Analog Input: Features

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Analog Input

Features
 8-channel Analog Input

 Current Input, Voltage Input and Thermocouple Input

 High Resolution: 16-bit

 3000 VDC Intra-module Isolation

 35 VDC Overvoltage Protection

I-87018 I-87018-G
8-ch Thermocouple Input Module

 Introduction
The I-87018 is an 8-channel analog input module that provides current input and voltage input,
as well as thermocouple input. The input type can be set to either current or voltage, as well as
thermocouple. The I-87018 also features 3000 VDC intra-module isolation.

 Applications  I/O Specifications


●Building Automation Analog Input
●Factory Automation Channels 8
●Machine Automation Type Voltage, Current, Thermocouple
●Remote Maintenance Sensor Type
Thermocouple
(J, K, T, E, R, S, B, N, C, L, M, LDIN43710)
●Remote Diagnosis
Resolution 16-bit
●Testing Equipment
Accuracy ±0.1% of FSR

Sampling Rate 10 Hz (Total)

-3dB Bandwidth 15.7 Hz

 System Specifications Input Impedance >400 kΩ

CPU Module Common Mode Rejection 150 dB


Yes, Module (1.6 Seconds), Communication Normal Mode Rejection 100 dB
Watchdog Timer
(Programmable)
Overvoltage Protection -35 VDC ~ +35 VDC
Isolation

Intra-module Isolation 3000 VDC

LED Indicators/Display  Thermocouple Type


Status 1 x Power and Communication Type Temperature Range

COM Ports J -210 ~ +760 °C

Baud Rate 115200 bps K -270 ~ +1372 °C

Data Format N, 8, 1 T -270 ~ +400 °C

Protocol DCON E -270 ~ +1000 °C

Power R 0 ~ +1768 °C

Power Consumption 1.1 W Max. S 0 ~ +1768 °C

Mechanical B 0 ~ +1820 °C

Dimensions (W x L x H) 31 mm x 116 mm x 88 mm N -270 ~ 1300 °C

Environment C 0 ~ 2320 °C

Operating Temperature -25 ~ +75 °C L -200 ~ +800 °C

Storage Temperature -30 ~ +75 °C M -200 ~ +100 °C

Humidity 5 ~ 95% RH, Non-condensing LDIN43710 -200 ~ +900 °C

ICP DAS CO., LTD Website: http://www.icpdas.com Vol. 2020.10 1/2


 Internal I/O Structure  Dimensions (Units: mm)

88.0
66.7 31.0
Temperature Vin0+
Sensor Vin0-
Vin1+
Vin1-
57.0
Photo-isolation 116.0 54.0
TxD ESD 101.2 22.0
RxD Embedded
ADC Protection 110.0
Controller MUX
INIT Block

EEPROM 4.0

Vin6+ 4.6
+V Vin6-
+5 V Vin7+ Left View Front View Top View
GND Vin7-
-V

 Wire Connections  Pin Assignments


Voltage Input Wire Connection
Voltage Input Wiring Terminal No. Pin Assignment

Vin+ -87018 01 Vin0+


+ H/A
mV/V V 0 1 2 3 4 5 6 7 02 Vin0-
- Vin- L/A
8 CH Analog Input
03 Vin1+
04 Vin1-
Current Input Wire Connection
05 Vin2+
Current Input Wiring
06 Vin2-
Vin+ 07 Vin3+
Vin- 1 08 Vin3-
ƻ 09 Vin4+
Note: When connecting to a current source,
10 Vin4-
DQRSWLRQDOH[WHUQDOƻUHVLVWRULVUHTXLUHG
11 Vin5+
Thermocouple Input Wire Connection 12 Vin5-

Thermocouple Input Wiring 13 Vin6+


14 Vin6-
+ Vin+
15 Vin7+
- Vin-
16 Vin7-

16

 Ordering Information
I-87018 CR 8-ch Thermocouple Input Module (Blue Cover) (RoHS)

I-87018-G CR 8-ch Thermocouple Input Module (Gray Cover) (RoHS)

 Accessories
2AB125R 125 Ω, 0.1% DIP Resistor used for Current Type Input Modules

ICP DAS CO., LTD Website: http://www.icpdas.com Vol. 2020.10 2/2