AA SPEC 114001 Steel Structures
AA SPEC 114001 Steel Structures
AA SPEC 114001 Steel Structures
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
1 SCOPE 2
2 TECHNICAL REQUIREMENTS TO BE SPECIFIED 3
3 DEFINITIONS 3
4 REQUIREMENTS 4
4.1 DESIGN STANDARDS, SPECIFICATIONS AND RELATED PUBLICATIONS 4
4.2 DESIGN RESPONSIBILITY 4
4.3 QUALITY MANAGEMENT OF DESIGN PROCESS 4
4.4 DESIGN CALCULATIONS 4
4.5 DESIGN DRAWINGS 8
4.6 APPROVAL OF DESIGNS AND DESIGN DRAWINGS 8
4.7 REVIEW OF CONNECTION DESIGN DETAILS AND FABRICATION DRAWINGS 8
4.8 MATERIALS 9
4.9 LOADS 9
4.10 LOAD FACTORS AND LOAD COMBINATIONS 13
4.11 FOUNDATION LOADS 13
4.12 DESIGN REQUIREMENTS AND PROCEDURES 13
4.13 DEFLECTIONS 13
4.14 CONSTRUCTION DETAILS 14
APPENDIX A: RELATED DOCUMENTS 18
APPENDIX B: RECORD OF AMENDMENTS 19
APPENDIX C: MATERIAL COEFFICIENTS FOR STORED BULK SOLIDS 20
APPENDIX D: ULTIMATE LIMIT STATE LOAD FACTORS AND LOAD
COMBINATIONS FOR GENERAL STRUCTURES AND BUILDINGS 21
APPENDIX E: SERVICEABILITY LIMIT STATE LOAD FACTORS AND LOAD
COMBINATIONS FOR GENERAL STRUCTURES AND BUILDINGS 22
APPENDIX F: DYNAMIC EFFECTS OF ROTATING, VIBRATING OR IMPACTING
MACHINERY AND EQUIPMENT 23
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
1 SCOPE
This specification details the requirements for the design of steel structures, and of steel
components in structures framed in other materials, for underground and surface
applications in mine shafts and plants.
It is intended for use in the design of steel structures, provided all specific requirements,
as set out in the relevant national structural design and construction standards, and
legislation, are taken into account.
The use of this specification, together with appropriate qualifications, variations and
additions, or supplementary rules, shall be specified on the relevant design drawings, or in
the project specification, or in another Anglo American specification.
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
3 DEFINITIONS
For the purposes of this specification the following definitions shall apply:
BS : British Standard
CLIENT : The company appointing the Engineer to carry out the structural design.
The Client can also be the Owner
ENGINEER : The company responsible for the structural design, for preparation of
the Design Drawings (or approval of Design Drawings prepared by
others), for accepting the Fabrication Drawings and erection method
statement and, where applicable, inspection of construction for
conformity with the design
OWNER : Legal owner of structure, or company benefiting from the use of the
structure
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
4 REQUIREMENTS
4.1 DESIGN STANDARDS, SPECIFICATIONS AND RELATED PUBLICATIONS
All designs must adhere to the national normative codes. The design standards,
specifications and related publications listed in Appendix A form part of this specification
and all structural design shall comply with the relevant requirements of these documents.
It should be noted that only limit-states design is allowed, with the exception where
national normative codes (for example the earth quake code in Chile) refer to allowable
stress design.
Formal calculations shall be prepared for all steel structures. Calculations shall be
recorded on calculation sheets and shall be neat, logically set out, short and descriptive,
and easy to follow. Calculations shall be documented in such a way that they can be
easily audited. An index shall be provided for each set of calculations applicable to a
particular structure.
Calculations shall be retained by the engineer for a minimum period of 10 years from the
date of commissioning of the particular structure. A copy of the calculations shall be
provided to the client and the owner, who shall retain them for as long as the structure is
in use.
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
4.4.3 References
4.4.4 Headings
A logical system of main headings and sub-headings shall be used to define, on each
calculation sheet, the particular area of the structure and the particular structural
component(s) under consideration. All headings shall be underlined.
