Product Catalog

Packaged Rooftop Air Conditioners


Foundation™
Cooling and Gas/Electric
7.5 to 12.5 Tons, 60 Hz

September 2023 RT-PRC091F-EN


Introduction
Packaged Rooftop Air Conditioners

Through the years, Trane has designed and developed the most complete line of Packaged Rooftop
products available in the market today.
Trane customers demanded a product that provided exceptional reliability, was easy to install, and was
competitively priced.
Trane listened and is proud to introduce the new Foundation™ Light Commercial rooftop unit. With
Foundation, Trane continues to provide the highest standards in quality and reliability, comfort,
performance, and ease of installation. light commercial products.

Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in
whole or in part without written permission. Trane reserves the right to revise this publication at any
time, and to make changes to its content without obligation to notify any person of such revision or
change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

Revision History
• Updated Convertible Units, Quick-Access Panels, Field Installed Options sections in Features and
Benefits chapter.
• Barometric Relief content moved to Features and Benefits chapter - Field Installed Options from
Application Considerations chapter.
• Updated General data tables.
• Updated Gross Cooling Capacities tables.
• Updated Gas fired heating capacities table in Performance Data chapter.
• Updated Electric heater voltage correction factors (applicable to auxiliary heat capacity) table in
Performance Data chapter.
• Removed TCONT402AN32DA content in Thermostats in Controls chapter.
• Updated Unit wiring with electric heat (single point connection) table in Electric Data chapter.
• Added 460V information to Unit wiring with cooling only (no electric heat) or gas heat and Electrical
characteristics tables in Electric Data chapter.

©2023 Trane RT-PRC091F-EN


Introduction

• Updated Accessory net weight (lb) table in Weights chapter.


• Updated Motorized Outside Air Damper in Mechanical Specifications chapter.

RT-PRC091F-EN 3
Table of Contents
Features and Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Standard and Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Outstanding Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Variety of Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Condensate Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Air Delivery Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14


General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Gross Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Evaporator Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Economizer Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

4 RT-PRC091F-EN
Features and Benefits
Foundation™ has features and benefits that make it first class in the light commercial rooftop market.
Designed with input from field contractors and technicians, its convertible airflow and ease of installation
are outstanding.

Standard and Optional Features


Medium Foundation

Options(a)

Standard
Factory Installed Field Installed

1-year Limited Parts Warranty X

5-year Limited Compressor Warranty X

5-year Limited Heat Exchanger Warranty X

5K SCCR X

Barometric Relief Damper X

Belt Drive Motors X

CO2 sensor - Demand Control Ventilation (DCV) X

Colored Connectors and Wiring X

Compressor Discharge Temperature Limit (DTL) X

Condensate Overflow Switch X

Convertible Airflow X

Easy Access Low Voltage Connections X

Economizer (Downflow) X

Electric Heaters X

Filters X

Hail/Vandal Guards X

High Pressure Control X

High Static Motor Kit(b) X

Insulation - 1/2-inch, 1-lb Density X

Liquid Line Refrigerant Drier X

Low Ambient Cooling X

Low Leak Economizer X

Low Pressure Control X

Low Voltage Circuit Protection X

LP Conversion Kit X

Manual Outside Air Damper X

Motorized 2-Position Damper X

Phase Loss/Reversal Monitor X

Powered Exhaust X

Quick Access Panels X

Remote Potentiometer X

Scroll Compressors X

Single Point Power X

RT-PRC091F-EN 5
Features and Benefits

Medium Foundation

Options(a)

Standard
Factory Installed Field Installed

Single Side Service X

Thermal Expansion Valve X(c)

Through-the-base electrical & gas connection provisions X


(a) Refer to model number description for option availability or contact Product Support.
(b) Available on constant volume units only. See Accessories chapter for more information.
(c) Fixed orifice

Outstanding Standard Features


Colored And Numbered Wiring
Save time and money tracing wires and diagnosing the unit.

Compressors
Foundation™ contains the best compressor technology available to achieve the highest possible
performance.

Controls – Electromechanical
This 24-volt control includes the control transformer and contactor pressure lugs for power wiring.

Convertible Units
Foundation™ 7.5 to 12.5 ton units ship in the downflow configuration. Their convertible design makes it
easy to convert them to a horizontal airflow configuration without an additional kit.1

Discharge Line Thermostat


The high pressure controls and the discharge line thermostat signals are wired in series and connected
to the safety input of the LSD. The compressor contactor coil is connected to the ‘CC’ terminal of the
LSD. If the high pressure control switch or the discharge line thermostat is open, the 24 Vac signal to the
SI input of the LSD is interrupted and the compressor contactor coil supply is disabled by the LSD. It has
an automatic lockout. The high pressure controls and discharge line thermostats are wired in the system
protection detection port. If the high pressure control switch or the discharge line thermostat is open, the
main control board will turn off the compressor of the corresponding system. There is no automatic
lockout.

Efficiency
Product efficiencies meet the requirements of ASHRAE 90.1 - 2016.

Easy Access Low Voltage Terminal Board


Foundation™ Low Voltage Terminal Board is mounted outside the main electrical control cabinet. It is
extremely easy to locate and attach the thermostat control wiring and also test operation of all unit
functions. This is another cost and time saving installation feature.

Insulation
All panels in the evaporator section of the unit have foil-faced, glass fiber insulation. All base panels
have foil-faced, glass fiber insulation. All edges are either captured or sealed to ensure no insulation
fibers get into the airstream.

1. The 7.5 ton unit requires a conversion kit.

6 RT-PRC091F-EN
Features and Benefits

Heat Exchanger
The cabinet features a tubular heat exchanger in heat capacities – all available for vertical and
horizontal discharge directions. The heat exchanger is fabricated using aluminized steel burners and
corrosion-resistant, aluminized steel tubes as standard on all models. As part of the heat exchanger
assembly, an induced draft blower is used to pull the gas mixture through the burner tubes. A direct
spark ignition system, which doubles as a safety device to prove the flame, is used to ignite the gas
mixture.

Locking Safety Device with Anti-Short Cycle Timer


This device monitors compressor safety switch trips to prevent short cycling, protecting the compressor.
A manual reset is required after a fourth safety switch trip.

Low Ambient Cooling


All Foundation units have cooling capabilities down to 0°F as standard.

Low Voltage Connections


The wiring of the low voltage connections to the unit and the thermostat is as simple as R-R, G-G, Y-Y,
and W-W. This simplified system makes it easy for the installer to wire.

Microchannel Condenser Coil


Microchannel condensing coils are all-aluminum coils with fully-brazed construction. This design
reduces risk of leaks and provides increased coil rigidity — making them more rugged on the jobsite.
Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow for exceptional heat
transfer. Microchannel all-aluminum construction provides several additional benefits:
• Light weight (simplifies coil handling)
• Easy to recycle
• Minimize galvanic corrosion

Motors
All indoor fan motors are belt drive as standard.

Pressure Cutouts
Low and high pressure cutouts are standard on all Foundation™ models.

Quick-Access Panels
Remove screws (four or fewer) for access to the standardized internal components and wiring.

RT-PRC091F-EN 7
Features and Benefits

Quick-Adjust Fan Motor Mounting Plate


With the quick-adjust slider plate, the belt and sheaves can be quickly adjusted without moving the
mounted fan motor. This results in reduced time spent on routine maintenance.

Single Point Power


A single electrical connection powers the unit and all on-board options.

Single Side Service


Single side service is standard on all units.

Sloped Drain Pans


Every Foundation™ unit has a non-corrosive, sloped drain pan made of rigid PVC - standard on all
units.

LP Conversion Kit
LP kits are provided as standard with each GCC 090-150 unit for conversion of gas heat units from
natural gas to propane.

Variety of Options
Factory Installed Options
Oversized Motors
Multi-speed only – Factory installed oversized motors are available for high static applications.

Field Installed Options


Condensate Overflow Switch
A condensate overflow switch is available to shut the unit down in the event that the condensate drain
becomes clogged. This option protects the unit from water overflowing from the drain pan and entering
the base of the unit.

CO2 Sensor - Demand Control Ventilation (DCV)


Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand (need) for
ventilation by regulating the rate at which the HVAC system brings outdoor air into the building. A CO2
sensor measures the concentration (parts per million, ppm) of CO2 in the air. As the CO2 concentration
changes, the outside air damper modulates to meet the current ventilation needs of the zone. DCV is a
passive system; direct control of the indoor fan is not possible with standard or low leak economizers.
The CO2 sensor kit is available as a field installed accessory.

Economizer
Economizers are equipped with either dry bulb, reference, or comparative enthalpy sensing. These
economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly
installed, they offer valuable energy savings.

Electric Heaters
Electric heat is available as a field installed option.

Low Leak Economizer with Fault Detection and Diagnostics


This economizer meets the damper leakage requirements for ASHRAE 90.1, IECC, and California Title
24 standards (3 cfm/ft^2 at 1.0 in. w.g. for outside air dampers and 4 cfm/ft^2 for return dampers).

Manual Outside Air Damper


A 0-50 percent manual air damper is available.

8 RT-PRC091F-EN
Features and Benefits

Motorized Outside Air Damper


A 0–50 percent motorized outside air dampers is available.

Power Exhaust
This option is available on downflow units and provides exhaust of the return air, when using a downflow
economizer, to maintain proper building pressurization. This is an excellent option for relieving most
building overpressurization problems.

Barometric Relief
Designed to be used on downflow and horizontal configuration for standard and downflow low leak
economizer units, barometric relief is an unpowered means of relieving excess building pressure.
This product line offers an optional barometric relief damper for use in conjunction with economizer
option. This accessory consists of gravity dampers which open with increased pressure. As building
pressure increases, the pressure in the unit return air section also increases, opening the dampers and
relieving the conditioned space.
Notes:
• The effectiveness of barometric relief damper during economizing operation is system
related.
• Pressure drop of the return air system should be considered to control building
pressurization.

Reference or Comparative Enthalpy


Measures and communicates humidity while maximizing comfort control.

Remote Potentiometer
When installed in the economizer control circuitry, this accessory provides a method to remotely adjust
the minimum damper position.

Roof Curbs
Available for downflow units. Only one roof curb for all 7.5 to 12.5 ton Foundation™ units simplifies curb
selection.

Thermostats
Available in programmable and non-programmable.

Through-the-Base Electrical Utility Access


An electrical service entrance shall be provided allowing access for both control and main power
connections inside the curb and through the base of the unit. This option will allow for field installation of
liquid-tight conduit and an external field installed disconnect switch.
Factory provided through the base openings simplify wiring and piping. Because these utility openings
frequently minimize the number of roof penetrations, the integrity of roofing materials is enhanced.

Through-the-Base Gas Piping (Gas Heat Units Only)


This option shall have all piping necessary including, black steel, manual gas shut-off valve, elbows, and
union. This assembly will require minor field labor to install.

Tool-less Hail Guards


Tool-less, hail protection quality coil guards shall be field-installed for condenser coil protection. This
option protects the condenser coil from vandalism and/or hail damage.

Other Benefits
Easy to Install, Service and Maintain
Because today’s owners are very cost-conscious when it comes to service and maintenance,
Foundation was designed with direct input from service contractors. This valuable information helped to
design a product that would get the service technician off the job quicker and save the owner money.
Foundation does this by offering outstanding standard features enhanced by a variety of factory and

RT-PRC091F-EN 9
Features and Benefits

field installed options, multiple control options, rigorously tested proven designs and superior product
and technical support.

Outstanding Flexibility
The Foundation 7.5-12.5 ton units match the footprint of specific Carrier WeatherMaker™ units.

Rigorous Testing
All of Foundation’s designs were rigorously rain tested at the factory to ensure water integrity. Each part
of the top overlaps in such a way that water cannot leak into the unit. These overlapped edges are
gasketed and sealed to ensure superior water integrity.
Actual shipping tests were performed to determine packaging requirements. Factory shake tests were
used as part of the package design process to help assure that the unit arrives at the job site in top
condition.
For the microchannel coils, the supplier will perform the leak check at 450 psig. The completely
assembled refrigerant system is leak tested at a minimum of 225 psig with a refrigerant and nitrogen
mixture.
All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected
immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it
lives up to rigorous Trane requirements.

Unmatched Support
Trane Sales Representatives are a Support Group that can assist you with:
• Product
• Special Applications
• Application
• Specifications
• Service
• Computer Programs and much more
• Training

10 RT-PRC091F-EN
Application Considerations
Application of this product should be within the cataloged airflow and cooling considerations.

Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to ensure adequate
serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear
inadequate should be reviewed with local Trane sales personnel.

Condensate Trap
The evaporator is a draw-through configuration. A trap must be field provided prior to start-up on the
cooling cycle.

Unit Pitch
These units have sloped condensate drain pans. Units must be installed level. Any unit slope must be
toward access side of the unit.

RT-PRC091F-EN 11
Selection Procedure
Cooling Capacity
1. Calculate the building’s total and sensible cooling loads for the building at design conditions. Use
the following calculation methods or any other standard accepted method.
Factors used in unit selection:
• Total Cooling Load: 120 MBh
• Sensible Cooling Load: 96 MBh
• Airflow: 4000 cfm
• Electrical Characteristics: 460/60/3
• Summer Design Conditions: Entering Evaporator Coil: 80ºF DB/67ºF WB
• Outdoor Ambient: 95ºF
• External Static Pressure: 0.38 in. wg
• Rooftop – Downflow configuration
• Accessories: Roof Curb, Electric Heat
2. As a starting point, a rough determination must be made of the size of the unit. The final selection
will be made after examining the performance at the given conditions. Divide the total cooling load
by nominal Btuh per ton (12 MBh per ton); then round up to the nearest unit size.
120 MBh / 12 MBh = 10 Tons
3. shows that a GCC120A has a gross cooling capacity of 122.1 MBh and 96.3 MBh sensible capacity
at 4000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the evaporator.
Find capacity at intermediate conditions not in the table
When the design conditions are between two numbers that are in the capacity table, interpolation is
required to approximate the capacity.
Note: Extrapolation outside of the table conditions is not recommended.
4. In order to select the correct unit which meets the building’s requirements, the fan motor heat must
be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is
dependent on the effort by the motor - cfm and static pressure. To determine the total unit static
pressure you add the external static pressure to the additional static related by the added features:

External Static Duct System 0.38 wg

Standard Filter 2 in. from 0.05 wg

Electric Heater Size kW from 0.07 wg

Total Static Pressure 0.47 wg

Note: Reference heating capacity section on this page for determination of heater size. No additional static add for gas/heat
exchanger.

Note: The Evaporator Fan Performance has already accounted for the pressure drop for standard
filters and wet coils (see note below in ). Therefore, the actual total static pressure is 0.47 -
0.05 (from ) = 0.42 wg.
With 4000 cfm and 0.42 wg. shows 1.9 bhp for this unit. Note below the table is the formula to
calculate fan motor heat.
3-hp fan motor heat (MBh) = 2.90 x fan bhp + 0.4750
2.90 x 2.06 + 0.4750 = 5.435 MBh

Now subtract the fan motor heat from the gross cooling capacity of the unit:
Net Total Cooling Capacity = 122.1 MBh - 5.435 = 116.665 MBh.

12 RT-PRC091F-EN
Selection Procedure

Net Sensible Cooling Capacity = 96.3 MBh - 5.435 = 90.865 MBh.


5. Compare your resulting capacities to the building load. If the performance will not meet the required
load of the building’s total or sensible cooling load, try a selection at the next higher size unit.

