150.67-NM1 (308) Ycalyork

Download as pdf or txt
Download as pdf or txt
You are on page 1of 196

AIR-COOLED LIQUID CHILLERS

HERMETIC SCROLL
INSTALLATION, OPERATION, MAINTENANCE Supersedes 150.67-NM1 (507) Form 150.67-NM1 (308)
035-21456-000

YCAL0019, 0022, 0033, 0043, 0046, 0066


AIR-COOLED SCROLL CHILLERS
STYLE E (60 Hz)
15-60 TON

LD10950
DUAL CIRCUIT

SINGLE CIRCUIT

R-410A
FORM 150.67-NM1 (308)

IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES

This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation, maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
oils, materials under pressure, rotating components, operating/service personnel. It is expected that this
and both high and low voltage. Each of these items individual possesses independent training that will
has the potential, if misused or handled improperly, to enable them to perform their assigned tasks properly
cause bodily injury or death. It is the obligation and and safely. It is essential that, prior to performing any
responsibility of operating/service personnel to identify task on this equipment, this individual shall have read
and recognize these inherent hazards, protect themselves, and understood this document and any referenced
and proceed safely in completing their tasks. Failure to materials. This individual shall also be familiar with and
comply with any of these requirements could result in comply with all applicable governmental standards and
serious damage to the equipment and the property in regulations pertaining to the task in question.

SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:

DANGER indicates an imminently CAUTION identifies a hazard which


hazardous situation which, if not could lead to damage to the machine,
avoided, will result in death or serious damage to other equipment and/or
injury. environmental pollution. Usually an
instruction will be given, together with
a brief explanation.

WARNING indicates a potentially NOTE is used to highlight additional


haz ard ous sit u a tion which, if not information which may be helpful to
avoided, could result in death or se- you.
rious injury.

External wiring, unless specified as an optional connection in the manufacturer’s product


line, is NOT to be connected inside the micro panel cabinet. Devices such as relays, switches,
transducers and controls may NOT be installed inside the panel. NO external wiring is al-
lowed to be run through the micro panel. All wiring must be in accordance with YORK’s
published specifications and must be performed ONLY by qualified YORK personnel. YORK
will not be responsible for damages/problems resulting from improper connections to the
controls or application of improper control signals. Failure to follow this will void the
manufacturer’s warranty and cause serious damage to property or injury to persons.

2 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

CHANGEABILITY OF THIS DOCUMENT


In complying with YORK’s policy for continuous product improvement, the information contained in this document
is subject to change without notice. While YORK makes no commitment to update or provide current information
automatically to the manual owner, that information, if applicable, can be obtained by contacting the nearest YORK
Engineered Systems Service office.

It is the responsibility of operating/service personnel to verify the applicability of these documents to the equipment in
question. If there is any question in the mind of operating/service personnel as to the applicability of these documents,
then prior to working on the equipment, they should verify with the owner whether the equipment has been modified
and if current literature is available.

SINGLE CIRCUIT AND DUAL CIRCUIT MODELS

This manual contains installation, operation and maintenance instructions for both single and dual refriger-
ant circuit models. If your unit is a single circuit model (YCAL0019-0033) , disregard references to “System
2” which may appear in this manual. Any references to Sys 2 are applicable to YCAL0043-0066 models.

JOHNSON CONTROLS 3
FORM 150.67-NM1 (308)
TABLE OF CONTENTS
SECTION 1 – GENERAL CHILLER INFORMATION & SAFETY......................................................................10
INTRODUCTION .........................................................................................................................................10
WARRANTY ................................................................................................................................................10
SAFETY .......................................................................................................................................................10
Standards for Safety ...........................................................................................................................10
Responsibility for Safety ....................................................................................................................11
ABOUT THIS MANUAL ..............................................................................................................................11
MISUSE OF EQUIPMENT ...........................................................................................................................11
Suitability for Application ...................................................................................................................11
Structural Support ............................................................................................................................... 11
Mechanical Strength ..........................................................................................................................11
General Access .................................................................................................................................... 11
Pressure Systems ...............................................................................................................................12
Electrical...............................................................................................................................................12
Rotating Parts ......................................................................................................................................12
Sharp Edges.........................................................................................................................................12
Refrigerants and Oils ..........................................................................................................................12
High Temperature and Pressure Cleaning ........................................................................................12
Emergency Shutdown .........................................................................................................................12

SECTION 2 – PRODUCT DESCRIPTION .........................................................................................................13


INTRODUCTION .........................................................................................................................................13
GENERAL SYSTEM DESCRIPTION ..........................................................................................................13
Compressors .......................................................................................................................................13
Evaporator (Heat Exchanger) .............................................................................................................13
Condenser ............................................................................................................................................14
MILLENIUM CONTROL CENTER...............................................................................................................14
POWER PANEL...........................................................................................................................................15
ACCESSORIES AND OPTIONS .................................................................................................................16
Power Options .....................................................................................................................................16
Control Options ...................................................................................................................................16
Compressor, Piping, Evaporator Options .........................................................................................17
Condenser and Cabinet Options........................................................................................................17
Sound Reduction Options ..................................................................................................................17
Unit Components ................................................................................................................................19
Control / Power Panel Components .................................................................................................20
PRODUCT IDENTIFICATION NUMBER (PIN)............................................................................................23
BASIC UNIT NOMENCLATURE .................................................................................................................23
REFRIGERANT FLOW DIAGRAM .............................................................................................................28

SECTION 3 – HANDLING AND STORAGE ......................................................................................................29


DELIVERY AND STORAGE ........................................................................................................................29
INSPECTION ...............................................................................................................................................29
MOVING THE CHILLER ..............................................................................................................................29
Lifting Weights .....................................................................................................................................29
UNIT RIGGING ............................................................................................................................................31

4 JOHNSON CONTROLS
FORM 150.67-NM1 (308)
TABLE OF CONTENTS (CONT’D)
SECTION 4 – INSTALLATION ...........................................................................................................................33
INSTALLATION CHECKLIST......................................................................................................................33
HANDLING ..................................................................................................................................................33
INSPECTION ...............................................................................................................................................33
LOCATION AND CLEARANCES ................................................................................................................33
Foundation ...........................................................................................................................................33
Ground Level Locations .....................................................................................................................34
Rooftop Locations ...............................................................................................................................34
Noise Sensitive Locations ..................................................................................................................34
SPRING ISOLATORS (OPTIONAL)............................................................................................................34
COMPRESSOR MOUNTING ......................................................................................................................34
REMOTE COOLER OPTION ......................................................................................................................34
CHILLED LIQUID PIPING ...........................................................................................................................34
PIPEWORK ARRANGEMENT ....................................................................................................................35
DUCT WORK CONNECTION ....................................................................................................................36
General Requirements .......................................................................................................................36
WIRING ........................................................................................................................................................36
Evaporator Pump Start Contacts .......................................................................................................36
System Run Contacts .........................................................................................................................36
Alarm Status Contacts ........................................................................................................................37
Remote Start/Stop Contacts ...............................................................................................................37
Remote Emergency Cutoff .................................................................................................................37
Remote Temp Reset Input ..................................................................................................................37
Load Limit Input...................................................................................................................................37
Flow Switch Input ................................................................................................................................37
COMPRESSOR HEATERS .........................................................................................................................37
RELIEF VALVES .........................................................................................................................................37
HIGH PRESSURE CUTOUT .......................................................................................................................37
SINGLE-POINT SUPPLY CONNECTION ...................................................................................................38
CONTROL WIRING .....................................................................................................................................39

SECTION 5 – TECHNICAL DATA .....................................................................................................................40


OPERATIONAL LIMITATIONS (ENGLISH) ................................................................................................40
Voltage Limitations ..............................................................................................................................40
Temperatures and Flows ....................................................................................................................40
Ethylene & Propolyne Glycol Correction Factors ............................................................................40
OPERATIONAL LIMITATIONS (SI) .............................................................................................................43
Voltage Limitations ..............................................................................................................................43
Temperatures and Flows (Si) ..............................................................................................................43
Ethylene & Propolyne Glycol Correction Factors ............................................................................43
PHYSICAL DATA (ENGLISH) .....................................................................................................................46
SOUND DATA (ENGLISH) ..........................................................................................................................48
ELECTRICAL DATA (ENGLISH).................................................................................................................50
ELECTRICAL NOTES AND LEGEND ........................................................................................................53
ELEMENTARY WIRING DIAGRAM ............................................................................................................54

JOHNSON CONTROLS 5
FORM 150.67-NM1 (308)

TABLE OF CONTENTS (CONT’D)


CONNECTION WIRING DIAGRAM ............................................................................................................72
ELEMENTARY WIRING DIAGRAM DETAILS ............................................................................................80
DIMENSIONS (ENGLISH) ...........................................................................................................................82
TECHNICAL DATA – CLEARANCES .......................................................................................................106
ISOLATORS ..............................................................................................................................................109

SECTION 6 – COMMISSIONING.....................................................................................................................117
COMMISSIONING ..................................................................................................................................... 117
PREPARATION – POWER OFF................................................................................................................117
Inspection .......................................................................................................................................... 117
Refrigerant Charge ............................................................................................................................117
Service and Oil Line Valves ..............................................................................................................117
Compressor Oil.................................................................................................................................. 117
Fans ................................................................................................................................................... 117
Isolation / Protection .........................................................................................................................117
Control Panel ..................................................................................................................................... 117
Power Connections ...........................................................................................................................117
Grounding .......................................................................................................................................... 117
Supply Voltage ................................................................................................................................... 118
PREPARATION – POWER ON .................................................................................................................118
Switch Settings .................................................................................................................................. 118
Compressor Heaters .........................................................................................................................118
Water System ..................................................................................................................................... 118
Flow Switch ........................................................................................................................................ 118
Temperature Sensor(s) .....................................................................................................................118
EQUIPMENT STARTUP CHECKLIST ......................................................................................................119
Checking The System Prior To Initial Start (No Power) ................................................................. 119
Unit Checks .................................................................................................................................... 119
Compressor Heaters(Power On – 24 Hours Prior To Start) ........................................................... 119
Panel Checks(Power On – Both Unit Switch Off) ......................................................................... 119
SETPOINTS ENTRY LIST .........................................................................................................................120
CHECKING SUPERHEAT AND SUBCOOLING .......................................................................................121
LEAK CHECKING .....................................................................................................................................121
UNIT OPERATING SEQUENCE ...............................................................................................................122

SECTION 7 – UNIT CONTROLS .....................................................................................................................123


INTRODUCTION .......................................................................................................................................123
IPU II and I/O Boards .........................................................................................................................123
Unit Switch .........................................................................................................................................124
Display ................................................................................................................................................124
Keypad................................................................................................................................................124
Battery Back-up .................................................................................................................................124
Transformer .......................................................................................................................................124
Single System Select and Programming # of Compressors ........................................................124

6 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

TABLE OF CONTENTS (CONT’D)


“STATUS” KEY .........................................................................................................................................125
Unit Status..........................................................................................................................................125
General Status Messages .................................................................................................................125
Fault Safety Status Messages ..........................................................................................................127
Unit Warning ......................................................................................................................................129
Status Key Messages ........................................................................................................................130
Status Key Messages Quick Reference List ...................................................................................130
DISPLAY/PRINT KEYS .............................................................................................................................131
Oper Data Key ....................................................................................................................................131
Oper Data Quick Reference List.......................................................................................................134
Print Key .............................................................................................................................................135
Operating Data Printout ....................................................................................................................135
History Printout .................................................................................................................................136
History Displays ................................................................................................................................136
Software Version ...............................................................................................................................138
“ENTRY” KEYS.........................................................................................................................................139
Up and Down Arrow Keys .................................................................................................................139
Enter/adv Key.....................................................................................................................................139
“SETPOINTS” KEYS ................................................................................................................................140
Cooling Setpoints ..............................................................................................................................140
Leaving Chilled Liquid Control ........................................................................................................140
Return Chilled Liquid Control ..........................................................................................................141
Remote Setpoint Control ..................................................................................................................141
SCHEDULE/ADVANCE DAY KEY ............................................................................................................141
PROGRAM KEY ........................................................................................................................................143
System Trip Volts ...............................................................................................................................144
Unit Trip Volts ....................................................................................................................................145
PROGRAM KEY LIMITS AND DEFAULT .................................................................................................145
SETPOINTS QUICK REFERENCE LIST ..................................................................................................146
“UNIT” KEYS ...........................................................................................................................................147
Options Key .......................................................................................................................................147
CLOCK ......................................................................................................................................................151
UNIT KEYS OPTIONS PROGRAMMING QUICK REFERENCE LIST .....................................................152

SECTION 8 – UNIT OPERATION ....................................................................................................................153


CAPACITY CONTROL ..............................................................................................................................153
SUCTION PRESSURE LIMIT CONTROLS ..............................................................................................153
DISCHARGE PRESSURE LIMIT CONTROLS .........................................................................................153
LEAVING CHILLED LIQUID CONTROL ...................................................................................................153
LEAVING CHILLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING .....................154
LEAVING CHILLED LIQUID CONTROLOVERRIDE TO REDUCE CYCLING.........................................154
RETURN CHILLED LIQUID CONTROL....................................................................................................155
RETURN CHILLLED LIQUID SYSTEM LEAD/LAG AND COMPRESSOR SEQUENCING ....................156
ANTI-RECYCLE TIMER ............................................................................................................................157

JOHNSON CONTROLS 7
FORM 150.67-NM1 (308)

TABLE OF CONTENTS (CONT’D)


ANTI-COINCIDENCE TIMER ....................................................................................................................157
EVAPORATOR PUMP CONTROL & YORK HYDRO KIT PUMP CONTROL ..........................................157
EVAPORATOR HEATER CONTROL ........................................................................................................157
PUMPDOWN CONTROL ..........................................................................................................................157
STANDARD CONDENSER FAN CONTROL ............................................................................................157
General ...............................................................................................................................................161
Potentiometer Configuration ............................................................................................................161
YCAL 0019-00022 LOW AMBIENT FAN CONTROL OPTION .................................................................161
Wiring .................................................................................................................................................162
PROGRAMMING YCAL 0012-0022 ..........................................................................................................163
YCAL 0033 LOW AMBIENT FAN CONTROL OPTION ............................................................................164
General ...............................................................................................................................................164
CONFIGURATION (JUMPERS AND POTENTIOMETERS) .....................................................................165
Wiring .................................................................................................................................................165
YCAL0033 PROGRAMMING ....................................................................................................................165
YCAL0043 – 0066 LOW AMBIENT FAN CONTROL OPTION .................................................................167
General ...............................................................................................................................................167
CONFIGURATION (JUMPERS AND POTENTIOMETERS) .....................................................................168
Wiring .................................................................................................................................................169
PROGRAMMING ......................................................................................................................................169
LOAD LIMITING ........................................................................................................................................171
COMPRESSOR RUN STATUS .................................................................................................................171
ALARM STATUS .......................................................................................................................................171
BAS/EMS TEMPERATURE RESET USINGA VOLTAGE OR CURRENT SIGNAL .................................172

SECTION 9 – SERVICE AND TROUBLESHOOTING.....................................................................................173


CLEARING HISTORY BUFFERS .............................................................................................................173
SERVICE MODE .......................................................................................................................................173
SERVICE MODE – OUTPUTS ..................................................................................................................173
SERVICE MODE – CHILLER CONFIGURATION .....................................................................................174
SERVICE MODE – ANALOG & DIGITAL INPUTS ...................................................................................174
CONTROL INPUTS/OUTPUTS .................................................................................................................175
MICROBOARD LAYOUT ..........................................................................................................................176
CHECKING INPUTS AND OUTPUTS .......................................................................................................177
Digital Inputs ......................................................................................................................................177
Analog Inputs – Temperature ...........................................................................................................177
Outside Air Sensor ............................................................................................................................177
Liquid & Refrigerant Sensor Test Points ........................................................................................178
Analog Inputs – Pressure .................................................................................................................179
Digital Outputs ...................................................................................................................................180

8 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

TABLE OF CONTENTS (CONT’D)


OPTIONAL PRINTER INSTALLATION .....................................................................................................181
Parts....................................................................................................................................................181
The following parts are required:.....................................................................................................181
Assembly and Wiring ........................................................................................................................181
Obtaining a Printout ..........................................................................................................................181
TROUBLESHOOTING ..............................................................................................................................182

SECTION 10 – MAINTENANCE ......................................................................................................................185


IMPORTANT ..............................................................................................................................................185
COMPRESSORS .......................................................................................................................................185
Oil Level check ..................................................................................................................................185
Oil Analysis ........................................................................................................................................185
CONDENSER FAN MOTORS ...................................................................................................................185
CONDENSER COILS ................................................................................................................................185
OPERATING PARAMETERS ....................................................................................................................185
ON-BOARD BATTERY BACK-UP ............................................................................................................185
PLATE AND FRAME HEAT EXCHANGER (EVAPORATOR) HEATER ...................................................185
OVERALL UNIT INSPECTION .................................................................................................................185
ISN CONTROL ..........................................................................................................................................186
Received Data (Control Data) ...........................................................................................................186
Transmitted Data ...............................................................................................................................186
ISN Operational and Fault Codes.....................................................................................................188
BACNET AND MODBUS DATA COMMUNICTION ..................................................................................189
Serial Communication Analog Value Data ......................................................................................192
Serial Communication Binary Value Data .......................................................................................192
Serial Communication Analog Input Data .......................................................................................192
Serial Communication Binary Input Data ........................................................................................194
TEMPERATURE CONVERSION CHART .................................................................................................195
R410-APRESSURE TEMPERATURE CHART .........................................................................................196

JOHNSON CONTROLS 9
General Chiller Introduction & Safety
FORM 150.67-NM1 (308)

SECTION 1 – GENERAL CHILLER INFORMATION & SAFETY


INTRODUCTION For warranty purposes, the following conditions must
YORK YCAL0019-0066 (15-65 ton, 53-218??) be satisfied:
chillers are manufactured to the highest design and
construction standards to ensure high performance, • The initial start of the unit must be carried out
reliability and adaptability to all types of air by trained personnel from an Authorized YORK
conditioning installations. Service Center (see Commissioning Page 117).

The unit is intended for cooling water or glycol • Only genuine YORK approved spare parts, oils,
solutions and is not suitable for purposes other than coolants, and refrigerants must be used.
those specified in this manual.
• All the scheduled maintenance operations detailed
This manual contains all the information required for in this manual must be performed at the specified
correct installation and commissioning of the unit, times by suitably trained and qualified personnel
together with operating and maintenance instructions. (see Maintenance Section, Page 185).
The manuals should be read thoroughly before
attempting to operate or service the unit. • Failure to satisfy any of these conditions will
automatically void the warranty (see Warranty
All procedures detailed in the manuals, including Policy).
installation, commissioning and maintenance tasks
must only be performed by suitably trained and SAFETY
qualified personnel. Standards for Safety
YCAL chillers are designed and built within an ISO
The manufacturer will not be liable for any 9002 accredited design and manufacturing organization.
injury or damage caused by incorrect installation, The chillers comply with the applicable sections of the
commissioning, operation or maintenance resulting following Standards and Codes:
from a failure to follow the procedures and
instructions detailed in the manuals. • ANSI/ASHRAE Standard 15- Safety Code for
Mechanical Refrigeration.
WARRANTY
YORK warrants all equipment and materials against • ANSI/NFPA Standard 70- National Electrical
defects in workmanship and materials for a period of Code (N.E.C.).
eighteen months from date of shipment, unless labor • ASME Boiler and Pressure Vessel Code- Section
or extended warranty has been purchased as part of VIII Division 1.
the contract.
• ARI Standard 550/590-98- Water Chilling
The warranty is limited to parts only replacement and Packages Using the Vapor Compression Cycle.
shipping of any faulty part, or sub-assembly, which • ASHRAE 90.1- Energy Efficiency compliance.
has failed due to poor quality or manufacturing errors.
All claims must be supported by evidence that the • ARI 370- Sound Rating of Large Outdoor
failure has occurred within the warranty period, and Refrigeration and Air Conditioning Equipment.
that the unit has been operated within the designed • Conform to Intertek Testing Services, formerly
parameters specified. ETL, for construction of chillers and provide
ETL/cETL listing label.
All warranty claims must specify the unit model,
serial number, order number and run hours/starts. • Manufactured in facility registered to ISO 9002.
Model and serial number information is printed on the
• OSHA – Occupational Safety and Health Act.
unit identification plate.
In addition, the chillers conform to Underwriters
The unit warranty will be void if any modification to
Laboratories (U.L.) for construction of chillers and
the unit is carried out without prior written approval
provide U.L./cU.L. Listing Label.
from YORK.

10 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

Responsibility for Safety The contents of this manual include suggested best
Every care has been taken in the design and working practices and procedures. These are issued
manufacture of the unit to ensure compliance with for guidance only, and they do not take precedence
the safety requirements listed above. However, the over the above stated individual responsibility and/or 1
individual operating or working on any machinery is local safety regulations.
primarily responsible for:
This manual and any other document supplied with
• Personal safety, safety of other personnel, and the unit are the property of YORK which reserves
the machinery. all rights. They may not be reproduced, in whole or
in part, without prior written authorization from an
• Correct utilization of the machinery in authorized YORK representative.
accordance with the procedures detailed in the
manuals. MISUSE OF EQUIPMENT
Suitability for Application
ABOUT THIS MANUAL The unit is intended for cooling water or glycol
The following terms are used in this document to alert solutions and is not suitable for purposes other than
the reader to areas of potential hazard. those specified in these instructions. Any use of the
equipment other than its intended use, or operation
of the equipment contrary to the relevant procedures
may result in injury to the operator, or damage to the
equipment.

The unit must not be operated outside the design


parameters specified in this manual.
A WARNING is given in this document to identify a
hazard, which could lead to personal injury. Usually Structural Support
an instruction will be given, together with a brief
Structural support of the unit must be provided as
explanation and the possible result of ignoring the
indicated in these instructions. Failure to provide
instruction.
proper support may result in injury to the operator, or
damage to the equipment and/or building.

Mechanical Strength
The unit is not designed to withstand loads or stresses
from adjacent equipment, pipework or structures.
Additional components must not be mounted on the
A CAUTION identifies a hazard which could lead to unit. Any such extraneous loads may cause structural
damage to the machine, damage to other equipment failure and may result in injury to the operator, or
and/or environmental pollution. Usually an instruction damage to the equipment.
will be given, together with a brief explanation and
the possible result of ignoring the instruction. General Access
There are a number of areas and features, which
may be a hazard and potentially cause injury when
working on the unit unless suitable safety precautions
are taken. It is important to ensure access to the unit
is restricted to suitably qualified persons who are
familiar with the potential hazards and precautions
necessary for safe operation and maintenance of
equipment containing high temperatures, pressures
A NOTE is used to highlight additional information, and voltages.
which may be helpful to you but where there are no
special safety implications.

JOHNSON CONTROLS 11
General Chiller Introduction & Safety
FORM 150.67-NM1 (308)

Pressure Systems High Temperature and Pressure Cleaning


The unit contains refrigerant vapor and liquid under High temperature and pressure cleaning methods
pressure, release of which can be a danger and cause (e.g. steam cleaning) should not be used on any part
injury. The user should ensure that care is taken of the pressure system as this may cause operation of
during installation, operation and maintenance to the pressure relief device(s). Detergents and solvents,
avoid damage to the pressure system. No attempt which may cause corrosion, should also be avoided.
should be made to gain access to the component parts
of the pressure system other than by suitably trained Emergency Shutdown
and qualified personnel. In case of emergency, the control panel is fitted
with a Unit Switch to stop the unit in an emergency.
Electrical
When operated, it removes the low voltage 120
The unit must be grounded. No installation or VAC electrical supply from the inverter system, thus
maintenance work should be attempted on the shutting down the unit.
electrical equipment without first switching power
OFF, isolating and locking-off the power supply.
Servicing and maintenance on live equipment must
only be performed by suitably trained and qualified
personnel. No attempt should be made to gain access
to the control panel or electrical enclosures during
normal operation of the unit.

Rotating Parts
Fan guards must be fitted at all times and not
removed unless the power supply has been isolated. If
ductwork is to be fitted, requiring the wire fan guards
to be removed, alternative safety measures must be
taken to protect against the risk of injury from rotating
fans.

Sharp Edges
The fins on the air-cooled condenser coils have sharp
metal edges. Reasonable care should be taken when
working in contact with the coils to avoid the risk of
minor abrasions and lacerations. The use of gloves is
recommended.

Frame rails, brakes, and other components may also


have sharp edges. Reasonable care should be taken
when working in contact with any components to
avoid risk of minor abrasions and lacerations.

Refrigerants and Oils


Refrigerants and oils used in the unit are generally
nontoxic, non-flammable and non-corrosive, and pose
no special safety hazards. Use of gloves and safety
glasses is, however, recommended when working on
the unit. The build up of refrigerant vapor, from a
leak for example, does pose a risk of asphyxiation in
confined or enclosed spaces and attention should be
given to good ventilation.

12 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

SECTION 2 – PRODUCT DESCRIPTION

LD10950

DUAL CIRCUIT

INTRODUCTION
YORK Millennium® Air-Cooled Scroll Chillers provide All exposed power wiring is routed through liquid-
chilled water for all air conditioning applications using tight, non-metallic conduit.
central station air handling or terminal units. They are
completely self-contained and are designed for outdoor GENERAL SYSTEM DESCRIPTION
(roof or ground level) installation. Each complete Compressors
packaged unit includes hermetic scroll compressors, a
The chiller has suction-gas cooled, hermetic, scroll
liquid cooler, air cooled condenser, a charge of refrigerant
compressors. The YCAL compressors incorporate
R-410A and a weather resistant microprocessor control
a compliant scroll design in both the axial and
center, all mounted on a pressed steel base.
radial direction. All rotating parts are statically and
dynamically balanced. A large internal volume and oil
The units are completely assembled with all
reservoir provides greater liquid tolerance. Compressor
interconnecting refrigerant piping and internal wiring,
crankcase heaters are also included for extra protection
ready for field installation.
against liquid migration.
Prior to delivery, the packaged unit is pressure-tested, Evaporator (Heat Exchanger)
evacuated, and fully charged with Refrigerant-R410A
and oil. After assembly, a complete operational test is The Brazed Plate Heat Exchanger is equipped with a
performed with water flowing through the cooler to heater controlled by the microprocessor. The heater
assure that the refrigeration circuit operates correctly. provides freeze protection for the cooler down to -
20 °F (-29 °C) ambient. The cooler is covered with
The unit structure is heavy-gauge, galvanized steel. This 3/4” (19mm) flexible, closed-cell, foam insulation
galvanized steel is coated with baked-on powder paint, (K~0.25).
which, when subjected to ASTM B117 1000 hour, salt
spray testing, yields a minimum ASTM 1654 rating of Brazed plate heat exchangers shall be UL (Underwriters
“6”. Corrosion resistant wire mesh panels are added to Laboratories) listed. Installing contractor must include
protect the condenser coil from incidental damage and accommodations in the chilled water piping to allow
restrict unauthorized access to internal components. proper drainage and venting of the heat exchanger. Water
Units are designed in accordance with NFPA 70 inlet and outlet connections are grooved for compatibility
(National Electric Code), ASHRAE/ANSI 15 Safety with factory supplied victaulic connections.
code for mechanical refrigeration, ASME, Listed and
labeled with Intertek Testing Services (ETL) and rated
in accordance with ARI Standard 550/590-2003.
JOHNSON CONTROLS 13
Product Description
FORM 150.67-NM1 (308)

The heat exchanger is a brazed plate stainless steel DISPLAY/PRINT of typical information:
construction, single or dual circuit heat exchanger • Chilled liquid temperatures
capable of refrigerant working pressure of 650 PSIG • Ambient temperature
(3103 kPa) and liquid side pressure of 150 PSIG (1034 • System pressures (each circuit)
kPa) (Option for 300 PSIG [2068 kPa] available). Each • Operating hours and starts (each compressor)
heat exchanger is covered in 3/4” (19mm) flexible, • Print calls up to the liquid crystal display
closed cell insulation, thermal conductivity of 0.26k • Operating data for the systems
(BTU/HR-FT2 – °F] /in) maximum. • History of fault shutdown data for up to
the last six fault shutdown conditions.
A strainer with a mesh size between .5 and 1.5 mm (40 • An RS-232 port, in conjunction with this
mesh) is recommended upstream of the heat exchanger press-to-print button, is provided to permit
to prevent clogging. the capability of hard copy print-outs via a
separate printer (by others).
Condenser
Coils – Fin and tube condenser coils of seamless, ENTRY section to:
internally-enhanced, high-condensing-coefficient, ENTER setpoints or modify system values.
corrosion resistant copper tubes are arranged in
staggered rows, mechanically expanded into aluminum
SETPOINTS updating can be performed to:
fins. Integral subcooling is included. The design working
• Chilled liquid temperature setpoint and range
pressure of the coil is 650 PSIG (45 bar).
• Remote reset temperature range
• Set daily schedule/holiday for start/stop
Low Sound Fans – The condenser fans are composed
• Manual override for servicing
of corrosion resistant aluminum hub and glass-fiber
• Low and high ambient cutouts
reinforced composite blades molded into a low noise
• Number of compressors
airfoil section. They are designed for maximum
• Low liquid temperature cutout
efficiency and are statically and dynamically balanced
• Low suction pressure cutout
for vibration free operation. They are directly driven
• High discharge pressure cutout
by independent motors, and positioned for vertical air
• Anti-recycle timer (compressor start cycle
discharge. All blades are statically and dynamically
time)
balanced for vibration-free operation. The fan guards
• Anti-coincident timer (delay compressor
are constructed of heavy-gauge, rust-resistant, PVC
starts)
coated steel wire.
UNIT section to:
Motors – The fan motors are Totally Enclosed Air-
• Set time
Over (TEAO), direct drive, 6 pole, current protected.
• Set unit options
They feature ball bearings that are double-sealed and
permanently lubricated.
UNIT ON/OFF switch
MILLENIUM CONTROL CENTER
All controls are contained in a NEMA 3R/12 (and The microprocessor control center is capable of
equivalent to IP55*) cabinet with hinged outer door displaying the following:
and includes:
• Return and leaving liquid temperature
Liquid Crystal Display with Light Emitting Diode back-
lighting for outdoor viewing: • Low leaving liquid temperature cutout set-
• Two display lines ting
• Twenty characters per line • Low ambient temperature cutout setting
• Outdoor air temperature
Color coded 12-button non-tactile keypad with sections
for: • English or Metric data

14 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

• Suction pressure cutout setting POWER PANEL


• Each system suction pressure Each panel contains:
• Discharge pressure (optional) • Compressor power terminals
• Liquid Temperature Reset via a YORK ISN • Compressor motor starting contactors per
DDC or Building Automation System (by oth- l.E.C.**
ers) via: • Control power terminals to accept incoming
2
- a pulse width modulated (PWM) input as for
standard. 115-1-60 control power
- a 4-20 milliamp or 0 -10 VDC input with the • Fan contactors & overload current protec-
optional B.A.S. interface option. tion
• Anti-recycle timer status for each system
• Anti-coincident system start timer condition The power wiring is routed through liquid-tight
conduit to the compressors and fans.
• Compressor run status
• No cooling load condition
• Day, date and time
• Daily start/stop times
• Holiday status
• Automatic or manual system lead/lag con-
trol
• Lead system definition
• Compressor starts & operating hours
(each compressor)
• Status of hot gas valves, evaporator heater
and fan operation
• Run permissive status
• Number of compressors running
• Liquid solenoid valve status
• Load & unload timer status
• Water pump status

Provisions are included for: pumpdown at shutdown;


optional remote chilled water temperature reset and
two steps of demand load limiting from an external
building automation system. Unit alarm contacts are
standard.

The operating program is stored in non-volatile


memory (EPROM) to eliminate chiller failure due to
AC powered failure/battery discharge. Programmed
setpoints are retained in lithium battery-backed RTC
memory for 5 years minimum.

* Intensity of Protection European Standard


** International Electrotechnical Commission

JOHNSON CONTROLS 15
Product Description
FORM 150.67-NM1 (308)

ACCESSORIES AND OPTIONS


POWER OPTIONS
COMPRESSOR POWER CONNECTION – Single- AMBIENT KIT (HIGH) – Required if units are to
point (YCAL0019-0066) terminal block connection is operate when the ambient temperature is above 110 °F
provided as standard. The following power connections (43 °C). Includes discharge pressure transducers. (This
are available as options. (See electrical data for specific option includes the Discharge Pressure Transducer /
voltage and options availability) (Factory-Mounted). Readout Capability option) (Field-Mounted).

SINGLE-POINT SUPPLY TERMINAL BLOCK BUILDING AUTOMATION SYSTEM INTER-


– (standard on YCAL0019 – 0066 models) Includes FACE – The factory addition of a Printed Circuit Board
enclosure, terminal-block and interconnecting wiring to to accept a 4-20 milliamp, 0-10VDC or contact closure
the compressors. Separate external protection must be input to reset the leaving chiller liquid temperature from
supplied, by others, in the incoming compressor-power a Building Automation System. (Only one of following
wiring. (Do not include this option if either the Single- options can be offered on a unit at a time: BAS, Remote
Point Non-fused Disconnect Switch or Single-Point Control Panel or Multi-unit Sequence Control) (Fac-
Circuit Breaker options have been included). tory-Mounted). (The standard unit capabilities include
remote startstop, remote water temperature reset via a
SINGLE-POINT NON-FUSED DISCONNECT PWM input signal or up to two steps of demand (load)
SWITCH – Unit-mounted disconnect switch with limiting depending on model). (The standard control
external, lockable handle (in compliance with Article panel can be directly connected to a YORK Building
440-14 of N.E.C.), can be supplied to isolate the unit Automated System via the standard onboard RS485
power voltage for servicing. Separate external fusing communication port).
must be supplied, by others in the power wiring, which
must comply with the National Electrical Code and/or LANGUAGE LCD AND KEYPAD DISPLAY – Span-
local codes. ish, French, and German unit LCD controls and keypad
displays are available. Standard language is English.
SINGLE-POINT CIRCUIT BREAKER – A unit
mounted circuit breaker with external, lockable handle DISCHARGE PRESSURE TRANSDUCERS AND
(in compliance with N.E.C. Article 440-14), can be READOUT CAPABILITY – The addition of pressure
supplied to isolate the power voltage for servicing (this transducers allows models to sense and display discharge
option includes the Single-Point Power connection). pressure. This is recommended for brine chilling appli-
cations. (This option is included with either the low or
CONTROL TRANSFORMER – Converts unit power high ambient kits) (Factory-Mounted).
voltage to 115-1-60 (0.5 or 1.0 KVA capacity). Fac-
tory mounting includes primary and secondary wiring • Suction Pressure Transducers: Permits unit to
between the transformer and the control panel (Fac- sense and display suction pressure. This capability
tory-Mounted). is standard on YCAL0019-0066 models.

POWER FACTOR CORRECTION CAPACITORS MOTOR CURRENT MODULE – Capable of moni-


– Will correct unit compressor power factors to a 0.90- toring compressor motor current. Provides extra protec-
0.95 (Factory-Mounted). tion against compressor reverse rotation, phase-loss and
phase imbalance. Option consists of one module per
CONTROL OPTIONS electrical system (Factory-Mounted).
AMBIENT KIT (LOW) – Units will operate to 25 °F (- MULTI-UNIT SEQUENCING – A separate Sequenc-
4 °C). This accessory includes all necessary components ing Control Center can be provided to handle sequencing
to permit chiller operation to 0 °F (-18 °C). (This option control of up to eight chillers in parallel based on mixed
includes the Discharge Pressure Transducer / Readout liquid temperature (interconnecting wiring by others).
Capability option). For proper head pressure control (Only one of following options can be offered on a unit
in applications below 25 °F (-4 °C), where wind gusts at a time: BAS, Remote ControSl Panel or Multi-unit
may exceed five mph, it is recommended that Optional Sequence Control) (Factory-Mounted).
Condenser Louvered Enclosure Panels also be included
(Factory-Mounted).

16 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

COMPRESSOR, PIPING, EVAPORATOR REMOTE DX COOLER – Not available at this


OPTIONS time.
LOW TEMPERATURE BRINE – Required for brine
CONDENSER AND CABINET OPTIONS
chilling below 30 °F (-1 °C) leaving brine temperature
for YCAL0019 – 0066 models. Option includes resized Condenser coil protection against corrosive environ-
thermal expansion valve (Factory-Mounted). ments is available by choosing any of the following 2
options. For additional application recommendations,
CHICAGO CODE RELIEF VALVES – Unit will refer to FORM 150.12-ES1 (Factory-Mounted).
be provided with relief valves to meet Chicago code
requirements (Factory-Mounted). PRE-COATED FIN CONDENSER COILS – The
unit's coils are constructed with black epoxy coated
SERVICE ISOLATION VALVE – Service suction aluminum fins. This can provide corrosion resistance
and discharge (ball type) isolation valves are added to comparable to copper-fin coils in typical seashore loca-
unit per system. This option also includes a system high tions. Either these or the post-coated coils (below), are
pressure relief valve in compliance with ASHRAE 15 recommended for units being installed at the seashore
(Factory-Mounted). or where salt spray may hit the unit.

