Schneider Electric TeSys-F LC1F115M7

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Product datasheet

Specifications

TeSys F contactor - 3P (3 NO) -


AC-3 - <= 440 V 115 A - coil 220 V
AC
LC1F115M7

notification_critical_stroke To be discontinued on: Dec 31, 2023

notification_critical_stroke To be discontinued

Main
Range TeSys

Range Of Product TeSys F

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Contactor

Device Short Name LC1F

Contactor Application Resistive load


Motor control

Utilisation Category AC-3


AC-1
AC-4

Poles Description 3P

[Ue] Rated Operational Voltage <= 690 V AC 50/60 Hz


<= 460 V DC

[Uc] Control Circuit Voltage 220 V AC 40...400 Hz

[Ie] Rated Operational Current 200 A (at <40 °C) at <= 440 V AC-1
115 A (at <55 °C) at <= 440 V AC-3

Complementary
[Uimp] Rated Impulse Withstand 8 kV
Voltage
[Ith] Conventional Free Air 200 A (at 40 °C)
Thermal Current
Rated Breaking Capacity 920 A conforming to IEC 60947-4-1

[Icw] Rated Short-Time Withstand 1100 A 40 °C - 10 s


Current 640 A 40 °C - 30 s
520 A 40 °C - 1 min
400 A 40 °C - 3 min
320 A 40 °C - 10 min

Associated Fuse Rating 125 A aM at <= 440 V


200 A gG at <= 440 V

Average Impedance 0.37 mOhm - Ith 200 A 50 Hz

[Ui] Rated Insulation Voltage 1000 V conforming to IEC 60947-4-1


1500 V conforming to VDE 0110 group C

Power Dissipation Per Pole 15 W AC-1


5 W AC-3

Overvoltage Category III

Power Pole Contact Composition 3 NO

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Dec 28, 2023 1


Motor Power Kw 55 kW at 380...400 V AC 50/60 Hz (AC-3)
59 kW at 415 V AC 50/60 Hz (AC-3)
59 kW at 440 V AC 50/60 Hz (AC-3)
75 kW at 500 V AC 50/60 Hz (AC-3)
80 kW at 660...690 V AC 50/60 Hz (AC-3)
30 kW at 220...230 V AC 50/60 Hz (AC-3)
18.5 kW at 400 V AC 50/60 Hz (AC-4)

Control Circuit Voltage Limits Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)


Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C)

Mechanical Durability 10 Mcycles

Inrush Power In Va 770 VA, 40...400 Hz cos phi 0.9 (at 20 °C)

Hold-In Power Consumption In Va 8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)

Maximum Operating Rate 2400 cyc/h 55 °C

Operating Time 35 ms closing (at Uc)


130 ms opening (at Uc)

Connections - Terminals Power circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mm


Power circuit: lugs-ring terminals 1 cable(s) 95 mm²
Power circuit: connector 1 cable(s) 95 mm²
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bolted connection

Tightening Torque Power circuit: 10 N.m


Control circuit: 1.2 N.m

Mounting Support Plate

Heat Dissipation 5.9…7.2 W

Standards IEC 60947-4-1


IEC 60947-1
EN 60947-4-1
EN 60947-1
JIS C8201-4-1

Product Certifications RINA


BV
RMRoS
CB
LROS (Lloyds register of shipping)
DNV
UL
CCC
ABS
UKCA

Compatibility Code LC1F

Control Circuit Type AC at 40...400 Hz

Environment
Ip Degree Of Protection IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106

Protective Treatment TH

Ambient Air Temperature For -40…60 °C


Operation
Ambient Air Temperature For -60…80 °C
Storage
Permissible Ambient Air 60…70 °C at Uc
Temperature Around The Device
Height 162 mm

Width 163.3 mm

2 Dec 28, 2023


Depth 171 mm

Operating Altitude 3000 m without derating

Net Weight 3.43 kg

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 18.500 cm

Package 1 Width 20.000 cm

Package 1 Length 22.500 cm

Package 1 Weight 3.964 kg

Unit Type Of Package 2 S04

Number Of Units In Package 2 4

Package 2 Height 30.000 cm

Package 2 Width 40.000 cm

Package 2 Length 60.000 cm

Package 2 Weight 16.506 kg

Unit Type Of Package 3 P06

Number Of Units In Package 3 18

Package 3 Height 75.000 cm

Package 3 Width 80.000 cm

Package 3 Length 60.000 cm

Package 3 Weight 81.952 kg

Contractual warranty
Warranty 18 months

Dec 28, 2023 3


Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

4 Dec 28, 2023