONS SHALL BE AS FOLLOWS: • #11 BARS AND SMALLER = 3/4" W18x50 30 16.0
• FOR EACH SAMPLING, A TOTAL OF (4) CYLINDERS SHALL BE TAKEN. TESTING SCHEDULE SHALL BE TO TEST (1) CYLINDER @ 7-DAYS AND (2)
• PORTLAND CEMENT: = ASTM C150, TYPE I/II • BEAMS AND COLUMNS = 1.5"
TESTS @ 28-DAYS. IF ANY OF THE 28-DAY TESTS FAIL TO MEET THE SPECIFIED DESIGN STRENGTH, HOLD THE REMAINING CYLINDER AND TEST W18x55 4 3.3
• AGGREGATE: 6. ALL EXPOSED CONCRETE EDGES SHALL CHAMFERED 3/4", UNLESS OTHERWISE NOTED.
AT 56-DAYS, OTHERWISE DISCARD THE LAST CYLINDER WITH NO FURTHER TESTING REQUIRED. W18x60 11 8.4
• N.W.C. = ASTM C33, NO. 67, TYPICAL 7. FURNISH AND INSTALL 15 MIL REINFORCED VAPOR RETARDER (STEGO WRAP BY STEGO INDUSTRIES OR APPROVED EQUAL) DIRECTLY BELOW GRADE
3. CONTRACTOR SHALL COORDINATE AND SCHEDULE WITH THE TESTING AGENCY TO ENSURE THAT INFORMATION REQUESTED BY OWNER IS W18x65 3 2.9
• L.W.C. = NORLITE 66/33 BLENDED EXPANDED SHALE AGGREGATE SLABS UNLESS OTHERWISE INDICATED. PLACE SHEETS WITH SEAMS PARALLEL TO DIRECTION OF CONCRETE PLACEMENT. LAP SHEETS A MINIMUM OF 6"
OBTAINED IN A TIMELY MANNER AND SHALL PROVIDE THE AGENCY WITH COMPLETE AND REASONABLE ACCESS TO THE PROJECT SITE AND TO W18x76 13 15.9
• WATER: = POTABLE AT ALL EDGES AND SEAL WITH STEGO TAPE (OR EQUAL). LAP AND SEAL SHEETS AT FOUNDATION WALLS AND INTERIOR FOOTINGS AND SEAL ALL
THE AREA BEING TESTED/INSPECTED.
• MAXIMUM W/C RATIOS: = 0.55 (3,000 PSI), 0.52 (3,500 PSI), 0.50 (4,000 PSI), 0.52 (WHEN USING BARRIER ONE ADMIXTURE). HOLES, RIPS OR PENETRATIONS. W18x86 4 4.6
• SLUMP (P.O.P): = 5" MAX W/WATER REDUCER (WR), 8" MAX W/HIGH RANGE WATER REDUCER (H.R.W.R.) 8. GRADE SLAB CONTROL (SAW CUT) AND CONSTRUCTION JOINTS SHALL BE LOCATED AS SHOWN ON THE DRAWINGS OR AS APPROVED. LOCATIONS OF W18x97 6 9.1
• ADMIXTURES: CONSTRUCTION JOINTS MAY BE SUBSTITUTED WITH CONTROL JOINTS IF ACCEPTABLE TO THE ENGINEER. IN NO CASE SHALL JOINT SPACING EXCEED W18x106 2 4.2
• USE AIR ENTRAINING AGENT CONFORMING TO ASTM C260 WITH 5%+/- 1.5% (WALLS), 6% +/- 1.5% (SLABS) TOTAL AIR IN ALL 25'-0" IN ANY DIRECTION, NOR SHALL LENGTH TO WIDTH RATIO EXCEED 1.5:1.0. WHERE CONSTRUCTION JOINTS ARE REQUIRED, PLACEMENT OF SHOP DRAWINGS & PROJECT SUBMITTALS
W21x44 15 7.6
EXTERIOR CONCRETE (FOOTINGS, WALLS & SLABS). USE 3%-5% AIR IN ALL L.W.C. TO AIDE IN PUMPING AND WEIGHT. ABUTTING SLAB SECTIONS SHALL BE DELAYED A MINIMUM OF 3 DAYS TO PERMIT "INITIAL" SHRINKAGE. 1. THE STRUCTURAL SHOP DRAWING REVIEW IS INTENDED TO HELP THE ENGINEER VERIFY HIS/HER DESIGN CONCEPT. THIS REVIEW IS ONLY FOR GENERAL
• USE WATER REDUCING AGENT CONFORMING TO ASTM C494, TYPE A IN ALL CONCRETE. CALCIUM CHLORIDE IS NOT ALLOWED TO W21x48 5 2.9