HOT GAS BY-PASS – Permits continuous, stable POST-COATED DIPPED CONDENSER COILS
operation at capacities below the minimum step of com- – The unit's coils are constructed with dipped-cured
pressor unloading to as low as 5% capacity (depending condenser coils. This is another choice for seashore
on both the unit and operating conditions) by introduc- and other corrosive applications (with the exception of
ing an artificial load on the cooler. Hot gas by-pass is strong alkalies, oxidizers and wet bromine, chlorine and
installed on only refrigerant system #1 on two-circuited fluorine in concentrations greater than 100 ppm).
units (Factory-Mounted).
COPPER FIN CONDENSER COILS – The unit's
Heat Exchanger 300 PSIG (21 bar) DWP WATER- coils are constructed with copper fins. (This is not
SIDE – The waterside will be of 300 PSIG (21 bar) recommended for units in areas where they may be
instead of the standard 150 PSIG DWP. 300 PSIG R.F. exposed to acid rain).
flanges are included on the Heat Exchanger nozzles
(Factory-Mounted). The companion flanges will be ENCLOSURE PANELS (UNIT) – Tamperproof
field-supplied by others. Enclosure Panels prevent unauthorized access to units.
Enclosure Panels can provide an aesthetically pleas-
FLANGES (VICTAULIC TYPE) – Consists of two ing alternative to expensive fencing. Additionally, for
(2) Flange adapters for grooved end pipe (standard 150 proper head pressure control, YORK recommends the
psi [10.5 bar] cooler). use of :
FLOW SWITCH – The flow switch or its equivalent LOUVERED PANELS (Full Unit) – Louvered panels
must be furnished with each unit. surround the front, back, and sides of the unit. They
prevent unauthorized access and visually screen unit
150 PSIG (10.5 bar) DWP – For standard units. Johnson components. Unrestricted air flow is permitted through
Controls model F61MG-1C Vapor-proof SPDT, NEMA generously sized louvered openings. This option is ap-
4X switch (150 PSIG [10.5 bar] DWP), -20 °F to 250 °F plicable for any outdoor design ambient temperature up
(-29 °C to 121 °C), with 1” NPT connection for upright to 115 °F (46 °C) (Factory-Mounted).
mounting in horizontal pipe (Field-Mounted).
SOUND REDUCTION OPTIONS
300 PSIG (21 bar) DWP – For units with optional 300
PSIG (21 bar) DX cooler. McDonnell & Miller model SOUND ATTENUATION – One or both of the fol-
FS74W Vapor-proof SPDT, NEMA 4X switch (300 lowing sound attenuation options are recommended for
PSIG (21 bar) DWP), -20 °F to 300 °F (-29 °C to 149 residential or other similar sound-sensitive locations.
°C), with 1¼ inch MPT connection for upright mounting Louvered Panels can be ordered for winter applications
in horizontal pipe (Field-Mounted). where wind gusts may exceed five miles per hour. The
following types of enclosure options are available:
DIFFERENTIAL PRESSURE SWITCH – Alterna-
tive to an above mentioned flow switch. Pretempco
model DPS300AP40PF-82582-5 (300 psi max. working
pressure), SPDT 5 amp 125/250VAC switch, Range 0
– 40 PSID, deadband 0.5 – 0.8 psi, with 1/4” NPTE
Pressure Connections.

JOHNSON CONTROLS 17
Product Description
FORM 150.67-NM1 (308)

COMPRESSOR ACOUSTIC SOUND BLANKET


– Each compressor is individually enclosed by an acous-
tic sound blanket. The sound blankets are made with
one layer of acoustical absorbent textile fiber of 5/8”
(15mm) thickness; one layer of anti-vibrating heavy
material thickness of 1/8” (3mm). Both are closed by
two sheets of welded PVC, reinforced for temperature
and UV resistance (Factory-Mounted).

ULTRA QUIET FANS – Lower RPM, 8-pole fan


motors are used with steeper-pitch fans (Factory-
Mounted).

VIBRATION ISOLATORS – Level adjusting, spring


type 1” (25.4mm) or seismic deflection or neoprene
pad isolators for mounting under unit base rails (Field-
Mounted).

18 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

UNIT COMPONENTS YCAL 0019 – 0033

2
FAN ASSEMBLIES

CONTROL / POWER PAN

CONDENSER
COILS

HEAT EXCHANGER

COMPRESSORS

FIG. 1 – UNIT COMPONENTS SINGLE SYSTEM UNITS

JOHNSON CONTROLS 19
Product Description
FORM 150.67-NM1 (308)

CONTROL / POWER PANEL COMPONENTS YCAL0019 – 0033

CIRCUIT BREAKER KEYPAD & DISPLAY UNIT SWITCH

COMPRESSOR CONTACTORS USER TERMINAL BLOCK


LD11463

FIG. 2 – CONTROL/POWER PANEL COMPONENTS SINGLE SYSTEM UNITS

20 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

UNIT COMPONENTS YCAL0043 – 0066

FAN ASSEMBLIES

CONDENSER COILS

HEAT EXCHANGER

LD12477

COMPRESSORS CONTROL / POWER PANEL

FIG. 3 – UNIT COMPONENTS DUAL SYSTEM UNITS

JOHNSON CONTROLS 21
Product Description
FORM 150.67-NM1 (308)

CONTROL / POWER PANEL COMPONENTS YCAL0043 – 0066

TERMINAL BLOCK FAN FUSES CR1 / CR2

COMPRESSOR CONTACTS TB1 CTB1

LD11458a
FIG. 4 – CONTROL/POWER PANEL COMPONENTS DUAL SYSTEM UNITS

22 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

PRODUCT IDENTIFICATION NUMBER (PIN)

BASIC UNIT NOMENCLATURE


2

YCAL0043EE 46XEA
1 2 3 4 5 6 7 8 9 10 11 12 17 14 15
BASE PRODUCT TYPE NOMINAL CAPACITY UNIT DESIGNATOR REFRIGERANT VOLTAGE/STARTER DESIGN/DEVELOPMENT LEVEL

Y : YORK 0 # # # E : High Efficiency E : R-410A 1 7 : 200 / 3/ 60 E : Design Series A


C : Chiller 1 # # # 2 8 : 230 / 3 / 60 A : Engineering
A : Air-Cooled Even Number: 4 0 : 380 / 3 / 60 Change
U : Condensing 60 HZ Nominal Tons 4 6 : 460 / 3 / 60 or PIN Level
Unit Odd Number: 5 8 : 575 / 3 / 60
L : Scroll 50 HZ Nominal kW
X : Across the Line

FEATURE DESCRIPTION OPTION DESCRIPTION


MODEL Model (PIN 1-4) YCAL YCAL
0019 0019
0022 0022
0033 0033
CAP Capacity (PIN 5-8)
0043 0043
0046 0046
0066 0066
UNIT Unit Designator (PIN 9) E High Efficiency
REF Refrigerant (PIN 10) C R-22
17 200/3/60
28 230/3/60
VOLTS Voltage (PIN 11 & 12)
40 380/3/60
46 460/3/60
58 575/3/60
STARTER Starter (PIN 13) X Across The Line Starter
DESIGN Design Series (PIN 14) E Design Series E
DEV Development Level (PIN 15) A Development Level A

JOHNSON CONTROLS 23
Product Description
FORM 150.67-NM1 (308)

PRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)


FEATURE DESCRIPTION OPTION DESCRIPTION
SX Single Point Terminal Block
POWER Power Field (PIN 16 & 17) SD Single Point Non-Fused Disconnect
BX Single Point Circuit Breaker
QQ Special Power Option Required
X No Control Transformer Required
TRANS Cntrl Transformer (PIN 18) T Control Transformer Required
Q Special Control Transformer Required
X No Power Capacitor Required
PFC Power Factor Capacitor (PIN 19) C Power Capacitor Required
Q Special Power Capacitor Required
X No Ambient Kits Required
L Low Ambient Kits Required
AMB Ambient Kits (PIN 20)
H High Ambient Kits Required
A High/Low Ambient Kits Required
Q Special Ambient Kits Required
X No BAS Reset/Offset Required
BAS BAS Reset/Offset (PIN 21) M ISN Microgateway Required
T BAS Reset/Offset Required
Q Special BAS Reset/Offset Required
X English
S Spanish
LCD Language (PIN 22)
F French
G German
Q Special Language Required
X No Readout Kit Required
RDOUT Readout Kits (PIN 23) R Discharge Readout Kit Required
Q Special Pressure Readout Required
SAFETY Safety Codes (PIN 24) L N American Safety Code (Cul/Cet)
X No Option Required
SENSOR (PIN 25)
Q Special Quote
X No Motor Current
PUMP (PIN 26) C Motor Current Readout
Q Special Quote
X No Remote Panel Required
REMOTE Remote Panel (PIN 27) O OptiView Remote Panel Required
Q Special Remote Panel Required
X No Sequence Kit Required
SEQ Sequence Kit (PIN 28) S Sequence Kit Required= {SEQ/S}
Q Special Sequence Required
NUM Leaving Water Temp=
TEMP Leaving Water Temp {TEMP/NUM} Degrees
(PIN 29, 30) QQ Special LWT Requirements
24 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

PRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)

FEATURE DESCRIPTION OPTION DESCRIPTION


X No Chicago Code Kit Required
C Chicago Code Kit Required 2
CHICAGO Chicago Code Kit (PIN 31)
S Service Isolation Valves
B Both Chicago Code & Serv Isolation
Q Special Chicago Code Kit Required
X Standard Valves Required
VALVES Valves (PIN 32)
Q Special Optional Valves Required
X No Hot Gas Bypass Required
HGBP Hot Gas Bypass (PIN 33) 1 Hot Gas Bypass Required-1 Circuit
2 Hot Gas Bypass Required-2 Circuit
Q Special Hot Gas Required
X No Option Required
GAUGE (PIN 34)
Q Special Quote
X No Option Required
OVERLOAD (PIN 35)
Q Special Quote
X No Option Required
PIN 36 (PIN 36)
Q Special Quote
X Crankcase Heater Standard
HTR Crankcase Heater (PIN 37)
Q Special Crankcase Heater Required
X 150 PSIG DWP Waterside
DWP DWP (PIN 38) 3 300 PSIG DWP Waterside
Q Special DWP
X Standard Insulation
INS Insulation (PIN 39) D Double Thick Insulation
Q Special Insulation Required
X Standard Victaulic
FLANGES Flanges (PIN 40) V Victaulic to Flange Adapter
Q Special Flanges Required
X No Flow Switch Required
S One Flow Switch Required
T Two Flow Switches Required
U Three Flow Switches Required
FLOW Flow Switch (PIN 41) D One Differential Pressure Switch
Required
E Two Differential Pressure Switches
Required
F Three Differential Pressure Switches
Required
Q Special Flow Switch Required

JOHNSON CONTROLS 25
Product Description
FORM 150.67-NM1 (308)

PRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)

FEATURE DESCRIPTION OPTION DESCRIPTION


X UL Pressure Code Vessel
VESSEL Vessel Codes (PIN 42) A ASME Pressure Vessel Code
Q Special Pressure Vessel Code
X Standard Cooler Required
CLR Cooler (PIN 43) R Remote Cooler Required
Q Special Cooler Required
X No Option Required
PIN 44 (PIN 44)
Q Special Quote
X Aluminum Coil
B Pre-Coated Fin Coil
COILS Coils (PIN 45)
C Copper Coil
P Post-Coated Dipped Coil
Q Special Coil
X No Option Required
PIN 46 (PIN 46)
Q Special Quote
X TEAO Fan Motors
FANMOTORS Fan Motors (PIN 47)
Q Special Fan Motors Required
1 Wire Enclosures-Factory
ENCL Enclosure Panel (PIN 48) 7 Louvered Enclosure-Factory
Q Special Enclosures Panels
X No Acoustic Blanket Required
ACOUSTIC Acoustic Blanket (PIN 49) B Acoustic Blanket Required
Q Special Acoustic Blanket Required
X No Option Required
PIN 50 (PIN 50)
Q Special Quote
X No Option Required
PIN 51 (PIN 51)
Q Special Quote
X Standard Low Sound Fans Required
FANS Sound Fans (PIN 52) L Ultra Low Sound Fans Required
Q Special Sound Fans Required
X No Option Required
PAINT (PIN 53)
Q Special Quote
X No Isolators Required
1 1” Deflection Isolators Required
ISOL Vibration Isolators (PIN 54)
N Neoprene Isolators Required
S Seismic Isolators Required
Q Special Isolators Required

26 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

PRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)


FEATURE DESCRIPTION OPTION DESCRIPTION
X 18 months parts only (year 1)

B 18 months labor (year 1) (entire unit)

C 30 months parts (year 1&2) (entire unit)


2
WARRANTY Warranty (PIN 55) D 30 months P&L (year 1&2) (entire unit)

E 48 months Compressor Parts Only (year 1-5)

F 18 months (year 1) – (entire unit), 48 months P&L


(year 2-5) (compressor only)
G 48 months parts (year 2-5) (entire unit)

H 18 months labor (year 1) – (entire unit), 48 months


(P&L) (year 2-5) (entire unit)
I 18 months labor (year 1) – (entire unit), 30 months
parts (year 1&2) (entire unit)
J 18 months labor (year 1) – (entire unit), 48 months
parts (year 2-5) (compressor only)
K 18 months labor (year 1) – (entire unit), 48 months
parts (year 2-5) (entire unit)
L 18 months labor (year 1) – (entire unit), 30 months
parts (year 1&2) (entire unit) 48 month parts (year2-5)
(compressor only)
M 18 months labor (year 1) – (entire unit), 48 months
parts (year 1&2) (entire unit) 48 month P&L (year2-5)
(compressor only)
N 30 months parts (year 1&2) – (entire unit), 48 months
parts (year 2-5) (compressor only)
O 30 months P&L (year 1&2) – (entire unit), 48 months
parts (year 2-5) (compressor only)
P 30 months P&L (year 1&2) – (entire unit), 48 months
P&L (year 2-5) (compressor only)
R 30 months P&L (year 1&2) – (entire unit), 48 months
parts (year 2-5) (entire unit)
Q Special Warranty
X No Refrigerant Warranty Required
REFWTY Refrigerant Warranty (PIN 56) 1 1 Year Refrigerant
2 2 Year Refrigerant
5 5 Year Refrigerant
X No Option Required
A Buy American Act Compliance
Both Buy American Act Compliance and
SHIP Ship Instructions (PIN 57) B Container Shipping Kit
C Container Shipping Kit (Factory Load)
P Container Shipping Kit (Factory Prep)
Q Special Quote
X No Option Required
PIN 58 (PIN 58)
Q Special Quote
X No Option Required
PIN 59 (PIN 59)
Q Special Quote

JOHNSON CONTROLS 27
Product Description
FORM 150.67-NM1 (308)

PRODUCT IDENTIFICATION NUMBER (PIN) (CON’T)


FEATURE DESCRIPTION OPTION DESCRIPTION
X No Option Required
PIN 60 (PIN 60)
Q Special Quote
MFG Plant of Mfg. (PIN 61) R Plant of Manufacture-Monterrey
MEX Mexico
LOC Mfg. Location
SAT San Antonio
YW YorkWorks Version CV YorkWorks ConVersion
UV YorkWorks Version
SQ Special Quote Q Special Quote

REFRIGERANT FLOW DIAGRAM

AIR COOLED CONDENSERS

HOT DISCHARGE
GAS LINE

OPTIONAL
OPTIONAL
DISCHARGE LINE
BALL VALVE

OPTIONAL
SERVICE VALVE

LD11417

FIG. 5 – REFRIGERANT FLOW DIAGRAM

28 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

SECTION 3 – HANDLING AND STORAGE


DELIVERY AND STORAGE MOVING THE CHILLER
To ensure consistent quality and maximum reliability, (YCAL0043 – 0066 DUAL SYSTEM ONLY)
all units are tested and inspected before leaving the Prior to moving the unit, ensure that the installation
factory. Units are shipped completely assembled site is suitable for installing the unit and is easily
and containing refrigerant under pressure. Units are capable of supporting the weight of the unit and all
shipped without export crating unless crating has been associated services.
specified on the Sales Order.
The units are designed to be lifted using cables. A
If the unit is to be put into storage, prior to spreader bar or frame should be used in order to 3
installation, the following precautions should be prevent damage to the unit from the lifting chains.
observed:
Units are provided with lifting eyes in the sides of the
• The chiller must be “blocked” so that the base is base frame, which can be attached to directly using
not permitted to sag or bow. shackles or safety hooks.

• Ensure that all openings, such as water The unit must only be lifted by the base
connections, are securely capped. frame at the points provided. Never
move the unit on rollers, or lift the unit
• Do not store where exposed to ambient air using a forklift truck.
temperatures exceeding 110 °F (43 °C).

• The condensers should be covered to protect Care should be taken to avoid damaging the
the fins from potential damage and corrosion, condenser cooling fins when moving the unit.
particularly where building work is in progress.
Lifting Weights
• The unit should be stored in a location where
there is minimal activity in order to limit the risk For details of weights and weight distribution, refer to
of accidental physical damage. the data shipped in the chiller information packet and
unit nameplate.
• To prevent inadvertent operation of the pressure
relief devices the unit must not be steam cleaned. The unit should be lifted by inserting
hooks through the holes provided in unit
• It is recommended that the unit is periodically base rails. Spreader bars should be used
inspected during storage. to avoid crushing the unit frame rails with
the lifting chains (See below).
INSPECTION
Remove any transit packing and inspect the unit to
ensure that all components have been delivered and
that no damage has occurred during transit. If any
damage is evident, it should be noted on the carrier’s
freight bill and a claim entered in accordance with the
instructions given on the advice note.

Major damage must be reported immediately to your


local YORK representative.

JOHNSON CONTROLS 29
Handling and Storage
FORM 150.67-NM1 (308)

MOVING THE CHILLER


(YCAL0019 – 0033 SINGLE CIRCUIT ONLY)
Prior to moving the unit, ensure that the installation
site is suitable for installing the unit and is easily
capable of supporting the weight of the unit and all
associated services.

The units are designed to be lifted using cables or an


appropriate forklift. Refer to the unit dataplate for unit
weight. When using lifting cables, a spreader bar or
frame should be used in order to prevent damage to
the unit from the lifting chains.

Units are provided with lifting eyes in the sides of the


base frame, which can be attached to directly using
shackles or safety hooks.

The unit must only be lifted by the base


frame at the points provided.

Care should be taken to avoid damaging the


condenser cooling fins when moving the unit.

Lifting Weights

For details of weights and weight distribution, refer to


the data shipped in the chiller information packet and
unit nameplate.

30 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

UNIT RIGGING
Lifting Instructions are placed on a label on the chiller
and on the shipping bag.

Forks must extend beyond the width of the unit for proper lift. The thick-
ness of the fork blade must be smaller then the opening of the lifting
hole. Improper fork positioning could result in damage to the unit.

FIG. 6 – UNIT RIGGING/LIFTING (YCAL0019 – 0033 SINGLE CIRCUIT MODELS ONLY)

JOHNSON CONTROLS 31
Handling and Storage
FORM 150.67-NM1 (308)

FIG. 6A – UNIT RIGGING/LIFTING (YCAL0043- 0066 DUAL CIRCUIT MODELS)

LD10951
Use spreader bars to avoid lifting chains hitting the
chiller.

Never lift the chiller using a forklift or


by hooking to the top rails. Use only
the lifting holes provided.

Lifting Instructions are placed on a label on the chiller


and on the shipping bag.

32 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

SECTION 4 – INSTALLATION
To ensure warranty coverage, this INSPECTION
equipment must be commissioned Immediately upon receiving the unit, it should be
and serviced by an authorized YORK inspected for possible damage which may have
service mechanic or a qualified service occurred during transit. If damage is evident, it should
person experienced in chiller instal- be noted in the carrier’s freight bill. A written request
lation. Installation must comply with for inspection by the carrier’s agent should be made at
all applicable codes, particularly in once. See “Instruction” manual, Form 50.15-NM for
regard to electrical wiring and other more information and details.
safety elements such as relief valves,
LOCATION AND CLEARANCES
HP cutout settings, design working
pressures, and ventilation require- These units are designed for outdoor installations on
ground level, rooftop, or beside a building. Location
ments consistent with the amount and
type of refrigerant charge.
should be selected for minimum sun exposure and to 4
insure adequate supply of fresh air for the condenser.
The units must be installed with sufficient clearances for
Lethal voltages exist within the control air entrance to the condenser coil, for air discharge away
panels. Before servicing, open and tag from the condenser, and for servicing access.
all disconnect switches.
In installations where winter operation is intended and
INSTALLATION CHECKLIST snow accumulations are expected, additional height must
The following items, 1 through 5, must be checked be provided to ensure normal condenser air flow.
before placing the units in operation.
Clearances are listed under “Notes” in the
1. Inspect the unit for shipping damage. “DIMENSIONS” section.
2. Rig unit using spreader bars. Foundation
3. Open the unit only to install water piping system.
Do not remove protective covers from water con- The unit should be mounted on a flat and level
nections until piping is ready for attachment. Check foundation, floor, or rooftop capable of supporting
water piping to ensure cleanliness. the entire operating weight of the equipment. See
PHYSICAL DATA for operating weight. If the unit is
4. Pipe unit using good piping practice (see ASHRAE elevated beyond the normal reach of service personnel,
handbook section 215 and 195). a suitable catwalk must be capable of supporting service
5. Check to see that the unit is installed and operated personnel, their equipment, and the compressors.
within limitations (Refer to LIMITATIONS).

The following pages outline detailed procedures to be


followed to install and start-up the chiller.

HANDLING
These units are shipped as completely assembled units
containing full operating charge, and care should be
taken to avoid damage due to rough handling.

JOHNSON CONTROLS 33
Installation
FORM 150.67-NM1 (308)

Ground Level Locations SPRING ISOLATORS (OPTIONAL)


It is important that the units be installed on a substantial When ordered, four (4) isolators will be furnished.
base that will not settle. A one piece concrete slab
with footers extended below the frost line is highly Identify the isolator, locate at the proper mounting point,
and adjust per instructions.
recommended. Additionally, the slab should not be tied
to the main building foundations as noise and vibration COMPRESSOR MOUNTING
may be transmitted. Mounting holes are provided in the
The compressors are mounted on four (4) rubber
steel channel for bolting the unit to its foundation (see
isolators. The mounting bolts should not be loosened
DIMENSIONS). or adjusted at installation of the chiller.
For ground level installations, precautions should be REMOTE COOLER OPTION
taken to protect the unit from tampering by or injury to Not available at this time.
unauthorized persons. Screws and/or latches on access
panels will prevent casual tampering. However, further CHILLED LIQUID PIPING
safety precautions such as a fenced-in enclosure or
General – When the unit(s) has been located in its
locking devices on the panels may be advisable. final position, the unit water piping may be connected.
Normal installation precautions should be observed in
Rooftop Locations order to receive maximum operating efficiencies. Piping
Choose a spot with adequate structural strength to should be kept free of all foreign matter. All chilled water
safely support the entire weight of the unit and service evaporator piping must comply in all respects with local
plumbing codes and ordinances.
personnel. Care must be taken not to damage the roof.
Since elbows, tees and valves decrease pump capacity,
Consult the building contractor or architect if the roof all piping should be kept as straight and as simple as
is bonded. Roof installations should have wooden possible. All piping must be supported independent
beams (treated to reduce deterioration), cork, rubber, of the chiller.
or vibration isolators under the base to minimize
vibration. Consideration should be given to com-
pressor access when laying out water
Noise Sensitive Locations piping. Routing the water piping too
Efforts should be made to assure that the chiller is not
close to the unit could make compres-
located next to occupied spaces or noise sensitive areas
sor servicing/replacement difficult.
where chiller noise level would be a problem. Chiller
noise is a result of compressor and fan operation. Hand stop valves should be installed in all lines to fa-
Considerations should be made utilizing noise levels cilitate servicing.
published in the YORK Engineering Guide for
the specific chiller model. Sound blankets for the Piping to the inlet and outlet connections of the chiller
compressors and low sound fans are available. should include high-pressure rubber hose or piping
loops to ensure against transmission of water pump
vibration. The necessary components must be obtained
in the field.

34 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

Drain connections should be provided at all low points The Flow Switch MUST NOT be used
to permit complete drainage of the cooler and system to start and stop the chiller (i.e. start-
water piping. ing and stopping the chilled water
A small valve or valves should be installed at the highest pump). It is intended only as a safety
point or points in the chilled water piping to allow any switch.
trapped air to be purged. Vent and drain connections
should be extended beyond the insulation to make them PIPEWORK ARRANGEMENT
accessible. The following are suggested pipework arrangements for
single unit installations, for multiple unit installations,
The piping to and from the cooler must be designed to each unit should be piped as shown.
suit the individual installation. It is important that the
following considerations be observed: Recommendations of the Building Services
Research Association.
1. The chilled liquid piping system should be laid out
so that the circulating pump discharges directly
into the cooler. The suction for this pump should 4
be taken from the piping system return line and not
the cooler. This piping scheme is recommended,
but is not mandatory.

2. The inlet and outlet cooler connection sizes are 3”


(YCAL0043 – 0066).

3. A strainer, preferably 40 mesh, must be installed


in the cooler inlet line just ahead of the cooler. This
is important to protect the cooler from entrance of LD06596
large particles which could cause damage to the
evaporator. ISOLATING VALVE - NORMALLY OPEN

4. All chilled liquid piping should be thoroughly ISOLATING VALVE - NORMALLY CLOSED
flushed to free it from foreign material before
the system is placed into operation. Use care not
to flush any foreign material into or through the
cooler. FLOW REGULATING VALVE
5. As an aid to servicing, thermometers and pressure
gauges should be installed in the inlet and outlet
water lines.
FLOW MEASUREMENT DEVICE
6. The chilled water lines that are exposed to outdoor
ambients should be wrapped with supplemental
heater cable and insulated to protect against freeze-
STRAINER
up during low ambient periods, and to prevent
formation of condensation on lines in warm humid
locations.
PRESSURE TAPPING
7. A chilled water flow switch, (either by YORK or
others) MUST be installed in the leaving water
piping of the cooler. There should be a straight
horizontal run of at least 5 diameters on each side
of the switch. Adjust the flow switch paddle to the FLOW SWITCH
size of the pipe in which it is to be installed (see
manufacturer’s instructions furnished with the FLANGED CONNECTION
switch). The switch is to be wired to terminals 13 LD06597

– 14 of CTB1 located in the control panel, as shown


FIG. 7 – CHILLED LIQUID SYSTEM
on the unit wiring diagram.
JOHNSON CONTROLS 35
Installation
FORM 150.67-NM1 (308)

DUCT WORK CONNECTION Copper power wiring only should be used for supplying
General Requirements power to the chiller. This is recommended to avoid safety
and reliability issues resulting from connection failure at
The following duct work recommendations are the power connections to the chiller. Aluminum wiring
intended to ensure satisfactory operation of the unit. is not recommended due to thermal characteristics
Failure to follow these recommendations could cause that may cause loose terminations resulting from the
damage to the unit, or loss of performance, and may contraction and expansion of the wiring. Aluminum
invalidate the warranty. oxide may also build up at the termination causing hot
spots and eventual failure. If aluminum wiring is used
When ducting is to be fitted to the fan discharge it to supply power to the chiller, AL-CU compression
is recommended that the duct should be the same fittings should be used to transition from aluminum to
cross-sectional area as the fan outlet and straight for copper. This transition should be done in an external
at least three feet (1 meter) to obtain static regain box separate to the power panel. Copper conductors
from the fan. Duct work should be suspended with can then be run from the box to the chiller.
flexible hangers to prevent noise and vibration being
transmitted to the structure. A flexible joint is also A 120-1-60, 15 amp source must be supplied for the
recommended between the duct attached to the fan control panel through a fused disconnect when a control
and the next section for the same reason. Flexible panel transformer (optional) is not provided (Refer to
connectors should not be allowed to concertina. FIG. 8).
The unit(s) is not designed to take structural loading. See unit wiring diagrams for field and power wiring
No significant amount of weight should be allowed connections, chilled water pump starter contacts,
to rest on the fan outlet flange, deck assemblies or alarm contacts, compressor run status contacts, PWM
condenser coil module. No more than 3 feet (1 meter) input, and load limit input. Refer to section on UNIT
of light construction duct work should be supported OPERATION for a detailed description of operation
by the unit. Where cross winds may occur, any duct concerning aforementioned contacts and inputs.
work must be supported to prevent side loading on the
unit. Evaporator Pump Start Contacts

If the ducts from two or more fans are to be combined Terminal block TB1 – terminals 23 to 24, are normally-
into a common duct, back-flow dampers should be open contacts that can be used to switch field supplied
fitted in the individual fan ducts. This will prevent re- power to provide a start signal to the evaporator pump
circulation of air when only one of the fans is running. contactor. The contacts will be closed when any of the
following conditions occur:
Units are supplied with outlet guards for safety and
to prevent damage to the fan blades. If these guards 1. Low Leaving Chilled Liquid Fault
are removed to fit duct work, adequate alternative 2. Any compressor is running
precautions must be taken to ensure persons cannot be
harmed or put at risk from rotating fan blades. 3. Daily schedule is not programmed OFF and the
Unit Switch is ON
WIRING
The pump will not run if the micro panel has been
Liquid Chillers are shipped with all factory-mounted powered up for less than 30 seconds, or if the pump
controls wired for operation. has run in the last 30 seconds, to prevent pump motor
overheating. Refer to FIG. 9 and unit wiring diagram.
Field Wiring – Power wiring must be provided through
a fused disconnect switch to the unit terminals (or System Run Contacts
optional molded disconnect switch) in accordance with Contacts are available to monitor system status.
N.E.C. or local code requirements. Minimum circuit Normally-open auxiliary contacts from each compressor
ampacity and maximum dual element fuse size are contactor are wired in parallel with TB1 – terminals 25
given in Tables 6. to 26 for system 1, and TB1 – terminals 27 to 28 for
system 2 (YCAL0043 - YCAL0066). Refer to FIG. 4,
9 and unit wiring diagram.

36 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

Alarm Status Contacts Load Limit Input


Normally-open contacts are available for each refrigerant Load limiting is a feature that prevents the unit from
system. These normally-open contacts close when the loading beyond a desired value. The unit can be “load
system is functioning normally. The respective contacts limited” either 33%, 40%, 50%, 66% or 80%, depending
will open when the unit is shut down on a unit fault, or on the number of compressors on unit. The field
locked out on a system fault. Field connections are at
connections are wired to CTB1 – terminals 13 to 21, and
TB1 terminals 29 to 30 (system 1), and terminals 31 to
32 (system 2 YCAL0043 - YCAL0066). work in conjunction with the PWM inputs. A detailed
explanation is provided in the Unit Control section.
Remote Start/Stop Contacts Refer to Fig. 4, 9 and unit wiring diagram.
To remotely start and stop the chiller, dry contacts
can be wired in series with the flow switch and CTB1 When using the Load Limit feature,
- terminals 13 to 14. Refer to FIG 4, 9 and unit wiring the PWM feature will not function
diagram. – SIMULTANEOUS OPERATION
OF LOAD LIMITING AND TEM-
Remote Emergency Cutoff PERATURE RESET (PWM INPUT) 4
Immediate shutdown of the chiller can be accomplished CANNOT BE DONE.
by opening a field-installed dry contact to break the elec-
trical circuit between terminals 5 to L on terminal block Flow Switch Input
TB1. The unit is shipped with a factory jumper installed The flow switch is field wired to CTB1 terminals 13
between terminals 5 to L, which must be removed if - 14. See Page 22 and unit wiring diagram.
emergency shutdown contacts are installed. Refer to
FIG. 9 and unit wiring diagram. COMPRESSOR HEATERS
Remote Temp Reset Input
Compressor heaters are standard. ZP103, ZP120
& ZP137 compressors utilize 90W heaters; ZP180
The Remote Temp Reset input allows reset of the chilled compressors utilize 70W heaters; ZP235 compressors
liquid setpoint by supplying a voltage or current signal utilize 120W heaters. If power is OFF more than two
field wiring should be connected to CTB1 – terminals hours, the crankcase heaters must be energized for 18
A+ to A-. A detailed explanation is provided in the Unit – 24 hours prior to restarting a compressor. This will
Control section. Refer to Fig’s. 2 and 4 and unit wiring assure that liquid slugging and oil dilution does not
diagram. damage the compressors on start.

RELIEF VALVES
Relief valves are located on both the high and low
pressure side of the piping. High side relief valve
pressure setting is 650 PSIG. Low side relief valve
pressure setting is 450 PSIG.

HIGH PRESSURE CUTOUT


A high pressure cutout is installed in the discharge piping
of each system. The cutout opens at 585 PSIG ± 10
PSIG and closes at 440 PSIG ± 25 PSIG.

JOHNSON CONTROLS 37
Installation
FORM 150.67-NM1 (308)

SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED


DISCONNECT SWITCH OR CIRCUIT BREAKER

Power Panel Control Panel

2
L
Terminal Block, MICROPANEL
NF Disconnect SW
or Circuit Breaker

CTB2 Flow Switch


1L1 1L2 1L3
GRD

13 14
CTB1

Field Provided 120-1-60


Micropanel Power Supply if Control
Transformer not Supplied
Field Provided Unit Power Supply

See electrical note 9 LD07719

Electrical Notes and Legend located on page 53.

It is possible that multiple sources of power can be supplying the unit power panel. To prevent
serious injury or death, the technician should verify that NO LETHAL VOLTAGES are
present inside the panel AFTER disconnecting power, PRIOR to working on equipment.

The unit evaporator heater uses 120VAC. Disconnecting 120VAC power from the unit, at
or below freezing temperatures, can result in damage to the evaporator and unit as a result
of the chilled liquid freezing.

FIG. 8 – SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT SWITCH


OR CIRCUIT BREAKER (0043 – 0066)

38 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

CONTROL WIRING

FLOW SW REMOTE START/STOP


13
14
LOAD LIMIT INPUT
13
21

CTB1 LD07725A

4
*

* Factory wired with optional transformer.

CTB2 LD07730

It is possible that multiple sources of power can be supplying the unit power panel. To prevent
serious injury or death, the technician should verify that NO LETHAL VOLTAGES are
present inside the panel AFTER disconnecting power, PRIOR to working on equipment.

The unit evaporator heater uses 120VAC. Disconnecting 120VAC power from the unit, at
or below freezing temperatures, can result in damage to the evaporator and unit as a result
of the chilled liquid freezing.

FIG. 9 – CONTROL WIRING

JOHNSON CONTROLS 39
Technical Data
FORM 150.67-NM1 (308)

SECTION 5 – TECHNICAL DATA


OPERATIONAL LIMITATIONS (ENGLISH)
TABLE 1 – TEMPERATURES AND FLOWS
ENGLISH
LEAVING WATER
COOLER FLOW (GPM) AIR ON CONDENSER ( °F)
YCAL TEMPERATURE ( °F)
MIN MAX MIN MAX MIN MAX
0019 40 55 17 68 0 125
0022 40 55 21 84 0 125
0033 40 55 34 136 0 125
0043 40 55 40 200 0 125
0046 40 55 40 200 0 125
0066 40 55 60 300 0 125

Excessive flow will cause damage to the cooler. Do not exceed max. cooler flow. Special care
should be taken when multiple chillers are fed by a single pump.

NOTES:
1. For leaving brine temperature below 40 °F (4.4 °C), contact your nearest YORK Office for application requirements.
2. For leaving water temperature higher than 55 °F (12.8 °C), contact the nearest YORK Office for application guidelines.
3. The evaporator is protected against freezing to -20 °F (-28.8 °C) with an electric heater as standard.
4. For operation at temperatures below 25 °F (-3.9 °C), the optional Low Ambient Kit will need to be installed on the system.
5. For operation at temperatures above 110 °F (43 °C), the optional High Ambient Kit will need to be installed on the system.

VOLTAGE LIMITATIONS
The following voltage limitations are absolute and operation beyond these limitations may cause serious damage
to the compressor.
TABLE 2 – VOLTAGE LIMITATIONS
UNIT POWER MIN. MAX.
200-3-60 180 220
230-3-60 207 253
380-3-60 355 415
460-3-60 414 506
575-3-60 517 633

40 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

YCAL0019-0033 HEAT EXCHANGER FLOW, GPM

ENGLISH
1000.0

100.0
PRESSURE DROP, Ft H2O

10.0

B
1.0 5

0.1
1 10 100 1000
FLOW, GPM
LD12450

YCAL COOLER CURVE


0019 A
0022 B
0033 C

Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges.

JOHNSON CONTROLS 41
Technical Data
FORM 150.67-NM1 (308)

YCAL0043-0066 HEAT EXCHANGER FLOW, GPM

ENGLISH
100
A
B C
Press Drop, Ft H 2O

10

1
10 100 1000
FLOW, GPM

LD12451

YCAL COOLER CURVE


0043 A
0046 B
0066 C

Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges.

42 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

OPERATIONAL LIMITATIONS (SI)


TABLE 1A – TEMPERATURES AND FLOWS (SI)

LEAVING WATER
COOLER FLOW (L/S) AIR ON CONDENSER ( °C)
YCAL TEMPERATURE ( °C)
MIN MAX MIN MAX MIN MAX
0019 4.4 12.8 1.1 4.3 -17.7 51.7
0022 4.4 12.8 1.3 5.3 -17.7 51.7
0033 4.4 12.8 2.2 8.6 -17.7 51.7
0043 4.4 12.8 2.5 12.6 -17.7 51.7
0046 4.4 12.8 2.5 12.6 -17.7 51.7
0066 4.4 12.8 3.8 18.9 -17.7 51.7

Excessive flow will cause damage to the cooler. Do not exceed max. cooler flow. Special care
should be taken when multiple chillers are fed by a single pump.

5
NOTES:
1. For leaving brine temperature below 40 °F (4.4 °C), contact your nearest YORK Office for application requirements.
2. For leaving water temperature higher than 55 °F (12.8 °C), contact the nearest YORK Office for application guidelines.
3. The evaporator is protected against freezing to -20 °F (-28.8 °C) with an electric heater as standard.
4. For operation at temperatures below 25 °F (-3.9 °C), the optional Low Ambient Kit will need to be installed on the system.
5. For operation at temperatures above 110 °F (43 °C), the optional High Ambient Kit will need to be installed on the system.

