Trane A
Trane A
Through the years, Trane has designed and developed the most complete line of Packaged Rooftop
products available in the market today.
Trane customers demanded a product that provided exceptional reliability, was easy to install, and was
competitively priced.
Trane listened and is proud to introduce the new Foundation™ Light Commercial rooftop unit. With
Foundation, Trane continues to provide the highest standards in quality and reliability, comfort,
performance, and ease of installation. light commercial products.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in
whole or in part without written permission. Trane reserves the right to revise this publication at any
time, and to make changes to its content without obligation to notify any person of such revision or
change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
• Updated Convertible Units, Quick-Access Panels, Field Installed Options sections in Features and
Benefits chapter.
• Barometric Relief content moved to Features and Benefits chapter - Field Installed Options from
Application Considerations chapter.
• Updated General data tables.
• Updated Gross Cooling Capacities tables.
• Updated Gas fired heating capacities table in Performance Data chapter.
• Updated Electric heater voltage correction factors (applicable to auxiliary heat capacity) table in
Performance Data chapter.
• Removed TCONT402AN32DA content in Thermostats in Controls chapter.
• Updated Unit wiring with electric heat (single point connection) table in Electric Data chapter.
• Added 460V information to Unit wiring with cooling only (no electric heat) or gas heat and Electrical
characteristics tables in Electric Data chapter.
RT-PRC091F-EN 3
Table of Contents
Features and Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Standard and Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Outstanding Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Variety of Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Condensate Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Air Delivery Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4 RT-PRC091F-EN
Features and Benefits
Foundation™ has features and benefits that make it first class in the light commercial rooftop market.
Designed with input from field contractors and technicians, its convertible airflow and ease of installation
are outstanding.
Options(a)
Standard
Factory Installed Field Installed
5K SCCR X
Convertible Airflow X
Economizer (Downflow) X
Electric Heaters X
Filters X
Hail/Vandal Guards X
LP Conversion Kit X
Powered Exhaust X
Remote Potentiometer X
Scroll Compressors X
RT-PRC091F-EN 5
Features and Benefits
Medium Foundation
Options(a)
Standard
Factory Installed Field Installed
Compressors
Foundation™ contains the best compressor technology available to achieve the highest possible
performance.
Controls – Electromechanical
This 24-volt control includes the control transformer and contactor pressure lugs for power wiring.
Convertible Units
Foundation™ 7.5 to 12.5 ton units ship in the downflow configuration. Their convertible design makes it
easy to convert them to a horizontal airflow configuration without an additional kit.1
Efficiency
Product efficiencies meet the requirements of ASHRAE 90.1 - 2016.
Insulation
All panels in the evaporator section of the unit have foil-faced, glass fiber insulation. All base panels
have foil-faced, glass fiber insulation. All edges are either captured or sealed to ensure no insulation
fibers get into the airstream.
6 RT-PRC091F-EN
Features and Benefits
Heat Exchanger
The cabinet features a tubular heat exchanger in heat capacities – all available for vertical and
horizontal discharge directions. The heat exchanger is fabricated using aluminized steel burners and
corrosion-resistant, aluminized steel tubes as standard on all models. As part of the heat exchanger
assembly, an induced draft blower is used to pull the gas mixture through the burner tubes. A direct
spark ignition system, which doubles as a safety device to prove the flame, is used to ignite the gas
mixture.
Motors
All indoor fan motors are belt drive as standard.
Pressure Cutouts
Low and high pressure cutouts are standard on all Foundation™ models.
Quick-Access Panels
Remove screws (four or fewer) for access to the standardized internal components and wiring.
RT-PRC091F-EN 7
Features and Benefits
LP Conversion Kit
LP kits are provided as standard with each GCC 090-150 unit for conversion of gas heat units from
natural gas to propane.
Variety of Options
Factory Installed Options
Oversized Motors
Multi-speed only – Factory installed oversized motors are available for high static applications.
Economizer
Economizers are equipped with either dry bulb, reference, or comparative enthalpy sensing. These
economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly
installed, they offer valuable energy savings.
Electric Heaters
Electric heat is available as a field installed option.
8 RT-PRC091F-EN
Features and Benefits
Power Exhaust
This option is available on downflow units and provides exhaust of the return air, when using a downflow
economizer, to maintain proper building pressurization. This is an excellent option for relieving most
building overpressurization problems.
Barometric Relief
Designed to be used on downflow and horizontal configuration for standard and downflow low leak
economizer units, barometric relief is an unpowered means of relieving excess building pressure.
This product line offers an optional barometric relief damper for use in conjunction with economizer
option. This accessory consists of gravity dampers which open with increased pressure. As building
pressure increases, the pressure in the unit return air section also increases, opening the dampers and
relieving the conditioned space.
Notes:
• The effectiveness of barometric relief damper during economizing operation is system
related.
• Pressure drop of the return air system should be considered to control building
pressurization.
Remote Potentiometer
When installed in the economizer control circuitry, this accessory provides a method to remotely adjust
the minimum damper position.
Roof Curbs
Available for downflow units. Only one roof curb for all 7.5 to 12.5 ton Foundation™ units simplifies curb
selection.
Thermostats
Available in programmable and non-programmable.
Other Benefits
Easy to Install, Service and Maintain
Because today’s owners are very cost-conscious when it comes to service and maintenance,
Foundation was designed with direct input from service contractors. This valuable information helped to
design a product that would get the service technician off the job quicker and save the owner money.
Foundation does this by offering outstanding standard features enhanced by a variety of factory and
RT-PRC091F-EN 9
Features and Benefits
field installed options, multiple control options, rigorously tested proven designs and superior product
and technical support.
Outstanding Flexibility
The Foundation 7.5-12.5 ton units match the footprint of specific Carrier WeatherMaker™ units.
Rigorous Testing
All of Foundation’s designs were rigorously rain tested at the factory to ensure water integrity. Each part
of the top overlaps in such a way that water cannot leak into the unit. These overlapped edges are
gasketed and sealed to ensure superior water integrity.
Actual shipping tests were performed to determine packaging requirements. Factory shake tests were
used as part of the package design process to help assure that the unit arrives at the job site in top
condition.
For the microchannel coils, the supplier will perform the leak check at 450 psig. The completely
assembled refrigerant system is leak tested at a minimum of 225 psig with a refrigerant and nitrogen
mixture.
All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected
immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it
lives up to rigorous Trane requirements.
Unmatched Support
Trane Sales Representatives are a Support Group that can assist you with:
• Product
• Special Applications
• Application
• Specifications
• Service
• Computer Programs and much more
• Training
10 RT-PRC091F-EN
Application Considerations
Application of this product should be within the cataloged airflow and cooling considerations.
Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to ensure adequate
serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear
inadequate should be reviewed with local Trane sales personnel.
Condensate Trap
The evaporator is a draw-through configuration. A trap must be field provided prior to start-up on the
cooling cycle.
Unit Pitch
These units have sloped condensate drain pans. Units must be installed level. Any unit slope must be
toward access side of the unit.
RT-PRC091F-EN 11
Selection Procedure
Cooling Capacity
1. Calculate the building’s total and sensible cooling loads for the building at design conditions. Use
the following calculation methods or any other standard accepted method.
Factors used in unit selection:
• Total Cooling Load: 120 MBh
• Sensible Cooling Load: 96 MBh
• Airflow: 4000 cfm
• Electrical Characteristics: 460/60/3
• Summer Design Conditions: Entering Evaporator Coil: 80ºF DB/67ºF WB
• Outdoor Ambient: 95ºF
• External Static Pressure: 0.38 in. wg
• Rooftop – Downflow configuration
• Accessories: Roof Curb, Electric Heat
2. As a starting point, a rough determination must be made of the size of the unit. The final selection
will be made after examining the performance at the given conditions. Divide the total cooling load
by nominal Btuh per ton (12 MBh per ton); then round up to the nearest unit size.
120 MBh / 12 MBh = 10 Tons
3. shows that a GCC120A has a gross cooling capacity of 122.1 MBh and 96.3 MBh sensible capacity
at 4000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the evaporator.
Find capacity at intermediate conditions not in the table
When the design conditions are between two numbers that are in the capacity table, interpolation is
required to approximate the capacity.
Note: Extrapolation outside of the table conditions is not recommended.
4. In order to select the correct unit which meets the building’s requirements, the fan motor heat must
be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is
dependent on the effort by the motor - cfm and static pressure. To determine the total unit static
pressure you add the external static pressure to the additional static related by the added features:
Note: Reference heating capacity section on this page for determination of heater size. No additional static add for gas/heat
exchanger.
Note: The Evaporator Fan Performance has already accounted for the pressure drop for standard
filters and wet coils (see note below in ). Therefore, the actual total static pressure is 0.47 -
0.05 (from ) = 0.42 wg.
With 4000 cfm and 0.42 wg. shows 1.9 bhp for this unit. Note below the table is the formula to
calculate fan motor heat.
3-hp fan motor heat (MBh) = 2.90 x fan bhp + 0.4750
2.90 x 2.06 + 0.4750 = 5.435 MBh
Now subtract the fan motor heat from the gross cooling capacity of the unit:
Net Total Cooling Capacity = 122.1 MBh - 5.435 = 116.665 MBh.
12 RT-PRC091F-EN
Selection Procedure
Heating Capacity
Note: Heating capacity procedures DIFFER for cooling (E) and gas/electric (G) units.