Heating Capacity
Note: Heating capacity procedures DIFFER for cooling (E) and gas/electric (G) units.
1. Calculate the building heating load.
2. Size the system heating capacity to match the calculated building heating load. The following are
building heating requirements:
460 volt/3 phase Power Supply
Total heating load of 100.0 MBh
4000 cfm
The electric heat accessory capacities are listed in . From the table, a 2 kW heater will deliver 109.2
MBh at 480 volts. In order to determine capacity at 460 volts, the heater voltage correction factor
from must be used. Therefore, 109.2 MBh x 0.94 (voltage correction factor) = 102.6 MBh.
Gas/electric: Fuel natural gas total heating load of 100 MBh. shows 125 MBh and 180 MBh input
models. The output capacities of these furnaces are 70 MBh and 100 MBh respectively. The
medium heat model with 100 MBh output best matches the building requirements.

Air Delivery Selection


External static pressure drop through the air distribution system has been calculated to be 0.38 inches
of water. From the 32 kW heater is 0.04 inches of water (0.38 + 0.04). Enter for a EBC120A4E0 at 4000
cfm and 0.42 static pressure. The standard motor will give the desired airflow at 758 rpm and rated bhp
of 1.89.

RT-PRC091F-EN 13
Model Number Description

Digit 1 — Unit Type Digit 11— Minor Design Sequence Digit 20 to 24


Not Used
E = Packaged Cooling, Electric Heat A = Rev A
G = Packaged Gas/Electric B = Rev B

Digit 2 — Efficiency Digit 12, 13 — Service Sequence

C = ASHRAE 90.1 - 2016 00 = None

Digit 3 — Airflow Configuration Digit 14 — Fresh Air Selection

C = Convertible 0 = No Fresh Air Options


Note: Fresh air options are available as field
Digit 4, 5, 6 — Nominal Gross Cooling installed accessories.
Capacity (MBh)
Digit 15 — Supply Fan/Drive Type/Motor
090 = 7.5 Tons
102 = 8.5 Tons 7 = Multi-Speed Standard Motor
120 = 10 Tons 9 = Multi-Speed Oversized Motor
150 = 12.5 Tons
Digit 16 — Unit
Digit 7 — Major Design Sequence
M = Medium Foundation
A = Rev A

Digit 17 — Condenser Coil Protection


Digit 8 — Voltage Selection
0 = Standard Coil
3 = 208-230/60/3
4 = 460/60/3
Digit 18 — Through The Base Provisions
Digit 9 — Unit Controls
0 = No Through the Base Provisions
E = Electromechanical Note: Through the base Provisions are available as
field installed accessories.
Digit 10 — Heating Capacity
Digit 19 — Disconnect Switch
0 = Cooling Only (field installed electric heat)
H = Gas Heat - High 0 = No Disconnect/No Circuit Breaker
L = Gas Heat - Low Note: Non-Fused Disconnect are available as field
M = Gas Heat - Medium installed accessories.
X = Gas Heat - Stainless Steel HX - Low
Y = Gas Heat - Stainless Steel HX - Medium
Z = Gas Heat - Stainless Steel HX - High

14 RT-PRC091F-EN
General Data
Table 1. General data – 7.5 to 12.5 tons – 230 volts
7.5 Ton 8.5 Ton 10 Ton 12.5 Ton
E/GCC090 E/GCC105 E/GCC120 E/GCC150
Cooling Performance(a)
Gross Cooling Capacity 90000 102000 120000 150000
EER (Downflow/Horizontal) 11.2 11.2 11.2 11.0
Nominal Airflow CFM / AHRI Rated CFM 3200/3000 3700/3000 3700/3200 4600/4000
AHRI Net Cooling Capacity 86000 104000 114000 140000
Integrated Energy Efficiency Ratio (IEER) 14.8 14.8 14.8 14.2
Percent Capacity @ part load (Stage 1/Stage 2) 58/100 47/100 44/100 32/100
System Power (kW) 7.68 9.29 10.18 12.73
Compressor
Number/Type 2 / Scrolls 2 / Scrolls 2 / Scrolls 2 / Scrolls
Sound
Outdoor Sound Rating (BELS) 8.2 8.2 8.2 8.7
Outdoor Coil
Type Microchannel Microchannel Microchannel Microchannel
Coil Width (in.) (System A + System B 0.63+0.63 0.81+1.0 0.81+1.0 1.28+1.28
Face Area (sq. ft.) 23.81 27.38 27.38 27.38
Rows/FPI 1/23 1/23 1/23 1/23
Indoor Coil
Type Microchannel Microchannel Microchannel Microchannel
Tube Size (in.) ID 0.98 0.98 1.57 1.57
Face Area (sq. ft.) 12.88 12.88 12.88 12.88
Rows/FPI 3/17 3/17 4/17 4/17
Refrigerant Control EXV EXV EXV EXV
1 / 3/4 1 / 3/4 1 / 3/4 1 / 3/4
Drain Connection Number/Size (in.)
PVC Pipe Socket PVC Pipe Socket PVC Pipe Socket PVC Pipe Socket
Outdoor Fan
Type Propeller Propeller Propeller Propeller
Number Used/Diameter (in.) 2 / 23-1/2 2 / 23-1/2 2 / 23-1/2 2 / 23-1/2
Drive Type/No. Speeds Direct / 10 Direct / 10 Direct / 10 Direct / 10
cfm 8400 8300 8300 10000
Number Motors/hp 2 / 1/3HP 2 / 1/3HP 2 / 1/3HP 2 / 3/4HP
Motor rpm 960 960 960 1070
Indoor Fan
Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1 / 15x15 1 / 15x15 1 / 15x15 1 / 15x15
Drive Type/No. Speeds Belt / 1 Belt / 1 Belt / 1 Belt / 1
Number Motors 1 1 1 1
Motor hp (Standard/Oversized) 2.0 / 3.0 2.0 / 5.0 3.0 / 5.0 3.0 / 5.0
Motor rpm (Standard/Oversized) 1725 1725 1725 1725
Motor Frame Size (Standard/Oversized) 56 / 56 56 / 56 56 / 56 56 / 56
Filters
Type Furnished Throwaway Throwaway Throwaway Throwaway
Number Size Recommended (4)20*20*2 (4)20*20*2 (4)20*20*2 (4)20*20*2
Refrigerant Charge (Pounds of R-410A)(b)
Circuit A 3.97 lbs 4.85 lbs 5.29 lbs 7.50 lbs
Circuit B 3.53 lbs 4.41 lbs 5.07 lbs 5.73 lbs
(a) Units are AHRI Certified to AHRI Standard 340-360 (I-P). Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F entering wet bulb with minimum
external static pressure as determined by rating standard.
(b) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RT-PRC091F-EN 15
General Data

Table 2. General data – 7.5 to 12.5 tons – 460 volts


7.5 Ton 8.5 Ton 10 Ton 12.5 Ton
E/GCC090 E/GCC105 E/GCC120 E/GCC150
Cooling Performance(a)
Gross Cooling Capacity 90000 102000 120000 150000
EER (Downflow/Horizontal) 11.2 11.2 11.2 11.0
Nominal Airflow CFM / AHRI Rated CFM 3200/3000 3700/3000 3700/3200 4600/4000
AHRI Net Cooling Capacity 86000 104000 114000 140000
Integrated Energy Efficiency Ratio (IEER) 14.8 14.8 14.8 14.2
Percent Capacity @ part load (Stage 1/Stage 2) 58/100 47/100 44/100 32/100
System Power (kW) 7.68 9.29 10.18 12.73
Compressor
Number/Type 2 / Scrolls 2 / Scrolls 2 / Scrolls 2 / Scrolls
Sound
Outdoor Sound Rating (BELS) 8.2 8.2 8.2 9.2
Outdoor Coil
Type Microchannel Microchannel Microchannel Microchannel
Coil Width (in.) (System A + System B 0.63+0.63 1.0+1.0 1.0+1.0 1.28+1.28
Face Area (sq. ft.) 23.81 27.38 27.38 27.38
Rows/FPI 1/23 1/23 1/23 1/23
Indoor Coil
Type Microchannel Microchannel Microchannel Microchannel
Tube Size (in.) ID 0.98 0.98 1.57 1.57
Face Area (sq. ft.) 12.88 12.88 12.88 12.88
Rows/FPI 3/17 3/17 4/17 4/17
Refrigerant Control EXV EXV EXV EXV
1 / 3/4 1 / 3/4 1 / 3/4 1 / 3/4
Drain Connection Number/Size (in.)
PVC Pipe Socket PVC Pipe Socket PVC Pipe Socket PVC Pipe Socket
Outdoor Fan
Type Propeller Propeller Propeller Propeller
Number Used/Diameter (in.) 2 / 23-1/2 2 / 23-1/2 2 / 23-1/2 2 / 23-1/2
Drive Type/No. Speeds Direct / 10 Direct / 10 Direct / 10 Direct / 10
cfm 8400 8300 8300 10000
Number Motors/hp 2 / 1/3HP 2 / 1/3HP 2 / 1/3HP 2 / 3/4HP
Motor rpm 960 960 960 1070
Indoor Fan
Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1 / 15X15 1 / 15X15 1 / 15X15 1 / 15X15
Drive Type/No. Speeds Belt / 1 Belt / 1 Belt / 1 Belt / 1
Number Motors 1 1 1 1
Motor hp (Standard/Oversized) 2.0 /3.0 2.0 / 5.0 3.0 / 5.0 3.0 / 5.0
Motor rpm (Standard/Oversized) 1725 1725 1725 1725
Motor Frame Size (Standard/Oversized) 56/56 56/56 56/56 56/56
Filters
Type Furnished Throwaway Throwaway Throwaway Throwaway
Number Size Recommended (4)20*20*2 (4)20*20*2 (4)20*20*2 (4)20*20*2
Refrigerant Charge (Pounds of R-410A)(b)
Circuit A 3.97 lbs 4.85 lbs 5.29 lbs 7.72 lbs
Circuit B 3.31 lbs 4.41 lbs 4.85 lbs 5.95 lbs
(a) Units are AHRI Certified to AHRI Standard 340-360 (I-P) . Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F entering wet bulb with minimum
external static pressure as determined by rating standard.
(b) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

16 RT-PRC091F-EN
General Data

Table 3. General data – heating performance – 7.5 to 12.5 tons


Heating Performance(a)
7.5 to 8.5 Tons 10 to 12.5 Tons
Heating Models Low Medium High Low Medium High
Heating Input (Btu/h) 125000 180,000 225000 180,000 225000 250000
1st Stage (Btu) 87500 126,000 168000 126,000 168000 200000
Heating Output (Btu/h) 100000 144,000 180,000 144,000 180000 200000
1st Stage (Btu) 70000 100,000 125,000 100,000 125000 160000
Steady State Efficiency % 81% 81% 81% 81% 81% 81%
No. Burners 3 5 6 5 6 6
No. Stages 2 2 2 2 2 2
Gas Supply Line Pressure (in. wc)

Natural Gas (minimum/maximum) 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc.

LP (minimum/maximum) 11.0/14.0 in. wc. 11.0/14.0 in. wc. 11.0/14.0 in. wc. 11.0/14.0 in. wc. 11.0/14.0 in. wc. 11.0/14.0 in. wc.

Gas Connection Pipe Size (in.) 1/2 1/2 3/4 1/2 3/4 3/4
(a) Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards
(ANSI). Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.

RT-PRC091F-EN 17
Performance Data
Gross Cooling Capacities
Table 4. Gross cooling capacities 7.5 tons
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
Ent 85 95 105
CFM DB (° Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
F)
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 82.8 56.6 92.4 47.8 101.8 36.3 74.8 54.7 87.3 44.7 94.7 36.7 68.4 51.2 78.0 42.8 88.1 35.1
80 82.0 69.1 91.5 58.3 101.0 49.1 73.9 65.2 86.2 56.8 93.7 43.9 67.6 59.7 77.1 54.3 87.2 45.3
2400
85 81.6 76.7 91.2 64.7 100.9 61.4 73.5 70.7 85.7 64.5 92.7 52.4 67.2 64.1 76.6 61.6 86.2 50.1
90 81.4 77.3 90.9 66.7 100.6 76.5 73.3 73.3 85.5 67.5 92.8 55.1 67.0 67.0 76.4 64.5 86.2 52.7
75 86.1 62.2 95.8 52.6 105.2 40.1 78.0 60.2 90.6 49.2 98.3 45.5 71.5 56.3 81.3 47.1 91.6 43.5
80 85.3 75.6 94.9 63.8 104.7 53.8 77.0 71.3 89.5 62.1 96.7 45.9 70.7 65.3 80.3 59.4 90.0 43.9
2700
85 84.8 79.2 94.4 70.7 104.3 67.2 76.5 75.1 89.0 70.5 96.3 57.7 70.1 68.7 79.7 67.4 89.7 55.1
90 84.6 79.0 94.1 71.4 103.9 81.7 76.3 74.9 88.7 72.3 96.2 66.7 69.9 68.5 79.5 69.1 89.6 63.8
75 85.9 67.2 95.8 56.8 105.4 43.3 77.7 65.0 90.6 53.1 97.9 39.4 71.1 60.8 81.0 50.8 91.0 37.8
80 85.2 80.9 95.0 68.7 104.8 57.9 76.8 76.8 89.5 66.9 97.0 54.8 70.3 70.3 80.1 64.0 90.3 52.3
3000
85 84.6 80.3 94.3 76.1 104.3 72.4 76.2 76.2 88.7 75.9 96.4 70.1 69.7 69.7 79.4 72.6 89.7 67.0
90 84.3 80.1 93.9 75.4 103.9 86.4 75.9 75.9 88.4 76.4 96.0 85.0 69.4 69.4 79.1 73.0 89.3 81.1
75 87.6 73.1 97.7 61.9 107.5 47.1 79.4 70.7 92.4 57.9 99.3 34.7 72.6 66.2 82.7 55.3 92.4 33.4
80 87.0 77.1 97.0 74.4 106.9 62.8 78.6 78.6 91.4 72.5 99.3 65.9 71.8 71.8 81.8 69.4 92.4 63.0
3300
85 86.2 81.9 96.1 82.5 106.2 78.5 77.8 77.8 90.4 82.3 98.4 85.8 71.2 71.2 81.0 78.7 91.6 82.1
90 85.9 81.6 95.6 80.1 105.7 91.8 77.3 77.3 90.0 81.2 97.7 97.7 70.8 70.8 80.6 80.6 90.9 90.9
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
Ent 115 120 125
CFM DB (° Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
F)
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 58.8 48.2 69.2 41.4 79.5 34.0 50.4 43.3 63.9 43.3 73.4 33.1 27.6 24.7 33.6 24.3 38.5 20.3
80 58.1 51.3 68.4 52.5 78.6 39.5 49.9 44.4 63.2 54.9 72.7 47.2 27.3 24.5 33.2 30.5 38.1 28.5
2400
85 57.8 56.4 68.0 59.7 77.8 48.4 49.5 49.5 62.8 57.8 71.9 42.8 27.1 27.1 33.0 32.0 37.7 25.9
90 57.6 57.6 67.9 62.1 77.7 50.9 49.1 49.1 62.7 62.7 71.6 49.7 26.9 26.9 32.9 32.0 37.5 29.9
75 61.7 53.0 72.3 45.7 82.4 36.5 53.2 47.6 67.0 47.6 76.7 41.2 30.0 27.4 36.1 27.0 41.2 25.3
80 61.0 56.2 71.5 57.6 81.7 42.7 52.5 48.5 66.2 59.6 75.4 41.5 29.7 27.0 35.7 33.3 40.5 25.5
2700
85 60.6 59.1 71.0 65.3 81.3 55.9 52.1 50.7 65.8 59.3 75.2 52.0 29.5 28.1 35.5 33.2 40.4 31.6
90 60.4 59.0 70.8 66.6 81.0 65.5 51.8 50.4 65.5 64.1 75.0 60.1 29.4 28.0 35.4 33.0 40.3 36.3
75 61.2 57.2 71.9 49.3 82.2 38.8 53.7 51.8 66.5 51.5 76.0 35.7 29.7 29.7 35.3 29.0 40.2 22.2
80 60.5 60.5 71.2 62.0 81.5 50.7 53.1 53.1 65.8 60.6 75.4 49.4 29.4 29.4 34.9 33.9 39.9 30.1
3000
85 60.0 60.0 70.6 70.4 81.0 64.8 52.7 52.7 65.3 60.1 74.9 63.2 29.2 29.2 34.6 33.6 39.6 38.1
90 59.8 59.8 70.3 70.3 80.7 78.4 52.5 52.5 65.0 65.0 74.9 65.6 29.1 29.1 34.5 33.5 39.6 39.5
75 62.3 62.3 73.5 53.7 83.9 41.8 56.2 56.2 68.0 56.1 77.2 31.6 31.3 31.3 36.3 31.8 41.1 20.0
80 61.9 61.9 72.8 67.3 83.3 60.7 55.6 55.6 67.3 62.1 77.4 59.5 31.0 31.0 36.0 35.0 41.1 36.2
3300
85 61.4 61.4 72.1 72.1 82.6 75.7 55.3 55.3 66.7 61.5 76.6 76.6 30.8 30.8 35.6 34.6 40.7 40.7
90 61.1 61.1 71.7 71.7 82.2 82.2 55.1 55.1 66.4 66.4 76.7 76.7 30.7 30.7 35.5 35.5 40.8 40.8
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBh = Total gross capacity
3. SHC = Sensible heat capacity
4. Ambient Temperature above 120°F, the system B shuts down.

18 RT-PRC091F-EN
Performance Data

Table 5. Gross cooling capacities 8.5 tons


Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
Ent 85 95 105
CFM DB (° Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
F)
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 100.4 69.9 112.0 60.4 122.8 45.3 93.5 67.0 106.2 56.3 118.1 45.5 88.4 63.7 101.4 53.4 112.5 44.7
80 99.5 84.9 110.9 73.2 121.9 60.5 92.4 84.8 105.0 70.8 116.9 54.1 87.3 80.6 100.2 67.2 111.3 57.3
2700
85 99.1 93.9 110.5 80.9 121.7 75.2 91.2 89.7 104.4 80.0 115.7 64.2 86.2 84.7 99.6 76.0 110.2 63.2
90 98.8 94.6 110.3 83.4 121.4 93.1 90.9 89.5 104.2 83.7 115.8 67.4 86.0 84.4 99.4 79.5 110.1 66.4
75 102.3 76.3 114.0 65.9 124.9 49.5 95.3 73.2 108.2 61.4 120.5 55.7 90.1 70.5 103.3 59.3 114.6 55.5
80 101.4 92.2 113.0 79.5 124.2 65.8 92.8 92.1 106.9 76.9 118.5 56.1 87.0 87.8 102.1 73.7 112.7 56.6
3050
85 100.8 96.6 112.4 87.9 123.8 81.8 92.4 91.2 106.3 86.9 118.0 70.1 86.3 87.1 101.4 82.9 112.3 70.4
90 100.6 96.3 112.1 88.7 123.3 99.0 92.2 91.0 105.9 88.5 117.9 79.9 86.9 85.9 101.1 83.9 112.2 78.8
75 104.1 83.6 116.1 73.5 127.0 56.7 96.8 80.7 110.0 68.2 121.9 51.0 91.7 76.6 105.1 64.5 116.2 49.7
80 102.5 99.7 115.1 87.2 126.3 73.1 93.2 95.0 109.1 84.3 120.9 68.3 87.9 89.8 104.2 79.9 115.3 67.4
3400
85 101.8 98.9 114.2 95.9 125.7 90.3 92.3 94.3 108.1 94.7 120.1 86.0 87.3 89.0 103.3 89.8 114.6 85.3
90 101.9 98.1 113.8 94.2 125.1 104.3 92.6 93.2 107.7 94.2 119.6 101.5 87.6 87.9 103.0 89.3 114.1 100.2
75 106.1 91.4 118.2 79.8 129.4 60.6 99.0 87.9 112.2 74.5 123.6 46.1 93.6 83.7 107.1 71.0 117.7 46.5
80 103.6 102.4 117.4 94.6 128.8 78.7 93.7 97.7 111.1 91.7 123.7 81.7 88.3 92.1 106.0 87.2 117.6 81.9
3750
85 103.4 101.1 116.3 102.9 128.0 95.5 93.9 95.8 109.9 102.4 122.6 104.1 87.9 90.8 104.9 97.1 116.6 102.4
90 102.4 101.2 115.8 100.7 127.4 111.0 92.7 95.9 109.4 101.9 117.0 121.7 86.8 91.1 104.5 96.4 111.7 114.9
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
Ent 115 120 125
CFM DB (° Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
F)
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 78.9 61.8 89.7 52.6 102.5 43.6 76.2 54.2 84.8 64.9 98.4 61.9 38.4 30.8 45.3 30.4 48.6 25.6
80 77.4 75.8 88.6 66.2 101.4 50.5 75.5 67.4 82.9 82.0 97.4 88.4 37.4 35.9 44.9 37.4 48.1 34.8
2700
85 76.9 75.4 88.1 74.9 100.4 61.6 74.1 72.8 82.5 81.4 96.3 80.1 37.1 35.7 44.6 39.2 47.7 31.9
90 76.7 75.2 88.0 78.3 100.3 64.7 73.6 72.3 82.3 81.2 96.0 93.1 36.9 35.5 44.5 39.1 47.5 36.4
75 80.4 68.5 91.2 58.4 103.9 47.4 77.8 60.6 86.6 71.1 100.5 75.8 39.4 34.4 46.3 33.8 49.7 30.9
80 78.0 77.8 90.4 72.6 103.0 55.2 77.0 69.5 84.3 83.8 98.8 76.7 37.4 37.3 45.9 40.9 48.9 31.7
3050
85 77.4 77.2 89.8 81.8 102.5 70.9 74.8 74.6 83.6 83.5 97.8 95.7 37.2 37.0 45.7 40.8 48.8 38.2
90 77.6 76.5 89.5 82.6 102.2 81.2 74.8 73.7 84.3 82.1 98.3 94.7 37.8 36.0 45.5 40.1 48.7 43.0
75 82.1 74.5 93.1 63.6 105.9 51.0 81.0 66.8 88.4 78.0 101.9 68.0 40.2 38.1 47.4 37.6 50.6 29.6
80 78.9 79.7 92.3 78.7 105.1 65.6 80.3 73.4 84.6 86.3 101.2 83.2 37.9 39.7 47.1 42.9 50.4 38.1
3400
85 78.2 79.1 90.9 88.0 104.5 81.8 77.2 78.1 84.7 84.9 99.1 97.8 38.3 39.0 46.7 41.5 50.1 45.4
90 77.2 79.4 89.4 88.9 104.0 98.4 76.0 78.6 83.8 85.1 98.7 98.2 37.2 39.7 46.6 41.9 48.6 47.4
75 81.2 81.1 94.7 70.0 107.6 56.0 84.3 72.9 90.0 84.7 103.2 60.6 39.8 41.5 48.7 40.9 51.7 27.8
80 78.1 82.6 94.0 85.8 107.3 78.7 83.5 78.2 85.5 88.6 103.6 83.0 38.9 41.7 48.1 43.8 51.9 44.2
3750
85 78.7 81.1 89.8 91.6 106.4 95.0 79.6 81.9 85.4 86.9 100.0 100.3 38.2 42.2 47.2 43.9 48.1 49.9
90 77.7 81.3 88.9 91.6 102.9 104.1 78.5 82.4 84.6 87.0 100.0 100.6 37.6 42.4 46.7 44.0 47.5 50.3
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBh = Total gross capacity
3. SHC = Sensible heat capacity
4. Ambient Temperature above 120°F, the system B shuts down.

RT-PRC091F-EN 19
Performance Data

Table 6. Gross cooling capacities 10 tons


Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 112.3 80.8 122.7 73.2 135.1 44.7 109.0 70.8 119.1 64.2 131.5 43.8 97.5 62.9 106.5 57.0 121.1 39.7
80 111.2 99.6 121.5 90.2 134.1 61.5 107.6 91.1 117.6 82.6 130.1 53.1 96.2 80.9 105.1 73.3 119.8 52.1
3200
85 111.0 110.6 121.0 100.5 133.9 77.8 107.0 104.1 116.9 94.2 128.6 63.9 95.7 92.4 104.5 83.7 118.5 57.9
90 111.9 110.3 120.7 103.8 133.5 97.6 108.2 106.6 116.6 98.9 128.7 67.4 96.9 95.3 104.2 87.8 118.4 61.1
75 114.8 88.2 125.3 79.8 137.8 48.8 111.4 77.3 121.6 70.0 134.5 54.2 99.7 68.6 108.9 62.2 123.9 49.1
80 113.7 108.2 124.1 98.0 137.0 66.8 110.0 98.9 120.1 90.6 132.1 54.7 98.5 87.9 107.5 79.6 121.7 49.6
3600
85 114.5 112.1 123.4 109.1 136.5 84.5 110.7 108.3 119.3 102.3 131.6 69.8 99.2 96.8 106.7 90.9 121.2 63.2
90 114.2 111.8 123.0 110.2 136.0 103.6 110.4 108.0 118.9 105.0 131.4 81.3 98.9 96.5 106.4 93.2 121.1 73.7
75 117.4 97.4 128.1 88.4 140.8 54.7 114.0 85.6 124.4 77.7 136.7 48.2 102.1 76.2 111.4 69.2 126.0 43.9
80 117.9 116.4 127.0 107.6 140.0 74.0 112.7 108.7 122.9 98.6 135.5 67.8 100.9 96.7 110.1 87.8 124.9 61.6
4000
85 117.0 115.5 126.0 119.6 139.3 93.1 113.2 111.7 121.8 112.3 134.6 87.4 101.5 100.0 109.1 100.0 124.1 79.4
90 116.6 115.1 125.5 118.4 138.7 111.5 112.7 111.2 121.3 113.0 134.0 106.4 101.1 99.6 108.7 100.5 123.5 96.5
75 120.2 106.5 131.1 96.9 144.0 60.2 116.8 93.7 127.4 85.2 139.1 42.7 104.7 83.6 114.1 75.9 128.3 39.0
80 120.8 119.3 130.1 117.1 143.2 80.9 117.1 115.6 125.9 107.5 139.1 82.5 105.0 103.5 112.9 95.8 128.3 75.0
4400
85 119.7 118.2 130.1 128.8 142.3 101.5 115.9 114.4 124.5 122.2 137.8 107.9 104.0 102.5 111.7 109.0 127.2 98.2
90 119.2 117.7 128.2 126.3 141.6 119.0 115.2 113.7 123.9 120.7 137.5 136.8 103.5 102.0 111.2 107.4 126.1 124.6
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
115 120 125
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 88.6 58.8 96.8 53.2 111.6 36.5 85.2 51.0 91.1 67.0 106.8 53.5 40.4 24.5 43.2 32.1 50.8 25.7
80 87.5 75.6 95.6 68.4 110.4 42.9 84.3 66.7 90.0 86.1 105.6 78.1 40.0 32.0 42.7 41.2 50.2 37.4
3200
85 87.0 86.3 95.0 78.2 109.2 53.2 85.1 83.5 90.9 89.3 104.4 70.4 40.8 39.5 43.6 42.3 49.6 33.7
90 88.2 86.6 94.8 82.0 109.0 56.1 84.5 82.9 90.7 89.1 104.0 82.4 40.5 39.2 43.5 42.2 49.4 39.5
75 90.7 64.1 99.0 58.1 113.6 38.6 87.3 55.5 93.3 73.0 109.4 66.3 41.8 26.7 44.7 35.0 52.4 31.8
80 89.6 82.1 97.8 74.3 112.6 45.8 86.1 72.2 93.6 91.2 107.4 66.9 41.2 34.6 45.2 43.2 51.4 32.1
3600
85 90.4 88.0 97.1 84.9 112.0 61.0 86.9 84.5 93.0 90.6 107.0 85.3 42.0 40.0 44.9 42.9 51.2 40.8
90 90.1 87.7 96.8 87.1 111.6 72.1 86.4 84.0 92.6 90.2 106.8 101.3 41.8 39.8 44.7 42.7 51.1 47.5
75 93.0 71.3 101.4 64.8 116.2 43.1 91.6 62.5 95.6 81.0 111.3 58.5 44.4 31.0 46.3 39.8 53.8 29.1
80 91.9 90.5 100.3 82.1 115.3 56.8 90.5 81.2 96.0 94.5 110.4 82.5 43.9 39.9 46.9 45.8 53.4 40.5
4000
85 92.6 91.1 99.4 93.5 114.5 73.1 91.3 89.8 95.2 93.7 109.6 106.5 44.7 43.5 46.5 45.4 53.0 51.9
90 92.2 90.7 99.0 94.0 114.0 88.8 90.9 89.4 94.8 93.3 110.7 109.6 44.5 43.3 46.3 45.2 53.9 53.0
75 95.5 78.2 104.0 71.2 119.0 47.1 96.2 69.3 98.1 88.8 113.4 51.4 47.2 34.8 48.1 44.1 55.5 26.3
80 95.9 94.4 103.0 89.7 118.2 68.9 95.2 90.2 98.6 97.1 113.6 100.2 46.8 44.8 48.8 47.7 55.6 49.5
4400
85 95.0 93.5 101.9 101.9 117.2 86.2 96.0 94.5 97.6 96.1 113.9 112.4 47.5 46.4 48.3 47.2 56.5 55.0
90 94.5 93.0 101.4 100.5 116.6 107.9 95.7 94.2 97.2 95.7 114.1 112.6 47.4 46.3 48.1 47.0 56.6 55.1
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBh = Total gross capacity
3. SHC = Sensible heat capacity
4. Ambient Temperature above 120°F, the system B shuts down.

