PHOTOVOLTAIC ROOF MOUNT SYSTEM

RESERVED FOR AHJ


18 MODULES-ROOF MOUNTED - 6.48 kWDC, 5.39 kWAC
303 TEAKWOOD DR, EAGLE POINT, OR 97524 USA
SYSTEM SUMMARY: DESIGN CRITERIA: GOVERNING CODES: SHEET INDEX
(N) 18 - YINGLI SOLAR YL360D-34D1/2 (360W) MODULES ROOF TYPE: - CORRUGATED METAL 2020 NATIONAL ELECTRICAL CODE (NEC) PV-0 COVER SHEET PURELIGHT POWER
(N) 04 - HOYMILES HM-1200N MICRO-INVERTERS ROOF FRAMING: - SEAM @8" O.C. 2021 OREGON FIRE CODE (OFC) PV-1 SITE PLAN WITH ROOF PLAN 541 PARSONS DR.
(N) 01 - HOYMILES HM-600N MICRO-INVERTER STORY: - 01 STORY 2021 OREGON RESIDENTIAL SPECIALTY CODE (ORSC) PV-2 ROOF PLAN WITH MODULES
MEDFORD, OR 97501
CSLB : 226333
(N) 01 - JUNCTION BOX SNOW LOAD : - 96 PSF 2019 OREGON STRUCTURAL SPECIALTY CODE (OSSC) PV-3 ATTACHMENT DETAILS PHONE: (541) 816-4047
(E) 200A SPLIT BUS PANEL WIND SPEED :- 25 MPH (ASCE 7-16) PV-4 BRANCH LAYOUT Email: [email protected]

(N) 30A FUSED AC DISCONNECT WIND EXPOSURE:- B PV-5 ELECTRICAL LINE DIAGRAM VERSION
(N) 100A SOLAR LOAD CENTER RISK CATEGORY:- II PV-6 ELECTRICAL CALCULATION DESCRIPTION DATE REV
(N) PRODUCTION METER OCCUPANCY: R-3 RESIDENTIAL PV-7 WARNING LABELS INITIAL RELEASE 06/02/2022 UR
PV-7.1 PLACARD
PV-8 ADDITIONAL NOTES
PV-9+ EQUIPMENT SPEC SHEETS

GENERAL NOTES:
1. PV SYSTEMS AND SUPPORTING STRUCTURE SHALL COMPLY
WITH REQUIREMENTS OF 2021 OESC & 2019 OSSC.
2. 3111.3.2 - PV RACKING AND ATTACHMENTS SHALL BE UL 1703
CERTIFIED. ARRAY LOCATION
3. 3111.3.4 - PV SYSTEM SHALL HAVE A FIRE CLASSIFICATION
THAT IS EQUAL TO OR GREATER THAN THE ROOF ASSEMBLY
PROJECT NAME
REQUIRED BY OSSC SECTION 1505.1.

EAGLE POINT, OR 97524 USA


4. 3111.4.3 - 3111.4.7- PV LAYOUT SHALL NOT RESTRICT EGRESS,

AHJ: CITY OF EAGLE POINT


LIGHT VENTILATION, OR ROOF DRAINAGE REQUIREMENTS.
PROJECT SITE

UTILITY: PACIFIC POWER


5. 3111.4.8.1 - GENERAL PATHWAY REQUIREMENTS:

HOWARD LEACHMAN
· 36" WIDE PATHWAY SHALL NOT BE REQUIRED ON

303 TEAKWOOD DR,


STRUCTURES WITH A PV ARRAY AREA OF 1,000 SF OR LESS

APN# 10547110
INSTALLED ON A ROOF WITH A SLOPE THAT EXCEEDS 2:12 AND
WITH AN INTERSECTING ADJACENT ROOF AND WHERE NO
SECTION IS LARGER THAN 150 FEET MEASURED IN LENGTH OR
WIDTH.
· WHERE PV ARRAY DOES NOT EXCEED 25% AS MEASURED IN
PLAN VIEW OF TOTAL ROOF AREA OF A STRUCTURE, A
MINIMUM OF 12" UNOBSTRUCTED PATHWAY SHALL BE
MAINTAINED ALONG EACH SIDE OF ANY HORIZONTAL RIDGE.
· WHERE THE SOLAR ARRAY EXCEEDS 25% AS MEASURED IN
PLAN VIEW OF TOTAL ROOF AREA OF THE STRUCTURE, A
MINIMUM OF ONE 36" UNOBSTRUCTED PATHWAY SHALL BE
PROVIDED IN ADDITION TO A MINIMUM 12" UNOBSTRUCTED
ALONG EA. SIDE OF ANY HORIZONTAL RIDGE.
6. ROOF STRUCTURE IS CONVENTIONAL LIGHT FRAMED WOOD
CONSTRUCTION WITH SEAM @ 8" O.C. REFER TO ALLOWABLE
SPAN REQUIREMENTS IN TABLE 305.4.1.
7. 3111.4.8.5.1 - DISCONNECTS, J-BOXES, COMBINER BOXES OR
GUTTERS SHALL NOT BE PLACED IN ANY REQUIRED PATHWAY SHEET NAME
OR CUTOUT.
8. PV MODULES AND RACKING SHALL BE DIRECTLY ATTACHED TO COVER SHEET
ROOF FRAMING AS SHOWN IN PV-2. WHEN ATTACHMENT
LOCATED WITHIN 3' OF ROOF EDGE, HIP, EAVE, RIDGE SHALL
SHEET SIZE
BE 24" O.C. MAX.
9. 3111.5.4 - MAX MODULE HEIGHT < 18" OFF ROOF SURFACE. ANSI B
11" X 17"
1 AERIAL PHOTO 2 VICINITY MAP SHEET NUMBER
PV-0 SCALE: NTS PV-0 SCALE: NTS
PV-0
ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE

RESERVED FOR AHJ


PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR
DOORS, AND LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION IN
LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD (N) PRODUCTION METER (N) 30A FUSED AC DISCONNECT
OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS.
NOTE: CHECK WITH CITY/COUNTY OR LAND SURVEYOR (N) 100A SOLAR LOAD CENTER
FOR ACCURATE PROPERTY LOCATION. (E) UTILITY METER

NOTE: PV AC DISCONNECT LOCATED WITHIN (N) 3/4" OR GREATER EMT


10 FEET OF THE MAIN BILLING METER CONDUIT RUN (IN ATTIC)
(E) 200A SPLIT BUS PANEL
ROOF #1 PURELIGHT POWER
541 PARSONS DR.
(18) YINGLI SOLAR YL360D-34D1/2 MEDFORD, OR 97501
(360W) SOLAR MODULES ROOF ACCESS POINT CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION

PROPERTY LINE ~162.48' DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROPE
10'-4"
SLC PVM ACD UM
MSP

R
TY LINE
EXISTING
88'-11" DRIVEWAY

TEAKWOOD DR
~80.85'

~80.30'
26'-10" PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


01- STORY

JB

UTILITY: PACIFIC POWER


POOL HOUSE

HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
E
RTY LIN
PROPE

5'-8"
PROPERTY LINE
~176.34'
(E) TREES (TYP.)
(E) FENCE
(E) STRUCTURE (TYP.) (N) JUNCTION BOX SHEET NAME

SITE PLAN WITH


ROOF PLAN
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER
SITE PLAN WITH ROOF PLAN
1 SCALE: 1/16" = 1'-0"
PV-1
RESERVED FOR AHJ
MODULE TYPE, DIMENSIONS & WEIGHT ARRAY AREA & ROOF AREA CALC'S
NUMBER OF MODULES = 18 MODULES ROOF
ARRAY ROOF
MODULE TYPE = YINGLI SOLAR YL360D-34D1/2 (360W) MODULES # OF AREA AREA
AREA
ROOF COVERED BY
MODULE WEIGHT = 42.99 LBS / 19.5 KG. MODULES (Sq. Ft.) (Sq. Ft.)
ARRAY (%)
MODULE DIMENSIONS = 69.09"X 40.86" = 19.60 SF
UNIT WEIGHT OF ARRAY = 2.19 PSF #1 18 352.88 538.66 65.51
(N) 30A FUSED AC DISCONNECT
ARRAY AREA & ROOF AREA CALC'S ROOF DESCRIPTION
(N) PRODUCTION METER (E) UTILITY METER ROOF TYPE
AREA OF ROOF(PLAN
AREA OF NEW ARRAY TOTAL ROOF AREA
VIEW) (N) 100A SOLAR LOAD CENTER ROOF SEAM
(Sq. Ft.) COVERED BY ARRAY % ROOF AZIMUTH PURELIGHT POWER
(Sq. Ft.) (E) 200A SPLIT BUS PANEL TILT SPACING 541 PARSONS DR.
352.88 3141.54 11% #1 04° 270° 8" O.C. MEDFORD, OR 97501