1. Calculate the building heating load.
2. Size the system heating capacity to match the calculated building heating load. The following are
building heating requirements:
460 volt/3 phase Power Supply
Total heating load of 100.0 MBh
4000 cfm
The electric heat accessory capacities are listed in . From the table, a 2 kW heater will deliver 109.2
MBh at 480 volts. In order to determine capacity at 460 volts, the heater voltage correction factor
from must be used. Therefore, 109.2 MBh x 0.94 (voltage correction factor) = 102.6 MBh.
Gas/electric: Fuel natural gas total heating load of 100 MBh. shows 125 MBh and 180 MBh input
models. The output capacities of these furnaces are 70 MBh and 100 MBh respectively. The
medium heat model with 100 MBh output best matches the building requirements.
RT-PRC091F-EN 13
Model Number Description
14 RT-PRC091F-EN
General Data
Table 1. General data – 7.5 to 12.5 tons – 230 volts
7.5 Ton 8.5 Ton 10 Ton 12.5 Ton
E/GCC090 E/GCC105 E/GCC120 E/GCC150
Cooling Performance(a)
Gross Cooling Capacity 90000 102000 120000 150000
EER (Downflow/Horizontal) 11.2 11.2 11.2 11.0
Nominal Airflow CFM / AHRI Rated CFM 3200/3000 3700/3000 3700/3200 4600/4000
AHRI Net Cooling Capacity 86000 104000 114000 140000
Integrated Energy Efficiency Ratio (IEER) 14.8 14.8 14.8 14.2
Percent Capacity @ part load (Stage 1/Stage 2) 58/100 47/100 44/100 32/100
System Power (kW) 7.68 9.29 10.18 12.73
Compressor
Number/Type 2 / Scrolls 2 / Scrolls 2 / Scrolls 2 / Scrolls
Sound
Outdoor Sound Rating (BELS) 8.2 8.2 8.2 8.7
Outdoor Coil
Type Microchannel Microchannel Microchannel Microchannel
Coil Width (in.) (System A + System B 0.63+0.63 0.81+1.0 0.81+1.0 1.28+1.28
Face Area (sq. ft.) 23.81 27.38 27.38 27.38
Rows/FPI 1/23 1/23 1/23 1/23
Indoor Coil
Type Microchannel Microchannel Microchannel Microchannel
Tube Size (in.) ID 0.98 0.98 1.57 1.57
Face Area (sq. ft.) 12.88 12.88 12.88 12.88
Rows/FPI 3/17 3/17 4/17 4/17
Refrigerant Control EXV EXV EXV EXV
1 / 3/4 1 / 3/4 1 / 3/4 1 / 3/4
Drain Connection Number/Size (in.)
PVC Pipe Socket PVC Pipe Socket PVC Pipe Socket PVC Pipe Socket
Outdoor Fan
Type Propeller Propeller Propeller Propeller
Number Used/Diameter (in.) 2 / 23-1/2 2 / 23-1/2 2 / 23-1/2 2 / 23-1/2
Drive Type/No. Speeds Direct / 10 Direct / 10 Direct / 10 Direct / 10
cfm 8400 8300 8300 10000
Number Motors/hp 2 / 1/3HP 2 / 1/3HP 2 / 1/3HP 2 / 3/4HP
Motor rpm 960 960 960 1070
Indoor Fan
Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 1 / 15x15 1 / 15x15 1 / 15x15 1 / 15x15
Drive Type/No. Speeds Belt / 1 Belt / 1 Belt / 1 Belt / 1
Number Motors 1 1 1 1
Motor hp (Standard/Oversized) 2.0 / 3.0 2.0 / 5.0 3.0 / 5.0 3.0 / 5.0
Motor rpm (Standard/Oversized) 1725 1725 1725 1725
Motor Frame Size (Standard/Oversized) 56 / 56 56 / 56 56 / 56 56 / 56
Filters
Type Furnished Throwaway Throwaway Throwaway Throwaway
Number Size Recommended (4)20*20*2 (4)20*20*2 (4)20*20*2 (4)20*20*2
Refrigerant Charge (Pounds of R-410A)(b)
Circuit A 3.97 lbs 4.85 lbs 5.29 lbs 7.50 lbs
Circuit B 3.53 lbs 4.41 lbs 5.07 lbs 5.73 lbs
(a) Units are AHRI Certified to AHRI Standard 340-360 (I-P). Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F entering wet bulb with minimum
external static pressure as determined by rating standard.
(b) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
RT-PRC091F-EN 15
General Data
16 RT-PRC091F-EN
General Data
Natural Gas (minimum/maximum) 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc. 4.5 / 14.0 in. wc.
LP (minimum/maximum) 11.0/14.0 in. wc. 11.0/14.0 in. wc. 11.0/14.0 in. wc. 11.0/14.0 in. wc. 11.0/14.0 in. wc. 11.0/14.0 in. wc.
Gas Connection Pipe Size (in.) 1/2 1/2 3/4 1/2 3/4 3/4
(a) Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards
(ANSI). Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
RT-PRC091F-EN 17
Performance Data
Gross Cooling Capacities
Table 4. Gross cooling capacities 7.5 tons
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
Ent 85 95 105
CFM DB (° Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
F)
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 82.8 56.6 92.4 47.8 101.8 36.3 74.8 54.7 87.3 44.7 94.7 36.7 68.4 51.2 78.0 42.8 88.1 35.1
80 82.0 69.1 91.5 58.3 101.0 49.1 73.9 65.2 86.2 56.8 93.7 43.9 67.6 59.7 77.1 54.3 87.2 45.3
2400
85 81.6 76.7 91.2 64.7 100.9 61.4 73.5 70.7 85.7 64.5 92.7 52.4 67.2 64.1 76.6 61.6 86.2 50.1
90 81.4 77.3 90.9 66.7 100.6 76.5 73.3 73.3 85.5 67.5 92.8 55.1 67.0 67.0 76.4 64.5 86.2 52.7
75 86.1 62.2 95.8 52.6 105.2 40.1 78.0 60.2 90.6 49.2 98.3 45.5 71.5 56.3 81.3 47.1 91.6 43.5
80 85.3 75.6 94.9 63.8 104.7 53.8 77.0 71.3 89.5 62.1 96.7 45.9 70.7 65.3 80.3 59.4 90.0 43.9
2700
85 84.8 79.2 94.4 70.7 104.3 67.2 76.5 75.1 89.0 70.5 96.3 57.7 70.1 68.7 79.7 67.4 89.7 55.1
90 84.6 79.0 94.1 71.4 103.9 81.7 76.3 74.9 88.7 72.3 96.2 66.7 69.9 68.5 79.5 69.1 89.6 63.8
75 85.9 67.2 95.8 56.8 105.4 43.3 77.7 65.0 90.6 53.1 97.9 39.4 71.1 60.8 81.0 50.8 91.0 37.8
80 85.2 80.9 95.0 68.7 104.8 57.9 76.8 76.8 89.5 66.9 97.0 54.8 70.3 70.3 80.1 64.0 90.3 52.3
3000
85 84.6 80.3 94.3 76.1 104.3 72.4 76.2 76.2 88.7 75.9 96.4 70.1 69.7 69.7 79.4 72.6 89.7 67.0
90 84.3 80.1 93.9 75.4 103.9 86.4 75.9 75.9 88.4 76.4 96.0 85.0 69.4 69.4 79.1 73.0 89.3 81.1
75 87.6 73.1 97.7 61.9 107.5 47.1 79.4 70.7 92.4 57.9 99.3 34.7 72.6 66.2 82.7 55.3 92.4 33.4
80 87.0 77.1 97.0 74.4 106.9 62.8 78.6 78.6 91.4 72.5 99.3 65.9 71.8 71.8 81.8 69.4 92.4 63.0
3300
85 86.2 81.9 96.1 82.5 106.2 78.5 77.8 77.8 90.4 82.3 98.4 85.8 71.2 71.2 81.0 78.7 91.6 82.1
90 85.9 81.6 95.6 80.1 105.7 91.8 77.3 77.3 90.0 81.2 97.7 97.7 70.8 70.8 80.6 80.6 90.9 90.9
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
Ent 115 120 125
CFM DB (° Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
F)
61 67 73 61 67 73 61 67 73
MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 58.8 48.2 69.2 41.4 79.5 34.0 50.4 43.3 63.9 43.3 73.4 33.1 27.6 24.7 33.6 24.3 38.5 20.3
80 58.1 51.3 68.4 52.5 78.6 39.5 49.9 44.4 63.2 54.9 72.7 47.2 27.3 24.5 33.2 30.5 38.1 28.5
2400
85 57.8 56.4 68.0 59.7 77.8 48.4 49.5 49.5 62.8 57.8 71.9 42.8 27.1 27.1 33.0 32.0 37.7 25.9
90 57.6 57.6 67.9 62.1 77.7 50.9 49.1 49.1 62.7 62.7 71.6 49.7 26.9 26.9 32.9 32.0 37.5 29.9
75 61.7 53.0 72.3 45.7 82.4 36.5 53.2 47.6 67.0 47.6 76.7 41.2 30.0 27.4 36.1 27.0 41.2 25.3
80 61.0 56.2 71.5 57.6 81.7 42.7 52.5 48.5 66.2 59.6 75.4 41.5 29.7 27.0 35.7 33.3 40.5 25.5
2700
85 60.6 59.1 71.0 65.3 81.3 55.9 52.1 50.7 65.8 59.3 75.2 52.0 29.5 28.1 35.5 33.2 40.4 31.6
90 60.4 59.0 70.8 66.6 81.0 65.5 51.8 50.4 65.5 64.1 75.0 60.1 29.4 28.0 35.4 33.0 40.3 36.3
75 61.2 57.2 71.9 49.3 82.2 38.8 53.7 51.8 66.5 51.5 76.0 35.7 29.7 29.7 35.3 29.0 40.2 22.2
80 60.5 60.5 71.2 62.0 81.5 50.7 53.1 53.1 65.8 60.6 75.4 49.4 29.4 29.4 34.9 33.9 39.9 30.1
3000
85 60.0 60.0 70.6 70.4 81.0 64.8 52.7 52.7 65.3 60.1 74.9 63.2 29.2 29.2 34.6 33.6 39.6 38.1
90 59.8 59.8 70.3 70.3 80.7 78.4 52.5 52.5 65.0 65.0 74.9 65.6 29.1 29.1 34.5 33.5 39.6 39.5
75 62.3 62.3 73.5 53.7 83.9 41.8 56.2 56.2 68.0 56.1 77.2 31.6 31.3 31.3 36.3 31.8 41.1 20.0
80 61.9 61.9 72.8 67.3 83.3 60.7 55.6 55.6 67.3 62.1 77.4 59.5 31.0 31.0 36.0 35.0 41.1 36.2
3300
85 61.4 61.4 72.1 72.1 82.6 75.7 55.3 55.3 66.7 61.5 76.6 76.6 30.8 30.8 35.6 34.6 40.7 40.7
90 61.1 61.1 71.7 71.7 82.2 82.2 55.1 55.1 66.4 66.4 76.7 76.7 30.7 30.7 35.5 35.5 40.8 40.8