9. SLAB CONTROL (SAW CUT) JOINTS SHALL BE CLEANED AND FILLED WITH A TWO-COMPONENT, SEMI-RIGID EPOXY FILLER. EPOXY FILLER SHALL BE CONFORMANCE WITH THE DESIGN CONCEPT AND DOES NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH THE DESIGN DRAWINGS &
INCREASE SET TIME. INSTALLED FOR THE FULL DEPTH OF A "SAWCUT" JOINT. SPECIFICATIONS ALL OF WHICH HAVE A PRIORITY OVER THESE SHOP DRAWINGS. CONTRACTOR IS RESPONSIBLE FOR CONFIRMED & CORRELATED W21x50 17 10.9
9. CONCRETE MASONRY UNITS (CMU): 10. ALL RE-ENTRANT CORNERS IN SLAB-ON-GRADE (OR AT DISCONTINUANCE OF CONSTRUCTION JOINT) TO BE REINFORCED WITH 2-#4 X 4'-0" DIMENSIONS, FABRICATION PROCESSES, MEANS, METHODS, TECHNIQUES, SAFETY, AND COORDINATION OF THE WORK WITH OTHER DRAWINGS AND W21x55 4 2.8
• HOLLOW LOAD-BEARING UNITS: LIGHT WEIGHT BLOCK CONFORMING TO ASTM C90, GRADE N, TYPE I WITH A MINIMUM COMPRESSIVE CENTERED IN SLAB. THOSE OF HIS SUBCONTRACTORS. W21x62 32 23.1
STRENGTH (NET AREA) OF 2000 PSI. UNITS SHALL HAVE TWO CELLS WITH A MINIMUM CONTACT AREA OF 50%. 11. SEPARATE SLABS ON GRADE FROM VERTICAL SURFACES WITH 1/2" THICK FLEXIBLE FOAM EXPANSION JOINT FILLER (CERAMAR BY W.R. MEADOWS, OR 2. THE STRUCTURAL SHOP DRAWINGS WILL BE RETURNED FOR RESUBMITTAL IF NOT REVIEWED AND STAMPED BY CONTRACTOR OR IF A CURSORY REVIEW W21x68 2 1.7
• MORTAR: MORTAR CEMENT COMPLYING WITH ASTM C270 TYPE S (1800 PSI) APP'VD EQUIVALENT). EXTEND JOINT FILLER FROM BOTTOM OF SLAB TO WITHIN 1/2" OF FINISHED SLAB SURFACE AND INSTALL JOINT SEALER. SHOWS MAJOR ERRORS WHICH SHOULD HAVE BEEN FOUND BY THE CONTRACTOR'S REVIEW. ALL SHOP DRAWINGS SHALL INCLUDE PLAN LAYOUTS W21x73 3 3.2
• GROUT: ASTM C476, WITH MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2000 PSI 12. WHERE CONCRETE IS TO BE PLACED BY PUMPING, ALL WORK MUST CONFORM TO ACI 304.2. WHEN PLACING CONCRETE AT TEMPERATURES ABOVE 90° SHOWING LOCATIONS OF ITEMS DETAILED ON THE SHOP DRAWINGS. ANY CHANGES, SUBSTITUTIONS, OR DEVIATIONS FROM THE CONTRACT
W21x83 8 9.3
10. NON-SHRINK GROUT: NON-METALLIC GROUT (ASTM C1107) WITH A MINIMUM COMPRESSIVE STRENGTH OF 6000 PSI, SEALTIGHT 588 F OR BELOW 40°F, STRICTLY ADHERE TO THE PROCEDURES AND RECOMMENDATIONS IN ACI 305 (HOT WEATHER CONCRETE) AND ACI 306 (COLD DOCUMENTS SHALL BE CLOUDED BY VENDOR SUBMITTING THE SHOP DRAWING. ANY OF THE AFOREMENTIONED WHICH ARE NOT CLOUDED OR
PRECISION GROUT, MANUFACTURED BY W.R. MEADOWS (OR APPROVED EQUAL). FLAGGED BY SUBMITTING PARTIES, SHALL NOT BE CONSIDERED APPROVED AFTER ENGINEER'S REVIEW UNLESS NOTED ACCORDINGLY. W21x101 12 18.6
WEATHER CONCRETE).