11% ROOF AREA (ARRAY <25% OF ROOF AREA) (N) 3/4" OR GREATER EMT CSLB : 226333
PHONE: (541) 816-4047
CONDUIT RUN (IN ATTIC) Email: [email protected]
12" FIRE PATHWAY
BILL OF MATERIALS VERSION

12"
DESCRIPTION DATE REV
EQUIPMENT QTY DESCRIPTION SLC PVM ACD UM

8"
INITIAL RELEASE 06/02/2022 UR
RAIL 09 UNIRAC SM LIGHT RAIL 168" DARK MSP
SPLICE 08 BND SPLICE BAR PRO SERIES DRK
MID CLAMP 34 SM PRO SERIES MID - DRK
END CLAMP 04 SM PRO SERIES UNIV END - MILL
ATTACHMENT 49 S-5! PROTEA BRACKET
GROUNDING LUG 01 GROUNDING LUG

TEAKWOOD DR
FRONT YARD
REAR YARD

ROOF #1
PROJECT NAME
TILT - 04°
AZIMUTH - 270°

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


PHOTOVOLTAIC MODULES

UTILITY: PACIFIC POWER


YINGLI SOLAR YL360D-34D1/2 (360W)
(N) JUNCTION BOX

HOWARD LEACHMAN
303 TEAKWOOD DR,
69.09"

APN# 10547110
62'-9"

JB

40.86"
(E) CORRUGATED METAL ROOF (TYP.)
12" FIRE PATHWAY

(N) (49) S-5! PROTEA BRACKET


ATTACHMENTS SPACED AT 24" & 48" O.C.

(N) UNIRAC SM LIGHT RAIL


LEGEND
(E) SEAM @ 8" O.C. (TYP.) UM - UTILITY METER
MSP - MAIN SERVICE PANEL

ROOF #1 ACD - AC DISCONNECT


(18) YINGLI SOLAR YL360D-34D1/2 SLC - SOLAR LOAD CENTER
(360W) SOLAR MODULES
PVM - PRODUCTION METER
JB - JUNCTION BOX
SHEET NAME

- CHIMNEY ROOF PLAN


8"

5'-9" WITH MODULES


8" 2'-0"
- VENT, ATTIC FAN
SHEET SIZE
(ROOF OBSTRUCTION)
- ROOF ATTACHMENT ANSI B
NOTE: ACTUAL ROOF CONDITIONS AND
- SEAM 11" X 17"
VISIBLE, LOCKABLE,LABELED AC DISCONNECT RAFTERS (OR SEAM) LOCATIONS MAY
ROOF PLAN WITH MODULES SHEET NUMBER

1
LOCATED WITHIN 10' OF UTILITY METER VARY. INSTALL PER MANUFACTURER(S) - CONDUIT
SCALE: 3/32" = 1'-0" NOTE: PV AC DISCONNECT LOCATED WITHIN
INSTALLATION GUIDELINES AND
ENGINEERED SPANS FOR ATTACHMENTS
- FIRE PATHWAY PV-2
10 FEET OF THE MAIN BILLING METER
RESERVED FOR AHJ
NOTE: ACTUAL ROOF CONDITIONS AND RAFTERS (OR SEAM)
LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S)
INSTALLATION GUIDELINES AND ENGINEERED SPANS FOR
ATTACHMENTS

PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
UNIRAC SM LIGHT RAIL Email: [email protected]

VERSION
PV MODULE
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

(E) CORRUGATED
METAL ROOF

PROJECT NAME
UNIRAC SM LIGHT RAIL

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


(N) S-5! PROTEA BRACKET

UTILITY: PACIFIC POWER


HOWARD LEACHMAN
303 TEAKWOOD DR,
ATTACHMENT

APN# 10547110
CORRUGATED
METAL ROOF
(N) END CLAMP (N) MID CLAMP

ENLARGE DETAIL PV MODULE

8" (TYP.)
SHEET NAME
2'-0" (TYP.)
CORRUGATED METAL ROOF ATTACHMENT
4'-0" (TYP.) DETAIL
SHEET SIZE

ANSI B
11" X 17"
1 SOLAR MODULE ATTACHMENT DETAIL SHEET NUMBER

PV-3 SCALE: NTS


PV-3
RESERVED FOR AHJ
(18) YINGLI SOLAR YL360D-34D1/2 (360W) MODULES
(04) HOYMILES HM-1200N MICRO-INVERTERS 12" FIRE PATHWAY
(01) HOYMILES HM-600N MICRO-INVERTER

12"
(01) BRANCH OF 12 MODULES &
(01) BRANCH OF 06 MODULES CONNECTED IN PARALLEL PER BRANCH

PHOTOVOLTAIC MODULES
YINGLI SOLAR YL360D-34D1/2 (360W)
69.09"
PURELIGHT POWER
541 PARSONS DR.