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBh = Total gross capacity
3. SHC = Sensible heat capacity
4. Ambient Temperature above 120°F, the system B shuts down.
18 RT-PRC091F-EN
Performance Data
RT-PRC091F-EN 19
Performance Data
20 RT-PRC091F-EN
Performance Data
RT-PRC091F-EN 21
Performance Data
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — — — 725 1.12 748 1.28 773 1.43
2700 — — — — — — — — — — 718 1.26 742 1.39 766 1.51 789 1.64 815 1.76
3000 — — — — — — 710 1.25 735 1.37 761 1.49 784 1.61 808 1.74 832 1.86 863 2.02
3300 — — — — 724 1.36 749 1.49 776 1.63 803 1.77 829 1.89 861 2.06 883 2.18 906 2.31
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2700 841 1.88 872 2.04 897 2.16 921 2.27 944 2.38 967 2.50 990 2.62 1013 2.72 1036 2.82 1059 2.93
3000 885 2.13 908 2.25 933 2.36 956 2.48 979 2.59 1002 2.70 1026 2.80 1049 2.91 1073 3.02 — —
3300 930 2.44 954 2.58 977 2.70 999 2.82 1025 2.93 1048 3.03 — — — — — — — —
Table 9. Belt drive evaporator fan performance - 7.5 tons with low gas heat - GCC90A(3,4)EL - horizontal airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — — — 711 1.02 734 1.18 759 1.32
3000 — — — — — — — — 721 1.26 747 1.39 768 1.51 794 1.64 818 1.76 849 1.91
3300 — — — — 713 1.26 739 1.39 766 1.52 789 1.67 815 1.79 847 1.95 869 2.08 892 2.20
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 776 1.41 809 1.66 840 1.76 863 1.94 885 2.05 909 2.15 934 2.27 956 2.37 981 2.48 1005 2.58
2700 827 1.77 858 1.93 882 2.03 906 2.15 929 2.26 952 2.38 975 2.49 998 2.60 1021 2.69 1044 2.80
3000 871 2.03 894 2.14 918 2.25 943 2.37 966 2.47 988 2.58 1012 2.69 1037 2.79 1061 2.90 1084 3.01
3300 915 2.34 939 2.47 962 2.59 985 2.70 1011 2.81 1034 2.90 1056 3.02 — — — — — —
22 RT-PRC091F-EN
Performance Data
Table 10. Belt drive evaporator fan performance - 7.5 tons with med gas heat - GCC90A(3,4)EM - downflow airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — — — 723 1.11 746 1.27 771 1.41
2700 — — — — — — — — — — 716 1.24 740 1.37 764 1.49 787 1.62 813 1.74
3000 — — — — — — — — 733 1.36 751 1.39 782 1.60 806 1.73 830 1.85 861 2.00
3300 — — — — 722 1.36 742 1.41 774 1.62 801 1.76 827 1.88 856 2.04 881 2.16 904 2.29
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 797 1.57 821 1.74 852 1.84 875 2.02 898 2.13 922 2.24 946 2.36 968 2.46 993 2.57 1017 2.67
2700 839 1.86 870 2.02 895 2.13 918 2.23 941 2.35 964 2.47 987 2.58 1010 2.68 1033 2.78 1056 2.89
3000 883 2.11 906 2.23 931 2.34 953 2.45 976 2.56 999 2.67 1023 2.77 1046 2.87 1067 2.99 — —
3300 928 2.42 952 2.56 974 2.67 996 2.79 1022 2.90 1045 3.01 — — — — — — — —
Table 11. Belt drive evaporator fan performance - 7.5 tons with med gas heat - GCC90A(3,4)EM - horizontal airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — 713 1.09 737 1.21 760 1.37 785 1.52
2700 — — — — — — — — — — 730 1.35 754 1.48 778 1.60 801 1.73 827 1.85
3000 — — — — — — 722 1.34 747 1.46 773 1.58 796 1.70 820 1.83 844 1.95 875 2.11
3300 — — — — 736 1.45 761 1.58 788 1.72 815 1.86 841 1.98 873 2.15 895 2.27 918 2.40
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 811 1.68 835 1.85 866 1.97 889 2.15 912 2.26 936 2.37 961 2.49 983 2.59 1008 2.70 1032 2.80
2700 853 1.97 884 2.13 909 2.25 933 2.36 956 2.47 979 2.59 1002 2.71 1025 2.81 1048 2.91 1071 3.02
3000 897 2.22 920 2.34 945 2.45 968 2.57 991 2.68 1014 2.79 1038 2.89 1061 3.00 — — — —
3300 942 2.53 966 2.67 989 2.79 1011 2.91 1037 3.02 — — — — — — — — — —
RT-PRC091F-EN 23
Performance Data
Table 12. Belt drive evaporator fan performance - 7.5 tons with high gas heat - GCC90A(3,4)EH - downflow airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — — — 733 1.17 756 1.32 781 1.47
2700 — — — — — — — — — — 726 1.30 750 1.43 774 1.55 797 1.68 823 1.80
3000 — — — — — — 718 1.30 743 1.41 760 1.45 792 1.66 816 1.78 840 1.90 871 2.06
3300 — — — — 732 1.41 752 1.46 784 1.68 811 1.82 837 1.94 869 2.10 891 2.22 913 2.35
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 807 1.63 831 1.80 862 1.96 884 2.08 907 2.19 931 2.30 956 2.42 978 2.52 1003 2.63 1027 2.73
2700 849 1.92 879 2.08 904 2.18 928 2.29 951 2.41 974 2.52 997 2.63 1020 2.74 1043 2.84 1066 2.95
3000 893 2.17 915 2.29 940 2.39 963 2.51 986 2.62 1009 2.73 1033 2.82 1056 2.93 1078 3.05 — —
3300 937 2.48 961 2.61 984 2.73 1006 2.85 1032 2.96 1055 3.07 — — — — — — — —
Table 13. Belt drive evaporator fan performance - 7.5 tons with high gas heat - GCC90A(3,4)EH - horizontal airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — 723 1.15 747 1.27 770 1.43 795 1.58
2700 — — — — — — — — 716 1.29 740 1.41 764 1.54 788 1.66 811 1.79 837 1.91
3000 — — — — — — 732 1.40 757 1.52 783 1.64 806 1.76 830 1.89 854 2.01 885 2.17
3300 — — — — 746 1.51 771 1.64 798 1.78 825 1.92 851 2.04 883 2.21 905 2.33 928 2.46
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 821 1.74 845 1.91 876 2.09 899 2.21 922 2.32 946 2.43 971 2.55 993 2.65 1018 2.76 1042 2.86
2700 863 2.03 894 2.19 919 2.31 943 2.42 966 2.53 989 2.65 1012 2.77 1035 2.87 1058 2.97 1081 3.08
3000 907 2.28 930 2.40 955 2.51 978 2.63 1001 2.74 1024 2.85 1048 2.95 1071 3.06 — — — —
3300 952 2.59 976 2.73 999 2.85 1021 2.97 1047 3.08 — — — — — — — — — —
24 RT-PRC091F-EN
Performance Data
Table 14. Belt drive evaporator fan performance - 7.5 tons cooling only - ECC150A(3,4)E0 - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3000 — — — — — — — — — — 727 1.26 750 1.38 774 1.50 799 1.62 828 1.75
3300 — — — — — — 715 1.26 742 1.40 769 1.53 794 1.65 826 1.79 848 1.95 871 2.08
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 765 1.35 789 1.51 820 1.64 843 1.76 866 1.93 889 2.03 914 2.15 936 2.25 961 2.36 985 2.46
2700 800 1.58 837 1.77 862 1.92 886 2.03 909 2.14 932 2.25 955 2.37 978 2.47 1001 2.57 1024 2.68
3000 850 1.87 873 2.02 898 2.12 921 2.24 944 2.35 967 2.46 991 2.56 1014 2.66 1038 2.77 1060 2.89
3300 895 2.20 919 2.34 942 2.46 964 2.58 990 2.68 1013 2.78 1038 2.89 1051 3.01 — — — —
Table 15. Belt drive evaporator fan performance - 7.5 tons cooling only - ECC150A(3,4)E0 - horizontal airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2400 — — — — — — — — — — — — — — — — 728 1.15 753 1.30
3000 — — — — — — — — 715 1.24 741 1.36 764 1.48 788 1.61 812 1.73 843 1.85
3300 — — — — — — 729 1.36 756 1.50 783 1.64 809 1.76 841 1.89 863 2.05 886 2.18
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2400 779 1.46 803 1.63 834 1.75 857 1.87 880 2.04 904 2.15 929 2.27 951 2.37 976 2.48 1000 2.58
