11
Controllers
OPTIGO 5
Controllers
HVAC Controller
Brand
¾ Regin
Application
¾ Temperature control
¾ CO2 - control
¾ Humidity control
¾ Pressure control
¾ Pressure control with outdoor compensation
Specifications
¾ Supply voltage: 24 V AC
¾ 1 analogue input for PT1000
¾ 1 digital input
¾ 1 universal input 0 - 10 V DC or digital
¾ 2 analogue ouputs 0 - 10 V DC
Mounting
¾ DIN-rail
Accessoires
¾ Transfo 230 / 24 V AC, type TRAFO 15/D
¾ Duct temperature sensor, type TG-KH/PT1000 / TG-K3/PT1000
¾ Room temperature sensor, type TG-R5/PT1000
¾ Outdoor temperature sensor, type TG-UH3/PT1000
¾ Pressure transmitter, type DMD
¾ Pressure switch, type DTV
¾ CO2 transmitter, type WOX/E(-D) (room) / DOX-E (duct)
¾ Humidity transmitter, type HRTN (room) / DTTH (duct)
Technical data
¾ Power consumpition: 6 VA
¾ IP 20
Controllers
Function
¾ Temperature control : the temperature at the sensor is kept at the setpoint value by controlling output signals on AO1
and AO2. A single PI control loop is used. The output AO1 can by configured as : heating / cooling / changeover, the
output AO2 can by configured as : not used / cooling / heating / damper
¾ CO2 control : The CO2-value at the sensor is kept at the setpoint value by controlling the ouput signal AO1. A single PI
control loop is used. The output signal will increase when the CO2-value rises above the setpoint value
¾ Humidity control : The humidity at the sensor is kept at the setpoint value by controlling the output signals on AO1 and
AO2. AO1 is used for humidification, AO2 for dehumidification. A single PI loop is used. Humidification and
dehumidification can be used simultaneously, a neutral zone can be set between.
¾ Pressure control : The pressure at the sensor is kept at the setpoint value by controlling output signal AO1. A single PI
control loop is used. The output signal will increase when the pressure signal falls below the setpoint value.
¾ Pressure control with outdoor compensation : The pressure at the sensor is kept at the setpoint value by controlling
the output signal on AO1. The setpoint is automatically adjusted according to the outdoor temperature. A single loop
PI control is used. The output signal will increase when the pressure signal falls below the setpoint value. the setpoint
value follows a settable pressure-to-outdoor temperature relation
Settings
¾ Temperature setpoints :
1. Temperature: -20 to 40°C
2. Hysteresis: 0 to 10°C
3. P-band: 0 to 99 s
4. I-time: 0 to 999 s
5. Min-limit damper: 0 to 99%
¾ Other settings
1. CO2 setpoint: 0 to 5000 ppm (settable range correnponds the range of the sensor)
2. Humidity setpoint: 0 to 100 %
3. Pressure setpoint: 0 to 500 kPa (settable range corresponds the range of the sensor)
4. P-band: 0 to 100 %
5. I-time: 0 to 990 s
6. Outdoor compensation, start: -30 to 50°C
7. Pressure at -20°C outdoor temp.: 50 to 500 kPa