VOLTAGE LIMITATIONS
The following voltage limitations are absolute and operation beyond these limitations may cause serious damage
to the compressor.

TABLE 2A – VOLTAGE LIMITATIONS


UNIT POWER MIN. MAX.
200-3-60 180 220
230-3-60 207 253
380-3-60 355 415
460-3-60 414 506
575-3-60 517 633

TABLE 3A – ETHYLENE & PROPOLYNE GLYCOL CORRECTION FACTORS


ETHYLENE GLYCOL PROPYLENE GLYCOL
% COMPR GPM PRESS FREEZE % COMPR GPM PRESS FREEZE
TONS TONS
WEIGHT KW F/TON DROP PT WEIGHT KW F/TON DROP PT
10.0 1.0 1.0 24.3 1.0 26.2 10.0 1.0 1.0 24.0 1.0 26.0
20.0 1.0 1.0 25.1 1.1 17.9 20.0 1.0 1.0 24.3 1.1 19.0
30.0 1.0 1.0 25.9 1.2 6.7 30.0 1.0 1.0 24.9 1.3 9.0
40.0 1.0 1.0 26.9 1.4 -8.1 40.0 1.0 1.0 25.6 1.4 -6.0
50.0 1.0 1.0 28.0 1.6 -28.9 50.0 0.9 1.0 26.6 1.7 -28.0

JOHNSON CONTROLS 43
Technical Data
FORM 150.67-NM1 (308)

OPERATIONAL LIMITATIONS (SI)

YCAL0019-0033 HEAT EXCHANGER FLOW, GPM

SI
1000.0
A

100.0
PRESSURE DROP, kPA

10.0

1.0
C

0.1
0.1 1 10 100
FLOW, L/S

YCAL COOLER CURVE


0019 A
0022 B LD12453

0033 C

Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges.

44 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

OPERATIONAL LIMITATIONS (SI)

YCAL0043-0066 HEAT EXCHANGER FLOW, GPM

SI
1000

A
B C
100
Press Drop, kPA

10
5

1
1 10 100
FLOW, L/S

LD12452

YCAL COOLER CURVE


0043 A
0046 B
0066 C

Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges.

JOHNSON CONTROLS 45
Technical Data
FORM 150.67-NM1 (308)

PHYSICAL DATA (ENGLISH)


YCAL0019_ – YCAL0066_
60Hz
TABLE 4 – PHYSICAL DATA (ENGLISH)

Dimension General Unit Data Nominal Comp. Capacity

Refrigerant Shipping Weight Operating Weight Circuit 1 Circuit 2


Model
Nominal Number of Charge, Oil Charge,
YCAL Alum. Copper Alum. Copper
Length Width Height Tons, Refrigerant Operating, Gallons
Fin Fin Fin Fin Comp. Comp. Comp. Comp. Comp. Comp.
R-410A Circuits R-22 (lbs) ckt1/ckt2
Coils, Coils, Coils, Coils, 1 2 3 4 5 6
ckt1/ckt2
lbs lbs lbs lbs
0019 109.79 44.70 46.06 14.5 1 25 1.8 1454 1597 1481 1624 8 8

0022 109.79 44.70 46.06 17.8 1 30 1.8 1567 1781 1597 1811 10 10

0033 118.57 44.70 50.00 28.0 1 50 2.2 2034 2240 2077 2283 15 15

0043 144.81 90.56 47.75 34.9 2 35/35 1.8/1.8 2942 3300 2967 3325 10 10 10 10

0046 144.81 90.56 47.75 38.0 2 40/35 1.8/1.8 2968 3326 3001 3359 12 12 10 10

0066 153.63 90.56 62.63 60.1 2 65/65 2.3/2.2 4097 4703 4142 4748 20 20 15 15

46 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

PHYSICAL DATA (ENGLISH) (CON’T)


YCAL0019_ – YCAL0066_

Condenser Condenser Fans, Low Sound Condenser Fans, Ultra Quiet Evaporator
Number of Minimum Maximum
Fans Maximum Maximum Nominal
Number of Chiller Chiller
Total Fins Fan Total Total Water Water Refrig Water
Rows Fan Number of Fans Fan Fan Water Water
Face per Power Chiller Chiller Volume, Side Side Conn.
Ckt. 1/ RPM ckt1/ckt2 Hp RPM Flow Flow
Area ft2 Inch ckt1/ckt2 hp/fan CFM CFM gallons Pressure, Pressure, Size,
Ckt. 2 Rate, Rate,
PSIG PSIG inches
gpm gpm
34.7 2 17 2 0.5 1100 13000 2 3.3 300 450 10 150 2

34.7 3 17 2 0.5 1100 13000 2 3.6 300 450 10 150 2

43.5 3 17 2 1.5 1140 24000 2 2 838 24000 5.2 300 450 10 150 2

87.0 2/2 17 2/2 2 1140 47400 2/2 2 838 47400 2.7 300 450 40 200 3

87.0 2/2 17 2/2 2 1140 47400 2/2 2 838 47400 3.5 300 450 40 200 3 5
128.0 3/3 13 2/2 2 1140 52000 2/2 2 838 52000 4.9 300 450 60 300 3

JOHNSON CONTROLS 47
Technical Data
FORM 150.67-NM1 (308)

SOUND DATA (ENGLISH)


YCAL0019_ – YCAL0033_
TABLE 5 – SOUND DATA – 60 HZ

SINGLE CIRCUIT UNITS

Low Noise Fan (Standard)


63 125 250 500 1000 2000 4000 8000 dBA
YCAL0019 83 82 81 81 79 74 69 67 83
YCAL0022 84 83 82 82 79 75 70 68 84
YCAL0033 91 91 92 90 85 81 77 74 91

Low Noise Fan with Compressor Sound Blankets


63 125 250 500 1000 2000 4000 8000 dBA
YCAL0019 83 82 81 79 78 73 68 64 82
YCAL0022 84 83 82 80 78 73 68 65 82
YCAL0033 91 91 92 89 84 80 76 73 91

Ultra Quiet Fan (Optional)


63 125 250 500 1000 2000 4000 8000 dBA
YCAL0033 93 90 88 87 84 80 76 74 89

Ultra Quiet Fan with Compressor Sound Blankets


63 125 250 500 1000 2000 4000 8000 dBA
YCAL0033 93 90 88 86 82 78 74 73 88

48 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

SOUND DATA (ENGLISH)


YCAL0043_ – YCAL0066_
TABLE 5 – SOUND DATA – 60 Hz – (Cont’d)

DUAL CIRCUIT UNITS

Low Noise Fan (Standard)


63 125 250 500 1000 2000 4000 8000 dBA
YCAL0043 92 91 92 90 86 81 77 74 92
YCAL0046 92 91 92 90 86 81 77 74 92
YCAL0066 94 94 95 93 90 86 82 77 95

Low Noise Fan With Compressor Sound Blankets


63 125 250 500 1000 2000 4000 8000 dBA
YCAL0043 92 91 92 90 86 81 77 73 91
YCAL0046 92 91 92 90 86 81 77 73 91
YCAL0066 94 94 95 93 89 84 80 75 94

Ultra Quiet Fan (Optional)


63 125 250 500 1000 2000 4000 8000 dBA
5
YCAL0043 94 88 88 87 83 79 75 74 88
YCAL0046 94 88 88 87 83 79 75 74 88
YCAL0066 96 92 91 90 87 84 81 77 92

Ultra Quiet Fan With Compressor Sound Blankets


63 125 250 500 1000 2000 4000 8000 dBA
YCAL0043 94 88 88 85 82 77 74 73 87
YCAL0046 94 88 88 85 82 77 74 73 87
YCAL0066 96 92 91 89 86 81 78 75 91

JOHNSON CONTROLS 49
Technical Data
FORM 150.67-NM1 (308)

ELECTRICAL DATA (ENGLISH)


YCAL0019_ – YCAL0066_ (Without Pump)
SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 8)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused
Disconnect Switch (optional) or Circuit Breaker (optional)).

TABLE 6 – ELECTRICAL DATA (ENGLISH)

FIELD WIRING LUGS6 FIELD WIRING LUGS6


MIN N/F D.E. FUSE CKT. BKR.5
MODEL VOLT TERMINAL BLOCK (std) NF DISC. SWITCH (opt)
MCA1 DISC
YCAL 60 Hz LUGS/ LUGS/
MDSW2 MIN. MAX4 MIN. MAX LUG WIRE RANGE LUG WIRE RANGE
PHASE PHASE
200 101 150 125 125 125 125 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
230 94 100 110 125 110 125 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
0019 380 54 60 60 70 60 70 1 14 AWG – 2/0 1 14 AWG – 1/0
460 45 60 50 60 50 60 1 14 AWG – 2/0 1 14 AWG – 1/0
575 36 60 40 50 40 50 1 14 AWG – 2/0 1 14 AWG – 1/0
200 108 150 150 150 125 150 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
230 100 150 125 125 125 125 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
0022 380 58 60 60 80 70 80 1 14 AWG – 2/0 1 14 AWG – 1/0
460 48 60 60 60 60 60 1 14 AWG – 2/0 1 14 AWG – 1/0
575 39 60 60 60 45 60 1 14 AWG – 2/0 1 14 AWG – 1/0
200 151 200 175 200 175 200 1 6 AWG – 350 kcmil 1 4 AWG – 300 kcmil
230 140 150 175 175 175 175 1 6 AWG – 350 kcmil 1 4 AWG – 300 kcmil
0033 380 81 100 90 110 90 110 1 14 AWG – 2/0 1 14 AWG – 1/0
460 67 100 80 90 80 90 1 14 AWG – 2/0 1 14 AWG – 1/0
575 54 60 60 70 60 70 1 14 AWG – 2/0 1 14 AWG – 1/0
200 224 250 250 250 250 250 1 6 AWG – 350 kcmil 2 *(2) 3/0 – 250 kcmil
230 209 250 225 250 225 250 1 6 AWG – 350 kcmil 2 *(2) 3/0 – 250 kcmil
0043 380 121 150 150 150 150 150 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
460 99 150 110 110 110 110 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
575 80 100 90 90 90 90 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
200 228 250 250 250 250 250 1 6 AWG – 350 kcmil 2 *(2) 3/0 – 250 kcmil
230 212 250 225 250 225 250 1 6 AWG – 350 kcmil 2 *(2) 3/0 – 250 kcmil
0046 380 123 150 150 150 150 150 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
460 101 150 110 110 110 110 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
575 81 100 90 90 90 90 1 14 AWG – 2/0 1 4 AWG – 300 kcmil
200 324 400 350 400 350 400 1 4 AWG – 500 kcmil 1 250 kcmil – 500 kcmil
230 301 400 350 350 350 350 1 4 AWG – 500 kcmil 1 250 kcmil – 500 kcmil
0066 380 175 200 200 200 200 200 1 6 AWG – 350 kcmil 1 6 AWG – 350 kcmil
460 143 200 175 175 175 175 1 6 AWG – 350 kcmil 1 6 AWG – 350 kcmil
575 115 150 125 125 125 125 1 6 AWG – 350 kcmil 1 6 AWG – 350 kcmil

* Panels will have (3) 250 KEMIL lug kit shipped loose to accommodate larger wire size if needed.

50 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELECTRICAL DATA (ENGLISH) (CON’T)


YCAL0019_ – YCAL0066_
SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 8)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused
Disconnect Switch (optional) or Circuit Breaker (optional)).

FIELD WIRING LUGS6 SYSTEM #1 COMPRESSOR & FAN SYSTEM #2 COMPRESSOR & FAN
CIRCUIT BREAKER (opt) COMPR. #1 COMPR. #2 FANS COMPR. #1 COMPR. #2 FANS

LUGS/ PHASE LUG WIRE RANGE RLA LRA RLA LRA QTY FLA(EA) RLA LRA RLA LRA QTY FLA(EA)

1 6 AWG – 350MCM 42.2 250 42.2 250 2 2.6 — — — — — —


1 6 AWG – 350MCM 39.0 250 39.0 250 2 2.6 — — — — — —
1 14 AWG – 1/0 22.5 155 22.5 155 2 1.6 — — — — — —
1 14 AWG – 1/0 18.6 114 18.6 114 2 1.3 — — — — — —
1 14 AWG – 1/0 14.9 100 14.9 100 2 1.0 — — — — — —
1 6 AWG – 350MCM 45.4 250 45.4 250 2 2.6 — — — — — —
1 6 AWG – 350MCM 42.0 250 42.0 250 2 2.6 — — — — — —
1 14 AWG – 1/0 24.2 155 24.2 155 2 1.6 — — — — — —
1 14 AWG – 1/0 20.0 125 20.0 125 2 1.3 — — — — — —
1 14 AWG – 1/0 16.0 100 26.0 100 2 1.0 — — — — — — 5
1 6 AWG – 350MCM 59.9 425 59.9 425 2 7.6 — — — — — —
1 6 AWG – 350MCM 55.5 425 55.5 425 2 7.4 — — — — — —
1 14 AWG – 1/0 32.0 239 32.0 239 2 4.5 — — — — — —
1 14 AWG – 1/0 26.4 187 26.4 187 2 3.4 — — — — — —
1 14 AWG – 1/0 21.1 148 21.1 148 2 2.9 — — — — — —
2 *(2) 3/0 – 250 kcmil 45.4 250 45.4 250 2 7.6 45.4 250 45.4 250 2 7.6
2 *(2) 3/0 – 250 kcmil 42.0 250 42.0 250 2 7.4 42.0 250 42.0 250 2 7.4
1 6 AWG – 350MCM 24.2 155 24.2 155 2 4.5 24.2 155 24.2 155 2 4.5
1 6 AWG – 350MCM 20.0 125 20.0 125 2 3.4 20.0 125 20.0 125 2 3.4
1 6 AWG – 350MCM 16.0 100 16.0 100 2 2.9 16.0 100 16.0 100 2 2.9
2 *(2) 3/0 – 250 kcmil 47.0 250 47.0 250 2 7.6 45.4 250 45.4 250 2 7.6
2 *(2) 3/0 – 250 kcmil 43.5 43.5 250 250 2 7.4 42.0 250 42.0 250 2 7.4
1 6 AWG – 350MCM 25.1 155 25.1 155 2 4.5 24.2 155 24.2 155 2 4.5
1 6 AWG – 350MCM 20.7 125 20.7 125 2 3.4 20.0 125 20.0 125 2 3.4
1 6 AWG – 350MCM 16.6 100 16.6 100 2 2.9 16.0 100 16.0 100 2 2.9
1 250 kcmil – 500 kcmil 76.9 505 76.9 505 2 7.6 59.9 425 59.9 425 2 7.6
1 250 kcmil – 500 kcmil 71.2 505 71.2 505 2 7.4 55.5 425 55.5 425 2 7.4
1 6 AWG – 350MCM 41.1 280 41.1 280 2 4.5 32.0 239 32.0 239 2 4.5
1 6 AWG – 350MCM 33.9 225 33.9 225 2 3.4 26.4 187 26.4 187 2 3.4
1 6 AWG – 350MCM 27.1 180 27.1 180 2 2.9 21.1 148 21.1 148 2 2.9

JOHNSON CONTROLS 51
Technical Data
FORM 150.67-NM1 (308)

ELECTRICAL DATA
TABLE 7 – MICRO PANEL POWER SUPPLY

CONTROL OVER CURRENT PROTECTION,


UNIT VOLTAGE MCA
POWER SEE NOTE B NF DISC Sw
UNIT NOTE A
MODELS w/o MIN MAX
VOLTAGE
CONTROL 115-1-60/50
15A 10A 15A 30 A / 240V
TRANS
-17 200-1-60 15A 10A 15A 30 A / 240V
-28 230-1-60 15A 10A 15A 30 A / 240V
MODELS w/
-40 380-1-60 15A 10A 15A 30 A / 480V
CONTROL
-46 460-1-60 15A 10A 15A 30 A / 480V
TRANS
-50 380/415-1-60 15A 10A 15A 30A / 415V
-58 575-1-60 15A 10A 15A 30 A / 600V

A. Minimum #14 AWG, 75 °C, Copper Recommended


B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker

It is possible that multiple sources of power can be supplying the unit power panel. To pre-
vent serious injury or death, the technician should verify that NO LETHAL VOLTAGES are
present inside the panel AFTER disconnecting power, PRIOR to working on equipment.

The unit evaporator heater uses 120VAC. Disconnecting 120VAC power from the unit, at or
below freezing temperatures, can result in damage to the evaporator and unit as a result of
the chilled liquid freezing.

TABLE 8 – VOLTAGE RANGE

VOLTAGE RANGE
VOLTAGE CODE UNIT POWER MIN. MAX.
-17 200-3-60 180 220
-28 230-3-60 207 253
-40 380/415-3-60 342 440
-46 460-3-60 414 506
-50 380/415-3-50 342 440
-58 575-3-60 517 633

52 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELECTRICAL NOTES AND LEGEND


NOTES:

1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of
the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory
Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system
providing power to the transformer: -17, add 2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps, -46, add 1.3 amps;
-58, add 1 amps.

2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included
in the circuit, per N.E.C. Article 440.

3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not
recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at
ambient temperatures in excess of 95ºF (35ºC) is anticipated.

4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated
load amps for all other loads included in the circuit, per N.E.C. Article 440-22.

5. Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated load amps
for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, an
HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated
load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.

6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the 5
unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase
of the wire range specified. Actual wire size and number of wires per phase must be determined based on the
National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.

7. A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C.
Table 250-95. A control circuit grounding lug is also supplied.

8. The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the
unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended
to be a Load Break Device.

9. Field Wiring by others which complies to the National Electrical Code & Local Codes.

LEGEND:

ACR-LINE ACROSS THE LINE START VOLTAGE CODE


C.B. CIRCUIT BREAKER -17 = 200-3-60
D.E. DUAL ELEMENT FUSE -28 = 230-3-60
DISC SW DISCONNECT SWITCH -40 = 380-3-60
FACT MOUNT CB FACTORY MOUNTED CIRCUIT BREAKER -46 = 460-3-60
FLA FULL LOAD AMPS
-58 = 575-3-60
HZ HERTZ
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM LEGEND:
MIN NF MINIMUM NON FUSED Field Wiring
RLA RATED LOAD AMPS
S.P. WIRE SINGLE POINT WIRING Factory Wiring
UNIT MTD SERV SW UNIT MOUNTED SERVICE (NON-FUSED
DISCONNECT SWITCH)
LRA LOCKED ROTOR AMPS

JOHNSON CONTROLS 53
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM


YCAL0019, 0022 & 0033 STANDARD UNITS
YCAL0019, 0022 & 0033 STANDARD LOW SOUND UNITS
YCAL0033 ULTRA LOW SOUND UNITS (460, 380-415V/3/50 Hz ONLY)

LD12699

FIG. 10 – CONTROL CIRCUIT, SINGLE

54 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM (CON’T)

LD12700

FIG. 10 (CON’T) – CONTROL CIRCUIT, SINGLE

JOHNSON CONTROLS 55
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM


YCAL0033 ULTRA LOW SOUND UNIT UNITS (200, 230, 380 & 575V ONLY)

LD12705

FIG. 11 – CONTROL CIRCUIT, SINGLE

56 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM (CON’T)

LD12706

FIG. 11 (CON’T) – CONTROL CIRCUIT, SINGLE

JOHNSON CONTROLS 57
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM


YCAL0043, 0046 & 0066 STANDARD UNITS
YCAL0043, 0046 & 0066 STANDARD LOW SOUND UNITS
YCAL0043, 0046 & 0066 ULTRA LOW SOUND UNITS (460, 380-415V/3/50 Hz ONLY)

LD12693

FIG. 12 – CONTROL CIRCUIT, DUAL

58 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM (CON’T)

FIG. 12 (CON’T) – CONTROL CIRCUIT, DUAL LD12694

JOHNSON CONTROLS 59
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM


YCAL0043, 0046 & 0066 ULTRA LOW SOUND UNITS (200, 230, 380 & 575V ONLY)

LD12711

FIG. 13 – CONTROL CIRCUIT, DUAL

60 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM (CON’T)

FIG. 13 (CON’T) – CONTROL CIRCUIT, DUAL LD12712

JOHNSON CONTROLS 61
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM


YCAL 0019 & 0022 STANDARD UNITS
YCAL 0019 & 0022 STANDARD LOW SOUND UNITS
YCAL 0019 & 0022 ULTRA LOW SOUND UNITS (460, 380-415V/3/50 Hz ONLY)

LD 12197

FIG. 14 – POWER CIRCUIT, SINGLE

62 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM (CON’T)

LD 12198

FIG. 14 (CON’T) – POWER CIRCUIT, SINGLE

JOHNSON CONTROLS 63
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM


YCAL 0033 STANDARD UNITS
YCAL 0033 STANDARD LOW SOUND UNITS
YCAL 0033 ULTRA LOW SOUND UNITS (460, 380-415V/3/50 Hz ONLY)

FIG. 14A – POWER CIRCUIT, SINGLE LD12701

64 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM (CON’T)

FIG. 14A (CON’T) – POWER CIRCUIT, SINGLE LD12702

JOHNSON CONTROLS 65
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM


YCAL 0033 ULTRA LOW SOUND UNITS (200, 230, 380 & 575V ONLY)

FIG. 14B – POWER CIRCUIT, SINGLE LD12707

66 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM (CON’T)

FIG. 14B (CON’T) – POWER CIRCUIT, SINGLE LD12708

JOHNSON CONTROLS 67
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM


YCAL0043, 0046, & 0066 ULTRA LOW SOUND UNITS (200, 230, 380 & 575V ONLY)

FIG. 14C – POWER CIRCUIT, DUAL LD12707


LD12691

68 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM (CON’T)

FIG. 14C (CON’T) – POWER CIRCUIT, DUAL


LD12708
LD12692

JOHNSON CONTROLS 69
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM


YCAL0043, 0046 & 0066 STANDARD UNITS
YCAL0043, 0046 & 0066 STANDARD LOW SOUND UNITS
YCAL0043, 0046 & 0066 ULTRA LOW SOUND UNITS (460, 380-415V/3/50 Hz ONLY)

FIG. 14D – POWER CIRCUIT, DUAL LD12695

70 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM (CON’T)

FIG. 14DS (CON’T) – POWER CIRCUIT, DUAL LD12696

JOHNSON CONTROLS 71
Technical Data
FORM 150.67-NM1 (308)

CONNECTION WIRING DIAGRAM


YCAL0019, 0022, 0026, & 0033 STANDARD UNITS
YCAL0019, 0022, 0026, & 0033 STANDARD LOW SOUND UNITS
YCAL 0033 ULTRA LOW SOUND UNITS (460, 380-415V/3/50 Hz ONLY)

LD12703

FIG. 15 – CONNECTION WIRING DIAGRAM MICROBOARD, SINGLE CIRCUIT

72 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

CONNECTION WIRING DIAGRAM (CON’T)

LD12704

FIG. 15 (CON’T) CONNECTION WIRING DIAGRAM MICROBOARD, SINGLE CIRCUIT

JOHNSON CONTROLS 73
Technical Data
FORM 150.67-NM1 (308)

CONNECTION WIRING DIAGRAM


YCAL 0033 ULTRA LOW SOUND UNITS (200, 230, 380 & 575V ONLY)

LD12709

FIG. 15A – CONNECTION WIRING DIAGRAM MICROBOARD, SINGLE CIRCUIT

74 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

CONNECTION WIRING DIAGRAM (CON’T)

LD12710

FIG. 15A (CON’T) CONNECTION WIRING DIAGRAM MICROBOARD, SINGLE CIRCUIT

JOHNSON CONTROLS 75
Technical Data
FORM 150.67-NM1 (308)

CONNECTION WIRING DIAGRAM


YCAL0043, 0046 & 0066 ULTRA LOW SOUND UNITS (200, 230, 380 & 575V ONLY)

LD12713

FIG. 15B – CONNECTION WIRING DIAGRAM MICROBOARD, DUAL CIRCUIT

76 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

CONNECTION WIRING DIAGRAM (CON’T)

LD12714

FIG. 15B (CON’T) CONNECTION WIRING DIAGRAM MICROBOARD, DUAL CIRCUIT

JOHNSON CONTROLS 77
Technical Data
FORM 150.67-NM1 (308)

CONNECTION WIRING DIAGRAM


YCAL0043, 0046 & 0066 STANDARD UNITS
YCAL0043, 0046 & 0066 STANDARD LOW SOUND UNITS
YCAL0043, 0046 & 0066 ULTRA LOW SOUND UNITS (460, 380-415V/3/50 Hz ONLY)

LD12697

FIG. 15C – CONNECTION WIRING DIAGRAM MICROBOARD, DUAL CIRCUIT

78 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

CONNECTION WIRING DIAGRAM (CON’T)

LD12698

FIG. 15C (CON’T) CONNECTION WIRING DIAGRAM MICROBOARD, DUAL CIRCUIT

JOHNSON CONTROLS 79
Technical Data
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM DETAILS


YCAL0019, 0022 & 0033 STANDARD UNITS
YCAL0019, 0022 & 0033 STANDARD LOW SOUND UNITS
YCAL 0033 ULTRA LOW SOUND UNITS

LD12690

FIG. 16 – ELEMENTARY WIRING DIAGRAM DETAILS, SINGLE CIRCUIT

80 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

ELEMENTARY WIRING DIAGRAM DETAILS


YCAL0043, 0046 & 0066 STANDARD UNITS
YCAL0043, 0046 & 0066 STANDARD LOW SOUND UNITS
YCAL0043, 0046 & 0066 ULTRA LOW SOUND UNITS

LD12689

FIG. 16A – ELEMENTARY WIRING DIAGRAM DETAILS, DUAL CIRCUIT

JOHNSON CONTROLS 81
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS (ENGLISH)

DIMENSIONS – YCAL0019 (ENGLISH)

3 1/4"
6 3/4"
7/8" TYP.

3 15/16" VIEW B-B


BOTTOM OF PANEL

2" DIA
(2) 3.0 X 1.50
46 1/16"
B B RIGGING HOLES
45 1/4" BOTH ENDS

2 1/4"
11 5/8"

TO ACCESS PANEL 16 1/4" 11"


12 13/16" 12 13/16"
8 5/16" 8 5/16"
18 3/4"
2" VICTAULIC CONN
(typ)
44 5/16"
BASE WIDTH

LEFT END

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

LD11813

NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall – 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".

82 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0019 (ENGLISH) (CON’T)

9/16" DIA MOUNTING HOLES(typ)


1 1/16"

CONTROL
PANEL COMPR
44 3/8"
END CAP END END
WIDTH
32 1/8"

6 1/8"

1 1/16"
ORIGIN 2 1/4"
Y 5"
17" TOP VIEW

C
G X
5
1"
9 1/16"
CONTROL PANEL

38 3/16"

2 1/4" 3 3/8"
13 3/4"

(2) 7.0 X 2.25


FORKLIFT HOLES
BOTH SIDES (2) 3.0 X 1.50
15 5/8" RIGGING HOLES
44 1/2" BOTH SIDES
74 1/2"
97 1/8"

Z 109 3/16"

FRONT VIEW

C
G X

LD11814

JOHNSON CONTROLS 83
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0022 (ENGLISH)

3 1/4"
6 3/4"
7/8" TYP.

3 15/16" VIEW B-B


BOTTOM OF PANEL

2" DIA
(2) 3.0 X 1.50
46 1/16"
B B RIGGING HOLES
45 1/4" BOTH ENDS

2 1/4"
11 5/8"

TO ACCESS PANEL 16 1/4" 11"


12 13/16" 12 13/16"
8 5/16" 8 5/16"
18 3/4"
2" VICTAULIC CONN
(typ)
44 5/16"
BASE WIDTH

LEFT END

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

LD11815

NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall – 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".

84 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0022 (ENGLISH) (CON’T)

9/16" DIA MOUNTING HOLES(typ)


1 1/16"

CONTROL
PANEL COMPR
44 3/8"
END CAP END END
WIDTH
32 1/8"

6 1/8"

1 1/16"
ORIGIN 2 1/4"
Y 5"
17" TOP VIEW

C
G X

1" 5
9 1/16"
CONTROL PANEL

38 3/16"

2 1/4" 3 3/8"
13 3/4"

(2) 7.0 X 2.25


FORKLIFT HOLES
BOTH SIDES (2) 3.0 X 1.50
15 5/8" RIGGING HOLES
44 1/2" BOTH SIDES
74 1/2"
97 1/8"

Z 109 3/16"

FRONT VIEW

C
G X

LD10966

JOHNSON CONTROLS 85
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0033 (ENGLISH)

82
171
22 TYP.

100 VIEW B-B


BOTTOM OF PANEL

51 DIA
1272 B B (2) 76 X 38
1250 RIGGING HOLES
BOTH ENDS
216
58 394

TO ACCESS PANEL 340 274


325 325
211 211
483
51 VICTAULIC CONN
(typ)
1126
BASE WIDTH

LEFT END

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

LD11821

NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall – 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".

86 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0033 (ENGLISH) (CON’T)

9/16" DIA MOUNTING HOLES(typ)


1 1/16"

CONTROL
PANEL COMPR
44 3/8"
END END
END CAP
WIDTH
32 1/8"
6 1/8"

1 1/16"
ORIGIN 1 7/8"
Y 5"
17"
TOP VIEW

5
C
G X

1"
9"

CONTROL PANEL

42 1/8"

3 3/8"
17 3/4" 2 1/4"

(2) 7.0 X 2.25


FORKLIFT HOLES
15 5/8" BOTH SIDES (2) 3.0 X 1.50
RIGGING HOLES
50 1/2" BOTH SIDES
80 1/2"
Z 105 1/16"
118 5/16"

C
G X FRONT VIEW
LD10966
LD10972

JOHNSON CONTROLS 87
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0043 (ENGLISH)

6 3/4"
3 1/4" 7/8" TYP.

3 15/16"
VIEW B-B
BOTTOM OF PANEL

LIQUID IN

ELECTRICAL ACCESS
47 3/4" PANEL
46 15/16"
34 5/8"
9 15/16"
15 3/4"

3" VICTAULIC (typ)


LIQUID OUT
12 5/8"
45 1/8"

90 1/4" BASE WIDTH

LEFT END

Aluminum Copper
Center of Gravity (in.) Center of Gravity (In.)
YCAL YCAL
X Y X Y
0043 59.6 43.6 0043 63.6 43.7

LD10962

NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall – 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".

88 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0043 (ENGLISH) (CON’T)


9/16" DIA MOUNTING HOLES(typ)
1 1/16" L1 L2

COOLER COIL
END END

90 9/16"
END CAP
WIDTH

45 5/16"

R1 R2 1 1/16"
5
ORIGIN 9 13/16" 9 13/16"
21 13/16" TOP VIEW

X
CG

5 5/16"
38"
CONTROL PANEL

25 3/8" B B

13 5/8"
LD10968
LD10962
TWO LIFTING HOLES
BOTH SIDES 13 15/16"
Z 15 1/16"
144 13/16"

X
C
G FRONT VIEW

JOHNSON CONTROLS 89
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0046 (ENGLISH)

6 3/4"
3 1/4" 7/8" TYP.

3 15/16"
VIEW B-B
BOTTOM OF PANEL

LIQUID IN

ELECTRICAL ACCESS
47 3/4" PANEL
46 15/16"
34 5/8"
9 15/16"
15 3/4"

3" VICTAULIC (typ)


LIQUID OUT
12 5/8"
45 1/8"

90 1/4" BASE WIDTH

LEFT END

Aluminum Copper
Center of Gravity (In.) Center of Gravity (In.)
YCAL YCAL
X Y X Y
0046 59.2 43.5 0046 63.2 43.7

LD10963

NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall – 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".

90 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0046 (ENGLISH) (CON’T)

9/16" DIA MOUNTING HOLES(typ)


1 1/16" L1 L2

COOLER COIL
END END

90 9/16"
END CAP
WIDTH

45 5/16"

5
R1 R2 1 1/16"

ORIGIN 9 13/16" 9 13/16"


20 1/16" TOP VIEW

X
CG

5 5/16"
38"
CONTROL PANEL

25 3/8" B B

13 5/8"

LD10964
TWO LIFTING HOLES
BOTH SIDES 13 15/16"
Z 15 1/16"
144 13/16"

X
C
G FRONT VIEW

JOHNSON CONTROLS 91
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0066 (ENGLISH)

6 3/4"
3 1/4" 7/8" TYP.

3 15/16" VIEW B-B


BOTTOM OF PANEL

LIQUID IN

62 5/8"
61 7/8" ELECTRICAL ACCESS
PANEL
34 11/1
9 15/16"
15 3/4"

3" VICTAULIC (typ)


LIQUID OUT
12 5/8"

43 1/8"
90 1/4" BASE WIDTH
LEFT END

Aluminum Copper
Center of Gravity (In.) Center of Gravity (In.)
YCAL YCAL
X Y X Y
0066 59.7 44.9 0066 65.2 44.9

LD10971

NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall – 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".

92 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0066 (ENGLISH) (CON’T)

9/16" DIA MOUNTING HOLES(typ)


1 1/16" L1 L2

COOLER COIL
END END

90 9/16"
END CAP
WIDTH

43 5/16"

5
R1 R2 1 1/16

ORIGIN
9 13/16" 9 13/16
16 11/16" TOP VIEW

X 5 3/16"
CG
38"

CONTROL
PANEL
25 3/8" B B

28 9/16"

LD10972
TWO LIFTING HOLES
BOTH SIDES
16"
Z 15 1/16"
153 5/8"

JOHNSON CONTROLS 93
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0019 (SI)

82
171
22 TYP.

100 VIEW B-B


BOTTOM OF PANEL

51 DIA
(2) 76 X 38
1170
B B RIGGING HOLES
1149 BOTH ENDS

58
295

TO ACCESS PANEL 412 280


325 325
211 211
477
51 VICTAULIC CONN
(typ)
1126
BASE WIDTH

LEFT END

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

LD11825

NOTE: All dimensions are in mm unless specified otherwise.


NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall – 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.

94 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0019 (SI) (CON’T)

14 DIA MOUNTING HOLES(typ)


28

CONTROL
PANEL COMPR
1128
END CAP END END
WIDTH
815

156

28
ORIGIN 58
Y 126
431 TOP VIEW

C
G X

25
230
5
CONTROL PANEL

970

58 86
350

(2) 178 X 57
FORKLIFT HOLES
BOTH SIDES (2) 76 X 38
398 RIGGING HOLES
1130 BOTH SIDES
1892
2466

Z 2774

FRONT VIEW

C
G X

LD11826

JOHNSON CONTROLS 95
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0022 (SI)

82
171
22 TYP.

100 VIEW B-B


BOTTOM OF PANEL

51 DIA
(2) 76 X 38
1170
B B RIGGING HOLES
1149 BOTH ENDS

58
295

TO ACCESS PANEL 412 280


325 325
211 211
477
51 VICTAULIC CONN
(typ)
1126
BASE WIDTH

LEFT END

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

LD11827

NOTE: All dimensions are in mm unless specified otherwise.


NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall – 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.

96 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0022 (SI) (CON’T)

14 DIA MOUNTING HOLES(typ)


28 328 530

CONTROL
PANEL COMPR
1128
END CAP END END
WIDTH
815

156

317 512 28
ORIGIN 58
Y 126
431 TOP VIEW

C
G X

25 5
230
CONTROL PANEL

970

58 86
350

(2) 178 X 57
FORKLIFT HOLES
BOTH SIDES (2) 76 X 38
398 RIGGING HOLES
1130 BOTH SIDES
1892
2466

Z 2774

FRONT VIEW

C
G X

LD11828

JOHNSON CONTROLS 97
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0033 (SI)

82
171
22 TYP.

100 VIEW B-B


BOTTOM OF PANEL

51 DIA
1272 B B (2) 76 X 38
1250 RIGGING HOLES
BOTH ENDS
216
58 394

TO ACCESS PANEL 340 274


325 325
211 211
483
51 VICTAULIC CONN
(typ)
1126
BASE WIDTH

LEFT END

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

LD11833

NOTE: All dimensions are in mm unless specified otherwise.


NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall – 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.

98 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0033 (SI) (CON’T)

14 DIA MOUNTING HOLES(typ)


28

CONTROL
PANEL COMPR
1128
END END
END CAP
WIDTH
815
156

28
ORIGIN 47
Y 126
431
TOP VIEW

C
G X

5
25
229

CONTROL PANEL

1070

86
450 58

(2) 178 X 57
FORKLIFT HOLES
398 BOTH SIDES (2) 76 X 38
RIGGING HOLES
1282 BOTH SIDES
2044
Z 2669
3005

C
G X FRONT VIEW

LD11834

JOHNSON CONTROLS 99
Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0043 (SI)

171
82 22 TYP.

100
VIEW B-B
BOTTOM OF PANEL

LIQUID IN

ELECTRICAL ACCESS
1213 PANEL
1192
879
252
401

76 VICTAULIC (typ)
LIQUID OUT
321
1146

2292 BASE WIDTH

LEFT END

Aluminum Copper
Center of Gravity (mm) Center of Gravity (mm)
YCAL YCAL
X Y X Y
0043 1513.7 1107.0 0043 1616.1 111.1

LD10973

NOTE: All dimensions are in mm unless specified otherwise.


NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall – 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.

