Tutorial 1 - Getting Started and Basic Features
Tutorial 1 - Getting Started and Basic Features
Exercise:
1. Create a new case by using either the Menu or Toolbar. Give the case name and file path to save
the case.
2. Open the main page of your new case. Build a case to study the inrush phenomena when
energizing a transformer. The component data is as shown in Figure 1. The transformer is rated
100MVA, 230/33 kV.
RL
Source Data
Z+ = 10 Ohms at 88 Deg.
Z0 = 7 Ohms at 82 Deg.
230 kV BUS
Ea
Timed
Breaker
BRK Logic
Open@t0
BRK
Transformer Data
Notes:
Inrush is related to core saturation. Verify that saturation is included in the model used
for this simulation.
Ask your instructor to explain the large resistance connected to the LV side.
6. Inrush current magnitude depends on the ‘Point On Wave’ (POW) switching conditions. Use a
manual switch to operate the breaker. Note the point on wave dependency of the inrush peak.
BRK
BRK C O
BRK
1
Figure 3: Two-state switch attached to a control panel
RL
Source Data
15 km overhead line
TL1
Ia
230 kV BUS
Ea
C1 C2 C3
10
Tower: 3L1
30 Conductors: chukar
Ground_Wires: 1/2_HighStrengthSteel
Exercise:
1. Include a 230 kV three conductor overhead line between 230 kV bus and the ‘network
equivalence’ voltage source (see Figure 4).
1.1. Right click on the canvas and select the ‘Component Wizard’ in the drop down menu
shown in Figure 6 (a)
1.2. Select ‘Transmission Line’ tab in the pop- up window shown in
(b) (b)
(a) (b)
1.3. Click Finish ,move the mouse pointer to the canvas and place the component by a left click
1.4. Edit Parameters - Use the ‘Edit Parameters’ tab to define the line length, rated frequency
and the number of conductors
1.5. Edit Definition - Use the ‘Edit definition’ tab to define the conductor positions and
conductor material data (see Figure 5)
NOTE: The instructor will demonstrate the steps involved in adding a transmission line model
to the circuit. Overhead line data entry will be discussed in detail in a separate tutorial.
2. Run the case and observe the transformer energizing transients (Figure 7 and Figure 8 show
230kV bus voltage and transformer inrush current respectively )
Main : Graphs
230kV Bus Voltage (L-G)
200
150
100
50
0
kV
-50
-100
-150
-200
sec 0.8700 0.8750 0.8800 0.8850 0.8900 0.8950 0.9000
Main : Graphs
Transformer Current
1.20
1.00
0.80
0.60
0.40
kA
0.20
0.00
-0.20
-0.40
-0.60
sec 0.975 1.000 1.025 1.050 1.075 1.100 1.125 1.150 1.175
Exercise:
1. Modify the case to include a 12.47 kV/1.5 MVA (Wound rotor type) induction machine (see
Figure )
2. Enter the induction motor data (see under Model Data shown in Page 10)
3. Assume that the load torque is proportional to the square of the speed. The steady state load is
approximately 80% of the motor rating. i.e.
2
T ¿=0.8 ω
*
w X2 0.8 Tm
Note: Your instructor will explain the calculation program structure of EMTDC and the
definition of ‘electric’ and ‘control’ type models.
4. The breaker (initially open) will be closed at 1.5 s to start the motor.
5. Plot the following signals:
Machine speed, mechanical torque and developed electric torque.
Motor (starting) current, bus voltages (both instantaneous and rms).
Note: Some variables can be measured from within the component. These are normally listed
under the parameter section ‘Internal output variables’
TF-1
#1
100 MVA, 230 kV/33 kV
#2
Short line of 15 km (Represented by a PI
section model)
PI Section
Z+ = 0.2 E-4 + j0.3 E-3 Ohms/m
Z0 = 0.3 E-3 + j0.1 E-2 Ohms/m
Use default values for the capacitances
A
Closed@t0 V
R_C1 Transformer Data
R_C1
Logic
Breaker
Timed TF-2
3 MVA, 33 kV/12.47 kV
42.5 [uH]
#1 #2 A
IM
V
TL Switch
Tin
0
Open@t0
BM Logic
Breaker
Timed
If time permits…
Add a load of 1 MVA at 0.8-power factor at the 12.47 kV bus. The same transformer supplies this load.
Does the load see an unacceptable voltage sag during motor start?
4. Model Data
Machine Parameters
1.5 MVA Induction machine
Wound rotor Type
Voltage = 12.47 kV(L-L) /7.697 kV (Phase)
Inertia = 1.3 [s]
Turns ratio = 0.6
Stator resistance = 0.05 p.u.
Rotor Resistance = 0.08 p.u.
Magnetizing Inductance: 4.5 p.u.
Stator leakage Inductance: 0.1 p.u.
Rotor leakage Inductance: 0.1 p.u.
Short Line
Length = 15 km
Z+ ¿¿= 0.2 E-4 + j0.3 E-3 Ohms/m
Z 0= 0.3 E-3 + j0.1 E-2 Ohms/m
Use default values for the capacitances
2
T ¿=0.8 ω
*
w X2 0.8 Tm
Capacitor Leg