20 RT-PRC091F-EN
Performance Data

Table 7. Gross cooling capacities 12.5 tons


Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Ent Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 132.6 110.1 148.7 86.4 164.2 58.0 128.9 108.8 143.8 84.7 155.5 54.8 120.7 105.1 129.6 78.4 145.2 50.8
4000 80 132.3 132.1 148.3 108.9 163.8 80.0 128.8 123.5 143.5 107.8 155.3 77.2 120.5 116.8 129.1 100.9 145.0 72.9
85 131.7 131.7 147.9 131.6 163.5 102.4 128.5 128.5 143.2 128.3 155.1 98.1 120.1 120.1 128.8 121.6 144.8 94.3
90 131.3 131.3 147.6 147.6 163.2 125.2 128.1 128.1 143.0 140.4 154.7 120.2 119.8 119.8 128.5 128.5 144.6 117.1
75 136.3 123.4 152.6 96.8 168.3 65.3 132.4 122.0 147.5 94.9 159.9 70.7 124.0 117.2 133.1 87.7 149.2 65.0
4500 80 136.0 136.0 152.2 121.4 168.2 89.3 132.3 132.3 147.3 120.1 158.3 81.2 123.9 123.9 132.6 112.0 147.8 70.3
85 135.1 135.1 151.5 146.4 167.4 114.1 131.8 131.8 146.8 142.8 159.6 110.1 123.1 123.1 132.1 132.1 148.7 105.4
90 134.7 134.7 151.1 151.1 167.0 135.7 131.4 131.4 146.5 146.5 158.7 151.1 122.8 122.8 131.8 131.8 148.5 146.1
75 139.9 136.6 156.6 107.5 172.6 72.6 136.1 135.0 151.5 105.3 163.0 61.0 127.5 126.4 136.8 97.6 152.3 56.8
5000 80 139.8 139.8 156.4 133.8 172.5 98.7 136.0 136.0 151.3 132.5 163.1 101.5 126.9 126.9 136.4 124.1 152.4 87.9
85 138.6 138.6 155.3 155.3 171.5 126.0 135.3 135.3 150.4 150.4 163.8 140.0 126.5 126.5 135.6 135.6 153.0 134.6
90 138.1 138.1 154.7 154.7 170.9 146.3 134.6 134.6 149.9 149.9 162.4 162.4 126.0 126.0 135.1 135.1 152.1 152.1
75 143.7 142.1 160.7 119.0 177.0 80.4 139.8 138.3 155.6 116.5 166.2 53.0 131.0 129.7 140.4 107.9 155.4 49.6
5500 80 143.1 143.1 160.4 147.2 176.9 108.9 139.2 139.2 155.4 145.9 168.1 95.8 130.5 130.5 140.3 136.7 157.2 96.1
85 142.3 142.3 159.1 159.1 175.6 138.7 139.0 139.0 154.1 154.1 168.3 136.4 129.9 129.9 139.1 139.1 157.3 139.8
90 141.6 141.6 158.4 158.4 174.9 157.5 138.0 138.0 153.5 153.5 166.2 166.2 129.3 129.3 138.5 138.5 155.6 155.6
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
115 120 125
Ent Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 105.5 99.4 122.0 73.9 132.1 44.4 100.8 97.4 114.1 70.5 128.5 44.5 54.5 52.5 62.1 48.5 71.1 30.7
4000 80 105.2 105.2 121.7 97.6 131.9 68.2 100.5 100.5 113.8 93.4 128.3 66.1 54.3 54.3 61.9 60.0 70.8 45.6
85 105.0 105.0 121.5 121.1 131.6 92.3 100.3 100.3 113.6 112.9 128.1 87.5 54.0 54.0 61.6 61.6 70.5 61.7
90 104.7 104.7 121.3 121.3 131.2 116.5 100.1 100.1 113.3 113.3 127.8 108.6 53.8 53.8 61.4 61.4 70.3 70.3
75 108.5 105.9 125.3 82.8 135.0 48.4 103.8 102.5 117.4 78.8 132.3 56.9 56.7 55.8 64.4 54.4 73.7 39.1
4500 80 108.2 108.2 125.0 104.4 135.1 74.6 103.1 103.1 116.9 102.8 131.0 83.8 56.3 56.3 64.2 64.2 73.4 54.5
85 107.8 107.8 124.7 124.7 135.6 98.9 102.9 102.9 116.8 116.0 131.9 109.6 56.0 56.0 63.9 63.9 73.1 69.6
90 107.5 107.5 124.3 124.3 135.0 122.6 102.7 102.7 116.2 116.2 131.6 131.6 55.9 55.9 63.5 63.5 72.9 72.9
75 111.8 110.3 128.9 92.2 139.7 53.3 109.8 108.6 120.8 87.8 135.0 50.0 60.4 58.9 66.9 60.9 75.8 35.2
5000 80 111.5 111.5 128.7 120.2 139.5 92.9 109.3 108.7 120.5 106.3 135.3 71.2 60.1 60.1 66.7 66.7 75.8 49.9
85 110.9 110.7 128.1 128.1 139.3 131.8 109.1 109.1 120.0 119.3 135.7 93.2 59.8 59.8 66.2 66.2 75.8 67.2
90 110.5 110.5 127.6 127.6 138.5 138.5 108.8 108.8 119.4 119.4 136.0 115.6 59.7 59.7 65.9 65.9 75.7 75.7
75 115.1 113.7 132.5 102.1 142.5 58.5 116.0 114.3 124.2 97.4 137.8 44.0 64.3 63.1 69.4 67.6 78.0 31.9
5500 80 114.9 114.9 132.5 132.4 142.9 99.4 115.7 115.7 124.1 109.6 139.7 88.7 64.1 64.1 69.3 69.3 78.8 61.9
85 114.1 114.1 131.6 131.6 143.0 137.6 115.6 115.6 123.3 123.3 139.6 124.5 63.8 63.8 68.7 68.7 78.5 78.5
90 113.6 113.6 130.9 130.9 142.0 142.0 115.3 115.3 122.7 122.7 139.2 139.2 63.4 63.4 68.3 68.3 78.2 78.2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBh = Total gross capacity
3. SHC = Sensible heat capacity
4. Ambient Temperature above 120°F, the system B shuts down.

RT-PRC091F-EN 21
Performance Data

Evaporator Fan Performance


7.5 Tons
Table 8. Belt drive evaporator fan performance - 7.5 tons with low gas heat - GCC90A(3,4)EL - downflow airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Standard Motor
2400 — — — — — — — — — — — — — — 725 1.12 748 1.28 773 1.43

2700 — — — — — — — — — — 718 1.26 742 1.39 766 1.51 789 1.64 815 1.76

3000 — — — — — — 710 1.25 735 1.37 761 1.49 784 1.61 808 1.74 832 1.86 863 2.02

3300 — — — — 724 1.36 749 1.49 776 1.63 803 1.77 829 1.89 861 2.06 883 2.18 906 2.31
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

High Static (oversize) Motor


2400 799 1.59 823 1.76 854 1.88 877 2.06 900 2.17 924 2.28 949 2.40 971 2.50 996 2.61 1020 2.71

2700 841 1.88 872 2.04 897 2.16 921 2.27 944 2.38 967 2.50 990 2.62 1013 2.72 1036 2.82 1059 2.93

3000 885 2.13 908 2.25 933 2.36 956 2.48 979 2.59 1002 2.70 1026 2.80 1049 2.91 1073 3.02 — —

3300 930 2.44 954 2.58 977 2.70 999 2.82 1025 2.93 1048 3.03 — — — — — — — —

Table 9. Belt drive evaporator fan performance - 7.5 tons with low gas heat - GCC90A(3,4)EL - horizontal airflow

External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — — — 711 1.02 734 1.18 759 1.32

2700 — — — — — — — — — — — — 728 1.28 752 1.40 775 1.52 801 1.65

3000 — — — — — — — — 721 1.26 747 1.39 768 1.51 794 1.64 818 1.76 849 1.91

3300 — — — — 713 1.26 739 1.39 766 1.52 789 1.67 815 1.79 847 1.95 869 2.08 892 2.20

External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 776 1.41 809 1.66 840 1.76 863 1.94 885 2.05 909 2.15 934 2.27 956 2.37 981 2.48 1005 2.58

2700 827 1.77 858 1.93 882 2.03 906 2.15 929 2.26 952 2.38 975 2.49 998 2.60 1021 2.69 1044 2.80

3000 871 2.03 894 2.14 918 2.25 943 2.37 966 2.47 988 2.58 1012 2.69 1037 2.79 1061 2.90 1084 3.01

3300 915 2.34 939 2.47 962 2.59 985 2.70 1011 2.81 1034 2.90 1056 3.02 — — — — — —

22 RT-PRC091F-EN
Performance Data

Table 10. Belt drive evaporator fan performance - 7.5 tons with med gas heat - GCC90A(3,4)EM - downflow airflow

External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — — — 723 1.11 746 1.27 771 1.41

2700 — — — — — — — — — — 716 1.24 740 1.37 764 1.49 787 1.62 813 1.74

3000 — — — — — — — — 733 1.36 751 1.39 782 1.60 806 1.73 830 1.85 861 2.00

3300 — — — — 722 1.36 742 1.41 774 1.62 801 1.76 827 1.88 856 2.04 881 2.16 904 2.29

External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 797 1.57 821 1.74 852 1.84 875 2.02 898 2.13 922 2.24 946 2.36 968 2.46 993 2.57 1017 2.67

2700 839 1.86 870 2.02 895 2.13 918 2.23 941 2.35 964 2.47 987 2.58 1010 2.68 1033 2.78 1056 2.89

3000 883 2.11 906 2.23 931 2.34 953 2.45 976 2.56 999 2.67 1023 2.77 1046 2.87 1067 2.99 — —

3300 928 2.42 952 2.56 974 2.67 996 2.79 1022 2.90 1045 3.01 — — — — — — — —

Table 11. Belt drive evaporator fan performance - 7.5 tons with med gas heat - GCC90A(3,4)EM - horizontal airflow

External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — 713 1.09 737 1.21 760 1.37 785 1.52

2700 — — — — — — — — — — 730 1.35 754 1.48 778 1.60 801 1.73 827 1.85

3000 — — — — — — 722 1.34 747 1.46 773 1.58 796 1.70 820 1.83 844 1.95 875 2.11

3300 — — — — 736 1.45 761 1.58 788 1.72 815 1.86 841 1.98 873 2.15 895 2.27 918 2.40

External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 811 1.68 835 1.85 866 1.97 889 2.15 912 2.26 936 2.37 961 2.49 983 2.59 1008 2.70 1032 2.80

2700 853 1.97 884 2.13 909 2.25 933 2.36 956 2.47 979 2.59 1002 2.71 1025 2.81 1048 2.91 1071 3.02

3000 897 2.22 920 2.34 945 2.45 968 2.57 991 2.68 1014 2.79 1038 2.89 1061 3.00 — — — —

3300 942 2.53 966 2.67 989 2.79 1011 2.91 1037 3.02 — — — — — — — — — —

RT-PRC091F-EN 23
Performance Data

Table 12. Belt drive evaporator fan performance - 7.5 tons with high gas heat - GCC90A(3,4)EH - downflow airflow

External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — — — 733 1.17 756 1.32 781 1.47

2700 — — — — — — — — — — 726 1.30 750 1.43 774 1.55 797 1.68 823 1.80

3000 — — — — — — 718 1.30 743 1.41 760 1.45 792 1.66 816 1.78 840 1.90 871 2.06

3300 — — — — 732 1.41 752 1.46 784 1.68 811 1.82 837 1.94 869 2.10 891 2.22 913 2.35

External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 807 1.63 831 1.80 862 1.96 884 2.08 907 2.19 931 2.30 956 2.42 978 2.52 1003 2.63 1027 2.73

2700 849 1.92 879 2.08 904 2.18 928 2.29 951 2.41 974 2.52 997 2.63 1020 2.74 1043 2.84 1066 2.95

3000 893 2.17 915 2.29 940 2.39 963 2.51 986 2.62 1009 2.73 1033 2.82 1056 2.93 1078 3.05 — —

3300 937 2.48 961 2.61 984 2.73 1006 2.85 1032 2.96 1055 3.07 — — — — — — — —

Table 13. Belt drive evaporator fan performance - 7.5 tons with high gas heat - GCC90A(3,4)EH - horizontal airflow

External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — 723 1.15 747 1.27 770 1.43 795 1.58

2700 — — — — — — — — 716 1.29 740 1.41 764 1.54 788 1.66 811 1.79 837 1.91

3000 — — — — — — 732 1.40 757 1.52 783 1.64 806 1.76 830 1.89 854 2.01 885 2.17

3300 — — — — 746 1.51 771 1.64 798 1.78 825 1.92 851 2.04 883 2.21 905 2.33 928 2.46

External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 821 1.74 845 1.91 876 2.09 899 2.21 922 2.32 946 2.43 971 2.55 993 2.65 1018 2.76 1042 2.86

2700 863 2.03 894 2.19 919 2.31 943 2.42 966 2.53 989 2.65 1012 2.77 1035 2.87 1058 2.97 1081 3.08

3000 907 2.28 930 2.40 955 2.51 978 2.63 1001 2.74 1024 2.85 1048 2.95 1071 3.06 — — — —

3300 952 2.59 976 2.73 999 2.85 1021 2.97 1047 3.08 — — — — — — — — — —

24 RT-PRC091F-EN
Performance Data

Table 14. Belt drive evaporator fan performance - 7.5 tons cooling only - ECC150A(3,4)E0 - downflow airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

2400 — — — — — — — — — — — — — — — — 714 1.05 739 1.20

2700 — — — — — — — — — — — — — — 732 1.27 755 1.40 781 1.52

3000 — — — — — — — — — — 727 1.26 750 1.38 774 1.50 799 1.62 828 1.75

3300 — — — — — — 715 1.26 742 1.40 769 1.53 794 1.65 826 1.79 848 1.95 871 2.08
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor

2400 765 1.35 789 1.51 820 1.64 843 1.76 866 1.93 889 2.03 914 2.15 936 2.25 961 2.36 985 2.46

2700 800 1.58 837 1.77 862 1.92 886 2.03 909 2.14 932 2.25 955 2.37 978 2.47 1001 2.57 1024 2.68

3000 850 1.87 873 2.02 898 2.12 921 2.24 944 2.35 967 2.46 991 2.56 1014 2.66 1038 2.77 1060 2.89

3300 895 2.20 919 2.34 942 2.46 964 2.58 990 2.68 1013 2.78 1038 2.89 1051 3.01 — — — —

Table 15. Belt drive evaporator fan performance - 7.5 tons cooling only - ECC150A(3,4)E0 - horizontal airflow

External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — — — — — 728 1.15 753 1.30

2700 — — — — — — — — — — — — 722 1.26 746 1.38 769 1.51 795 1.63

3000 — — — — — — — — 715 1.24 741 1.36 764 1.48 788 1.61 812 1.73 843 1.85

3300 — — — — — — 729 1.36 756 1.50 783 1.64 809 1.76 841 1.89 863 2.05 886 2.18

External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 779 1.46 803 1.63 834 1.75 857 1.87 880 2.04 904 2.15 929 2.27 951 2.37 976 2.48 1000 2.58

2700 821 1.75 852 1.88 877 2.03 901 2.14 924 2.25 947 2.37 970 2.49 993 2.59 1016 2.69 1039 2.80

3000 865 1.97 888 2.12 913 2.23 936 2.35 959 2.46 982 2.57 1006 2.67 1029 2.78 1053 2.89 1075 3.01

3300 910 2.31 934 2.45 957 2.57 979 2.69 1005 2.80 1028 2.90 1053 3.01 — — — — — —

RT-PRC091F-EN 25
Performance Data

8.5 Tons
Table 16. Belt drive evaporator fan performance - 8.5 tons with low gas heat - GCC102A(3,4)EL - downflow airflow

External Static Pressure (Inches of Water)


0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

2700 — — — — — — — — — — 752 1.17 779 1.34 804 1.50 830 1.66 855 1.82

3050 — — — — — — — — 745 1.18 771 1.35 796 1.52 820 1.69 845 1.86 878 2.18

3400 — — — — 748 1.29 773 1.44 797 1.59 821 1.77 845 1.94 876 2.29 898 2.46 920 2.62

3750 747 1.45 773 1.62 799 1.78 824 1.95 847 2.12 875 2.45 897 2.61 919 2.75 941 2.91 963 3.05

External Static Pressure (Inches of Water)


1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
2700 878 1.95 910 2.21 932 2.30 954 2.43 977 2.57 999 2.70 1021 2.82 1043 2.96 1065 3.09 1087 3.21