40.86"
MEDFORD, OR 97501
CSLB : 226333
ROOF #1 PHONE: (541) 816-4047
Email: [email protected]
(18) YINGLI SOLAR YL360D-34D1/2
(360W) MODULES VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

(04) HOYMILES HM-1200N


MICRO-INVERTERS

BRANCH #1
REAR YARD

TEAKWOOD DR
FRONT YARD
12" FIRE PATHWAY
PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
BRANCH #2

(01) HOYMILES HM-600N


MICRO-INVERTER

SHEET NAME

BRANCH LAYOUT

SHEET SIZE

ANSI B
11" X 17"
BRANCH LAYOUT
1
SHEET NUMBER

SCALE: 3/32" = 1'-0" PV-4


RESERVED FOR AHJ
(18) YINGLI SOLAR YL360D-34D1/2 (360W) MODULES BILL OF MATERIALS
(04) HOYMILES HM-1200N MICRO-INVERTERS EQUIPMENT QTY DESCRIPTION
(01) HOYMILES HM-600N MICRO-INVERTER SOLAR PV MODULE 18 YINGLI SOLAR YL360D-34D1/2 (360W) MODULES
(01) BRANCH OF 12 MODULES & INVERTER #1 04 HOYMILES HM-1200N MICRO-INVERTERS
(01) BRANCH OF 06 MODULES CONNECTED IN PARALLEL PER BRANCH INVERTER #2 01 HOYMILES HM-600N MICRO-INVERTER
600V, 55A MAX, 4 INPUTS, MOUNTED ON ROOF FOR WIRE & CONDUIT
JUNCTION BOX 01
TRANSITION
SYSTEM SIZE:- 18 x 360W/1000 = 6.48 kWDC
LOAD CENTER 01 100A SOLAR LOAD CENTER
SYSTEM SIZE:- 5.39 kWAC PURELIGHT POWER
PV METER 01 PRODUCTION METER 541 PARSONS DR.
MEDFORD, OR 97501
MINIMUM WIRE SIZES SPECIFIED.USE OF AC DISCONNECT 30A FUSED, VISIBLE, LOCKABLE, LABELED, CSLB : 226333
AC DISCONNECT 01 PHONE: (541) 816-4047
LARGER WIRE IS ACCEPTABLE DISCONNECT SQUARE-D D221NRB, WITH 30A FUSES, 240 VAC Email: [email protected]

VERSION
DESCRIPTION DATE REV

AC DISCONNECT SHALL BE LOCATED BI-DIRECTIONAL INITIAL RELEASE 06/02/2022 UR


WITHIN 10 FEET OF UTILITY METER ONCOR METER
1-PHASE, 3-W,
120V/240V, 60Hz

3 x HOYMILES HM-1200N MICRO-INVERTERS WITH 12 PV MODULES IN BRANCH CIRCUIT


#1

(N) 100A SOLAR LOAD


CENTER SUPPLY SIDE TAP
(03) HOYMILES HM-1200N
MICRO-INVERTERS (240V)
(N) JUNCTION (E) 200A SPLIT BUS
1 x HOYMILES HM-1200N MICRO-INVERTER WITH 04 PV MODULES & BOX (N) AC DISCONNECT 30A PANEL,120/240V
(N) PV
1 x HOYMILES HM-600N MICRO-INVERTER WITH 02 PV MODULES IN BRANCH CIRCUIT #1 PRODUCTION
FUSED, VISIBLE LOCKABLE
LABELED, SQUARE-D
L1 L1 METER
20A D221NRB WITH
L2 L2
LINE 30A FUSES, 240 VAC PROJECT NAME
20A

EAGLE POINT, OR 97524 USA


L1 L1 M 30A FUSES

AHJ: CITY OF EAGLE POINT


L2 L2 L1 L1

UTILITY: PACIFIC POWER


G L2 L2
LOAD

HOWARD LEACHMAN
303 TEAKWOOD DR,
N N
(01) HOYMILES HM-1200N
(01) HOYMILES HM-600N G
MICRO-INVERTER (240V) G N
MICRO-INVERTER (240V)

