0% found this document useful (0 votes)
43 views42 pages

X80 User Manual v1-1

Uploaded by

Giau Ngoc Hoang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views42 pages

X80 User Manual v1-1

Uploaded by

Giau Ngoc Hoang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 42

© 2016 Mikro Sdn Bhd All Rights Reserved

X80 user manual

V1.1
X80
Power Factor Regulator

MODBUS-RTU

1
Precaution for Safe use
of Equipment
Please read the instructions carefully before operating the equipment. The following
symbols will appear through out this user manual to warn of potential dangers or
hazardous situation that will arises while operating the equipment. Mikro® will not
be liable for any improper use of the equipment stipulated in this user manual.

The DANGER
personnel will results in serious injuries or death.
DANGER

The WARNING
symbol indicates that potentially hazardous situation might arise if
instructions are not followed that will result in serious injuries or death.

WARNING

The CAUTION
symbol indicates that injuries to the user or damage to the equipment will
happen if the stated instructions are not followed.
CAUTION

®
’s Power Factor Regulator.

2 © 2016 Mikro Sdn Bhd All Rights Reserved


04 PRODUCT OVERVIEW
04 – Introduction
05 – Feature List
06 – Packing List

07 SETTING UP THE REGULATOR


07 – Installation
08 – Wiring
09 – Quick Commissioning

10 DISPLAY
10 – General Measurements
11 – Alarm Status
12 – Harmonics Table and Graph

13 SETTINGS
13 – Switching Program
14 – Target Power Factor
14 – Sensitivity
14 – Reconnection Time
14 – C/K
15 –
15 – Signal Contact
15 – Fan
16 – Alarm
17 – Phase Detection
17 – Automatic CT Polarity Correction
17 – Restore to Default Settings
17 – Password

18 COMMUNICATION
18 – Communication Setup

19 MAINTENANCE
19 – Maintenance
19 – Getting Technical Support

20 APPENDIX
20 –
22 – Appendix B: ModBus-RTU Table
35 – Appendix C: Setting Parameters
36 – Appendix D: Calculations
ŀ &. &.Table)
ŀ 6HQVLWLYLty
ŀ 7+',DQG7+'9

Contents 3
PRODUCT OVERVIEW

Introduction
Mikro®’s power factor regulator X80 is designed to detect and compensate
displacement power factor caused by inductive load by switching in banks of
capacitors. As oppose to traditional regulator that only measures reactive power
on a single phase basis but compensates three phases, the X80’s Three Phase
m o d e l i s a t r u e t h r e e p h a s e s y s t e m a s r e a c t i ve p o w e r o f a l l t h r e e p h a s e s a r e
measured individually and compensated optimally.

Mikro® SRZHUIDFWRUUHJXODWRU;DOVRSURYLGHVIOH[LELOLW\LQFRQILJXULQJ RU
disabling) different levels of alarms. The alarms then can be linked to a dedicated
signal contact to alert the users of potential issues such as under compensation WKXV
avoiding penalty charges from the utilities).

As the name suggest, Mikro®’s power factor regulator X80 provides the user
with a 2 inch wide, 64 x 128 dot matrix LCD for displaying its various measurement
parameters such as: frequency, voltage, current, THD, active, reactive, apparent power
and temperature. The dot matrix LCD allows up to 31st voltage and current harmonics
to be display in graphical and table form.

As per the other Mikro®’s power factor regulator series, it includes the automatic C/K
and rated step size detection feature for ease of commissioning for typical inductive
loads. Taking advantage of the dot matrix LCD, the X80 also provides a guided
step-by-step commissioning menu that enables fast setup.

The regulator extends its connectivity by adopting the Modbus-RTU protocol. Through
the use of RS485 standard protocol, the user will be able to network the regulator with
other IEDs that links to a center monitoring station.

4 © 2016 Mikro Sdn Bhd All Rights Reserved


Feature List
2” inch, 64 x 128 dot matrix LCD display with back lighting
Three phase and single phase detection of reactive power
 RUIRUVWHSPRGHO RXWSXWZLWKWZRDGGLWLRQDOLQGHSHQGHQWFRQWDFWIRUVLJQDO
alarm output and fan output
Three phase compensation mode based on:
Optimum Demand
Selected Phase
Highest Load
5 different switch program:
Automatic
Linear
Four Quadrant
Rotational
Manual
Automatic detection of C/K and rated step value
Automatic Current Transformer polarity correction*
Step-by-step guided commissioning
No Voltage release
Measurement Parameters:
Active, Reactive, Apparent Power
Temperature
Phase Voltage and Phase Current
Frequency
Power Factor and Displacement Power FDFWRU &RVij
7+'9DQG7+',

7+',
Under Compensation
Over Compensation
Under Current
Over Current
Under Voltage
Over Voltage
Over Temperature
Rated Step Detection Error
Current Transformer Polarity Error*
Alarm linked signal contact
Programmable fan control
Modbus-RTU communication support

* Available in single phase models only.

Product Overview
Context 5
Packing List
No Description Quantity

1 X80 Power Factor Regulator 1

2 Thermistor 1

3 Thermistor holder 1

6 © 2016 Mikro Sdn Bhd All Rights Reserved


Setting Up The Regulator

Installation

DANGER

regulator.

Setting Up The Regulator 7


Wiring Diagram

X80 Connection diagram for 3 Phase 12 Step model


DANGER
P1 P2
L1 P1 P2

LOAD
L2
P1 P2
L3
N

FUSE
32 44 43 42 41 40 39 38 37 36 35 34 33
N L1 L2 L3 In Out In Out In Out N L
CT1 CT2 CT3 AUX

FUSE
X80
1 2 3 4 5 6 7 8 9 10 1112 FAN SIG

K12
31 30 24 23 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20 21 22
RP
N-
GND
P+
T2 Thermistor
T1

FAN
SIG

RS485
K2
Modbus-RTU
K1

X80 Connection diagram for Single Phase 12 Step model

P1 P2
L1

LOAD
L2
L3
N
FUSE

32 44 43 42 41 40 39 38 37 36 35 34 33
N L1 In Out N L
CT1 AUX
FUSE

X80
1 2 3 4 5 6 7 8 9 10 11 12 FAN SIG
K12

31 30 24 23 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20 21 22
RP
N-
GND
P+
T2 Thermistor
T1

FAN
SIG

K2

RS485
Modbus-RTU
K1

8 © 2016 Mikro Sdn Bhd All Rights Reserved


Quick Commissioning
The regulator is pre-programmed with the most common parameters as its
factory default setting. Users are normally not required to change any setting upon
commissioning. If the user requires any changes in the setting, the quick
commissioning feature will provide the user with a step-by-step guidance in setting up
all the mandatory parameters for the regulator to function properly.