Example : Main heading : FLOOR BEAMS LEVEL 10.0
Sub-heading : BEAM B1
4.4.5 Information
For each structure or structural element, the following information shall be shown on the
relevant calculation sheet(s):
• Identification: Each structure or structural element shall be identified with an
individual component number. These component numbers shall correspond with the
component numbers shown on a drawing or sketch, included in the calculations,
defining the general arrangement of the structure.
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
When diagrams or values are shown, it must always be stated whether these values
are nominal values (un-factored) or whether they are design values (factored).
• Design calculations: If the design is done manually, all relevant manual
calculations shall be shown. If computer software is used for the design, the relevant
computer calculations, proving the adequacy of the selected section, shall be pasted
onto calculation sheets, or printed out on electronic calculation sheets. Most of the
commercially available computer design software does not perform all the required
code checks, and computer calculations thus need to be supplemented with manual
calculations (in most instances) in order to complete the design. Computer design
software shall only be used where it can be shown that the software has been
verified by manual calculation, or by comparison with different software.
All relevant load effects, e.g. bending, shear, web bearing, web crippling, axial load,
deflection, etc. shall be considered in the calculations and the adequacy of the
selected section to sustain all the relevant load effects, shall be proven.
• Conclusion: For each structural element under consideration, a conclusion shall
always be stated in the calculations, for example:
▪ USE 203 x 133 x 25 UB
▪ 203 x 133 x 25 UB ADEQUATE
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
4.4.6 Units
4.4.7 Symbols
All symbols used in the calculations shall be consistent with the symbols used in the
particular code of practice or standard being used.
For example:
M, V, C and T : Nominal (un-factored) bending moment, shear force, compressive
force and tensile force.
Mu, Vu, Cu and Tu : Design (factored) bending moment, shear force, compressive
force or tensile force.
4.4.8 Terminology
Terminology used shall be consistent with the relevant code of practice or standard used.
The terms permanent load and imposed load shall be used, rather than dead load and live
load.
All member forces, which are required for the design of end connections of steel
components shall be defined in a format suitable for issuing to the steelwork contractor.
Generally, the following minimum information will be required:
• Floor layouts with the maximum combination of design (factored) beam end shears
(and axial loads and moments, where applicable) indicated at the beam ends.
• Bracing layouts with the maximum combination of design (factored) axial forces
indicated.
• A column schedule defining the maximum design (factored) axial force in each
segment of each column.
Approved November 2019 Page 7 of 25
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
All structural calculations shall be thoroughly checked by the person conducting the
design. In addition, all structural calculations shall be reviewed for accuracy by the
responsible registered person referred to in Clause 4.2.
Approval of a design means that the design is complete, that the design constitutes an
appropriately engineered solution, that the design complies with this specification in terms
of structural strength, stability and serviceability, and that the design is fit for the intended
service. Approval of a design drawing means that the drawing is complete, that the
drawing conforms to the design and that the structural content of the drawing is correct. A
signature on a design drawing confirms that both the design and the design drawing are
approved.
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
4.8 MATERIALS
The specified steel grade for structural steel elements shall be as follows:
When designing modifications to existing structures, due cognisance shall be taken of the
actual steel grade used in the original construction.
The specified bolt property class for fasteners shall be as per Clause 4.14.5.
The steel grade and bolt property classes adopted in the design shall be specified on the
relevant design drawings and calculations.
4.9 LOADS
4.9.1 Nominal loads
Nominal permanent and imposed loads shall be determined in accordance with national
normative codes of practice and, where required, in accordance with the relevant design
standards, specifications and related publications listed in Appendix A. In addition, the
provisions of Clauses 4.9.2 to 4.9.12 shall apply.