APN# 10547110
TERMINATOR CAP ON LAST CABLE NG BOND
CONNECTOR AC TRUNK CABLE (TYP)

(2) TRUNK CABLE (3) #10 AWG THWN-2


#6 BARE CU IN FREE AIR
(1) #10 AWG THWN-2 EGC
IN 3/4" EMT CONDUIT RUN (3) #6 AWG THWN-2 EXISTING
(2) #10 AWG THWN-2 + RED IN 1" EMT CONDUIT RUN GROUNDING
(2) #10 AWG THWN-2 - BLACK
#6 BARE CU GND IN FREE AIR SYSTEM
(1) #10 AWG THWN-2 GND
IN 3/4" EMT CONDUIT RUN IRREVERSIBLE CRIMP MADE
TO GROUNDING SYSTEM

DISCONNECT NOTES:
1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH VISIBLE, LOCKABLE,LABELED
IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS AC DISCONNECT LOCATED
MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) WITHIN 10' OF UTILITY METER
2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY
INTERCONNECTION NOTES: PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH. NOTE: PV AC DISCONNECT LOCATED SHEET NAME
1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE 3. FUSED AC DISCONNECT TO BE USED. WITHIN 10’ OF THE MAIN BILLING METER
DETERMINED IN ACCORDANCE WITH [NEC 705.12], AND [NEC 690.54]. ELECTRICAL
GROUNDING & GENERAL NOTES:
3. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9],
1. A SECOND FACILITY GROUNDING ELECTRODE IS NOT REQUIRED PER [NEC 690.47(C)(3)]
SERVICE INFO. LINE DIAGRAM
[NEC 230.95] AND [NEC 690.4]
4. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. 2. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE. UTILITY PROVIDER: PACIFIC POWER SHEET SIZE
3. DC GEC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTING ELECTRODE
5. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE
4. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS
MAIN SERVICE VOLTAGE: 240V ANSI B
BUSBAR RELATIVE TO THE MAIN BREAKER. MAIN PANEL BRAND: CUTLER-HAMMER
FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. 11" X 17"
5. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE MAIN SERVICE PANEL: (E) 200A
ELECTRICAL LINE DIAGRAM SHEET NUMBER

1 SCALE: NTS
FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS.
6. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER
AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT.
MAIN SERVICE LOCATION:
SERVICE FEED SOURCE:
NORTH
UNDERGROUND PV-5
RESERVED FOR AHJ
SOLAR MODULE SPECIFICATIONS AC CONDUCTOR AMPACITY CALCULATIONS: AC CONDUCTOR AMPACITY CALCULATIONS:
YINGLI SOLAR YL360D-34D1/2 FROM JUNCTION BOX TO SOLARLOADCENTER: FROMACDISCONNECTTOINTERCONNECTION:
MANUFACTURER / MODEL #
(360W)MODULES # OF INVERTERS: 05 (04- HOYMILES HM-1200N + 01-HOYMILES HM-600N)
EXPECTED WIRE TEMP (°C): 36°
VMP 33.65V TEMP CORRECTION PER TABLE 310.15(B)(1): 0.91 EXPECTED WIRE TEMP (°C): 36°
# OF CURRENT CARRYING CONDUCTORS: 4 TEMP CORRECTION PER TABLE 310.15(B)(1): 0.91
IMP 10.70A # OF CURRENT CARRYING CONDUCTORS: 3
CONDUIT FILL CORRECTION PER NEC 310.15(C)(1): 0.80
VOC 40.85V CIRCUIT CONDUCTOR SIZE: 10 AWG CONDUIT FILL PER NEC 310.15(C)(1): 1.0
ISC 11.19A CIRCUIT CONDUCTOR AMPACITY: 40A CIRCUIT CONDUCTOR SIZE: 6 AWG
CIRCUIT CONDUCTOR AMPACITY: 65A
MODULE DIMENSION 69.09"L x 40.86"W x 1.38"D (In Inch)
REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): PURELIGHT POWER
1.25 X # MICRO-INVERTERS (MAX. BRANCH LENGTH) X MAX OUTPUT REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B): 541 PARSONS DR.
INVERTER SPECIFICATIONS 1.25 X # MICRO-INVERTERS X MAX OUTPUT CURRENT = MEDFORD, OR 97501
CURRENT CSLB : 226333
MANUFACTURER / MODEL # HOYMILES HM-1200N 1.25 X 3 X 5A = 18.75A 1.25 X ((04 X 5A) + (01 x 2.46A)) = 28.08A PHONE: (541) 816-4047
Email: [email protected]
NOMINAL AC POWER 1200W
DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE DERATEDAMPACITYOFCIRCUITCONDUCTORSPERNECTABLE310.16: VERSION
NOMINAL OUTPUT VOLTAGE 240 VAC TEMP CORR. PER NEC TABLE 310.15(B)(1) X DESCRIPTION DATE REV
310.15(B)(1)
NOMINAL OUTPUT CURRENT 5A TEMP CORR. PER NEC TABLE 310.15(B)(1) X CONDUIT FILL CORR. PER NEC 310.15(C)(1) X INITIAL RELEASE 06/02/2022 UR