1 4

Press
 button from Home menu. Press
 button, then press c or d to
set the value. To navigate to the next
page, press c or d to select “f“, then
press
 button.

2 5

Press

selection. To navigate to the next page,
Press c or d button to navigate to the
following pages.
press c or d to select “f“, then press
 button.

3 6

Press
 button, then press c or d to
set the value. To navigate to the next
Press

and then the press c or d to set the
page, press c or d to select “f“, then value. Back to the Main menu, press c or
press
 button. d to select “f“, then press
 button.

Setting Up The Regulator 9


DISPLAY

General Measurement
2
3
1

4 5

No Description

1 Shows the phase that the regulator is currently measuring

2 ,QGLFDWHVWKHORDGFRQGLWLRQ LQGXFWLve or capacitive)

3 Alarm, Fan & Keylock status indication

4 0HDVXUHPHQW GLVSODFHPHQWSRZHUIDFWRr, current & temperature) and


setting parDPHWHUV WDUJHWSRZHUIDFWRU VZLWFKLQJSURJram)

5 Shows the status of the outputs

NOTES:
By pressing the Exit button, user can cycle between different phases to display the
respective phase parDPHWHUV DSSOLFDEOHIRUWKUHHSKDVHPRGHOV 

Detail measurements of other power parameters such as phase voltages, phase


currents, active power, reactive power, apparent power, frequency, alarm status and
temperature can be intuitivHO\DFFHVVYLDWKHVXEPHQXV PHDVXUHPHQWV 

10 © 2016 Mikro Sdn Bhd All Rights Reserved


Alarm Status
When any of the alarm occurs, the regulator will display which of the alarm happen
via the alarm status menu. The table below shows the details of the alarm activation/
de-activation timing.

Alarm Delay Time


Description Symbol Activate Deactivate
Total Harmonic Distortion 7+', 5 min 2.5 min
Under Current Under Current 10 s 5s
Over Current Over Current 2 min 1 min
Under Voltage Under Voltage 100 ms 5s
No Voltage Release No Volt. Release instantaneous instantaneous
Over Voltage Over Voltage 15 min 7.5 min
Under Compensate Under Comp. 15 min 7.5 min
Over Compensate Over Comp. 15 min 7.5 min
Step Error Step Error - -
CT Polarity Error CT Error 10 s 5s
Over Temperature Temperature 5 min 2.5 min

Under Compensate Alarm


All the capacitors are connected and the power factor is lower than the set
power factor.

Over Compensate Alarm


All the capacitors are disconnected and the power factor is higher than the set
power factor.

Step Error Alarm


Step Error Alarm will be triggered if all the capacitor bank are detected to be invalid
in Auto CK setting.

CT Polarity Error Alarm


Current Transformer Polarity Alarm will be triggered if the measured Active Power
is negative due to wrong Current Transformer connection.

No Voltage Release Alarm


No Voltage Release Alarm will be triggered if the measured voltage is lower than 100V.

NOTES:
ŀThere will be an alarm symbol blinking when any one of the alarm is being activated.
ŀThe alarm status will show which of the alarms are activated.
ŀThe Fan and Signal output contact will not be turn off when any of the alarms occurs.
ŀThe signal contact output is programmable to link to the desired alarm signal.
ŀCT Polarity Alarm is not applicable for the Three Phase model.

Display 11
Harmonics Table and Graph
The power factor regulator has the capability of displaying voltage and current
harmonics up till the 31st order IXQGDPHQWDO frequency is considered to be 1st
order). The regulator will display the harmonics frequency in graphical form EDU
graph) or table form which shows the harmonics value in relative  to the fundamental
frequency.

12 © 2016 Mikro Sdn Bhd All Rights Reserved


SETTINGS

Switching Program

switching algorithms:

1. MANUAL
This mode is typically reserved for testing the regulator when commissioning it for the

pressing the c or d button. The c Button will turns on and d button will turns off the

2. AUTOMATIC
The regulator selects the most appropriate step to switch in order to achieve the
target power factor in the shortest reaction time within the minimum number of steps.
For equal aging of capacitor and contactor the program will select the least used step
to switch in or the most used step to switch out, if there are 2 or more equally rated
steps.

3. ROTATIONAL

achieve the target power factor.

4. FOUR-QUADRANT
This mode is the same as automatic switching mode with the exception of that it
operates in both import power and export power UHJHQHrative) conditions. There will
be no automatic CT polarity correction in this mode.

5. LINEAR

sequence to achieve the target power factor.

NOTES:
ŀ For single phase model, in automatic, rotational and linear switch program, all the
ative.
ŀFor three phase model, three phase detection mode and in automatic, rotational and
linear switch program, all the capacitor banks will be disconnected if the measured

L1, L2, L3 or max load, the capacitor will be disconnected only if the selected phase
is regenerative.

Settings 13
Target Power Factor
The user will be able to set the target displacement power factor value from 0.8
capacitive to 0.8 inductive. The regulator will switch the capacitor banks on and off,
attempting to achieve this set value.

Sensitivity
The sensitivity setting controls the reaction time for the regulator to switch. The
reaction time to switch is dependent on the demand, step size and the sensitivity
setting. A small demand, large step size and a high sensitivity setting will result in
a slower switching whereas a large demand, small step size and a small sensitivity
setting will result in a faster switching speed. The reaction time is counted dynamically
as the demand changes providing an optimal reaction time. Please refer to appendix
D.2 for more details.

