External Static Pressure (E.S.P) & Air Flow
External Static Pressure (E.S.P) & Air Flow
Hl 115 8.7
Standard Mid 110 6(59) 7.3 4(39) 8(78)
Low 105 5.6
High Hl 135 11.3
Mid 130 8(78) 9.6 6(59) 12(118)
(factory set)
Low 120 6.5
15k 11.0
Hl 123
Standard Mid 120 6(59) 10.1 4(39) 8(78)
Low 115 8.7
High HI 140 13.0
Mid 135 8(78) 11.3 6(59) 12(118)
(factory set)
Low 130 9.6
18k
HI 130 13.2
Standard Mid 125 6(59) 11.7 4(39) 8(78)
Low 110 7.3
High HI 150 16.0
Mid 145 8(78) 14.4 6(59) 12(118)
(factory set) Low 140 13.0
24k
HI 145 17.5
Standard Mid 135 6(59) 14.7 4(39) 8(78)
Low 128 12.6
Note:
The above table shows the available E.S.P. range.
Indoor Units
ARNU48GBRA2, ARNU54GBRA2
Capacity Mode Standard
Set value ESP(mmAq(Pa)) Lower Limit of External Upper Limit of External
CMM Static Pressure(mmAq(Pa)) Static Pressure(mmAq(Pa))
High HI 116 44.8
Mid 111 14(137) 40.6 10(98) 20(196)
(factory set) 33.3
Low 106
48k 44.4
HI 106
Standard Mid 102 10(98) 39.5 7(67) 14(137)
Low 95 33.5
High HI 121 51.0
Mid 116 14(137) 44.8 10(98) 20(196)
(factory set) 40.6
Low 111
54k 51.5
HI 112
Standard Mid 108 10(98) 47.5 7(67) 14(137)
Low 102 39.5
ARNU76GB8A2, ARNU96GB8A2
Standard Lower Limit of External Upper Limit of External
Capacity Mode Set value ESP(mmAq(Pa)) CMM
Static Pressure(mmAq(Pa)) Static Pressure(mmAq(Pa))
High HI 102 60.0
Mid 98 22(216) 50.0 12(118) 25(245)
(factory set)
76k Low 98 50.0
HI 86 64.0
Standard Mid 83 15(147) 50.0 12(118) 25(245)
Low 83 50.0
High HI 105 72.0
Mid 102 22(216) 64.0 12(118) 25(245)
(factory set) Low 102 64.0
96k
HI 94 76.0
Standard Mid 89 15(147) 64.0 12(118) 25(245)
Low 89 64.0
Note:
The above table shows the available E.S.P. range.