Topic 3 Special Installations
Topic 3 Special Installations
PROTECTION INSTALLATION
INTRODUCTION
All electrical installations and installed equipment must be safe to use and free from the dangers of electric
shock, but some installations require special consideration because of the inherent dangers of the installed
conditions. The danger may arise because of the corrosive or explosive nature of the atmosphere, because
the installation must be used in damp or low temperature conditions or because there is a need to provide
additional mechanical protection for the electrical system. In this section we will consider some of the
installations which require special consideration.
Flammable and explosive installations are to be found in the petroleum and chemical industries, which are
classified as group II industries. Mining is classified as group I and receives special consideration from the
Mining Regulations because of the extreme hazards of working underground. Petrol filling pumps must be
wired and controlled by flameproof equipment to BS 5345 and meet the requirements of the
Petroleum Regulation Act 1928 and 1936 and any local licensing laws concerning the keeping and
dispensing of petroleum spirit.
If an area is not classified as zone 0, 1 or 2, then it is deemed to be non-hazardous, so that normal industrial electrical
equipment may be used. The electrical equipment used in zone 2 will contain a minimum amount of protection. For
example, normal sockets and switches cannot be installed in a zone 2 area, but oil-filled radiators may be installed if
they are directly connected and controlled from outside the area. Electrical equipment in this area should be marked
Prepared by Mr. Omondi Ferdinand – 0712747442
Electrical Trainer - Kisumu Page 2
UNIT: BUILDING SERVICES & TOPIC 3: SPECIAL
PROTECTION INSTALLATION
Ex‘o’ for oil-immersed or Ex‘p’ for powder-filled. In Zone 1 all electrical equipment must be flameproof, as shown
in Fig. 4.43, and marked Ex‘d’ to indicate a flameproof enclosure.
Ordinary electrical equipment cannot be installed in Zone 0, even when it is flameproof protected. However, many
chemical and oil-processing plants are entirely dependent upon instrumentation and data transmission for their safe
operation. Therefore, very low-power instrumentation and data-transmission circuits can be used in special
circumstances, but the equipment must be intrinsically safe, and used in conjunction with a ‘safety barrier’ installed
outside the hazardous area. Intrinsically safe equipment must be marked Ex‘ia’ or Ex’s’, specially certified for use in
zone 0.
Intrinsic safety
An intrinsically safe circuit is one in which no spark or thermal effect is capable of causing ignition of a given
explosive atmosphere. The intrinsic safety of the equipment in a hazardous area is assured by incorporating a Zener
diode safety barrier into the control circuit such as that shown in Fig. 4.45.
In normal operation the voltage across a Zener diode is too low for it to conduct, but if a fault occurs the voltage
across Z1 and Z2 will rise, switching them on and blowing the protective fuse. Z2 is included in the circuit as a ‘back-
up’ in case the first Zener diode fails.
An intrinsically safe system, suitable for use in Zone 0, is one in which all the equipment, apparatus and
interconnecting wires and circuits are intrinsically safe.
2) Temporary installations
Temporary electrical supplies provided on construction sites can save many man-hours of labour by providing the
energy required for fixed and portable tools and lighting which speeds up the completion of a project. However,
construction sites are dangerous places and the temporary electrical supply which is installed to assist the
construction process must comply with all of the relevant wiring regulations for permanent installations (Regulation
110–01–01).
All equipment must be of a robust construction in order to fulfil the on-site electrical requirements while being
exposed to rough handling, vehicular nudging, the wind, rain and sun. All socket outlets, plugs and couplers must be
of the industrial type to BS 4343 and specified by Regulation 604–12–02 as shown in Fig. 4.40.
Where an electrician is not permanently on site, MCBs are preferred so that overcurrent protection devices can be
safely reset by an unskilled person. The British Standards Code of Practice 1017, The Distribution of Electricity on
Construction and Building Sites, advises that protection against earth faults may be obtained by first providing a low
impedance path, so that overcurrent devices can operate quickly, and secondly by fitting a residual current device
(RCD) in addition to the overcurrent protection device.
A construction site installation should be tested and inspected in accordance with Part 7 of the Wiring Regulations
every three months throughout the construction period.
The source of supply for the temporary installation may be from a petrol or diesel generating set or from the local
supply company. When the local electricity company provides the supply, the incoming cable must be terminated in
a waterproof and locked enclosure to prevent unauthorized access and provide metering arrangements.
IEE Regulation 604–02–02 recommends the following voltages for the distribution of electrical supplies to plant and
equipment on construction sites:
400 V three-phase for supplies to major items of plant having a rating above 3.75 kW such as cranes and
lifts. These supplies must be wired in armoured cables.
230 V single-phase for supplies to items of equipment which are robustly installed such as floodlighting
towers, small hoists and site offices. These supplies must be wired in armoured cable unless run inside the
site offices.