2700 821 1.75 852 1.88 877 2.03 901 2.14 924 2.25 947 2.37 970 2.49 993 2.59 1016 2.69 1039 2.80
3000 865 1.97 888 2.12 913 2.23 936 2.35 959 2.46 982 2.57 1006 2.67 1029 2.78 1053 2.89 1075 3.01
3300 910 2.31 934 2.45 957 2.57 979 2.69 1005 2.80 1028 2.90 1053 3.01 — — — — — —
RT-PRC091F-EN 25
Performance Data
8.5 Tons
Table 16. Belt drive evaporator fan performance - 8.5 tons with low gas heat - GCC102A(3,4)EL - downflow airflow
2700 — — — — — — — — — — 752 1.17 779 1.34 804 1.50 830 1.66 855 1.82
3050 — — — — — — — — 745 1.18 771 1.35 796 1.52 820 1.69 845 1.86 878 2.18
3400 — — — — 748 1.29 773 1.44 797 1.59 821 1.77 845 1.94 876 2.29 898 2.46 920 2.62
3750 747 1.45 773 1.62 799 1.78 824 1.95 847 2.12 875 2.45 897 2.61 919 2.75 941 2.91 963 3.05
3050 900 2.34 922 2.49 944 2.60 966 2.72 988 2.85 1010 2.95 1032 3.04 1054 3.14 1076 3.22 1098 3.30
3400 942 2.77 964 2.89 986 3.00 1008 3.09 1025 3.20 1051 3.30 1072 3.39 1095 3.47 1117 3.55 1140 3.66
3750 985 3.20 1007 3.31 1029 3.41 1051 3.52 1071 3.63 1092 3.71 1116 3.82 1135 3.91 1158 4.01 1181 4.08
Table 17. Belt drive evaporator fan performance - 8.5 tons with low gas heat - GCC102A(3,4)EL - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3050 — — — — — — — — — — 734 1.26 758 1.42 781 1.58 805 1.74 836 2.04
3400 — — — — — — 736 1.35 759 1.49 782 1.65 805 1.81 834 2.14 855 2.30 876 2.45
3750 — — 736 1.51 761 1.66 785 1.82 807 1.98 833 2.29 854 2.44 875 2.57 896 2.72 917 2.85
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
2700 836 1.82 867 2.07 888 2.15 909 2.27 930 2.40 951 2.52 972 2.64 993 2.77 1014 2.89 1035 3.00
3050 857 2.19 878 2.33 899 2.43 920 2.54 941 2.66 962 2.76 983 2.84 1004 2.93 1025 3.01 1046 3.08
3400 897 2.59 918 2.70 939 2.80 962 2.89 983 2.99 1001 3.08 1022 3.17 1042 3.24 1068 3.32 1084 3.42
3750 938 2.99 959 3.09 980 3.19 1002 3.29 1022 3.39 1042 3.47 1063 3.57 1081 3.65 1103 3.75 1123 3.81
26 RT-PRC091F-EN
Performance Data
Table 18. Belt drive evaporator fan performance - 8.5 tons with med gas heat - GCC102A(3,4)EM- downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2700 — — — — — — — — 735 1.21 762 1.36 789 1.52 814 1.68 839 1.83 863 1.98
3050 — — — — — — — — 771 1.35 796 1.52 820 1.69 845 1.86 878 2.18 900 2.34
3400 — — 732 1.33 758 1.47 783 1.63 807 1.77 830 1.93 862 2.18 884 2.43 906 2.59 927 2.74
3750 755 1.64 783 1.79 809 1.94 833 2.11 861 2.43 883 2.58 904 2.73 926 2.87 948 3.02 969 3.15
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
2700 896 2.19 918 2.36 939 2.44 961 2.56 983 2.69 1004 2.82 1026 2.94 1048 3.07 1069 3.19 1091 3.30
3050 922 2.49 944 2.60 966 2.72 988 2.85 1010 2.95 1032 3.04 1054 3.14 1076 3.22 1098 3.30 1102 3.38
3400 949 2.89 970 3.00 992 3.10 1014 3.19 1035 3.29 1057 3.38 1078 3.47 1100 3.55 1122 3.63 1143 3.73
3750 991 3.29 1013 3.40 1034 3.50 1056 3.60 1077 3.70 1099 3.78 1121 3.88 1142 3.96 1164 4.05 1185 4.13
Table 19. Belt drive evaporator fan performance - 8.5 tons with med gas heat - GCC102A(3,4)EM- horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3050 — — — — — — — — — — 744 1.43 767 1.59 790 1.74 823 2.02 844 2.18
3400 — — — — — — 746 1.52 768 1.65 791 1.81 821 2.04 842 2.27 862 2.42 883 2.57
3750 — — 746 1.67 770 1.81 794 1.98 820 2.27 841 2.41 861 2.56 882 2.68 903 2.82 923 2.94
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
2700 854 2.05 874 2.20 895 2.28 915 2.39 936 2.52 956 2.63 977 2.75 998 2.87 1018 2.98 1039 3.09
3050 864 2.32 885 2.45 906 2.55 926 2.65 947 2.76 967 2.86 988 2.94 1008 3.02 1029 3.10 1050 3.16
3400 904 2.70 924 2.80 945 2.90 965 2.98 986 3.08 1006 3.16 1027 3.24 1048 3.32 1068 3.39 1089 3.49
3750 944 3.08 964 3.17 985 3.27 1005 3.36 1026 3.46 1047 3.53 1067 3.63 1088 3.70 1108 3.78 1129 3.86
RT-PRC091F-EN 27
Performance Data
Table 20. Belt drive evaporator fan performance - 8.5 tons with high gas heat - GCC102A(3,4)EH - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static
Standard Motor (oversize)
Motor
2700 — — — — — — — — 753 1.28 780 1.44 805 1.61 831 1.77 856 1.93 881 2.09
3050 — — — — — — 742 1.35 774 1.47 797 1.62 822 1.79 846 1.96 882 2.28 904 2.45
3400 — — 744 1.44 775 1.57 799 1.71 823 1.86 847 2.03 880 2.39 902 2.56 924 2.73 946 2.89
3750 773 1.72 799 1.88 825 2.04 851 2.23 879 2.56 901 2.72 923 2.88 945 3.02 967 3.18 989 3.32
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
2700 915 2.33 937 2.48 959 2.57 981 2.70 1003 2.84 1025 2.96 1047 3.09 1069 3.23 1091 3.36 1113 3.48
3050 926 2.61 948 2.76 970 2.87 992 2.99 1014 3.11 1036 3.22 1058 3.31 1080 3.40 1103 3.49 1125 3.56
3400 968 3.04 990 3.16 1012 3.26 1034 3.36 1056 3.47 1078 3.56 1100 3.65 1122 3.73 1145 3.82 1167 3.93
3750 1011 3.47 1033 3.57 1055 3.68 1077 3.79 1099 3.89 1121 3.98 1143 4.09 1166 4.17 1188 4.26 1210 4.34
Table 21. Belt drive evaporator fan performance - 8.5 tons with high gas heat - GCC102A(3,4)EH - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
2700 — — — — — — — — — — 743 1.35 767 1.50 791 1.65 815 1.80 839 1.95
3050 — — — — — — — — 737 1.37 759 1.51 783 1.67 806 1.83 840 2.13 861 2.29
3400 — — — — 738 1.47 761 1.60 784 1.74 807 1.90 838 2.23 859 2.39 880 2.55 901 2.70
3750 736 1.61 761 1.76 786 1.91 810 2.08 837 2.39 858 2.54 879 2.69 900 2.82 921 2.97 942 3.10
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
2700 871 2.18 892 2.32 913 2.40 934 2.52 955 2.65 976 2.77 997 2.89 1018 3.02 1039 3.14 1060 3.25
3050 882 2.44 903 2.58 924 2.68 945 2.79 966 2.91 987 3.01 1008 3.09 1029 3.18 1050 3.26 1071 3.33
3400 922 2.84 943 2.95 964 3.05 985 3.14 1006 3.24 1027 3.33 1048 3.41 1069 3.49 1090 3.57 1111 3.67
3750 963 3.24 984 3.34 1005 3.44 1026 3.54 1047 3.64 1068 3.72 1089 3.82 1110 3.90 1131 3.98 1152 4.06
28 RT-PRC091F-EN
Performance Data
Table 22. Belt drive evaporator fan performance - 8.5 tons cooling only - ECC102A(3,4)E0 - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3050 — — — — — — — — 732 1.22 753 1.38 775 1.49 799 1.64 819 1.80 840 1.94
3400 — — — — — — 745 1.39 766 1.56 794 1.71 817 1.87 842 2.03 866 2.20 892 2.46
3750 — — 733 1.52 756 1.67 784 1.81 801 1.93 828 2.09 853 2.25 877 2.52 902 2.68 927 2.82
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2700 828 1.75 848 1.91 876 2.08 899 2.34 921 2.46 945 2.57 968 2.68 992 2.78 1016 2.88 1039 2.98
3050 867 2.22 890 2.35 915 2.47 934 2.59 958 2.70 980 2.80 1005 2.91 1028 3.01 1052 3.11 1073 3.20
3400 918 2.61 939 2.73 960 2.85 986 2.97 1008 3.08 1031 3.17 1050 3.27 1073 3.37 1090 3.47 1113 3.56