Reconnection Time
This setting prevents the reconnection of the same capacitor bank before it is fully
discharged. This parameter is usually set based on the discharge time of the largest
capacitor size in used. When a step is being turned on while the reconnection time is
counting down, the LCD will display the blinking step indicating that particular step is
pending to turn on.

C/K
The C/K value determines the threshold current value for the regulator to switch
2Q2If). The C/K value is determined manually via table D.1.0 $SSHQGL[ D.1) base
on the smallest capacitor bank size, system voltage and CT ratio. The regulator can
automatically detect the C/K value by setting it to auto.

14 © 2015 Mikro Sdn Bhd All Rights Reserved


The rated step setting allows the user to program the outputs in accordance to the

on and will not be part of the switching. If the C/K setting is automatic, the rated step
size will be determined by the regulator.

Signal Contact
The signal contact feature provides a way to alert the user when an abnormality
condition is detected in the system. The user can link the signal contact with any of
the 10 alarms available individually or collectively. e.g. If the signal contact is linked
with under compensate, the under compensate alarm is enabled. When the regulator
detected an under compensate condition, the alarm will trigger and the signal contact
will switch.

Fan

Setting Description

None Fan output permanently off.

Fixed On Fan output permanently on.

Output On Fan output will turn on when any of the output

Temperature Fan output will turn on when the temperature


6HWWLQJrange = 20 oC-35 oC) exceed user set value.

Settings 15
Alarm
The list of available alarm and its setting range are shown below:

Default
Alarm Setting Actions User Set Range
setting
7+',1 Disconnect all steps  ±RU2))

Under Current 2 0.15 A 0.01 – 0.15 A or OFF

Over Current 1 5.5 A 5.50 – 7.00 A or OFF

Under Voltage 2 Disconnect all steps 204 V 195 – 204 V or OFF

Over Voltage 1 263 V 253 – 264 V or OFF

Under Compensate 5 OFF ON/OFF

Over compensate 5 OFF ON/OFF

Step Error 3,5 OFF ON/OFF

CT Polarity Error 4
OFF ON/OFF
6LQJOH3KDVHRQO\

No Voltage Release 6 Disconnect all steps - -

Over Temperature 1 Disconnect all steps 65 oC 36 – 70 oC or OFF

1
The measured value must exceed the set limit value to activate.
2
The measured value must be lower than the set limit value to activate.
3

4
There will be no CT polarity alarm in Four-Quadrant mode or Three Phase model.
5
In manual mode, there will be no under compensate alarm,
over compensate alarm and step error alarm.
6
The alarm will activate if any of the phase is below 100 VAC.

16 © 2016 Mikro Sdn Bhd All Rights Reserved


Phase Detection
For the three phase model, the user has the options to select the method to detect
and compensate the displacement power factor as desired. The user can choose to set
L1, L2, L3, maximum load or three phases. For maximum load setting, the regulator
will compensate base on the phase that has the maximum load. For the three phase
setting, the regulator will calculate the demand for all 3 phases and consolidate it for
optimum compensation.

Automatic CT Polarity Correction


The automatic CT polarity correction automatically corrects the reversed
connection of the current transformer in terms of measured parameters and compensation
calculation. This feature is not available for the four quadrant switching program as
the regulator would not be able to distinguish the reversed connection of the current
transformer. The automatic CT polarity correction is only available for single phase
model.

Restore Default Settings


The user can reset to default factory setting by pressing all 2 buttons GRZQ and
up) simultaneously for 5 seconds. The user will have 3 options, reset settings, reset
password and reset settings and password to choose from. Refer to appendix C for the
factory default value.

Password
When the regulator is locked, the user will be required to key in the password when
attempting to change any settings of the regulator WKH user will still be able to view
the measurement parameters and alarm status). The user has the options to reset
the password by pressing all 2 buttons GRZQ and up) simultaneously for 5 seconds.
The default password is 0,0,0,0. The regulator will lock when it is idle for more than 5
PLQXWHV DORFNV\PERODSSHDUZKHQORFked).

Settings 17
COMMUNICATION

Communication Setup
The regulator supports the Modbus-RTU protocol. The protocol uses a master/slave meth-
od where the regulator is the slave device. The data’s are transmitted serially via the RS485
protocol. The user can connect a RS485 to RS232 adapter to establish a communication
through the PC serial port. The supported function codes are 03 UHDG holding register),
04 UHDG input register), 06 ZULWH single register) and 16 ZULWH multiple registers). The
default parity mode is Even and None parity requires 2 stop bit. Refer to the connection
diagram to setup the communication.

1 to 32 PFR

RS232 / 485
Modbus-RTU
2-wire converter

Shield Cable

Host

18 © 2016 Mikro Sdn Bhd All Rights Reserved


Remote Set
Enabling the Remote Set allows the remote terminal to read and write the power fac-
tor regulator setting via Modbus RTU, otherwise the setting data can only be read.
Enabling feature can only be done at the panel unit.

Baudrate
There are 2 baudrates available for selection.
1) 9600bps 2) 19200bps

Parity Bit
There are 3 selections for parity bit set in data frame.
1) None 2) Odd 3) Even

Maintenance
There are no user serviceable parts on this product. Please do not open the product,
as opening it will void the warranty. Please contact your nearest sales representative if
the product requires any service or repair.

Getting Technical Support


For technical support, you can obtain assistances via :

Address : Mikro Sdn Bhd


No. 3, Jalan Anggerik Mokara 31/48,
Seksyen 31, Kota Kemuning,
40460 Shah Alam, Selangor,
Malaysia.

