Internship Report Final.1
Internship Report Final.1
CHAPTER 1
INTRODUCTION
Objectives
Initially, there are one 66 kV incoming lines marked ‘I/C KIADB’ and one outgoing lines
marked ‘O/G-SHANTHIGRAMA’ connected to the bus-bars. Such an arrangement of one
incoming lines is called a Loop in Loop out.
Presently the station distributes 10 number of 11kV Feeder lines and Two capacitor bank
• KMF
• UDAYAGIRI
• RING ROAD
• GHANDIPURA
• BUVANAHALLI
• SERI CULTURE
• DODDAPURA
• SATHYAMANGLA
• F-1 STATION AUXILARY
• INTER LINK
CHAPTER 2
CLASSIFICATION OF SUB-STATION
The substation is the medium of transferring the power from generating unit to the consumer end.
It consists of different types of equipment like power transformer, isolator, circuit breaker, etc.
Power cable which helps in the power to the load. The sub categories of the electrical substations
are explained below. The substation which generates the power is known as the generating
substation. Similarly, the transmission substation transmits the power, and the distributing
substations distribute the power to the load. The subcategories of the electrical substations are
explained below [2].
The substations may be classified in numerous ways, such as
• Nature of duties
• Service rendered
• Operating voltage
• Importance and
• Design.
Figure 2.1 show the step-up primary substation. There can also be a tap on the incoming power
feed from the generation plant to provide electric power to operate equipment in the generation
plant [3].
line for use in an industrial facility along the way. Otherwise, the power goes to a distribution
substation.
In addition to transforming voltage, distribution substations also isolate faults in either the
transmission or distribution systems. Distribution substations are typically the points of voltage
regulator, although on long distribution circuits (of several miles/kilometers), voltage regulation
equipment may also be installed along the line [3].
• Transformer substation
• Switching substation and
• Converting substation.
This equipment transforms the electrical current to allow it to keep moving through the bulk
power system or to move into the local grid, where it goes to consumers. In addition to converting
power for local use, a transformer substation will send bulk power back out into the system. Since
it is nearly impossible to store electricity of this type, the transformer takes excess power out of
the local system and converts it back to bulk power. In addition, whenever the local system has
enough power, the transformer substation will send any bulk power it receives back out into the
grid [4].
• Grid Substations- This substation is used for transferring the bulk power from one point
to another. If any fault occurs on the substation, then the continuity of whole of the supply
is affected by it.
• Town Substations- These substations down the voltages at 33/11kV for more distribution
in the towns. If there are any faults occurs in this substation, then the supply of the whole
town is blocked.
• Indoor Substations.
• Outdoor type substations.
A. Pole Mounted Substations.
B. Foundation Mounted Substations.
The indoor substation is subdivided into several compartments like control compartment,
indicating and metering instruments and protective device compartment main bus-bar
compartment, current transformer and cable sealing box compartment as shown below in figure
2.3.
The transformers having a capacity up to 500 KVA are mounted on the double pole structure and
for the transformer having a capacity between 25 to 250 KVA 4-pole structure with the suitable
platform is used. Such types of the substation are placed in very thickly populated location. Their
maintenance cost is low, and by using a large number of the substation in a town, it is desirable
to lay the distributors lower cost.
CHAPTER 3
A single line diagram also called the one-line diagram is a symbolic or graphical representation
of a three-phase power system. It has a diagrammatic representation of all the equipment and
connections. The electrical elements such as circuit breakers, transformers, bus bars, isolator and
conductors, are represented using standardized schematic symbols so that they can be read and
understood easily. In a single line diagram, instead of representing each of three phases with
separate lines, only a single conductor is represented using a single line. A single line diagram
makes it easy to understand an electrical system, particularly in the case of complicated systems
in substations. It helps in a detailed study and evaluation of the system and its efficiency [7].
The figure 3.1 represent single line diagrams of typical power substation 66/11kV and their power
flow, principles of incoming lines (incomers) and outgoing lines (feeders), bus bar arrangement
functionality and so on.
There are one 66 kV incoming lines marked ‘I/C KIADB’ and one outgoing line marked ‘O/G-
SHANTHIGRAMA’ connected to the bus-bars. Such an arrangement of one incoming line is
called a Loop in Loop out. Figure 3.2 shows the symbols used in single line diagram.