3750 951 2.95 974 3.08 994 3.19 1011 3.31 1035 3.42 1054 3.53 1076 3.63 1096 3.73 1120 3.83 1138 3.93
Table 23. Belt drive evaporator fan performance - 8.5 tons cooling only - ECC102A(3,4)E0 - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3050 — — — — — — — — — — 731 1.31 752 1.42 776 1.56 795 1.71 816 1.85
3400 — — — — — — — — 744 1.49 771 1.63 793 1.78 817 1.93 841 2.09 866 2.34
3750 — — — — 734 1.59 761 1.72 778 1.84 804 1.99 828 2.14 851 2.40 876 2.55 900 2.69
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
2700 804 1.66 823 1.82 845 1.98 873 2.23 894 2.34 917 2.45 940 2.55 963 2.65 986 2.74 1009 2.84
3050 842 2.11 864 2.24 888 2.35 907 2.46 930 2.57 951 2.67 976 2.77 998 2.86 1021 2.96 1042 3.05
3400 891 2.48 912 2.60 932 2.72 957 2.83 979 2.93 1001 3.02 1019 3.12 1042 3.21 1058 3.30 1081 3.39
3750 923 2.81 946 2.93 965 3.04 982 3.15 1005 3.26 1023 3.36 1045 3.46 1064 3.55 1087 3.65 1105 3.74
RT-PRC091F-EN 29
Performance Data
10 Tons
Table 24. Belt drive evaporator fan performance - 10 tons with low gas heat - GCC120A(3,4)EL - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — — — 737 1.34 761 1.49 785 1.64 809 1.79 833 1.94 857 2.09
3600 — — — — 739 1.46 760 1.58 782 1.72 804 1.86 828 2.02 851 2.18 875 2.34 906 2.64
4000 737 1.59 760 1.71 782 1.86 805 1.99 828 2.13 851 2.29 874 2.45 903 2.78 924 2.94 945 3.09
4400 780 2.03 805 2.18 830 2.33 854 2.49 876 2.65 902 2.96 923 3.11 944 3.24 965 3.39 986 3.52
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
3200 879 2.21 910 2.46 931 2.54 952 2.66 973 2.79 994 2.91 1015 3.03 1036 3.16 1057 3.28 1078 3.39
3600 927 2.79 948 2.93 969 3.03 990 3.14 1011 3.26 1032 3.36 1053 3.44 1074 3.53 1095 3.61 1116 3.68
4000 966 3.23 987 3.34 1008 3.44 1031 3.53 1052 3.63 1072 3.72 1093 3.81 1116 3.88 1137 3.96 1159 4.06
4400 1007 3.66 1028 3.76 1049 3.86 1071 3.96 1092 4.06 1113 4.14 1135 4.24 1156 4.32 1178 4.42 1201 4.48
Table 25. Belt drive evaporator fan performance - 10 tons with low gas heat - GCC120A(3,4)EL - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 729 1.36 753 1.51 777 1.66 801 1.81 825 1.96 849 2.11 873 2.26
3600 — — 733 1.52 755 1.62 776 1.75 798 1.89 820 2.03 844 2.19 867 2.35 891 2.53 922 2.81
4000 753 1.76 776 1.88 798 2.02 821 2.16 844 2.31 867 2.45 892 2.61 919 2.95 940 3.11 961 3.26
4400 796 2.21 821 2.35 846 2.51 866 2.67 887 2.84 918 3.13 939 3.28 960 3.42 981 3.56 1002 3.69
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard
High Static (oversize) Motor
Motor
3200 905 2.49 926 2.61 947 2.72 968 2.83 989 2.96 1010 3.08 1031 3.2 1052 3.33 1073 3.45 1094 3.56
3600 943 2.96 964 3.09 985 3.22 1006 3.32 1027 3.43 1048 3.53 1069 3.62 1090 3.69 1111 3.78 1132 3.85
4000 982 3.39 1003 3.51 1024 3.61 1045 3.69 1066 3.81 1087 3.89 1108 3.97 1129 4.05 1150 4.13 1171 4.22
4400 1023 3.82 1044 3.93 1065 4.03 1086 4.13 1107 4.23 1128 4.32 1149 4.41 1170 4.49 1191 4.57 1212 4.65
30 RT-PRC091F-EN
Performance Data
Table 26. Belt drive evaporator fan performance - 10 tons with med gas heat - GCC120A(3,4)EM- downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 738 1.44 762 1.59 786 1.74 810 1.89 834 2.04 858 2.19 882 2.34
3600 — — 742 1.59 764 1.71 785 1.83 807 1.97 829 2.11 853 2.27 876 2.43 910 2.73 931 2.89
4000 762 1.84 785 1.96 807 2.11 830 2.24 853 2.38 876 2.54 907 2.87 928 3.03 949 3.19 970 3.34
4400 805 2.28 830 2.43 855 2.58 879 2.75 906 3.06 927 3.21 948 3.36 969 3.49 990 3.64 1011 3.77
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
3200 914 2.57 935 2.71 956 2.79 977 2.91 998 3.04 1019 3.16 1040 3.28 1061 3.41 1082 3.53 1103 3.64
3600 952 3.04 973 3.18 994 3.28 1015 3.39 1036 3.51 1057 3.61 1078 3.69 1099 3.78 1120 3.86 1141 3.93
4000 991 3.48 1012 3.59 1033 3.69 1054 3.78 1075 3.88 1096 3.97 1117 4.05 1138 4.13 1159 4.21 1180 4.31
4400 1032 3.91 1053 4.01 1074 4.11 1095 4.21 1116 4.31 1137 4.39 1158 4.49 1179 4.57 1200 4.65 1221 4.73
Table 27. Belt drive evaporator fan performance - 10 tons with med gas heat - GCC120A(3,4)EM - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 754 1.62 778 1.77 802 1.92 826 2.07 850 2.22 874 2.37 898 2.52
3600 736 1.67 758 1.78 780 1.88 801 2.01 823 2.15 845 2.29 869 2.45 892 2.61 926 2.91 947 3.07
4000 778 2.02 801 2.14 823 2.28 846 2.42 869 2.56 902 2.88 923 3.05 944 3.21 965 3.37 986 3.52
4400 821 2.46 846 2.61 871 2.76 901 3.08 922 3.24 943 3.39 964 3.54 985 3.68 1006 3.82 1027 3.95
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
3200 930 2.75 951 2.88 972 2.98 993 3.09 1014 3.22 1035 3.34 1056 3.46 1077 3.59 1098 3.71 1119 3.82
3600 968 3.22 989 3.35 1010 3.47 1031 3.58 1052 3.69 1073 3.79 1094 3.88 1115 3.96 1136 4.04 1157 4.11
4000 1007 3.66 1028 3.77 1049 3.87 1070 3.96 1091 4.06 1112 4.15 1133 4.23 1154 4.31 1175 4.39 1196 4.48
4400 1048 4.08 1069 4.19 1090 4.29 1111 4.39 1132 4.49 1153 4.58 1174 4.67 1195 4.75 1216 4.83 1237 4.91
RT-PRC091F-EN 31
Performance Data
Table 28. Belt drive evaporator fan performance - 10 tons with high gas heat - GCC120A(3,4)EH - downflow airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 738 1.44 762 1.59 786 1.74 810 1.89 834 2.04 858 2.19 882 2.34
3600 — — 742 1.59 764 1.71 785 1.83 807 1.97 829 2.11 853 2.27 876 2.43 910 2.73 931 2.89
4000 762 1.84 785 1.96 807 2.11 830 2.24 853 2.38 876 2.54 907 2.87 928 3.03 949 3.19 970 3.34
4400 805 2.28 830 2.43 855 2.58 879 2.75 906 3.06 927 3.21 948 3.36 969 3.49 990 3.64 1011 3.77
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
3200 914 2.57 935 2.71 956 2.79 977 2.91 998 3.04 1019 3.16 1040 3.28 1061 3.41 1082 3.53 1103 3.64
3600 952 3.04 973 3.18 994 3.28 1015 3.39 1036 3.51 1057 3.61 1078 3.69 1099 3.78 1120 3.86 1141 3.93
4000 991 3.48 1012 3.59 1033 3.69 1054 3.78 1075 3.88 1096 3.97 1117 4.05 1138 4.13 1159 4.21 1180 4.31
4400 1032 3.91 1053 4.01 1074 4.11 1095 4.21 1116 4.31 1137 4.39 1158 4.49 1179 4.57 1200 4.65 1221 4.73
Table 29. Belt drive evaporator fan performance - 10 tons with high gas heat - GCC120A(3,4)EH - horizontal airflow
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — 754 1.62 778 1.77 802 1.92 826 2.07 850 2.22 874 2.37 898 2.52
3600 736 1.67 758 1.78 780 1.88 801 2.01 823 2.15 845 2.29 869 2.45 892 2.61 926 2.91 947 3.07
4000 778 2.02 801 2.14 823 2.28 846 2.42 869 2.56 902 2.88 923 3.05 944 3.21 965 3.37 986 3.52
4400 821 2.46 846 2.61 871 2.76 901 3.08 922 3.24 943 3.39 964 3.54 985 3.68 1006 3.82 1027 3.95
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