100 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0043 (SI) (CON’T)

14 DIA MOUNTING HOLES(typ)


28 L1 L2

COOLER COIL
END END

2301
END CAP
WIDTH

1150

R1 R2 28

ORIGIN 249 249 5


554 TOP VIEW

X
CG

135
965
CONTROL PANEL

645 B B

346

TWO LIFTING HOLES


BOTH SIDES 355 LD10974
Z 383
3678

X
C
G FRONT VIEW

JOHNSON CONTROLS 101


Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0046 (SI)

171
82 22 TYP.

100
VIEW B-B
BOTTOM OF PANEL

LIQUID IN

ELECTRICAL ACCESS
1213 PANEL
1192
879
252
401

76 VICTAULIC (typ)
LIQUID OUT
321
1146

2292 BASE WIDTH

LEFT END

Aluminum Copper
Center of Gravity (mm) Center of Gravity (mm)
YCAL YCAL
X Y X Y
0046 1503.5 1105.5 0046 1605.9 1109.7

LD10975

NOTE: All dimensions are in mm unless specified otherwise.


NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall – 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.

102 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0046 (SI) (CON’T)

14 DIA MOUNTING HOLES(typ)


28 L1 L2

COOLER COIL
END END

2301
END CAP
WIDTH

1150

R1 R2 28

ORIGIN 249 249 5


509 TOP VIEW

X
CG

135
965
CONTROL PANEL

645 B B

346

TWO LIFTING HOLES


BOTH SIDES 355 LD10976
Z 383
3678

X
C
G FRONT VIEW

JOHNSON CONTROLS 103


Technical Data
FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0066 (SI)

171
82 22 TYP.

100 VIEW B-B


BOTTOM OF PANEL

LIQUID IN

1590
1572 ELECTRICAL ACCESS
PANEL
880
252
401

76 VICTAULIC (typ)
LIQUID OUT
321

1095
2292 BASE WIDTH
LEFT END

Aluminum Copper
Center of Gravity (mm) Center of Gravity (mm)
YCAL YCAL
X Y X Y
0066 1517.6 1140.3 0066 1655.5 1141.1

LD10983

NOTE: All dimensions are in mm unless specified otherwise.


NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall – 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.

104 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

DIMENSIONS – YCAL0066 (SI) (CON’T)

14 DIA MOUNTING HOLES(typ)


28

COOLER COIL
END END

2301
END CAP
WIDTH

1100

28

ORIGIN
249 249
5
424 TOP VIEW

X 131
CG
965

CONTROL
PANEL
645 B B

726

TWO LIFTING HOLES


BOTH SIDES
406
Z 383
LD10984
3902

X
C
G FRONT VIEW

JOHNSON CONTROLS 105


Technical Data
FORM 150.67-NM1 (308)

TECHNICAL DATA – CLEARANCES

(2 m)

(1.3 m) (2 m)
(2 m)

LD10506

NOTES:
1. No obstructions allowed above the unit.
2. Only one adjacent wall may be higher than the unit.
3. Adjacent units should be 10 feet (3 Meters) apart.

FIG. 17 – UNIT CLEARANCES – ALL MODELS

106 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

WEIGHT DISTRIBUTION AND ISOLATOR MOUNTING POSITIONS


YCAL0019 – 0033 (WITHOUT PUMP PACKAGE OPTION)

GENERAL

Weights of specific chiller models vary significantly as Whenever the isolator option is ordered, the isolators
options are added. As a result, total weights, weights at will be shipped loose with the chiller. Packed with the
individual isolator positions, and actual isolator selection isolators and also in the control panel information packet
at each position cannot be published due to the vast is a drawing and table specifically for each chiller, based
number of possible combinations. This information on the option selection. The drawing and table will be
will be available when the specific chiller/ option similar to the ones shown below. The drawing will show
selection is made from the local YORK sales office. the isolator locations along with the weight in pounds
Be aware, weights may change with each option along and kilograms at the specific location, isolator position,
with possible isolator changes. Weights and isolators and location measurements for each isolator.
may need to be recalculated when the option selections
are changed.
ISOLATOR LOCATIONS

Order No: 069528190101 kg lbs


Line No: 1
Unit Shipping Wt.
(Display on unit data
5
nameplate) 617 1361

L2 R2

Y L1 R1
CONTROL
PANEL END

C
G X

X D I S T A N C E Y D I S T A N C E OPERATING WEIGHT
LOCATION VENDOR NUMBER
INCHES / MM INCHES / MM LBS / (kg)

R1 43.22 (1097.8) 4.94 (125.5) CIP-B-450 / RED 276 (125.2)


L1 1.09 (27.7) 4.94 (125.5 CIP-B-450 / RED 284 (128.8)
R2 43.22 (1097.8) 92.25 (2343.2) CIP-B-276750 / WHITE 407 (184.6)
(189.6)L2 1.09 (27.7) 92.25 2343.2) CIP-B-750 / WHITE 418 (189.6)

“SAMPLE PRINTOUT” TYPICAL OF THE INFORMATION SUPPLIED IN THE ISOLATOR PACKAGE AND IN THE CHILLER
PANEL LITERATURE PACKET

JOHNSON CONTROLS 107


Technical Data
FORM 150.67-NM1 (308)

ISOLATOR SELECTION
YCAL0019 – 0033 (WITHOUT PUMP PACKAGE OPTION)

Standard Aluminum Condenser Fins Optional Copper Condenser Fins


Location L1 L2 R1 R2 L1 L2 R1 R2

1” Deflection CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750

YCAL0019 Neoprene ND-C ND-C ND-C ND-C ND-C ND-C ND-C ND-C
SLRS- SLRS- SLRS- SLRS- SLRS- SLRS-2- SLRS-2- SLRS-
Seismic
2-C2-420 2-C2-660 2-C2-420 2-C2-660 2-C2-420 C2-660 C2-420 2-C2-660

1” Deflection CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750

YCAL0022 Neoprene ND-C ND-C ND-C ND-C ND-C ND-C ND-C ND-C
SLRS- SLRS- SLRS- SLRS- SLRS-2 SLRS-2- SLRS-2- SLRS-2-
Seismic
2-C2-420 2-C2-660 2-C2-420 2-C2-660 -C2-520 C2-660 C2-520 C2-660
CIP-B-
1” Deflection CIP-B-450 CIP-B-1000 CIP-B-450 CIP-B-750 CIP-B-1000 CIP-B-750 CIP-B-1000
1000

YCAL0033 Neoprene ND-C ND-C ND-C ND-C ND-C ND-C ND-C ND-C

SLRS- SLRS- SLRS- SLRS- SLRS- SLRS-2- SLRS-2- SLRS-2-


Seismic
2-C2-520 2-C2-920 2-C2-520 2-C2-920 2-C2-520 C2-920 C2-520 C2-920

NOTE: Isolators are selected using a service factor.

YCAL0019, 0022, 0033


L1 L2

CONTROL
PANEL
END

R1 R2

SAMPLE

108 JOHNSON CONTROLS


FORM 150.67-NM1 (308)
ISOLATORS
WEIGHT DISTRIBUTION AND ISOLATOR MOUNTING POSITIONS
YCAL0043 – 0066

GENERAL

Weights of specific chiller models vary significantly as Whenever the isolator option is ordered, the isolators
options are added. As a result, total weights, weights at will be shipped loose with the chiller. Packed with the
individual isolator positions, and actual isolator selection isolators and also in the control panel information packet
at each position cannot be published due to the vast is a drawing and table specifically for each chiller, based
number of possible combinations. This information will on the option selection. The drawing and table will be
be available when the specific chiller/ option selection similar to the ones shown below. The drawing will show
is made from the local YORK sales office. Be aware, the isolator locations along with the weight in pounds
weights will change with each option along with possible and kilograms at the specific location, isolator position,
isolator changes. Weights and isolators may need to be and location measurements for each isolator.
recalculated when the option selections are changed.

Approximate Isolator Locations


Order No: 051138540701 Unit Shipping kg lbs.
Line No: 1 Weight 5
(Display on unit
1564 3448
data nameplate)

L2 R2

0
L1 R1
TOP VIEW
0
Y

Location X Distance Y Distance Vendor Number Operating Weight


inches (mm) inches (mm)
R1 135.01 (3429.3) 1.09 (27.7) CIP-B-1000 / Blue 726 (329.3)
L1 9.79 (248.7) 1.09 (27.7) CIP- B-1650 / Black 1113 (504.9)
R2 135.01 (3429.3) 89.16 (2264.7) CIP-B-1000 / Blue 648 (293.9)
L2 9.79 (248.7) 89.16 (2264.7) CIP-B- 1250 / Gray 993 (450.4)
SAMPLE PRINTOUT SUPPLIED IN THE ISOLATOR PACKAGE AND IN THE CHILLER PANEL LITERATURE PACKET.

JOHNSON CONTROLS 109


Technical Data
FORM 150.67-NM1 (308)

NEOPRENE ISOLATOR CROSS-REFERENCE

ND-X

"CS" Cap Screw

Steel Plate - Top & "MBD" Max. Bolt Dia.


Bottom Neoprene
covered to prevent
corrosion

BC
H L

W
T

ENGLISH (Inches)
Size D H L T W BC CS MBD
ND-C 2-9/16 2-3/ 4 5-1/ 2 1/4 2-5/16 4-1/8 1/2-13 x 1 1/ 2
ND-D 3-3/8 2-3/4 6-1/4 5/16 4 5 1/2-13 x 1 1/ 2
ND-DS 3-3/8 2-3/4 6-1/4 5/16 4 5 1/2-13 x 1 1/ 2

SI (mm)
ND-C 65.1 69.9 139.7 6.4 58.7 101.9 1/2- 13 x 1” 12.7
ND-D 85.7 69.9 158.8 7.9 101.6 127.0 1/2- 13 x 1” 12.7
ND-DS 85.7 69.9 158.8 7.9 101.6 127.0 1/2- 13 x 1” 12.7

Weight Range Weight Range


Model Number Color YORK P/N
(lbs) (kg)
Up to 751 lbs Up to 341 kg ND-C Yellow 029-24584-001
751 to 1651 lbs 341 to 749 kg ND-D Yellow 029-24584-002
1651 to 3226 lbs 749 to 1463 kg ND-DS Yellow 029-24584-004

110 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

ISOLATOR SELECTION
YCAL0019 – 0033 (WITHOUT PUMP PACKAGE OPTION)

Standard Aluminum Condenser Fins Optional Copper Condenser Fins


Location L1 L2 R1 R2 L1 L2 R1 R2

1” Deflection CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750

YCAL0019 Neoprene ND-C ND-C ND-C ND-C ND-C ND-C ND-C ND-C
SLRS- SLRS- SLRS- SLRS- SLRS- SLRS-2- SLRS-2- SLRS-
Seismic
2-C2-420 2-C2-660 2-C2-420 2-C2-660 2-C2-420 C2-660 C2-420 2-C2-660

1” Deflection CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750 CIP-B-450 CIP-B-750

YCAL0022 Neoprene ND-C ND-C ND-C ND-C ND-C ND-C ND-C ND-C
SLRS- SLRS- SLRS- SLRS- SLRS-2 SLRS-2- SLRS-2- SLRS-2-
Seismic
2-C2-420 2-C2-660 2-C2-420 2-C2-660 -C2-520 C2-660 C2-520 C2-660
CIP-B-
1” Deflection CIP-B-450 CIP-B-1000 CIP-B-450 CIP-B-750 CIP-B-1000 CIP-B-750 CIP-B-1000
1000

YCAL0033 Neoprene ND-C ND-C ND-C ND-C ND-C ND-C ND-C ND-C

SLRS- SLRS- SLRS- SLRS- SLRS- SLRS-2- SLRS-2- SLRS-2-


Seismic
2-C2-520 2-C2-920 2-C2-520 2-C2-920 2-C2-520 C2-920 C2-520 C2-920
5
NOTE: iIsolators are selected using a serevice factor.

YCAL0019, 0022, 0033


L1 L2

CONTROL
PANEL
END

R1 R2

SAMPLE - ISOLATOR LOCATIONS

JOHNSON CONTROLS 111


Technical Data
FORM 150.67-NM1 (308)

ONE INCH DEFLECTION SPRING ISOLATOR CROSS-REFERENCE

CIP-X-

Illustration shows single spring CIP-B or CIP-C mount.

EQUIPMENT BASE Mounting may be


A operated 1/2" above
Free & Operating
Dowel Pin is 3/8" dia. for Height.
CIP-A & 1/2" thereafter
NOTE-
FERROUS HOUSING
CIP Mounts are not
to be used in seismic
SIDE ACCESS INTERNAL or wind load
ADJUSTMENT BOLT applications. TYPE CIP DIMENSIONS (inches)†
Turn clockwise to load
spring and maintain Free Free Min
& Operating Height. Size A L T W SW HCL HCW MBD SBC Ht. Ht.
FREE & CIP-B 5 3/ 4 8 1/4 1/ 2 2 3/4 7/ 16 6 1/2 11/2 3 /8 7 1/4 61/8 5 1/4
OPERATING CIP-C 6 5/ 8 8 7/8 9/ 16 3 1/2 7/ 16 7 1/4 13/4 3/ 8 7 7/8 63/4 6 3/4
HEIGHT

NON-SKID NEOPRENE †Casting dimensions may vary ±1/8"


ACOUSTICAL ISOLATION PAD L
(Bolting to floor is not necessary for
indoor applications)
T
W

SBC
HCL
MAX BOLT
DIA. - MBD

Slot Width - SW
All springs have additional
HCW
travel to solid equal to 50%
of the rated deflection.

BASE PLATE DIMENSIONS

FOR UNITS WITH ALL POINT LOADS LESS THAN 1404 LBS (637 KG)
Weight Range (lbs) Weight Range (kg) Model Number Color YORK P/N
239 to 384 lbs 108 to 174 kg CIP-B- Red 029-24583-002
384 to 639 lbs 174 to 290 kg CIP-B- White 029-24583-003
639 to 851 lbs 290 to 386 kg CIP-B- Blue 029-24583-004
851 to 1064 lbs 386 to 483 kg CIP-B- Gray 029-24583-005
1064 to 1404 lbs 483 to 637 kg CIP-B- Black 029-24583-006

FOR UNITS WITH ANY POINT LOAD ABOVE 1404 LBS (637 KG)
Weight Range (lbs) Weight Range (kg) Model Number Color YORK P/N
Up to 851 lbs Up to 386 kg CIP-C- Black 029-24583-007
851 to 1149 lbs 386 to 521 kg CIP-C- Yellow 029-24583-008
1149 to 1489 lbs 521 to 675 kg CIP-C- Red w/Black 029-24583-009
Yellow w/
1489 to 1786 lbs 675 to 910 kg CIP-C- 029-24583-010
Red
Green w/
1786 to 2028 lbs 910 to 920 kg CIP-C- 029-24583-011
Yellow
2028 to 2254 lbs 920 to 1022 kg CIP-C- Red w/ Red 029-24583-012
2254 to 2936 lbs 1022 to 1332 kg CIP-C- Green w/ Red 029-24583-013

112 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

INSTALLATION OF 1" DEFLECTION MOUNTS

1. Floor or steel frame should be level and smooth. 5. Complete piping and fill equipment with water,
refrigerant, etc.
2. For pad installations, isolators do not normally
require bolting. If necessary, anchor isolators to 6. Turn leveling bolt of first isolator four full revolu-
floor through bolt holes in the base plate. tions and proceed to each mount in turn.

Isolators must be bolted to the sub-


7. Continue turning leveling bolts until the equipment
structure and the equipment must be
is fully supported by all mountings and the equip-
bolted to the isolators when outdoor ment is raised free of the spacer blocks or shims.
equipment is exposed to wind forces. Remove the blocks or shims.

8. Turn the leveling bolt of all mountings in either


3. Lubricate the threads of adjusting bolt. Loosen the
direction in order to level the installation.
hold down bolts to allow for isolator adjustment.

9. Tighten the nuts on hold down bolts to permit a


4. Block the equipment 10mm (1/4”) higher than
clearance of 2mm (1/8”) between resilient washer
the specified free height of the isolator. To use
and underside of channel cap plate.
the isolator as blocking for the equipment, insert
a 10mm (1/4”) shim between the upper load plate
5
and vertical uprights. Lower the equipment on the 10. Installation is now complete.
blocking or shimmed isolators.

JOHNSON CONTROLS 113


Technical Data
FORM 150.67-NM1 (308)

NEOPRENE ISOLATOR CROSS-REFERENCE

ND-X

"CS" Cap Screw

Steel Plate - Top & "MBD" Max. Bolt Dia.


Bottom Neoprene
covered to prevent
corrosion

BC
H L

W
T

ENGLISH (Inches)
Size D H L T W BC CS MBD
ND-C 2-9/16 2-3/ 4 5-1/ 2 1/4 2-5/16 4-1/8 1/2-13 x 1 1/ 2
ND-D 3-3/8 2-3/4 6-1/4 5/16 4 5 1/2-13 x 1 1/ 2
ND-DS 3-3/8 2-3/4 6-1/4 5/16 4 5 1/2-13 x 1 1/ 2

SI (mm)
ND-C 65.1 69.9 139.7 6.4 58.7 101.9 1/2- 13 x 1” 12.7
ND-D 85.7 69.9 158.8 7.9 101.6 127.0 1/2- 13 x 1” 12.7
ND-DS 85.7 69.9 158.8 7.9 101.6 127.0 1/2- 13 x 1” 12.7

Weight Range Weight Range


Model Number Color YORK P/N
(lbs) (kg)
Up to 751 lbs Up to 341 kg ND-C Yellow 029-24584-001
751 to 1651 lbs 341 to 749 kg ND-D Yellow 029-24584-002
1651 to 3226 lbs 749 to 1463 kg ND-DS Yellow 029-24584-004

114 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

TWO INCH DEFLECTION, SEISMIC SPRING ISOLATOR CROSS-REFERENCE


SLRS
SLRS-2-C2 has 2 springs.
"D" Tap - 4 Holes unless
otherwise requested
E
Vertical Limit E E
Stops-Out of
contact during E
normal operation
H
MBD -Max
Bolt
Diameter
Rubber
Snubbing T
Collar

HCL Adjustment
HCW L Bolt 5
W

Non-Skid Neoprene Pad-


Lower Internal
Enclosed Neoprene Pad can be removed if
Restraining Steel mounts are welded
Nut Acoustical into position.
Housing Pad
NOTES: Illustration above shows a SLRS-4-C2 (4 springs). SLRS-8-2 & C2 have 1 spring, and SLRS-2-C2 has two springs.
SLRS-6-C2 has six springs and SLRS-9-C2 has nine springs.

ENGLISH
SIZE H T D E L HCL W HCW MBD
2-C2 8-1/2” 3/8” 5/8” 1-3/8” 14” 12-1/4” 5-1/4” 3-1/ 2” 5/8"

SI
SIZE H T D E L HCL W HCW MBD
2-C2 215.9 9.5 15.9 34.9 355.6 311.2 133.4 88.9 5/8"

*Weight Range Weight Range


Model Number Color YORK P/N
(lbs) (kg)
Up to 358 lbs Up to 162 kg SLRS-2-C2- Red 029-24585-006
358 to 443 lbs 162 to 201 kg SLRS-2-C2- White 029-24585-007
443 to 582 lbs 201 to 264 kg SLRS-2-C2- Black 029-24585-008
582 to 783 lbs 264 to 335 kg SLRS-2-C2- Blue 029-24585-009
783 to 1038 lbs 335 to 471 kg SLRS-2-C2- Green 029-24585-010
1038 to 1497 lbs 471 to 679 kg SLRS-2-C2- Gray 029-24585-011
1497 to 2058 lbs 679 to 933 kg SLRS-2-C2- Silver 029-24585-012
2058 to 2619 lbs 933 to 1188 kg SLRS-2-C2- Gray w/ red 029-24585-013
2619 to 3180 lbs 1188 to 1442 kg SLRS-2-C2- Silver w/ red 029-24585-014
*Value is de-rated by 15%

JOHNSON CONTROLS 115


Technical Data
FORM 150.67-NM1 (308)

SLRS SEISMIC ISOLATOR INSTALLATION AND ADJUSTMENT

TO INSTALL AND ADJUST MOUNTS

1. Supports for mountings must be leveled to installation's acceptable tolerances.


2. Mountings not subjected to seismic or wind forces do not require bolting to supports.
3. Mountings subjected to seismic or wind forces must be bolted or welded in position.
4. If mountings are welded in position, remove lower friction pad before welding.
5. Set mountings with top channels held in place by the lower restraining nuts and limit stops.
6. Place equipment on mountings and secure by bolting or welding.
7. Hold lower restraining nut in place and turn vertical limit stop bolt counter-clockwise until there is a 1/8" gap
between the bolt head and the steel washer.
8. Turn adjustment bolt 8 turns on each mount.
9. Take one additional complete turn on each adjustment bolt in sequence until the top plate lifts off of the lower
restraining nuts. Take no additional turns on that mount. Continue with equal turns on the other mounts until
the top plates lift off of the lower restraining nuts of all mounts.
10. Hold the limit stop bolt in place and turn the lower restraining nut clockwise and tighten it against the stanchion.
Repeat the same procedure on all mounts.
11. Top plate should remain at a fixed elevation, plus or minus 1/8".

"D" Tap - 4 Holes unless


otherwise requested
Vertical Limit
Stops-Out of
contact during LIMIT STOP
normal operation BOLT

MBD -Max 1/8"


Bolt
Diameter LOWER
Rubber RESTRAINING
Snubbing BOLTS
Collar
1/4"

Adjustment
Bolt

Non-Skid Neoprene Pad-


Lower Internal
Enclosed Neoprene Pad can be removed if
Restraining Steel mounts are welded SHIPPED & INSTALLED AFTER ADJUSTMENT
Nut Acoustical into position.
Housing Pad

LD10568

116 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

SECTION 6 – COMMISSIONING

COMMISSIONING Compressor Oil


To add oil to a circuit – connect a YORK hand oil
Commissioning of this unit should pump (Part No. 470-10654-000) to the 1/4” oil
only be carried out by YORK Autho- charging connection on the compressors with a length
rized personnel. of clean hose or copper line, but do not tighten the
flare nut. Using clean oil of the correct type (“T” oil),
pump oil until all air has been purged from the hose
then tighten the nut. Stroke the oil pump to add oil
to the oil system. Approximately 1.8-2.3 gallons is
Commissioning personnel should be thoroughly present in the each refrigerant system. Oil levels in
familiar with the information contained in this the oil equalizing line sight glass should be between
literature, in addition to this section. the bottom and the middle of the sight glass with the
system off. High oil levels may cause excessive oil
Perform the commissioning using the detailed checks carryover in the system. High oil concentration in
outlined in the EQUIPMENT START-UP CHECK the system may cause nuisance trips resulting from
LIST (Page 119) as the commissioning procedure is incorrect readings on the level sensor and temperature
carried out. sensors. Temperature sensor errors may result in
poor liquid control and resultant liquid overfeed
PREPARATION – POWER OFF and subsequent damage to the compressor. While
The following basic checks should be made with the running, a visible sign of oil splashing in the sight
customer power to the unit switched OFF. glass is normal.

Inspection Fans

Inspect unit for installation damage. If found, take Check that all fans are free to rotate and are not 6
action and/or repair as appropriate. damaged. Ensure blades are at the same height when
rotated. Ensure fan guards are securely fixed.
Refrigerant Charge
Isolation / Protection
Packaged units are normally shipped as standard
with a full refrigerant operating charge. Check that Verify all sources of electrical supply to the unit are
refrigerant pressure is present in both systems and taken from a single point of isolation. Check that
that no leaks are apparent. If no pressure is present, a the maximum recommended fuse sizes given in the
leak test must be undertaken, the leak(s) located and Technical Data Section has not been exceeded.
repaired. Remote systems and units are supplied with
a nitrogen holding charge. These systems must be Control Panel
evacuated with a suitable vacuum pump/recovery unit Check the panel to see that it is free of foreign
as appropriate to below 500 microns. materials (wire, metal chips, etc.) and clean out if
required.
Do not liquid charge with static water in the cooler.
Care must also be taken to liquid charge slowly to Power Connections
avoid excessive thermal stress at the charging point.
Once the vacuum is broken, charge into the condenser Check that the customer power cables are connected
coils with the full operating charge as given in the correctly to the terminal blocks or optional circuit
Technical Data Section. breaker. Ensure that connections of power cables
within the panels to the circuit breaker or terminal
Service and Oil Line Valves blocks are tight.
Open each compressor suction, economizer, and Grounding
discharge service valve. If valves are of the back-seat
type, open them fully (counterclockwise) then close Verify that the unit’s protective ground terminal(s)
one turn of the stem to ensure operating pressure are properly connected to a suitable grounding point.
is fed to pressure transducers. Open the liquid line Ensure that all unit internal ground connections are
service valve and oil return line ball valve fully in tight.
each system.

JOHNSON CONTROLS 117


Commissioning
FORM 150.67-NM1 (308)

Supply Voltage Flow rates and pressure drops must be within the
Verify that the site voltage supply corresponds to the limits given in the Technical Data Section. Operation
unit requirement and is within the limits given in the outside of these limits is undesirable and could cause
Technical Data Section. damage.

PREPARATION – POWER ON If mains power must be switched OFF for extended


maintenance or an extended shutdown period, the
compressor suction, discharge and economizer service
Perform the commissioning using the
stop valves should be closed (clockwise). If there is
detailed checks outlined in the EQUIP-
a possibility of liquid freezing due to low ambient
MENT START-UP CHECK SHEET temperatures, the coolers should be drained or power
as the commissioning procedure is should be applied to the chiller. This will allow the
carried out. cooler heater to protect the cooler from freezing down
to –20 °F. Before placing the unit back in service,
Apply power to the chiller. Turn ON the option panel valves should be opened and power must be switched
circuit breaker if supplied. on (if power is removed for more than 8 hours) for
at least 8 hours (24 hours if ambient temperature is
The machine is now live! below 86 °F [30 °C]) before the unit is restarted.

Flow Switch
Verify a chilled water flow switch is correctly fitted in
the customer’s piping on the cooler outlet, and wired
Switch Settings into the control panel correctly using shielded cable.

\Assure the chiller OFF/ON UNIT switch at the There should be a straight run of at least 5 pipe
bottom of the keypad is OFF. Place the optional diameters on either side of the flow switch. The flow
circuit breaker handle on the panel door to ON. The switch should be connected to terminals 2 and 13 in
customer’s disconnection devices can now be set to the panel.
ON.
Temperature Sensor(s)
Verify the control panel display is illuminated. Assure
Ensure the leaving liquid temperature sensor is coated
the system switches under the SYSTEM SWITCHES
with heat conductive compound (Part No. 013-00890-
Key are in the OFF position.
000) and is inserted to the bottom of the water outlet
Compressor Heaters sensor well in the cooler. This sensor also provides
some freeze protection and must always be fully
\Verify the compressor heaters are energized. If inserted in the water outlet sensor well.
the ambient temperature is above 96 °F (36 °C) the
compressor heaters must be on for at least 8 hours
before start-up to ensure all refrigerant liquid is driven
out of the compressor and the oil. If the ambient
temperature is below 86 °F (30 °C), allow 24 hours.

Water System
Verify the chilled liquid system has been installed
correctly, and has been commissioned with the correct
direction of water flow through the cooler. The inlet
should be at the refrigerant piping connection end of
the cooler. Purge air from the top of the cooler using
the plugged air vent mounted on the top of the cooler
body.

118 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

EQUIPMENT STARTUP CHECKLIST

JOB NAME: ______________________________  7. Check the control panel to ensure it is free of


foreign material (wires, metal chips, etc.).
SALES ORDER #: _________________________
 8. Visually inspect wiring (power and control). Wir-
LOCATION: ______________________________ ing MUST meet N.E.C. and local codes.
SOLD BY: ________________________________  9. Check tightness of power wiring inside the power
INSTALLING panel on both sides of the motor contactors and
CONTRACTOR: ___________________________ overloads.
START-UP 10. Check for proper size fuses in main and control
TECHNICIAN/ circuits, and verify overload setting corresponds
COMPANY: _______________________________ with RLA and FLA values in electrical tables.
11. Assure 120VAC Control Power to TB1 has 15
START-UP DATE : _________________________
amp minimum capacity.
 12. Be certain all water temp sensors are inserted
CHILLER MODEL #: _______________________ completely in their respective wells and are coated
SERIAL #: ______________________________ with heat conductive compound.
13. Assure that evaporator TXV bulbs are strapped
onto the suction lines at 4 or 8 o’clock positions
CHECKING THE SYSTEM or suction temp. sensors if EEVs are installed.
PRIOR TO INITIAL START (NO POWER)
COMPRESSOR HEATERS
Unit Checks (POWER ON – 24 HOURS PRIOR TO START) 6
 1. Inspect the unit for shipping or installation dam-
age.  1. Apply 120VAC and verify its value between ter-
 2. Assure that all piping has been completed. minals 5 and 2 of CTB2. The voltage should be
 3. Visually check for refrigerant piping leaks. 120VAC +/- 10%.
 4. Open suction line ball valve, discharge line ball Power must be applied 24 hours prior to
valve, and liquid line valve for each system. start-up.
 5. The compressor oil level should be maintained Each heater should draw approximately 0.5-1A.
so that an oil level is visible or splashing in the
sight glass when fully loaded. At shutdown, the
oil level should be between the bottom and middle PANEL CHECKS
of the oil equalizing sight glass. (POWER ON – BOTH UNIT SWITCH OFF)
 6. Assure water pumps are on. Check and adjust
water pump flow rate and pressure drop across  1. Apply 3-phase power and verify its value. Volt-
the cooler (see OPERATIONAL LIMITATIONS). age imbalance should be no more than 2% of the
Verify flow switch operation. average voltage.
 2. Apply 120VAC and verify its value on the terminal
Excessive flow may cause catastrophic block in the Power Panel. Make the measurement
damage to the heat exchanger (evapo- between terminals 5 and 2 of CTB2. The voltage
rator). should be 120VAC +/- 10%.
 3. Program/verify the Cooling Setpoints, Program
Setpoints, and unit Options. Record the values be-
low (see sections on Setpoints and Unit Keys for
programming instruction) in Table 9.

JOHNSON CONTROLS 119


Commissioning
FORM 150.67-NM1 (308)

TABLE 9 – SETPOINTS ENTRY LIST The chilled liquid setpoint may need
OPTIONS to be temporarily lowered to ensure
Display Language all compressors cycle “on.”
Sys 1 Switch
Sys 2 Switch
Chilled Liquid
* Ambient Control
Local/Remote Mode
Control Mode
Display Units
* Lead/Lag Control This unit uses scroll compressors
* Fan Control which can only operate in one direc-
Manual Override tion. Failure to observe this will lead
Current Feedback
** Soft Start
to compressor failure.
** Unit Type
** Refrigerant Type
** Expansion Valve Type
COOLING SETPOINTS  6. YCAL0043 – YCAL0066 units only – Turn sys-
Cooling Setpoint tem 1 “OFF” and system 2 “ON” (refer to Option
Range
2 under “UNIT KEYS” section for more informa-
EMS-PWM Max. Setpoint
PROGRAM
tion on system switches).
Discharge Pressure Cutout
Suct. Pressure Cutout Place the Unit Switch in the control panel to the
Low Amb. Temp. Cutout
“ON” position. As each compressor cycles “ON”,
Leaving Liquid Temp. Cutout
Anti-Recycle Time ensure that the discharge pressure rises and the
Fan Control On Pressure suction pressure decreases. If this does not oc-
Fan Differential Off Pressure cur, the compressor being tested is operating in
Total # of Compressors the reverse direction and must be corrected. After
* Number of Fans/System verifying proper compressor rotation, turn the
* Unit/Sys Voltage
Unit Switch to “OFF”.
Unit ID

* NOT ON ALL MODELS The chilled liquid setpoint may need


** VIEWABLE ONLY
to be temporarily lowered to ensure all
 4. Put the unit into Service Mode (as described under compressors cycle “ON”.
the Control Service and Troubleshooting section)
and cycle each condenser fan to ensure proper
rotation.
 5. Prior to this step, turn system 2 off (if applicable
–refer to Option 2 under “Unit Keys” section for
more information on system switches). Connect a
manifold gauge to system 1 suction and discharge
service valves.
Place the Unit Switch in the control panel to the
“ON” position. As each compressor cycles on,
ensure that the discharge pressure rises and the
suction pressure decreases. If this does not oc-
cur, the compressor being tested is operating in
the reverse direction and must be corrected. After
verifying proper compressor rotation, turn the
Unit Switch to “OFF.”

120 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

CHECKING SUPERHEAT AND SUBCOOLING Assure that superheat is set at a minimum of 10 °F (5.56
The subcooling temperature of each system can be °C) with a single compressor running on each circuit.
calculated by recording the temperature of the liquid
line at the outlet of the condenser and subtracting it from  2. Record the suction temperature, suction pressure,
the liquid line saturation temperature at the liquid stop suction saturation temperature, and superheat of
valve (liquid line saturation temp. is converted from a each system below:
temperature/pressure chart).
Example: SYS 1 SYS 2
Liquid line pressure = Suction Temp = _______ _______ °F
325 PSIG converted to temp. 101 °F Suction Pressure = _______ _______ PSIG
minus liquid line temp. - 86 °F
Saturation Temp = _______ _______ °F
Subcooling = 15 °F
Superheat = _______ _______ °F
The subcooling should be adjusted to 15 °F at design
LEAK CHECKING
conditions.
 1. Leak check compressors, fittings, and piping to
 1. Record the liquid line pressure and its correspond- ensure no leaks.
ing temperature, liquid line temperature and
subcooling below: If the unit is functioning satisfactorily during the initial
operating period, no safeties trip and the compressors
SYS 1 SYS 2 cycle to control water temperature to setpoint, the chiller
Liq Line Press = _______ _______ PSIG is ready to be placed into operation.
Saturated Temp = _______ _______ °F
Liq Line Temp = _______ _______ °F
Subcooling = _______ _______ °F
6
After the subcooling is verified, the suction superheat
should be checked. The superheat should be checked
only after steady state operation of the chiller has been
established, the leaving water temperature has been pulled
down to the required leaving water temperature, and the
unit is running in a fully loaded condition. Correct superheat
setting for a system is 10 °F – 15 °F (5.56 °C – 8.33 °C)
18” (46 cm) from the heat exchanger.

Superheat should typically be set for no less than 10


°F with only a single compressor running on a circuit.
The superheat is calculated as the difference between the
actual temperature of the returned refrigerant gas in the
suction line entering the compressor and the temperature
corresponding to the suction pressure as shown in a
standard pressure/temperature chart.
Example:
Suction Temp = 46 °F
minus Suction Press
105 PSIG converted to Temp - 34 °F
Superheat = 12 °F

When adjusting the expansion valve (TXV only), the


adjusting screw should be turned not more than one
turn at a time, allowing sufficient time (approximately
15 minutes) between adjustments for the system and the
thermal expansion valve to respond and stabilize.

JOHNSON CONTROLS 121


Commissioning
FORM 150.67-NM1 (308)

UNIT OPERATING SEQUENCE


The operating sequence described below relates to 4. Several seconds after the compressor starts, that
operation on a hot water start after power has been systems first condenser fan will be cycled on (out-
applied, such as start-up commissioning. When a door air temperature > 25 °F (-4 °C) or discharge
compressor starts, internal timers limit the minimum pressure). See the section on Operating Controls
time before another compressor can start to 1 minute. for details concerning condenser fan cycling.

1. For the chiller system to run, the Flow Switch must 5. After 1 minute of compressor run time, the next
be closed, any remote cycling contacts must be compressor in sequence will start when a system
closed, the Daily Schedule must not be scheduling has to load. Additional compressors will be started
the chiller off, and temperature demand must be at 60 second intervals as needed to satisfy tempera-
present. ture setpoint.

2. When power is applied to the system, the micropro- 6. If demand requires, the lag system will cycle
cessor will start a 2 minute timer. This is the same on with the same timing sequences as the lead
timer that prevents an instantaneous start after a system after the lead system has run for five min-
power failure. utes. Refer to the section on Capacity Control for
a detailed explanation of system and compressor
3. At the end of the 2 minute timer, the microproces- staging.
sor will check for cooling demand. If all conditions
allow for start, a compressor on the lead system 7. As the load decreases below setpoint, the compres-
will start and the liquid line solenoid will open. sors will be shut down in sequence. This will occur
Coincident with the start, the anti-coincident timer at intervals of either 60, 30, or 20 seconds based
will be set and begin counting downward from “60” on water temperature as compared to setpoint, and
seconds to “0” seconds. control mode. See the section on Capacity Control
for a detailed explanation.
If the unit is programmed for Auto Lead/Lag, the
system with the shortest average run-time of the 8. When the last compressor in a “system” (two or
compressors will be assigned as the “lead” system. three compressors per system), is to be cycled
A new lead/lag assignment is made whenever all off, the system will initiate a pump-down. Each
systems shut down. “system” has a pump-down feature upon shut-off.
On a non-safety, non-unit switch shutdown, the
LLSV will be turned off and the last compressor
will be allowed to run until the suction pressure
falls below the suction pressure cutout or for 180
seconds, whichever comes first.

122 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

SECTION 7 – UNIT CONTROLS


YORK MILLENNIUM CONTROL CENTER

00065VIP

INTRODUCTION IPU II and I/O Boards

The YORK MicroComputer Control Center is a The IPU and I/O boards are assembled to function as a
microprocessor based control system designed to provide single microprocessor controller requiring no additional
the entire control for the liquid chiller. The control logic hardware. The IPU II board contains a coldfire
embedded in the microprocessor based control system microprocessor and is the controller and decision
will provide control for the chilled liquid temperatures, maker in the control panel. The I/O board handles all
as well as sequencing, system safeties, displaying status, of the chiller I/O (Inputs and Outputs). System inputs
and daily schedules. The MicroComputer Control Center from pressure transducers and temperature sensors are
consists of four basic components, 1) IPU II & I/O connected to the I/O board. The I/O board contains a
Boards, 2) transformer, 3) display and 4) keypad. The processor capable of reading the inputs and controlling
keypad allows programming and accessing setpoints, the outputs. It communicates through the transition
pressures, temperatures, cutouts, daily schedule, options, header with the IPU II microprocessor. 7
and fault information.
The I/O board circuitry multiplexes the analog inputs,
Remote cycling, demand limiting and chilled liquid digitizes them, and constantly scans them to keep watch
temperature reset can be accomplished by field supplied on the chiller operating conditions. The input values are
contacts. transmitted serially to the IPU II microprocessor board.
From this information, the IPU II then issues commands
Compressor starting/stopping and loading/unloading to the I/O board relay outputs to control contactors,
decisions are performed by the Microprocessor to solenoids, etc. for Chilled Liquid Temperature Control
maintain leaving or return chilled liquid temperature. and to react to safety conditions. The I/O board
These decisions are a function of temperature deviation converts logic signals to operate relay outputs to 115
from setpoint. VAC levels used by motor contactors, fan contactors,
solenoid valves, etc. to control system operation. The
A Master ON/Off switch is available to activate or low voltage side of all relay coils on the I/O board are
deactivate the unit. powered by +12V.

Keypad commands are actuated upon by the


microprocessor to change setpoints, cutouts, scheduling,
operating requirements, and to provide displays. The
keypad and display are connected to the I/O board.

The on-board power supply converts 24 VAC from


75 VA, 120/24 VAC 50/60Hz UL listed class 2 power
transformer to +12V, +5V and +3.3V using switching

JOHNSON CONTROLS 123


Unit Controls
FORM 150.67-NM1 (308)

and linear voltage regulators located on the I/O and IPU Display Messages may show characters indicating
II boards. These voltages are used to operate integrated “greater than” (>) or “less than” (<). These characters
circuitry on the board. The 40 character display and indicate the actual values are greater than or less than
unit sensors (transducers and temp sensors) are supplied the limit values which are being displayed.
power for the micro board +5V supply. 24V AC is
rectified, but not regulated, to provide unregulated +30 Keypad
VDC to supply all of the digital inputs. The 12 button non-tactile keypad allows the user
to retrieve vitals system parameters such as system
The IPU II board contains one green “Power” LED
pressures, temperatures, compressor running times
to indicate that the board is powered up and one red
and starts, option information on the chiller, and
“Status” LED to indicate by blinking that the processor
system setpoints. This data is useful for monitoring
is operating.
chiller operation, diagnosing potential problems,
troubleshooting, and commissioning the chiller.
The I/O board contains one green “Power” LED to
indicate that the board is powered up and one red
It is essential the user become familiar with the use of the
“Status” LED to indicate by blinking that the processor
keypad and display. This will allow the user to make full
is operating. The I/O board also contains two sets of
use of the capabilities and diagnostic features available.
Receiver/Transmit LED’s, one for each available serial
communication port. The receive LED’s are green, and
Battery Back-up
the Transmit LED’s are red.
The IPU II contains a Real Time Clock integrated circuit
A jumper on the I/O board selects 4-20mA or 0-10 chip with an internal battery backup. The purpose of
VDC as the input type on the remote temperature reset this battery backup is to assure any programmed values
analog input. (setpoints, clock, cutouts, etc.) are not lost during a
power failure regardless of the time involved in a power
cut or shutdown period.
Unit Switch
A unit ON/OFF switch is just underneath the keypad. Transformer
This switch allows the operator to turn the entire unit A 75 VA, 120/24VAC 50/60Hz transformer is provided
“OFF” if desired. The switch must be placed in the “ON” to supply power to the Microprocessor Board, which in
position for the chiller to operate. turn rectifies, filters, and regulates as necessary to supply
power to the display, sensors, and transducers.
Display
The 40 Character Display (2 lines of 20 characters) Single System Select and Programming
# of Compressors
is a liquid crystal display used for displaying system
parameters and operator messages. The control software is common between single (1) and
dual (2) system units. A jumper is installed between
The display in conjunction with the keypad, allows the terminals 13 and 17 on the user terminal block to
operator to display system operating parameters as well configure a unit for a single system. Dual (2) system
as access programmed information already in memory. chillers do not have a jumper installed. The jumper is
The display has a lighted background for night viewing only checked by the micro on powerup.
and for viewing in direct sunlight.
The total number of compressors is programmable under
When a key is pressed, such as the OPER DATA key, the Program Key. Single (1) system chillers can have 2
system parameters will be displayed and will remain or 3 compressors. Dual (2) system chillers can have 4,
on the display until another key is pressed. The system 5, or 6 compressors.
parameters can be scrolled with the use of the ↑ (UP)
and ↓ (DOWN) arrow keys. The display will update all
information at a rate of about 1 a second.

124 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

“STATUS” KEY

00066VIP

R E MO T E C O N T R O L L E D
Unit Status S H U T D OWN
Pressing the STATUS key will enable the operator to
determine current chiller operating status. The messages The REMOTE CONTROLLED SHUTDOWN message
displayed will include running status, cooling demand, indicates that either an ISN system or RCC has turned
fault status, external cycling device status. The display the unit “OFF”, not allowing it to run.
will be a single message relating to the highest priority
message as determined by the micro. Status messages D A I L Y S C H E D U L E
fall into the categories of General Status and Fault S H U T D OWN
Status.

The following General, Safety, and Warning messages The DAILY SCHEDULE SHUTDOWN message
are displayed when the Status key is pressed. Following indicates that the daily/holiday schedule programmed
each displayed message is an explanation pertaining to is keeping the unit from running.
that particular message. REMOTE STOP 7
NO RUN PERM
General Status Messages
In the case of messages which apply to individual REMOTE STOP NO RUN PERM shows that either
systems, SYS 1 and SYS 2 messages will both be the flow switch is open or a remote start/stop contact is
displayed and may be different. In the case of single open in series with the flow switch. These contacts are
system units, all SYS 2 messages will be blank. connected to J13-5. A 3-second delay is built into the
software to prevent nuisance shutdowns due to erroneous
U N I T SW I T C H O F F signals on the run permissive input.
S H U T D OWN
S Y S 1 S Y S SW I T C H O F F
This message informs the operator that the UNIT switch S Y S 2 S Y S SW I T C H O F F
on the control panel is in the OFF position which will
not allow the unit to run. SYS SWITCH OFF tells that the system switch under
OPTIONS is turned “OFF”. The system will not be
allowed to run until the switch is turned back on.

JOHNSON CONTROLS 125


Unit Controls
FORM 150.67-NM1 (308)

S Y S 1 N O C O O L L O A D The limiting pressure is a factory set limit to keep the


S Y S 2 N O C O O L L O A D system from faulting on the high discharge pressure
cutout due to high load or pull down conditions. When
This message informs the operator that the chilled the unload point is reached, the micro will automatically
liquid temperature is below the point (determined by the unload the affected system by de energizing one
setpoint and control range) that the micro will bring on a compressor. The discharge pressure unload will occur
system or that the micro has not loaded the lead system when the discharge pressure gets within 10 PSIG (0.69
far enough into the loading sequence to be ready to bring barg) of the programmed discharge pressure cutout.
the lag system “ON”. The lag system will display this This will only happen if the system is fully loaded and
message until the loading sequence is ready for the lag will shut only one compressor off. If the system is not
system to start. fully loaded, discharge limiting will not go into effect.
Reloading the affected system will occur when the
S Y S 1 C OM P S R U N X discharge pressure drops to 85% of the unload pressure
S Y S 2 C OM P S R U N X and 10 minutes have elapsed.

S Y S 1 S U C T L I M I T I N G
The COMPS RUNNING message indicates that the S Y S 2 S U C T L I M I T I N G
respective system is running due to demand. The “X”
will be replaced with the number of compressors in that When this message appears, suction pressure limiting is
system that are running. in effect. The suction pressure limit is a control point that
limits the loading of a system when the suction pressure
S Y S 1 A R T I M E R X X S drops to within 15% above the suction pressure cutout.
S Y S 2 A R T I M E R X X S On a standard system programmed for 44 PSIG/3.0 Bar
suction pressure cutout, the micro would inhibit loading
The anti-recycle timer message shows the amount of of the affected system with the suction pressure less than
time left on the respective systems anti-recycle timer. or equal to 1.15 * 44 PSIG/3.0 Bar = 50 PSIG/3.5 Bar.
This message is displayed when the system is unable to The system will be allowed to load after 60 seconds
start due the anti-recycle timer being active. and after the suction pressure rises above the suction
pressure load limit point.
S Y S 1 A C T I M E R X X S
S Y S 2 A C T I M E R X X S S Y S 1 L O A D L I M I T X X %
S Y S 2 L O A D L I M I T X X %
The anti-coincidence timer is a software feature that
guards against 2 systems starting simultaneously. This This message indicates that load limiting is in effect and
assures instantaneous starting current does not become the percentage of the limiting in effect. This limiting
excessively high due to simultaneous starts. The micro could be due to the load limit/pwm input, ISN or RCC
limits the time between compressor starts to 1 minute controller sending a load limit command.
regardless of demand or the anti-recycle timer being
timed out. The anti-coincidence timer is only present M A N U A L
on two system units. O V E R R I D E

S Y S 1 D S C H L I M I T I N G If MANUAL OVERRIDE mode is selected, the STATUS


S Y S 2 D S C H L I M I T I N G display will display this message. This will indicate that
the Daily Schedule is being ignored and the chiller will
When this message appears, discharge pressure limiting start-up when chilled liquid temperature allows, Remote
is in effect. The Discharge Pressure Limiting feature Contacts, UNIT switch and SYSTEM switches permitting.
is integral to the standard software control; however This is a priority message and cannot be overridden by
the discharge transducer is optional on some models. anti-recycle messages, fault messages, etc. when in the
Therefore, it is important to keep in mind that this STATUS display mode. Therefore, do not expect to see
control will not function unless the discharge transducer any other STATUS messages when in the MANUAL
is installed in the system. OVERRIDE mode. MANUAL OVERRIDE is to only
be used in emergencies or for servicing. Manual override
mode automatically disables itself after 30 minutes.

126 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

S Y S 1 P U M P I N G D OWN S Y S 1 L OW S U C T P R E S S
S Y S 2 P U M P I N G D OWN S Y S 2 L OW S U C T P R E S S

The PUMPING DOWN message indicates that a The Suction Pressure Cutout is a software cutout that
compressor in the respective system is presently in the helps protect the chiller from an evaporator freeze-up
process of pumping the system down. When pumpdown should the system attempt to run with a low refrigerant
is initiated on shutdown, the liquid line solenoid or EEV charge or a restriction in the refrigerant circuit.
will close and a compressor will continue to run. When
the suction pressure decreases to the suction pressure Repeated starts after resetting a low
cutout setpoint or runs for 180 seconds, whichever suction pressure fault will cause evapo-
comes first, the compressor will cycle off. rator freeze-up. Whenever a system
locks out on this safety or any safety,
Fault Safety Status Messages
immediate steps should be taken to
Safety Status messages appear when safety thresholds identify the cause.
in the unit have been exceeded. Safeties are divided
into two categories – system safeties and unit safeties. At system start, the cutout is set to 10% of programmed
System safeties are faults that cause the individual value. During the next 3 minutes the cutout point is
system to be shut down. Unit safeties are faults that cause ramped up to the programmed cutout point. If at any time
all running compressors to be shut down. Following are during this 3 minutes the suction pressure falls below the
display messages and explanations. ramped cutout point, the system will stop. This cutout is
completely ignored for the first 30 seconds of system run
System Safeties time to avoid nuisance shutdowns, especially on units
System safeties are faults that cause individual systems that utilize a low pressure switch in place of the suction
to be shut down if a safety threshold is exceeded for 3 pressure transducer.
seconds. They are auto reset faults in that the system
will be allowed to restart automatically after the fault After the first 3 minutes, if the suction pressure falls
condition is no longer present. However, if 3 faults on below the programmed cutout setting, a “transient
the same system occur within 90 minutes, that system protection routine” is activated. This sets the cutout at
will be locked out on the last fault. This condition is then 10% of the programmed value and ramps up the cutout
7
a manual reset. The system switch (under OPTIONS over the next 30 seconds. If at any time during this 30
key) must be turned off and then back on to clear the seconds the suction pressure falls below the ramped
lockout fault. Fault messages will be displayed whenever cutout, the system will stop.
a system is locked out.
S Y S 1 M P / H P C O F A U L T
S Y S 1 H I G H D S C H P R E S S Y S 2 M P / H P C O F A U L T
S Y S 2 H I G H D S C H P R E S

The Discharge Pressure Cutout is a software cutout in S Y S 1 M P / H P C O I N H I B


the microprocessor and is backed-up by a mechanical S Y S 2 M P / H P C O I N H I B
high pressure cutout switch located in the refrigerant
circuit. It assures that the system pressure does not The Motor Protector/Mechanical High Pressure Cutout
exceed safe working limits. The system will shutdown protect the compressor motor from overheating or the
when the programmable cutout is exceeded and will be system from experiencing dangerously high discharge
allowed to restart when the discharge pressure falls 40 pressure.
PSIG below the cutout. Discharge transducers must be
installed for this function to operate. This fault condition is present when CR1 (SYS 1) or
CR2 (SYS 2) relays de-energize due to the HP switch or
motor protector opening. This causes the respective CR
contacts to open causing 0VDC to be read on the inputs
to the microboard. The fault condition is cleared when a
30VDC signal is restored to the input.

JOHNSON CONTROLS 127


Unit Controls
FORM 150.67-NM1 (308)

The internal motor protector opens at 185 °F – 248 °F During the 30 minute timeout, the MP/HPCO INHIB
(85 °C – 120 °C) and auto resets. The mechanical HP message will be displayed. The MP/HPCO fault will
switch opens at 585 PSIG +/- 10 PSIG (27.92 barg +/- .69 only be displayed after 3 shutdowns in 90 minutes,
barg) and closes at 330 PSIG +/- 25 PSIG (22.75 barg indicating the system is locked out and will not
+/- 1.72 barg). restart.

The compressor is also equipped with a discharge S Y S 1 H I G H M T R C U R R


temperature sensor for the purpose of sensing internal S Y S 2 H I G H M T R C U R R
scroll temperature. This sensor protects the scrolls
from overheating due to inadequate cooling that may When the System Current Feedback option is installed
occur when refrigerant charge is low, or superheat is and selected (Option 11 under OPTIONS Key Current
too high. Feedback), this safety will operate as follows. If the
actual feedback voltage of the system proportional to
When the sensor senses a high temperature, it opens the currents exceeds the programmed trip voltage for 5
motor protector circuit in the compressor causing the seconds, the system will shutdown.
compressor to shut down.
This safety will shut down a system if either suction
During the first two faults an MP/HP INHIBIT message temperature or suction pressure sensors read out of
will be displayed and the system will not be locked range high or low. This condition must be present for 3
out. Only after the third fault in 90 minutes will the seconds to cause a system shutdown. The safety locks
MP/HPCO FAULT message be displayed. out a system after the first fault and will not allow
automatic restarting.
Whenever the motor protector or discharge sensor
shuts down a compressor and the system, the internal
compressor contacts will open for a period of 30 minutes
to assure that the motor or scroll temperatures have
time to dissipate the heat and cool down. The MP/HP
INHIBIT message will be displayed while these
contacts are open or when the HPCO is open. While
this message is displayed, the compressors will not
be permitted to start.

After 30 minutes, the contacts will close and the system


will be permitted to restart. The micro will not try to
restart the compressors in a system that shuts down on
this safety for a period of 30 minutes to allow the internal
compressor to time out.

128 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

Unit Safeties U N I T F A U L T :
Unit safeties are faults that cause all running compressors H I G H M T R C U R R
to be shut down. Unit faults are auto reset faults in that
the unit will be allowed to restart automatically after the When the CURRENT FEEDBACK ONE PER UNIT
fault condition is no longer present. option is selected under the OPTIONS Key, the unit will
U N I T F A U L T :
shut down when the voltage exceeds the programmed
L OW A M B I E N T T E M P
trip voltage for 5 seconds.

The trip voltage is programmed at the factory according


The Low Ambient Temp Cutout is a safety shutdown to compressor or unit RLA.
designed to protect the chiller from operating in a low
ambient condition. If the outdoor ambient temperature Restart will occur after the anti-recycle timer times
falls below the programmable cutout, the chiller will out.
shut down. Restart can occur when temperature rises 2
°F above the cutoff. Unit Warning
U N I T F A U L T : The following messages are not unit safeties and
L OW L I Q U I D T E M P will not be logged to the history buffer. They are unit
warnings and will not auto-restart. Operator intervention
is required to allow a restart of the chiller.
The Low Leaving Chilled Liquid Temp Cutout protects
the chiller form an evaporator freeze-up should the ! ! L OW B A T T E R Y ! !
chilled liquid temperature drop below the freeze point. C H E C K P R O G / S E T P / O P T N
This situation could occur under low flow conditions
or if the micro panel setpoint values are improperly
The Low Battery Warning can only occur at unit
programmed. Anytime the leaving chilled liquid
power-up. On micro panel power-up, the RTC battery
temperature (water or glycol) drops below the cutout
is checked. If a low battery is found, all programmed
point, the chiller will shutdown. Restart can occur when
setpoints, program values, options, time, schedule, and
chilled liquid temperature rises 2 °F above the cutout.
history buffers will be lost. These values will all be reset
U N I T F A U L T : to their default values which may not be the desired 7
1 1 5 V A C U N D E R V O L T A G E operating values. Once a faulty battery is detected,
the unit will be prevented from running until the
PROGRAM key is pressed. Once PROGRAM is pressed
The Under Voltage Safety assures that the system is
the anti-recycle timers will be set to the programmed
not operated at voltages where malfunction of the
anti-recycle time to allow the operator time to check
microprocessor could result in system damage. When the
setpoints, and if necessary, reprogram programmable
115VAC to the micro panel drops below a certain level, a
values and options.
unit fault is initiated to safely shut down the unit. Restart
is allowed after the unit is fully powered again and the
If a low battery is detected, it should be replaced as
anti-recycle timers have finished counting down.
soon as possible. The programmed values will all be lost
and the unit will be prevented from running on the next
power interruption. The RTC/battery (031-00955-000)
is located at U17 on the microboard.

I N C O R R E C T
U N I T T Y P E

This indicates the condensing unit jumper is installed


on J11-12. This jumper must be removed to operate the
chiller.

JOHNSON CONTROLS 129


Unit Controls
FORM 150.67-NM1 (308)

STATUS KEY MESSAGES


TABLE 10 – STATUS KEY MESSAGES QUICK REFERENCE LIST

STATUS KEY MESSAGES

General Messages Fault Messages

Unit Switch Off System Safeties Unit Safeties &


Shutdown Warning Messages

Remote Controlled System X High Disch Pressure Low Ambient Temp


Shutdown

Daily Schedule System X Low Suct Pressure Low Liquid Temp


Shutdown

Flow Switch/Rem Stop System X MP/HPCO Inhibit 115VAC Undervoltage


No Run Permissive

System X Switch Off Low Battery


System X MP/HPCO Fault
Check Prog/Step/Optn
(Unit Warning Message)

System X
No Cooling load System X HIGH MTR CURR
(Optional) Incorrect Unit Type
System X Comps Run (Unit Warning Message)

System X AR Timer

High Motor Current


System X AC Timer

System X Disch Limiting

System X Suction Limiting

System X Percentage Load Limiting

LD11297A
Manual Overide Status

System X Pumping Down (on shutdown)

130 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

DISPLAY/PRINT KEYS

00067VIP

The Display/Print keys allow the user to retrieve system With the “UNIT TYPE” set as a liquid chiller (no jumper
and unit information that is useful for monitoring to J11-12), the following list of operating data screens
chiller operation, diagnosing potential problems, are viewable under the Oper Data key in the order that
troubleshooting, and commissioning the chiller. they are displayed. The ↓ (DOWN) arrow key scrolls
through the displays in the order they appear below:
System and unit information, unit options, setpoints,
and scheduling can also be printed out with the use of The chiller MUST be set to be a liquid
a printer. Both real-time and history information are
7
chiller (no jumper to J11-12). DO
available. NOT operate the chiller if not properly
set up.
Oper Data Key
The OPER DATA key gives the user access to unit and
system operating parameters. When the OPER DATA
key is pressed, system parameters will be displayed and
L C H L T = 4 6 . 2 ° F
remain on the display until another key is pressed. After
R C H L T = 5 7 . 4 ° F °
pressing the OPER DATA key, the various operating data
screens can be scrolled through by using the ↑ (UP) and This display shows chilled leaving and return liquid
↓ (DOWN) arrow keys or the ENTER/ADV key located temperatures. The minimum limit on the display for
under the “ENTRY” section. these parameters are 2.2 °F (-19 °C). The maximum
limit on the display is 140 °F (60 °C).
System 2 information will only be dis-
played for 2 system units. A M B I E N T A I R T E M P
= 8 7 . 5 ° F

This display shows the ambient air temperature. The


minimum limit on the display is 0.4 °F (-17.6 °C). The
maximum limit on the display is 131.2 °F (55.1 °C).

JOHNSON CONTROLS 131


Unit Controls
FORM 150.67-NM1 (308)

S Y S X S P = 7 2 . 1 P S I G C O O L I N G D E M A N D
D P = 2 2 7 . 0 P S I G 2 O F 8 S T E P S

These displays show suction and discharge pressures The display of COOLING DEMAND indicates the
for each system. The discharge pressure transducer is current “step” in the capacity control scheme when in
optional on some models. Return Water Control Mode. The number of available
steps are determined by how many compressors are in
If the optional discharge transducer is not installed, the the unit. In the above display, the “2” does not mean
discharge pressure would display 0 PSIG (0 barg). that two compressor are running but only indicates that
the capacity control scheme is on step 2 of 8. Capacity
The minimum limits for the display are: Control is covered in more detail in this publication
Suction Pressure: 0 PSIG (0 barg) which provides specific information on compressor
Discharge Pressure: 0 PSIG (0 barg)
staging (for Return Water Control only).
The maximum limits for the display are:
Suction Pressure: 400 PSIG (27.58 barg) T E M P E R R O R X X X . X ° F
Discharge Pressure: 650 PSIG (44.82 barg) T E M P R A T E X X X . X ° F / M

SY S X H O U R S 1 = X X X X X
2 = X X X X X, 3 = X X X X X The COOLING DEMAND message will be replaced
with this message when Leaving Chilled liquid control
S Y S X S T A R T S 1 = X X X X X is selected. This message indicates the temperature
2 = X X X X X, 3 = X X X X X error and the rate of change of the chilled liquid
temperature.
The above two messages will appear sequentially for
L E A D S Y S T E M I S
each system. The first display shows accumulated
S Y S T E M N U M B E R 2
running hours of each compressor for the specific
system. The second message shows the number of starts
for each compressor on each system. This display indicates the current LEAD system. In this
example system 2 is the LEAD system, making system
Run times and starts will only be dis- 1 the LAG system. The LEAD system can be manually
played for the actual number of sys- selected or automatic. Refer to the programming under
the “OPTIONS” key. The Lead System display will only
tems and compressors on the unit.
appear on a two system unit.

A unit utilizing hot gas bypass should


A total of 99,999 hours and starts can be logged before be programmed for MANUAL with
the counter rolls over to “0”. system 1 as the lead system. Failure
to do so will prevent hot gas operation
L O A D T I M E R 5 8 S E C if system 2 switches to the lead system
U N L O A D T I M E R 0 S E C when programmed for AUTOMATIC
LEAD/LAG.
This display of the load and unload timers indicate
the time in seconds until the unit can load or unload.
Whether the systems loads or unloads is determined by
how far the actual liquid temperature is from setpoint.
A detailed description of unit loading and unloading is
covered under the topic of Capacity Control.

132 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

E V A P O R A T O R H E A T E R PWM TEMP – EMS temperature reset


S T A T U S I S = X X X
* R e f e r t o t h e s e c t i o n o n O P E R AT I N G
CONTROLS.
This display indicates the status of the evaporator heater.
The evaporator heater is controlled by ambient air
If the micro is programmed for CURRENT FEEDBACK
temperature. When the ambient temperature drops below
ONE PER UNIT under the OPTIONS Key, the display
40 °F the heater is turned on. When the temperature rises
will show up as the first display prior to the SYS 1
above 45 °F the heater is turned off. An under voltage
displays. Total chiller current is displayed as shown
condition will keep the heater off until full voltage is
below:
restored to the system.
U N I T A M P S = 5 4 . 0
E V A P O R A T O R WA T E R V O L T S = 1 . 2
P U M P S T A T U S = X X XX

If the micro is programmed for CURRENT FEEDBACK


The evaporator pump dry contacts are energized when NONE, no current display will appear.
any compressor is running, or the unit is not OFF on
the daily schedule and the unit switch is on, or the unit S Y S X C OM P S T A T U S
has shutdown on a Low Leaving Chilled Liquid fault. 1 = X X X 2 = X X X 3 = X X X
However, even if one of above is true, the pump will not
run if the micro panel has been powered up for less than S Y S X R U N T I M E
30 seconds or if the pump has run in the last 30 seconds X X - X X - X X - X X D - H - M - S
to prevent pump motor overheating.

E V A P P U M P T O T A L R U N S Y S X L L S V I S O N
H O U R S = X X X X X H O T G A S S O L I S O F F

S Y S X F A N S T A G E 3
The Evaporator Pump Total Run Hours display indicates
the total pump run hours. Total hours continually
increments similar to Compressor Run Hours. If dual
S Y S X A M P S = 3 6 . 0
7
pumps are fitted, run hours indicates total hours on both
pumps. V O L T S = 0 . 8

A C T I V E R E MO T E C T R L The preceding five messages will appear sequentially,


N O N E first for system 1, then for system 2.

The first message indicates the system and the associated


There are several types of remote systems that can compressors which are running.
be used to control or monitor the unit. The following
messages indicate the type of remote control mode The second message indicates the system run time in
active: days – hours – minutes – seconds. Please note that this
is not accumulated run time but pertains only to the
NONE – no remote control active. Remote monitoring current system cycle.
may be via ISN.
The third message indicates the system, and whether the
ISN – YORK Talk via ISN allows remote load limiting liquid line solenoid or EEV pilot solenoid and hot gas
and temperature reset through an ISN system. solenoid are being turned on by the microboard. Please
note that hot gas is not available for system 2, so there
is no message pertaining to the hot gas solenoid when
LOAD LIM – Load limiting enabled using contact
system 2 message is displayed.
closure.
The fourth message indicates the stage of condenser fan
operation that is active.

JOHNSON CONTROLS 133


Unit Controls
FORM 150.67-NM1 (308)

See the section on Condenser Fan Control in the UNIT TABLE 11 – OPERATION DATA
OPERATION section for more information.
Oper Data Key
The fifth message displays current as sensed by the
optional current feedback circuitry. The display reads
out in amps along with the DC feedback voltage from Leaving & Chilled Liquid Temps
the module. Current is calculated by:
Ambient Air Temperature
225A • Actual Volts
5 Volts System 1 Discharge & Suction Pressure

Individual displays will be present for each system, if *System X Accumulated Hours
CURRENT FEEDBACK ONE PER SYSTEM is pro-
grammed under the OPTIONS Key. Combined compres- *System X Accumulated Starts
sor current for each system is displayed.
Load and Unload Timers
Oper Data Quick Reference List
Cooling Demand Steps
The following table is a quick reference list for (Return Chilled Liquid Control Only)
information available under the OPER DATA key.
Temp Rate & Temp Error
(Leaving Chilled Liquid Control Only)

Lead System Indicator

Evaporator Heater Status

Evaporator Water Pump Status

Active Remote Control

Current Feedback One Per Unit

*System X Compressors Status

*System X Run Time

* Sys X LLSV & HGSV Status

*System X Condenser Fan Stage

Current Feedback One Per System

* Block of information repeats for each system LD12585

134 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

Print Key
The PRINT key allows the operator to obtain a printout UNIT DATA
RETURN LIQUID TEMP 58.2 DEGF
of real-time system operating data or a history printout LEAVING LIQUID TEMP 53.0 DEGF
of system data at the “instant of the fault” on the last six DISCHARGE AIR TEMP 55.3 DEGF
faults which occurred on the unit. An optional printer is COOLING RANGE 42.0 +/- 2.0 DEGF
HEATING RANGE 122.0 +/- 2.0 DEGF
required for the printout. SYS 1 SETPOINT 70 +/- 3 PSIG
SYS 2 SETPOINT 70 +/- 3 PSIG
Operating Data Printout REMOTE SETPOINT 44.0 DEGF
AMBIENT AIR TEMP 74.8 DEGF
Pressing the PRINT key and then OPER DATA key LEAD SYSTEM SYS 2
allows the operator to obtain a printout of current system EVAPORATOR PUMP ON
EVAPORATOR HEATER OFF
operating parameters. When the OPER DATA key is ACTIVE REMOTE CONTROL NONE
pressed, a snapshot will be taken of system operating LAST DEFROST SYS X DURATION XXXS
conditions and panel programming selections. This data TIME TO SYS X DEFROST XX MIN
BIVALENT DELAY REMAINING XX MIN
will be temporarily stored in memory and transmission UNIT XXX.X AMPS X.X VOLTS
of this data will begin to the printer. A sample Operating SOFTWARE VERSION C.M02.13.00
Data printout is shown below. (Note: Not all values are
SYSTEM 1 DATA
printed for all models.) COMP STATUS 1=OFF 2=OFF 3=OFF
RUN TIME 0- 0- 0- 0 D-H-M-S
TIME YYYYYYY 0- 0- 0- 0 D-H-M-S
LAST STATE YYYYYYY
YORK INTERNATIONAL CORPORATION SUCTION PRESSURE 105 PSIG
MILLENNIUM LIQUID CHILLER DISCHARGE PRESSURE 315 PSIG
SUCTION TEMPERATURE 46.0 DEGF
UNIT STATUS SAT SUCTION TEMP 34.0 DEGF
2:04PM 01 OCT 07 SUCTION SUPERHEAT 12.0 DEGF
COOLER INLET REFRIG 31.6 DEGF
SYS 1 NO COOLING LOAD DEFROST TEMPERATURE 52.8 DEGF
SYS 2 COMPRESSORS RUNNING 2 LIQUID LINE SOLENOID OFF
MODE SOLENOID OFF
OPTIONS HOT GAS BYPASS VALVE OFF
CHILLED LIQUID WATER CONDENSER FAN STAGE OFF
AMBIENT CONTROL STANDARD EEV OUTPUT 0.0 %
LOCAL/REMOTE MODE
CONTROL MODE
REMOTE
LEAVING LIQUID
SYSTEM XXX.X AMPS X.X VOLTS 7
LEAD/LAG CONTROL AUTOMATIC SYSTEM 2 DATA
FAN CONTROL AMB & DSCH PRESS COMP STATUS 1=ON, 2=OFF, 3=ON
CURRENT FEEDBACK NONE RUN TIME 0-0-1-46 D-H-M-S
POWER FAILURE RESTART AUTOMATIC TIME YYYYYYY 0-0-0-0 D-H-M-S
SOFT START ENABLED LAST STATE YYYYYYY
EXPANSION VALVE THERMOSTATIC SUCTION PRESSURE 110 PSIG
REMOTE TEMP RESET 4 TO 20 MA DISCHARGE PRESSURE 320 PSIG
SUCTION TEMPERATURE 49.3 DEGF
PROGRAM VALUES SAT SUCTION TEMP 36.0 DEGF
DSCH PRESS CUTOUT 570 PSIG SUCTION SUPERHEAT 13.3 DEGF
SUCT PRESS CUTOUT 80 PSIG COOLER INLET REFRIG 31.6 DEGF
SUCT PRESS CUT COOLING 42 PSIG DEFROST TEMPERATURE 52.8 DEGF
SUCT PRESS CUT HEATING 31 PSIG LIQUID LINE SOLENOID ON
LOW AMBIENT CUTOUT 25.0 DEGF MODE SOLENOID ON
LEAVING LIQUID CUTOUT 25.0 DEGF CONDENSER FAN STAGE 3
ANTI RECYCLE TIME 600 SECS EEV OUTPUT 63.2%
FAN CONTROL ON PRESS 425 PSIG SYSTEM XXX.X AMPS X.X VOLTS
FAN DIFF OFF PRESS 125 PSIG
NUMBER OF COMPRESSORS 6 DAILY SCHEDULE
NUMBER OF FANS PER SYSTEM 4 S M T W T F S *=HOLIDAY
UNIT TRIP VOLTS 3.0 SUN START=00:00AM STOP=00:00AM
REFRIGERANT TYPE R-22 MON START=00:00AM STOP=00:00AM
DEFROST INIT TEMP 41.0 DEGF TUE START=00:00AM STOP=00:00AM
DEFROST INITIATION TIME 60MIN WED START=00:00AM STOP=00:00AM
DEFROST TERMINATION TIME 3MIN THU START=00:00AM STOP=00:00AM
BIVALENT HEAT DELAY TIME 30 MIN FRI START=00:00AM STOP=00:00AM
REMOTE UNIT ID PROGRAMMED 2 SAT START=00:00AM STOP=00:00AM
YORK HYDRO KIT PUMPS 1 (410a) HOL START=00:00AM STOP=00:00AM
PUMP TOTAL RUN HOURS XXXXX (410a)

JOHNSON CONTROLS 135


Unit Controls
FORM 150.67-NM1 (308)

See Service And Troubleshooting section History Displays


for Printer Installation information. The HISTORY key gives the user access to many unit
and system operating parameters at the time of a unit
or system safety shutdown. When the HISTORY key is
pressed the following message is displayed.

History Printout D I S P L A Y S A F E T Y S H U T-
D OWN N O . 1 ( 1 TO 9 )
Pressing the PRINT key and then the HISTORY key
allows the operator to obtain a printout of information
relating to the last 9 Safety Shutdowns which occurred. While this message is displayed, the ↑ (UP) arrow key can be
The information is stored at the instant of the fault, used to select any of the six history buffers. Buffer number
regardless of whether the fault caused a lockout to 1 is the most recent, and buffer number 6 is the oldest safety
occur. The information is also not affected by power shutdown that was saved.
failures (long-term internal memory battery backup
is built into the circuit board) or manual resetting of a After selecting the shutdown number, pressing the ENTER
fault lock-out. key displays the following message which shows when the
shutdown occurred.
When the HISTORY key is pressed, a printout is S H U T D OWN O C C U R R E D
transmitted of all system operating conditions which 0 3 : 5 6 P M 2 9 J A N 0 2
were stored at the “instant the fault occurred” for each of
the 9 Safety Shutdowns buffers. The printout will begin
with the most recent fault which occurred. The most The ↑ (UP) and ↓ (DOWN) arrow keys are used to scroll
recent fault will always be stored as Safety Shutdown forward and backward through the history buffer to
No. 1. identically formatted fault information will then display the shutdown conditions stored at the instant the
be printed for the remaining safety shutdowns. fault occurred. The ↓ (DOWN) arrow key scrolls through
the displays in the order they appear below:
Information contained in the Safety Shutdown buffers is
very important when attempting to troubleshoot a system U N I T F A U L T :
problem. This data reflects the system conditions at the L OW L I Q U I D T E M P
instant the fault occurred and often reveals other system
conditions which actually caused the safety threshold
to be exceeded. Displays the type of fault that occurred.

The history printout is similar to the operational data


U N I T T Y P E
printout shown in the previous section. The differences L I Q U I D C H I L L E R
are in the header and the schedule information. The daily
schedule is not printed in a history print.
Displays the type of chiller; Liquid, Condensing Unit
One example history buffer printout is shown following. or Heat Pump.
The data part of the printout will be exactly the same as
the operational data print so it is not repeated here. The C H I L L E D L I Q U I D
X X X X X
difference is that the Daily Schedule is not printed in the
history print and the header will be as follows.
Displays the chilled liquid type; Water or Glycol.
YORK INTERNATIONAL CORPORATION
MILLENNIUM LIQUID CHILLER

SAFETY SHUTDOWN NUMBER 1


SHUTDOWN @ 3:56PM 29 SEP 07

SYS 1 HIGH DSCH PRESS SHUTDOWN


SYS 2 NO FAULTS

136 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

A M B I E N T C O N T R O L L OW A M B I E N T T E M P
X X X X X X X X X X C U T O U T = X X X . X ° F

Displays the type of Ambient Control; Standard or Low Displays the programmed Low Ambient Cutout.
Ambient.
L E A V I N G L I Q U I D T E M P
C U T O U T = X X X . X ° F
L O C A L / RE MO T E MO D E
X X X X X X X X X
Displays the Leaving Liquid Temp. Cutout
programmed.
Displays Local or Remote control selection.
F A N C O N T R O L O N
C O N T R O L MO D E P R E S S U R E = X X X P S I G
L E A V I N G L I Q U I D
Displays the programmed Fan On Pressure.
Displays the type of chilled liquid control; Leaving or
Return. F A N D I F F E R E N T I A L OFF
P R E S S U R E = PS I G
L E A D / L A G C O N T R O L
X X X X X X X X Displays the programmed Fan Off Differential.

Displays the type of lead/lag control; Manual System 1, S Y S 1 T R I P V O L T S


Manual System 2 or Automatic. This is only selectable = X . X V O L T S
on 2-system chillers.
Displays the programmed High Current Trip Voltage.
F A N CO N T R O L
D I S C H A R G E PR E S S U R E S Y S 2 T R I P V O L T S
= X . X V O L T S
Displays the type of fan control; Discharge Pressure or
Ambient and Discharge Pressure. Displays the programmed High Current Trip Voltage.