CONDUIT FILL CORR. PER NEC 310.15(C)(1) X CIRCUIT CONDUCTOR AMPACITY =


CIRCUIT CONDUCTOR AMPACITY = 0.91 X 1.0 X 75 = 68.25A
INVERTER SPECIFICATIONS
0.91 X 0.80 X 40 = 29.12A RESULT SHOULD BE GREATER THAN (28.08A) OTHERWISE LESS THE
MANUFACTURER / MODEL # HOYMILES HM-600N ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY
NOMINAL AC POWER 590W RESULT SHOULD BE GREATER THAN (18.75A) OTHERWISE LESS THE

NOMINAL OUTPUT VOLTAGE 240 VAC


ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY ELECTRICAL NOTES
NOMINAL OUTPUT CURRENT 2.46A 1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED
AC CONDUCTOR AMPACITY CALCULATIONS: FOR ITS APPLICATION.
2.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90
AMBIENT TEMPERATURE SPECS
FROMSOLARLOADCENTERTO ACDISCONNECT: DEGREE C WET ENVIRONMENT.
# OF INVERTERS: 05 (04- HOYMILES HM-1200N + 01-HOYMILES HM-600N) 3.) WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL
WEATHER STATION: MEDFORD ROGUE VALLEY INTL AP
EXPECTED WIRE TEMP (°C): 36° BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO
RECORD LOW TEMP -8° TEMP CORRECTION PER TABLE 310.15(B)(1): 0.91 THE NEAREST RIDGE, HIP, OR VALLEY.
AMBIENT TEMP (HIGH TEMP 2%) 36° # OF CURRENT CARRYING CONDUCTORS: 3 4.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING PROJECT NAME
CONDUIT HEIGHT RUN IN ATTIC
CONDUIT FILL PER NEC 310.15(C)(1): 1.0 ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26.

EAGLE POINT, OR 97524 USA


CIRCUIT CONDUCTOR SIZE: 10 AWG 5.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS.

AHJ: CITY OF EAGLE POINT


CONDUCTOR TEMPERATURE RATE 90° CIRCUIT CONDUCTOR AMPACITY: 35A CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS,

UTILITY: PACIFIC POWER


MODULE TEMPERATURE COEFFICIENT OF Voc -0.29%/°C SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE

HOWARD LEACHMAN
303 TEAKWOOD DR,
REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B): CODES AND STANDARDS.
1.25 X # MICRO-INVERTERS X MAX OUTPUT CURRENT = 6.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE
NUMBER OF CURRENT

APN# 10547110
PERCENT OF VALUES 1.25 X ((04 X 5A) + (01 x 2.46A)) = 28.08A NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY.
CARRYING CONDUCTORS IN EMT
.80 4-6 7.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND
DERATEDAMPACITYOFCIRCUITCONDUCTORSPERNECTABLE310.16: READILY VISIBLE.
.70 7-9 TEMP CORR. PER NEC TABLE 310.15(B)(1) X 8.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE
.50 10-20 CONDUIT FILL CORR. PER NEC 310.15(C)(1) X FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP
CIRCUIT CONDUCTOR AMPACITY = MANUFACTURER'S INSTRUCTION.
0.91 X 1.0 X 40 = 36.4A 9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER
RESULT SHOULD BE GREATER THAN (28.08A) OTHERWISE LESS THE G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.
ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY 10.) THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE

VOLTAGE DROP CALCULATIONS


WIRE RUN # OF INV V (VOLTS) I (AMPS) L (FT) VD (%) WIRE SIZE* RACEWAY
SHEET NAME
BRANCH (MODULE) TO PASS THRU J. BOX 3 240 15.00 40 0.87% 12 AWG FREE AIR
ELECTRICAL
PASS THRU SOLAR J. BOX TO LOAD CENTER
(MAX BRANCH) 3 240 15.00 50 0.65% 10 AWG 3/4" EMT CALCULATION
LOAD CENTER TO AC DISCONNECT 5 240 22.46 10 0.19% 10 AWG 3/4" EMT SHEET SIZE

AC DISCONNECT TO INTERCONNECTION 5 240 22.46 10 0.08% 6 AWG 1" EMT ANSI B


MAX VOLTAGE DROP: 1.79% 11" X 17"
ELECTRICAL CALCULATION SHEET NUMBER

1 SCALE: NTS PV-6


RESERVED FOR AHJ
PHOTOVOLTAIC SYSTEM
! WARNING ! AC DISCONNECT !
ELECTRICAL SHOCK HAZARD ELECTRIC SHOCK HAZARD
SOLAR PV SYSTEM EQUIPPED
RATED AC OUTPUT CURRENT 22.46A WITH RAPID SHUTDOWN
TERMINALSONLINEANDLOAD NOMINAL OPERATING CURRENT 240V
SIDESMAYBEENERGIZEDIN LABEL LOCATION:
THEOPENPOSITION AC DISCONNECT, PHOTOVOLTAIC SYSTEM TURNRAPIDSHUTDOWN PURELIGHT POWER
POINT OF INTERCONNECTION SWITCHTOTHE"OFF" 541 PARSONS DR.
LABEL LOCATION: SOLAR ELECTRIC MEDFORD, OR 97501
INVERTER(S), AC DISCONNECT(S), AC (PER CODE: NEC 2020.690.54 POSITIONTOSHUTDOWN PV PANELS
CSLB : 226333
COMBINER PANEL (IF APPLICABLE). PHONE: (541) 816-4047
PVSYSTEMANDREDUCE Email: [email protected]
PER CODE(S): NEC 2020: NEC 706.15
(C)(4) & NEC 690.13(B) SHOCKHAZARDINTHE VERSION
ARRAY. DESCRIPTION DATE REV

RAPID SHUTDOWN INITIAL RELEASE 06/02/2022 UR

PHOTOVOLTAIC
FOR SOLAR PV LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE
SYSTEM SERVICE DISCONNECTING MEANS TO WHICH THE
PV SYSTEMS ARE CONNECTED.
AC DISCONNECT LABEL LOCATION:
UTILITY SERVICE ENTRANCE/METER, INVERTER/DC
PER CODE: NEC 2020 : IFC 605.11.3.1(1) & 690.56(C)

LABEL LOCATION: DISCONNECT IF REQUIRED BY LOCAL AHJ, OR


OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.
AC DISCONNECT PER CODE(S): NEC 2020: 690.56(C)(2)
NEC 690.13(B)
PARALLEL
GENERATION ON SITE
PHOTOVOLTAICPOWERSOURCE
! WARNING DUALPOWERSOURCE
SECONDSOURCEISPHOTOVOLTAICSYSTEM LABEL LOCATION:
LOCATION: AT UTILITY SERVICE METER
PROJECT NAME
EMT/CONDUIT RACEWAYS
LABEL LOCATION:

EAGLE POINT, OR 97524 USA


(PER CODE: NEC690.31(D)(2)
POINT OF INTERCONNECTION

AHJ: CITY OF EAGLE POINT


PRODUCTION METER

! WARNING

UTILITY: PACIFIC POWER


NEC 705.12(3)(3) & NEC 690.59)