3200 930 2.75 951 2.88 972 2.98 993 3.09 1014 3.22 1035 3.34 1056 3.46 1077 3.59 1098 3.71 1119 3.82
3600 968 3.22 989 3.35 1010 3.47 1031 3.58 1052 3.69 1073 3.79 1094 3.88 1115 3.96 1136 4.04 1157 4.11
4000 1007 3.66 1028 3.77 1049 3.87 1070 3.96 1091 4.06 1112 4.15 1133 4.23 1154 4.31 1175 4.39 1196 4.48
4400 1048 4.08 1069 4.19 1090 4.29 1111 4.39 1132 4.49 1153 4.58 1174 4.67 1195 4.75 1216 4.83 1237 4.91
32 RT-PRC091F-EN
Performance Data
Table 30. Belt drive evaporator fan performance - 10 tons cooling only - ECC120A(3,4)E0 - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — — — — — — — 758 1.55 782 1.69 807 1.84 833 2.01
3600 — — — — — — — — 736 1.55 770 1.83 798 1.95 820 2.09 845 2.26 870 2.41
4000 — — — — — — 752 1.85 782 2.06 809 2.21 836 2.37 860 2.54 882 2.71 914 2.99
4400 — — 745 2.08 772 2.19 799 2.34 825 2.47 852 2.63 876 2.79 909 3.08 934 3.24 958 3.39
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
3200 858 2.17 881 2.34 913 2.62 936 2.74 959 2.85 982 2.96 1005 3.07 1028 3.17 1051 3.27 1074 3.37
3600 896 2.59 926 2.84 949 2.96 972 3.08 995 3.19 1018 3.3 1041 3.41 1064 3.51 1087 3.61 1110 3.71
4000 939 3.14 962 3.27 985 3.39 1008 3.51 1031 3.62 1054 3.72 1077 3.82 1100 3.92 1123 4.02 1146 4.12
4400 981 3.52 1004 3.65 1027 3.77 1050 3.89 1073 3.99 1096 4.11 1119 4.22 1142 4.32 1165 4.42 1188 4.52
Table 31. Belt drive evaporator fan performance - 10 tons cooling only - ECC120A(3,4)E0 - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
3200 — — — — — — — — — — 747 1.61 774 1.73 798 1.87 823 2.02 849 2.18
3600 — — — — — — — — 752 1.73 786 2.01 814 2.13 836 2.28 861 2.44 886 2.59
4000 — — — — 742 1.85 768 2.03 798 2.24 825 2.39 852 2.55 876 2.72 898 2.89 930 3.16
4400 735 2.17 761 2.26 788 2.38 815 2.52 841 2.65 868 2.81 892 2.97 925 3.25 950 3.41 974 3.56
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor High Static (oversize) Motor
3200 874 2.35 897 2.52 929 2.79 952 2.91 975 3.02 998 3.13 1021 3.24 1044 3.34 1067 3.44 1090 3.54
3600 919 2.87 942 3.01 965 3.13 988 3.25 1011 3.36 1034 3.47 1057 3.58 1080 3.68 1103 3.78 1126 3.88
4000 955 3.31 978 3.44 1001 3.56 1024 3.68 1047 3.79 1070 3.89 1093 3.99 1116 4.09 1139 4.19 1162 4.29
4400 997 3.69 1020 3.82 1043 3.94 1066 4.06 1089 4.17 1112 4.28 1135 4.39 1158 4.49 1181 4.59 1204 4.69
RT-PRC091F-EN 33
Performance Data
12.5 Tons
Table 32. Belt drive evaporator fan performance - 12.5 tons with low heat heat - GCC150A(3,4)EL - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
4000 — — — — — — 793 2.09 820 2.24 847 2.38 873 2.52 899 2.66 924 2.77 949 2.89
4500 — — 791 2.23 816 2.41 842 2.58 869 2.76 897 2.91 925 3.19 951 3.37 977 3.53 1002 3.69
5000 822 2.56 848 2.76 874 2.93 899 3.26 924 3.41 950 3.59 976 3.77 1001 3.96 1028 4.11 1056 4.27
5500 873 2.99 899 3.31 925 3.46 950 3.63 975 3.81 999 3.99 1024 4.17 1049 4.36 1075 4.53 1101 4.71
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
4000 973 3.12 997 3.26 1020 3.37 1043 3.48 1065 3.59 1087 3.73 1108 3.86 1129 3.97 1149 4.09 1169 4.18
4500 1026 3.86 1050 4.01 1073 4.16 1095 4.31 1117 4.44 1141 4.56 1166 4.64 1191 4.72 1213 4.79 1235 4.86
5000 1083 4.42 1109 4.57 1135 4.72 1160 4.87 1185 5.02 1212 5.18 1236 5.33 — — — — — —
5500 1125 4.89 1149 5.07 1181 5.22 1204 5.34 1228 5.49 — — — — — — — — — —
Table 33. Belt drive evaporator fan performance - 12.5 tons with low gas heat - GCC150A(3,4)EL - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
4000 — — — — 773 2.03 801 2.18 828 2.33 855 2.47 881 2.61 907 2.74 932 2.86 957 2.98
4500 — — 799 2.32 824 2.51 850 2.67 877 2.84 905 3.02 933 3.28 959 3.46 985 3.62 1010 3.78
5000 830 2.65 856 2.84 882 3.02 915 3.34 932 3.52 958 3.68 984 3.86 1009 4.04 1036 4.21 1064 4.36
5500 881 3.08 916 3.41 937 3.54 958 3.72 983 3.89 1007 4.08 1032 4.26 1057 4.44 1083 4.62 1109 4.79
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
4000 981 3.21 1005 3.34 1028 3.46 1051 3.57 1073 3.68 1095 3.82 1116 3.94 1137 4.06 1157 4.18 1177 4.27
4500 1034 3.94 1058 4.12 1081 4.25 1103 4.40 1125 4.53 1149 4.64 1174 4.73 1199 4.81 1221 4.88 1243 4.94
5000 1091 4.51 1117 4.66 1143 4.81 1168 4.96 1193 5.11 1218 5.24 — — — — — — — —
34 RT-PRC091F-EN
Performance Data
Table 34. Belt drive evaporator fan performance - 12.5 tons with med gas heat - GCC150A(3,4)EM- downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
4000 — — — — 783 2.09 811 2.24 838 2.39 865 2.53 891 2.67 917 2.81 942 2.92 967 3.04
4500 — — 809 2.38 834 2.56 860 2.73 887 2.91 915 3.06 943 3.34 969 3.52 995 3.68 1020 3.84
5000 840 2.71 866 2.91 892 3.08 917 3.41 942 3.56 968 3.74 994 3.92 1019 4.11 1046 4.26 1074 4.42
5500 891 3.14 917 3.46 943 3.61 968 3.78 993 3.96 1017 4.14 1042 4.32 1067 4.51 1093 4.68 1119 4.86
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
4000 991 3.27 1015 3.41 1038 3.52 1061 3.63 1083 3.74 1105 3.88 1126 4.01 1147 4.12 1167 4.24 1187 4.33
4500 1044 4.01 1068 4.16 1091 4.31 1113 4.46 1135 4.59 1159 4.71 1184 4.79 1209 4.87 1231 4.94 1253 5.01
5000 1101 4.57 1127 4.72 1153 4.87 1178 5.02 1203 5.17 1230 5.33 — — — — — — — —
Table 35. Belt drive evaporator fan performance - 12.5 tons with med gas heat - GCC150A(3,4)EM - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
4000 — — 770 2.07 798 2.24 826 2.39 853 2.54 880 2.68 906 2.82 932 2.95 957 3.07 982 3.19
4500 802 2.35 824 2.53 849 2.71 875 2.88 902 3.05 930 3.21 958 3.49 984 3.67 1010 3.83 1035 3.99
5000 855 2.86 881 3.05 907 3.23 932 3.55 957 3.71 983 3.89 1009 4.07 1034 4.25 1061 4.41 1089 4.57
5500 906 3.29 932 3.61 958 3.75 983 3.93 1008 4.11 1032 4.29 1057 4.47 1082 4.65 1108 4.83 1134 5.01
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
4000 1006 3.42 1030 3.55 1053 3.67 1076 3.78 1098 3.89 1120 4.03 1141 4.15 1162 4.27 1182 4.39 1202 4.48
4500 1059 4.15 1083 4.31 1106 4.46 1128 4.61 1150 4.74 1174 4.85 1199 4.94 1224 5.02 1246 5.09 1268 5.15
5000 1116 4.72 1142 4.87 1168 5.02 1193 5.17 1218 5.32 — — — — — — — — — —
RT-PRC091F-EN 35
Performance Data
Table 36. Belt drive evaporator fan performance - 12.5 tons with high gas heat - GCC150A(3,4)EH - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
4000 — — — — 783 2.09 811 2.24 838 2.39 865 2.53 891 2.67 917 2.81 942 2.92 967 3.04
4500 — — 809 2.38 834 2.56 860 2.73 887 2.91 915 3.06 943 3.34 969 3.52 995 3.68 1020 3.84
5000 840 2.71 866 2.91 892 3.08 917 3.41 942 3.56 968 3.74 994 3.92 1019 4.11 1046 4.26 1074 4.42
5500 891 3.14 917 3.46 943 3.61 968 3.78 993 3.96 1017 4.14 1042 4.32 1067 4.51 1093 4.68 1119 4.86