Imposed floor loads shall be assessed with due regard to the intended use or occupancy
of the structure. Imposed floor loads shall be approved by the client and the owner prior to
commencement of design. The loads adopted in the design shall be noted on the design
drawings. The minimum uniformly distributed floor load adopted shall be as follows:
• Floors supporting electrical switchgear : 7,5 kN/m2
• Other floors and platforms (excluding office floors) : 5,0 kN/m2
• Office floors : 3,0 kN/m2
• Stairs, landings and access walkways : 3,0 kN/m2
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
Notes:
Elevated conveyor gantries, the floor area shall be taken as the solid plan area of the
gantry, including that part of the gantry below the conveyor belt
Floor members in plant buildings shall be designed to resist a minimum concentrated load
of 10 kN, placed in the centre of the span. This point load need not be considered as
cumulative with the uniformly distributed load.
Equipment loads shall be obtained from certified equipment drawings, provided by the
supplier of the equipment. Such drawings shall form part of the design calculations. The
loads adopted in the design shall be indicated on the design drawings. Where certified
loading information is unavailable, equipment loads shall be assessed in consultation with,
and approved by, the client and the owner prior to the commencement of design, and
shall be verified once certified information becomes available.
See Appendix F.
4.9.5.1 Applied loads: Loads induced by belt tension shall be resisted by support steelwork at
the point of load application, e.g. at the head end, tail end or take-up pulleys. This
requirement may be relaxed for short conveyors (20 metres or less), belt feeders and
cantilevered conveyors, which may be designed so that the belt tension loads are resisted
by the conveyor sub-structure between points of load application.
4.9.5.2 Start-up loads: Loads induced during start-up conditions shall be accurately assessed
and in no case shall be taken as less than 1.4 times the normal operating loads. The start-
up loads shall be used for both structural steelwork and foundation design.
For the assessment of loads induced by belt tensioning devices, other than gravity
devices, an impact factor of 2.0 shall apply. This impact factor need not be combined with
the factor of 1.4 referred to in Clause 4.9.5.2.
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
4.9.7.1 Terrain category: The relevant terrain category shall be assessed in consultation with,
and approved by the client and the owner. The terrain category adopted for inland terrains
shall not be less severe than a category that falls midway between areas with low
vegetation and areas with regular obstacles, as defined hereunder:
Area with low vegetation: Separations of at least 20 obstacle heights (for example grass
lands).
Area with regular obstacles: Cover of vegetation or buildings or with isolated obstacles
with separations of maximum 20 obstacle heights (such as villages, suburban terrain, and
permanent forest).
4.9.7.2 Conveyor and pipe gantries: For the assessment of wind loads on conveyor and pipe
gantries, the force coefficient Cf shall be taken as 1.6 and the effective area Ae shall be
taken as the solid projected area of the gantry, whether the gantry has open or closed
sides.
Loads imposed by stored bulk materials on walls of bunkers, silos and bins shall be
assessed in accordance with DIN 1055 Part 6.
Material coefficients for stored bulk materials, required by DIN 1055 Part 6, shall be
determined by testing. Due regard shall be given to variations in the characteristics of bulk
materials resulting from process modifications, moisture content variations, compaction,
etc. All material coefficients used in the design must be confirmed by the client and the
owner. Stored bulk materials shall be clearly identified on the design drawings.
In the absence of test results, the values given in Appendix C may be used for preliminary
design purposes.
In the calculation of material pressures, the material coefficients for pressure ratio λ and
wall friction μ shall be adjusted 10 % upwards and 10 % downwards and the pressures
shall be obtained as follows:
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
The loads applied to box fronts shall always be based on hydrostatic pressure – see ISO
10208 or SANS 10208 Part 4. In addition to the density prescriptions in Appendix C, the
minimum ore pass contents shall be taken as a minimum density of 2000 kg/m3. Loads
applied to box fronts shall be considered as operational loads, and not as emergency
loads.
Provision shall be made in the design of structures and structural elements for expansion
and contraction resulting from elevated temperatures, temperature changes and
temperature differentials. For the assessment of the effects of climatic temperature
changes on exposed structures or structural elements, a temperature variation of plus or
minus 20 C shall be considered.
Steel : 12 x 10-6 / oC
Concrete : 10 x 10-6 / oC
A formal risk assessment shall be carried out to establish whether abnormal loads or
conditions should be considered in the design. Should the risk assessment indicate that
there is an unacceptable risk of an abnormal loading event or condition occurring, the
effects of such an abnormal loading event or condition shall be taken into account in the
design. Abnormal loading events or conditions may be caused by any of the following:
• Impact from vehicles and other moving objects.