11. SEMI-RIGID EPOXY JOINT FILLER: TWO COMPONENT RESIN OR URETHANE CONTAINING 100% SOLIDS AND HAVING A MINIMUM "SHORE A" 13. PROPER VIBRATION OF ALL CONCRETE IS ESSENTIAL. THE CONTRACTOR SHALL MAKE PROVISIONS FOR BACK-UP VIBRATION EQUIPMENT. 3. THE FOLLOWING SHOP DRAWINGS/SUBMITTALS & CALCULATIONS, WHEN APPLICABLE, ARE REQUIRED FOR SUBMITTAL FOR REVIEW BY STRUCTURAL W21x111 8 12.6
HARDNESS OF 80 IN ACCORDANCE WITH ASTM D2240. 14. THE CONCRETE CONTRACTOR SHALL INSTALL (OR GIVE OTHER TRADES AMPLE OPPORTUNITY TO INSTALL) ALL ANCHORS, BOLTS, PLATES, NAILERS, ENGINEER: W21x122 2 3.8
12. REINFORCEMENT STEEL: ASTM A615, GRADE 60, (GRADE 40, #3 BAR) (DEFORMED). REBAR SHALL BE EPOXY COATED AT ALL EXTERIOR SLABS, SLOTS, CHASES, PIPE SLEEVES, ETC., AS REQUIRED BY OTHER TRADES. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE SETTING SCREEDS AND • STRUCTURAL FILL, CRUSHED STONE FILL, SAND AND SELECT BACKFILL AS APPLICABLE W21x132 2 4.8
INCLUDING UNDER GROUND PARKING GARAGE SLABS. FORMS. INSTALL DOVETAIL SLOTS AND ANCHORS IN CONCRETE WHEREVER MASONRY WALLS ARE TO BE CONSTRUCTED ADJACENT TO CONCRETE • VAPOR RETARDER W21x147 4 10.0
13. ANCHOR BOLTS: ASTM F1554, 36 KSI U.N.O. (SIZE & SPACING AS INDICATED ON DRAWINGS) WALLS • WATERSTOPS
W24x55 44 37.4
14. STRUCTURAL STEEL: 15. FOUNDATION WALL CONTROL AND CONSTRUCTION JOINTS SHALL BE LOCATED AS SHOWN ON THE PLANS. LOCATIONS OF CONSTRUCTION JOINTS • CONCRETE MIX DESIGN (W/ALL APPLICABLE ADMIXTURES)
• "W" STRUCTURAL STEEL SECTIONS: ASTM A992, (FY=50 KSI) W24x62 26 20.3
MAY BE SUBSTITUTED WITH CONTROL JOINTS IF ACCEPTABLE TO THE ENGINEER. CONTRACTOR SHALL DELAY PLACEMENT OF ABUTTING WALL • CONCRETE REINFORCEMENT (PER ACI STANDARDS)
• MISC. STEEL - SHAPES, PLATES, BARS, ETC.: ASTM A36 (FY=36 KSI) SECTIONS A MINIMUM OF 3 DAYS. NO HORIZONTAL JOINTS SHALL BE PERMITTED EXCEPT AS SHOWN ON PLANS. • CURING COMPOUND W24x68 55 48.9
• HSS TUBES: ASTM A500, GRADE C (FY=50 KSI) 16. PROVIDE FINISHED CONCRETE SLAB SURFACES AS SPECIFIED HEREIN. FINISHED FLOOR FLATNESS/LEVELNESS MEASUREMENTS SHALL MEET OR EXCEED • EXPANSION JOINT MATERIAL (CONCRETE SLABS) W24x76 24 23.8
• PIPE: ASTM A53, TYPE E OR S, GRADE B, (FY=35 KSI) THE FOLLOWING (PER ASTM E 1155).......................(OVERALL VALUE - MINIMUM LOCAL VALUE): • SLAB SAW JOINT FILLER W24x84 16 18.9
• BOLTS (CONNECTIONS): ASTM A325 OR ASTM 490 • TYPICAL EXTERIOR SLAB: NON-SLIP BROOM FINISH F(F)20/F(L)15 - F(F)17/F(L)15 • CMU BLOCK CERTIFICATES W24x94 6 7.8
• BOLTS (ANCHORAGE): ASTM F1554, GR. 36 U.N.O. • TYPICAL INTERIOR SLAB: STEEL TROWEL FINISH F(F)36/F(L)20 - F(F)24/F(L)17 • MORTAR & GROUT MIX DESIGN (W/ALL APPLICABLE ADMIXTURES) W24x146 1 2.6
• WELD ELECTRODES: E70XX 17. ALL WALL FORM TIES SHALL BE REMOVED AND GROUND SMOOTH. PROVIDE FINISHED CONCRETE WALL FINISHES IN ACCORDANCE WITH ACI 347 AS • CMU REINFORCEMENT (PER ACI STANDARDS)
W27x84 15 19.4
FOLLOWS: • STRUCTURAL STEEL & STEEL EMBEDS (PER AISC STANDARDS)
• METAL DECK (FLOOR & ROOF) (PER SDI STANDARDS) W27x94 4 6.6
• "CLASS A" FOR ALL EXPOSED INTERIOR WALL SURFACES (MAXIMUM 1/8" OUT OF PLUMB OR IRREGULARITY IN 5'-0")
CODES AND STANDARDS • "CLASS C" FOR ALL PERMANENTLY EXPOSED EXTERIOR SURFACES (MAXIMUM 1/2" OUT OF PLUMB OR IRREGULARITY IN 5'-0"). • WELDER CERTIFICATES (PER AWS STANDARDS) W27x102 4 8.7
DESIGN AND CONSTRUCTION SHALL COMPLY WITH THE LATEST REVISION (UNLESS OTHERWISE INDICATED) OF APPLICABLE CODES AND STANDARDS, • "CLASS D" FOR ALL NON-EXPOSED EXTERIOR SURFACES (MAXIMUM 1" OUT OF PLUMB OR IRREGULARITY IN 5'-0"). 4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PURCHASE AND OBTAIN, FROM A TESTING FIRM APPROVED BY THE ENGINEER, A SIEVE ANALYSIS W27x114 1 2.4
INCLUDING THE FOLLOWING: 18. IF THE CONCRETE FINISH IS DETERMINED TO BE OUT OF SPEC, THE CONCRETE CONTRACTOR SHALL GRIND ANY IMPERFECTIONS TO OBTAIN A SMOOTH AND A LABORATORY MOISTURE-DENSITY CURVE FOR THE PROPOSED CRUSHED STONE, GRANULAR FILL AND FOR THE SUB-GRADE AT EACH SOIL STRATA W27x146 6 15.8
• BUILDING CODE: 2015 IBC WITH VERMONT STATE SUPPLEMENT SURFACE. ALL COSTS ASSOCIATED WITH THIS WORK WILL BE THE RESPONSIBILITY OF THE CONCRETE CONTRACTOR. WHERE FOOTINGS OR A GRADE SLAB IS INTENDED TO BEAR DIRECTLY ON NATIVE MATERIAL. THE RESULTS SHALL BE SUBMITTED TO THE ENGINEER FOR W30x90 12 17.9
• DESIGN LOADS: AMERICAN SOCIETY OF CIVIL ENGINEERS, ASCE 7-10, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES 19. CONCRETE TEMPERATURE DURING THE FIRST SEVEN DAYS SHALL BE MAINTAINED BETWEEN 50°F AND 90°F. RAPID DRYING MUST BE PREVENTED. REVIEW. WHERE MATERIAL IS PROPOSED FOR GRANULAR FILL, THE SUBMITTAL PROCEDURE SHALL BE REPEATED UNTIL A MATERIAL MEETING THE
SPECIFICATIONS IS PROVIDED.
