REPORTE DE PRUEBAS
SALA 800-ER-034
INT. DE ENTRADA
Company: COSERPO SAC
Test Person: JENSEN GARCIA R.
Date tested: 02-Apr-22, 04:38:26 PM
Testmodules Passed: 5
Testmodules Failed: 0
Test Object - Device Settings
Substation/Bay:
Substation: SALA 800-ER-34 Substation address:
Bay: INTERRUPTOR DE ENTRADA Bay address: 800-MV-001.M04
Device:
Name/description: REF545 Manufacturer: ABB
Device type: FEEDER Device address:
Serial/model number: ER329050
Additional info 1: PT: 4.2kV/120V
Additional info 2: CT: 1000/5
Nominal Values:
f nom: 60.00 Hz Number of phases: 3
V nom (secondary): 120.0 V V primary: 4.200 kV
I nom (secondary): 5.000 A I primary: 1.000 kA
CMC356
Test Equipment
Type Serial Number
CMC356 NJ628X
Hardware Check
Performed At Result Details
4/2/2022 4:29:02 PM Passed
Group:MEDIDAS
Medidas :
Medidas :
Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 02-Apr-2022 16:29:11 Test End: 02-Apr-2022 16:31:09
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC
Test Results
1/8
REPORTE DE PRUEBAS
SALA 800-ER-034
Title: MEDIDAS
Fault Calculator:
Table Inputmode Parameters (All values are primary)
Direct V L1-E 2.425 kV 0.00 ° 60.000 Hz
V L2-E 2.425 kV -120.00 ° 60.000 Hz
V L3-E 2.425 kV 120.00 ° 60.000 Hz
I L1 100.0 A -30.00 ° 60.000 Hz
I L2 100.0 A -150.00 ° 60.000 Hz
I L3 100.0 A 90.00 ° 60.000 Hz
Generator Settings
V L1-E 2424.870V 0.00° +90° I L3
V L2-E 2424.870V -120.00° V L3-E
V L3-E 2424.870V 120.00°
I L1 100.000A -30.00°
V L1-E
I L2 100.000A -150.00°
180° 0°
I L3 100.000A 90.00°
V IL2-E
L2 I L1
80.0 V -90° 500.0 mA
Binary Inputs
Name Slope Time
Overload 1->0 n/a
Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed
Group end:MEDIDAS
Group:50/51 SOBRECORRIENTE FASES
50/51 SOBRECORRIENTE FASES :
50/51 L1-L2-L3:
Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0.04 s VT connection: n/a
TimeTolRel: 5.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I> IEC Extremely Inverse 1.15 Iref 0.15 0.95 Non Directional
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes Io> IEC Definite Time 0.20 Iref 0.05 s 0.95 Non Directional
2/8
REPORTE DE PRUEBAS
SALA 800-ER-034
Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 02-Apr-2022 16:32:55 Test End: 02-Apr-2022 16:33:30
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC
Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.00 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 240.0 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: Yes
Thermal reset method: Manual
Thermal reset message: Please reset the Thermal Memory of the device under
test before continuing.
Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2-L3 I> 1.750 10.06 A -60.00 ° 5.822 s 4.766 s 7.092 s
L1-L2-L3 I> 2.115 12.16 A -60.00 ° 3.456 s 2.882 s 4.123 s
L1-L2-L3 I> 2.549 14.66 A -60.00 ° 2.182 s 1.838 s 2.574 s
L1-L2-L3 I> 3.172 18.24 A -60.00 ° 1.324 s 1.123 s 1.551 s
Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2-L3 I> 1.750 10.06 A -60.00 ° 5.822 s 5.826 s 0.06810 % No Passed
L1-L2-L3 I> 2.115 12.16 A -60.00 ° 3.456 s 3.463 s 0.2140 % No Passed
L1-L2-L3 I> 2.549 14.66 A -60.00 ° 2.182 s 2.191 s 0.4094 % No Passed
L1-L2-L3 I> 3.172 18.24 A -60.00 ° 1.324 s 1.339 s 1.126 % No Passed
Charts for Fault Types:
Angle
Type
L1-L2-L3 -60.00 °
10000.000
1000.000
100.000
10.000
t/s
1.000
0.100
0.010
5 7 10 20 30 50 70 100
I/A
3/8
REPORTE DE PRUEBAS
SALA 800-ER-034
Test State:
4 out of 4 points tested.
4 points passed.
0 points failed.
Test passed
50/51 L1-L2:
Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0.04 s VT connection: n/a
TimeTolRel: 5.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I> IEC Extremely Inverse 1.15 Iref 0.15 0.95 Non Directional
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes Io> IEC Definite Time 0.20 Iref 0.05 s 0.95 Non Directional
Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 02-Apr-2022 16:34:36 Test End: 02-Apr-2022 16:35:20
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC
Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.00 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 240.0 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: Yes
Thermal reset method: Manual
Thermal reset message: Please reset the Thermal Memory of the device under
test before continuing.
Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2 I> 1.750 10.06 A -60.00 ° 5.822 s 4.766 s 7.092 s
L1-L2 I> 2.115 12.16 A -60.00 ° 3.456 s 2.882 s 4.123 s
L1-L2 I> 2.549 14.66 A -60.00 ° 2.182 s 1.838 s 2.574 s
L1-L2 I> 3.172 18.24 A -60.00 ° 1.324 s 1.123 s 1.551 s
Binary Inputs:
Trigger Logic: And
4/8
REPORTE DE PRUEBAS
SALA 800-ER-034
Name Trigger State
TRIP 1
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 I> 1.750 10.06 A -60.00 ° 5.822 s 5.851 s 0.4993 % No Passed
L1-L2 I> 2.115 12.16 A -60.00 ° 3.456 s 3.475 s 0.5438 % No Passed
L1-L2 I> 2.549 14.66 A -60.00 ° 2.182 s 2.199 s 0.7714 % No Passed
L1-L2 I> 3.172 18.24 A -60.00 ° 1.324 s 1.344 s 1.480 % No Passed
Charts for Fault Types:
Angle
Type
L1-L2 -60.00 °
10000.000
1000.000
100.000
10.000
t/s
1.000
0.100
0.010
5 7 10 20 30 50 70 100
I/A
Test State:
4 out of 4 points tested.
4 points passed.
0 points failed.
Test passed
50/51 L2-L3:
Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0.04 s VT connection: n/a
TimeTolRel: 5.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I> IEC Extremely Inverse 1.15 Iref 0.15 0.95 Non Directional
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes Io> IEC Definite Time 0.20 Iref 0.05 s 0.95 Non Directional
Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 02-Apr-2022 16:36:42 Test End: 02-Apr-2022 16:37:19
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC
5/8
REPORTE DE PRUEBAS
SALA 800-ER-034
Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.00 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 240.0 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: Yes
Thermal reset method: Manual
Thermal reset message: Please reset the Thermal Memory of the device under
test before continuing.
Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L2-L3 I> 1.750 10.06 A -60.00 ° 5.822 s 4.766 s 7.092 s
L2-L3 I> 2.115 12.16 A -60.00 ° 3.456 s 2.882 s 4.123 s
L2-L3 I> 2.549 14.66 A -60.00 ° 2.182 s 1.838 s 2.574 s
L2-L3 I> 3.172 18.24 A -60.00 ° 1.324 s 1.123 s 1.551 s
Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L2-L3 I> 1.750 10.06 A -60.00 ° 5.822 s 5.848 s 0.4529 % No Passed
L2-L3 I> 2.115 12.16 A -60.00 ° 3.456 s 3.476 s 0.5872 % No Passed
L2-L3 I> 2.549 14.66 A -60.00 ° 2.182 s 2.203 s 0.9502 % No Passed
L2-L3 I> 3.172 18.24 A -60.00 ° 1.324 s 1.344 s 1.496 % No Passed
Charts for Fault Types:
Angle
Type
L2-L3 -60.00 °
10000.000
1000.000
100.000
10.000
t/s
1.000
0.100
0.010
5 7 10 20 30 50 70 100
I/A
Test State:
4 out of 4 points tested.
4 points passed.
0 points failed.
Test passed
6/8
REPORTE DE PRUEBAS
SALA 800-ER-034
0/51 L3-L1:
Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs: 0.04 s VT connection: n/a
TimeTolRel: 5.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No
Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I> IEC Extremely Inverse 1.15 Iref 0.15 0.95 Non Directional
Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes Io> IEC Definite Time 0.20 Iref 0.05 s 0.95 Non Directional
Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 02-Apr-2022 16:37:50 Test End: 02-Apr-2022 16:38:26
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC
Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.00 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 240.0 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: Yes
Thermal reset method: Manual
Thermal reset message: Please reset the Thermal Memory of the device under
test before continuing.
Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L3-L1 I> 1.750 10.06 A -60.00 ° 5.822 s 4.766 s 7.092 s
L3-L1 I> 2.115 12.16 A -60.00 ° 3.456 s 2.882 s 4.123 s
L3-L1 I> 2.549 14.66 A -60.00 ° 2.182 s 1.838 s 2.574 s
L3-L1 I> 3.172 18.24 A -60.00 ° 1.324 s 1.123 s 1.551 s
Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1
7/8
REPORTE DE PRUEBAS
SALA 800-ER-034
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L3-L1 I> 1.750 10.06 A -60.00 ° 5.822 s 5.840 s 0.3069 % No Passed
L3-L1 I> 2.115 12.16 A -60.00 ° 3.456 s 3.473 s 0.5033 % No Passed
L3-L1 I> 2.549 14.66 A -60.00 ° 2.182 s 2.205 s 1.065 % No Passed
L3-L1 I> 3.172 18.24 A -60.00 ° 1.324 s 1.347 s 1.737 % No Passed
Charts for Fault Types:
Angle
Type
L3-L1 -60.00 °
10000.000
1000.000
100.000
10.000
t/s
1.000
0.100
0.010
5 7 10 20 30 50 70 100
I/A
Test State:
4 out of 4 points tested.
4 points passed.
0 points failed.
Test passed
Group end:50/51 SOBRECORRIENTE FASES
8/8