• Equipment failure.
• Explosion.
• Fire.
• Extraordinary climatic conditions: hurricane winds, floods, rain, hail, snow, etc.
• Riot and panic in crowds.
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
4.10.1 Load factors and load combinations for general structures and buildings
The minimum load factors and load combinations referenced in normative codes shall be
interpreted as a minimum as shown in Appendix D for ultimate limit states and in
Appendix E for serviceability limit states.
The provisions of national normative codes of practice and the provisions of the relevant
design standards, specifications and related publications listed in Appendix A shall apply.
In addition, the provisions of Clauses 4.12.2 and 4.12.3 shall apply.
4.12.2 Fatigue
All structural members subject to fluctuating load cycles shall be assessed for fatigue
damage in accordance with BS 7608 or BS 5400 Part 10. Except for slender or flexible
structures such as towers, masts and stacks, wind loads shall not be considered as
fluctuating loads.
See Appendix F.
4.13 DEFLECTIONS
Deflection shall be considered as a serviceability limit state. Deflections under the action
of imposed loads shall not exceed the smaller of the limits specified in the national
normative codes of practice, Annex D, or in the relevant design standards, specifications
and related publications listed in Appendix A. In addition, the maximum vertical deflection
under the action of combined permanent and imposed loads shall not exceed the
deflection limits shown in TABLE 1 in this specification.
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
TABLE 1
DEFLECTION
MEMBERS SUPPORTING: COMMENTS
LIMIT
L is the length or width of the tank and
the deflection is the relative deflection
Pressed steel panel tanks L/750
between the tank centre and tank
corners
Vehicular or rail traffic L/500 Not applicable to bridges (see BS 5400)
Overhead Vertical L/800 Based on max wheel load
cranes (or Horizontal L/800 Crane lateral load
OEM spec) Horizontal H/400 Crane lateral load or wind load
Conveyor trippers L/500
Brick or block walls L/400 Maximum deflection is 20 mm
Not cantilevered L/300
Conveyors
Cantilevered L/200
Monorail travelling carriages L/300
Unless otherwise specified, L is the span of a simply supported member, any span of a
continuous member, or the free length of a cantilevered member.
The provisions and recommendations of the relevant design standards, specifications and
related publications listed in Appendix A shall apply.
Regardless of the applied corrosion protection system, the minimum metal thickness of
steelwork shall be in accordance with TABLE 2.
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
TABLE 2
COLD-
WEBS OF I-, SEALED
FORMED ALL OTHER
EXPOSURE H- AND [- HOLLOW PLATES
PURLINS SECTIONS
SECTIONS SECTIONS
AND GIRTS
Steel exposed to
severe corrosive
environments
6,5 mm 6,0 mm Not allowed 8,0 mm 8,0 mm
Steel in
underground
construction
Steel exposed to
5,5 mm 5,0 mm Not allowed 6,0 mm 7,0 mm
the weather
Steel not exposed
to severe 3,0 mm
corrosive [use only if
environments 5,0 mm 4,5 mm specifically 5,0 mm 6,0 mm
agreed to by
Steel not exposed
the owner]
to the weather
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
Back-to-back channels or angles are not permitted for steel in underground construction,
steel exposed to the weather or steel exposed to severe corrosive environments.
For simply supported beams, i.e. beams which are designed to have vertical shear
reactions only and which are not subject to fixing moments or axial forces, end
connections shall be in accordance with AA Specification 114002.
4.14.5 Fasteners
4.14.5.1 Ordinary bolts: Unless HSFG bolts or special fasteners are required, ordinary bolts of the
following property class and minimum diameter shall be used in all bolted connections:
Main structural connections (beams, plate girders, lattice girders, trusses, rafters,
columns, posts, hangers, bracing systems, etc.): M20 Class 8.8 bolts with Class 8 nuts.
Secondary structural connections (purlins, girts, sag bars, handrail standards, stair treads,
ladders, etc.): M16 Class 4.8 bolts with Class 4 nuts.
