TEST REPORT FOR EOCR RELAY

ELECTROTEST DOC. No :
DATE :
PVT. LTD. TESTING DATE :
PANEL:- 415 V MCC PANEL
CLIENT : TATA STEEL ,JAMSHEDPUR FEEDER :-
LOCATION : FEEDER NO. :-
Relay Details:- Make:-LS Sl No- 21080008 Model No :- DMP06i
Current:- 0.5 – 6 A Aux supply :- 85-245 V AC/DC

Test Condition:- Relay tested at panel cubicle.


Relay Setting :-
PROTECTION SETTING
PHA 3P Ud 0.0 s
CHA Def rP ON
O-t 10 s rT 1.0 s
d-t 10 s UC 30 %
r-C 5A gF 0.05 A
Ctr 1 gT 0.5 s
Loc 600 % gD 0.0 s
StL 300 % IC 1000 %
P-f ON Id 0.0 s
Pd 0.0 s c5 1a1b
PU 20 % AL 1-tp

Test results:-
Current Injected Operating
Function Phase Time setting Remarks
setting current(A) time(sec)
Over Current(OC) R,Y,B in series 5.0 A 20.0 sec 6.0 20.243 OK
Instantaneous(IC) R,Y,B in series 1000 % 0.0 sec 50.0 0.039 OK
Lock Rotor (Loc) R,Y,B in series 600 % 10.0 sec 30.0 10.065 OK
Stall (StL) R,Y,B in series 300 % 13.0 sec 15.0 12.095 OK
E/F (g-F) CBCT / ZCT 0.05 A 0.5 sec 0.06 0.535 OK
Phase Reverse (r-P) R,Y,B in series ON 1.0 sec 1.0 1.049 OK
RY ON 0.0 sec 1.0 2.979 OK
Phase Failure
YB ON 0.0 sec 1.0 2.978 OK
(P-F)
BR ON 0.0 sec 1.0 2.975 OK
RY 20 % 0.0 sec 1.0 4.982 OK
Unbalance
YB 20 % 0.0 sec 1.0 4.980 OK
(P-U)
BR 20 % 0.0 sec 1.0 4.982 OK

Remarks : Test results found satisfactory, Relay is fit for service.

Checked by ELECTROTEST ASC TSL E&P


Name Sonu Kumar Singh
Designation: Sr. T&C Engg
Signature.
Date: