Rele Off Delay Tele

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

V2ZE10 24-240V AC/DC

VEO
Art.Nr.: 125110

V2ZE10P 24-240V AC/DC


TIME RELAY / SINGLE-FUNCTION TIME RELAY Art.Nr.: 125610

On-Delay Control elements

10 time ranges Fine adjustment

Setting of time range


Supply voltage 24-240V AC/DC
Status indication
1 change-over contact
LED U/t: Supply voltage
Width 22,5mm LED R: Relay status

TECHNICAL DATA
SUPPLY CIRCUIT

Terminals A1-A2

Supply voltage 24 … 240 V AC/DC

Supply voltage tolerance -15 / +10 %

Rated frequency 50/60 Hz or DC

Rated frequency tolerance 48 … 63 Hz

Rated consumption 230 V AC typ. 0,35 W / 0,7 VA

24 V DC typ. 0,25 W / 0,25 VA

Standby consumption 230 V AC typ. 0,16 W / 0,3 VA

24 V DC typ. 0,03 W / 0,09 VA

Duty-cycle 100%

Backup power time < 30 ms

Recovery time > 100 ms

Drop-out voltage ≥ 15,5 V

TIMING CIRCUIT

Time ranges 10 0,05 … 1 s


0,15 … 3 s
0,5 … 10 s
1,5 … 30 s
3 … 60 s
9 … 180 s
0,5 … 10 min
3 … 60 min
0,5 … 10 h
5 … 100 h

http://tele-online.com Page 1 of 7
V2ZE10 24-240V AC/DC

VEO
Art.Nr.: 125110

V2ZE10P 24-240V AC/DC


TIME RELAY / SINGLE-FUNCTION TIME RELAY Art.Nr.: 125610

RANGE OF FUNCTIONS

Functions 1 E

STATUS INDICATION

Supply voltage / time lapse LED U/t (green) on supply voltage applied

LED U/t (green)


flashes
indication of lapse of time

Relay status LED R (yellow) on output relay energized

OUTPUT CIRCUIT

Terminals 15-16-18

Kind of output Relay

Number of contacts change-over


1
contact

Contact material AgNi

Rated voltage
250 V
(IEC 60947-5-1)

Maximum switching voltage 400 V AC

Minimum switching voltage / switching current 12 V / 10 mA

Rated current AC-1 8 A / 250 V


(IEC 60947-5-1)
AC-15 1,5 A / 240 V (B300)

DC-12 8 A / 24 V

Endurance mechanical 20 x 10⁶ switching cycles

electrical (AC-1) 100 x 103 switching cycles

Rated frequency of operation with load 6/min

without load 1200/min

Fuse rating 8 A fast acting

ACCURACY

Base accuracy < 1 % (of full scale)

Setting accuracy < 5 % (of full scale)

Repeat accuracy < 0,5 % or ±5 ms

Temperature influence < 0,01 % / °C

Voltage influence -

Frequency influence -

http://tele-online.com Page 2 of 7
V2ZE10 24-240V AC/DC

VEO
Art.Nr.: 125110

V2ZE10P 24-240V AC/DC


TIME RELAY / SINGLE-FUNCTION TIME RELAY Art.Nr.: 125610

ENVIRONMENTAL CONDITIONS

Ambient temperature operation -25 … +60 °C

storage -40 … +70 °C

Relative humidity 5 … 95 %

Vibration EN 61812-1 10 … 60 Hz: 0,15 mm; 60 … 150 Hz: 20 m/s2

EN 60947-1 2 … 13,2 Hz: 1 mm; 13,2 … 100 Hz: 7 m/s2

Shock EN 60947-1 ±150 m/s2 11 ms

GENERAL DATA

Dimensions W×H×D 22,5 x 67 x 76 mm

Mounting DIN rail (EN60715)

Mounting position any

Housing material PA 66, self-extinguishing plastic, class V-0

Degree of protection housing IP40

terminals IP20

Electrical connection V2ZE10 Screw terminal

Wire size flexible with wire


0,5 … 2,5 mm² (20 AWG … 13 AWG)
end ferrule

flexible without
wire end ferrule
0,5 … 4 mm² (20 AWG … 12 AWG)

rigid 0,5 … 4 mm² (20 AWG … 12 AWG)

Stripping length 8 mm

Tightening torque max. 1Nm

Electrical connection V2ZE10P Push-in terminal

Wire size flexible with wire


0,25 … 1,5 mm² (24 AWG … 16 AWG)
end ferrule

flexible with
plastic ferrule
0,25 … 0,75 mm² (24 AWG … 19 AWG)

flexible without
wire end ferrule
0,2 … 1,5 mm² (24 AWG … 16 AWG)

rigid 0,2 … 1,5 mm² (24 AWG … 16 AWG)

Stripping length 8 mm

MTTF -

Weight 84 g

ISOLATION DATA

Pollution degree
2
(IEC 61812-1)

Overvoltage category
III
(IEC 61812-1)

http://tele-online.com Page 3 of 7
V2ZE10 24-240V AC/DC

VEO
Art.Nr.: 125110

V2ZE10P 24-240V AC/DC


TIME RELAY / SINGLE-FUNCTION TIME RELAY Art.Nr.: 125610

ISOLATION DATA

Rated Insulation voltage supply circuit /


300 V
(IEC 61812-1) output cicuit

Rated impulse withstanding voltage supply circuit /


6 kV
(IEC 61812-1) output cicuit

Insulation test voltage supply circuit /


3200 V
(IEC 61812-1) output cicuit

Insulation supply circuit /


protective seperation
output cicuit

STANDARDS

Product standard IEC 61812-1

Interference immunity IEC 61812-1 class A

Interference emission IEC 61812-1 class A

Approvals

http://tele-online.com Page 4 of 7
V2ZE10 24-240V AC/DC

VEO
Art.Nr.: 125110

V2ZE10P 24-240V AC/DC


TIME RELAY / SINGLE-FUNCTION TIME RELAY Art.Nr.: 125610

FUNCTIONS

ON delay (E)
When the supply voltage U is applied, the set interval t begins
(green LED U/t flashes). After the interval t has expired (green U
LED U/t illuminated) the output relay R switches into on-po-
sition (yellow LED illuminated). This status remains until the LED U/t
supply voltage is interrupted. If the supply voltage is inter-
rupted before the expiry of the interval t, the interval already
R t <t
expired is erased and is restarted when the supply voltage is
next applied.

http://tele-online.com Page 5 of 7
V2ZE10 24-240V AC/DC

VEO
Art.Nr.: 125110

V2ZE10P 24-240V AC/DC


TIME RELAY / SINGLE-FUNCTION TIME RELAY Art.Nr.: 125610

CONNECTIONS

UN (+)
(-)

A1 A2

16 18 15

16 18 15

http://tele-online.com Page 6 of 7
V2ZE10 24-240V AC/DC

VEO
Art.Nr.: 125110

V2ZE10P 24-240V AC/DC


TIME RELAY / SINGLE-FUNCTION TIME RELAY Art.Nr.: 125610

DIMENSIONS

67 mm
76 mm 22,5 mm

CONTACT

TELE Haase Steuergeräte Ges.m.b.H. CALL US +43 / 1 / 614 74 - 0


Vorarlberger Allee 38
1230 Vienna ONLINE SUPPORT [email protected]
Austria

http://tele-online.com Page 7 of 7