Tel : +6 03 5525 3863


Fax : +6 03 5525 3873

Website : www.itmikro.com

Communication 19
APPENDIX A

&855(17,1387 ($&+3+ASE)
Nominal Current 5 A rms
Operating Limits 0.01-10 A rms
Rated frequency 50 Hz or 60 Hz
VOLT$*(,1387 ($&+3+ASE with respect to neutral)
Nominal Voltage 230 VAC
Operating Limits 0 - 277 V L-N
Consumption 0.05 VA
Rated Frequency 50 Hz or 60 Hz
Category III *
THERMISTOR INPUT
Thermistor Temperature range 0 – 100 °C
AUXILIARY
Auxiliary Input Voltage Range 85-265 V rms
Consumption 10 VA max
Rated Frequency 50 Hz / 60 Hz
RELAY OUTPUT
Number of outputs 14
Contact arrangement NO contact type
Contact rating 5 A , 250 V$& &26ij 
Expected electrical life 100,000 operations at rated current
Expected mechanical life 5 x 106 operations
CONTROL RANGE
Target Power factor 0.80 Inductive – 0.80 Capacitive
C/K setting 0.03 – 1.20 / Automatic detect
Sensitivity 5 – 300 s/ Step
Reconnection time 5 – 240 s
Switching program Automatic/ Manual/ Four-quadrant/ Rotational/ Linear
0/ 1/ 2/ 3/ 4/ 5/ 6/ 8/ 12/ 16/ Fixed
Detection mode L1 / L2 / L3 / Max Load / Three Phase
Fan Setting Fixed on / Output On / Temperature / None
Signal Contact Linked to 10 different programmable alarm / None
ALARM SETTING RANGE
7+', ±2))
Over Voltage 253 – 264 V/ OFF
Under Voltage 195 – 204 V/ OFF
Over Current 5.50 – 7.00 A/ OFF
Under Current 0.01 – 0.15 A/ OFF
Under Compensate On / OFF
Over Compensate On / OFF
**CT Polarity Error On / OFF
Step Error On / OFF
Over Temperature 36 – 70 °C / OFF

20 © 2016 Mikro Sdn Bhd All Rights Reserved


DISPLAY
7+',DQG7+'9 ±
Harmonics Resolution Up to 31st Harmonics
Active power 0 – 3000 W
Reactive power 0 – 3000 VAR
Apparent power 0 – 3000 VA
Voltage 0 – 300 VAC
Current 0.00 – 10.0 A rms
Temperature 0 – 100 °C
Frequency 45 – 65 Hz
Power Factor -1.00 – 1.00
Displacement Power Factor -1.00 – 1.00
** This feature is not available in Three phase model.

MECHANICAL
Mounting Panel mounting
'LPHQVLRQ K[Z[G 144mm x 144mm x 122mm
IP Protection IP54 Front Panel, IP20 Meter Body
Approximate weight NJ IRUWKUHHSKDVHPRGHO 
NJIRU VLQJOHSKDVHPRGHO
ENVIRONMENT CONDITIONS
Temperature -5 °C to +55 °C
Humidity 56 da\VDW5+DQGƒ&QRQFRQGHQVLQJ
Pollution Degree II
Dielectric Withstand IEC61010-1
Altitude 2000 m
EMC
(6' (OHFWURVWDWLF'LVFKDUJH IEC61000-4-2 CD Level II AD Level III
EF7 (OHFWULFFast Transient) IEC61000-4-4 Level III
Surge IEC61000-4-5 Level II
Conducted Immunity IEC61000-4-6 Level III
Magnetic Field Immunity IEC61000-4-8 Level III
Radiated Field Immunity IEC61000-4-3 Level III
Voltage Dip IEC61000-4-11
Conducted and Radiated Emission EN55011
Harmonics IEC61000-3-2
Flicker Emission IEC61000-3-3

branch circuits and lighting systems in large buildings”.

Appendix A 21
APPENDIX B

ModBus Table
FORMAT DEFINITION
FORMAT TYPE DESCRIPTION
F1 Power Measurement &
Calibration

modbus address i+1

F2 3 phase Voltage and b15-b0:Unsigned Integer.


Current Harmonic The vDOXHLVH[SUHVVHGDV[
Measurement (JPHDQV
negative vDOXH  LQKDUPRQLFLQGLFDWHVWKDW
the measured rms vROWDJHLVEHORZRIWKH
rated vROWDJH Y LH9RUPHDVXUHGUPV
FXUUHQWLVEHORZRIWKHrDWHGFXUUHQW $ LH
0.1A.
Max value for Voltage harmonic and current har-
PRQLFLV  +DUPRQLFvalue which is
KLJKHUWKHQZLOOEHFDSSHGDV

F3 Product Information High byte: First ASCII Character


b15-b8: Unsigned Char.

Low byte : Second ASCII Character


b7-b0: Unsigned char

F4 Switching Program & High byte: Switching Program


C/K Setting b15-b12: don’t care
b11-b8 : 0: Manual
1: Rotational
2: Four-quadrant
3: Automatic
4: Linear

Low byte: C/K Setting


b7-b0: Unsigned Char. The valid range is from 3
WR AutoCk). The value is expressed as x/100
i.e. 3 means 0.03.

22 © 2016 Mikro Sdn Bhd All Rights Reserved


F5 Reconnection Time & High byte: Reconnection time
Power factor Setting b15-b8 :Unsigned Char. The valid range is from
5 to 240.

Low byte: Power Factor Setting


b7-b0 :Unsigned Char. The valid range is from
80 to 120.
&RVij Value
---------------------------
0.80 Ind 80
0.98 Ind 98
1.00 Res 100
0.98 Cap 102
0.80 Cap 120

F6 High byte: Step X*


b15-b8: Unsigned Char. Valid values: 0, 1, 2, 3,
 )Lxed)

Low byte Step X + 1*


b7-b0: Unsigned Char. Valid values: 0, 1, 2, 3,
 )Lxed)

step 9-12 is not applicable

F7 Detection Phase Setting High byte: Detection Phase*


b15-b12: don’t care
b11-b8: 0: L1
1: L2
2: L3
3: 3 Phase
4: Maximum load

Low byte: Don’t care

*It is not applicable for single phase model

F8 $ODUPVHWWLQJIRU7+', b15-b0 :Unsigned int. The valid range is from 20


Limit to 300. 0 is for Off. The value is expressed in
LHPHDQ

F9 Alarm setting for High byte: Under Current


Under Current and b15-b8 : Unsigned Char. The valid range is from
Over Current Limit 1 to 15. 0 is for Off. The value is expressed as
x/100 i.e. 1 means 0.01.

