800 MV 001.M04

The document reports the results of electrical protection device tests conducted at a substation. Measurements were taken of voltage, current, and fault calculations were performed. Overcurrent protection elements were then tested under various fault conditions and tripped within tolerance of their time curves.

Uploaded by

alonso
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views8 pages

800 MV 001.M04

The document reports the results of electrical protection device tests conducted at a substation. Measurements were taken of voltage, current, and fault calculations were performed. Overcurrent protection elements were then tested under various fault conditions and tripped within tolerance of their time curves.

Uploaded by

alonso
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

REPORTE DE PRUEBAS

SALA 800-ER-034

INT. DE ENTRADA
Company: COSERPO SAC
Test Person: JENSEN GARCIA R.
Date tested: 02-Apr-22, 04:38:26 PM
Testmodules Passed: 5
Testmodules Failed: 0

Test Object - Device Settings

Substation/Bay:
Substation: SALA 800-ER-34 Substation address:
Bay: INTERRUPTOR DE ENTRADA Bay address: 800-MV-001.M04

Device:
Name/description: REF545 Manufacturer: ABB
Device type: FEEDER Device address:
Serial/model number: ER329050
Additional info 1: PT: 4.2kV/120V
Additional info 2: CT: 1000/5

Nominal Values:
f nom: 60.00 Hz Number of phases: 3
V nom (secondary): 120.0 V V primary: 4.200 kV
I nom (secondary): 5.000 A I primary: 1.000 kA

CMC356

Test Equipment
Type Serial Number
CMC356 NJ628X

Hardware Check
Performed At Result Details
4/2/2022 4:29:02 PM Passed

Group:MEDIDAS

Medidas :

Medidas :

Test Module
Name: OMICRON QuickCMC Version: 4.30
Test Start: 02-Apr-2022 16:29:11 Test End: 02-Apr-2022 16:31:09
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC

Test Results

1/8
REPORTE DE PRUEBAS

SALA 800-ER-034

Title: MEDIDAS

Fault Calculator:
Table Inputmode Parameters (All values are primary)
Direct V L1-E 2.425 kV 0.00 ° 60.000 Hz
V L2-E 2.425 kV -120.00 ° 60.000 Hz
V L3-E 2.425 kV 120.00 ° 60.000 Hz
I L1 100.0 A -30.00 ° 60.000 Hz
I L2 100.0 A -150.00 ° 60.000 Hz
I L3 100.0 A 90.00 ° 60.000 Hz

Generator Settings
V L1-E 2424.870V 0.00° +90° I L3
V L2-E 2424.870V -120.00° V L3-E
V L3-E 2424.870V 120.00°
I L1 100.000A -30.00°
V L1-E
I L2 100.000A -150.00°
180° 0°
I L3 100.000A 90.00°

V IL2-E
L2 I L1
80.0 V -90° 500.0 mA

Binary Inputs
Name Slope Time
Overload 1->0 n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

Group end:MEDIDAS
Group:50/51 SOBRECORRIENTE FASES

50/51 SOBRECORRIENTE FASES :


50/51 L1-L2-L3:
Test Object - Overcurrent Parameters

General - Values:
TimeTolAbs: 0.04 s VT connection: n/a
TimeTolRel: 5.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No

Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I> IEC Extremely Inverse 1.15 Iref 0.15 0.95 Non Directional

Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes Io> IEC Definite Time 0.20 Iref 0.05 s 0.95 Non Directional

2/8
REPORTE DE PRUEBAS

SALA 800-ER-034

Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 02-Apr-2022 16:32:55 Test End: 02-Apr-2022 16:33:30
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC

Test Settings:

Fault Model:
Time reference: Fault inception
Load current: 0.00 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 240.0 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: Yes
Thermal reset method: Manual
Thermal reset message: Please reset the Thermal Memory of the device under
test before continuing.

Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2-L3 I> 1.750 10.06 A -60.00 ° 5.822 s 4.766 s 7.092 s
L1-L2-L3 I> 2.115 12.16 A -60.00 ° 3.456 s 2.882 s 4.123 s
L1-L2-L3 I> 2.549 14.66 A -60.00 ° 2.182 s 1.838 s 2.574 s
L1-L2-L3 I> 3.172 18.24 A -60.00 ° 1.324 s 1.123 s 1.551 s

Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1

Shot Test Results:


Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2-L3 I> 1.750 10.06 A -60.00 ° 5.822 s 5.826 s 0.06810 % No Passed
L1-L2-L3 I> 2.115 12.16 A -60.00 ° 3.456 s 3.463 s 0.2140 % No Passed
L1-L2-L3 I> 2.549 14.66 A -60.00 ° 2.182 s 2.191 s 0.4094 % No Passed
L1-L2-L3 I> 3.172 18.24 A -60.00 ° 1.324 s 1.339 s 1.126 % No Passed

Charts for Fault Types:


Angle
Type

L1-L2-L3 -60.00 °

10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

5 7 10 20 30 50 70 100
I/A

3/8
REPORTE DE PRUEBAS

SALA 800-ER-034

Test State:
4 out of 4 points tested.
4 points passed.
0 points failed.

Test passed

50/51 L1-L2:
Test Object - Overcurrent Parameters

General - Values:
TimeTolAbs: 0.04 s VT connection: n/a
TimeTolRel: 5.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No

Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I> IEC Extremely Inverse 1.15 Iref 0.15 0.95 Non Directional

Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes Io> IEC Definite Time 0.20 Iref 0.05 s 0.95 Non Directional

Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 02-Apr-2022 16:34:36 Test End: 02-Apr-2022 16:35:20
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC

Test Settings:
Fault Model:
Time reference: Fault inception
Load current: 0.00 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 240.0 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: Yes
Thermal reset method: Manual
Thermal reset message: Please reset the Thermal Memory of the device under
test before continuing.

Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L1-L2 I> 1.750 10.06 A -60.00 ° 5.822 s 4.766 s 7.092 s
L1-L2 I> 2.115 12.16 A -60.00 ° 3.456 s 2.882 s 4.123 s
L1-L2 I> 2.549 14.66 A -60.00 ° 2.182 s 1.838 s 2.574 s
L1-L2 I> 3.172 18.24 A -60.00 ° 1.324 s 1.123 s 1.551 s

Binary Inputs:
Trigger Logic: And

4/8
REPORTE DE PRUEBAS

SALA 800-ER-034

Name Trigger State


TRIP 1

Shot Test Results:


Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L1-L2 I> 1.750 10.06 A -60.00 ° 5.822 s 5.851 s 0.4993 % No Passed
L1-L2 I> 2.115 12.16 A -60.00 ° 3.456 s 3.475 s 0.5438 % No Passed
L1-L2 I> 2.549 14.66 A -60.00 ° 2.182 s 2.199 s 0.7714 % No Passed
L1-L2 I> 3.172 18.24 A -60.00 ° 1.324 s 1.344 s 1.480 % No Passed

Charts for Fault Types:


Angle
Type

L1-L2 -60.00 °

10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

5 7 10 20 30 50 70 100
I/A

Test State:
4 out of 4 points tested.
4 points passed.
0 points failed.

Test passed

50/51 L2-L3:
Test Object - Overcurrent Parameters

General - Values:
TimeTolAbs: 0.04 s VT connection: n/a
TimeTolRel: 5.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No

Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I> IEC Extremely Inverse 1.15 Iref 0.15 0.95 Non Directional

Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes Io> IEC Definite Time 0.20 Iref 0.05 s 0.95 Non Directional

Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 02-Apr-2022 16:36:42 Test End: 02-Apr-2022 16:37:19
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC

5/8
REPORTE DE PRUEBAS

SALA 800-ER-034

Test Settings:

Fault Model:
Time reference: Fault inception
Load current: 0.00 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 240.0 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: Yes
Thermal reset method: Manual
Thermal reset message: Please reset the Thermal Memory of the device under
test before continuing.

Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L2-L3 I> 1.750 10.06 A -60.00 ° 5.822 s 4.766 s 7.092 s
L2-L3 I> 2.115 12.16 A -60.00 ° 3.456 s 2.882 s 4.123 s
L2-L3 I> 2.549 14.66 A -60.00 ° 2.182 s 1.838 s 2.574 s
L2-L3 I> 3.172 18.24 A -60.00 ° 1.324 s 1.123 s 1.551 s

Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1

Shot Test Results:


Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L2-L3 I> 1.750 10.06 A -60.00 ° 5.822 s 5.848 s 0.4529 % No Passed
L2-L3 I> 2.115 12.16 A -60.00 ° 3.456 s 3.476 s 0.5872 % No Passed
L2-L3 I> 2.549 14.66 A -60.00 ° 2.182 s 2.203 s 0.9502 % No Passed
L2-L3 I> 3.172 18.24 A -60.00 ° 1.324 s 1.344 s 1.496 % No Passed

Charts for Fault Types:


Angle
Type

L2-L3 -60.00 °

10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

5 7 10 20 30 50 70 100
I/A

Test State:
4 out of 4 points tested.
4 points passed.
0 points failed.

Test passed

6/8
REPORTE DE PRUEBAS

SALA 800-ER-034

0/51 L3-L1:
Test Object - Overcurrent Parameters

General - Values:
TimeTolAbs: 0.04 s VT connection: n/a
TimeTolRel: 5.00 % CT starpoint connection: n/a
CurrentTolAbs: 0.05 Iref
CurrentTolRel: 5.00 %
Directional: No

Elements - Phase:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes I> IEC Extremely Inverse 1.15 Iref 0.15 0.95 Non Directional

Elements - Residual:
Active Name Tripping characteristic I Pick-up Time Reset Ratio Direction
Yes Io> IEC Definite Time 0.20 Iref 0.05 s 0.95 Non Directional

Test Module
Name: OMICRON Overcurrent Version: 4.30
Test Start: 02-Apr-2022 16:37:50 Test End: 02-Apr-2022 16:38:26
User Name: JENSEN GARCIA R. Manager: WILMER PANUERA
Company: COSERPO SAC

Test Settings:

Fault Model:
Time reference: Fault inception
Load current: 0.00 A
Load angle: n/a
Prefault time: 100.0 ms
Abs. max time: 240.0 s
Post fault time: 500.0 ms
Rel. max time: 100.0 %
Enable voltage output: Yes
Fault voltage LN (for all but two phase faults): 30.00 V
Fault voltage LL (for two phase faults): 51.96 V
Decaying DC active: No
Time constant: n/a
CB char min time: 50.00 ms
Thermal reset active: Yes
Thermal reset method: Manual
Thermal reset message: Please reset the Thermal Memory of the device under
test before continuing.

Shot Test:
Type Relative To Factor Magnitude Angle tnom tmin tmax
L3-L1 I> 1.750 10.06 A -60.00 ° 5.822 s 4.766 s 7.092 s
L3-L1 I> 2.115 12.16 A -60.00 ° 3.456 s 2.882 s 4.123 s
L3-L1 I> 2.549 14.66 A -60.00 ° 2.182 s 1.838 s 2.574 s
L3-L1 I> 3.172 18.24 A -60.00 ° 1.324 s 1.123 s 1.551 s

Binary Inputs:
Trigger Logic: And
Name Trigger State
TRIP 1

7/8
REPORTE DE PRUEBAS

SALA 800-ER-034

Shot Test Results:


Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
L3-L1 I> 1.750 10.06 A -60.00 ° 5.822 s 5.840 s 0.3069 % No Passed
L3-L1 I> 2.115 12.16 A -60.00 ° 3.456 s 3.473 s 0.5033 % No Passed
L3-L1 I> 2.549 14.66 A -60.00 ° 2.182 s 2.205 s 1.065 % No Passed
L3-L1 I> 3.172 18.24 A -60.00 ° 1.324 s 1.347 s 1.737 % No Passed

Charts for Fault Types:


Angle
Type

L3-L1 -60.00 °

10000.000
1000.000
100.000
10.000
t/s

1.000
0.100
0.010

5 7 10 20 30 50 70 100
I/A

Test State:
4 out of 4 points tested.
4 points passed.
0 points failed.

Test passed

Group end:50/51 SOBRECORRIENTE FASES