Bolt shear resistances shall always be calculated on the assumption that the bolt threads
will be in the shear plane.
Ordinary bolts in structures supporting vibrating equipment shall be provided with lock
nuts or other means of preventing loosening of the nuts.
4.14.5.2 High strength friction grip (HSFG) bolts: The minimum bolt property class shall be
Class 8.8S.
4.14.5.3 Special fasteners: Fasteners of special types (e.g. swage-lock bolts, fitted bolts, high
strength bolts with lock nuts or patented self-locking nuts) may be used, where
appropriate. The minimum bolt property class shall be Class 8.8.
The following steel sections and products may only be available in commercial quality
steel (also referred to as mild steel or steel with unknown yields tress) and shall not be
used unless it is clearly demonstrated in the design that commercial quality steel is
acceptable, using the reduced material strength for unidentified steel specified in national
normative codes of practice.
• Flat bar sections with a width smaller than 100 mm.
• Round sections with a diameter smaller than 45 mm.
• Equal angle sections with a leg length smaller than 60 mm.
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
The latest editions of the following documents are deemed to form part of this specification:
AA Specification 114002 : Construction of structural steelwork
BS EN 10025 : Hot-rolled products for non-alloy structural steels
BS EN 12285 : Workshop fabricated steel tanks
Part 2: Horizontal cylindrical single skin and double skin tanks for
the aboveground storage of flammable and non-flammable water
polluting liquids
BS EN 14015 : Specification for the design and manufacture of site built, vertical,
cylindrical, flat-bottomed, above ground, welded, steel tanks for
the storage of liquids at ambient temperature and above
BS 2853 : Specification for the design and testing of steel overhead runway
beams
BS 4076 : Specification for steel chimneys
BS 5400 : Steel, concrete and composite bridges
Part 10: Code of practice for fatigue
BS 7608 : Code of practice for fatigue design and assessment of steel
structures
BS 7854 : Evaluation of machine vibration by measurements on non-
rotating parts
DIN 1055 : Design loads for buildings
Part 6: Loads in silo bins
ISO 2631 - 1978 : Guide for the evaluation of human exposure to whole-body
vibration
(NB: Do not use SABS ISO 2631-1:1997)
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
• Material coefficients for stored bulk solids, as defined in DIN 1055 Part 6, shall be
determined by testing.
• For preliminary design purposes only, the values given in the following table can be used:
BULK ANGLE OF PRESSURE COEFFICIENTS
BULK OVERPRESSURE MATERIAL
DENSITY SLOPE RATIO OF WALL
MATERIAL COEFFICIENT COEFFICIENT
(kN/m3) (DEGREES) (Ph/Pv) FRICTION
1 2 3 eh G
Coal
11,0 40 0,45 0,60 0,45 0,40 1,4 0,5
(crushed)
Coal
17,5 35 0,45 0,70 0,60 0,50 1,5 0,5
(pulverised)
Platinum ore
24,0 40 0,45 0,70 0,60 0,50 1,3 0,5
(Merensky)
Platinum ore
28,0 40 0.45 0,70 0,60 0,50 1,3 0,5
(UG2)
Note:
Where the effective coefficient of internal friction has been established by testing, the pressure ratio
may be calculated as follows:
= 1,1 (1 – Sin )
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
APPENDIX D: ULTIMATE LIMIT STATE LOAD FACTORS AND LOAD COMBINATIONS FOR
GENERAL STRUCTURES AND BUILDINGS
The following table gives load factors to be applied to commonly encountered nominal loads when
determining design load combinations at the ultimate limit state.
The listed load factors are not applicable to headgear and collar structures, stages, conveyances
and shaft system structures. For these structures refer to ISO 10208 or SANS 10208.