Y O R K H Y D R O
M A N U A L O V E R R I D E MO D E
X X X X X X X X X
K I T P U M P S = X 7
Displays whether Manual Override was Enabled or Indicates the Pump Control option is selected.
Disabled.
L C H L T = X X X . X ° F
C U R R E N T F E E D B A C K R C H L T = X X X . X ° F
X X X X X X X X X X X X X X X X
Displays the Leaving and Return chilled Liquid
Displays type of Current Feedback utilized. Temperature at the time of the fault.

S O F T S T A R T S E T P O I N T = X X X . X ° F
X X X X X X X R A N G E = + / - ° F

Displays whether the optional European Soft Start was Displays the programmed Setpoint and Range, if
installed and selected. the chiller is programmed for leaving chilled liquid
control.
D I S C H A R G E P R E S S U R E
C U T O U T = X X X X P S I G S E T P O I N T = X X X . X ° F
R A N G E = + X X . X ° F
Displays the programmed Discharge Pressure Cutout.
Displays the programmed Setpoint and Range, if the
S U C T I O N P R E S S U R E chiller is programmed for return chilled liquid control.
C U T O U T = X X X X P S I G
A M B I E N T A I R T E M P
= X X X . X ° F
Displays the programmed Suction Pressure Cutout.
Displays the Ambient Temp. at the time of the fault.
JOHNSON CONTROLS 137
Unit Controls
FORM 150.67-NM1 (308)

Displays the System Suction Temp and Saturated


L E A D S Y S T E M I S Suction Temp when an EEV is installed.
S Y S T E M N U M B E R X

Displays which system is in the lead at the time of the S Y S X L L S V I S X X X


fault. H O T G A S S O L I S X X X

E V A P O R A T O R H E A T E R
Displays whether the System Liquid Line Solenoid
S T A T U S I S X X X
or Hot Gas Solenoid was energized at the time of the
fault.
Displays status of the Evaporator Heater at the time of
the fault. S Y S X F A N S T A G E X X X

E V A P O R A T O R WA T E R
P U M P S T A T U S X X X X Displays the number of Fan Stages in the system active
at the time of the fault.
Displays status of Evaporator Water Pump at the time S Y S X AC T U A L A M P S
of fault. Status may read on, off or trip. = X X X . X A M P S

E V A P P U M P T O T A L R U N Displays the system Amperage (calculated approximately)


H O U R S = X X X X at the time of the fault.

Evap Pump total run hours at the time of fault. For this message to appear, CURRENT FEEDBACK ONE
PER SYSTEM must be programmed under the options
key. If the micro is programmed as one CURRENT
A C T I V E R E MO T E C T R L
FEEDBACK ONE PER UNIT under the program key, the
X X X X
display will be the first display prior to the SYS 1 info. If
the micro is programmed for CURRENT FEEDBACK
Displays whether Remote Chiller Control was active NONE, no current display will appear.
when the fault occurred.
U N I T A C T U A L A M P S Displays for System 1 starting with SYS X NUMBER
= X X X . X A M P S OF COMPS RUNNING X through SYS X AMPS =
XXX.X VOLTS = X.X will be displayed first, followed
This is only displayed when the Current Feedback by displays for System 2.
Option is one per unit.
Further explanation of the above displays is covered
S Y S X C OM P S T A T U S under the STATUS, OPER DATA, COOLING
1 = X X X 2 = X X X 3 = X X X SETPOINTS, PROGRAM, and OPTIONS keys.

Displays which Compressors were running in the system Software Version


when the fault occurred.
The software version may be viewed by first pressing
S Y S X R U N T I M E the HISTORY key and then repeatedly pressing the ↓
X X - X X - X X - X X D - H - M - S (DOWN) arrow key until you scroll past the first history
buffer choice.
Displays the system run time when the fault occurred.
D I S P L A Y S A F E T Y S H U T -
S Y S X S P = X X X X P S I G D OWN N O . 1 ( 1 T O 6 )
D P = X X X X P S I G

Displays the system Suction and Discharge Pressure of


the time of the fault. After the ↓ (DOWN) arrow key is pressed again, the
software version will appear.
S Y S X S U C T = X X X . X ° F
C O N T R O L C. M X X. Z Z. Y Y
S A T S U C T = X X X . X ° F
I / O C. M X X. 1 8. Y Y

138 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

“ENTRY” KEYS

00068VIP 7

The Entry Keys allows the user to view, change programmed Enter/adv Key
values. The ENTRY keys consist of an ↑ (UP) arrow key, ↓
The ENTER/ADV key must be pushed after any change
(DOWN) arrow key, and an ENTER/ADV key.
is made to the cooling setpoints, daily schedule, safety
setpoints, chiller options, and the clock. Pressing this key
Up and Down Arrow Keys
“enters” the new values into memory. If the ENTER/
Used in conjunction with the OPER DATA, HISTORY, ADV key is not pressed after a value is changed, the
COOLING SETPOINTS, SCHEDULE/ADVANCE changes will not be “entered” and the original values
DAY, OPTIONS and CLOCK keys, the ↑ (UP) and ↓ will be used to control the chiller.
(DOWN) arrow keys allow the user to scroll through
the various data screens. Refer to the section on Programming and a description on the use of the ↑ (UP)
“DISPLAY/PRINT” keys for specific information on arrow key, and ↓ (DOWN) arrow, and ENTER/ADV
the displayed information and specific use of the ↑ (UP) keys are covered in detail under the SETPOINTS, and
and ↓ (DOWN) arrow keys. UNIT keys.

The ↑ (UP) arrow key, and ↓ (DOWN) arrow key are also
used for programming the control panel such as changing
numerical or text values when programming cooling
setpoints, setting the daily schedule, changing safety
setpoints, chiller options, and setting the clock.

JOHNSON CONTROLS 139


Unit Controls
FORM 150.67-NM1 (308)

“SETPOINTS” KEYS

00069VIP

Programming of the cooling setpoints, daily schedule, Leaving Chilled Liquid Control
and safeties is accomplished by using the keys located
under the SETPOINTS section. S E T P O I N T = 4 5 . 0 ° F
R A N G E = +/- 2 . 0 ° F
The three keys involved are labeled COOLING
SETPOINTS, SCHEDULE/ADVANCE DAY, and
The above message shows the current chilled water
PROGRAM.
temperature SETPOINT at 45.0 °F (notice the cursor po-
sitioned under the number 0). Pressing either the ↑ (UP)
Following are instructions for programming the
or ↓ (DOWN) arrow will change the setpoint in .5 °F
respective setpoints. The same instruction should be increments. After using the ↑ (UP) or ↓ (DOWN) arrow
used to view the setpoints with the exception that the keys to adjust to the desired setpoint, the ENTER/ADV
setpoint will not be changed. key must be pressed to enter this number into memory
and advance to the RANGE SETPOINT.
Cooling Setpoints
Entry of the setpoint will be indicated by the cursor mov-
The Cooling Setpoint and Range can be programmed by
ing under the current RANGE setpoint. The ↑ (UP) and
pressing the COOLING SETPOINTS key. The cooling ↓ (DOWN) arrow keys are used to set the RANGE, in
mode (leaving chilled liquid or return chilled liquid) will .5 °F increments, to the desired RANGE setpoint. After
be displayed for a few seconds, and the setpoint display adjusting the setpoint, the ENTER/ADV key must be
entry screen will appear. pressed to enter the data into memory.

Notice that the RANGE was programmed for +/- X.X° F.


This indicates the SETPOINT to be in the center of the
control range. If the control mode has been programmed
for RETURN LIQUID control, the message below

140 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

would be displayed in place of the previous message. R E M S E T P = 4 4 . 0 ° F


When in leaving chilled liquid temperature control, the R A N G E = + / - 2 . 0 ° F
micro will attempt to control the leaving water tem-
perature within the temperature range of the setpoint + (leaving chilled liquid control)
or – the range. In the above example, control will be in R E M S E T P = 4 4 . 0 ° F
the range of 43 – 47 °F. R A N G E = + 10 . 0 ° F

Return Chilled Liquid Control (return chilled liquid control)


S E T P O I N T = 4 5 . 0 ° F
The low limit, high limit, and default values for the keys
R A N G E = + 1 0 . 0 ° F
under “SETPOINTS” are listed in Table 12.

In return chilled liquid control, the range no longer has Pressing the COOLING SETPOINTS a third time will
a +/- X.X °F, but only a + X.X °F RANGE setpoint. bring up the display that allows the Maximum EMS-
This indicates that the setpoint is not centered within PWM Temperature Reset to be programmed. This
the RANGE but could be described as the bottom of message is shown below.
the control range. A listing of the limits and the pro- M A X E M S - PWM R E MO T E
grammable values for the COOLING SETPOINTS are T E M P R E S E T = + 2 0 ° F
shown in Table 12.

The SETPOINT and RANGE displays just described The Temp Reset value is the maximum allowable remote
were based on LOCAL control. If the unit was pro- reset of the temperature setpoint. The setpoint can be
grammed for REMOTE control (under the OPTIONS reset upwards by the use of an Energy Management
key), the above programmed setpoints would have no System or from the Temperature Reset Option Board.
effect. See page 172 for a detailed explanation of this feature.

When in return chilled liquid temperature control, the As with the other setpoints, the ↑ (UP) arrow and ↓
micro will turn all compressors off at setpoint and will (DOWN) arrow keys are used to change the Temp Reset
turn compressors on as return chilled liquid tempera- value. After using the ↑ (UP) and ↓ (DOWN) arrows to
ture rises. All compressors will be on at setpoint + the adjust to the desired setpoint, the ENTER/ADV key must 7
range. If the range equals the temperature drop across be pressed to enter this number into memory.
the evaporator when fully loaded, the leaving chilled
liquid temperature will remain near the setpoint + or – a SCHEDULE/ADVANCE DAY KEY
few degrees as the chiller loads and unloads according The SCHEDULE is a seven day daily schedule that
to return chilled liquid temperature. allows one start/stop time per day. The schedule can be
programmed Monday through Sunday with an alternate
Both LEAVING and RETURN control are described in holiday schedule available. If no start/stop times are
detail under the section on CAPACITY CONTROL. programmed, the unit will run on demand, providing the
chiller is not shut off on a unit or system shutdown. The
Remote Setpoint Control daily schedule is considered “not programmed” when
the times in the schedule are all zeros (00:00 AM).
Pressing the COOLING SETPOINTS key a second
time will display the remote setpoint and cooling
To set the schedule, press the SCHEDULE/ADVANCE
range. This display automatically updates about every
DAY key. The display will immediately show the
2 seconds. Notice that these setpoints are not “locally”
following display.
programmable, but are controlled by a remote device
such as an ISN control, remote reset option board, or
MO N S T A R T = 0 0 : 0 0 A M
remote PWM signal. These setpoints would only be valid
S T O P = 0 0 : 0 0 A M
if the unit was operating in the REMOTE mode.

The following messages illustrate both leaving


chilled liquid control and return chilled liquid control
respectively.

JOHNSON CONTROLS 141


Unit Controls
FORM 150.67-NM1 (308)

TABLE 12 – COOLING SETPOINTS, PROGRAMMABLE LIMITS AND DEFAULTS

SETPOINT KEY MODE LOW LIMIT HIGH LIMIT DEFAULT


40.0 °F **70.0 °F 44.0 °F
WATER COOLING
4.4 °C 21.1 °C 6.7 °C
LEAVING CHILLED LIQUID SETPOINT
10.0 °F **70.0 °F 44.0 °F
GLYCOL COOLING*
-12.2 °C 21.1 °C 6.7 °C
LEAVING CHILLED LIQUID 1.5 °F 2.5 °F 2.0 °F

CONTROL RANGE 0.8 °C 1.4 °C 1.1 °C
40.0 °F 70.0 °F 44.0 °F
WATER COOLING
4.4 °C 21.1 °C 6.7 °C
RETURNED CHILLED LIQUID SETPOINT
10.0 °F 70.0 °F 44.0 °F
GLYCOL COOLING* 21.1 °C 21.1 °C 6.7 °C
RETURN CHILLED LIQUID 4.0 °F 20.0 °F 10.0 °F

CONTROL RANGE 2.2 °C 11.1 °C 5.6 °C
MAX EMS-REMOTE 2 °F 40 °F 20 °F

TEMPERATURE RESET 1.0 °C 22.0 °C 11.0 °C
* Refer to Engineering Guide for operation below 30 °F (-1.1 °C). Alternate thermal expansion valves must be used
below 30 °F (-1.1 °C).
* When using glycol, Leaving Chilled Liquid Setpoint should not be set below 20 °F (-6.7 °C).
** Do not exceed 55 °F (12.8 °C) setpoint before contacting the nearest YORK Office for application
guidelines.

The line under the 0 is the cursor. If the value is wrong, H O L S T A R T = 0 0 : 0 0 A M


it may be changed by using the ↑ (UP) and ↓ (DOWN) S T O P = 0 0 : 0 0 A M
arrow keys until correct. Pressing the ENTER/ADV
key will enter the times and then move the cursor to the The times may be set using the same procedure as
minute box. The operation is then repeated if necessary. described above for the days of the week. After
This process may be followed until the hour, minutes, changing the meridian of the stop time, pressing the
and meridian (AM or PM) of both the START and STOP ENTER/ADV key will advance the schedule to the
points are set. After changing the meridian of the stop following display:
time, pressing the ENTER/ADV key will advance the
schedule to the next day. S __ M T W T F S
H O L I D A Y N O T E D B Y *
Whenever the daily schedule is changed
for Monday, all the other days will The line below the empty space next to the S is the
change to the new Monday schedule. cursor and will move to the next empty space when
This means if the Monday times are the ENTER/ADV key is pressed. To set the Holiday,
not applicable for the whole week the cursor is moved to the space following the day of
then the exceptional days would need the week of the holiday and the ↑ (UP) arrow key is
pressed. An * will appear in the space signifying that
to be reprogrammed to the desired
day as a holiday. The * can be removed by pressing the
schedule.
↓ (DOWN) arrow key.
To page to a specific day, press the SCHEDULE/ The Holiday schedule must be programmed weekly
ADVANCE DAY key until the desired day appears. The –once the Holiday schedule runs, it will revert to the
start and stop time of each day may be programmed normal daily schedule.
differently using the ↑ (UP) and ↓ (DOWN) arrow, and
ENTER/ADV keys.

After SUN (Sunday) schedule appears on the display a


subsequent press of the SCHEDULE/ADVANCE DAY
key will display the Holiday schedule. This is a two part
display. The first reads:
142 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

PROGRAM KEY L OW A M B I E N T T E M P
There are several operating parameters under the C U T O U T = 2 5 . 0 ° F
PROGRAM key that are programmable. These setpoints
can be changed by pressing the PROGRAM key, and The LOW AMBIENT TEMP CUTOUT allows the user
then the ENTER/ADV key to enter Program Mode. to select the chiller outside ambient temperature cutout
Continuing to press the ENTER/ADV key will display point. If the ambient falls below this point, the chiller
each operating parameter. While a particular parameter will shut down. Restart can occur when temperature rises
is being displayed, the ↑ (UP) and ↓ (DOWN) arrow 2 °F (1.11 °C) above the cutout setpoint.
keys can be used to change the value. After the value is
changed, the ENTER/ADV key must be pressed to enter L E A V I N G L I Q U I D T E M P
the data into memory. Table 13 shows the programmable C U T O U T = 3 6 . 0 ° F
limits and default values for each operating parameter.
The LEAVING LIQUID TEMP CUTOUT protects
Following are the displays for the programmable values the chiller from an evaporator freeze-up. Anytime the
in the order they appear: leaving chilled liquid temperature drops to the cutout
point, the chiller shuts down. Restart will be permitted
d D I S C H A R G E P R E S S U R E when the leaving chilled liquid temperature rises 2 °F
C U T O U T = 3 9 5 P S I G (1.11 °C) above the cutout setpoint.

DISCHARGE PRESSURE CUTOUT is the discharge When water cooling mode is programmed (OPTIONS
pressure at which the system will shutdown as monitored key), the value is fixed at 36.0 °F (2.22 °C) and cannot
by the optional discharge transducer. This is a software be changed. Glycol cooling mode can be programmed
shutdown that acts as a backup for the mechanical high to values listed in Table 13.
pressure switch located in the refrigerant circuit. The
system can restart when the discharge pressure drops A N T I R E C Y C L E T I M E R
= 6 0 0 S E C
40 PSIG (2.76 barg) below the cutout point.

If the optional discharge pressure transducer is not The programmable anti-recycle timer assures that
installed, this programmable safety would not apply. systems do not short cycle, and the compressor motors
It should be noted that every system has a mechanical have sufficient time to dissipate heat after a start. 7
high pressure cutout that protects against excessive This timer is programmable under the PROGRAM
high discharge pressure regardless of whether or not the key between 300 – 600 seconds. Whenever possible,
optional discharge pressure is installed. to reduce cycling and motor heating, the anti-recycle
timer should be adjusted as high as possible. The
S U C T I O N P R E S S U R E programmable anti-recycle timer starts the timer when
C U T O U T = 80 . 0 P S I G the first compressor in a system starts. The timer begins
to count down. If all the compressors in the circuit cycle
The SUCTION PRESSURE CUTOUT protects the off, a compressor within the circuit will not be permitted
chiller from an evaporator freeze-up. If the suction to start until the anti-recycle timer has timed out. If the
pressure drops below the cutout point, the system will lead system has run for less than 5 minutes, 3 times
shut down. Typically, the cutout should be set to 80 PSIG in a row, the anti-recycle timer will be extended to 10
(5.52 Bars) form water cooling. minutes, if currently programmed for < 10 minutes.

F A N C O N T R O L O N
There are some exceptions when the
P R E S S U R E = XX X P S I G
suction pressure is permitted to tem-
porarily drop below the cutout point.
The Fan Control On-Pressure is the programmed
Details are explained under the topic
pressure value that is used to stage the condenser fans
of SYSTEM SAFETIES. on, in relation to discharge pressure. Refer to Condenser
Fan Control in the UNIT OPERATION section and
Tables 19, 20, 21 and 22.

JOHNSON CONTROLS 143


Unit Controls
FORM 150.67-NM1 (308)

This MUST be programmed correctly


F A N D I F F E R E N T I A L O F F
to assure proper chiller operation.
PR E S S U R E = XX X P S I G

The Fan Differential Off Pressure is the programmed


differential pressure value that is used to stage the
condenser fans off, in relation to discharge pressure. Refer
to Condenser Fan Control in the UNIT OPERATION N U M B E R O F F A N S
section and Tables 19, 20, 21 and 22. P E R S Y S T E M = X

T O T A L N U M B E R O F The Number of Fans Per System must be pro-


C OM P R E S S O R S = 6
grammed as needed to match the number of fans
on each system.
The TOTAL NUMBER OF COMPRESSORS is the total
quantity of compressors in the chiller, and determines S Y S X T R I P V O L T S
the stages of cooling available. Note in Table 13, the = X. X V O L T S
chiller may have single or dual systems. Single system
units can have 2 or 3 compressors, while dual system U N I T T R I P V O L T S
units may have 4 or 6 compressors. = X. X V O L T S

This MUST be programmed correctly Depending on the option, the trip voltage for a
to assure proper chiller operation. specific system or unit high current trip can be
programmed. It also calibrates the current readout
A single system chiller MUST have a under the OPER DATA key. The approximate
jumper between terminals J9-7 and programmed value is calculated using the following
+24V on the I/O board. This connec- formulas:
tion can be made between terminals
System Trip Volts
13 and 17 on terminal block CTB1. If
the jumper is not installed, the unit will For individual system high current trip programming
act as a 2-system chiller. The jumper on chillers:
is only checked by the micro at unit • Add the sum of the compressor and fan RLA’s
power-up. If the jumper is removed, in the system
power must be removed and re-applied • Multiply the sum by 1.25
to register the change in memory. • Divide by 225A
• The resulting voltage is the value that should be
programmed

For example, if fan and compressor RLA’s total 100A:


5V x 100A 625VA
x 1.25 = = 2.8V
225A 225A

The programmed value will be 2.8V. A similar


calculation and programming will be necessary for the
other system in a 2-system chiller.

144 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

R E M O T E U N I T I D
Unit Trip Volts
P R O G R A M M E D = X
For total chiller high current trip programming on
460VAC chillers: When communications is required with a BAS or
OptiView Panel, individual unit IDs are necessary for
• Add the sum of all the the compressor and
communications with specific chillers on a single RS-
fan RLA’s in the chiller.
485 line. ID 0-7 is selectable.
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be
programmed.

For example, if fan and compressor RLA’s total 180A:


5V x 180A 1125VA
x 1.25 = = 5.0V
225A 225A

The programmed value will be 5.0V.

TABLE 13 – PROGRAM KEY LIMITS AND DEFAULT

PROGRAM VALUE MODE LOW LIMIT HIGH LIMIT DEFAULT


325 PSIG 575 PSIG 570 PSIG
DISCHARGE PRESSURE CUTOUT —
22.4 BARG 39.6 BARG 39.3 BARG
80.0 PSIG 120.0 PSIG 80.0 PSIG
WATER COOLING
SUCTION PRESSURE CUTOUT 5.52 BARG 8.27 BARG 5.52 BARG
42.0 PSIG 70.0 PSIG 44.0 PSIG
GLYCOL COOLING
2.9 BARG 4.83 BARG 3.03 BARG
25.0 °F 60.0 °F 25.0 °F
STANDARD AMBIENT
-3.9 °C 15.6 °C -3.9 °C
LOW AMBIENT TEMP. CUTOUT
0 °F 60.0 °F 25.0 °F
7
LOW AMBIENT
-17.8 °C 15.6 °C -3.9 °C
36 °F
WATER COOLING — —
LEAVING CHILLED LIQUID 2.2 °C
TEMP. CUTOUT -1.0 °F 36.0 °F 36.0 °F
GLYCOL COOLING
-18.3 °C 2.2 °C 2.2 °C
ANTI-RECYCLE TIMER — 300 SEC. 600 SEC. 600 SEC.
360 PSIG 485 PSIG 385 PSIG
FAN CONTROL ON PRESSURE —
24.8 BARG 33.4 BARG 26.5 BARG
80 PSID 160 PSID* 125 PSID
FAN DIFFERENTIAL OFF PRESSURE —
5.51 BARD 11.03 BARD* 8.62 BARD
SINGLE SYSTEM 2 3 3
TOTAL NUMBER OF COMPRESSORS DUAL SYSTEM 4 6 6

NUMBER OF FANS PER SYSTEM 2 4 3

UNIT/SYSTEM TRIP VOLTS CURRENT FEEDBACK 0.5 Volts 4.5 Volts 2.5 Volts

REMOTE UNIT ID — 0 7 0

* The minimum discharge pressure allowed is 235 PSIG. The Fan Differential Off Pressure High Limit will be lowered (reduced) to
prevent going below 235 PSIG based on where the fan control On Pressure is programmed.

JOHNSON CONTROLS 145


Unit Controls
FORM 150.67-NM1 (308)

TABLE 14 – SETPOINTS QUICK REFERENCE LIST

Quick Reference Programming Chart


Setpoints Section

Cooling Setpoints Key Schedule/ Program Mode


(press key to adv.) Advance Day Key (press enter to adv.)

Local Leaving Mon. – Sun. Discharge


Water Temp Control & Pressure
(Display Only) Holiday Cutout
Schedule

Chilled Liquid Suction


Setpoint Pressure
& Cutout
Range

Remote Setpoint Low Ambient Temp.


& Cutout
Range
(Display Only)

Leaving Liquid
EMS - PWM Temperature
Remote Temp Cutout
Reset Setpoint

Anti-Recycle
Table 14
Table 16 provides a quick reference of the setpoints list for the Setpoints Keys.
Timer

Fan Control
On-Pressure

Fan Differential
Off-Pressure

Total Numbers
of
Compressors

Number of
Fans Per System

SYS / Unit
Trip Volts Option

Remote Unit ID

LD07404c

146 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

“UNIT” KEYS

OPTIONS

CLOCK

00070VIP

Options Key This allows both systems to run


or
There are many user programmable options under the
S Y S 1 SW I T C H O N
OPTIONS key. The OPTIONS key is used to scroll
S Y S 2 SW I T C H O F F
through the list of options by repeatedly pressing the
OPTIONS key. After the selected option has been This turns system 2 off
displayed, the ↑ (UP) and ↓ (DOWN) arrow keys are then S Y S 1 SW I T C H O F F
used to change that particular option. After the option S Y S 2 SW I T C H O N
is changed, the ENTER/ADV key must be pressed to
enter the data into memory. This turns system 1 off
or
Many of the OPTIONS displayed S Y S 1 SW I T C H O F F
are only programmable under the S Y S 2 SW I T C H O F F
SERVICE MODE and not under the 7
OPTIONS key. Options only program- This turns systems 1 & 2 off
mable under the SERVICE MODE
are noted in the details describing the Turning a system off with its system
option. switch allows a pumpdown to be per-
formed prior to shutdown.
Table 15 shows the programmable options. Following
are the displays in the order they appear:

Option 1 – Language: Option 3 – Chilled Liquid Cooling Type:

D I S P L A Y L A N G U A G E C H I L L E D L I Q U I D
E N G L I S H WA T E R

English, Spanish, French, German, and Italian can be The chilled liquid is water. The Cooling Setpoint can be
programmed. programmed from 40 °F to 70 °F (4.4 °C to 21.1 °C)
or
Option 2 – System Switches: (two system units C H I L L E D L I Q U I D
only)
G L Y C O L
(Single System Display is similar)
S Y S 1 SW I T C H O N The chilled liquid is glycol. The Cooling Setpoint can
S Y S 2 SW I T C H O N be programmed from 10 °F to 70 °F (-12.2 °C to 21.1
°C).

JOHNSON CONTROLS 147


Unit Controls
FORM 150.67-NM1 (308)

Option 4 – Ambient Control Type: Option 7 – Display Units:

A M B I E N T C O N T R O L D I S P L A Y U N I T S
S T A N D A R D I M P E R I A L

The low ambient cutout is adjustable from 25 °F to 60 °F This mode displays system operating values in Imperial
(-3.9 °C to 15.6 °C). units of °F or PSIG.
or
or
A M B I E N T C O N T R O L
L OW A M B I E N T D I S P L A Y U N I T S
S I

The low ambient cutout is programmable down to 0 °F This mode displays system operating values in Scientific
(-17.8 °C). A low ambient kit MUST be installed for International Units of °C or barg.
this option to be chosen. If the kit is NOT installed,
and low ambient is selected, low pressure faults and Option 8 – Lead/Lag Type (two system units
compressor damage may occur. only):
Option 5 – Local/Remote Control Type: L E A D / L A G C O N T R O L
M A N U A L S Y S 1 L E A D
L O C A L / R E MO T E MO D E L
L O C A L
SYS 1 selected as lead compressor. SYS 1 lead option
MUST be chosen if Hot Gas Bypass is installed.
When programmed for LOCAL, an ISN or RCC control or
can be used to monitor only. The micro panel will operate
on locally programmed values and ignore all commands L E A D / L A G C O N T R O L
from remote devices, or through the RS-485 inputs. The M A N U A L S Y S 2 L E A D
chiller will communicate and send data to the remote
monitoring devices. SYS 2 selected as lead compressor.
or or
L O C A L / R E MO T E MO D E L E A D / L A G C O N T R O L
R E MO T E A U T OM A T I C

This mode should be selected when an ISN or RCC Lead/lag between systems may be selected to help
control is to be used to control the chiller. This mode equalize average run hours between systems on
will allow the ISN to control the following items: chillers with 2 refrigerant systems. Auto lead/lag
Remote Start/Stop, Cooling Setpoint, Load Limit, and allows automatic lead/lag of the two systems based
History Buffer Request. If the unit receives no valid on an average run hours of the compressors in each
ISN transmission for 5 minutes, it will revert back to system. A new lead/lag assignment is made whenever
the locally programmed values. all compressors shut down. The micro will then assign
Option 6 – Unit Control Mode: the “lead” to the system with the shortest average run
time.
C O N T R O L MO D E
R E T U R N L I Q U I D Option 9 – Condenser Fan Control Mode:

Unit control is based on return chilled liquid temp. Re- F A N C O N T R O L


turn Chilled Liquid Control can only be selected on units D I S C H A R G E PR E S S U R E
that have 4 to 6 compressors (dual system units).
or Condenser fans are controlled by discharge pressure
C O N T R O L MO D E only. This mode must be chosen.
L E A V I N G L I Q U I D
or

148 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

F A N C O N T R O L Option 12 – Power Fail Restart:


A M B I E N T & D S C H P R E S S P OWE R F A I L R E S T A R T
A U T OM A T I C
Do not select this option on R-410A chillers.
Chiller auto restarts after a power failure.
Option 10 – Manual Override Mode:
P OWE R F A I L R E S T A R T
M A N U A L O V E R R I D E MO D E M A N U A L
D I S A B L E D

After a power failure, the UNIT switch must be


This option allows overriding of the daily schedule toggled before restart at the unit is allowed.
that is programmed. MANUAL OVERRIDE MODE NORMALLY MANUAL RESTART should NOT BE
– DISABLED indicates that override mode has no SELECTED.
effect.
or Option 13 – Soft Start Enable/Disable:

M A N U A L O V E R R I D E MO D E S O F T S T A R T
E N A B L E D D I S A B L E D

Manual Override Mode is enabled. This is a service SOFT START “DISABLED” MUST be selected on all
function and when enabled, will allow the unit to chillers.
start when shut down on the daily schedule. It will This message may not be viewable on non-European
automatically be disabled after 30 minutes. chillers.

Option 11 – Current Feedback Options Option 14 – Unit Type:


Installed:
U N I T T Y P E
C U R R E N T F E E D B A C K L I Q U I D C H I L L E R
N O N E
The UNIT TYPE message cannot be modified under
the unit keys. 7
This mode should be selected when the panel is not
equipped with current sensing capability. “LIQUID CHILLER” must be dis-
or played, or damage to compressors or
C U R R E N T F E E D B A C K
other components will occur if oper-
O N E P E R U N I T
ated in the HEAT PUMP or CON-
DENSING UNIT modes.

This mode should be selected when an optional


2ACE Module is installed to allow combined current If unit type needs to be changed to make the unit a
monitoring of all systems by sensing current on the liquid chiller, remove power and then remove the
incoming line. jumper on J11-12. Reapply power to the micropanel
or and the microprocessor will store the change.

C U R R E N T F E E D B A C K Option 15 – Refrigerant Type:


O N E P E R S Y S T E M
R E F R I G E R A N T T Y P E
R – 41 0 A
This mode should be selected when an optional
2ACE module is installed to allow individual current Refrigerant type R-410A must be selected under Service
monitoring of each system. SYS 1 input is to J7 of the Mode. Refrigerant type is displayed under the Options
I/O. SYS 2 input is to J8 of the I/O. Key, but is only programmable in Service Mode.

JOHNSON CONTROLS 149


Unit Controls
FORM 150.67-NM1 (308)

Incorrect programming may cause F L A S H C A R D U P D A T I N G


damage to compressors. P L E A S E WA I T . . .

After the update is completed, an automatic reboot will


occur. If an error occurred, the following message will
appear with the error code and no reboot will occur:
Option 16 – Expansion Valve Type:
F L A S H C A R D U P D A T E
E X P A N S I O N V A L V E T Y P E E R R O R XXXXX
T H E R M O S T A T I C

Expansion valve type, thermostatic or electronic If the update resulted in an error, the original program
may be selected under Service Mode. Expansion will still be active. When an error occurs, assure the
valve type is displayed under the Options key, but is correct Flash Card was utilized. Incorrect chiller
only programmable in Service Mode. YCAL 0019 software will cause an error. If this is not the case, the
– 0066 chillers will typically always be equipped with Flash Card is most likely defective or the IPU and I/O
thermostaic expansion valves. combo board is bad.

Incorrect programming may cause Option 18 – Remote Temperature Reset:


damage to compressors.
R E MO T E T E M P R E S E T
IN P U T XXXXXXXXXXXXXX

Remote Temp Reset input selection is programmable


according to the type of input utilized. The following
Also see the UNIT KEYS PROGRAMMING QUICK options are available:
REFERENCE LIST in Table 15.
• DISABLED (default)
Option 17 – Flash Card Update: • 0.0 – 10.0 (DC)
• 2.0 – 10.0V (DC)
F L A S H C A R D U P D A T E
• 0.0 – 20.0 mA
D I S A B L E D
• 4.0 – 20.0 mA
A Flash Card is used to input the operating program
into the chiller IPU. A Flash Card is used instead of an
The options display message for Re-
EPROM. Normally, a Flash Card update is not required mote Temp Reset Input only appears if
and the message above will be displayed. the Temp reset Option is enabled under
Service Mode.
If the operating software is to be updated, insert the
Flash Card into the Flash Card input port. Turn off the
unit switch and set the FLASH CARD UPDATE TO
“ENABLED” using the ↑ and ↓ keys.

F L A S H C A R D U P D A T E
E N A B L E D

Press the ENTER key and the following message will


be displayed until the update has been completed. The
keypad and display will not respond during the update.
DO NOT reset or power down the chiller until the update
is completed.

150 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

Option 19 – Pump Control: Option 20 – Pump Selection:

Pump Control is utilized to operate the optional onboard The displays for this PUMP SELECTION option should
pump kit or to control an external pump through dry only appear if “YORK HYDRO KIT PUMPS = 2” are
contacts 23 and 24. To use this option, the following selected under Option 19. Presently, this option should
selection should be made in the Service Mode: not be used.

Y O R K H Y D R O CLOCK
K I T P U M P S = 1
The CLOCK display shows the current day, time, and
date. Pressing the CLOCK key will show the current
When YORK HYDRO KIT PUMPS = 1, the controls day, time, and date.
will be closed to run the pumps whenever any one of
the following conditions are true: It is important that the date and time be correct,
• Low Leaving Chilled Liquid Fault otherwise the daily schedule will not function as desired
• Any compressor is running if programmed. In addition, for ease of troubleshooting
via the History printouts, the day, time, and date should
• Daily Schedule is ON and Remote Stop is
be correct.
closed.
To change the day, time, and date press the CLOCK
Even if one of the above conditions
key. The display will show something similar to the
are true, the pump will not run if the following:
chiller has been powered up for less
than 30 seconds; or if the pump has T O D A Y I S F R I 0 8 : 5 1 A M
run in the last 30 seconds to prevent 2 5 J A N 0 2
pump overheating.
The line under the F is the cursor. If the day is correct,
E X T E R N A L press the ENTER/ADV key. The cursor will move under
E V A P P U M P the 0 in 08 hours. If the day is incorrect, press the ↑
(UP) or ↓ (DOWN) arrow keys until the desired day is
displayed and then press the ENTER/ADV key at which 7
EXTERNAL EVAP PUMP should be selected if an time the day will be accepted and the cursor will move
external pump is being controlled with the chiller pump under the first digit of the “2 digit hour”. In a similar
contacts. The operation will be the same as YORK manner, the hour, minute, meridian, month, day, and
HDRO KIT PUMPS = 1 year may be programmed, whenever the cursor is under
the first letter/numeral of the item. Press the ↑ (UP) or
The following option should not be selected. ↓ (DOWN) arrow keys until the desired hour, minute,
meridian; day, month, and year are displayed. Pressing
Y O R K H Y D R O the ENTER/ADV Key will save the valve and move the
K I T P U M P S = 2 cursor on to the next programmable variable.

Jumper J11 on the microboard must


be set to the “CLKON” position to turn
on the clock. If this is not done, the
clock will not function.