3050 900 2.34 922 2.49 944 2.60 966 2.72 988 2.85 1010 2.95 1032 3.04 1054 3.14 1076 3.22 1098 3.30

3400 942 2.77 964 2.89 986 3.00 1008 3.09 1025 3.20 1051 3.30 1072 3.39 1095 3.47 1117 3.55 1140 3.66

3750 985 3.20 1007 3.31 1029 3.41 1051 3.52 1071 3.63 1092 3.71 1116 3.82 1135 3.91 1158 4.01 1181 4.08

Table 17. Belt drive evaporator fan performance - 8.5 tons with low gas heat - GCC102A(3,4)EL - horizontal airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

2700 — — — — — — — — — — — — 742 1.25 766 1.40 790 1.55 814 1.70

3050 — — — — — — — — — — 734 1.26 758 1.42 781 1.58 805 1.74 836 2.04

3400 — — — — — — 736 1.35 759 1.49 782 1.65 805 1.81 834 2.14 855 2.30 876 2.45

3750 — — 736 1.51 761 1.66 785 1.82 807 1.98 833 2.29 854 2.44 875 2.57 896 2.72 917 2.85
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
2700 836 1.82 867 2.07 888 2.15 909 2.27 930 2.40 951 2.52 972 2.64 993 2.77 1014 2.89 1035 3.00

3050 857 2.19 878 2.33 899 2.43 920 2.54 941 2.66 962 2.76 983 2.84 1004 2.93 1025 3.01 1046 3.08

3400 897 2.59 918 2.70 939 2.80 962 2.89 983 2.99 1001 3.08 1022 3.17 1042 3.24 1068 3.32 1084 3.42

3750 938 2.99 959 3.09 980 3.19 1002 3.29 1022 3.39 1042 3.47 1063 3.57 1081 3.65 1103 3.75 1123 3.81

26 RT-PRC091F-EN
Performance Data

Table 18. Belt drive evaporator fan performance - 8.5 tons with med gas heat - GCC102A(3,4)EM- downflow airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

2700 — — — — — — — — 735 1.21 762 1.36 789 1.52 814 1.68 839 1.83 863 1.98

3050 — — — — — — — — 771 1.35 796 1.52 820 1.69 845 1.86 878 2.18 900 2.34

3400 — — 732 1.33 758 1.47 783 1.63 807 1.77 830 1.93 862 2.18 884 2.43 906 2.59 927 2.74

3750 755 1.64 783 1.79 809 1.94 833 2.11 861 2.43 883 2.58 904 2.73 926 2.87 948 3.02 969 3.15
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
2700 896 2.19 918 2.36 939 2.44 961 2.56 983 2.69 1004 2.82 1026 2.94 1048 3.07 1069 3.19 1091 3.30

3050 922 2.49 944 2.60 966 2.72 988 2.85 1010 2.95 1032 3.04 1054 3.14 1076 3.22 1098 3.30 1102 3.38

3400 949 2.89 970 3.00 992 3.10 1014 3.19 1035 3.29 1057 3.38 1078 3.47 1100 3.55 1122 3.63 1143 3.73

3750 991 3.29 1013 3.40 1034 3.50 1056 3.60 1077 3.70 1099 3.78 1121 3.88 1142 3.96 1164 4.05 1185 4.13

Table 19. Belt drive evaporator fan performance - 8.5 tons with med gas heat - GCC102A(3,4)EM- horizontal airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

2700 — — — — — — — — — — — — 752 1.42 775 1.57 799 1.71 822 1.85

3050 — — — — — — — — — — 744 1.43 767 1.59 790 1.74 823 2.02 844 2.18

3400 — — — — — — 746 1.52 768 1.65 791 1.81 821 2.04 842 2.27 862 2.42 883 2.57

3750 — — 746 1.67 770 1.81 794 1.98 820 2.27 841 2.41 861 2.56 882 2.68 903 2.82 923 2.94
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
2700 854 2.05 874 2.20 895 2.28 915 2.39 936 2.52 956 2.63 977 2.75 998 2.87 1018 2.98 1039 3.09

3050 864 2.32 885 2.45 906 2.55 926 2.65 947 2.76 967 2.86 988 2.94 1008 3.02 1029 3.10 1050 3.16

3400 904 2.70 924 2.80 945 2.90 965 2.98 986 3.08 1006 3.16 1027 3.24 1048 3.32 1068 3.39 1089 3.49

3750 944 3.08 964 3.17 985 3.27 1005 3.36 1026 3.46 1047 3.53 1067 3.63 1088 3.70 1108 3.78 1129 3.86

RT-PRC091F-EN 27
Performance Data

Table 20. Belt drive evaporator fan performance - 8.5 tons with high gas heat - GCC102A(3,4)EH - downflow airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static
Standard Motor (oversize)
Motor
2700 — — — — — — — — 753 1.28 780 1.44 805 1.61 831 1.77 856 1.93 881 2.09

3050 — — — — — — 742 1.35 774 1.47 797 1.62 822 1.79 846 1.96 882 2.28 904 2.45

3400 — — 744 1.44 775 1.57 799 1.71 823 1.86 847 2.03 880 2.39 902 2.56 924 2.73 946 2.89

3750 773 1.72 799 1.88 825 2.04 851 2.23 879 2.56 901 2.72 923 2.88 945 3.02 967 3.18 989 3.32
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

2700 915 2.33 937 2.48 959 2.57 981 2.70 1003 2.84 1025 2.96 1047 3.09 1069 3.23 1091 3.36 1113 3.48

3050 926 2.61 948 2.76 970 2.87 992 2.99 1014 3.11 1036 3.22 1058 3.31 1080 3.40 1103 3.49 1125 3.56

3400 968 3.04 990 3.16 1012 3.26 1034 3.36 1056 3.47 1078 3.56 1100 3.65 1122 3.73 1145 3.82 1167 3.93

3750 1011 3.47 1033 3.57 1055 3.68 1077 3.79 1099 3.89 1121 3.98 1143 4.09 1166 4.17 1188 4.26 1210 4.34

Table 21. Belt drive evaporator fan performance - 8.5 tons with high gas heat - GCC102A(3,4)EH - horizontal airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

2700 — — — — — — — — — — 743 1.35 767 1.50 791 1.65 815 1.80 839 1.95

3050 — — — — — — — — 737 1.37 759 1.51 783 1.67 806 1.83 840 2.13 861 2.29

3400 — — — — 738 1.47 761 1.60 784 1.74 807 1.90 838 2.23 859 2.39 880 2.55 901 2.70

3750 736 1.61 761 1.76 786 1.91 810 2.08 837 2.39 858 2.54 879 2.69 900 2.82 921 2.97 942 3.10
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

2700 871 2.18 892 2.32 913 2.40 934 2.52 955 2.65 976 2.77 997 2.89 1018 3.02 1039 3.14 1060 3.25

3050 882 2.44 903 2.58 924 2.68 945 2.79 966 2.91 987 3.01 1008 3.09 1029 3.18 1050 3.26 1071 3.33

3400 922 2.84 943 2.95 964 3.05 985 3.14 1006 3.24 1027 3.33 1048 3.41 1069 3.49 1090 3.57 1111 3.67

3750 963 3.24 984 3.34 1005 3.44 1026 3.54 1047 3.64 1068 3.72 1089 3.82 1110 3.90 1131 3.98 1152 4.06

28 RT-PRC091F-EN
Performance Data

Table 22. Belt drive evaporator fan performance - 8.5 tons cooling only - ECC102A(3,4)E0 - downflow airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

2700 — — — — — — — — — — — — 745 1.14 763 1.31 788 1.45 810 1.59

3050 — — — — — — — — 732 1.22 753 1.38 775 1.49 799 1.64 819 1.80 840 1.94

3400 — — — — — — 745 1.39 766 1.56 794 1.71 817 1.87 842 2.03 866 2.20 892 2.46

3750 — — 733 1.52 756 1.67 784 1.81 801 1.93 828 2.09 853 2.25 877 2.52 902 2.68 927 2.82
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor

2700 828 1.75 848 1.91 876 2.08 899 2.34 921 2.46 945 2.57 968 2.68 992 2.78 1016 2.88 1039 2.98

3050 867 2.22 890 2.35 915 2.47 934 2.59 958 2.70 980 2.80 1005 2.91 1028 3.01 1052 3.11 1073 3.20

3400 918 2.61 939 2.73 960 2.85 986 2.97 1008 3.08 1031 3.17 1050 3.27 1073 3.37 1090 3.47 1113 3.56

3750 951 2.95 974 3.08 994 3.19 1011 3.31 1035 3.42 1054 3.53 1076 3.63 1096 3.73 1120 3.83 1138 3.93

Table 23. Belt drive evaporator fan performance - 8.5 tons cooling only - ECC102A(3,4)E0 - horizontal airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

2700 — — — — — — — — — — — — — — 741 1.25 765 1.38 786 1.52

3050 — — — — — — — — — — 731 1.31 752 1.42 776 1.56 795 1.71 816 1.85

3400 — — — — — — — — 744 1.49 771 1.63 793 1.78 817 1.93 841 2.09 866 2.34

3750 — — — — 734 1.59 761 1.72 778 1.84 804 1.99 828 2.14 851 2.40 876 2.55 900 2.69
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor

2700 804 1.66 823 1.82 845 1.98 873 2.23 894 2.34 917 2.45 940 2.55 963 2.65 986 2.74 1009 2.84

3050 842 2.11 864 2.24 888 2.35 907 2.46 930 2.57 951 2.67 976 2.77 998 2.86 1021 2.96 1042 3.05

3400 891 2.48 912 2.60 932 2.72 957 2.83 979 2.93 1001 3.02 1019 3.12 1042 3.21 1058 3.30 1081 3.39

3750 923 2.81 946 2.93 965 3.04 982 3.15 1005 3.26 1023 3.36 1045 3.46 1064 3.55 1087 3.65 1105 3.74

RT-PRC091F-EN 29
Performance Data

10 Tons
Table 24. Belt drive evaporator fan performance - 10 tons with low gas heat - GCC120A(3,4)EL - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — — — 737 1.34 761 1.49 785 1.64 809 1.79 833 1.94 857 2.09
3600 — — — — 739 1.46 760 1.58 782 1.72 804 1.86 828 2.02 851 2.18 875 2.34 906 2.64
4000 737 1.59 760 1.71 782 1.86 805 1.99 828 2.13 851 2.29 874 2.45 903 2.78 924 2.94 945 3.09
4400 780 2.03 805 2.18 830 2.33 854 2.49 876 2.65 902 2.96 923 3.11 944 3.24 965 3.39 986 3.52
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
3200 879 2.21 910 2.46 931 2.54 952 2.66 973 2.79 994 2.91 1015 3.03 1036 3.16 1057 3.28 1078 3.39
3600 927 2.79 948 2.93 969 3.03 990 3.14 1011 3.26 1032 3.36 1053 3.44 1074 3.53 1095 3.61 1116 3.68
4000 966 3.23 987 3.34 1008 3.44 1031 3.53 1052 3.63 1072 3.72 1093 3.81 1116 3.88 1137 3.96 1159 4.06
4400 1007 3.66 1028 3.76 1049 3.86 1071 3.96 1092 4.06 1113 4.14 1135 4.24 1156 4.32 1178 4.42 1201 4.48

Table 25. Belt drive evaporator fan performance - 10 tons with low gas heat - GCC120A(3,4)EL - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 729 1.36 753 1.51 777 1.66 801 1.81 825 1.96 849 2.11 873 2.26
3600 — — 733 1.52 755 1.62 776 1.75 798 1.89 820 2.03 844 2.19 867 2.35 891 2.53 922 2.81
4000 753 1.76 776 1.88 798 2.02 821 2.16 844 2.31 867 2.45 892 2.61 919 2.95 940 3.11 961 3.26
4400 796 2.21 821 2.35 846 2.51 866 2.67 887 2.84 918 3.13 939 3.28 960 3.42 981 3.56 1002 3.69
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
3200 905 2.49 926 2.61 947 2.72 968 2.83 989 2.96 1010 3.08 1031 3.2 1052 3.33 1073 3.45 1094 3.56
3600 943 2.96 964 3.09 985 3.22 1006 3.32 1027 3.43 1048 3.53 1069 3.62 1090 3.69 1111 3.78 1132 3.85
4000 982 3.39 1003 3.51 1024 3.61 1045 3.69 1066 3.81 1087 3.89 1108 3.97 1129 4.05 1150 4.13 1171 4.22
4400 1023 3.82 1044 3.93 1065 4.03 1086 4.13 1107 4.23 1128 4.32 1149 4.41 1170 4.49 1191 4.57 1212 4.65

30 RT-PRC091F-EN
Performance Data

Table 26. Belt drive evaporator fan performance - 10 tons with med gas heat - GCC120A(3,4)EM- downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 738 1.44 762 1.59 786 1.74 810 1.89 834 2.04 858 2.19 882 2.34
3600 — — 742 1.59 764 1.71 785 1.83 807 1.97 829 2.11 853 2.27 876 2.43 910 2.73 931 2.89
4000 762 1.84 785 1.96 807 2.11 830 2.24 853 2.38 876 2.54 907 2.87 928 3.03 949 3.19 970 3.34
4400 805 2.28 830 2.43 855 2.58 879 2.75 906 3.06 927 3.21 948 3.36 969 3.49 990 3.64 1011 3.77
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
3200 914 2.57 935 2.71 956 2.79 977 2.91 998 3.04 1019 3.16 1040 3.28 1061 3.41 1082 3.53 1103 3.64
3600 952 3.04 973 3.18 994 3.28 1015 3.39 1036 3.51 1057 3.61 1078 3.69 1099 3.78 1120 3.86 1141 3.93
4000 991 3.48 1012 3.59 1033 3.69 1054 3.78 1075 3.88 1096 3.97 1117 4.05 1138 4.13 1159 4.21 1180 4.31
4400 1032 3.91 1053 4.01 1074 4.11 1095 4.21 1116 4.31 1137 4.39 1158 4.49 1179 4.57 1200 4.65 1221 4.73

Table 27. Belt drive evaporator fan performance - 10 tons with med gas heat - GCC120A(3,4)EM - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 754 1.62 778 1.77 802 1.92 826 2.07 850 2.22 874 2.37 898 2.52
3600 736 1.67 758 1.78 780 1.88 801 2.01 823 2.15 845 2.29 869 2.45 892 2.61 926 2.91 947 3.07
4000 778 2.02 801 2.14 823 2.28 846 2.42 869 2.56 902 2.88 923 3.05 944 3.21 965 3.37 986 3.52
4400 821 2.46 846 2.61 871 2.76 901 3.08 922 3.24 943 3.39 964 3.54 985 3.68 1006 3.82 1027 3.95
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
3200 930 2.75 951 2.88 972 2.98 993 3.09 1014 3.22 1035 3.34 1056 3.46 1077 3.59 1098 3.71 1119 3.82
3600 968 3.22 989 3.35 1010 3.47 1031 3.58 1052 3.69 1073 3.79 1094 3.88 1115 3.96 1136 4.04 1157 4.11
4000 1007 3.66 1028 3.77 1049 3.87 1070 3.96 1091 4.06 1112 4.15 1133 4.23 1154 4.31 1175 4.39 1196 4.48
4400 1048 4.08 1069 4.19 1090 4.29 1111 4.39 1132 4.49 1153 4.58 1174 4.67 1195 4.75 1216 4.83 1237 4.91