LOAD
LOAD FACTORS TO BE APPLIED TO NOMINAL LOADS
COMBINATION
Gn Qn Qm n Qf n Qr n Wn Cv n Ch n Tn
1 1,5
2 1,2 * 1,6 1,6 1,3 0,5 # 0 0,8 0,8 0,6
3 1,2 * 0,5 + 1,6 1,3 0,5 # 0 0,8 0,8 0,6
4 1,2 * 0,5 + 1,6 1,3 0,5 # 0 0,8 0,8 0,6
5 1,2 * 0,5 + 1,6 1,3 1,6 0 0,8 0,8 0,6
6 1,2 * 0,5 + 1,6 1,3 0,5 # 1,3 $ 0,8 0,8 0,6
7 1,2 * 0,5 + 1,6 1,3 0,5 # 0 1,6 1,2 0,6
8 1,2 * 0,5 + 1,6 1,3 0,5 # 0 1,2 1,6 0,6
9 1,2 * 0,5 + 1,6 1,3 0,5 # 0 0,8 0,8 1,2
10 0,9 1,3 $
Notes:
1. Dominant imposed loads shown bold.
2. # For accessible roofs only. Use 0 for inaccessible roofs.
3. + For un-sustained floor loads only. Use 1.0 for sustained floor loads (e.g. filing, storage and
parking).
4. $ Use 1.5 for chimneys, light masts and free-standing towers.
5. * For permanent loads which can be accurately assessed only. Use 1.4 if there is any doubt
about the accuracy of the load.
6. For other loads, e.g. seismic and settlement loads, refer to national normative codes of
practice
7. Throughout this Appendix, load can also be read as load effect.
8. Nominal loads:
Gn = Permanent load
Qn = Imposed floor load
Qm n = Imposed material load (e.g. bunker contents), plant load or equipment load
Qf n = Imposed load from fluids (e.g. tank or pipe contents)
Qr n = Imposed roof load
Wn = Wind load
Cv n = Vertical crane load
Ch n = Horizontal crane load
Tn = Temperature load
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
The following table gives load factors to be applied to commonly encountered nominal loads when
determining design load combinations at the serviceability limit state.
The listed load factors are not applicable to headgear and collar structures, stages, conveyances
and shaft system structures. For these structures refer to ISO 10208 or SANS 10208.
LOAD
LOAD FACTORS TO BE APPLIED TO NOMINAL LOADS
COMBINATION
Gn Qn Qm n Qf n Qr n Wn Cv n Ch n Tn
1 1,1 1,0 1,0 1,0 0,3 # 0 0,5 0,5 0,5
2 1,1 0,3 + 1,0 1,0 0,3 # 0 0,5 0,5 0,5
3 1,1 0,3 + 1,0 1,0 0,3 # 0 0,5 0,5 0,5
4 1,1 0,3 + 1,0 1,0 1,0 0 0,5 0,5 0,5
5 1,1 0,3 + 1,0 1,0 0,3 # 0,6 0,5 0,5 0,5
6 1,1 0,3 + 1,0 1,0 0,3 # 0 1,0 0,75 0,5
7 1,1 0,3 + 1,0 1,0 0,3 # 0 0,75 1,0 0,5
8 1,1 0,3 + 1,0 1,0 0,3 # 0 0,5 0,5 1,0
9 1,0 0,6
Notes:
1. Dominant imposed loads shown bold.
2. # For accessible roofs only. Use 0 for inaccessible roofs.
3. + For un-sustained floor loads only. Use 0.6 for sustained floor loads (e.g. filing, storage
and parking).
4. Throughout this Appendix, load can also be read as load effect.
5. Nominal loads:
Gn = Permanent load
Qn = Imposed floor load
Qm n = Imposed material load (e.g. bunker contents) and plant load or equipment
load
Qf n = Imposed load from fluids (e.g. tank or pipe contents)
Qr n = Imposed roof load
Wn = Wind load
Cv n = Vertical crane load
Ch n = Horizontal crane load
Tn = Temperature load
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
1. General: Suitable provision shall be made in the design for the dynamic effects of
rotating, vibrating or impacting machinery and equipment. Dynamic effects shall be
determined and interpreted in accordance with this Appendix.
2. Structural framing: In general, the transmission of dynamic loads from floor members to
columns and foundations shall be by the shortest and most direct route possible. Where
practical, the vibrating part(s) of the structure shall be isolated from the rest of the
structure.