JOHNSON CONTROLS 151


Unit Controls
FORM 150.67-NM1 (308)

TABLE 15 – UNIT KEYS OPTIONS PROGRAMMING QUICK REFERENCE LIST

Options Key
Expansion Valve Type
(press Options Key
to adv.) (Thermoplastic or Electric)
(Programmed under Service
Display Language Mode, Viewable Only)
Must be programmed
System Switches for Thermostatic
on/off
Flash Card Update
Chilled Liquid Type
(water or glycol)
Remote Temp Reset

Ambient Control
Pump Control
(standard or low)

Pump Selection
Local/Remote Mode

Unit Control Mode


(Return or Leaving)

Display Units
(English or Metric)

System Lead/Lag Control


(Manual or Automatic)

Fan Control Mode

Manual Override Mode

Current Feedback Option

Power Failure Restart

Soft Start Option

Unit Type
(”Chiller” MUST be Selected
Via No Jumper Installed
(Viewable Only)

Refrigerant Type
R-410A
(Programmed under Service Mode)
Viewable Only)

Table 15 provides a quick reference list for the Unit key setpoints. LD07405d

152 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

SECTION 8 – UNIT OPERATION


CAPACITY CONTROL LEAVING CHILLED LIQUID CONTROL

To initiate the start sequence of the chiller, all run The setpoint, when programmed for Leaving Chilled
permissive inputs must be satisfied (flow/remote start/ Liquid Control, is the temperature the unit will control
stop switch), and no chiller or system faults exist. to within +/- the (control) cooling range. The Setpoint
High Limit is the Setpoint plus the Cooling Range. The
The first phase of the start sequence is initiated by the Setpoint Low Limit is the Setpoint minus the Cooling
Daily Schedule Start or any Remote Cycling Device. If Range. Fig. 18 should be utilized to aid in understanding
the unit is shut down on the daily schedule, the chilled the following description of Leaving Chilled Liquid
water pump microboard contacts (TB8 6-7) will close Control.
to start the pump when the daily schedule start time
has been reached. Once flow has been established and If the leaving chilled liquid temperature is above the
the flow switch closes, capacity control functions are Setpoint High Limit, the lead compressor on the lead
initiated, if the remote cycling contacts wired in series system will be energized along with the liquid line
with the flow switch are closed. solenoid. Upon energizing any compressor, the 60
second Anti-Coincidence timer will be initiated to
It should be noted that the chilled water pump contacts prevent multiple compressors from turning on.
(TB8 6-7) are not required to be used to cycle the chilled
water pump. However, in all cases the flow switch must If after 60 seconds of run-time the leaving chilled liquid
be closed to allow unit operation. temperature is still above the Setpoint High Limit,
the next compressor in sequence will be energized.
The control system will evaluate the need for cooling Additional compressors will be energized at a rate of
by comparing the actual leaving or return chilled liquid once every 60 seconds if the chilled liquid temperature
temperature to the desired setpoint, and regulate the remains above the Setpoint High Limit and the chilled
leaving or return chilled liquid temperature to meet that liquid temperature is dropping less than 3 °F/min. The
desired setpoint. lag system will not be allowed to start a compressor until
the lead system has run for 5 minutes.
SUCTION PRESSURE LIMIT CONTROLS
If the chilled liquid temperature falls below the Setpoint
The anticipatory controls are intended to prevent the High Limit but is greater than the Setpoint Low Limit,
unit from ever actually reaching a low-pressure cutout. loading and unloading do not occur. This area of control
Loading is prevented, if the suction pressure drops below is called the control range.
1.15 x suction pressure cutout (15% below the cutout).
Loading may reoccur after suction pressure rises above If the chilled liquid temperature drops to between
the unload point and a period of one minute elapses. This Setpoint Low Limit and 0.5 °F (.28 °C) below the
control is only operable if the optional suction pressure Setpoint Low Limit, unloading (a compressor turns off)
transducers are installed. occurs at a rate of 1 every 30 seconds. If the chilled liquid 8
temperature falls to a value greater than 0.5 °F (.28 °C)
DISCHARGE PRESSURE LIMIT CONTROLS below the Setpoint Low Limit but not greater than 1.5 °F
(.83 °C) below the Setpoint Low Limit, unloading occurs
The discharge pressure limit controls unload a system at a rate of 20 seconds. If the chilled liquid temperature
before it reaches a safety limit due to high load or dirty falls to a value greater than 1.5 °F (.83 °C) below the
condenser coils. The micro monitors discharge pressure Setpoint Low Limit, unloading occurs at a rate of 10
and unloads a system, if fully loaded, by one compressor seconds. If the chilled liquid temperature falls below
when discharge pressure exceeds the programmed cutout 1 °F above the low chilled liquid temperature cutout,
minus 10 PSIG (0.69 barg). Reloading will occur when unloading occurs at a rate of 10 seconds if it is greater
the discharge pressure on the affected system drops than 10 seconds.
to 85% of the unload pressure and 10 minutes have
In water cooling mode on R-410A chillers, the minimum
elapsed.
low limit of the control range will be 40.0ºF. For leaving
This control is only applicable if optional discharge chilled liquid temperature setpoint and control range
pressure transducers are installed. combinations that result in the low limit of the control
range being below 40.0ºF, the low limit will be reset
to 40.0ºF and the difference will be added to the high
limit. This will result in a control range the same size as
programmed but not allow the unit to run below 40.0ºF.
This control will not affect glycol chillers.
JOHNSON CONTROLS 153
Unit Operation
FORM 150.67-NM1 (308)

Hot gas, if present, will be the final step of capacity. Hot microprocessor will increase the setpoint high limit
gas is energized when only a single compressor is running according to the chart at right, with a maximum value
and LWT<SP. Hot gas is turned off as temperature rises allowed of 50 °F (See Fig. 19).
when LWT>SP + CR/2. If temperature remains below
the setpoint low limit on the lowest step of capacity, the If adding the setpoint adjust value to the setpoint high
micro will close the liquid line solenoid, after turning limit causes the setpoint high limit to be greater than 50
off hot gas, and pump the system down before turning °F, the setpoint high limit will be set to 50 °F, and the
off the last compressor in a system. difference will be added to the setpoint low limit.
The leaving chilled liquid setpoint is programmable Once a system runs for greater than 5 minutes, the
from 40 °F to 70 °F (4.4 °C to 21.1 °C) in water chilling
setpoint adjust will be set back to 0. This will occur
mode and from 10 °F to 70 °F (-12.2 °C to 21.1 °C) in
glycol chilling mode. In both modes, the cooling range while the system is still running.
can be from +/-1.5 °F to +/-2.5 °F (+/-.83 °C to 1.39

SETPOINT ADJUST (DEG. F)


°C).leaving chilled liquid control
6
5
LEAVING CHILLED LIQUID CONTROL 4
OVERRIDE TO REDUCE CYCLING 3
2
To avoid compressor cycling the micro will adjust the 1
setpoint upward temporarily. The last run time of the 0
system will be saved. If the last run time was greater 0 1 2 3 4 5 6
than 5 minutes, no action is to be taken. If the last run
time for the lead system was less than 5 minutes, the LAST RUN TIME OF LEAD SYSTEM (MINUTES)

FIG. 19 – SETPOINT ADJUST

30 sec. Control Range 60 sec.


unloading (no compressor staging) loading

LWT 44.0 °F 46.0 °F 48.0°


(6.7 °C) (7.8 °C) (8.9 °C)
Low Limit Setpoint High limit

Leaving Water Temp. Control – Compressor Staging


Setpoint = 46.0 °F (7.8 °C) Range = +/- 2 °F(1.1 °C)

FIG. 18 – LEAVING WATER TEMPERATURE CONTROL EXAMPLE


Each compressor in a system will be assigned an
LEAVING CHILLED LIQUID SYSTEM LEAD/LAG
arbitrary priority number 1, 2, or 1, 2, 3. The non-running
AND COMPRESSOR SEQUENCING
compressor within a system with the lowest priority
A Lead/Lag option may be selected to help equalize number will always be the next compressor to start. The
average run hours between systems with 2 refrigerant running compressor with priority number 1 will always
systems. This may be programmed under the OPTIONS be the next to shut off. Whenever a compressor is shut
key. Auto Lead/Lag allows automatic Lead/Lag of the two off, the priority numbers of all compressors will be
systems based on average run hours of the compressors decreased by 1 with wrap-around. This control scheme
in each system. Manual Lead/Lag selects specifically the assures the same compressor does not repeatedly cycle
sequence which the micro starts systems. on and off.

On a hot water start, once a system starts, it will turn on all Once the second system starts a compressor on a 2
compressors before the next system starts a compressor. system chillers, the micro will attempt to equally load
The microprocessor will sequence compressors within each system as long as the system is not limiting or
each circuit to maximize individual compressor run time pumping down. Once this occurs, loading and unloading
on individual compressors within a system to prevent will alternate between systems, loading the lead system
short cycling. first or unloading the lag system first.

154 JOHNSON CONTROLS


Unit Operation
FORM 150.67-NM1 (308)

RETURN CHILLED LIQUID CONTROL As an example of compressor staging (refer to Table 19),
(Can be used on Dual System 4, 5 & 6 Comp a chiller with six compressors using a Cooling Setpoint
Units Only) programmed for 45 °F (7.20 °C) and a Range Setpoint
of 10 °F (5.56 °C). Using the formulas in Table 20, the
Return chilled liquid control is based on staging the control range will be split up into six (seven including
compressors to match the cooling load. The chiller will hot gas) segments, with the Control Range determining
be fully loaded when the return water temperature is the separation between segments. Note also that the
equal to the Cooling Setpoint plus the Range. The chiller Cooling Setpoint is the point at which all compressors
will be totally unloaded (all compressors off) when the are off, and Cooling Setpoint plus Range is the point
return water temperature is equal to the Cooling Setpoint all compressors are on. Specifically, if the return water
(See sample in Table 16). At return water temperatures temperature is 55 °F (12.8 °C), then all compressors
between the Cooling Setpoint and Cooling Setpoint will be on, providing full capacity. At nominal gpm, this
plus Range, compressor loading and unloading will be would provide approximately 45 °F (7.2 °C) leaving
determined by the formulas in Table 17. water temperature out of the evaporator.

Return Chilled Liquid Control MUST If the return water temperature drops to 53.4 °F (11.9
°C), one compressor would cycle off leaving five
only be used when constant chilled
compressors running. The compressors would continue
liquid flow is ensured.
to cycle off approximately every 1.7 °F (.94 °C), with
the exception of hot gas bypass. Notice that the hot
The RANGE MUST always be pro- gas bypass would cycle on when the return water
grammed to equal the temperature temperature dropped to 46.25 °F (7.9 °C). At this point
drop across the evaporator when the one compressor would be running with hot gas.
chiller is “fully loaded”. Otherwise,
chilled liquid temperature will over or Should the return water temperature rise from this
under shoot. Variable flow must never point to 46.7 °F (8.2 °C), the hot gas bypass would shut
be used in return chilled liquid mode. off, still leaving one compressor running. As the load
increased, the compressors would stage on every 1.7
Normal loading will occur at intervals of 60 seconds °F (.94 °C).
according to the temperatures determined by the formulas.
Unloading will occur at a rate of 30 seconds according Also note that Table 17 not only provides the formulas
to the temperatures determined in the formulas used for the loading (ON POINT) and unloading (OFF
to calculate the on and off points for each step of POINT) of the system, the “STEP” is also shown in the
tables. The “STEP” is the incriment in the sequence of
capacity.
the capacity control scheme that can be viewed under
8
The return chilled liquid setpoint is programmable from the OPER DATA key. Please refer to the section on the
40 °F to 70 °F (4.4 °C to 21.1 °C) in water chilling mode DISPLAY/PRINT keys for specific information on the
and from 10 °F to 70 °F (-12.2 °C to 21.1 °C) in glycol OPER DATA key.
chilling mode. In both modes, the cooling range can be
from 4 °F to 20 °F (2.2° to 11.1 °C).

TABLE 16 – SAMPLE COMPRESSOR STAGING FOR RETURN WATER CONTROL


Compressor Staging for Return Water Control
4 Compressor
Cooling Setpoint = 45 °F (7.2 °C) Range = 10 °F(5.6 °C)
# of Comp 0 * 1+HG 1 2 3 4
ON
RWT 45 °F 46.25 °F 47.5 °F 50.0 °F 52.5 °F 55.0 °F
(7.2 °C) (7.9 °C) (8.6 °C) (10.0 °C) (11.4 °C) (12.8 °C)
*Unloading only

JOHNSON CONTROLS 155


Unit Operation
FORM 150.67-NM1 (308)

TABLE 17 – RETURN CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)


*STEP COMPRESSOR COMPRESSOR ON POINT COMPRESSOR OFF POINT
0 0 SETPOINT SETPOINT
1 1 W/HGB SP + CR/8 (Note 1) SETPOINT
2 1 NO HGB SP + CR/4 SP + CR/8
3 2 SP + 2*CR/4 (Note 2) SP + CR/4
4 2 SP + 2*CR/4 SP + CR/4 (Note 3)
5 3 SP + 3*CR/4 SP + 2*CR/4
6 4 SP + CR SP + 3*CR/4
Notes:
1. Step 1 is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during Pumpdown.
2. Step 3 is skipped when loading occurs.
3. Step 4 is skipped when unloading occurs.
* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.

RETURN CHILLLED LIQUID SYSTEM LEAD/ from starting 2 times in a row. The micro will not attempt
LAG AND COMPRESSOR SEQUENCING to equalize run time on individual compressors within
A lead/Lag option may be selected to help equalize a system.
average run hours between systems with 2 refigerant
systems. This may be programmed under the OPTIONS Each compressor in a system will be assigned an
key. Auto Lead/Lag of the 2 systems based on average arbitrary number 1, or 2. The non-running compressor
run hours of the compressors in each system. Manual within a system with the lowest priority number will
Lead/Lag selects specifically the sequence which the always be the next compressor to start. The running
micro starts the systems. compressor with priority number 1 will always be the
next compressor to shut off. Whenever a compressor is
The micro will sequence compressors load and unload shut off, the priority numbers of all compressors in each
systems according to Table 18. The microprocessor will system will be decreased by 1 with the wrap around.
lead/lag compressors within each circuit to maximize This control scheme assures the same compressor does
individual compressor run time for the purpose of not repeatedly cycle on and off.
lubrication. It will also prevent the same compressor

TABLE 18 – RETURN CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)


LEAD SYSTEM LAG SYSTEM
Step COMP 1 COMP 2 - COMP 1 COMP 2 -
0 OFF OFF - OFF OFF -
1 ON + HG OFF - See NOTE 1 OFF OFF -
2 ON OFF - OFF OFF -
3 ON OFF - See NOTE 2 ON OFF -
4 ON ON - See NOTE 3 OFF OFF -
5 ON ON - ON OFF -
6 ON ON - ON ON -
NOTES
1. Step is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during pumpdown. For Leaving Chilled
Liquid Control the Hot Gas Bypass solenoid is energized only when the lead compressor is running and the LWT < SP, the Hot Gas Bypass
solenoid is turned off when the LWT > SP + CR/2.
1. Step 1 is not used for loading or unloading.
2. Step 3 is skipped when loading occurs.
3. Step 4 is skipped when unloading occurs.

156 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

ANTI-RECYCLE TIMER EVAPORATOR HEATER CONTROL


The programmable anti-recycle timer assures that The evaporator heater is controlled by ambient air
systems do not cycle. This timer is programmable temperature. When the ambient temperature drops
under the PROGRAM key between 300 – 600 seconds. below 40 °F (4.4 °C) the heater is turned on. When the
Whenever possible, to reduce cycling and motor heating, temperature rises above 45 °F (7.2 °C) the heater is turned
the anti-recycle timer should be adjusted to 600 seconds. off. An under voltage condition will keep the heater off
The programmable anti-recycle timer starts the timer until full voltage is restored to the system.
when the first compressor in a system starts. The timer
begins to count down. If all of the compressors in a PUMPDOWN CONTROL
circuit cycle off, a compressor within the circuit will Each system has a pump-down feature upon shut-off.
not be permitted to start until the anti-recycle timer Manual pumpdown from the keypad is not possible. On
has timed out. If the lead system has run for less than 5 a non-safety, non-unit switch shutdown, all compressors
minutes, 3 times in a row, the anti-recycle timer will be but one in the system will be shut off. The LLSV will
extended to 10 minutes. also be turned off. The final compressor will be allowed
to run until the suction pressure falls below the cutout, or
ANTI-COINCIDENCE TIMER for 180 seconds, whichever comes first.
This timer is not present on single-system units. Two
timing controls are present in software to assure STANDARD CONDENSER FAN CONTROL
compressors within a circuit or between systems, do not Condenser fan operation must be programmed with
start simultaneously. The anti-coincidence timer assures the Options key under “Fan Control.” Condenser fan
there is at least a one minute delay between system starts control can be selected for Ambient Temp. and Discharge
on 2-circuit systems. This timer is NOT programmable. Pressure, or Discharge Pressure only.
The load timers further assure that there is a minimum
time between compressor starts within a system. The condenser fan control by “Ambient Temperature
and Discharge Pressure” is a feature that is integral to
EVAPORATOR PUMP CONTROL & YORK HY- the standard software control. If the optional discharge
DRO KIT PUMP CONTROL transducer is not installed, the condenser fans will operate
The evaporator pump dry contacts (CTB2 – terminals 23 based on outdoor ambient temperature only. Refer to the
– 24) are energized when any of the following conditions following pages for model specific details.
are true:
1. Low Leaving Chilled Liquid Fault The condenser fan control by “Discharge Pressure” is
2. Any compressor is running a feature that can be selected if the discharge pressure
3. Daily Schedule is ON, Unit Switch is ON and transducer is installed and fan cycling is not a concern.
Remote Stop is closed. Fan control by discharge pressure will work according 8
to the tables on the following pages. The fan control
The pump will not run if the micro panel has been on-pressure and fan differential off-pressure are
powered up for less than 30 seconds or if the pump programmable under the PROGRAM key.
has run in the last 30 seconds to prevent pump motor
overheating. The delay between turning on and off fan stages is
always fixed at 5 seconds.
Whenever the option “YORK HYDRO KIT PUMPS
= 1” is selected under the OPTIONS key, the pump When a fan stage is turned on by pressure, the on
control will be as described above. DO NOT SELECT pressure for the next stage is increased 20 PSIG and
the option “YORK HYDRO KIT PUMPS = 2” under ramped back to the programmed on pressure over the
the OPTIONS key. If a dual pump option is installed, next 20 seconds. Typically, standard ambient control
the active pump is selected by the selector switch. ON pressure should be programmed at 385 PSIG with
a differential of 125 PSIG.

JOHNSON CONTROLS 157


Unit Operation
FORM 150.67-NM1 (308)

When a fan stage is turned off (programmed on pressure


minus programmed differential), the off pressure for the
next stage is decreased 20 PSIG and ramped back to the
programmed off pressure minus the differential over the
next 20 seconds.

A low ambient kit MUST be installed


when “AMBIENT CONTROL LOW
AMBIENT” is selected under the OP-
TIONS key.

Compressor damage could occur if


programming does not match installed
hardware.

Detailed Standard Fan Control operation is shown in


Table 19 and 20.

158 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

STANDARD CONDENSER FAN CONTROL – YCAL0019 – YCAL0033


TABLE 19 – YCAL0012 – YCAL0033 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE

MICROBOARD
FAN CONTACTOR FAN #
ON* OFF* OUTPUT
STAGE
SYS 1 SYS 1 SYS 1
DP> Fan Crtl On DP < Fan Ctrl On
1 7M TB7-9 1
Press Press – Diff.Press
*DP > Fan Ctrl On **DP < Fan Ctrl On 7M TB7-9 1
2 Press and Fan Stage Press – & & &
1 is energized Diff. Press 8M TB7-10 3

TABLE 20 – YCAL0012 – YCAL0033 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY

MICROBOARD
FAN CONTACTOR FAN #
OUTPUT
STAGE ON OFF
SYS 1 SYS 1 SYS 1
DP > Fan Ctrl DP < Fan Ctrl On
1 7M TB7-9 1
On Press Press – (Diff. Press.)
DP > Fan Ctrl On 7M TB7-9 1
**DP < Fan Ctrl On
2 Press and Fan Stage & & &
Press – Diff. Press.
1 is energized 8M TB7-10 3
* When a fan stage is turned on, the on pressure for the next stage is increased ** When a fan stage is turned off (programmed on pressure minus
20 PSIG and ramped back to the programmed on pressure over the next 20 differential), the off pressure for the next stage is decreased 20
seconds. PSIG and ramped back to the programmed off pressure minus the
differential.

FAN #2

FAN #1

LD12211

FIG. 20 – YCAL0019 – YCAL0033 FAN LOCATION (TYPICAL)

JOHNSON CONTROLS 159


Unit Operation
FORM 150.67-NM1 (308)

STANDARD CONDENSER FAN CONTROL – YCAL0043 – YCAL0066


TABLE 21 – YCAL0043 – YCAL0066 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE.

MICRO BOARD
FAN CONTACTOR FAN #
ON* OFF* OUTPUT
STAGE
SYS 1 SYS 2 SYS 1 SYS 2 SYS 1 SYS 2
DP> Fan Crtl On DP < Fan Ctrl On
1
Press Press – Diff.Press 7M 10M TB7-9 TB10-9 1 2

DP > Fan Ctrl On


TB7-9 TB10-9
Press and Fan Stage DP < Fan Ctrl On 7M 10M 1 2
2 & &
1 is energized Press – Diff. Press & & & &
TB7-10 TB10-10
8M 11M 3 4

TABLE 22 – YCAL0043 – YCAL0066 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY

MICRO BOARD
FAN CONTACTOR FAN #
ON OFF OUTPUT
STAGE
SYS 1 SYS 2 SYS 1 SYS 2 SYS 1 SYS 2
DP > Fan Ctrl DP < Fan Ctrl On
1 7M 10M TB7-9 TB10-9 1 2
On Press Press – Diff. Press.
DP > Fan Ctrl On 7M 10M TB7-9 TB10-9 1 2
DP < Fan Ctrl On
2 Press and Fan Stage & & & & & &
Press – Diff. Press.
1 is energized 8M 11M TB7-10 TB10-10 3 4
* When a fan stage is turned on, the on pressure for the next stage is increased ** When a fan stage is turned off (programmed on pressure minus
20 PSIG and ramped back to the programmed on pressure over the next 20 differential), the off pressure for the next stage is decreased 20
seconds. PSIG and ramped back to the programmed off pressure minus the
differential.

FAN #3
FAN #2 FAN #4
FAN #1

LD11419

FIG. 21 – YCAL0043 – YCAL0066 FAN LOCATION (TYPICAL)

160 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

YCAL0019-0022 LOW AMBIENT FAN CONTROL OPTION

General The VFD control signal is sent from a liquid temperature


The low ambient option consists of a single phase sensor connected to a condenser coil return bend. The
Variable Frequency Drive (VFD) that controls the speed sensor is connected to S1 and COM terminals of the
of the first fan (Fan 1) in the fan staging sequence. The VFD in the control panel. The sensor must always be
VFD is located in the control panel. An example of the insulated. The location of the sensor is shown in Fig.
VFD location is shown in Fig. 22. 23.

BULB

50094

FIG. 23 – LIQUID LINE SENSING BULB LOCATION

The VFD will not only control fan speed in low ambient
conditions, but in all ambients based on the liquid
line temperatute. Speed control of the fan will occur
VFD
50093b whenever the liquid line solenoid is energized.
FIG. 22 – TYPICAL VFD LOCATION

Potentiometer Configuration
The VFD will control fan speed based on the liquid
temperature of the system. As liquid line temperature The VFD is pre-configured from the factory prior to
rises and falls, the fan speed will operate between shipping and should be ready for operation when the
minimum and full speed RPM. chiller arrives on site. Potentiometers allow adjustment of
the minimum speed and for selection of the temperature
control range. A quick check of the potentiometer setting
As liquid temperature rises, the VFD will ramp the speed is recommended. The potentiometer settings should be
of the fan from a minimum speed of about 200 Hz to in the position shown in Fig. 24. 8
maximum RPM while attempting to control liquid line
temperature between 65-75° F. If the liquid temperature
is below 65-75° F, the VFD will shut off the motor even
though the VFD is powered by 7M.

50095

FIG. 24 – POTENTIOMETER SETTINGS

JOHNSON CONTROLS 161


Unit Operation
FORM 150.67-NM1 (308)

Wiring
VFD wiring is simple and requires only single phase
power in, single phase power out and a 2-wire signal
from the liquid line temperature sensor. No start, stop or
other alternate power requirements are needed to operate
the VFD. Fig. 25 shows the power and control wiring
schematically as well as the actual connections.

LD11799A

FIG. 25 – WIRING

162 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

PROGRAMMING YCAL0012 – 0022


Condenser fan control type must be programmed under both
the OPTIONS and PROGRAM keys when a VFD is installed
on the chiller. Under the OPTIONS key, FAN CONTROL
must be programmed for DISCHARGE PRESSURE
CONTROL only. This will assure condenser fan control of
the chiller is solely by discharge pressure, with no ambient
control.

Under the PROGRAM Key, the FAN CONTROL ON


PRESSURE should be programmed for 385 PSIG and
the FAN DIFFERENTIAL OFF PRESSURE must be
programmed for 125 PSIG.

Programming as suggested assures the chiller control points


for the second fan in the fan staging sequence and the
inverter control points are matched for optimum control of
the fans at reduced ambient temperatures, assuring superheat
and oil control is not compromised. When the chiller and
VFD fan control points are programmed properly, the fans
will operate as outlined in Table 26

TABLE 23 – YCAL0012 – 0022 VFD LOW AMBIENT OPTION – CONDENSER FAN CONTROL OPERATION
CONTACTOR MICROBOARD FAN #
FAN STAGE ON OFF
SYS 1 SYS 1 SYS 1
Fan Speed
Is A Function Of
1: Liquid Temperature FAN Will Turn OFF
VFD Control Fan will turn on when When Liquid
liquid line temperature Temperature Drops
7M TB7-3 1 8
(1 fan
Variable Speed) is above 65º F. Speed Below 65 °F
increases with
temperature,

Discharge
Pressure
2: < 260 PSIG (Pressure Is
1 Fan VFD < Fan Control ON Pres-
385 PSIG,
Control sure of TB7- 3
Both Fans
2nd Fan 385 PSIG Minus Fan 7M & 8M & 1&3
Will Be Running Full
Full Speed Differential TB7-10
Speed
Under Contactor Pressure of 125 PSIG =
Control 260 PSIG)
Fan 1 Will Still
Be Running

JOHNSON CONTROLS 163


Unit Operation
FORM 150.67-NM1 (308)

YCAL0033 LOW AMBIENT FAN CONTROL OPTION

General If pressure continues to fall, VFD speed will decrease in


an effort to maintain discharge pressure. Speed may drop
The low ambient option consists of a VFD (Variable
to the point where the VFD turns the fan completely off or
Frequency Drive) that controls the speed of the first fan
virtually off with a continued drop in pressure.
(Fan 1) in the fan staging sequence. The VFD is located on
The VFD control input signal is from the discharge
the top of chiller above the compressor section. Examples
pressure transducer in the respective system. The
of the typical VFD location and enclosure mountings are
transducer signal feeds both the chiller microprocessor
shown in Figs. 26 & 27.
board and the VFD. The VFD controls the fan speed based
on discharge pressure.
The VFD will control fan speed when only a single fan is
running on a system. As discharge pressure rises and falls,
The VFD will control the fan speed not only in low
the fan speed will be increased from zero RPM to full
ambient conditions, but in all ambients based on discharge
speed. As discharge pressure continues to rise, the VFD
pressure. Speed control of the respective system will
will operate the fan at full speed and the second fan will be
occur whenever high voltage power is applied to the
brought on in a system, if needed. Whenever the second
VFD power inputs through the 7M contactor. The chiller
fan is brought on, the inverter will already be running the
microprocessor will energize the 7M and 10M contactors
first fan at full speed. When discharge pressure falls, the
whenever the system liquid line solenoid is energized.
chiller microprocessor will turn the second fan off by de-
energizing the fan contactor.
The VFD controls the speed of the fan based on a discharge
pressure setpoint and a differential control range. When
a compressor starts in a system, the inverter is activated
through the 7M contactor, which is controlled from the
respective liquid line solenoid valve control signal. At
discharge pressures below 260 PSIG, the VFD will turn the
fan off or speed will be reduced to all but small movements
in fan rotation.

The pressures indicated in this section


describing the VFD control will vary from
VFD to VFD. Expect tolerances for the
entire pressure range of control to poten-
LD12080
VFD Enclosure Location tially shift -0 PSIG/+24 PSIG.

FIG. 26 – TYPICAL VFD ENCLOSURE LOCATIONS


The VFD will ramp up the speed of the fan as pressure rises
above the low end of the speed control range. Throughout
the pressure control range, the VFD controls the speed of
the fan based on a discharge pressure in the range of approx
260-292 PSIG. At pressures above 292 PSIG, the VFD will
run the system fan at full speed.

As pressure drops below 292 PSIG, the VFD will slow


the speed of the fan to try to maintain discharge pressure
within the control range. The VFD will try to maintain
pressure in the range of 260-292 PSIG by raising and
lowering the speed of the fan. If pressure drops below
260 PSIG, the VFD will virtually turn the system fan
completely off. Some slight fan movement or very slow
rotation may be noted, although the fan may appear to stop
LD12081
completely.
VFD Enclosure

FIG. 27- TYPICAL VFD ENCLOSURE


CONFIGURATIONS

164 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

CONFIGURATION (JUMPERS AND POTENTIOMETER SETTINGS


POTENTIOMETERS) P1 P2
Each VFD is pre-configured at the factory prior to 292 PSI 32 PSI
shipping and should be ready for operation when
it arrives onsite. A quick check of the settings is
recommended. The jumpers must be in the positions
shown in the following Table.

VFD JUMPERS
J2 REMOVE —
J3 IN —
J4 REMOVE —
J5 IN —
J6 IN —
J7 IN —
J8 IN —
J9 IN FOR 60 HZ REMOVE FOR 50 HZ

Potentiometer settings are also preset at the factory.


The potentiometers should be in the positions shown
in the following table. The pots do not have numerical P1 P2
LD11300A
settings and are set according to the arrow positions
FIG. 29 – POTENTIOMETER SETTINGS
indicated. DO NOT change the potentiometer
settings unless they do not match the positioning of 29 show the power and control wiring schematically
the potentiometers shown in Fig. 29. P1 should be as well as the actual connections. The VFD controlled
full CW (292 PSIG) and P2 should be full CCW (32 fan will operate whenever the liquid line solenoid on
PSIG). Modifying these settings may cause damage to the respective system is energized
the chiller or control problems.
YCAL0033 PROGRAMMING
The P1 pot sets the setpoint which is the top end of the
control range. This setting is the discharge pressure at Condenser fan control type must be programmed under
which the fan will be operating at full speed. The P2 both the OPTIONS and PROGRAM keys when an VFD
pot sets the range. This is the range of pressure where is installed on the chiller. Under the OPTIONS key, FAN
the VSD modulates the fan speed from 0 RPM to full CONTROL must be programmed for DISCHARGE
speed. The range is subtracted from the setpoint to PRESSURE CONTROL only. This will assure the
calculate the 0 RPM pressure. condenser fan control is solely by discharge pressure
with no ambient control. 8
Wiring
VFD wiring is simple and requires only 3-phase power Under the PROGRAM key, the FAN CONTROL ON
in, 3-phase power out, and a 2-wire signal from the PRESSURE should be programmed for 425 PSIG
transducer. No start, stop, or other alternate power and the FAN DIFFERENTIAL OFF PRESSURE
requirements are needed to run the VFD. Fig’s 28 and should be programmed for 125 PSIG.

7M

150A L1 T1 150

151A L2 T2 151
SPEED CONDENSER
CONTR. FAN NO. 1
152A L3 T3 152

LD11301a
FIG. 28 – INVERTER POWER WIRING SCHEMATIC

JOHNSON CONTROLS 165


Unit Operation
FORM 150.67-NM1 (308)

TB3 TB1 TB2

TB3

WHT BLK 152A 151A


151A 150A
150A 150 151 152

TO MICROBOARD (P4) TO PANEL 7M TO FAN #1 (EXISTING HARNESS)

FIG. 30 – INVERTER WIRING LD11302a

Programming as suggested assures the chiller control assuring superheat and oil control is not compromised.
points for the second fan in the fan staging sequence When the chiller and VFD fan control points are
and the inverter control points are matched for optimum programmed properly, the fans will operate as outlined
control of the fans at reduced ambient temperatures, in Table 24.
TABLE 24 – YCAL033 VFD LOW AMBIENT OPTION – CONDENSER FAN CONTROL OPERATION

MICRO
CONTACTOR FAN #
FAN STAGE ON OFF BOARD
SYS 1 SYS 1 SYS 1
Fan Speed
Is A Function Of
1: Discharge
Pressure. FAN Will Turn Off
VFD Control or Turn Very Slowly
When The Liquid 7M TB7-3 1
(1 fan When Pressure Drops
Line Solenoid Is Below 260 PSIG.
Variable Speed) Energized. Speed
Increases With
Pressure

Discharge
2: Pressure
< 260 PSIG (Pres-
1 Fan VFD
425 PSIG, sure Is
Control 7M TB7-3
Both Fans < Fan Control ON
2nd Fan & & 3
Will Be Running Full Pressure of
Full Speed 8M TB7-10
Speed 425 PSIG Minus Fan
Under Contactor Differential
Control Pressure of 125
PSIG = 300 PSIG)

166 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

YCAL0043 – 0066 LOW AMBIENT FAN CONTROL OPTION

General
The low ambient option consists of a VFD (Variable The VFD control input signal is from the discharge
Frequency Drive) for each system that controls the pressure transducer in the respective system. The
speed of the first fan (Fan 1, Sys #1 or Fan 2, Sys # 2) transducer signal feeds both the chiller microprocessor
in the fan staging sequence. The VFD’s are located in board input and the VFD.
an enclosure in the compressor/piping/heat exchanger
section on (2) compressor chillers. System # 1 VFD The VFD will control the fan speed not only in low
is located on the bottom and System # 2 is on the top. ambient conditions, but in all ambients based on
Single system chillers have the VFD installed on the top discharge pressure. Speed control of the respective
of chiller above the compressor section. Examples of system will occur whenever high voltage power is
the typical VFD location and enclosure mountings are applied to the VFD power inputs through the 7M (Sys 1)
shown in Figs. 31 and 32. or 10M (Sys 2) contactors. The chiller microprocessor
will energize the 7M and 10M contactors whenever the
The VFD will control fan speed when only a single fan respective system liquid line solenoid is energized.
is running on a system. As discharge pressure rises,
the fan speed will be increased from zero RPM to full The VFD controls the speed of the fan based on a
speed. As discharge pressure continues to rise, the VFD discharge pressure setpoint and a differential control
will operate the fan at full speed and the second fan will range. When a compressor starts in a system, the
be brought on in a system, if needed. Whenever the inverter is activated through the 7M (Sys 1) or 10
second fan is brought on, the inverter will already be M (Sys 2) contactor, which is controlled from the
running the first fan at full speed. respective liquid line solenoid valve control signal.
At discharge pressures below 260 PSIG, the VFD
If discharge pressure falls, the chiller microprocessor will turn the fan off or speed will be reduced to small
will turn the second fan off by de-energizing the fan movements in fan rotation.
contactor. If pressure continues to fall, VFD speed will
decrease in an effort to maintain discharge pressure. The pressures indicated in this
Speed may drop to the point where the VFD turns the section describing the VFD control
fan completely off or virtually off with a continued drop will vary from VFD to VFD. Expect
in pressure. tolerances for the entire pressure
range of control to potentially shift
-0 PSIG/+24 PSIG. 8

LD12080
LD11298

Dual System VFD Enclosure Location Single System VFD Enclosure Location

FIG. 31 – TYPICAL VFD ENCLOSURE LOCATIONS


JOHNSON CONTROLS 167
Unit Operation
FORM 150.67-NM1 (308)

#2
SYS.

#1
SYS.

LD12081

Single System VFD Enclosure

LD11299a
Dual System VFD Enclosure

FIG. 32 – TYPICAL VFD ENCLOSURE CONFIGURATIONS

The VFD will ramp up the speed of the fan as pressure rises VFD JUMPERS
above the low end of the speed control range. Throughout J2 REMOVE —
the pressure control range, the VFD controls the speed J3 IN —
J4 REMOVE —
of the fan based on discharge pressure in the range of J5 IN —
approx 260-292 PSIG. At pressures above 260 PSIG, J6 IN —
J7 IN —
the VFD will run the system fan at full speed. J8 IN —
REMOVE FOR
J9 IN FOR 60 HZ
As pressure drops below 292 PSIG, the VFD will 50 HZ
slow the speed of the fan to try to maintain discharge
pressure within the control range. The VFD will try Potentiometer settings are also preset at the factory.
to maintain pressure in the range of 260-292 PSIG by The potentiometers should be in the positions shown
raising and lowering the speed of the fan. If pressure in Fig.34. The pots do not have numerical settings and
drops below 260 PSIG, the VFD will virtually turn the are set according to the arrow positions indicated. DO
system fan completely off. Some slight fan movement NOT change the potentiometer settings unless they do
or very slow rotation may be noted, although the fan not match the positioning of the potentiometers shown
may appear to stop completely. in Fig. 34. P1 should be full CW (260 PSIG) and
P2 should be full CCW (32 PSIG). Modifying these
CONFIGURATION (JUMPERS AND settings may cause damage to the chiller or control
POTENTIOMETERS) problems.
Each VFD is pre-configured at the factory prior to The P1 pot sets the setpoint which is the top end of the
shipping and should be ready for operation when control range. This setting is the discharge pressure
it arrives onsite. A quick check of the settings is at which the fan will be operating at full speed. The
recommended. The jumpers must be in the positions P2 pot sets the range. This is the range of pressure
shown in the following Table. where the VSD modulates the fan speed from 0 RPM
to full speed. The range is subtracted from the setpoint
to calculate the 0 RPM pressure.

168 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

Wiring POTENTIOMETER SETTINGS

VFD wiring is simple and requires only 3-phase power P1 P2


in, 3-phase power out, and a 2-wire signal from the 292 PSI 32 PSI
transducer. No start, stop, or other alternate power
requirements are needed to run the VFD. Fig’s 33 and
34 show the power and control wiring schematically
as well as the actual connections. The VFD controlled
fan will operate whenever the liquid line solenoid on
the respective system is energized.

PROGRAMMING
Condenser fan control type must be programmed
under both the OPTIONS and PROGRAM keys when
a VFD is installed on the chiller. Under the OPTIONS
key, FAN CONTROL must be programmed for
DISCHARGE PRESSURE CONTROL only. This will
assure condenser fan control of the chiller is solely by
discharge pressure, with no ambient control.
P1 P2
LD11300a
Under the PROGRAM Key, the FAN CONTROL ON
FIG. 34 – POTENTIOMETER SETTINGS
PRESSURE should be programmed for 425 PSIG
and the FAN DIFFERENTIAL OFF PRESSURE
must be programmed for 125 PSIG.

Programming as suggested assures the chiller control


points for the second fan in the fan staging sequence
and the inverter control points are matched for optimum
control of the fans at reduced ambient temperatures.
When the chiller and VFD fan control points are
programmed properly, the fans will operate as outlined
in Table 25.