W30x99 7 11.8 BURLINGTON HIGH
• CONCRETE: AMERICAN CONCRETE INSTITUTE (ACI), CONCRETE REINFORCING STEEL INSTITUTE (CRSI), PRESTRESSED CONCRETE INSTITUTE (PCI) OR 20. CURING:
W30x108 11 21.6
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) A. HORIZONTAL SURFACES SHALL BE KEPT CONTINUOUSLY MOIST FOR A MINIMUM OF SEVEN DAYS. INSTALL A MOISTURE RETAINING COVER
(PNA HYDRACURE S16 SINGLE USE CURING COVER, OR APPROVED EQUIVALENT) OVER HORIZONTAL SURFACES IN ORDER TO RETAIN
5. CONCRETE DESIGN MIX: SUBMIT A CURRENT (WITHIN 6 MONTHS) DESIGN MIX, WITH 28-DAY COMPRESSIVE STRENGTH TEST RESULTS, TO ENGINEER FOR
APPROVAL A MINIMUM OF 15 DAYS PRIOR TO BEGINNING CONSTRUCTION. THE MIX DESIGN SHALL CONTAIN, AS A MINIMUM; AGGREGATE GRADATION, W30x116 10 19.4 SCHOOL &
• ACI 301 - SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS
• ACI 302 - CONCRETE FLOOR AND SLAB CONSTRUCTION
• ACI 304 - MEASURING, MIXING, TRANSPORTING AND PLACING CONCRETE
MOISTURE. CURING COMPOUND MAY BE USED IN LIEU OF A WET-CURE AT THE CONTRACTOR'S DISCRETION UPON OBTAINING ACCEPTANCE
FROM THE FLOOR MANUFACTURERS THAT THE CURING COMPOUND WILL NOT HAVE ILL EFFECTS ON THE BONDING OR LONG-TERM
ADMIXTURES TO BE USED, SOURCE OF CEMENT AND TYPE, BATCH QUANTITIES, AND DATE OF MIX DESIGN AND TEST RESULTS.
6. SUBMIT STEEL REINFORCEMENT SHOP DRAWINGS (CONCRETE & CMU), PREPARED BY THE CONTRACTOR IN ACCORDANCE WITH ACI STANDARDS, TO THE
W30x124
W30x292
3
1
6.9
5.5
BURLINGTON
• ACI 305 - HOT WEATHER CONCRETING
• ACI 306 - COLD WEATHER CONCRETING
PERFOMRANCE OF THE PROPOSED FLOORING MATERIALS.
B. VERTICAL SURFACES SHALL RECEIVE AN APPROVED NON-TOXIC CURING COMPOUND. APPLY AT A RATE AND NUMBER OF COATS AS
ENGINEER PRIOR TO FABRICATION. REPRODUCTION OF THE ENGINEER'S DRAWINGS IS NOT ACCEPTABLE. W33x118 4 9.7 TECHNICAL CENTER
W33x130 4 8.7
• ACI 315 - DETAILS AND DETAILING OF CONCRETE REINFORCEMENT SPECIFIED BY THE MANUFACTURER THAT WILL MEET ASTM C-309, TYPE 1 SPECIFICATION FOR LIQUID MEMBRANE FORMING CURING STRUCTURAL TESTS AND SPECIAL INSPECTIONS W33x141 1 2.6
• ACI 318 - BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE COMPOUNDS. THE OWNER OR OWNER'S AGENT SHALL EMPLOY ONE OR MORE APPROVED AGENCIES TO PERFORM SPECIAL INSPECTIONS DURING W33x152 2 5.5
• ACI SP-15 - FIELD REFERENCE MANUAL 21. CONCRETE REPAIRS: CONSTRUCTION OF THE TYPES OF WORK LISTED BELOW. REFER TO SPECIFICATION SECTION 01 4533 SPECIAL INSPECTIONS IN THE PROJECT
A. CONTRACTOR SHALL INSPECT CONCRETE SURFACES, AFTER REMOVAL OF FORMS, FOR AREAS OF DEFECTIVE (ROCK POCKETS, HONEYCOMB, W33x169 2 5.7
• ACI SP-66 - ACI DETAILING MANUAL MANUAL FOR FURTHER INFORMATION