Low byte: Over Current


b7-b0: Unsigned Char. The valid range is from
1 to 16. 0 is for Off. This value is expressed as
[ LHPHDQV PHDQV

Appendix B 23
F10 Alarm setting for High byte: Under Voltage Limit
Under Voltage and b15-b8: Unsigned Char. The valid range is from
Over Voltage Limit 195 to 204. 0 is for Off.

Low byte: Over Voltage Limit


b7-b0: Unsigned Char. The valid range is from
1 to 12. 0 is for Off. This value is expressed as
[LHPHDQVDQGPHDQV

F11 Fan Temperature and Alarm High byte: Fan Temperature Limit
setting for High b15-b8: Unsigned Char. The valid range is from
Temperature Limit 20 to 35.

Low byte: Over Temperature Limit


b7-b0: Unsigned Char. The valid range is from
36 to 70. 0 is for Off.

F12 Slave Address and High byte: Slave Address


Set Baud Rate b15-b8: Unsigned Char

Low byte: Set Baud Rate


b7-b1: don’t care
b0: Baud Rate
0: 19200 bps
1: 9600 bps

F13 Set Parity and Fan Setting High byte: Set Parity
b15-b10: don’t care
b9-b8: 0: None
1: Odd
2: Even

Low byte: Fan setting


b7-b4: don’t care
b3-b0: b0: None
b1: Fixed on
b2: Output ON
b3: Temperature

24 © 2016 Mikro Sdn Bhd All Rights Reserved


F14 Signal Contact and Alarm High byte: Signal contact
Settings (Alarm and None)
b15-b11: don’t care
b10-b8: 1: Alarm
2: None

Low byte : Alarm Settings for Under


Compensate, Over Compensate, Step Error
and CT polarity error
b7-b4 : don’t care
b3-b0 :
‘0’ = Off ; ‘1’ = On
b0: Under compensate
b1: Over compensate
b2: Step error
b3: CT polarity error*

*Only available in single phase model

F15 Signal Contact Alarm Hight byte: Signal Contact Alarm Linkage 1
Linkage 2 and Signal Con- b15-b8: Unsigneid Char.
tact Alarm Linkage 1 ‘1’: Linked to signal contact
‘0’: Not linked to signal contact
E7+',
b9: Under Current
b10: Over Current
b11: Under Voltage
b12: Over Voltage
b13: Under Compensate
b14: Over Compensate
b15: Step Error Alarm

Low byte: Signal Contact Alarm Linkage 2


b7-b2: don’t care
b1-b0 :
‘1’: Linked to signal contact
‘0’: Not linked to signal contact
b0: CT Polarity Error *
b1: Over Temperature

*Only available in single phase model

F16 Sensitivity b15-b0: Unsigned Int.


The valid range is from 5 to 300.

F17 Reserved b15-b0: Reserved

Appendix B 25
F18 Alarm Status High byte: Alarm Status High Byte
b15-b8:
b8 7+',$ODUP6WDWXV
b9 : Under Current Alarm Status
b10: Over Current Alarm Status
b11: Under Voltage Alarm Status
b12: Over Voltage Alarm Status
b13: Under Compensate Alarm Status
b14: Over Compensate Alarm Status
b15: Step Error Alarm Status

Low byte: Alarm Status Low Byte


b3-b0:
b0 : CT Polarity Alarm Status
b1 : Temperature High Status Alarm
b2 : Low Volt Release Alarm Status
b7-b4: don’t care

F19 Displacement PF b15-b0: Signed Integer from -100 to 100.


The value is expressed as x/100.
Eg. -86 means -0.86.

F20 Step Output Status b15-b12: don’t care


b11-b0 :
‘1’: Step Off
‘0’: Step On

example: b0 for step 1 status

note: b8 to b11 is not applicable for 8 steps


model.

26 © 2016 Mikro Sdn Bhd All Rights Reserved


Modbus Database
Address
Description Format Unit
Dec Hex
Read Only Product Information Functions 4
0 0000 Model Description 1 & 2 F3 00
1 0001 Model Description 3 & 4 F3 08
2 0002 Model Description 5 & 6 F3 00
3 0003 Model Description 7 & 8 F3 xx1
4 0004 Model Description 9 & 10 F3 xx2
5 0005 Model Description 11 & 12 F3 xx3
6 0006 Manufacturer 1 & 2 F3
7 0007 Manufacturer 3 & 4 F3
8 0008 Manufacturer 5 & 6 F3
9 0009 Firmware Version 1 & 2 F3
10 000A Firmware Version 3 & 4 F3
11 000B Number Of Outputs F3 xx4
12 000C Phase model F3 xx3
13 000D Frequency model F3 xx5
14 000E Reserved F17
15 000F Reserved F17
16 0010 Reserved F17

NOTES:

1
For 8 steps model, ‘xx’ = <space><space>
For 12 steps model, ‘xx’ = <space> ‘1’

2
For 8 steps model, ‘xx’ = ‘80’
For 12 steps model, ‘xx’ = ‘20’

3
For single phase model, ‘xx’ = ‘P1’
For three phase model, ‘xx’ = ‘P3’

4
For 8 steps model, ‘xx’ = <space> ‘8’
For 12 steps model, ‘xx’ = ‘12’

5
For 50Hz model, ‘xx’ = ‘50’
For 60Hz model, ‘xx’ = ‘60’

Appendix B 27
Address
Description Format Unit
Dec Hex
Read Only Measurement Functions 4
17 0011 Frequency F1 Hz
19 0013 Phase Voltage A F1 Vrms
21 0015 Phase Voltage B F1 Vrms
23 0017 Phase Voltage C F1 Vrms
25 0019 Phase Current A F1 Irms
27 001B Phase Current B F1 Irms
29 001D Phase Current C F1 Irms
31 001F Active Power Phase A F1 W
33 0021 Reactive Power Phase A F1 VAR
35 0023 Apparent Power Phase A F1 VA
37 0025 Power Factor Phase A F1
39 0027 Active Power Phase B F1 W
41 0029 Reactive Power Phase B F1 VAR
43 002B Apparent Power Phase B F1 VA
45 002D Power Factor Phase B F1
47 002F Active Power Phase C F1 W
49 0031 Reactive Power Phase C F1 VAR
51 0033 Apparent Power Phase C F1 VA
53 0035 Power Factor Phase C F1
55 0037 Total Active Power F1 W
57 0039 Total Reactive Power F1 VAR
59 003B Total Apparent Power F1 VA
61 003D Total Power Factor F1
63 003F Fundamental Active Power Phase A F1 W
65 0041 Fundamental Active Power Phase B F1 W
67 0043 Fundamental Active Power Phase C F1 W
69 0045 Fundamental Reactive Power Phase A F1 VAR
71 0047 Fundamental Reactive Power Phase B F1 VAR
73 0049 Fundamental Reactive Power Phase C F1 VAR
75 004B Harmonic Active Power Phase A F1 W
77 004D Harmonic Active Power Phase B F1 W
79 004F Harmonic Active Power Phase C F1 W
81 0051 Harmonic Reactive Power Phase A F1 VAR
83 0053 Harmonic Reactive Power Phase B F1 VAR

28 © 2016 Mikro Sdn Bhd All Rights Reserved


Address
Description Format Unit
Dec Hex
Read Only Measurement Functions 4
85 0055 Harmonic Reactive Power Phase C F1 VAR
87 0057 Total Voltage Harmonic Phase A F1 Vrms
89 0059 Total Voltage Harmonic Phase B F1 Vrms
91 005B Total Voltage Harmonic Phase C F1 Vrms
93 005D Total Current Harmonic Phase A F1 Irms
95 005F Total Current Harmonic Phase B F1 Irms
97 0061 Total Current Harmonic Phase C F1 Irms
99 0063 Voltage A Harmonics 0 F2 
100 0064 Voltage A Harmonics 1 F2 
101 0065 Voltage A Harmonics 2 F2 
102 0066 Voltage A Harmonics 3 F2 
103 0067 Voltage A Harmonics 4 F2 
104 0068 Voltage A Harmonics 5 F2 
105 0069 Voltage A Harmonics 6 F2 
106 006A Voltage A Harmonics 7 F2 
107 006B Voltage A Harmonics 8 F2 
108 006C Voltage A Harmonics 9 F2 
109 006D Voltage A Harmonics 10 F2 
110 006E Voltage A Harmonics 11 F2 
111 006F Voltage A Harmonics 12 F2 
112 0070 Voltage A Harmonics 13 F2 
113 0071 Voltage A Harmonics 14 F2 
114 0072 Voltage A Harmonics 15 F2 
115 0073 Voltage A Harmonics 16 F2 
116 0074 Voltage A Harmonics 17 F2 
117 0075 Voltage A Harmonics 18 F2 
118 0076 Voltage A Harmonics 19 F2 
119 0077 Voltage A Harmonics 20 F2 
120 0078 Voltage A Harmonics 21 F2 
121 0079 Voltage A Harmonics 22 F2 
122 007A Voltage A Harmonics 23 F2 
123 007B Voltage A Harmonics 24 F2 
124 007C Voltage A Harmonics 25 F2 
125 007D Voltage A Harmonics 26 F2 

Appendix B 29
Address
Description Format Unit
Dec Hex
Read Only Measurement Functions 4
126 007E Voltage A Harmonics 27 F2 
127 007F Voltage A Harmonics 28 F2 
128 0080 Voltage A Harmonics 29 F2 
129 0081 Voltage A Harmonics 30 F2 
130 0082 Voltage A Harmonics 31 F2 
131 0083 Voltage B Harmonics 0 F2 
132 0084 Voltage B Harmonics 1 F2 
133 0085 Voltage B Harmonics 2 F2 
134 0086 Voltage B Harmonics 3 F2 
135 0087 Voltage B Harmonics 4 F2 
136 0088 Voltage B Harmonics 5 F2 
137 0089 Voltage B Harmonics 6 F2 
138 008A Voltage B Harmonics 7 F2 
139 008B Voltage B Harmonics 8 F2 
140 008C Voltage B Harmonics 9 F2 
141 008D Voltage B Harmonics 10 F2 
142 008E Voltage B Harmonics 11 F2 
143 008F Voltage B Harmonics 12 F2 
144 0090 Voltage B Harmonics 13 F2 
145 0091 Voltage B Harmonics 14 F2 
146 0092 Voltage B Harmonics 15 F2 
147 0093 Voltage B Harmonics 16 F2 
148 0094 Voltage B Harmonics 17 F2 
149 0095 Voltage B Harmonics 18 F2 
150 0096 Voltage B Harmonics 19 F2 
151 0097 Voltage B Harmonics 20 F2 
152 0098 Voltage B Harmonics 21 F2 
153 0099 Voltage B Harmonics 22 F2 
154 009A Voltage B Harmonics 23 F2 
155 009B Voltage B Harmonics 24 F2 
156 009C Voltage B Harmonics 25 F2 
157 009D Voltage B Harmonics 26 F2 
158 009E Voltage B Harmonics 27 F2 
159 009F Voltage B Harmonics 28 F2 

