GPA

MODEL
Electric Fire Pump Controller
Full service full voltage
The model GPA full service full voltage across-the-line fire
Across-the-line starter
pump controller built to the latest NFPA20 standard and listed Micro-processor based
and approved by UL(218) and FM provides for:
D
• Full voltage across the line starting. Peak inrush current is
approximately 6 times the full load motor current (FLA). Inrush
current and starting torque are not reduced.
NOTE: Voltage at the controller line terminals shall not drop
is
more than 15% below controller nominal voltage under motor
starting conditions.

• 3-phase - 3-wire motor connection assures error free field


installation and simple change of motor rotation.
co
This type of controller is meant to be used where the capacity
of the electric power source and the electric supply utility
permits full voltage starting of a squirrel cage motor.

Only quality components, all U.L. listed or recognized and C.S.A.


nt
OPTIONAL
certified are used throughout to assure the best possible
reliability.

The complete assembled and wired controllers are factory CONTROLLER PROTECTION LEVEL:
tested before shipping and ready for immediate installation. • Standard NEMA - UL - CSA type 2 N.Y.C.
APPROVED
in
SUITABLE FOR USE AS SERVICE ENTRANCE EQUIPMENT • Optional - NEMA - UL - CSA type 3R
- NEMA - UL - CSA type 4
(where acceptable by local code)
- NEMA - UL - CSA type 4X
- NEMA - UL - CSA type 12
This controller meets the NFPA 20 requirements for connection
to a normal power source only. For normal and alternate power POWER AND MOTOR LEAD ENCLOSURE ENTRANCE
ue
sources, add a listed fire pump automatic transfer switch • Bottom gland plate
(Model GPG or GPU). Fire pump controller and automatic
transfer switch will be supplied as one unit. PRESSURE / EVENT RECORDER, ANNUNCIATOR AND LCD
DISPLAY
• Accessible without opening main door
Starting characteristics • Voltage and current indication
for a NEMA B squirrel cage motor • Pressure settings and system pressure indication
across-the-line starter • 7 day pressure and 15 day event data retrievable through
d
a USB (slave) communication port

600
Across-the-lin
e starting MICRO-PROCESSOR BASED LOGIC CONTROL
Locked rotor current • Mechanically protected and shielded
% of full load
Line current

450
WITHSTAND RATING (short circuit current):
300

150
208V. to 480V. 600V.
Full load current
Standard 100,000 A. 50,000 A.
20 40 60 80 100 Optional 150,000 A. 100,000 A.
Percent of motor speed (%)

OPERATIONAL TEMPERATURE LIMITS:


• 41ºF to 122ºF (5ºC to 50ºC)
GPA MODEL

Electric Fire Pump Controller


Full service full voltage
Across-the-line starter
Micro-processor based ANNUNCIATOR AND LCD DISPLAY

STANDARD FEATURES: Voltage and amperage module


Provides for:
MANUAL OPERATORS (FLANGE MOUNTED) • Phase sequence / Loss monitoring
• Single operator for both isolating switch and & alarms
circuit breaker door interlocked in the “ON” • Individual phase-to-phase voltage
position complete with interlock defeater screw indication
• Emergency manual start handle providing for • Individual phase current indication
manual across-the-line starting
• True elapsed run time
• Start and Stop pushbuttons
D
• Motor run visual indication
ELECTRICAL FEATURES • Over & under current visual indication
• Molded case isolation switch • Over & under voltage visual indication
• Molded case circuit breaker • Fail to start visual indication
• Motor starter HP rated • Phase loss visual indication
is
• 3 phase voltage surge suppressor • Phase unbalance visual indication
• Power available LED
CONTROL FEATURES
• Micro-processor logic based • Phase reversal LED
• Factory set (no field programming)
• Locked rotor protection Pressure and Sequencer module
co
• Phase sequence / loss Provides for:
• Provision for remote or deluge valve start • Cut-In & Cut-Out pressure setting
• Automatic start sequence • System pressure indication
• Pressure transducer (0-300psi) • Run period timer
• Manual and emergency control circuit
independant of micro-processor • Sequential start timer
• Weekly test setting
DRY ALARM CONTACTS - 8A. - 250VAC • Pressure recording
nt
• Power or phase failure and/or circuit breaker • Alarm & events recording
in open position - DPDT • Pump on demand LED
• Phase reversal - DPDT • Weekly test LED
• Pump run – 1N/O – 1N/C • USB (slave) communication port
• Trouble (alarm conditions) - DPDT
• Printer (optional)
• Modem (optional)
OPTIONAL FEATURES:
in
(Refer to GPO Brochure for details)

• Option Type A: Operational modifications


• Option Type B: Additional annunciations
• Option Type C: Extra alarm contacts
ue
BOTTOM GLAND PLATE
• Option Type D: Miscellaneous
For ease of power and motor lead entrance
• Option Type E: Load shedding provisions
• Option Type F: Automatic transfer switch
options
• Option Type H: Export packing

GPA - GPP - GPY GPR - GPS - GPW APPROX.


d
WEIGHT
208V.-240V. 380V.-416V. 440V.-480V. 600V. WIDTH HEIGHT DEPTH WIDTH HEIGHT DEPTH
HP HP HP HP in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (Kg)
5 to 30 5 to 50 5 to 60 5 to 75 20 (508) 36 (914)* 12 (305) 26 (660) 36 (914)* 12 (305) 275 (125)
40-60 60-100 75-150 100-150 24 (610) 54 (1371) 14 (355) 30 (762) 54 (1371) 14 (355) 375 (170)
75-150 125-350* 200-400 200-500 30 (762) 68 (1727) 18 (457) 36 (914) 68 (1727) 18 (457) 600 (270)
* If FLA is equal to or less then 500 A. * Height does not include mounting feet.

HOW TO ORDER: GPA - V/ HP / Ph / Hz + options


Tableau aGPA-R-S
Ex.: GPA - 208 / 20 / 3/ 60 + options

Tornatech inc., 7075, Place Robert-Joncas, # 132, Montreal, Quebec, Canada H4M 2Z2
GPA-BRO-001/E Rev.1
Tel.: + 1 514 334 0523 + 1 800 363 8448 (Canada & U.S.A.) Fax: + 1 514 334 5448 SUBJECT TO MODIFICATION WITHOUT NOTICE
E-mail: [email protected] www.tornatech.com All rights reserved. Printed in Canada