3. Dynamic loads: The magnitude, direction and exciting frequency of all dynamic loads
induced by machinery and equipment such as feeders, screens, shaking tables and
crushers, shall be obtained from the manufacturers of the equipment. The nature of the
dynamic excitation i.e. harmonic, periodic or random impulse-type excitation shall be
clearly established. Dynamic loads, obtained from manufacturers, shall be verified from
dynamic data such as motor torque, eccentricity of unbalanced masses, spring stiffness,
screen stroke and screen stroke angle.
Where a single structure supports multiple machinery units, the worst combination of any
two machines acting in phase shall be considered, unless machines are electrically or
mechanically coupled. Where multiple machines are electrically or mechanically coupled,
the worst combination shall be based on a rational assessment.
4. Modal analysis: A modal analysis shall be conducted to obtain the mode shape and
natural frequency of each significant vibration mode. A significant vibration mode is a
mode which is compatible with the displacement(s) produced by the dynamic load(s).
5. Dynamic response: The following dynamic responses shall be obtained at all strategic
locations on the structure:
• amplitude of acceleration and displacement
• amplitude of dynamic stress
6. Resonance: For the purposes of this Clause, resonance is defined as the condition in
which the exciting frequency (fe) equals the natural frequency (fn) of any significant
vibration mode of the structure.
When fn1 ≥ 1,4 fe the structure is considered high-tuned and when fn1 ≤ 0,6 fe the structure
is considered low-tuned (fn1 = fundamental [lowest] natural frequency of the structure).
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
High tuning is generally preferred. However, where it can be demonstrated that high
tuning is unrealistic, low tuning may be accepted provided the following conditions are
met:
• The client must approve the use of low tuning.
• The dynamic analysis must include all vibration modes up to at least a frequency of
3 fe.
• The dynamic analysis must consider start-up and shutdown conditions.
7. Vibration limits
7.1. Machine sensitivity: Vibration limits for rotating machinery shall be obtained from
BS 7854, or from the manufacturer.
7.2. Structural integrity: The integrity of all structural components subject to cyclic dynamic
stresses shall be evaluated on the basis of a fatigue assessment - see Clause 4.12.2.
7.3. Human response: For the assessment of vibrations, K-values shall be calculated from
the equations given in the following table.
EXCITING K-VALUE
FREQUENCY VIBRATIONS OF
HORIZONTAL VERTICAL
UNDETERMINED
(Hz) VIBRATIONS VIBRATIONS
DIRECTION
1 to 2 28 ah 28 au
0,5
10 av fe
2 to 4
33,5 au fe 0,25
4 to 8 56 ah / fe 20 av
8 to 80 160 av / fe 160 au / fe
Where fe = exciting frequency (Hz)
ah = root-mean-square (rms) value of horizontal acceleration( m / s2 )
au = root-mean-square (rms) value of acceleration of undetermined direction
( m / s2 )
av = root-mean-square (rms) value of vertical acceleration ( m / s2 )
1 hour 16
4 hours 7,0
8 hours 4,2
12 hours 3,5
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.
AA SPECIFICATION 114001
ISSUE 13
DESIGN OF STEEL STRUCTURES
COPYRIGHT
NOTES:
1.0 The K-value procedure followed above is equivalent to the assessment of vibrations in
accordance with ISO 2631 - 1978, using two thirds of the vibration limits obtained from the
fatigue-decreased proficiency boundary.
2.0 Unless otherwise agreed by the client and the owner, an exposure time of 8 hours shall be
adopted.
4.0 When vibration occurs simultaneously at more than one discrete frequency within the
range 1 to 80 Hz, each frequency component shall be evaluated separately with reference
to the appropriate limit at that frequency.
5.0 For the evaluation of narrow-band and broad-band vibrations, refer to ISO 2631- 1978.
6.0 If vibrations occur in more than one direction simultaneously, the corresponding limits
apply separately in each direction.
7.0 If vertical and horizontal vibrations occur at the same location, an equivalent K-value shall
be evaluated from the following equation:
Anglo American accepts no liability for any damage whatsoever that may result from the use of this material or the
information contained therein, irrespective of the cause and quantum thereof.