30 © 2016 Mikro Sdn Bhd All Rights Reserved


Address
Description Format Unit
Dec Hex
Read Only Measurement Functions 4
160 00A0 Voltage B Harmonics 29 F2 
161 00A1 Voltage B Harmonics 30 F2 
162 00A2 Voltage B Harmonics 31 F2 
163 00A3 Voltage C Harmonics 0 F2 
164 00A4 Voltage C Harmonics 1 F2 
165 00A5 Voltage C Harmonics 2 F2 
166 00A6 Voltage C Harmonics 3 F2 
167 00A7 Voltage C Harmonics 4 F2 
168 00A8 Voltage C Harmonics 5 F2 
169 00A9 Voltage C Harmonics 6 F2 
170 00AA Voltage C Harmonics 7 F2 
171 00AB Voltage C Harmonics 8 F2 
172 00AC Voltage C Harmonics 9 F2 
173 00AD Voltage C Harmonics 10 F2 
174 00AE Voltage C Harmonics 11 F2 
175 00AF Voltage C Harmonics 12 F2 
176 00B0 Voltage C Harmonics 13 F2 
177 00B1 Voltage C Harmonics 14 F2 
178 00B2 Voltage C Harmonics 15 F2 
179 00B3 Voltage C Harmonics 16 F2 
180 00B4 Voltage C Harmonics 17 F2 
181 00B5 Voltage C Harmonics 18 F2 
182 00B6 Voltage C Harmonics 19 F2 
183 00B7 Voltage C Harmonics 20 F2 
184 00B8 Voltage C Harmonics 21 F2 
185 00B9 Voltage C Harmonics 22 F2 
186 00BA Voltage C Harmonics 23 F2 
187 00BB Voltage C Harmonics 24 F2 
188 00BC Voltage C Harmonics 25 F2 
189 00BD Voltage C Harmonics 26 F2 
190 00BE Voltage C Harmonics 27 F2 
191 00BF Voltage C Harmonics 28 F2 
192 00C0 Voltage C Harmonics 29 F2 
193 00C1 Voltage C Harmonics 30 F2 

Appendix B 31
Address
Description Format Unit
Dec Hex
Read Only Measurement Functions 4
194 00C2 Voltage C Harmonics 31 F2 
195 00C3 Current A Harmonics 0 F2 
196 00C4 Current A Harmonics 1 F2 
197 00C5 Current A Harmonics 2 F2 
198 00C6 Current A Harmonics 3 F2 
199 00C7 Current A Harmonics 4 F2 
200 00C8 Current A Harmonics 5 F2 
201 00C9 Current A Harmonics 6 F2 
202 00CA Current A Harmonics 7 F2 
203 00CB Current A Harmonics 8 F2 
204 00CC Current A Harmonics 9 F2 
205 00CD Current A Harmonics 10 F2 
206 00CE Current A Harmonics 11 F2 
207 00CF Current A Harmonics 12 F2 
208 00D0 Current A Harmonics 13 F2 
209 00D1 Current A Harmonics 14 F2 
210 00D2 Current A Harmonics 15 F2 
211 00D3 Current A Harmonics 16 F2 
212 00D4 Current A Harmonics 17 F2 
213 00D5 Current A Harmonics 18 F2 
214 00D6 Current A Harmonics 19 F2 
215 00D7 Current A Harmonics 20 F2 
216 00D8 Current A Harmonics 21 F2 
217 00D9 Current A Harmonics 22 F2 
218 00DA Current A Harmonics 23 F2 
219 00DB Current A Harmonics 24 F2 
220 00DC Current A Harmonics 25 F2 
221 00DD Current A Harmonics 26 F2 
222 00DE Current A Harmonics 27 F2 
223 00DF Current A Harmonics 28 F2 
224 00E0 Current A Harmonics 29 F2 
225 00E1 Current A Harmonics 30 F2 
226 00E2 Current A Harmonics 31 F2 
227 00E3 Current B Harmonics 0 F2 

32 © 2016 Mikro Sdn Bhd All Rights Reserved


Address
Description Format Unit
Dec Hex
Read Only Measurement Functions 4
228 00E4 Current B Harmonics 1 F2 
229 00E5 Current B Harmonics 2 F2 
230 00E6 Current B Harmonics 3 F2 
231 00E7 Current B Harmonics 4 F2 
232 00E8 Current B Harmonics 5 F2 
233 00E9 Current B Harmonics 6 F2 
234 00EA Current B Harmonics 7 F2 
235 00EB Current B Harmonics 8 F2 
236 00EC Current B Harmonics 9 F2 
237 00ED Current B Harmonics 10 F2 
238 00EE Current B Harmonics 11 F2 
239 00EF Current B Harmonics 12 F2 
240 00F0 Current B Harmonics 13 F2 
241 00F1 Current B Harmonics 14 F2 
242 00F2 Current B Harmonics 15 F2 
243 00F3 Current B Harmonics 16 F2 
244 00F4 Current B Harmonics 17 F2 
245 00F5 Current B Harmonics 18 F2 
246 00F6 Current B Harmonics 19 F2 
247 00F7 Current B Harmonics 20 F2 
248 00F8 Current B Harmonics 21 F2 
249 00F9 Current B Harmonics 22 F2 
250 00FA Current B Harmonics 23 F2 
251 00FB Current B Harmonics 24 F2 
252 00FC Current B Harmonics 25 F2 
253 00FD Current B Harmonics 26 F2 
254 00FE Current B Harmonics 27 F2 
255 00FF Current B Harmonics 28 F2 
256 0100 Current B Harmonics 29 F2 
257 0101 Current B Harmonics 30 F2 
258 0102 Current B Harmonics 31 F2 
259 0103 Current C Harmonics 0 F2 
260 0104 Current C Harmonics 1 F2 
261 0105 Current C Harmonics 2 F2 

Appendix B 33
Address
Description Format Unit
Dec Hex
Read Only Measurement Functions 4
262 0106 Current C Harmonics 3 F2 
263 0107 Current C Harmonics 4 F2 
264 0108 Current C Harmonics 5 F2 
265 0109 Current C Harmonics 6 F2 
266 010A Current C Harmonics 7 F2 
267 010B Current C Harmonics 8 F2 
268 010C Current C Harmonics 9 F2 
269 010D Current C Harmonics 10 F2 
270 010E Current C Harmonics 11 F2 
271 010F Current C Harmonics 12 F2 
272 0110 Current C Harmonics 13 F2 
273 0111 Current C Harmonics 14 F2 
274 0112 Current C Harmonics 15 F2 
275 0113 Current C Harmonics 16 F2 
276 0114 Current C Harmonics 17 F2 
277 0115 Current C Harmonics 18 F2 
278 0116 Current C Harmonics 19 F2 
279 0117 Current C Harmonics 20 F2 
280 0118 Current C Harmonics 21 F2 
281 0119 Current C Harmonics 22 F2 
282 011A Current C Harmonics 23 F2 
283 011B Current C Harmonics 24 F2 
284 011C Current C Harmonics 25 F2 
285 011D Current C Harmonics 26 F2 
286 011E Current C Harmonics 27 F2 
287 011F Current C Harmonics 28 F2 
288 0120 Current C Harmonics 29 F2 
289 0121 Current C Harmonics 30 F2 
290 0122 Current C Harmonics 31 F2 
291 0123 Alarm Status F18
292 0124 Displacement PF1 F19
293 0125 Displacement PF2 F19
294 0126 Displacement PF3 F19
295 0127 Step Output Status F20