RT-PRC091F-EN 31
Performance Data

Table 28. Belt drive evaporator fan performance - 10 tons with high gas heat - GCC120A(3,4)EH - downflow airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 738 1.44 762 1.59 786 1.74 810 1.89 834 2.04 858 2.19 882 2.34
3600 — — 742 1.59 764 1.71 785 1.83 807 1.97 829 2.11 853 2.27 876 2.43 910 2.73 931 2.89
4000 762 1.84 785 1.96 807 2.11 830 2.24 853 2.38 876 2.54 907 2.87 928 3.03 949 3.19 970 3.34
4400 805 2.28 830 2.43 855 2.58 879 2.75 906 3.06 927 3.21 948 3.36 969 3.49 990 3.64 1011 3.77
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
3200 914 2.57 935 2.71 956 2.79 977 2.91 998 3.04 1019 3.16 1040 3.28 1061 3.41 1082 3.53 1103 3.64
3600 952 3.04 973 3.18 994 3.28 1015 3.39 1036 3.51 1057 3.61 1078 3.69 1099 3.78 1120 3.86 1141 3.93
4000 991 3.48 1012 3.59 1033 3.69 1054 3.78 1075 3.88 1096 3.97 1117 4.05 1138 4.13 1159 4.21 1180 4.31
4400 1032 3.91 1053 4.01 1074 4.11 1095 4.21 1116 4.31 1137 4.39 1158 4.49 1179 4.57 1200 4.65 1221 4.73

Table 29. Belt drive evaporator fan performance - 10 tons with high gas heat - GCC120A(3,4)EH - horizontal airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 754 1.62 778 1.77 802 1.92 826 2.07 850 2.22 874 2.37 898 2.52
3600 736 1.67 758 1.78 780 1.88 801 2.01 823 2.15 845 2.29 869 2.45 892 2.61 926 2.91 947 3.07
4000 778 2.02 801 2.14 823 2.28 846 2.42 869 2.56 902 2.88 923 3.05 944 3.21 965 3.37 986 3.52
4400 821 2.46 846 2.61 871 2.76 901 3.08 922 3.24 943 3.39 964 3.54 985 3.68 1006 3.82 1027 3.95
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
3200 930 2.75 951 2.88 972 2.98 993 3.09 1014 3.22 1035 3.34 1056 3.46 1077 3.59 1098 3.71 1119 3.82
3600 968 3.22 989 3.35 1010 3.47 1031 3.58 1052 3.69 1073 3.79 1094 3.88 1115 3.96 1136 4.04 1157 4.11
4000 1007 3.66 1028 3.77 1049 3.87 1070 3.96 1091 4.06 1112 4.15 1133 4.23 1154 4.31 1175 4.39 1196 4.48
4400 1048 4.08 1069 4.19 1090 4.29 1111 4.39 1132 4.49 1153 4.58 1174 4.67 1195 4.75 1216 4.83 1237 4.91

32 RT-PRC091F-EN
Performance Data

Table 30. Belt drive evaporator fan performance - 10 tons cooling only - ECC120A(3,4)E0 - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — — — — — — — 758 1.55 782 1.69 807 1.84 833 2.01
3600 — — — — — — — — 736 1.55 770 1.83 798 1.95 820 2.09 845 2.26 870 2.41
4000 — — — — — — 752 1.85 782 2.06 809 2.21 836 2.37 860 2.54 882 2.71 914 2.99
4400 — — 745 2.08 772 2.19 799 2.34 825 2.47 852 2.63 876 2.79 909 3.08 934 3.24 958 3.39
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
3200 858 2.17 881 2.34 913 2.62 936 2.74 959 2.85 982 2.96 1005 3.07 1028 3.17 1051 3.27 1074 3.37
3600 896 2.59 926 2.84 949 2.96 972 3.08 995 3.19 1018 3.3 1041 3.41 1064 3.51 1087 3.61 1110 3.71
4000 939 3.14 962 3.27 985 3.39 1008 3.51 1031 3.62 1054 3.72 1077 3.82 1100 3.92 1123 4.02 1146 4.12
4400 981 3.52 1004 3.65 1027 3.77 1050 3.89 1073 3.99 1096 4.11 1119 4.22 1142 4.32 1165 4.42 1188 4.52

Table 31. Belt drive evaporator fan performance - 10 tons cooling only - ECC120A(3,4)E0 - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — — — — — 747 1.61 774 1.73 798 1.87 823 2.02 849 2.18
3600 — — — — — — — — 752 1.73 786 2.01 814 2.13 836 2.28 861 2.44 886 2.59
4000 — — — — 742 1.85 768 2.03 798 2.24 825 2.39 852 2.55 876 2.72 898 2.89 930 3.16
4400 735 2.17 761 2.26 788 2.38 815 2.52 841 2.65 868 2.81 892 2.97 925 3.25 950 3.41 974 3.56
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
3200 874 2.35 897 2.52 929 2.79 952 2.91 975 3.02 998 3.13 1021 3.24 1044 3.34 1067 3.44 1090 3.54
3600 919 2.87 942 3.01 965 3.13 988 3.25 1011 3.36 1034 3.47 1057 3.58 1080 3.68 1103 3.78 1126 3.88
4000 955 3.31 978 3.44 1001 3.56 1024 3.68 1047 3.79 1070 3.89 1093 3.99 1116 4.09 1139 4.19 1162 4.29
4400 997 3.69 1020 3.82 1043 3.94 1066 4.06 1089 4.17 1112 4.28 1135 4.39 1158 4.49 1181 4.59 1204 4.69

RT-PRC091F-EN 33
Performance Data

12.5 Tons
Table 32. Belt drive evaporator fan performance - 12.5 tons with low heat heat - GCC150A(3,4)EL - downflow airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

4000 — — — — — — 793 2.09 820 2.24 847 2.38 873 2.52 899 2.66 924 2.77 949 2.89

4500 — — 791 2.23 816 2.41 842 2.58 869 2.76 897 2.91 925 3.19 951 3.37 977 3.53 1002 3.69

5000 822 2.56 848 2.76 874 2.93 899 3.26 924 3.41 950 3.59 976 3.77 1001 3.96 1028 4.11 1056 4.27

5500 873 2.99 899 3.31 925 3.46 950 3.63 975 3.81 999 3.99 1024 4.17 1049 4.36 1075 4.53 1101 4.71

External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

4000 973 3.12 997 3.26 1020 3.37 1043 3.48 1065 3.59 1087 3.73 1108 3.86 1129 3.97 1149 4.09 1169 4.18

4500 1026 3.86 1050 4.01 1073 4.16 1095 4.31 1117 4.44 1141 4.56 1166 4.64 1191 4.72 1213 4.79 1235 4.86

5000 1083 4.42 1109 4.57 1135 4.72 1160 4.87 1185 5.02 1212 5.18 1236 5.33 — — — — — —

5500 1125 4.89 1149 5.07 1181 5.22 1204 5.34 1228 5.49 — — — — — — — — — —

Table 33. Belt drive evaporator fan performance - 12.5 tons with low gas heat - GCC150A(3,4)EL - horizontal airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

4000 — — — — 773 2.03 801 2.18 828 2.33 855 2.47 881 2.61 907 2.74 932 2.86 957 2.98

4500 — — 799 2.32 824 2.51 850 2.67 877 2.84 905 3.02 933 3.28 959 3.46 985 3.62 1010 3.78

5000 830 2.65 856 2.84 882 3.02 915 3.34 932 3.52 958 3.68 984 3.86 1009 4.04 1036 4.21 1064 4.36

5500 881 3.08 916 3.41 937 3.54 958 3.72 983 3.89 1007 4.08 1032 4.26 1057 4.44 1083 4.62 1109 4.79
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

4000 981 3.21 1005 3.34 1028 3.46 1051 3.57 1073 3.68 1095 3.82 1116 3.94 1137 4.06 1157 4.18 1177 4.27

4500 1034 3.94 1058 4.12 1081 4.25 1103 4.40 1125 4.53 1149 4.64 1174 4.73 1199 4.81 1221 4.88 1243 4.94

5000 1091 4.51 1117 4.66 1143 4.81 1168 4.96 1193 5.11 1218 5.24 — — — — — — — —

5500 1133 4.98 1157 5.16 1183 5.29 1211 5.42 — — — — — — — — — — — —

34 RT-PRC091F-EN
Performance Data

Table 34. Belt drive evaporator fan performance - 12.5 tons with med gas heat - GCC150A(3,4)EM- downflow airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

4000 — — — — 783 2.09 811 2.24 838 2.39 865 2.53 891 2.67 917 2.81 942 2.92 967 3.04

4500 — — 809 2.38 834 2.56 860 2.73 887 2.91 915 3.06 943 3.34 969 3.52 995 3.68 1020 3.84

5000 840 2.71 866 2.91 892 3.08 917 3.41 942 3.56 968 3.74 994 3.92 1019 4.11 1046 4.26 1074 4.42

5500 891 3.14 917 3.46 943 3.61 968 3.78 993 3.96 1017 4.14 1042 4.32 1067 4.51 1093 4.68 1119 4.86
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

4000 991 3.27 1015 3.41 1038 3.52 1061 3.63 1083 3.74 1105 3.88 1126 4.01 1147 4.12 1167 4.24 1187 4.33

4500 1044 4.01 1068 4.16 1091 4.31 1113 4.46 1135 4.59 1159 4.71 1184 4.79 1209 4.87 1231 4.94 1253 5.01

5000 1101 4.57 1127 4.72 1153 4.87 1178 5.02 1203 5.17 1230 5.33 — — — — — — — —

5500 1143 5.04 1167 5.22 1199 5.37 1222 5.49 — — — — — — — — — — — —

Table 35. Belt drive evaporator fan performance - 12.5 tons with med gas heat - GCC150A(3,4)EM - horizontal airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

4000 — — 770 2.07 798 2.24 826 2.39 853 2.54 880 2.68 906 2.82 932 2.95 957 3.07 982 3.19

4500 802 2.35 824 2.53 849 2.71 875 2.88 902 3.05 930 3.21 958 3.49 984 3.67 1010 3.83 1035 3.99

5000 855 2.86 881 3.05 907 3.23 932 3.55 957 3.71 983 3.89 1009 4.07 1034 4.25 1061 4.41 1089 4.57

5500 906 3.29 932 3.61 958 3.75 983 3.93 1008 4.11 1032 4.29 1057 4.47 1082 4.65 1108 4.83 1134 5.01
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

4000 1006 3.42 1030 3.55 1053 3.67 1076 3.78 1098 3.89 1120 4.03 1141 4.15 1162 4.27 1182 4.39 1202 4.48

4500 1059 4.15 1083 4.31 1106 4.46 1128 4.61 1150 4.74 1174 4.85 1199 4.94 1224 5.02 1246 5.09 1268 5.15

5000 1116 4.72 1142 4.87 1168 5.02 1193 5.17 1218 5.32 — — — — — — — — — —

5500 1158 5.19 1182 5.37 — — — — — — — — — — — — — — — —

RT-PRC091F-EN 35
Performance Data

Table 36. Belt drive evaporator fan performance - 12.5 tons with high gas heat - GCC150A(3,4)EH - downflow airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

4000 — — — — 783 2.09 811 2.24 838 2.39 865 2.53 891 2.67 917 2.81 942 2.92 967 3.04

4500 — — 809 2.38 834 2.56 860 2.73 887 2.91 915 3.06 943 3.34 969 3.52 995 3.68 1020 3.84

5000 840 2.71 866 2.91 892 3.08 917 3.41 942 3.56 968 3.74 994 3.92 1019 4.11 1046 4.26 1074 4.42

5500 891 3.14 917 3.46 943 3.61 968 3.78 993 3.96 1017 4.14 1042 4.32 1067 4.51 1093 4.68 1119 4.86
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

4000 991 3.27 1015 3.41 1038 3.52 1061 3.63 1083 3.74 1105 3.88 1126 4.01 1147 4.12 1167 4.24 1187 4.33

4500 1044 4.01 1068 4.16 1091 4.31 1113 4.46 1135 4.59 1159 4.71 1184 4.79 1209 4.87 1231 4.94 1253 5.01

5000 1101 4.57 1127 4.72 1153 4.87 1178 5.02 1203 5.17 1230 5.33 — — — — — — — —

5500 1143 5.04 1167 5.22 1199 5.37 1222 5.49 — — — — — — — — — — — —

Table 37. Belt drive evaporator fan performance - 12.5 tons with high gas heat - GCC150A(3,4)EH - horizontal airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

4000 — — 770 2.07 798 2.24 826 2.39 853 2.54 880 2.68 906 2.82 932 2.95 957 3.07 982 3.19

4500 802 2.35 824 2.53 849 2.71 875 2.88 902 3.05 930 3.21 958 3.49 984 3.67 1010 3.83 1035 3.99

5000 855 2.86 881 3.05 907 3.23 932 3.55 957 3.71 983 3.89 1009 4.07 1034 4.25 1061 4.41 1089 4.57

5500 906 3.29 932 3.61 958 3.75 983 3.93 1008 4.11 1032 4.29 1057 4.47 1082 4.65 1108 4.83 1134 5.01
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

4000 1006 3.42 1030 3.55 1053 3.67 1076 3.78 1098 3.89 1120 4.03 1141 4.15 1162 4.27 1182 4.39 1202 4.48

4500 1059 4.15 1083 4.31 1106 4.46 1128 4.61 1150 4.74 1174 4.85 1199 4.94 1224 5.02 1246 5.09 1268 5.15

5000 1116 4.72 1142 4.87 1168 5.02 1193 5.17 1218 5.32 — — — — — — — — — —

5500 1158 5.19 1182 5.37 — — — — — — — — — — — — — — — —

36 RT-PRC091F-EN
Performance Data

Table 38. Belt drive evaporator fan performance - 12.5 tons cooling only - ECC150A(3,4)E0 - downflow airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

4000 — — — — — — 747 1.89 769 2.06 790 2.23 811 2.38 833 2.57 856 2.74 879 2.91

4500 — — 759 2.12 787 2.35 808 2.52 829 2.69 851 2.86 874 3.03 906 3.31 929 3.46 952 3.58

5000 807 2.52 828 2.68 854 2.85 871 3.02 903 3.31 928 3.46 952 3.62 976 3.78 999 3.93 1022 4.07

5500 870 2.99 882 3.15 914 3.43 937 3.59 960 3.75 983 3.91 1006 4.06 1029 4.22 1052 4.38 1075 4.52
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

4000 911 3.19 932 3.33 952 3.45 972 3.56 992 3.66 1011 3.76 1030 3.86 1050 3.95 1071 4.04 1094 4.14

4500 974 3.74 995 3.88 1015 4.01 1035 4.11 1055 4.21 1074 4.31 1093 4.41 1113 4.51 1134 4.59 1157 4.69

5000 1044 4.21 1065 4.34 1085 4.46 1105 4.58 1125 4.68 1144 4.78 1163 4.88 1183 4.98 1204 5.08 1227 5.18

5500 1097 4.66 1118 4.79 1138 4.91 1158 5.02 1178 5.12 1197 5.22 1216 5.32 — — — — — —

Table 39. Belt drive evaporator fan performance - 12.5 tons cooling only - ECC150A(3,4)E0 - horizontal airflow
External Static Pressure (Inches of Water)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor

4000 — — — — 742 1.85 763 2.02 785 2.19 806 2.36 827 2.53 849 2.7 872 2.87 895 3.04

4500 745 2.06 775 2.25 803 2.48 824 2.65 845 2.82 867 2.99 890 3.16 922 3.44 945 3.59 968 3.73

5000 823 2.65 844 2.81 870 2.98 887 3.15 919 3.43 944 3.59 968 3.75 992 3.91 1015 4.06 1038 4.2

5500 886 3.12 898 3.28 930 3.56 953 3.72 976 3.88 999 4.04 1022 4.19 1045 4.35 1068 4.51 1091 4.65
External Static Pressure (Inches of Water)

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor

4000 927 3.32 948 3.46 968 3.58 988 3.69 1008 3.79 1027 3.89 1046 3.99 1066 4.08 1087 4.17 1110 4.27

4500 990 3.87 1011 4.01 1031 4.13 1051 4.24 1071 4.34 1090 4.44 1109 4.54 1129 4.63 1150 4.72 1173 4.82

5000 1060 4.34 1081 4.47 1101 4.59 1121 4.71 1141 4.81 1160 4.91 1179 5.01 1199 5.11 1220 5.21 1243 5.31

5500 1113 4.79 1134 4.92 1154 5.04 1174 5.15 1194 5.25 1213 5.35 1232 5.45 — — — — — —
Notes:
1. The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor should
use only industry-recognized procedures.
2. Each ton of cooling requires between 300 and 450 cubic feet of air per minute (CFM), or 320 CFM nominally.
3. Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.
4. Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver treated air along the perimerter of the space. If they
are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Return air grilles must be properly sized to
carry air back to the blower. If they are too small, they also cause noise.
5. The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living space.
6. An air velocity meter or airflow hood can give a reading of system CFM.