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
4000 991 3.27 1015 3.41 1038 3.52 1061 3.63 1083 3.74 1105 3.88 1126 4.01 1147 4.12 1167 4.24 1187 4.33
4500 1044 4.01 1068 4.16 1091 4.31 1113 4.46 1135 4.59 1159 4.71 1184 4.79 1209 4.87 1231 4.94 1253 5.01
5000 1101 4.57 1127 4.72 1153 4.87 1178 5.02 1203 5.17 1230 5.33 — — — — — — — —
Table 37. Belt drive evaporator fan performance - 12.5 tons with high gas heat - GCC150A(3,4)EH - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
4000 — — 770 2.07 798 2.24 826 2.39 853 2.54 880 2.68 906 2.82 932 2.95 957 3.07 982 3.19
4500 802 2.35 824 2.53 849 2.71 875 2.88 902 3.05 930 3.21 958 3.49 984 3.67 1010 3.83 1035 3.99
5000 855 2.86 881 3.05 907 3.23 932 3.55 957 3.71 983 3.89 1009 4.07 1034 4.25 1061 4.41 1089 4.57
5500 906 3.29 932 3.61 958 3.75 983 3.93 1008 4.11 1032 4.29 1057 4.47 1082 4.65 1108 4.83 1134 5.01
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
4000 1006 3.42 1030 3.55 1053 3.67 1076 3.78 1098 3.89 1120 4.03 1141 4.15 1162 4.27 1182 4.39 1202 4.48
4500 1059 4.15 1083 4.31 1106 4.46 1128 4.61 1150 4.74 1174 4.85 1199 4.94 1224 5.02 1246 5.09 1268 5.15
5000 1116 4.72 1142 4.87 1168 5.02 1193 5.17 1218 5.32 — — — — — — — — — —
36 RT-PRC091F-EN
Performance Data
Table 38. Belt drive evaporator fan performance - 12.5 tons cooling only - ECC150A(3,4)E0 - downflow airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
4000 — — — — — — 747 1.89 769 2.06 790 2.23 811 2.38 833 2.57 856 2.74 879 2.91
4500 — — 759 2.12 787 2.35 808 2.52 829 2.69 851 2.86 874 3.03 906 3.31 929 3.46 952 3.58
5000 807 2.52 828 2.68 854 2.85 871 3.02 903 3.31 928 3.46 952 3.62 976 3.78 999 3.93 1022 4.07
5500 870 2.99 882 3.15 914 3.43 937 3.59 960 3.75 983 3.91 1006 4.06 1029 4.22 1052 4.38 1075 4.52
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
4000 911 3.19 932 3.33 952 3.45 972 3.56 992 3.66 1011 3.76 1030 3.86 1050 3.95 1071 4.04 1094 4.14
4500 974 3.74 995 3.88 1015 4.01 1035 4.11 1055 4.21 1074 4.31 1093 4.41 1113 4.51 1134 4.59 1157 4.69
5000 1044 4.21 1065 4.34 1085 4.46 1105 4.58 1125 4.68 1144 4.78 1163 4.88 1183 4.98 1204 5.08 1227 5.18
5500 1097 4.66 1118 4.79 1138 4.91 1158 5.02 1178 5.12 1197 5.22 1216 5.32 — — — — — —
Table 39. Belt drive evaporator fan performance - 12.5 tons cooling only - ECC150A(3,4)E0 - horizontal airflow
External Static Pressure (Inches of Water)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard Motor
4000 — — — — 742 1.85 763 2.02 785 2.19 806 2.36 827 2.53 849 2.7 872 2.87 895 3.04
4500 745 2.06 775 2.25 803 2.48 824 2.65 845 2.82 867 2.99 890 3.16 922 3.44 945 3.59 968 3.73
5000 823 2.65 844 2.81 870 2.98 887 3.15 919 3.43 944 3.59 968 3.75 992 3.91 1015 4.06 1038 4.2
5500 886 3.12 898 3.28 930 3.56 953 3.72 976 3.88 999 4.04 1022 4.19 1045 4.35 1068 4.51 1091 4.65
External Static Pressure (Inches of Water)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static (oversize) Motor
4000 927 3.32 948 3.46 968 3.58 988 3.69 1008 3.79 1027 3.89 1046 3.99 1066 4.08 1087 4.17 1110 4.27
4500 990 3.87 1011 4.01 1031 4.13 1051 4.24 1071 4.34 1090 4.44 1109 4.54 1129 4.63 1150 4.72 1173 4.82
5000 1060 4.34 1081 4.47 1101 4.59 1121 4.71 1141 4.81 1160 4.91 1179 5.01 1199 5.11 1220 5.21 1243 5.31
5500 1113 4.79 1134 4.92 1154 5.04 1174 5.15 1194 5.25 1213 5.35 1232 5.45 — — — — — —
Notes:
1. The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor should
use only industry-recognized procedures.
2. Each ton of cooling requires between 300 and 450 cubic feet of air per minute (CFM), or 320 CFM nominally.
3. Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.
4. Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver treated air along the perimerter of the space. If they
are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Return air grilles must be properly sized to
carry air back to the blower. If they are too small, they also cause noise.
5. The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living space.
6. An air velocity meter or airflow hood can give a reading of system CFM.
RT-PRC091F-EN 37
Performance Data
Table 41. High Static (Oversize) motor and drive/fan speed (rpm)
Tons Unit Model Number Fan Sheave 6 Turn Open 5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open Closed
ECC090
7.5 15-15 885 946 978 1047 1108 1175 1229
GCC090
ECC102
8.5 15-15 900 959 994 1060 1124 1189 1243
GCC102
ECC120
10 15-15 900 959 994 1060 1124 1189 1243
GCC120
ECC150
12.5 15-16 916 975 1031 1090 1148 1209 1268
GCC150
Table 42. Static pressure drop through accessories (inches water column)
Unit Model Standard Standard Electric Heater
Tons Cfm
Number Filters Economizer 10.4 16 25 32 41 50
2400 0.01 — 0.005 0.005 0.050 0.01 0.01 —
E/GCC090A
3000 0.03 — 0.010 0.010 0.010 0.02 0.02 —
(Downflow)
3375 0.04 — 0.015 0.015 0.015 0.03 0.03 —
7.5
2400 0.01 — 0.005 0.005 0.050 0.01 0.01 —
E/GCC090A
3000 0.03 — 0.010 0.010 0.010 0.02 0.02 —
(Horizontal)
3375 0.04 — 0.015 0.015 0.015 0.03 0.03 —
2720 0.02 — 0.010 0.010 0.010 0.02 0.02 —
E/GCC102A
3400 0.04 — 0.015 0.015 0.015 0.03 0.03 —
(Downflow)
3825 0.05 — 0.020 0.020 0.020 0.04 0.04 —
8.5
2720 0.02 — 0.010 0.010 0.010 0.02 0.02 —
E/GCC102A
3400 0.04 — 0.015 0.015 0.015 0.03 0.03 —
(Horizontal)
3825 0.05 — 0.020 0.020 0.020 0.04 0.04 —
3200 0.03 — 0.015 0.015 — 0.03 0.03 0.03
E/GCC120A
4000 0.05 — 0.020 0.020 — 0.04 0.04 0.04
(Downflow)
4500 0.07 — 0.025 0.025 — 0.05 0.05 0.05
10
3200 0.03 — 0.015 0.015 — 0.03 0.03 0.03
E/GCC120A
4000 0.05 — 0.020 0.020 — 0.04 0.04 0.04
(Horizontal)
4500 0.07 — 0.025 0.025 — 0.05 0.05 0.05
4000 0.05 — 0.020 0.020 — 0.04 0.04 0.04
E/GCC150A
5000 0.07 — 0.030 0.030 — 0.06 0.06 0.06
(Downflow)
5625 0.09 — 0.035 0.035 — 0.07 0.07 0.07
12.5 4000 0.05 — 0.020 0.020 — 0.04 0.04 0.04
E/GCC150A 5000 0.07 — 0.030 0.030 — 0.06 0.06 0.06
(Horizontal)
5625 0.09 — 0.035 0.035 — 0.07 0.07 0.07
38 RT-PRC091F-EN
Performance Data
RT-PRC091F-EN 39
Performance Data
Table 45. Electric heater voltage correction factors (applicable to auxiliary heat capacity)
Nominal Voltage Distribution Voltage Capacity Multiplier
208 0.75
240 230 0.92
240 1.00
460 460 1.00
40 RT-PRC091F-EN
Controls
Economizer Controls
The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two
optional controls, Reference Enthalpy Control and Comparative Enthalpy Control.
Remote Potentiometer
Minimum position setting of economizer can be remotely adjusted with this accessory.
