Hoy Miles
Hoy Miles
(N) 30A FUSED AC DISCONNECT WIND EXPOSURE:- B PV-5 ELECTRICAL LINE DIAGRAM VERSION
(N) 100A SOLAR LOAD CENTER RISK CATEGORY:- II PV-6 ELECTRICAL CALCULATION DESCRIPTION DATE REV
(N) PRODUCTION METER OCCUPANCY: R-3 RESIDENTIAL PV-7 WARNING LABELS INITIAL RELEASE 06/02/2022 UR
PV-7.1 PLACARD
PV-8 ADDITIONAL NOTES
PV-9+ EQUIPMENT SPEC SHEETS
GENERAL NOTES:
1. PV SYSTEMS AND SUPPORTING STRUCTURE SHALL COMPLY
WITH REQUIREMENTS OF 2021 OESC & 2019 OSSC.
2. 3111.3.2 - PV RACKING AND ATTACHMENTS SHALL BE UL 1703
CERTIFIED. ARRAY LOCATION
3. 3111.3.4 - PV SYSTEM SHALL HAVE A FIRE CLASSIFICATION
THAT IS EQUAL TO OR GREATER THAN THE ROOF ASSEMBLY
PROJECT NAME
REQUIRED BY OSSC SECTION 1505.1.
HOWARD LEACHMAN
· 36" WIDE PATHWAY SHALL NOT BE REQUIRED ON
APN# 10547110
INSTALLED ON A ROOF WITH A SLOPE THAT EXCEEDS 2:12 AND
WITH AN INTERSECTING ADJACENT ROOF AND WHERE NO
SECTION IS LARGER THAN 150 FEET MEASURED IN LENGTH OR
WIDTH.
· WHERE PV ARRAY DOES NOT EXCEED 25% AS MEASURED IN
PLAN VIEW OF TOTAL ROOF AREA OF A STRUCTURE, A
MINIMUM OF 12" UNOBSTRUCTED PATHWAY SHALL BE
MAINTAINED ALONG EACH SIDE OF ANY HORIZONTAL RIDGE.
· WHERE THE SOLAR ARRAY EXCEEDS 25% AS MEASURED IN
PLAN VIEW OF TOTAL ROOF AREA OF THE STRUCTURE, A
MINIMUM OF ONE 36" UNOBSTRUCTED PATHWAY SHALL BE
PROVIDED IN ADDITION TO A MINIMUM 12" UNOBSTRUCTED
ALONG EA. SIDE OF ANY HORIZONTAL RIDGE.
6. ROOF STRUCTURE IS CONVENTIONAL LIGHT FRAMED WOOD
CONSTRUCTION WITH SEAM @ 8" O.C. REFER TO ALLOWABLE
SPAN REQUIREMENTS IN TABLE 305.4.1.
7. 3111.4.8.5.1 - DISCONNECTS, J-BOXES, COMBINER BOXES OR
GUTTERS SHALL NOT BE PLACED IN ANY REQUIRED PATHWAY SHEET NAME
OR CUTOUT.
8. PV MODULES AND RACKING SHALL BE DIRECTLY ATTACHED TO COVER SHEET
ROOF FRAMING AS SHOWN IN PV-2. WHEN ATTACHMENT
LOCATED WITHIN 3' OF ROOF EDGE, HIP, EAVE, RIDGE SHALL
SHEET SIZE
BE 24" O.C. MAX.
9. 3111.5.4 - MAX MODULE HEIGHT < 18" OFF ROOF SURFACE. ANSI B
11" X 17"
1 AERIAL PHOTO 2 VICINITY MAP SHEET NUMBER
PV-0 SCALE: NTS PV-0 SCALE: NTS
PV-0
ROOF ACCESS POINT SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE
VERSION
PROPE
10'-4"
SLC PVM ACD UM
MSP
R
TY LINE
EXISTING
88'-11" DRIVEWAY
TEAKWOOD DR
~80.85'
~80.30'
26'-10" PROJECT NAME
JB
HOWARD LEACHMAN
303 TEAKWOOD DR,
APN# 10547110
E
RTY LIN
PROPE
5'-8"
PROPERTY LINE
~176.34'
(E) TREES (TYP.)
(E) FENCE
(E) STRUCTURE (TYP.) (N) JUNCTION BOX SHEET NAME
ANSI B
11" X 17"
SHEET NUMBER
SITE PLAN WITH ROOF PLAN
1 SCALE: 1/16" = 1'-0"
PV-1
RESERVED FOR AHJ
MODULE TYPE, DIMENSIONS & WEIGHT ARRAY AREA & ROOF AREA CALC'S
NUMBER OF MODULES = 18 MODULES ROOF
ARRAY ROOF
MODULE TYPE = YINGLI SOLAR YL360D-34D1/2 (360W) MODULES # OF AREA AREA
AREA
ROOF COVERED BY
MODULE WEIGHT = 42.99 LBS / 19.5 KG. MODULES (Sq. Ft.) (Sq. Ft.)
ARRAY (%)
MODULE DIMENSIONS = 69.09"X 40.86" = 19.60 SF
UNIT WEIGHT OF ARRAY = 2.19 PSF #1 18 352.88 538.66 65.51
(N) 30A FUSED AC DISCONNECT
ARRAY AREA & ROOF AREA CALC'S ROOF DESCRIPTION
(N) PRODUCTION METER (E) UTILITY METER ROOF TYPE
AREA OF ROOF(PLAN
AREA OF NEW ARRAY TOTAL ROOF AREA
VIEW) (N) 100A SOLAR LOAD CENTER ROOF SEAM
(Sq. Ft.) COVERED BY ARRAY % ROOF AZIMUTH PURELIGHT POWER
(Sq. Ft.) (E) 200A SPLIT BUS PANEL TILT SPACING 541 PARSONS DR.
352.88 3141.54 11% #1 04° 270° 8" O.C. MEDFORD, OR 97501
11% ROOF AREA (ARRAY <25% OF ROOF AREA) (N) 3/4" OR GREATER EMT CSLB : 226333
PHONE: (541) 816-4047
CONDUIT RUN (IN ATTIC) Email: [email protected]
12" FIRE PATHWAY
BILL OF MATERIALS VERSION
12"
DESCRIPTION DATE REV
EQUIPMENT QTY DESCRIPTION SLC PVM ACD UM
8"
INITIAL RELEASE 06/02/2022 UR
RAIL 09 UNIRAC SM LIGHT RAIL 168" DARK MSP
SPLICE 08 BND SPLICE BAR PRO SERIES DRK
MID CLAMP 34 SM PRO SERIES MID - DRK
END CLAMP 04 SM PRO SERIES UNIV END - MILL
ATTACHMENT 49 S-5! PROTEA BRACKET
GROUNDING LUG 01 GROUNDING LUG
TEAKWOOD DR
FRONT YARD
REAR YARD
ROOF #1
PROJECT NAME
TILT - 04°
AZIMUTH - 270°
HOWARD LEACHMAN
303 TEAKWOOD DR,
69.09"
APN# 10547110
62'-9"
JB
40.86"
(E) CORRUGATED METAL ROOF (TYP.)
12" FIRE PATHWAY
1
LOCATED WITHIN 10' OF UTILITY METER VARY. INSTALL PER MANUFACTURER(S) - CONDUIT
SCALE: 3/32" = 1'-0" NOTE: PV AC DISCONNECT LOCATED WITHIN
INSTALLATION GUIDELINES AND
ENGINEERED SPANS FOR ATTACHMENTS
- FIRE PATHWAY PV-2
10 FEET OF THE MAIN BILLING METER
RESERVED FOR AHJ
NOTE: ACTUAL ROOF CONDITIONS AND RAFTERS (OR SEAM)
LOCATIONS MAY VARY. INSTALL PER MANUFACTURER(S)
INSTALLATION GUIDELINES AND ENGINEERED SPANS FOR
ATTACHMENTS
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
UNIRAC SM LIGHT RAIL Email: [email protected]
VERSION
PV MODULE
DESCRIPTION DATE REV
(E) CORRUGATED
METAL ROOF
PROJECT NAME
UNIRAC SM LIGHT RAIL
APN# 10547110
CORRUGATED
METAL ROOF
(N) END CLAMP (N) MID CLAMP
8" (TYP.)
SHEET NAME
2'-0" (TYP.)
CORRUGATED METAL ROOF ATTACHMENT
4'-0" (TYP.) DETAIL
SHEET SIZE
ANSI B
11" X 17"
1 SOLAR MODULE ATTACHMENT DETAIL SHEET NUMBER
12"
(01) BRANCH OF 12 MODULES &
(01) BRANCH OF 06 MODULES CONNECTED IN PARALLEL PER BRANCH
PHOTOVOLTAIC MODULES
YINGLI SOLAR YL360D-34D1/2 (360W)
69.09"
PURELIGHT POWER
541 PARSONS DR.
40.86"
MEDFORD, OR 97501
CSLB : 226333
ROOF #1 PHONE: (541) 816-4047
Email: [email protected]
(18) YINGLI SOLAR YL360D-34D1/2
(360W) MODULES VERSION
DESCRIPTION DATE REV
BRANCH #1
REAR YARD
TEAKWOOD DR
FRONT YARD
12" FIRE PATHWAY
PROJECT NAME
APN# 10547110
BRANCH #2
SHEET NAME
BRANCH LAYOUT
SHEET SIZE
ANSI B
11" X 17"
BRANCH LAYOUT
1
SHEET NUMBER
VERSION
DESCRIPTION DATE REV
HOWARD LEACHMAN
303 TEAKWOOD DR,
N N
(01) HOYMILES HM-1200N
(01) HOYMILES HM-600N G
MICRO-INVERTER (240V) G N
MICRO-INVERTER (240V)
APN# 10547110
TERMINATOR CAP ON LAST CABLE NG BOND
CONNECTOR AC TRUNK CABLE (TYP)
DISCONNECT NOTES:
1. DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH VISIBLE, LOCKABLE,LABELED
IS OPENED THE CONDUCTORS REMAINING LIVE ARE CONNECTED TO THE TERMINALS AC DISCONNECT LOCATED
MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS) WITHIN 10' OF UTILITY METER
2. AC DISCONNECT MUST BE ACCESSIBLE TO QUALIFIED UTILITY
INTERCONNECTION NOTES: PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH. NOTE: PV AC DISCONNECT LOCATED SHEET NAME
1. INTERCONNECTION SIZING, LIMITATIONS AND COMPLIANCE 3. FUSED AC DISCONNECT TO BE USED. WITHIN 10’ OF THE MAIN BILLING METER
DETERMINED IN ACCORDANCE WITH [NEC 705.12], AND [NEC 690.54]. ELECTRICAL
GROUNDING & GENERAL NOTES:
3. GROUND FAULT PROTECTION IN ACCORDANCE WITH [NEC 215.9],
1. A SECOND FACILITY GROUNDING ELECTRODE IS NOT REQUIRED PER [NEC 690.47(C)(3)]
SERVICE INFO. LINE DIAGRAM
[NEC 230.95] AND [NEC 690.4]
4. ALL EQUIPMENT TO BE RATED FOR BACKFEEDING. 2. PV INVERTER IS UNGROUNDED, TRANSFORMER-LESS TYPE. UTILITY PROVIDER: PACIFIC POWER SHEET SIZE
3. DC GEC AND AC EGC TO REMAIN UNSPLICED, OR SPLICED TO EXISTING ELECTRODE
5. PV BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE
4. ANY EXISTING WIRING INVOLVED WITH PV SYSTEM CONNECTION THAT IS
MAIN SERVICE VOLTAGE: 240V ANSI B
BUSBAR RELATIVE TO THE MAIN BREAKER. MAIN PANEL BRAND: CUTLER-HAMMER
FOUND TO BE INADEQUATE PER CODE SHALL BE CORRECTED PRIOR TO FINAL INSPECTION. 11" X 17"
5. JUNCTION BOX QUANTITIES, AND PLACEMENT SUBJECT TO CHANGE IN THE MAIN SERVICE PANEL: (E) 200A
ELECTRICAL LINE DIAGRAM SHEET NUMBER
1 SCALE: NTS
FIELD - JUNCTION BOXES DEPICTED ON ELECTRICAL DIAGRAM REPRESENT WIRE TYPE TRANSITIONS.