110 V single-phase for supplies to all portable hand tools and all portable lighting equipment. The supply is
usually provided by a reduced voltage distribution unit which incorporates splash proof sockets fed from a
centre-tapped 110V transformer. This arrangement limits the voltage to earth to 55V, which is recognized as
safe in most locations. A 110 V distribution unit is shown in Fig. 4.40. Edison screw lamps are used for 110
V lighting supplies so that they are not interchangeable with 230 V site office lamps.
There are occasions when even a 110 V supply from a centre-tapped transformer is too high, for example, supplies to
inspection lamps for use inside damp or confined places. In these circumstances a safety extra low voltage (SELV)
supply would be required.
Industrial plugs have a keyway which prevents a tool from one voltage being connected to the socket outlet of a
different voltage. They are also colour coded for easy identification as follows:
440 V – red 50 V – white
230 V – blue 25 V – violet
110 V – yellow
The pulses are generated by a capacitor–resistor circuit inside the controller which may be mains or battery operated
(capacitor–resistor circuits. There must be no risk to any human coming into contact with the controller, which
should be manufactured to BS 2632. The output voltage of the controller must not exceed 10 kV and the energy must
not be greater than 5 J. The duration of the pulse must not be greater than 1.5ms and the pulse must never have a
frequency greater than one pulse per second. This shock level is very similar to that which can be experienced by
touching a spark plug lead on a motor car. The energy levels are very low at 5 J. There are 3.6 million joules
of energy in 1 kWh.
Earth electrodes connected to the earth terminal of an electric fence controller must be separate from the earthing
system of any other circuit and should be situated outside the resistance area of any electrode used for protective
earthing. The electric fence controller and the fence wire must be installed so that they do not come into contact with
any power, telephone or radio systems, including poles. Agricultural and horticultural installations should be tested
and inspected in accordance with Part 6 of the Wiring Regulations every 3 years.
These requirements are shown in Fig. 4.42. Information notices regarding type and voltage of the supply and
maximum permitted load must be displayed at the source of supply. The supply cables must be installed outside the
pitch area or be suitably armoured so that they cannot be damaged by caravan awning pegs (Regulation 608–12–02).
The caravan or motor caravan must be provided with a main isolating switch and a residual current device to break
all live conductors (Regulations 608– 03–02 and 608–07–04). An adjacent notice detailing how to connect and
disconnect the supply safely must also be provided, as shown in Regulation 608–07–05.
Electrical equipment must not be installed in fuel storage compartments. Caravans flex when being towed, and
therefore the installation must be wired in flexible or stranded conductors of at least 1.5mm cross-section. The
conductors must be supported on horizontal runs at least every 25 cm and the metalwork of the caravan and chassis
must be bonded with 4.0mm2 cable.
The wiring of the extra low-voltage battery supply must be run in such a way that it does not come into contact with
the 230V wiring system (Regulation 608–06–04).
The caravan should be connected to the pitch socket outlet by means of a flexible cable, not longer than 27m, and
having a minimum cross-sectional area of 2.5mm2.
Because of the mobile nature of caravans, it is recommended that the electrical installation be tested and inspected at
intervals considered appropriate, between 1 and 3 years but not exceeding three years (Regulation 608–07–05).
5) Bathroom Installations
In rooms containing a fixed bath tub or shower basin, additional regulations are specified. This is to reduce the risk
of electric shock to people in circumstances where body resistance is lowered because of contact with water. The
regulations may be found in Section 601 and can be summarized as follows:
Socket outlets must not be installed and no provision is made for connection of portable appliances.
Prepared by Mr. Omondi Ferdinand – 0712747442
Electrical Trainer - Kisumu Page 6
UNIT: BUILDING SERVICES & TOPIC 3: SPECIAL
PROTECTION INSTALLATION
Only shaver sockets which comply with BS EN 61184 or BS EN 60238, that is, those which contain an
isolating transformer, may be installed.
Every switch must be inaccessible to anyone using the bath or shower unless it is of the cord-operated type.
There are restrictions as to where appliances, switchgear and wiring accessories may be installed. See Zones
for bath and shower rooms below.
A supplementary bonding conductor must be provided, in addition to the main equipotential bonding
Zone 0 – being the most potentially dangerous zone for all practical purposes, no electrical equipment can be
installed in this zone.
However, the Regulations permit that where SELV fixed equipment cannot be located elsewhere, it may be installed
in this zone.
Zone 1 – water heaters, showers and shower pumps and SELV fixed equipment
Zone 2 – luminaries, fans and heating appliances and equipment from zone 1 plus shaver units to BSEN 60742
Zone 3 – fixed appliances are allowed plus the equipment from zones 1 and 2
Outside Zones – appliances are allowed plus accessories except socket outlets.
If under-floor heating is installed in these areas it must have an overall earthed metallic grid or the heating cable must
have an earthed metallic sheath, which must be supplementary bonded.