HOWARD LEACHMAN
303 TEAKWOOD DR,
PHOTOVOLTAIC SYSTEM

APN# 10547110
COMBINER PANEL
! WARNING
INVERTEROUTPUTCONNECTION
DO NOT ADD LOADS
DO NOT RELOCATE THIS MAIN PHOTOVOLTAIC NEC 690.15(B) : AC COMBINER PANEL
OVERCURRENT DEVICE SYSTEM DISCONNECT
LABEL LOCATION:
SERVICE PANEL IF SUM OF BREAKERS EXCEEDS PANEL RATING
PER CODE(S): NEC 705.12 (B)(3)(2)
LABEL LOCATION:
MAIN SERVICE DISCONNECT / UTILITY METER
(PER CODE: NEC 690.13(B))
! WARNING
DUAL POWER SUPPLY
NOTES AND SPECIFICATIONS:
SOURCES : UTILITY GRID
· SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE ! WARNING
2020 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS AND PV SOLAR
ARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THE
LOCAL AHJ. ELECTRIC SYSTEM SHEET NAME
· SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS THIS EQUIPMENT FED BY
USING EFFECTIVE WORDS, COLORS AND SYMBOLS. MULTIPLE SOURCES TOTAL
· LABELS SHALL BE PERMANENTLY AFFIXED TO THE RATING OF ALL OVERCURRENT
NEC 705.12(B)(3) : MAIN SERVICE PANEL WARNING LABELS
EQUIPMENT OR WIRING METHOD AND SHALL NOT BE HAND DEVICES EXCLUDING MAIN POWER
WRITTEN. SHEET SIZE
SUPPLY SHALL NOT EXCEED
· LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND
THE ENVIRONMENT INVOLVED.
AMPACITY OF BUSBAR ANSI B
· SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, 11" X 17"
PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE
LABEL LOCATION: SHEET NUMBER
SPECIFIED. POINTS OF CONNECTION/BREAKER
· DO NOT COVER EXISTING MANUFACTURER LABELS. CODE: NEC 705.12(B)(3)(3)
PV-7
CAUTION !
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN
AT: SPLIT BUS PANEL, UTILITY METER &
AC DISCONNECT

(N) PV MODULES

303 TEAKWOOD DR

(E) 200A SPLIT BUS PANEL (N) 30A FUSED AC DISCONNECT

(E) UTILITY METER


RESERVED FOR AHJ
1. EACH MODULE TO BE GROUNDED USING THE SUPPLIED CONNECTION POINT PER
MANUFACTURER'S REQUIREMENTS. ALL SOLAR MODULES, EQUIPMENT, AND METALLIC
COMPONENTS ARE TO BE BONDED. IF THE EXISTING GROUNDING ELECTRODE SYSTEM CAN
NOT BE VERIFIED OR IS ONLY METALLIC WATER PIPING, IT IS THE CONTRACTOR'S
RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE.
PURELIGHT POWER
2. ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF NATIONAL ELECTRICAL 541 PARSONS DR.
MEDFORD, OR 97501
CODE. LABEL SHALL BE METALLIC OR PLASTIC, ENGRAVED OR CSLB : 226333
PHONE: (541) 816-4047
MACHINE PRINTED IN A CONTRASTING COLOR TO THE PLAQUE. PLAQUE SHALL Email: [email protected]

BE UV RESISTANT IF EXPOSED TO SUNLIGHT. VERSION


DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR


3. DC CONDUCTORS SHALL BE RUN IN EMT AND SHALL BE LABELED, "CAUTION DC CIRCUIT" OR
EQUIV. EVERY 5 FT.

4. EXPOSED NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE


GROUNDED IN ACCORDANCE WITH 250.134 OR 250.138(A).

5. CONFIRM LINE SIDE VOLTAGE AT ELECTRIC UTILITY SERVICE PRIOR TO CONNECTING INVERTER.
VERIFY SERVICE VOLTAGE IS WITHIN INVERTER VOLTAGE OPERATIONAL RANGE.

6. OUTDOOR EQUIPMENT SHALL BE NEMA-3R RATED OR BETTER.

PROJECT NAME
7. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT EXPANSION JOINTS AND ANCHOR CONDUIT

EAGLE POINT, OR 97524 USA


RUNS AS REQUIRED PER NEC.

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
8. ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED

303 TEAKWOOD DR,


AND LISTED FOR SUCH USE, AND FOR ROOF-MOUNTED SYSTEMS, WIRING MUST BE

APN# 10547110
PERMANENTLY AND COMPLETELY HELP OFF OF THE ROOF SURFACE. NEC 110.2 - 110.4 / 300.4

9. ALL ROOF PENETRATIONS MUST BE FLASHED. SIMPLY CAULKING DOES NOT SUFFICE.

SHEET NAME

ADDITIONAL
NOTES
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-8
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-9
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-10
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-11
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-12
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-13
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS
SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-14
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-15
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-16
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-17
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]

VERSION
DESCRIPTION DATE REV

INITIAL RELEASE 06/02/2022 UR

PROJECT NAME

EAGLE POINT, OR 97524 USA

AHJ: CITY OF EAGLE POINT


UTILITY: PACIFIC POWER
HOWARD LEACHMAN
303 TEAKWOOD DR,

APN# 10547110
SHEET NAME

SPEC SHEETS

SHEET SIZE

ANSI B
11" X 17"
SHEET NUMBER

PV-18