0% found this document useful (0 votes)
73 views2 pages

Cat De110

This document provides specifications for a Cat C4.4 diesel generator including its engine model, dimensions, performance data, and emissions compliance. It lists technical details like power ratings, fuel consumption, cooling requirements, and alternator specifications.

Uploaded by

rafkhata01
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views2 pages

Cat De110

This document provides specifications for a Cat C4.4 diesel generator including its engine model, dimensions, performance data, and emissions compliance. It lists technical details like power ratings, fuel consumption, cooling requirements, and alternator specifications.

Uploaded by

rafkhata01
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Cat C4.

4
®
DIESEL GENERATOR SETS

Standby & Prime: 50 Hz

Engine Model Cat® C4.4 Inline 4-stroke Diesel


Bore x Stroke 105.0mm x 127.0mm (4.1in x 5.0 in)
Displacement 4.4 L (268.5 in³)
Compression Ratio 16.7:1
Aspiration Turbocharged Air To Air Charge Cooled
Fuel Injection System Inline
Governor Electronic
Image shown might not reflect actual configuration

Model Standby Prime Emission Strategy


50 Hz 50 Hz
DE110E3 EU IIIA
110.0 kVA (88.0 kW) 100.0 kVA (80.0 kW)

PACKAGE PERFORMANCE
Performance Standby Prime
Frequency 50 Hz 50 Hz
Genset Power Rating 110.0 kVA 100.0 kVA
Genset power rating with fan @ 0.8 power factor 88.0 kW 80.0 kW
Emissions EU IIIA
Performance Number P4522B
Fuel Consumption
Fuel Tank Capacity, litres (US gal) 250 (66.0)
100% load with fan, L/hr (gal/hr) 24.6 (6.5) 23.4 (6.2)
75% load with fan, L/hr (gal/hr) 20.7 (5.5) 19.5 (5.2)
50% load with fan, L/hr (gal/hr) 15.6 (4.1) 14.6 (3.9)
Cooling System1
Radiator air flow, m³/min (cfm) 201.0 (7098)
Total coolant capacity, L (gal) 17.0 (4.5)
Inlet Air
Max. Combustion Air Intake Restriction, kPa (in H2O) 5.0 (20.1)
Combustion air inlet flow rate, m³/min (cfm) 6.7 (238) 6.4 (227)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 50 (122)
Exhaust System
Exhaust stack gas temperature, °C (°F) 675 (1247) 657 (1215)
Exhaust gas flow rate, m³/min (cfm) 17.4 (614) 16.4 (580)
Exhaust system backpressure (maximum allowable), kPa (in. water) 15.0 (4.4)
Heat Rejection
Heat rejection to jacket water, kW (Btu/min) 51.9 (2952) 47.1 (2679)
Heat rejection to alternator, kW (Btu/min) 7.8 (444)
Heat rejection to atmosphere from engine, kW (Btu/min) 22.1 (1257) 20.0 (1137)

LEHE0707-05 1/2
Cat C4.4
®
DIESEL GENERATOR SETS

Alternator3 50 Hz
Voltages 415V 400V 380V
Motor starting capability @ 30% Voltage Dip, skVA 256 240 220
Current, amps 153 159 167
Temperature Rise, °C 125/40
Frame Size LC3114F
Excitation S.E

WEIGHTS & DIMENSIONS

A B
Note: General configuration not to be used for installation. See general dimension drawings for detail.

Dim “A” mm (in) Dim “B” mm (in) Dim “C” mm (in) Dry Weight kg (lb)
2089 (82.2) 1120 (44.1) 1495 (58.9) 1190 (2623)

APPLICABLE CODES AND STANDARDS: DEFINITIONS AND CONDITIONS


AS1359, NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, 1
For ambient and altitude capabilities consult your Cat dealer. Air flow restriction
ISO8528, NEMA MG1-22, NEMA MG1-33, 2006/95/EC, 2006/42/EC, (system) is added to existing restriction from factory.
2004/108/EC. 2
Emissions data measurement procedures are consistent with those described
Note: Codes may not be available in all model configurations. Please consult your
in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM,
local Cat Dealer representative for availability.
NOx. Data shown is based on steady state operating conditions of 77° F, 28.42
STANDBY: Output available with varying load for the duration of the interruption in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The
of the normal source power. Average power output is 70% of the standby power nominal emissions data shown is subject to instrumentation, measurement,
rating. Typical operation is 200 hours per year, with maximum expected usage of facility and engine to engine variations. Emissions data is based on 100% load
500 hours per year. and thus cannot be used to compare to EPA regulations which use values based
on a weighted cycle.
PRIME: Output available with varying load for an unlimited time. Average power
output is 70% of the prime power rating. Typical peak demand is 100% of prime 3
Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.
rated ekW with 10% overload capability for emergency use for a maximum of 1
hour in 12. Overload operation cannot exceed 25 hours per year
RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings
also apply at ISO3046 standard conditions.

www.Cat.com/electricpower
All rights reserved.
Materials and specifications are subject to change without notice.The International System of Units (SI) is used in this publication.
© 2021 Caterpillar. All Rights Reserved. CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow”, the “Power Edge” and
LEHE0707-05 (06/21) Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission
2/2

You might also like