• CRSI - MANUAL OF STANDARD PRACTICE ETC...) CONCRETE. REMOVE DEFECTIVE CONCRETE BY "CHIPPING" QUESTIONABLE AREA UNTIL SOUND CONCRETE HAS BEEN OBTAINED. W36x135 5 10.6
• ASTM C94 - STANDARD SPECIFICATION FOR READY MIX CONCRETE B. FOR EXISTING CONCRETE REPAIRS, CONTRACTOR SHALL INSPECT EXISTING CONCRETE AT LOCATIONS INDICATED ON THE DRAWINGS FOR COMPLY WITH IBC 2015, CHAPTER 17 "SPECIAL INSPECTIONS AND TESTS" AND IN ACCORDANCE WITH THE PROJECT MANUAL: Grand total 1418 807.2
• STEEL: AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC), AMERICAN WELDING SOCIETY (AWS), STEEL JOIST INSTITUTE (SJI), STEEL DECKING EVIDENCE OF DETERIORATION. REMOVE ALL LOOSENED CONCRETE AT DETERIORATED AREAS AND PREPARE SURFACE FOR PATCHING. • REFER TO 1705.12.5 FOR ARCHITECTURAL COMPONENT REQUIREMENTS
INSTITUTE (SDI), AMERICAN IRON AND STEEL INSTITUTE (AISI) C. CONCRETE PATCHING TO BE PERFORMED BY OR DIRECTLY SUPERVISED BY AN INDIVIDUAL HAVING AT LEAST 3 YEARS OF EXPERIENCE IN THE • REFER TO 1705.12.6 FOR MECHANICAL AND ELECTRICAL COMPONENT REQUIREMENTS
• AISC - MANUAL OF STEEL CONSTRUCTION - LOAD AND RESISTANCE FACTOR DEISGN (LRFD) PROPER INSTALLATION OF SPECIFIED MATERIALS.
• AWS D1.1 - STRUCTURAL WELDING CODE - STEEL D. UNLESS OTHERWISE SPECIFIED OR PERMITTED, FURNISH AND INSTALL "SINGLE SOURCE" PATCHING SYSTEM, WARRANTED BY ONE REFER TO "FIELD TESTING FOR QUALITY CONTROL" ON THIS SHEET FOR REQUIREMENTS ON FIELD TESTING OF INSTALLED MATERIALS.
• SDI - DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS & ROOF DECKS MANUFACTURER. ONLY PRODUCTS OBTAINED FROM A COMPANY REGULARLY ENGAGED (5 YEARS MINIMUM) IN MANUFACTURING SUCH
• SDI - DIAPHRAGM DESIGN MANUAL PRODUCTS SPECIFIED HEREIN WILL BE PERMITTED.
• MASONRY: AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) AND AMERICAN CONCRETE INSTITUTE (ACI)
• ASCE 5/ACI 530 - BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
22. SURFACE PREPARATION AND PATCHING SHALL BE PERFORMED AS FOLLOWS (WHERE MORE STRINGENT PREPARATION IS RECOMMENDED BY THE
MANUFACTURER OF THE PATCHING COMPOUND FOLLOW THE MANUFACTURER'S RECOMMENDATIONS):
SPECIAL INSPECTIONS
• ASCE 6/ACI 530.1 - SPECIFICATIONS FOR MASONRY STRUCTURES A. SURFACE PREPARATION: CONCRETE SURFACES SHALL BE CLEAN AND SOUND. REMOVE ALL DUST, LAITENCE, GREASE AND OTHER BOND-
INHIBITING MATERIALS FROM SURFACES BY MECHANICAL MEANS. SAW CUT EDGES (IF REQUIRED) OF HORIZONTAL PATCH AREAS TO OBTAIN IBC SECTION REQUIREMENTS
COLD WEATHER CONSTRUCTION PROCEDURES VERTICAL SIDES WITH A MINIMUM DEPTH OF 1/2". PREPARE PATCH AREA BY BUSHAMMERING, SANDBLASTING OR OTHER MECHANICAL
REQUIRED