3.3 Advantages
• Gives an overall understanding of the system and eases evaluation.
• It simplifies the trouble shooting process and makes it faster.
• It further ensures the safety of personnel and makes maintenance more convenient.
• It ensures a safer and more reliable operation of the system.
• Help identify fault locations and simplifies troubleshooting.
CHAPTER 4
CONTROL PANEL
An electrical control panel is an enclosure, typically a metal box or plastic molding which
contains important electrical components that control and monitor a number of mechanical
processes. They are energized systems that require maintenance, with planned preventative
maintenance and condition-based monitoring being the most effective methods. Electrical
personnel will need to gain access within control panels for fault finding, adjustments, and
electrical safety testing [9].
Operators will interact with the control of the panel to operate and control the plant and process.
Components within the control panel will facilitate many tasks, for example, they may monitor
flower of power in Substation.
An Electrical control panel is a CRCAM sheet enclosure that contains electrical switch gear that
controls and monitors a mechanical process electrically.
The figure 4.1 shows the power control center. A reputed PCC panel manufacturer read all field
data received for electrical power panels are designed. Power control center Panels are the most
essential part of electrical system. An industry from where the power of the industry is controlled.
All the base plates are neatly mounted with necessary electrical components to ease the wire
routings & wherever necessary PVC ferrules provided. The component Identification stickers are
provided both on the components & base plates. Main power control board which consists of
feeder breakers and provide breakers, monitoring devices and control devices.
controller through separable connectors. The motor is wired to terminals in the controller. Motor
control centers provide wire ways for field control and power cables [10].
CHAPTER 5
SUBSTATION EQUIPMENTS
For transferring of electrical power from generating unit to distributing unit’s various types of
electrical equipment are required. The equipment like bus bars, isolator, power transformer etc.,
are assembled together in the electrical substation through which consumers get electrical supply.
Working principle
The lightning arrester working principle is, once the voltage surge travels throughout the
conductor then it reaches the location of the lightning arrester where it is installed. So, it will
breakdown the insolation of the lightning arrester for a moment, so voltage surge can be discharge
towards the ground.
Once the voltage of the system falls under the fixed value, then the insulation will be restored
among the ground and conductor. Further, the current flow towards the ground will be stopped.
5.2 Isolator
It is a type of switches which is employed only for isolating the circuit when the current has only
been interrupted. The isolator is called disconnected switches operates under no load condition.
They are not equipped with arc-quenching devices. They do not have any specified current
breaking capacity or current making capacity. In some cases, it is used for breaking the charging
current of the transmission line [11].
Electrical Isolator is used to separate any type of electrical component from the system while the
system is offline/ online. Isolator doesn’t include any kind of system for avoiding arching
throughout disconnection. As in an electrical substation, an electrical isolator switch is mainly
used for disconnecting a power transformer once it is in a no-load situation otherwise a little load
is there. In full load condition, isolators don’t operate. Figure 5.2 shows the single break isolator
whereas Figure 5.3 shows the double break isolator.
Figure 5.2: Single break isolator [11] figure 5.3: Double break isolator [11]
Working principle
An electric isolator working principle is extremely easy as it operates in different ways like
manually operated, semi-automatic, and fully-automatic. Sometimes, these are used like switches
so-known as electrical isolator switches. This switch can be opened or closed depending on the
necessity. However, several times, these are arranged in a fixed position permanently to maintain
isolation like transformers, in electrical transmission lines, grid stations.
An electrical isolator switch is one kind of device used to isolate a specific circuit by maintaining
as well as preventing flowing currents. These switches are used in electrical appliances like
kitchen tools, power grids, etc. Isolator switches are available in different types like a single-
pole, double-pole, 3-pole, 4-pole, fused, and battery isolator switches.
Working principle
During the normal operating conditions, the contact of the oil circuit breaker is closed and carry
the current. When the fault occurs in the system, the contacts of the breaker are moving apart,
and an arc is struck between the contacts. Due to this arc, a large amount of heat is liberated, and
a very high temperature is reached which vaporizes the surrounding oil into gas. The gas, thus
liberated surrounds the arc and its explosive growth around it displace the oil violently. The arc
is extinguished when the distance between the fixed and moving contact reaches a certain critical
value, depends on the arc current and recovery voltage.