6. AC DISCONNECT NOTED IN EQUIPMENT SCHEDULE OPTIONAL IF OTHER
AC DISCONNECTING MEANS IS LOCATED WITHIN 10' OF SERVICE DISCONNECT.
MAIN SERVICE LOCATION:
SERVICE FEED SOURCE:
NORTH
UNDERGROUND PV-5
RESERVED FOR AHJ
SOLAR MODULE SPECIFICATIONS AC CONDUCTOR AMPACITY CALCULATIONS: AC CONDUCTOR AMPACITY CALCULATIONS:
YINGLI SOLAR YL360D-34D1/2 FROM JUNCTION BOX TO SOLARLOADCENTER: FROMACDISCONNECTTOINTERCONNECTION:
MANUFACTURER / MODEL #
(360W)MODULES # OF INVERTERS: 05 (04- HOYMILES HM-1200N + 01-HOYMILES HM-600N)
EXPECTED WIRE TEMP (°C): 36°
VMP 33.65V TEMP CORRECTION PER TABLE 310.15(B)(1): 0.91 EXPECTED WIRE TEMP (°C): 36°
# OF CURRENT CARRYING CONDUCTORS: 4 TEMP CORRECTION PER TABLE 310.15(B)(1): 0.91
IMP 10.70A # OF CURRENT CARRYING CONDUCTORS: 3
CONDUIT FILL CORRECTION PER NEC 310.15(C)(1): 0.80
VOC 40.85V CIRCUIT CONDUCTOR SIZE: 10 AWG CONDUIT FILL PER NEC 310.15(C)(1): 1.0
ISC 11.19A CIRCUIT CONDUCTOR AMPACITY: 40A CIRCUIT CONDUCTOR SIZE: 6 AWG
CIRCUIT CONDUCTOR AMPACITY: 65A
MODULE DIMENSION 69.09"L x 40.86"W x 1.38"D (In Inch)
REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): PURELIGHT POWER
1.25 X # MICRO-INVERTERS (MAX. BRANCH LENGTH) X MAX OUTPUT REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B): 541 PARSONS DR.
INVERTER SPECIFICATIONS 1.25 X # MICRO-INVERTERS X MAX OUTPUT CURRENT = MEDFORD, OR 97501
CURRENT CSLB : 226333
MANUFACTURER / MODEL # HOYMILES HM-1200N 1.25 X 3 X 5A = 18.75A 1.25 X ((04 X 5A) + (01 x 2.46A)) = 28.08A PHONE: (541) 816-4047
Email: [email protected]
NOMINAL AC POWER 1200W
DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE DERATEDAMPACITYOFCIRCUITCONDUCTORSPERNECTABLE310.16: VERSION
NOMINAL OUTPUT VOLTAGE 240 VAC TEMP CORR. PER NEC TABLE 310.15(B)(1) X DESCRIPTION DATE REV
310.15(B)(1)
NOMINAL OUTPUT CURRENT 5A TEMP CORR. PER NEC TABLE 310.15(B)(1) X CONDUIT FILL CORR. PER NEC 310.15(C)(1) X INITIAL RELEASE 06/02/2022 UR
HOWARD LEACHMAN
303 TEAKWOOD DR,
REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B): CODES AND STANDARDS.
1.25 X # MICRO-INVERTERS X MAX OUTPUT CURRENT = 6.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE
NUMBER OF CURRENT
APN# 10547110
PERCENT OF VALUES 1.25 X ((04 X 5A) + (01 x 2.46A)) = 28.08A NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY.
CARRYING CONDUCTORS IN EMT
.80 4-6 7.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND
DERATEDAMPACITYOFCIRCUITCONDUCTORSPERNECTABLE310.16: READILY VISIBLE.
.70 7-9 TEMP CORR. PER NEC TABLE 310.15(B)(1) X 8.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE
.50 10-20 CONDUIT FILL CORR. PER NEC 310.15(C)(1) X FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP
CIRCUIT CONDUCTOR AMPACITY = MANUFACTURER'S INSTRUCTION.