1. CONTRACTOR SHALL CONTINUOUSLY PROTECT SOILS, CONCRETE, MASONRY AND OTHER BUILDING MATERIALS FROM DAMAGE DUE TO COLD MEANS ACCEPTABLE TO THE ENGINEER TO OBTAIN A ROUGH "FRACTURED AGGREGATE" PROFILE. CLEAN AND REMOVE CONCRETE FROM 1705.2 STEEL CONSTRUCTION
(REFER TO AISC STANDARDS & SPECIFCATIONS)
TEMPERATURES, UNTIL THE BUILDING HAS BEEN TURNED OVER TO THE OWNER. PROTECTION MAY INCLUDE TEMPORARY ENCLOSURES, ALL SIDES OF EXPOSED REBAR (MINIMUM 1" CLEARANCE ALL SIDES) AND CLEAN REBAR TO WHITE METAL FINISH. PAINT EXPOSED REBAR WITH
INSULATED BLANKETS AND TEMPORARY HEATING. A PROPRIETARY ANTI-CORROSION COATING (SEALTIGHT PATCH-PRIME OR APPROVED EQUAL), COMPATIBLE WITH SUBSEQUENT PATCHING
1705.3 CONCRETE CONSTRUCTION
REQUIRED CONFORMED SET
2. CONTRACTOR SHALL REPAIR AND/OR REPLACE ANY DAMAGED OR DEFECTIVE WORK, IN A MANNER APPROVED BY THE ENGINEER. ALL COMPOUND. SURFACES TO RECEIVE PATCH SHALL BE DAMP OR DRY AS RECOMMENDED BY THE MANUFACTURER. (REF. TABLE)
PROTECTIVE AND CORRECTIVE WORK SHALL BE AT THE EXPENSE OF THE CONTRACTOR. B. PATCHING: PATCH DEFECTIVE AREAS WITH SIKADUR 365 (OR EQUAL AS APPROVED BY THE ENGINEER). IMMEDIATELY PRECEDING NOVEMBER 2ND, 2023
PLACEMENT OF THE CONCRETE PATCH, COAT THE EXISTING CONCRETE SURFACE WITH AN APPROVED BONDING AGENT. APPLY PATCH IN REQUIRED
3. CONTRACTOR SHALL SUBMIT LETTER TO THE ENGINEER, OUTLINING THEIR ANTICIPATED COLD WEATHER CONSTRUCTION PROCEDURES THAT 1705.4 MASONRY CONSTRUCTION
STRICT COMPLIANCE WITH THE MANUFACTURER'S RECOMMENDATIONS; INCLUDING, BUT NOT LIMITED TO, SURFACE PREPARATION, (REF. TABLE)
THEY WILL BE ADHERING TO THROUGHOUT THE COURSE OF THE PROJECT. THE LETTER SHALL CONTAIN INFORMATION RELATING TO THE
PLACEMENT OF EXISTING SOILS, ON-SITE STOCK PILES, CONCRETE, MASONRY, STEEL AND METAL DECK. AMBIENT CONDITIONS, CURING PROCEDURES AND PROTECTION OF FRESH PATCH.
23. CONCRETE CONTRACTOR SHALL INSTALL ELECTRICAL GROUNDING DETAIL TO FOUNDATION REBAR IN ACCORDANCE WITH THE NATIONAL 1705.5 WOOD CONSTRUCTION NOT IN PROJECT
4. WHEN ERECTING STRUCTURAL STEEL OR METAL DECK THAT ATTACHES DIRECTLY TO CONCRETE/CMU, THE MATERIAL SHALL BE ON SITE FOR A
MINIMUM OF 4 HRS PRIOR TO BEING ERECTED TO ALLOW THE STEEL TO BECOME ACCLIMATED TO ON-SITE TEMPERATURES PRIOR TO BEING ELECTRICAL CODE. COORDINATE ACTUAL INSTALLATION DETAILS WITH ELECTRICAL SUBCONTRACTOR TO ASSURE CONFORMANCE WITH THE CODE. 52 INSTITUTE ROAD
REQUIRED
ANCHORED TO CONCRETE/CMU TO AVOID THERMAL CONTRACTION. ADDITIONAL ENGINEERING & CONSTRUCTION REQUIRED TO REPAIR 1705.6 SOILS
(REF. TABLE)
BURLINGTON, VERMONT
CRACKS IN CONCRETE/CMU DUE TO NOT CONFORMING WITH THIS REQUIREMENT SHALL BE AT THE CONTRACTOR'S EXPENSE. PRECAST HOLLOWCORE PLANK
