Igs Log 3 0
Igs Log 3 0
IGS-LOG
IG,IS,IGS-NT monitoring sofware
User guide
• What is IGS-LOG?
• Communication
• Functions
Installation
The program is contained in the controller installation packages and does not have separate
installation package.
Hint
The program requires HASP dongle and appropriate drivers. The drivers are installed automatically
from the main installation package. Do not cancel the installation of the drivers.
Without a valid dongle the program will run in time-limited mode for 60min only.
Settings
Basic
This is path to the directory where the Sites structure is stored. If
Sites directory InteliMonitor is istalled together with IGS-LOG, both programs should share
the same sites directory.
Hint
IGS-LOG 3.0 is not compatible with Sites from WinEdit!
Fonts
Font that will be used for IGS-LOG menus, dialogs, messages etc.
Application font Changing of the font can sometimes cause wrong displaying of some
items because of different size.
Font and charset that will be used for controller history and log
Controller font windows. Auto-change charset will switch the charset automatically
according the charset in the controller.
If there are more languages in the controller, the preffered language
Preffered language will be used for history and log windows. If preffered language is not
found, default (first) is used.
Controller history
Controller history mode Automatic – gets all records form the controller
Explicit number – gets the number of records specified below
Always read history.... Use this checkbox if the controller is accessed from more
Logging
File type File type for saving logs (CSV/XLS) can be selected here.
If the log data of one site exceeds this limit, the oldest logs will be
Max disk space per site
deleted.
If the free space on the disk drops below this limit, the oldest logs
Min free disk space
will be deleted.
Open connection
Connection types
Controllers list
Open connection
Use the Connection menu item or the icon to open the connection. The sites window will appear,
which shows sites/gensets structure. Select the site you want connect to and select appropriate
connection type. See InteliMonitor documentation for more details about sites.
Hint
Access code must be entered for each controller in the site for modem or internet connection. Go to
the Acc column in the controllers section to enter the access code.
Hint
Proper COM port must be selected for direct connection!
Hint
Select modem from the list of installed modem that shall be used for the connection. Then enter
appropriate phone number.
Hint
Enter IP address of the internet bridge located on the site you are connecting to.
Offline connection
The offline connection enables to view/browse previously saved archives or logs. Select the file you
want to open from the list.
• If an archive set is opened (*.ast), combined history from appropriate archives is displayed. An
archive set can be saved using InteliMonitor.
• If a log is opened (*.xls, *.csv), log window is displayed and the log can be shown also as a
chart.
Controllers list
The controllers list window shows all active controllers in the site, their names, addresses, system
date/time and password status. Password can be also entered here and each controller can be
enabled/disabled for common history window.
Time synchronization
The column correction can be used to shift the time of history records separately for each controller to
see the common history in proper order. It is useful for the case the controllers are connected by
RS485 or are different types (Classic vs. NT line). Otherwise there is automatic time synchronisation
between controllers via CAN line, so no correction is necessary in IGS-LOG.
Recording a log
Hint
To record a log, an online connectiom must be estabilished first.
• Use Site | Logging menu item to start logging mode. The logging window will appear.
• To start/stop the logging itself, use Logging | Start or Logging | Stop menu items. The Logging
menu is visible only if the logging window is active. The log is saved automatically in the
moment of stopping it.
• When the log is running, it is possible to view it as a chart. Use Site | Chart or icon to
open charts window.
Charts
Channels
To view logged data as a chart, channels must be defined. Click to icon to open the Channels
window. Opening the window is enabled after logging is started (on-line mode) or saved log is opened
(off-line mode).
The window enables to select, edit and remove channels (columns from the log) that are displayed in
the Chart window. Channel configuration can be saved into a SHN file and used later for another
connection.
Chart
Click to to open the chart window. Opening the window is enabled after logging is started (on-line
mode) or saved log is opened (off-line mode). The Chart window displays trends of channels selected
in the channel window. The time distance between samples is given by time stamps of the samples,
which is primarily given by the Logging Interval (see chapter Logging).
time tracking - if pressed, the chart moves to show last samples. If not pressed, the chart
"freezes"
axes scroll mode - dragging of axes will shift the axe range
axes zoom mode - dragging of axes will change the axe scale
grid off
channel annotations on/off - if active, name and unit of each channel is shown in the chart
print preview
Controller history
Create an online connection and go to menu item Site | Common history to see the combined history
from all controllers that are enabled in the controllers list window.
• Each record in the common history window begins with the name of the controller the record
belongs to.
• If different types of controllers are used, some cells can be blank. A blank cell means the
respective history value (according the column) is not present in the controller, which the
respective record belongs to.
• To see the common history records in proper order, time of all controllers must be
synchronized. See controllers list chapter for more information.
• To see history of each controller separated, go to menu Site and select the appropiate
controller by name.
To see the history from an archive set saved by Intelimonitor, open appropriate AST file in off-line
connection mode. See the chapter connection types for more information.
Hint
It is not possible to save the AST file (archive set) using IGS-LOG. Use InteliMonitor instead.