UPS

12-1050

UPS12-220MRX
Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.

FEATURES & BENEFITS


APPLICATIONS • 10 year design life @ 25˚C • Proprietary Fixed Orifice Plate Pasting
• Absorbent Glass Mat (AGM) technology for technology applying active materials
• Data Centers on both sides of the grid for consistent
efficient gas recombination of up
to 99% and freedom from electrolyte cell-to-cell performance, higher
• Network Operations Centers
maintenance. capacity and uniform grid protection.
• Industrial Process Control Facilities • Thermally welded case-to-cover bond to
• 3 Year Warranty (refer Dynasty warranty
• Internet Housing Sites card, 41-9027) eliminate leakage.
• Patented Long Life Alloy having the • Can be operated in any orientation.
• Semiconductor Manufacturing
lowest calcium levels in the industry - Upright, side or end mounting
• Banks & Financial Markets minimizing grid growth, reducing gassing, recommended.
• Power Generation Plants and extending battery life. • Not restricted for air transport - Complies
• Patented UL Recognized Flame- with IATA/ICAO Special Provisions A67.
• Hospitals & Testing Laboratories arresting vents in each cell for safety and • Not restricted for surface transport -
• Emergency 911 Response Centers long life. Classified as non-hazardous material
• Designed with the same recombination, as related to DOT-CFR Title 49 parts
thermal runaway prevention, gassing and 171-189.
flame retardant characteristics of the Bell- • Not restricted for water transport -
core 4228 compliant Dynasty Telecom Classified as non-hazardous material per
products. IMDG Amendment 27.
• Flame retardant polypropylene case and
cover compliant with UL94V-2

TECHNICAL DATA
Constant Power Discharge Ratings - Watts per Cell @ 25°C (77°F) 20 hour IEC Rating:
rate to 1.75 10 hour rate
Operating Time (in minutes) to 1.67 Volts per Cell
Model VPC @ to 1.80 VPC
5 10 15 20 30 40 45 50 60 90 25°C @ 20°C
UPS12-220MRX 372 278 220 178 132 110 98.5 92.3 79.8 57.7 56 AH 49 AH

Cells Per Unit Voltage Per Unit Weight 1 Min Current to 1.75VPC Short Circuit Current Internal Resistance
(Kg) (Amps) (Amps) (mOhms)

6 12.98 19 383 1985 6.37


UPS
SPECIFICATIONS
Operating Temperature Range Discharge: -40˚F (-40˚C) to +160˚F (71˚C)
with temperature compensation Charge: -10˚F (-23˚C) to +140˚F (60˚C)
Nominal Operating Temperature Range +74˚F (23˚C) to +80˚F (27˚C)
Recommended Maximum Charging C/5 amperes @ 20hr rate
Current Limit
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is required.
Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than
batteries stored at lower temperatures. See C&D brochure 41-7272, Self-Discharge and
Inventory Control for details.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77˚F (25˚C)
Terminal Threaded copper alloy insert terminal to accept 10-32 UNF.
Terminal Hardware Initial Torque 30 in.-lbs. (3.4 N-m)

DIMENSIONS

[ 17.1 ]
0.67
#10-32 UNF
[ 139.2 ]

0.87
5.48

[ 22.2 ]
[ 205.1 ]
[ 200.3 ]
8.07
7.89

9.00
[ 228.6 ]
[ 4.8 ]
0.19
8.86 5.31
[ 225.1 ] [ 134.8 ]

CONSTANT POWER DISCHARGE RATINGS


Constant Power Discharge Ratings - Watts Per Cell @ 20°C (68°F)
Operating Time To End Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 334 251 198 163 123 103 92.4 86.8 75.5 54.9
1.70 345 257 204 166 124 104 93.3 87.7 76.2 55.3
1.67 349 261 207 168 125 104 93.9 88.2 76.6 55.5
1.65 352 263 209 169 126 105 94.2 88.4 76.8 55.7

Constant Power Discharge Ratings - Watts Per Cell @ 77°F (25°C)


Operating Time To End Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 355 267 211 172.5 130 108 96.9 90.8 78.7 57.1
1.70 367 274 217 176.3 131 109 97.9 91.7 79.4 57.5
1.67 372 278 220 178.2 132 110 98.5 92.3 79.8 57.7
1.65 375 280 222 179.5 133 110 98.8 92.5 80.0 57.9

CONSTANT CURRENT DISCHARGE RATINGS


Constant Current Discharge Ratings - Amperes @ 20°C (68°F)
Operating Time To End Point Voltage (in hours)
End Point
Volts/Cell 1 2 3 5 8 10 12 20 24
1.85 37.1 20.0 14.0 8.83 5.80 4.76 4.04 2.55 2.16
1.80 38.2 20.6 14.4 9.15 6.03 4.97 4.22 2.68 2.28
1.75 39.1 21.1 14.7 9.32 6.14 5.05 4.29 2.72 2.31

Constant Current Discharge Ratings - Amperes @ 77°F (25°C)


Operating Time To End Point Voltage (in hours)
End Point
Volts/Cell 1 2 3 5 8 10 12 20 24
1.85 38.6 20.8 14.5 9.13 5.97 4.88 4.14 2.61 2.22
1.80 39.8 21.4 14.9 9.46 6.22 5.10 4.33 2.75 2.34
1.75 40.7 21.9 15.2 9.64 6.33 5.18 4.40 2.79 2.37

Any data, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc. without
notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes no
warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of
1400 Union Meeting Road such information. Further, because the product(s) featured herein may be used under conditions beyond its control,
P.O. Box 3053 • Blue Bell, PA 19422-0858 C&D Technologies, Inc. hereby disclaims all warranties, either express or implied, concerning the fitness or suitabil-
(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630 ity of such product(s) for any particular use or in any specific application or arising from any course of
[email protected] dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s)
www.cdtechno.com featured herein for user’s intended purpose and in user’s specific application.
Copyright 2010 C&D TECHNOLOGIES, INC. Printed in U.S.A. 12-1050 0110/CD