1. PRECAST SUPPLIER/MANUFACTURER SHALL DESIGN AND DETAIL PRECAST SECTIONS/SYSTEMS TO CONFIGURATIONS SHOWN AND FOR DESIGN 1705.7 DRIVEN DEEP FOUNDATIONS NOT IN PROJECT
LOADS SPECIFIED BY THESE DRAWINGS. PRECASTER SHALL SUBMIT COMPLETE SHOP DRAWINGS, INCLUDING; ERECTION PLANS, "PIECE" DRAWINGS HSE PROJECT NO:
(WITH MEMBER SIZES, REINFORCING, AND EMBEDMENTS), CONNECTION DETAILS, ETC., FOR COMPLETE FABRICATION AND INSTALLATION OF
STRUCTURAL AND CRUSHED STONE FILL PRECAST SYSTEM. SHOP DRAWINGS TO BE PREPARED UNDER THE DIRECT SUPERVISION OF A PROFESSIONAL ENGINEER. PROFESSIONAL ENGINEER
1705.8 CAST-IN-PLACE DEEP
FOUNDATIONS
NOT IN PROJECT 22-001.00
REFERRED TO HEREIN IS UNDERSTOOD TO MEAN; "REGISTERED STRUCTURAL ENGINEER RETAINED BY PRE-CAST SUPPLIER, LICENSED TO PRACTICE ORIGINATION DATE: SCALE:
1. PRIOR TO PLACING STRUCTURAL OR CRUSHED STONE FILL REMOVE ALL ORGANIC MATERIAL, DEBRIS AND ANY OTHER DELETERIOUS MATERIAL.
IN THE STATE WHERE THE PROJECT IS LOCATED".
2. STRUCTURAL FILL AND SAND SHALL BE PLACED IN MAXIMUM 8" LIFTS AND COMPACTED TO 95% OF MAXIMUM DENSITY AT OPTIMUM MOISTURE 1705.9 HELICAL PILE FOUNDATIONS NOT IN PROJECT
CONTENT AS DETERMINED BY ASTM D1557, MODIFIED PROCTOR.
2. SUBMIT A COMPLETE SET OF COMPUTATIONS FOR PRE-CAST SECTIONS/SYSTEMS. COMPUTATIONS SHALL BE PRESENTED IN A LEGIBLE AND 06/23/2023 As indicated
COMPREHENSIBLE FORMAT AND SHALL BE PREPARED UNDER DIRECT SUPERVISION OF A PROFESSIONAL ENGINEER. ALL SUBMITTALS (SHOP
3. CRUSHED STONE FILL SHALL BE PLACED IN 12" (MAX) LIFTS AND CONSOLIDATED USING A HAND OPERATED VIBRATORY PLATE COMPACTOR. A REQUIRED DRAWN BY: CHECKED BY:
DRAWINGS, DETAILS, COMPUTATIONS, ETC.) SHALL BE SIGNED/SEALED BY A PROFESSIONAL ENGINEER RETAINED BY THE PRECAST 1705.10 FABRICATED ITEMS
MINIMUM OF TWO (2) PASSES PER LIFT IS REQUIRED. (REF. SECTION 1704.2.5)
MANUFACTURER.
3. EXPOSED SURFACES SHALL BE FINISHED AS INDICATED ON THE DRAWINGS. 1705.11 SPECIAL INSPECTIONS FOR
SMD TPH
4. HOLLOW CORE PLANK DELEGATED DESIGN SHALL BE IN ACCORDANCE WITH PCI MNL-120-99, ACI 318-95 AND LOCAL BUILDING CODES. NOT IN PROJECT
WIND RESISTANCE ISSUE LOG:
5. EOR TO PROVIDE ALL LOADS IMPARTED TO THE PLANK SYSTEM.
6. CONNECTION DETAILS SHALL BE SUBMITTED BY THE AWARDED SUBCONTRACTOR, AND SHALL BE DRAWN PER THE PCI CODE REFERENCED ABOVE. 1705.12 SPECIAL INSPECTIONS FOR CD ISSUE 06/23/2023
REQUIRED
SEISMIC RESISTANCE Cost Reduction-Rev. 5 11/02/2023
1705.13 TESTING FOR SEISMIC
REQUIRED
RESISTANCE
SHEET CONTENTS:
STRUCTURAL
STANDARD NOTES
& SPECIAL
11/1/2023 11:40:37 AM
S000
© 2022 Freeman French Freeman Inc.