0.91 X 1.0 X 40 = 36.4A 9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER
RESULT SHOULD BE GREATER THAN (28.08A) OTHERWISE LESS THE G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG.
ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY 10.) THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE
PHOTOVOLTAIC
FOR SOLAR PV LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE
SYSTEM SERVICE DISCONNECTING MEANS TO WHICH THE
PV SYSTEMS ARE CONNECTED.
AC DISCONNECT LABEL LOCATION:
UTILITY SERVICE ENTRANCE/METER, INVERTER/DC
PER CODE: NEC 2020 : IFC 605.11.3.1(1) & 690.56(C)
! WARNING
HOWARD LEACHMAN
303 TEAKWOOD DR,
PHOTOVOLTAIC SYSTEM
APN# 10547110
COMBINER PANEL
! WARNING
INVERTEROUTPUTCONNECTION
DO NOT ADD LOADS
DO NOT RELOCATE THIS MAIN PHOTOVOLTAIC NEC 690.15(B) : AC COMBINER PANEL
OVERCURRENT DEVICE SYSTEM DISCONNECT
LABEL LOCATION:
SERVICE PANEL IF SUM OF BREAKERS EXCEEDS PANEL RATING
PER CODE(S): NEC 705.12 (B)(3)(2)
LABEL LOCATION:
MAIN SERVICE DISCONNECT / UTILITY METER
(PER CODE: NEC 690.13(B))
! WARNING
DUAL POWER SUPPLY
NOTES AND SPECIFICATIONS:
SOURCES : UTILITY GRID
· SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE ! WARNING
2020 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS AND PV SOLAR
ARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THE
LOCAL AHJ. ELECTRIC SYSTEM SHEET NAME
· SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS THIS EQUIPMENT FED BY
USING EFFECTIVE WORDS, COLORS AND SYMBOLS. MULTIPLE SOURCES TOTAL
· LABELS SHALL BE PERMANENTLY AFFIXED TO THE RATING OF ALL OVERCURRENT
NEC 705.12(B)(3) : MAIN SERVICE PANEL WARNING LABELS
EQUIPMENT OR WIRING METHOD AND SHALL NOT BE HAND DEVICES EXCLUDING MAIN POWER
WRITTEN. SHEET SIZE
SUPPLY SHALL NOT EXCEED
· LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND
THE ENVIRONMENT INVOLVED.
AMPACITY OF BUSBAR ANSI B
· SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, 11" X 17"
PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE
LABEL LOCATION: SHEET NUMBER
SPECIFIED. POINTS OF CONNECTION/BREAKER
· DO NOT COVER EXISTING MANUFACTURER LABELS. CODE: NEC 705.12(B)(3)(3)
PV-7
CAUTION !
POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN
AT: SPLIT BUS PANEL, UTILITY METER &
AC DISCONNECT
(N) PV MODULES
303 TEAKWOOD DR
5. CONFIRM LINE SIDE VOLTAGE AT ELECTRIC UTILITY SERVICE PRIOR TO CONNECTING INVERTER.
VERIFY SERVICE VOLTAGE IS WITHIN INVERTER VOLTAGE OPERATIONAL RANGE.
PROJECT NAME
7. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT EXPANSION JOINTS AND ANCHOR CONDUIT
APN# 10547110
PERMANENTLY AND COMPLETELY HELP OFF OF THE ROOF SURFACE. NEC 110.2 - 110.4 / 300.4
9. ALL ROOF PENETRATIONS MUST BE FLASHED. SIMPLY CAULKING DOES NOT SUFFICE.
SHEET NAME
ADDITIONAL
NOTES
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-8
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-9
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-10
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-11
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-12
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-13
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-14
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-15
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-16
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-17
RESERVED FOR AHJ
PURELIGHT POWER
541 PARSONS DR.
MEDFORD, OR 97501
CSLB : 226333
PHONE: (541) 816-4047
Email: [email protected]
VERSION
DESCRIPTION DATE REV
PROJECT NAME
APN# 10547110
SHEET NAME
SPEC SHEETS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-18