34 © 2016 Mikro Sdn Bhd All Rights Reserved


Address
Description Format Unit
Dec Hex
Read/Write Control Parameters Functions 3, 6, 16
296 0128 Switching Program & C/K Setting F4
297 0129 Reconnection Time and Target Power Factor F5
298 012A Rated Step 1 and 2 F6
299 012B Rated Step 3 and 4 F6
300 012C Rated Step 5 and 6 F6
301 012D Rated Step 7 and 8 F6
302 012E Rated Step 9 and 10 F6
303 012F Rated Step 11 and 12 F6
304 0130 Detection Phase F7
305 0131 Alarm Setting for Under Current and Over Current F9
306 0132 Alarm setting for Under Voltage and Over Voltage F10
307 0133 Fan Temperature and Alarm Setting for F11
Over Temperature Limit

308 0134 Set Slave Address and Baud Rate F12

309 0135 Set Parity and Fan setting F13


310 0136 Sensitivity F16
311 0137 $ODUPVHWWLQJIRU7+',/LPLW F8
312 0138 Reserved
313 0139 Signal Contact and Alarm Settings F14
314 013A Signal Contact Alarm Linkage 2 and Signal Contact F15
Alarm Linkage 1
315 013B Reserved F17
316 013C Reserved F17

Appendix B 35
APPENDIX C

Setting Parameters
CONTROL SETTING PARAMETERS DEFAULT VALUE
Target Power factor 0.98 Inductive
C/K setting Auto
Sensitivity 45 s
Reconnection time 30 s
Switching program Auto mode
1 for all steps

Detection mode Max Load


Fan Setting None
Signal Contact None
ALARM SETTING PARAMETERS DEFAULT VALUE
7+', 
Over Voltage 263 VAC
Under Voltage 204 VAC
Over Current 5.50 A rms
Under Current 0.15 A rms
Under Compensate Off
Over Compensate Off
CT Polarity Error Off
Step Error Off
Over Temperature 65 °C
COMMUNICATION SETTING PARAMETERS DEFAULT VALUE
Slave Address 1
Baud Rate 19200 bps
Parity Even
Communication Enable Off

36 © 2016
2011 Mikro Sdn Bhd All Rights Reserved
APPENDIX D

Calculations

D.1 C/K

L &.HTXDWLRQ

Q VPDOOHVWFDSDFLWRUVWHS VAR)
V = nominal primary system vROWDJH 9
I = primary rating of the current
trDQVIRUPHU $

Example:
If Q = 20kVAR, V = 415V, I = 850A
then,

L &RPSXWHG&.value as show below:

C/K Value for 415V

C.T 6PDOOHVW&DSDFLWRULQ NVAR)


Ratio 5 10 12.5 15 20 25 30 40 50 60 100 150

30:5 1.16
50:5 0.70
75:5 0.46 0.93 1.16
100:5 0.35 0.70 0.87 1.04
150:5 0.23 0.46 0.58 0.70 0.93 1.16

200:5 0.17 0.35 0.43 0.52 0.70 0.87 1.04


250:5 0.14 0.28 0.35 0.42 0.56 0.70 0.83 1.11
300:5 0.12 0.23 0.29 0.35 0.46 0.58 0.70 0.93 1.16
400:5 0.09 0.17 0.22 0.26 0.35 0.43 0.52 0.70 0.87 1.04
500:5 0.07 0.14 0.17 0.21 0.28 0.35 0.42 0.56 0.70 0.83

600:5 0.06 0.12 0.14 0.17 0.23 0.29 0.35 0.46 0.58 0.70 1.16
800:5 0.04 0.09 0.11 0.13 0.17 0.22 0.26 0.35 0.43 0.52 0.87
1000:5 0.03 0.07 0.09 0.10 0.14 0.17 0.21 0.28 0.35 0.42 0.70 1.04
1500:5 0.05 0.06 0.07 0.09 0.12 0.14 0.19 0.23 0.28 0.46 0.70
2000:5 0.03 0.04 0.05 0.07 0.09 0.10 0.14 0.17 0.21 0.35 0.52

2500:5 0.03 0.03 0.04 0.06 0.07 0.08 0.11 0.14 0.17 0.28 0.42
3000:5 0.03 0.03 0.05 0.06 0.07 0.09 0.12 0.14 0.23 0.35
4000:5 0.03 0.03 0.04 0.05 0.07 0.09 0.10 0.17 0.26

Table D.1.0

Context
Appendix D 37
D.2 Sensitivity

L &.HTXDWLRQ

Example:
If Q1st = 15kVAR, Sensitivity = 60s/step, Qrq = 15kVAR

If Qrq = 45kVAR,

Q1st : smallest step size kVAR


Qrq : required kVAR

D.3 Total Harmonic Distortion for Current (%THDI)

in = nth order harmonic rms current


%THDI = i1 = fundamental rms current

NOTES:
If the measured current falls below 2% of the rated current, the %THDI will display “---“.
This is because the regulator will not be able to obtain a reliable measurement to calcu-
late the %THDI. For %THDI > 500%, %THDI will be capped at 500%

D.4 Total Harmonic Distortion for Voltage (%THDV)

Vn = nth order harmonic rms current


%THDI =
V1 = fundamental rms current

NOTES:
If the measured voltage falls below 5% of the rated voltage, the %THDV will display
“---“. This is because the regulator will not be able to obtain a reliable measurement to
calculate the %THDV. For %THDV > 500%, %THDV will be capped at 500%

Appendix D 38

You might also like