The working principle of this breaker is rather different from those in any other types of circuit
breakers. The main aim of all kind of circuit breaker is to prevent the reestablishment of arcing
after current zero by creating a situation where in the contact gap will withstand the system
recovery voltage.
• It may increase the arc voltage by cooling the arc plasma. As the temperature of arc
plasma is decreased, the mobility of the particle in arc plasma is reduced; hence more
voltage gradient is required to maintain the arc.
• It may increase the arc voltage by lengthening the arc path. As the length of arc path is
increased, the resistance of the path is increased, and hence to maintain the same arc
current more voltage is required to be applied across the arc path. That means arc voltage
is increased.
• Splitting up the arc into a number of series arcs also increases the arc voltage.
• In the normal operating conditions, the contacts of the breaker are closed. When the fault
occurs in the system, the contacts are pulled apart, and an arc is struck between them. The
displacement of the moving contacts is synchronized with the valve which enters the
high-pressure SF6 gas in the arc interrupting chamber at a pressure of about 16kg/cm^2.
• The SF6 gas absorbs the free electrons in the arc path and forms ions which do not act as
a charge carrier. These ions increase the dielectric strength of the gas and hence the arc is
extinguished. This process reduces the pressure of the SF6 gas up to 3kg/cm^2 thus; it is
stored in the low-pressure reservoir. This low-pressure gas is pulled back to the high-
pressure reservoir for re-use.
• When the fault occurs in the system, the contacts of the breaker are moved apart and
hence the arc is developed between them. When the current carrying contacts are pulled
apart, the temperature of their connecting parts is very high due to which ionization
occurs. Due to the ionization, the contact space is filled with vapour of positive ions
which is discharged from the contact material.
• The density of vapour depends on the current in the arcing. Due to the decreasing mode
of current wave their rate of release of vapour fall and after the current zero, the medium
regains its dielectric strength provided vapour density around the contacts reduced.
Hence, the arc does not restrike again because the metal vapour is quickly removed from
the contact zone.
5.4 Conductors
In the early days conductor used on transmission lines were usually Copper, but Aluminum
Conductors have Completely replaced Copper because of the much lower cost and lighter weight
of aluminum conductor compared with a Copper conductor of the same resistance. The fact that
Aluminum conductor has a larger diameter than a Copper conductor of the same resistance is
also an advantage. With a larger diameter the lines of electric flux originating on the conductor
will be farther apart at the conductor surface for the same voltage. This means a lower voltage
gradient at the conductor surface and less tendency to ionize the air around the conductor.
Ionization produces the undesirable effect called corona.
5.5 Batteries
In electric power stations and large capacity substations, the operation and automatic control
circuits the protective relay system, as well as emergency lighting circuits, are supplied by
station batteries. Station battery is assembled of a certain number accumulator cell depending
on the operating voltage of the respective DC circuit.
Storage batteries are two types lead acid battery and acid- alkaline batteries. Lead acid battery is
most commonly used in power stations and substations because their voltage is high and very
cheap low voltage.
A battery room is a room that houses batteries for backup or uninterruptible power systems. The
rooms are found in telecommunication central offices, and provide standby power for computing
equipment in data centers. Batteries provide direct current (DC) electricity, which may be used
directly by some types of equipment, or which may be converted to alternating current
(AC) by uninterruptible power supply (UPS) equipment. The batteries may provide power for
minutes, hours or days, depending on each system's design, although they are most commonly
activated during brief electric utility outages lasting only seconds.
5.6 Transformer
A transformer that is used to measure electrical quantities like current, voltage, power, frequency
and power factor is known as an instrument transformer. These transformers are mainly
used with relays to protect the power system. The Purpose of the instrument transformer is to
step down the voltage & current of the AC system because the level of voltage & current in a
power system is extremely high. So, designing the measuring instruments with high voltage &
current is difficult as well as expensive. In general, these instruments are mainly designed for 5
A & 110 V or 1A & 110V.
• Current Transformer
• Potential Transformer
Thus, the secondary winding of this transformer works almost in the condition of a short circuit.
Referring to figure 5.9, this winding includes two terminals where one of its terminals is
connected to ground to evade the huge current. So, insulation breakdown chances will be
reduced to guard the operator from huge voltage.