Thermostats
Model # Type Stages Display Type Features
TCONT302AS42DA Programmable 4H/2C Touchscreen Common preferred, not required 2/ 2 AA battery power
BAYSTAT814 Touchscreen 3H/2C Touchscreen Remote access via Pivot Mobile App
BAYSTAT300 Programmable 3H/2C Backlit Display and Keys BACnet MS-TP enabled
RT-PRC091F-EN 41
Electrical Data
Table 47. Unit wiring with cooling only (no electric heat) or gas heat
Standard Indoor Fan Motor Oversized Indoor Fan Motor
Unit Model Unit Operating Maximum Fuse Size Maximum Fuse Size
TONS Minimum Circuit Minimum Circuit
Number Voltage Range or Maximum Circuit or Maximum Circuit
Ampacity(a) Ampacity
Breaker Breaker
7.5 E/GCC090A 208-230 36 45 40 50
8.5 E/GCC102A 208-230 42 50 49 60
10 E/GCC120A 208-230 54 70 57 70
12.5 E/GCC150A 208-230 66 80 69 80
7.5 E/GCC090A 460 20 25 25 30
8.5 E/GCC102A 460 20 25 27 30
10 E/GCC120A 460 27 30 29 35
12.5 E/GCC150A 460 34 40 35 45
(a) For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.
Table 48. Unit wiring with electric heat (single point connection)
42 RT-PRC091F-EN
Electrical Data
Table 48. Unit wiring with electric heat (single point connection) (continued)
RT-PRC091F-EN 43
Electrical Data
Table 51. Electrical characteristics – combustion blower motor (gas heat units)
Combustion Blower Motor
Unit Model
TONS Amps
Number No. Volts Phase rpm
FLA
7.5 E/GCC090 1 208/230 1 2100 1.2
44 RT-PRC091F-EN
Jobsite Connections
Table 52. Typical number of wires
Thermostats
DISCONNECT
S W ITCH
( BY O T H E R S )
A
T H E RM O S TAT
RO O FTOP
UNIT
Notes:
• For specific wiring information, see the installation instructions.
• All wiring except power wire is low voltage.
• All customer supplied wiring to be copper and must conform to applicable electrical codes
and local electric codes. Wiring shown dotted is to be furnished and installed by the
customer.
RT-PRC091F-EN 45
Dimensional Data
Figure 1. Typical installation clearance for single and multiple unit applications (in inches)
END TO END
NOTE 2,3
SIDE BY SIDE
NOTE 2
NOTES:
1.FOR HORIZONTAL DISCHARGE UNIT,
THIS MEASURE IS REDUCED TO 1’ 6” NOTE 1
TO MINIMIZE DUCT EXTENSIONS.
4’ 0”
2.WHEN EQUIPPED WITH ECONOMIZER
OR BAROMETRIC RELIEF DAMPER, 1’ 6” Minimum clearance
CLERANCE DISTANCE IS TO BE 3’ 0” Side condensate drain is used
MEASURE FROM PROTRUDING HOOD
INSTEAD OF BASE. 1’ 6” Recommended service clearance
SINGLE UNIT 4’ 0” Unit disconnect is mounted on panel
46 RT-PRC091F-EN
Dimensional Data
Figure 2. Cooling with optional electrical heat and gas/electric units — overview
C O N D E N S AT E
G A S C O N N E C TIO N D R AIN
IN SID E C O N N E C TIO N
Figure 3. Cooling with optional electrical heat and gas/electric units — front and side views (in inches)
2-3/4”
Ø2
Ø1-3/8”
2-3/4”
Ø2
48-5/16”
48-3/4”
Ø1-3/8”
44-3/16”
30-3/16”
6-5/16”
Ø7/8”
14-7/16”
2-5/16”
7-3/4” 23-3/4” 7-3/4”
RT-PRC091F-EN 47
Dimensional Data
Figure 4. Cooling with optional electrical heat and gas/electric units — bottom view (in inches)
88-7/16”
25-5/8”
29-5/8” 14” 3-7/16”
12-7/16”
37-5/8”
40-11/16”
27-5/16”
12-3/8”
36-7/16” 3-7/16”
NOTES:
1.THROUGH THE BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.
2.VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION.
Figure 5. Cooling with optional electrical heat and gas/electric units — back view (horizontal configuration) (in
inches)
SUPPLY RETURN
36-7/16”
14”
5-5/8”
4-15/16”
23”
53-3/16”
48 RT-PRC091F-EN
Dimensional Data
Figure 6. Cooling with optional electric heat and gas/electric models — roof curb (in inches)
15 1/2”
15 13/16” 45 1/8”
37 15/16”
RETURN
3 9/16”
14.000
1 3/4”
54 9/16”
84 13/16”
Figure 7. Cooling with optional electric heat and gas/electric models — downflow unit clearance (in inches)
UNIT OUTLINE
39 11/16” 54 5/8”
CLEARANCE 48”
CLEARANCE 60”
RT-PRC091F-EN 49
Weights
Table 53. Maximum unit and corner weights (lb) and center of gravity dimensions (in.)
7.5 GCC090A 1087 1012 248 181 334 249 45.0 34.0
8.5 GCC102A 1111 1036 236 176 340 283 44.0 36.0
12.5 GCC150A 1235 1172 264 194 299 416 39.0 35.0
7.5 ECC090A 979 904 250 188 197 269 45.0 34.0
8.5 ECC102A 1003 928 252 187 200 289 44.0 36.0
12.5 ECC150A 1124 1049 302 197 208 342 39.0 35.0
(a) Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
(b) Weights do not include additional factory or field installed options/accessories.
(c) Corner weights are given for information only. 7.5–12.5 ton models must be supported continuously by a curb or equivalent frame support.
Note: To calculate additional weight for accessories, see Accessory net weights table.
Table 54. Accessory net weight (lb)
Accessories Net weight (lb)
CENTER O F
G R AV I TY
W I DTH
D C
50 RT-PRC091F-EN
Mechanical Specifications
General
• Packaged rooftop units cooling, heating capacities, and efficiencies are AHRI Certified within scope
of AHRI Standard (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air
Furnaces
• Packaged rooftop units are dedicated downflow or horizontal airflow
• Operating range between 125°F and 40°F in cooling standard from the factory
• Factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check
cooling operation, fan and blower rotation, and control sequence before leaving the factory
• Colored and numbered wring internal to the unit for simplified identification
• Units ETL listed and labeled, classified in accordance
Standard Features
Casing
• Zinc coated, heavy gauge, galvanized steel
• Weather-resistant baked enamel finish on phosphatized exterior surfaces
• Meets ASTM B117, 672 hour salt spray test
• Removable single side maintenance access panels
• Lifting handles in maintenance access panels (can be removed and reinstalled by removing no more
than 11 fasteners while providing a water and air tight seal)
• Exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2-inch, 1-
pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material
• Base of unit shall be insulated with 1/2-inch, 1-pound density, foil-faced, glass fiber material
• Base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8-inch
high downflow supply/return openings to provide an added water integrity precaution, if the
condensate drain backs up
• Downflow unit’s base pan shall have no penetrations within the perimeter of the curb other than the
raised 1 1/8-inch high supply/return openings to provide an added water integrity precaution, if the
condensate drain backs up
• Base of unit shall have provisions for forklift and crane lifting
Compressors
• All units have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps
• Suction gas-cooled motor with voltage utilization range of plus or minus 10 percent of unit
nameplate voltage
• Internal overloads standard with scroll compressors
• All models have phase monitors and Low and High Pressure Controls as standard
RT-PRC091F-EN 51
Mechanical Specifications
Filters
Two inch standard filters shall be factory supplied on all units.
Indoor Fan
• Belt driven, FC centrifugal fans with adjustable motor sheaves
• Motors thermally protected
• Oversized motors available for high static application
• Indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT)
Outdoor Fans
• Outdoor fan shall be externally drive, statically and dynamically balanced, draw-through in the
vertical discharge position.
• Fan motor(s) shall be permanently lubricated and shall have current overload protection.
Refrigerant Circuits
• Each refrigerant circuit shall have a fixed orifice, service pressure ports, and refrigerant line filter
driers factory installed as standard
• An area shall be provided for replacement suction line driers
Unit Top
The top cover shall be double hemmed and gasket sealed to prevent water leakage.
52 RT-PRC091F-EN
Mechanical Specifications
Oversized Motors
Oversized motors shall be available as a factory option for High Static applications.
Economizer — Horizontal
The horizontal economizer shall contain the same features as the downflow economizer with the
exception of barometric relief.
Electric Heaters
• Electric heat modules shall be available for installation within the basic unit
• Elements shall be constructed of heavy-duty nickel chromium elements internally delta connected
for 240 volt, wye connected for volt
• Power assemblies shall provide single-point connection
• Electric heat modules shall be UL listed or CSA certified
• If ordering the Through the Base Electrical option with an Electric Heater, the heater must be factory
installed.
Hail Guards
Tool-less, hail protection quality coil guards are available for condenser coil protection.
RT-PRC091F-EN 53
Mechanical Specifications
Powered Exhaust
The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better
building pressurization.
Remote Potentiometer
The minimum position setting of the economizer shall be adjusted with this accessory.
54 RT-PRC091F-EN
Notes
RT-PRC091F-EN 55
The AHRI Certified mark indicates Trane U.S. Inc. participation in the AHRI Certification program. For verification of individual certified products, go to
ahridirectory.org.
Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor
environments for commercial and residential applications. For more information, please visit trane.com or
tranetechnologies.com.
Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We
are committed to using environmentally conscious print practices.