RT-PRC091F-EN 37
Performance Data

Table 40. Standard motor and drive/fan speed (rpm)


Unit Model 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns
Tons Fan Sheave 1 Turn Open Closed
Number Open Open Open Open Open
ECC090
7.5 15-15 716 743 772 798 824 850 879
GCC090
ECC102
8.5 15-15 735 762 790 817 844 871 898
GCC102
ECC120
10 15-15 735 762 790 817 844 871 898
GCC120
ECC150 735 762 790 817 844 871 898
12.5 15-16
GCC150 770 806 843 878 912 948 982
Note: Factory Set at closed.

Table 41. High Static (Oversize) motor and drive/fan speed (rpm)

Tons Unit Model Number Fan Sheave 6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed

ECC090
7.5 15-15 885 946 978 1047 1108 1175 1229
GCC090

ECC102
8.5 15-15 900 959 994 1060 1124 1189 1243
GCC102

ECC120
10 15-15 900 959 994 1060 1124 1189 1243
GCC120

ECC150
12.5 15-16 916 975 1031 1090 1148 1209 1268
GCC150

Note: Factory Set at closed.

Table 42. Static pressure drop through accessories (inches water column)
Unit Model Standard Standard Electric Heater
Tons Cfm
Number Filters Economizer 10.4 16 25 32 41 50
2400 0.01 — 0.005 0.005 0.050 0.01 0.01 —
E/GCC090A
3000 0.03 — 0.010 0.010 0.010 0.02 0.02 —
(Downflow)
3375 0.04 — 0.015 0.015 0.015 0.03 0.03 —
7.5
2400 0.01 — 0.005 0.005 0.050 0.01 0.01 —
E/GCC090A
3000 0.03 — 0.010 0.010 0.010 0.02 0.02 —
(Horizontal)
3375 0.04 — 0.015 0.015 0.015 0.03 0.03 —
2720 0.02 — 0.010 0.010 0.010 0.02 0.02 —
E/GCC102A
3400 0.04 — 0.015 0.015 0.015 0.03 0.03 —
(Downflow)
3825 0.05 — 0.020 0.020 0.020 0.04 0.04 —
8.5
2720 0.02 — 0.010 0.010 0.010 0.02 0.02 —
E/GCC102A
3400 0.04 — 0.015 0.015 0.015 0.03 0.03 —
(Horizontal)
3825 0.05 — 0.020 0.020 0.020 0.04 0.04 —
3200 0.03 — 0.015 0.015 — 0.03 0.03 0.03
E/GCC120A
4000 0.05 — 0.020 0.020 — 0.04 0.04 0.04
(Downflow)
4500 0.07 — 0.025 0.025 — 0.05 0.05 0.05
10
3200 0.03 — 0.015 0.015 — 0.03 0.03 0.03
E/GCC120A
4000 0.05 — 0.020 0.020 — 0.04 0.04 0.04
(Horizontal)
4500 0.07 — 0.025 0.025 — 0.05 0.05 0.05
4000 0.05 — 0.020 0.020 — 0.04 0.04 0.04
E/GCC150A
5000 0.07 — 0.030 0.030 — 0.06 0.06 0.06
(Downflow)
5625 0.09 — 0.035 0.035 — 0.07 0.07 0.07
12.5 4000 0.05 — 0.020 0.020 — 0.04 0.04 0.04
E/GCC150A 5000 0.07 — 0.030 0.030 — 0.06 0.06 0.06
(Horizontal)
5625 0.09 — 0.035 0.035 — 0.07 0.07 0.07

38 RT-PRC091F-EN
Performance Data

Table 43. Gas fired heating capacities


Tons Gas Heat Option Heating Input(MBh)(a) Heating Output(MBh)(a) Air Temp Rise
Low 125/87.5 100/70 15-45
7.5 Medium 180/126 144/100 20-65
High 225/157.5 180/125 25-70
Low 125/87.5 100/70 15-45
8.5 Medium 180/126 144/100 20-65
High 225/157.5 180/125 25-70
Low 180/125 144/100 20-50
10 Medium 225/157.5 180/125 25-60
High 250/200 200/160 30-65
Low 180/125 144/100 15-50
12.5 Medium 225/157.5 180/125 20-60
High 250/200 200/160 25-65
(a) For two stage heaters (input or output), second stage is total heating capacity. Second stage/first stage.

Table 44. Auxiliary electric heat capacity


Ton(a) Stage 1 Stage 2
Unit Model
Tons kW MBh No. of Stages kW MBh kW MBh
Number
Input(b) Output Input Output Input Output
EHK-10C(UL) 10.4 35.49 1 10.4 35.49 — —
EHK-15C(UL) 16 54.59 1 16 54.59 — —

7.5 EHK-25C(UL) 25 85.30 1 25 85.30 — —


EHK-32C(UL) 32 109.19 2 16 54.59 16 54.59
EHK-41C(UL) 41 139.90 2 25 85.30 16 54.59
EHK-10C(UL) 10.4 35.49 1 10.4 35.49 — —
EHK-15C(UL) 16 54.59 1 16 54.59 — —

8.5 EHK-25C(UL) 25 85.30 1 25 85.30 — —


EHK-32C(UL) 32 109.19 2 16 54.59 16 54.59
EHK-41C(UL) 41 139.90 2 25 85.30 16 54.59
EHK-10C(UL) 10.4 35.49 1 10.4 35.49 — —
EHK-15C(UL) 16 54.59 1 16 54.59 — —

10 EHK-32C(UL) 32 109.19 2 16 54.59 16 54.59


EHK-41C(UL) 41 139.90 2 25 85.30 16 54.59

EHK-50C(UL) 50 170.61 2 25 85.30 25 85.30


EHK-10C(UL) 10.4 35.49 1 10.4 35.49 — —
EHK-15C(UL) 16 54.59 1 16 54.59 — —

12.5 EHK-32C(UL) 32 109.19 2 16 54.59 16 54.59


EHK-41C(UL) 41 139.90 2 25 85.30 16 54.59

EHK-50C(UL) 50 170.61 2 25 85.30 25 85.30


(a) Heaters are rated at 240V, 480V, and 600V. For other than rated voltage, CAP = (voltage/rated voltage)2 x rated cap.
(b) For all input/output categories, does not include fan power or heat.

RT-PRC091F-EN 39
Performance Data

Table 45. Electric heater voltage correction factors (applicable to auxiliary heat capacity)
Nominal Voltage Distribution Voltage Capacity Multiplier
208 0.75
240 230 0.92
240 1.00
460 460 1.00

Table 46. Air temperature rise across electric heaters(°F)


7.5 Ton 8.5 Ton 10 Ton 12.5 Ton
kW Stages
3000 cfm 3400 cfm 4000 cfm 5000 cfm
10.4 1 10.7 9.9 8.2 6.8
16 1 14.6 13.8 12.6 10.9
25 1 22.4 22.4 — —
32 2 28.2 27.1 25.3 22.9
41 2 37.5 35.6 32.4 30.1
50 2 — — 39.5 37

40 RT-PRC091F-EN
Controls
Economizer Controls
The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two
optional controls, Reference Enthalpy Control and Comparative Enthalpy Control.

Reference Enthalpy Control


Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable
setpoint. Enthalpy control offers a higher level of comfort control, along with energy savings potential,
than the standard dry bulb control. This is due to the additional wet bulb sensing capability.

Comparative Enthalpy Control


Comparative Enthalpy replaces the standard dry bulb control with two sensors that compare total heat
content of the indoor air and outdoor air to determine the most efficient air source. This control option
offers the highest level of comfort control, plus energy efficiency, available.

Remote Potentiometer
Minimum position setting of economizer can be remotely adjusted with this accessory.

Thermostats
Model # Type Stages Display Type Features

TCONT302AS42DA Programmable 4H/2C Touchscreen Common preferred, not required 2/ 2 AA battery power

BAYSTAT814 Touchscreen 3H/2C Touchscreen Remote access via Pivot Mobile App

BAYSTAT300 Programmable 3H/2C Backlit Display and Keys BACnet MS-TP enabled

RT-PRC091F-EN 41
Electrical Data
Table 47. Unit wiring with cooling only (no electric heat) or gas heat
Standard Indoor Fan Motor Oversized Indoor Fan Motor
Unit Model Unit Operating Maximum Fuse Size Maximum Fuse Size
TONS Minimum Circuit Minimum Circuit
Number Voltage Range or Maximum Circuit or Maximum Circuit
Ampacity(a) Ampacity
Breaker Breaker
7.5 E/GCC090A 208-230 36 45 40 50
8.5 E/GCC102A 208-230 42 50 49 60
10 E/GCC120A 208-230 54 70 57 70
12.5 E/GCC150A 208-230 66 80 69 80
7.5 E/GCC090A 460 20 25 25 30
8.5 E/GCC102A 460 20 25 27 30
10 E/GCC120A 460 27 30 29 35
12.5 E/GCC150A 460 34 40 35 45
(a) For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.

Table 48. Unit wiring with electric heat (single point connection)

Standard Indoor Fan Motor Oversized Indoor Fan Motor

Unit Model Heater kW Maximum Fuse Maximum Fuse


TONS Control Stages Minimum Minimum
Number Rating Size or Size or
Circuit Circuit
Maximum Maximum
Ampacity Ampacity
Circuit Breaker Circuit Breaker

208/230 Volts Three Phase


BAYHTMA341A 41.0 2 116/133 125/150 122/139 125/150
BAYHTMA332A 32.0 2 93/106 100/110 99/112 100/125
7.5 BAYHTMA325A 25.0 1 75/85 80/90 81/91 90/100
BAYHTMA315A 16.0 1 51/58 60/60 57/64 60/70
BAYHTMA310A 10.0 1 37/41 45/45 43/47 50/50
BAYHTMA341A 41.0 2 116/133 125/150 126/142 150/150
BAYHTMA332A 32.0 2 93/106 100/110 102/115 110/125
8.5 BAYHTMA325A 25.0 1 75/85 80/90 84/94 90/100
BAYHTMA315A 16.0 1 51/58 60/60 60/67 60/70
BAYHTMA310A 10.0 1 42/42 50/50 49/50 60/60
BAYHTMA350A 50.0 2 146/136 150/150 149/139 150/150
BAYHTMA341A 41.0 2 122/139 125/150 126/142 150/150
10 BAYHTMA332A 32.0 2 99/112 100/125 102/115 110/125
BAYHTMA315A 16.0 1 57/64 70/70 60/67 70/70
BAYHTMA310A 10.0 1 54/54 70/70 57/57 70/70
BAYHTMA350A 50.0 2 146/136 150/150 149/139 150/150
BAYHTMA341A 41.0 2 122/139 125/150 126/142 150/150
12.5 BAYHTMA332A 32.0 2 99/112 100/125 102/115 110/125
BAYHTMA315A 16.0 1 66/66 80/80 69/69 90/90
BAYHTMA310A 10.0 1 66/66 80/80 69/69 90/90
460 Volts Three Phase
BAYHTMA441A 41.5 2 70 70 76 80
BAYHTMA433A 33.0 2 57 60 63 70
7.5 BAYHTMA425A 25.0 1 44 45 50 50
BAYHTMA416A 15.0 1 31 35 37 40
BAYHTMA414A 14.0 1 27 30 33 35
BAYHTMA441A 41.5 2 70 70 78 80
BAYHTMA433A 33.0 2 57 60 65 70
8.5 BAYHTMA425A 25.0 1 44 45 52 60
BAYHTMA416A 15.0 1 31 35 39 40
BAYHTMA414A 14.0 1 27 30 35 40

42 RT-PRC091F-EN
Electrical Data

Table 48. Unit wiring with electric heat (single point connection) (continued)

Standard Indoor Fan Motor Oversized Indoor Fan Motor

Unit Model Heater kW Maximum Fuse Maximum Fuse


TONS Control Stages Minimum Minimum
Number Rating Size or Size or
Circuit Circuit
Maximum Maximum
Ampacity Ampacity
Circuit Breaker Circuit Breaker
BAYHTMA450A 50.0 2 74 80 76 80
BAYHTMA441A 41.5 2 76 80 78 80
10 BAYHTMA433A 33.0 2 63 70 65 70
BAYHTMA416A 15.0 1 37 40 39 40
BAYHTMA414A 14.0 1 33 35 35 40
BAYHTMA450A 50.0 2 74 80 76 80
BAYHTMA441A 41.5 2 76 80 78 80
12.5 BAYHTMA433A 33.0 2 63 70 65 70
BAYHTMA416A 15.0 1 37 40 39 45
BAYHTMA414A 14.0 1 34 40 35 45

Table 49. Electrical characteristics – compressor motor and condenser motor

Compressor Motors Condenser Fan Motors


Unit Model
TONS Amps(a) Amps
Number
No. Volts Phase rpm No. Volts Phase hp
RLA LRA FLA
7.5 E/GCC090A 2 203-230 3 3500 11.6/10.4 123/73 2 208-230 3 1/3 1.5
8.5 E/GCC102A 2 203-230 3 3500 15.6/11.6 93/123 2 208-230 3 1/3 1.5
10 E/GCC120A 2 203-230 3 3500 15.6/18.6 93/137 2 208-230 3 1/3 1.5
12.5 E/GCC150A 2 203-230 3 3500 23.2/15.6 164/93 2 208-230 3 3/4 4.5
7.5 E/GCC090A 2 460 3 3500 6.0/6.4 60/38 2 460 3 1/3 0.87
8.5 E/GCC102A 2 460 3 3500 6.5/6.0 60/60 2 460 3 1/3 0.87
10 E/GCC120A 2 460 3 3500 6.5/7.8 60/52 2 460 3 1/3 0.87
12.5 E/GCC150A 2 460 3 3500 11.2/6.5 75/60 2 460 3 3/4 2.1
(a) For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.