CHAPTER 6
TRANSFORMER
The transformer is the heart of the substation. The transformer changes the relationship between
the incoming voltage and current and the outgoing voltage and current. Substation transformers
are rated by their primary and secondary voltage relationship and their power carrying capability.
For example, a typical substation transformer would be rated 60-11 kV and 20 MVA; meaning
the primary or high voltage is 66 kV, the secondary or low voltage is 11 kV and the transformer
has a power rating of 20 MVA or 20,000 KVA. Substation transformers, like most utility
transformers, consist of a core and coils immersed in oil in a steel tank. The oil serves both as
an insulator and as a coolant to keep the core at reliable operating temperatures. Some large
transformers have fins for the oil to circulate through and thus dissipate heat. Some add fans to
force air across the fins. Others add pumps to forcibly circulate oil. And in some situations, a
utility may even add water spray systems which sprays the transformer case with cooling water
on hot days and high load conditions [13].
Not all transformer substations have the same capabilities. Some may only convert power for
local use, while others may only retransmit power. This allows the power company to both
reduce the amount of its machinery in any one spot and lessen the likelihood that a single
accident will disrupt the entire local system. Outside of the basic transformer substation
functions described above, some stations have specific specialized functions. Collector
substations connect to a power generation system that relies on sporadic or uneven factors such
as wind or water power.
• Laminated core
• Windings
• Insulating materials
• Transformer oil
• Conservator tank
• Buchholz relay
• Breather
• Cooling tubes
• Tap changer
• Explosion vent
• HV & LV Bushings
6.1.2 Windings
Windings consist of several copper coil turns bundled together; each bundle connected to form
a complete winding. Windings can be based either on the input-output supply or on the voltage
range. Windings that are based on supply are classified into primary and secondary windings,
meaning the windings to which the input and output voltage is applied respectively. On the other
hand, windings based on voltage range can be classified into high voltage and low voltage
windings. Figure 6.3 represents the transformer winding.
Function of Conservator tank of a Transformer : When transformer is loaded and when ambient
temperature rises, the volume of oil inside transformer increases. A conservator tank of
transformer shown in figure 6.5 provides adequate space to this expanded transformer oil. It also
acts as a reservoir for transformer insulating oil [14].
6.1.7 Breather
The breather shown in figure 6.7 is a cylindrical container filled with silica gel, which is used to
keep the air that enters the tank moisture-free. This is because the insulating oil when reacts with
moisture can affect the insulation and cause internal faults. which is why it is a must to keep the
air free from moisture. In the breather, when the air passes through the silica gel, the moisture
contents are absorbed by the silica crystal [14].
• Overheating protection
• Over current protection
• Differential Protection of Transformer
• Earth Fault Protection (Restricted)
• Over-fluxing protection
The capabilities of the IDMT relay is restricted. These sorts of relays have to be set 150% to
200% of the max rated current, otherwise, the relays will operate for emergency overload
conditions.
Therefore, these relays provide minor protection for faults inside the transformer tank [15].
The Percentage Biased Current Differential Protection is used to protect power transformers and
it is one of the most common transformer protection schemes that provide the best overall
protection. These types of protection are used for transformers of rating exceeding 2 MVA. The
transformer is star connected on one side and delta connected the other side. The CTs on the star
side are deltaconnected and those on the delta-connected side are star- connected. The neutral of
both the transformers are grounded.
These small electrical discharges in the windings will heat the insulating oil, and the oil will
break down, thus it produces gases, the severity of the breakdown, detects which glasses are
created [15].
CHAPTER 7
CONCLUSION
The power system establishing the substations near load centers makes it possible to supply
quality and reliable power by the utilities at competitive prices by minimizing losses in the initial
cost of transmission and distribution network. The following aspects play a vital role in
providing reliable and quality power to the consumers by the substations. Establishing receiving
stations and substations near the load center makes it possible to supply quality and reliable
power by the utilities competitive prices by minimizing losses in transmission and distribution.
Proper design of receiving stations and substation by the use of efficient equipment provides a
high level of service continuity and flexibility of operation reducing the cost of operation and
conditions to provide efficient operation with reduced down time. Selection of site plays a very
important role in construction of substation. We also got to know the real time monitoring of
REFERENCES