Table 50. Electrical characteristics – evaporator fan motor


Standard Evaporator Fan Motor Oversized Evaporator Fan Motor
Unit Model
TONS Amps Amps
Number No. Volts Phase hp No. Volts Phase hp
FLA FLA
7.5 E/GCC090A 1 208-230 3 2 7.2 1 208-230 3 3 12.0

8.5 E/GCC102A 1 208-230 3 2 7.2 1 208-230 3 5 14.6

10 E/GCC120A 1 208-230 3 3 12.0 1 208-230 3 5 14.6

12.5 E/GCC150A 1 208-230 3 3 12.0 1 208-230 3 5 14.6

7.5 E/GCC090A 1 460 3 2 3.5 1 460 3 3 8.7

8.5 E/GCC102A 1 460 3 2 3.5 1 460 3 5 10.3

10 E/GCC120A 1 460 3 3 8.7 1 460 3 5 10.3

12.5 E/GCC150A 1 460 3 3 8.7 1 460 3 5 10.3

RT-PRC091F-EN 43
Electrical Data

Table 51. Electrical characteristics – combustion blower motor (gas heat units)
Combustion Blower Motor
Unit Model
TONS Amps
Number No. Volts Phase rpm
FLA
7.5 E/GCC090 1 208/230 1 2100 1.2

8.5 E/GCC105 1 208/230 1 2100 1.2

10 E/GCC120 1 208/230 1 2100 1.2

12.5 E/GCC150 1 208/230 1 2100 1.2

7.5 E/GCC090 1 220 1 2100 1.2

8.5 E/GCC105 1 220 1 2100 1.2

10 E/GCC120 1 220 1 2100 1.2

12.5 E/GCC150 1 220 1 2100 1.2

44 RT-PRC091F-EN
Jobsite Connections
Table 52. Typical number of wires

Thermostats

3 Wires, 24V, Cooling only


A
4 Wires 24V, with Electric Heat

B 3 Power Wires + 1 Ground Wire (three phase)

DISCONNECT
S W ITCH
( BY O T H E R S )

A
T H E RM O S TAT
RO O FTOP
UNIT

Notes:
• For specific wiring information, see the installation instructions.
• All wiring except power wire is low voltage.
• All customer supplied wiring to be copper and must conform to applicable electrical codes
and local electric codes. Wiring shown dotted is to be furnished and installed by the
customer.

RT-PRC091F-EN 45
Dimensional Data
Figure 1. Typical installation clearance for single and multiple unit applications (in inches)

END TO END
NOTE 2,3

SIDE BY SIDE
NOTE 2

NOTES:
1.FOR HORIZONTAL DISCHARGE UNIT,
THIS MEASURE IS REDUCED TO 1’ 6” NOTE 1
TO MINIMIZE DUCT EXTENSIONS.
4’ 0”
2.WHEN EQUIPPED WITH ECONOMIZER
OR BAROMETRIC RELIEF DAMPER, 1’ 6” Minimum clearance
CLERANCE DISTANCE IS TO BE 3’ 0” Side condensate drain is used
MEASURE FROM PROTRUDING HOOD
INSTEAD OF BASE. 1’ 6” Recommended service clearance
SINGLE UNIT 4’ 0” Unit disconnect is mounted on panel

3.CLEARANCE IS THE SAME IF ANY


UNIT IS ROTATED 180
0
5’ 0” WITH ECONOMIZER
3’ 0” WITHOUT ECONOMIZER

3.ADDITIONAL CLEARANCE REQUIRED


WHEN BAROMETRIC DAMPER OR
ECONOMIZER IS INSTALLED.

46 RT-PRC091F-EN
Dimensional Data

Figure 2. Cooling with optional electrical heat and gas/electric units — overview

C O N D E N S AT E
G A S C O N N E C TIO N D R AIN
IN SID E C O N N E C TIO N

Figure 3. Cooling with optional electrical heat and gas/electric units — front and side views (in inches)

2-3/4”
Ø2
Ø1-3/8”

2-3/4”
Ø2
48-5/16”
48-3/4”

Ø1-3/8”

44-3/16”
30-3/16”
6-5/16”

Ø7/8”

14-7/16”
2-5/16”
7-3/4” 23-3/4” 7-3/4”

7-3/4” 23-3/4” 7-3/4” 9-7/8”


37-15/16”
(GBC UNIT ONLY) 58-7/8”
88-7/16”

RT-PRC091F-EN 47
Dimensional Data

Figure 4. Cooling with optional electrical heat and gas/electric units — bottom view (in inches)
88-7/16”

25-5/8”
29-5/8” 14” 3-7/16”

12-7/16”

37-5/8”

40-11/16”
27-5/16”

12-3/8”
36-7/16” 3-7/16”

NOTES:
1.THROUGH THE BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.
2.VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION.

Figure 5. Cooling with optional electrical heat and gas/electric units — back view (horizontal configuration) (in
inches)
SUPPLY RETURN
36-7/16”
14”

5-5/8”
4-15/16”

27-5/16” 12-3/8” 4-9/16”

23”

53-3/16”

48 RT-PRC091F-EN
Dimensional Data

Figure 6. Cooling with optional electric heat and gas/electric models — roof curb (in inches)

15 1/2”

54 9/16” 32 1/4” 3.000 84 13/16”


19 3/8”
3.000 SUPPLY

15 13/16” 45 1/8”

37 15/16”
RETURN
3 9/16”
14.000

1 3/4”

54 9/16”
84 13/16”

Figure 7. Cooling with optional electric heat and gas/electric models — downflow unit clearance (in inches)

CLEARANCE 68” CLEARANCE 48”

UNIT OUTLINE

39 11/16” 54 5/8”

CLEARANCE 48”
CLEARANCE 60”

RT-PRC091F-EN 49
Weights
Table 53. Maximum unit and corner weights (lb) and center of gravity dimensions (in.)

Weights (lb)(a) , (b) Corner Weights(c) Center of Gravity (in.)


Tons Unit Model No.
Shipping Net A B C D Length Width

7.5 GCC090A 1087 1012 248 181 334 249 45.0 34.0

8.5 GCC102A 1111 1036 236 176 340 283 44.0 36.0

10 GCC120A 1133 1058 237 190 273 358 39.0 34.0

12.5 GCC150A 1235 1172 264 194 299 416 39.0 35.0

7.5 ECC090A 979 904 250 188 197 269 45.0 34.0

8.5 ECC102A 1003 928 252 187 200 289 44.0 36.0

10 ECC120A 1023 948 277 180 187 304 39.0 34.0

12.5 ECC150A 1124 1049 302 197 208 342 39.0 35.0
(a) Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
(b) Weights do not include additional factory or field installed options/accessories.
(c) Corner weights are given for information only. 7.5–12.5 ton models must be supported continuously by a curb or equivalent frame support.

Note: To calculate additional weight for accessories, see Accessory net weights table.
Table 54. Accessory net weight (lb)
Accessories Net weight (lb)

Electric Heaters Model # E/GCC090 E/GCC102 E/GCC120 E/GCC150


10 kW (240V) BAYHTMA310A 43.65 43.65 43.65 43.65
16 kW (240V) BAYHTMA315A 45.04 45.04 45.04 45.04
25 kW (240V) BAYHTMA325A 46.01 46.01 46.01 46.01
32 kW (240V) BAYHTMA332A 54.59 54.59 54.59 54.59
41 kW (240V) BAYHTMA341A 55.56 55.56 55.56 55.56
50 kW (240V) BAYHTMA350A 56.53 56.53 56.53 56.53
Oversized Motor
2 HP (230 / 460) — 37.5 37.5 37.5 37.5
3 HP (230 / 460) — 45.0 45.0 45.0 45.0
5 HP (230 / 460) — 53.0 53.0 53.0 53.0
External Vent Hood 2.8

Figure 8. Center of gravity/corner weights


C E N T E R O F G R AV I TY
LE N G T H
A B

CENTER O F
G R AV I TY
W I DTH

D C

50 RT-PRC091F-EN
Mechanical Specifications
General
• Packaged rooftop units cooling, heating capacities, and efficiencies are AHRI Certified within scope
of AHRI Standard (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air
Furnaces
• Packaged rooftop units are dedicated downflow or horizontal airflow
• Operating range between 125°F and 40°F in cooling standard from the factory
• Factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check
cooling operation, fan and blower rotation, and control sequence before leaving the factory
• Colored and numbered wring internal to the unit for simplified identification
• Units ETL listed and labeled, classified in accordance

Standard Features
Casing
• Zinc coated, heavy gauge, galvanized steel
• Weather-resistant baked enamel finish on phosphatized exterior surfaces
• Meets ASTM B117, 672 hour salt spray test
• Removable single side maintenance access panels
• Lifting handles in maintenance access panels (can be removed and reinstalled by removing no more
than 11 fasteners while providing a water and air tight seal)
• Exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2-inch, 1-
pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material
• Base of unit shall be insulated with 1/2-inch, 1-pound density, foil-faced, glass fiber material
• Base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8-inch
high downflow supply/return openings to provide an added water integrity precaution, if the
condensate drain backs up
• Downflow unit’s base pan shall have no penetrations within the perimeter of the curb other than the
raised 1 1/8-inch high supply/return openings to provide an added water integrity precaution, if the
condensate drain backs up
• Base of unit shall have provisions for forklift and crane lifting

Compressors
• All units have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps
• Suction gas-cooled motor with voltage utilization range of plus or minus 10 percent of unit
nameplate voltage
• Internal overloads standard with scroll compressors
• All models have phase monitors and Low and High Pressure Controls as standard

Discharge Line Thermostat


• A bi-metal element discharge line thermostat is installed as a standard option on the discharge line
of each system
• Provides extra protection to the compressors against high discharge temperatures in case of loss of
charge, extremely high ambient and other conditions which could drive the discharge temperature
higher
• Wired in series with high pressure control
• When discharge temperature rises above the protection limit, the bi-metal disc in the thermostat
switches to the off position, opening the 24 Vac circuit
• When temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit,
providing power to the compressor

RT-PRC091F-EN 51
Mechanical Specifications

Evaporator and Condenser Coils


• Microchannel coils burst tested by manufacturer
• Microchannel condenser coils standard on all units
• Coils leak tested to ensure the pressure integrity
• Evaporator coil and condenser coil leak tested to 225 psig and pressure tested to 450 psig
• Sloped condensate drain pans are standard

Filters
Two inch standard filters shall be factory supplied on all units.

Gas Heat Section


• Progressive tubular heat exchanger, stainless steel burners and corrosion resistant steel
• Induced draft combustion blower shall be used to pull the combustion products through the firing
tubes
• Heater shall use a direct spark ignition (DSI) system
• On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before
ignition
• After three unsuccessful ignition attempts, entire heating system shall be locked out until manually
reset at the thermostat/zone sensor
• Units shall be suitable for use with natural gas or propane (field-installed kit)

Indoor Fan
• Belt driven, FC centrifugal fans with adjustable motor sheaves
• Motors thermally protected
• Oversized motors available for high static application
• Indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT)

Locking Safety Device


• Pressure switch monitoring allows for lockout in a situation where the switch is opened
• By monitoring the Y input as well as the pressure switches, advanced decision making can be made
to identify situations where faults/errors occur

Outdoor Fans
• Outdoor fan shall be externally drive, statically and dynamically balanced, draw-through in the
vertical discharge position.
• Fan motor(s) shall be permanently lubricated and shall have current overload protection.

Refrigerant Circuits
• Each refrigerant circuit shall have a fixed orifice, service pressure ports, and refrigerant line filter
driers factory installed as standard
• An area shall be provided for replacement suction line driers

Refrigerant Pressure Control


All units include High and Low Pressure Cutouts as standard.

Unit Top
The top cover shall be double hemmed and gasket sealed to prevent water leakage.

52 RT-PRC091F-EN
Mechanical Specifications

Factory Installed Options


Multi-Speed Indoor Fan System
Incorporates a multi-speed fan control to change the speed of the fan to 70% of full airflow based off of
compressor stages

Oversized Motors
Oversized motors shall be available as a factory option for High Static applications.

Field Installed Options


Condensate Overflow Switch
This option shall shut the unit down in the event that a clogged condensate drain line prevents proper
condensate removal from the unit.

Demand Control Ventilation with CO2 Sensor


• CO2 sensor shall have the ability to monitor the concentration (parts per million, ppm) of CO2
(Carbon Dioxide) in the air
• As the CO2 concentration changes, the outside air damper modulates to meet the current ventilation
needs of the zone

Economizer (Standard) — Downflow


• Assembly includes fully modulating 0–100% motor and dampers, barometric relief, minimum
position setting, preset linkage, wiring harness with plug, fixed dry bulb and spring return actuator
• Barometric relief damper shall provide a pressure operated damper that shall be gravity closing and
shall prohibit entrance of outside air during the equipment “off” cycle

Economizer — Horizontal
The horizontal economizer shall contain the same features as the downflow economizer with the
exception of barometric relief.

Electric Heaters
• Electric heat modules shall be available for installation within the basic unit
• Elements shall be constructed of heavy-duty nickel chromium elements internally delta connected
for 240 volt, wye connected for volt
• Power assemblies shall provide single-point connection
• Electric heat modules shall be UL listed or CSA certified
• If ordering the Through the Base Electrical option with an Electric Heater, the heater must be factory
installed.

Hail Guards
Tool-less, hail protection quality coil guards are available for condenser coil protection.

Low Leak Economizer with Fault Detection & Diagnostics – Downflow


• Controller shall have the capability to provide the value of each sensor used in controlling the
economizer operation
• System status is also indicted for the following conditions:
– Free cooling available
– Economizer enabled
– Compressor enabled
– Heating Enabled

RT-PRC091F-EN 53
Mechanical Specifications

– Mixed air low limit cycle active


• Fault Detection and Diagnostic system detects the following faults:
– Air temperature sensor failure/fault
– Not economizing when conditions indicate system should be economizing
– Economizing when conditions indicate system should not be economizing
– Dampers are not modulating
– Excessive amounts of outside air are being introduced though the economizer
• Fault Detection and Diagnostic system is certified by the California Energy Commission as meeting
requirements of California Title 24 120.2(i)1 through 120.2(i)8 in accordance with Section 100(h)

Manual Outside Air Damper


Manually set outdoor air dampers shall provide up to 50% outside air.

Motorized Outside Air Damper


• Outdoor air dampers shall open to set position when indoor fan starts
• Damper shall close to the full closed position when indoor fan shuts down

Powered Exhaust
The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better
building pressurization.

Reference or Comparative Enthalpy


• Used to measure and communicate outdoor humidity
• Unit receives and uses this information to provide improved comfort cooling while using the
economizer
• Comparative Enthalpy measures and communicates humidity for both outdoor and return air
conditions, and return air temperature – unit receives and uses this information to maximize use of
economizer cooling, and to provide maximum occupant comfort control
• Reference or Comparative Enthalpy option shall be available when a factory or field installed
Downflow Economizer is ordered
• Option is available on all models

Remote Potentiometer
The minimum position setting of the economizer shall be adjusted with this accessory.

Through the Base Gas Piping


• Unit shall include a standard through the base gas provision
• Option shall have all piping necessary including, black steel, manual gas shut-off valve, elbows, and
union
• Manual shutoff valve shall include a 1/8-inch NPT pressure tap
• Assembly will require minor field labor to install (Gas/Electric Only)

Through the Base Utilities Access


• Electrical service entrance shall be provided allowing electrical access for both control and main
power connections inside the curb and through the base of the unit
• Option shall allow for field installation of liquid-tight conduit and an external field installed disconnect
switch

54 RT-PRC091F-EN
Notes

RT-PRC091F-EN 55
The AHRI Certified mark indicates Trane U.S. Inc. participation in the AHRI Certification program. For verification of individual certified products, go to
ahridirectory.org.

Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor
environments for commercial and residential applications. For more information, please visit trane.com or
tranetechnologies.com.

Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We