7M

150A L1 T1 150

151A L2 T2 151
SPEED CONDENSER
CONTR. FAN NO. 1
152A L3 T3 152

10M
250A L1 T1 250

251A L2 T2 251
SPEED CONDENSER
CONTR. FAN NO. 2
252A L3 T3 252

FIG. 33 – INVERTER POWER WIRING SCHEMATIC LD11301

JOHNSON CONTROLS 169


Unit Operation
FORM 150.67-NM1 (308)

TB3 TB1 TB2

TB3

WHT BLK 152A 151A


151A 150A
150A 150 151 152

TO MICROBOARD (P4) TO PANEL 7 M TO FAN #1 (EXIS TING HARNESS)

TB3 TB1 TB2


TB3

WHT BLK 252A 251A 250A 250 251 252

TO MICROBOARD (P7) TO PANEL 10 M TO FAN #2 (EXIS TING HARNESS)


LD11302

FIG. 35 – INVERTER WIRING

TABLE 25 – YCAL0043-0066 VFD LOW AMBIENT OPTION – CONDENSER FAN CONTROL OPERATION
CONTACTOR MICROBOARD FAN #
FAN STAGE ON OFF
SYS 1 SYS 2 SYS 1 SYS 2 SYS 1 SYS 2
Fan Speed
Is A Function Of
1: Discharge FAN Will Turn
Pressure. Off or Turn Very
VFD Control
When The Liquid Slowly When 7M 10M TB7-3 TB10-9 1 2
(1 Fan Line Solenoid Pressure Drops
Variable Speed) Is Energized, Below 260 PSIG.
Speed Increases
With Pressure

Discharge
Pressure
2: < 260 PSIG
1 Fan VFD (Pressure Is
425 PSIG,
Control < Fan Control 7M 10M TB7-3 TB10-9 1 2
Both Fans
2nd Fan ON Pressure of & & and and & &
Will Be Running
Full Speed 425 PSIG Minus 8M 11M TB7-10 TB10-10 3 4
Full Speed
Under Contactor Fan Differential
Control Pressure of
125 PSIG = 300
PSIG)

170 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

LOAD LIMITING Simultaneous operation of Remote


Load Limiting is a feature that prevents the unit from Load Limiting and EMS-PWM Tem-
loading beyond the desired value. 2 and 4 compressor perature Reset (described on following
units can be load limited to 50%. This would allow only pages) cannot occur.
1 compressor per system to run. 3 and 6 compressor units
can be load limited to 33% or 66%. The 66% limit would
allow up to 2 compressors per system to run, and the COMPRESSOR RUN STATUS
33% limit would allow only 1 compressor per system
Compressor run status is indicated by closure of contacts
to run. Five-compressor units may be load limited to
at CTB2 – terminals 25 to 26 for system 1 and CTB2
40% (1 compressor per system runs) or 80% (up to 2
– terminals 27 to 28 for system 2.
compressors per system) are permitted to run. No other
values of limiting are available.
ALARM STATUS
There are two ways to load limit the unit. The first is System or unit shutdown is indicated by normally-open
through remote communication via an ISN. Load limit alarm contacts opening whenever the unit shuts down on
stages are sent through YORK Talk on pages 9 and 10 a unit fault, locks out on a system fault, or experiences
of feature 54. Page 9 is stage 1 load limit and page 10 a loss of power to the chiller electronics . System 1
is stage 2 load limit. alarm contacts are located at CTB2 – terminals 29 to 30.
System 2 alarm contacts are located at CTB2 – terminals
A second method of load limiting the unit is through 31 to 32. The alarm contacts will close when conditions
closing dry contacts connected to the Load Limit allow the unit to operate, or the fault is reset during a
(CTB1 – Terminals 13 -21). Load limiting involves loss of power, the contacts will remain open until power
closing the Load Limit input with a dry contact. Load is reapplied and no fault conditions exist.
limiting is either 80%, 66% or 50%, depending on the
number of compressors on the unit. Table 24 shows
the load limiting permitted for the various number of
compressors. Only Stage 1 is available utilizing a dry
contact.
TABLE 26 – COMPRESSOR OPERATION –
LOAD LIMITING

COMPRESSORS STAGE 1 STAGE 2


IN UNIT
2 50% - 8
3 66% 33%
4 50% -
5 80% 40%
6 66% 33%

JOHNSON CONTROLS 171


Unit Operation
FORM 150.67-NM1 (308)

BAS/EMS TEMPERATURE RESET USING


A VOLTAGE OR CURRENT SIGNAL

The Remote Reset Option allows the Control Center If a 4-20mA signal is supplied, it is applied to terminals
of the unit to reset the chilled liquid setpoint using a A+ and A- and jumper JP1 on the I/O board must be
0 - 10VDC input, or a 4-20mA input connected to CTB1 installed between pin 1 and 2. To calculate the chilled
terminals A- and A+. Whenever a reset is called for, the liquid setpoint for values between 4mA and 20 mA use
the following formula:
change may be noted by pressing the Cooling Setpoints
key twice. The new value will be displayed as “REM Setpoint = Local Chilled Liquid Setpoint + °Reset
SETP = XXX °F.”
If a 0 - 10VDC signal is supplied, it is applied to °Reset = (mA signal - 4) x (*Max Reset Value)
terminals A+ and A-, and jumper JP1 on the I/O board 16
Example:
must be inserted between pins 2 and 3. To calculate
Local Chilled Liquid Setpoint = 45° (7.22 °C)
the reset chilled liquid setpoint for values between 0VDC *Max Reset Value = 10 °F (5.56 °C)
and 10VDC use the following formula: Input Signal = 12 mA
Setpoint = Local Chilled Liquid Setpoint + °Reset (English)
°Reset = 8mA x 10 °F = 5 °F Reset
°Reset = (DC voltage signal) x (*Max Reset Value) 16
10 Setpoint = 45 °F + 5 °F = 50 °F
Example:
Local Chilled Liquid Setpoint = 45 °F (7.22 °C) (Metric)
*Max Reset Value = 20 °F (11.11 °C) °Reset = 8mA x 5.56 °C = 2.78 °C Reset
Input Signal = 6VDC 16
Setpoint = 7.22 °C + 2.78 °C = 10.0 °C
(English)
°Reset = 6VDC x 20 °F = 12 °F Reset A 240-24 Volt Ratio Transformer (T3)
10
New Setpoint = 45 °F + 12 °F = 57 °F is used to derive nominal 12 volt output
from the 120 volt supply.
(Metric)
°Reset = 6VDC x 11. 11 °C = 6.67 °C Reset
10
New Setpoint = 7.22 °C + 6.67 °C = 13.89 °C

* Max Reset Value is the “Max EMS-PWM Remote Temp. Reset” setpoint
value described in the programming section under Cooling Setpoints.
Programmable values are from 2 °F to 40 °F (1.11 °C to 11.11
°C).

172 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

SECTION 9 – SERVICE AND TROUBLESHOOTING


CLEARING HISTORY BUFFERS SYS 1 COMP 3 STATUS TB7-5 IS:
The history buffers may be cleared by pressing the HIS- SYS 1 HGBP STATUS TB7-7 IS:
TORY key and then repeatedly pressing the UP arrow SYS 2 COMP 1 STATUS TB10-2 IS:
key until you scroll past the last history buffer choice. SYS 2 LLSV STATUS TB10-3 IS:
The following message will be displayed: SYS 2 COMP 2 STATUS TB10-4 IS:
SYS 2 COMP 3 STATUS TB10-5 IS:
I I N I T I A L I Z E H I S T O R Y SYS 1 FAN OUTPUT 1 TB7-8 IS:
E N T E R = Y E S SYS 1 FAN OUTPUT 2 TB7-9 IS:
SYS 1 FAN OUTPUT 3 TB7-10 IS:
Pressing the ENTER/ADV key at this display will cause SYS 2 FAN OUTPUT 1 TB10-8 IS:
the history buffers to be cleared. Pressing any other key SYS 2 FAN OUTPUT 2 TB10-9 IS:
will cancel the operation. SYS 2 FAN OUTPUT 3 TB10-10 IS:
EVAP HEATER STATUS TB8-2 IS:
DO NOT CLEAR BUFFERS. Impor- SYS 1 ALARM STATUS TB8-3 IS:
SYS 2 ALARM STATUS TB9-2 IS:
tant information may be lost. Contact
EVAP PUMP STATUS TB8-6,7 IS:
factory service.
SYS 2 HGBV STATUS TB10-7 IS:
SPARE DO TB8-4 IS:
SPARE DO TB8-5 IS:
SPARE DO TB8-8, 9 IS:
SPARE DO TB9-4 IS:
SERVICE MODE SYS 1 EEV OUTPUT TB5-1, 2 = XXX%
SYS 2 EEV OUTPUT TB6-1, 2 = XXX%
Service Mode is a mode that allows the user to enable SYS 1 COND FAN SPEED J15-1,5 = XXX%
or disable all of the outputs (except compressors) on the SYS 2 COND FAN SPEED J15-2,6 = XXX%
unit, change chiller configuration setup parameters and SPARE AO J15-3,7 = XXX%
view all the inputs to the microboard. SPARE AO J15-4,8 = XXX%
DATA LOGGING MODE 1 = ON, 0 = OFF
To enter Service Mode, turn the Unit Switch off and DATA LOGGING TIMER X SECS
press the following keys in the sequence shown; PRO- SOFT START (disabled)
GRAM, UP ARROW, UP ARROW, DOWN ARROW, REFRIGERANT TYPE (R410A only)
DOWN ARROW, ENTER. Service Mode will time out EXPANSION VALVE TYPE (Thermostatic Only)
after 30 minutes and return to normal control mode, if REMOTE TEMP RESET OPTION =
the panel is accidentally left in this mode. Otherwise, REMOTE INPUT SERVICE TIME =
turning the unit switch on will take the panel out of “NORTH AMERICAN FEATURE SET ENABLED”
Service Mode. HYDRO PUMP SELECTION
EVAP PUMP TOTAL RUN HOURS
SERVICE MODE – OUTPUTS SYS 1 HOURS
After pressing the key sequence as described, the control SYS 2 HOURS 9
will enter Service Mode permitting the outputs (except SYS 1 STARTS
compressors), operating hours, refrigerant type, expan- SYS 2 STARTS
sion valve type, and start/hour counters to be viewed/
Each display will also show the output connection on
modified. The ENTER/ADV key is used to advance
the microboard for the respective output status shown.
through the outputs. Using the ↑ and ↓ (UP/DOWN ) ar-
For example:
row keys will turn the respective digital output on/off
or modify the value. S Y S 1 L L S V S T A T U S
T B 10 - 3 I S O F F
Following is the order of outputs that will appear as the
ENTER/ADV key is pressed:
This display indicates that the system 1 liquid line sole-
SYS 1 COMP 1 STATUS TB7-2 IS: noid valve is OFF, and the output connection from the
SYS 1 LLSV STATUS TB7-3 IS: microboard is coming from terminal block 10 – pin 3.
SYS 1 COMP 2 STATUS TB7-4 IS:
JOHNSON CONTROLS 173
Service and Troubleshooting
FORM 150.67-NM1 (308)

Pressing the ↑ (UP) arrow key will energize the liquid SERVICE MODE – ANALOG & DIGITAL
line solenoid valve and “OFF” will change to “ON” in INPUTS
the display as the LLSV is energized. Energizing and
de-energizing outputs may be useful during trouble- After entering Service Mode (PROGRAM ↑↑ ↓↓),
shooting. all digital and analog inputs to the microboard can be
viewed by pressing the OPER DATA key. After pressing
SERVICE MODE – CHILLER CONFIGURATION the OPER DATA key, the ↑ (UP) arrow and ↓ (DOWN)
arrow keys are used to scroll through the analog and
After the Outputs are displayed, the next group of
digital inputs.
displays relate to chiller configuration and start/hour
counters. Data logging, soft start, refrigerant type, pump Following is the order of analog and digital inputs that
control selection and expansion valve type all must be will appear when sequenced with the ↓ (Down) arrow
programmed to match actual chiller configuration. key:
(analog inputs)
Soft start (disabled), Refrigerant Type SYS 1 SUCT PRESSURE
(R410A), and Expansion Valve Type UNIT TYPE
(Thermostatic), and North American SYS 1 *DISCH PRESSURE
Feature (Enabled) MUST be properly SYS 1** SUCTION TEMP.
programmed or damage to compres- SYS 2** SUCTION TEMP.
sors and other system components AMBIENT AIR TEMP.
may result. LEAVING LIQUID TEMP.
RETURN LIQUID TEMP.
Following is a list of chiller configuration selections, in SYS 2 SUCTION PRESSURE
order of appearance: SYS 2 SPARE
DATA LOGGING MODE = : DO NOT MODIFY SYS 2 *DISCH PRESSURE
DATA LOGGING TIMER = : DO NOT MODIFY
SYS 1 MTR VOLTS
SOFT START
SYS 2 MTR VOLTS
REFRIGERANT TYPE
(digital inputs)
EXPANSION VALVE TYPE
PWM TEMP RESET INPUT
REMOTE TEMP RESET OPTION LOAD LIMIT INPUT
REMOTE INPUT SERVICE TIME FLOW SW / REM START
FEATURE SET SPARE
SINGLE SYSTEM SELECT
PUMP CONTROL SELECTION
SYS 1 MP / HPCO INPUT
SYS 1 HOURS SYS 2 MP / HPCO INPUT
SYS 2 HOURS * The discharge pressure transducer is optional on some models.
SYS 1 STARTS ** The suction temp. sensor is on EEV units only.

SYS 2 STARTS
The analog inputs will display the input connection,
The last displays shown on the above list are for the ac-
the temperature or pressure, and corresponding input
cumulated run and start timers for each system. All val-
voltage such as:
ues can also be changed using the ↑ (UP) and ↓ (Down)
arrow keys, but under normal circumstances would not
S Y S 1 S U C T P R J 7 - 1 0
be required or advised. After the last start display, the
2 . 1 V D C = 8 1 P S I G
micro will display the first programmable value under
the PROGRAM key.
This example indicates that the system 1 suction
pressure input is connected to plug 7 – pin 10 (J7-10)
on the I/O board. It indicates that the voltage is 2.1
volts dc which corresponds to 81 PSIG (5.6 bars)
suction pressure.

174 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

The digital inputs will display the input connection and TABLE 28 – I/O DIGITAL OUTPUTS
ON/OFF status such as: TB7-2 SYS 1 Compressor 1
TB7-3 SYS 1 Liquid Line Solenoid Valve
F L OW SW / R E M S T A R T
TB7-4 SYS 1 Compressor 2
J 13 - 5 I S O N
TB7-5 SYS 1 Compressor 3
This indicates that the flow switch/remote start input is TB7-7 SYS 1 Hot Gas Bypass Valve
connected to plug 13- pin 5 (J13-5) on the microboard, TB10-2 SYS 2 Compressor 1
and is ON (ON = +30VDC unregulated input, OFF = TB10-3 SYS 2 Liquid Line Solenoid Valve
0VDC input on digital inputs). TB10-4 SYS 2 Compressor 2
TB10-5 SYS 2 Compressor 3
CONTROL INPUTS/OUTPUTS TB7-8 SYS 1 Condenser Fan Output 1
Tables 27 through 30 are a quick reference list providing TB7-9 SYS 1 Condenser Fan Output 2
the connection points and a description of the inputs and TB7-10 SYS 1 Condenser Fan Output 3
outputs respectively. All input and output connections TB10-8 SYS 2 Condenser Fan Output 1
pertain to the connections at the microboard.
TB10-9 SYS 2 Condenser Fan Output 2
TABLE 27 – I/O DIGITAL INPUTS TB10-10 SYS 2 Condenser Fan Output 3
TB8-2 Evaporator Heater
J13-2 Unit ON/OFF Switch
TB8-3 SYS 1 Alarm
J13-3 Load Limit Stage 2 on 3, 5 & 6 Comp. Units
TB9-2 SYS 2 Alarm
J13-4 Load Limit Stage 1
TB8-6 & 7 Evaporator Pump Starter
J13-5 Flow Switch and Remote Start/Stop
TB10-7 SYS 2 Hot Gas Bypass Valve
J13-6 Spare
Single System Select TABLE 29 – I/O ANALOG INPUTS
J13-7
(Jumper = Single Sys, No Jumper = Two Sys)
SYS 1 Suction Transducer
CR1
J13-8 J7-10 -or-
(Sys 1 Motor Protector/High Pressure Cutout)
SYS 1 Low Pressure Switch
CR2
J13-10 Unit Type: Chiller = NO Jumper J11-12 to +24 VDC
(Sys 2 Motor Protector/High Pressure Cutout)
J11-12 YCUL Condensing Unit = Jumper J11-12 to +24 VDC
(Do NOT Use)
J7-11 SYS 1 Discharge Pressure Transducer (Optional)
J6-9 Ambient Air Temp. Sensor
J6-7 Leaving Chilled Liquid Temp. Sensor
J6-8 Return Chilled Liquid Temp. Sensor
SYS 2 Suction Pressure Transducer
J9-10 -or-
SYS 2 Low Pressure Switch

J9-11
SYS 2 Discharge Pressure Transducer
(Optional)
9
J7-12 Unit/SYS 1 Voltage
J9-12 SYS 2 Voltage
J11-11 Remote Temperature Reset

TABLE 30 – I/O ANALOG OUTPUTS


N/A Not Applicable

JOHNSON CONTROLS 175


Service and Troubleshooting
FORM 150.67-NM1 (308)

TB6 TB5 I/O BOARD


J15

TB1

TB7

J3

TB8

J5

IPU
BOARD
TB9
J6

J7

J8
TB10

J9

J10

J14 JP1
J13 J11
J12
LD12721

FIG. 36 – MICROBOARD LAYOUT

176 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

CHECKING INPUTS AND OUTPUTS TABLE 31 – OUTDOOR AIR SENSOR


TEMPERATURE/VOLTAGE/
CORRELATION
Digital Inputs
Refer to the unit wiring diagram. All digital inputs are VOLTAGE
connected to J13-1 of the I/O board. The term “digital” TEMP °F (Signal Input TEMP °C
refers to two states – either on or off. As an example, to Return)
when the flow switch is closed, 30 volts DC will be 0 0.7 -18
applied to J13, pin 5 (J13-5) of the I/O board. If the 5 0.8 -15
flow switch is open, 0 volts DC will then be present at
10 0.9 -12
J13-5.
15 1.0 -9
Pin 1 of J13 is an unregulated 30VDC source used to 20 1.1 -7
supply the DC voltage to the various user contacts, unit 25 1.2 -4
switch, flow switch, etc. This DC source is factory wired 30 1.4 -1
to CTB1, terminal 13. Any switch or contact used as a 35 1.5 2
digital input would be connected to this terminal, with
40 1.7 4
the other end connecting to its respective digital input on
the microboard. Any time a switch or contact is closed, 45 1.8 7
30VDC would be applied to that particular digital input. 50 2.0 10
Any time a switch or contact is open, 0VDC would be 55 2.2 13
applied to that particular digital input. 60 2.3 16
65 2.5 18
Typically, voltages of 24 – 36VDC could be measured
70 2.6 21
for the DC voltage on the digital inputs. This voltage
75 2.8 24
is in reference to ground. The unit case should be suf-
ficient as a reference point when measuring digital input 80 2.9 27
voltages. 85 3.1 29
90 3.2 32
Analog Inputs – Temperature 95 3.4 35
Refer to the unit wiring diagram. Temperature inputs are 100 3.5 38
connected to the microboard on plug J6. These analog 105 3.6 41
inputs represent varying DC signals corresponding to 110 3.7 43
varying temperatures. All voltages are in reference to
115 3.8 46
the unit case (ground). Following are the connections
for the temperature sensing inputs: 120 3.9 49
125 4.0 52
Outside Air Sensor 130 4.1 54
J6-6 = +5VDC regulated supply to sensor. 9
J6-9 = VDC input signal to the microboard.
See Table 29 for voltage readings that corre
spond to specific outdoor temperatures.
J6-3 = drain (shield connection = 0VDC) Return

JOHNSON CONTROLS 177


Service and Troubleshooting
FORM 150.67-NM1 (308)

TABLE 32 – ENTERING/LEAVING CHILLED LIQUID Liquid & Refrigerant Sensor Test Points
TEMP. SENSOR, TEMPERATURE/ (Table 32)
VOLTAGE CORRELATION
Entering Chilled Liquid Sensor
VOLTAGE J6-5 = +5VDC regulated supply to sensor.
TEMP °F (Signal Input TEMP °C J6-8 = VDC input signal to the I/O board. See
to Return) Table 32 for voltage readings that correspond
10 1.33 -12 to specific liquid temperatures.
12 1.39 -11 J6-2 = drain (shield connection = 0VDC) Return
14 1.46 -10
Leaving Chilled Liquid Temperature Sensor
16 1.51 -9
18 1.58 -8 J6-4 = +5VDC regulated supply to sensor.
J6-7 = VDC input signal to the microboard. See
20 1.65 -7
Table 32 for voltage readings that correspond
22 1.71 -6
to specific liquid temperatures.
24 1.78 -4 J6-1 = drain (shield connection = 0VDC) Return
26 1.85 -3
28 1.91 -2
30 1.98 -1
32 2.05 0
34 2.12 1
36 2.19 2
38 2.26 3
40 2.33 4
42 2.40 6
44 2.47 7
46 2.53 8
48 2.60 9
50 2.65 10
52 2.73 11
54 2.80 12
56 2.86 13
58 2.92 14
60 2.98 16
62 3.05 17
64 3.11 18
66 3.17 19
68 3.23 20
70 3.29 21
72 3.34 22
74 3.39 23
76 3.45 24
78 3.5 26
80 3.54 27

178 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

Analog Inputs – Pressure


V = (Pressure in PSIG x .01) + .5
Refer to the unit wiring diagram. Pressure inputs are or
connected to the microboard on plugs J7 and J9. These V = (Pressure in BARG x .145) + .5
analog inputs represent varying dc signals corresponding
to varying pressures. All voltages are in reference to the where V = dc voltage output
unit case (ground). Pressure = pressure sensed by transducer

System 1 discharge and suction pressures will be


connected to J7 of the microboard. System 2 discharge The I/O board connections for the Discharge Trans-
and suction pressure transducers will be connected to ducers:
J9 of the microboard.
System 1 Discharge Transducer
The discharge transducers are optional on all units. If the
discharge transducers are not installed, no connections J7-6 = +5VDC regulated supply to transducer.
are made to the microboard and the discharge pressure J7-11 =VDC input signal to the microboard. See
readout on the display would be zero. the formula above for voltage readings
that correspond to specific discharge
The suction pressure transducers are standard on all pressures.
YCAL’s. The suction pressure transducers have a range J7-7 = +5VDC return
of 0 to 400 PSIG. The output will be linear from 0.5VDC J7-2 = drain (shield connection = 0VDC)
to 4.5VDC over the 400 PSIG (27.5 barg) range.
System 2 Discharge Transducer
The discharge transducers have a range from 0 to 650
PSIG. The output will be linear from 0.5VDC to 4.5VDC
over the 600 PSIG (41.25 barg) range. Following is the J9-6 = +5VDC regulated supply to transducer.
formula that can be used to verify the voltage output of J9-11 = VDC input signal to the microboard. See
the transducer. All voltage reading are in reference to the formula above for voltage readings
ground (unit case). that correspond to specific discharge
pressures.
TABLE 33 – PRESSURE TRANSDUCERS J9-7 = +5VDC return
0-400 PSIG SUCTION 0-600 PSIG DISCHARGE J9-2 = drain (shield connection = 0VDC)
PRESSURE TRANSDUCER PRESSURE TRANSDUCER
PRESSURE VOLTAGE PRESSURE VOLTAGE
PSIG VDC PSIG VDC
0 0.5 0 0.5
50 1.0 75 1.0
100 1.5 150 1.5
150 2.0 225 2.0
200 2.5 300 2.5 9
250 3.0 375 3.0
300 3.5 450 3.5
350 4.0 525 4.0
400 4.5 600 4.5

RED WIRE = 5V, BLACK WIRE = 0V, WHITE/GREEN WIRE = SIGNAL

TEST POINTS:
Suction Pressure:
System 1: ...............................................Microboard J7-10 to J7-9
System 2: ...............................................Microboard J9-10 to J9-9
Discharge Pressure:
System 1: ...............................................Microboard J7-11 to J7-7
System 2: ...............................................Microboard J9-11 to J9-7

JOHNSON CONTROLS 179


Service and Troubleshooting
FORM 150.67-NM1 (308)

The suction transducers have a range from 0 to 400 PSIG Digital Outputs
(27.5 barg). The output will be linear from 0.5VDC to
Refer to the unit wiring diagram and Fig. 37. The digital
4.5VDC over the 400 PSIG (27.5 barg) range. Following
outputs are located on TB7, TB8, and TB9 and TB-10 of
is a formula that can be used to verify the voltage output
the microboard. ALL OUTPUTS ARE 120VAC with the
of the transducer. All voltage reading are in reference to
exception of TB8-6 to TB8-7 which are the contacts that
ground (unit case).
can be used for a remote evaporator pump start signal.
The voltage applied to either of these terminals would
V = (Pressure in PSIG x .02) + .5
or be determined by field wiring.
V = (Pressure in barg x .29) + .5
Each output is controlled by the microprocessor by
where V = dc voltage input to micro switching 120VAC to the respective output connection
Pressure = pressure sensed by transducer energizing contactors, evaporator heater, and solenoids
according to the operating sequence (see Fig. 37).
Following are the I/O board connections for the Suction
Transducer: 120VAC is supplied to the I/O board via connections
at TB7-1, TB7-6, TB10-1, TB10-6, TB8-1 and TB9-1.
System 1 Suction Transducer Fig. 37 illustrates the relay contact architecture on the
J7-5 = +5VDC regulated supply to transducer. microboard.
J7-10 = VDC input signal to the microboard. SYS 1
TB7-2 COMP 1
See the formula above for voltage readings that
correspond to specific suction pressures. TB7-3 LLSV 1
J7-9 = +5VDC return TB7
SYS 1
TB7-4 COMP 2
J7-1 = drain (shield connection = 0VDC)
SYS 1
TB7-5 COMP 3

System 2 Suction Transducer TB7-7


SYS 1
HGSV
J9-5 = +5VDC regulated supply to transducer. SYS 1
J9-10 = VDC input signal to the microboard. TB7-8 FAN 2
TB7
See the formula above for voltage readings that SYS 1
TB7-9 FAN 1
correspond to specific suction pressures.
SYS 1
J7-9 = +5VDC return TB7-10 FAN 3
J7-11 = drain (shield connection = 0VDC)
SYS 2
TB10-2 COMPR 1 (4)

TB10-3 LLSV 2
TB10
SYS 2
TB10-4 COMPR 2 (5)
SYS 2
TB10-5 COMPR 3 (6)

SYS 2
TB10-7 HGSV

TB10-8
TB10
TB10-9 SYS 2
FAN 2
SYS 2
TB10-10 FAN 4

TB8-6 EVAP
TB8-7 PUMP
TB8
HEAT EXCH
TB8-2 HEATER

LD12722

FIG. 37 – I/O BOARD RELAY CONTACT


ARCHITECTURE

180 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

OPTIONAL PRINTER INSTALLATION


The micro panel is capable of supplying a printout of Parts
chiller conditions or fault shutdown information at any The following parts are required:
given time. This allows operator and service personnel
to obtain data and system status with the touch of the
keypad. In addition to manual print selection, the micro 1. WEIGH-TRONIX model 1220 printer.
panel will provide an automatic printout whenever a 2. 2.25” (5.7cm) wide desk top calculator paper.
fault occurs. Detailed explanation of the print function
3. 25 ft. (7.62m) maximum length of Twisted Pair
is given under “Print Key” located in the Keypad and
Shielded Cable (minimum 3 conductor), #18 AWG
Display section.
stranded, 300V minimum insulation.
YORK recommends the field tested WEIGH-TRONIX 4. One 25 pin Cannon connector and shell.
model 1220 printer (or former IMP 24). This is a com- Connector: Cannon P/N DB-25P or equivalent.
pact low cost printer that is ideal for service work and
Shell: Cannon P/N DB-C2-J9.
data logging.

The WEIGH-TRONIX printer can be obtained by con- Assembly and Wiring


tacting WEIGH-TRONIX for purchase information at:
All components should be assembled and wired as
WEIGH-TRONIX shown in FIG. 38. Strip the outside insulation back
2320 Airport Blvd. several inches and individual wires about 3/8” (9.5 mm)
Santa Rosa, CA 95402 to connect the cable at the Microboard. Do not connect
Phone: 1-800-982-6622 or 1-707-527-5555 the shield at the printer-end of the cable.
(International Orders Only)
Obtaining a Printout
The part number for the printer that is packaged specifi-
cally for YORK is P/N 950915576. The cable to connect A printout is obtained by pressing the “PRINT” key on
the printer can either be locally assembled from the parts the keypad and then pressing either the “OPER DATA”
listed, or ordered directly from WEIGH-TRONIX under key or “HISTORY” key.
part number 287-040018.

Chiller Microboard Printer


TB3

TB3-3 TXD 2 RD 9
TB3-2 CTS 5 CTS

TB3-5 GND 7 SG

Shield (connect shield to Pin 5 Do not connect shield


of the connector. at printer end.

LD12723

FIG. 38 – PRINTER TO MICROBOARD ELECTRICAL CONNECTIONS

JOHNSON CONTROLS 181


Service and Troubleshooting
FORM 150.67-NM1 (308)

TROUBLESHOOTING
TABLE 34 – TROUBLESHOOTING

PROBLEM CAUSE SOLUTION

No display on panel. 1. No 115VAC to 24 VAC 1a. Check wiring and fuse


Unit will not operate. Transformer 1FU

b. Check wiring emergency


stop contacts 5 to L of TB1
Terminal Block.

c. Replace Control Transformer

2. No 24VAC to Microboard 2. Check wiring Control


Transformer to Microboard.

3. Control Transformer defective, no 3. Replace Control Transformer


24VAC output.

4. Short in wire to temp. sensors 4. Unplug connections at IPU II


or pressure transducers. & I/O Board to isolate.

5. Defective IPU II & I/O Board 5. Replace IPU II & I/O Board
or the Display Board. or the Display Board.

Contact YORK
Service before
Replacing circuit
Boards!

“FLOW SWITCH/REM 1. No chilled liquid flow. 1. Check chilled liquid flow.


STOP NO RUN PERMISSIVE”
2. Flow switch improperly 2. Check that the flow switch
installed. is installed according to
manufacturer’s
instructions.

3. Defective flow switch. 3. Replace flow switch.

4. Remote cycling device open. 4. Check cycling devices


connected to terminals
13 and 14 of the CTB1
Terminal Block.

“LOW SUCTION PRESSURE” 1. Improper suction pressure 1. Adjust per recommended


FAULT cutouts adjustments. settings.

2. Low refrigerant charge. 2. Repair leak if necessary


and add refrigerant.

3. Fouled filter dryer. 3. Change dryer/core.


CONT’D

182 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

TROUBLESHOOTING (CONT’D)

PROBLEM CAUSE SOLUTION

“LOW SUCTION PRESSURE” 4. TXV defective. 4. Replace TXV.


FAULT (CONT’D)
5. Reduced flow of chilled 5. Check GPM (See “Limita
tions” liquid through the
cooler in Installation section).
Check operation of pump,
clean pump strainer, purge
chilled liquid system of air.

6. Defective suction pressure 6. Replace transducer/low


transducer/low pressure pressure switch or faulty
switch or wiring. wiring. Refer to “Service”
section for pressure/voltage
formula.

7. LLSV defective 7. Replace LLSV

“HIGH DISCHARGE 1. Condenser fans not operating 1. Check fan motor,


PRESSURE” FAULT or operating backwards. and contactors. Assure fan
blows air upward.

2. Too much refrigerant. 2. Remove refrigerant.

3. Air in refrigerant system. 3. Evacuate and recharge


system.

4. Defective discharge 4. Replace discharge pressure


pressure transducer. transducer. Refer to Service
section for pressure/voltage
formula.

“LOW LIQUID TEMP” 1. Improperly adjusted leaving 1. Re-program the leaving 9


FAULT chilled liquid temp. cutout chilled liquid temp. cutout.
(glycol only).

2. Micro panel setpoint/range 2. Re-adjust setpoint/range.


values improperly programmed.

3. Chilled liquid flow too low. 3. Increase chilled liquid flow –


refer to Limitations in Instal-
lation section.

4. Defective LWT or RWT sensor 4. Compare sensor against a


(assure the sensor is properly known good temperature
installed in the bottom of the well sensing device. Refer to
with a generous amount of heat) Service section for temp./
conductive compound). voltage table. CONT’D

JOHNSON CONTROLS 183


Service and Troubleshooting
FORM 150.67-NM1 (308)

TROUBLESHOOTING (CONT’D)

PROBLEM CAUSE SOLUTION

“MP / HPCO” FAULT 1. Compressor internal motor 1. Verify refrigerant charge is


protector (MP) open. not low. Verify superheat
setting of °10 – 15 °F (5.6° –
8. 3 °C). Verify correct com-
pressor rotation. Verify
compressor is not over
loaded.

2. External overload tripped. 2. Determine cause and reset.

3. HPCO switch open. 3. See “High Press. Disch.”


Fault.

4. Defective HPCO switch. 4. Replace HPCO switch.

5. Defective CR relay. 5. Replace relay.

COMPRESSOR(S) WON’T 1. Demand not great enough. 1. No problem. Consult


START “Installation” Manual to aid
in understanding compres-
sor operation and capacity
control.

2. Defective water temperature 2. Compare the display with a


sensor. thermometer. Should be
within +/- 2 degrees. Refer
to Service section for RWT/
LWT temp./voltage table.

3. Contactor/Overload failure. 3. Replace defective part.

4. Compressor failure. 4. Diagnose cause of failure


and replace.

LACK OF COOLING EFFECT 1. Fouled evaporator surface. 1. Contact the local YORK
Low suction pressure will service representative.
be observed.

2. Improper flow through the 2. Reduce flow to within chiller


evaporator. design specs. See Limita-
tions in Installation section.

3. Low refrigerant charge. 3. Check subcooling and add


Low suction pressure will charge as needed.
be observed.

184 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

SECTION 10 – MAINTENANCE
It is the responsibility of the equipment owner to provide Exercise care when cleaning the coil
maintenance on the system. so that the coil fins are not damaged.

IMPORTANT
If system failure occurs due to improper maintenance
during the warranty period, YORK will not be liable
for costs incurred to return the system to satisfactory
operation. The following is intended only as a guide and OPERATING PARAMETERS
covers only the chiller unit components. It does not cover Regular checks of the system should be preformed to
other related system components which may or may not ensure that operating temperatures and pressures are
be furnished by YORK. System components should be within limitations, and that the operating controls are set
maintained according to the individual manufacture’s within proper limits. Refer to the Operation, Start-Up,
recommendations as their operation will affect the and Installation sections of this manual.
operation of the chiller.
ON-BOARD BATTERY BACK-UP
COMPRESSORS U5 is the Real Time Clock chip located on the 031-
02630 IPU II board that maintains the date/time and
Oil Level check stores customer programmed setpoints. The Real Time
Clock is a 128K bram, P/N 031-02565-000. The IPU
The oil level can only be tested when the compressor is II board must have JP1 installed when the 128K bram
running in stabilized conditions, to ensure that there is is installed.
no liquid refrigerant in the lower shell of the compressor.
When the compressor is running at stabilized conditions, Do not confuse JP1 on the IPU II
the oil level must be between 1/4 and 3/4 in the oil sight
(031-02630) board with JP1 on the I/O
glass. Note: at shutdown, the oil level can fall to the
(031-02550) board.
bottom limit of the oil sight glass. Use YORK “V” oil
when adding oil.

Oil Analysis
The oil used in these compressors is pale yellow in color PLATE AND FRAME HEAT EXCHANGER
(POE oil). If the oil color darkens or exhibits a change in (EVAPORATOR) HEATER
color, this may be an indication of contaminants in the
refrigerant system. If this occurs, an oil sample should
The Plate and Frame Heat Exchang-
be taken and analyzed. If contaminants are present, the
system must be cleaned to prevent compressor failure. er (evaporator) heater is 120VAC.
Disconnecting 120VAC power from
Never use the scroll compressor to the unit, at or below freezing tem-
pump the refrigerant system down into peratures, can result in damage to the
a vacuum. Doing so will cause internal evaporator and unit as a result of the
arcing of the compressor motor which chilled liquid freezing.
will result in failure of compressor.
OVERALL UNIT INSPECTION 10
In addition to the checks listed on this page, periodic
CONDENSER FAN MOTORS overall inspections of the unit should be accomplished
Condenser fan motors are permanently lubricated and to ensure proper equipment operation. Items such as
require no maintenance. loose hardware, component operation, refrigerant leaks,
unusual noises, etc. should be investigated and corrected
CONDENSER COILS immediately.
Dirt should not be allowed to accumulate on the
condenser coil surfaces. Cleaning should be as often as
necessary to keep coils clean.
JOHNSON CONTROLS 185
Maintenance
FORM 150.67-NM1 (308)

ISN CONTROL
Received Data (Control Data) TABLE 36 – ISN TRANSMITTED DATA
The unit receives 8 data values from the ISN. The first
4 are analog values and the last 4 are digital values. ISN
CHARACTER TYPE DATA
PAGE
These 8 data values are used as control parameters
when in REMOTE mode. When the unit is in LOCAL Leaving Chilled
P11 8-11 Analog
Liquid Temp.
mode, these 8 values are ignored. If the unit receives no
Return Chilled
valid ISN transmission for 5 minutes it will revert back P12 12-15 Analog
Liquid Temp.
to all local control values. Table 35 lists the 5 control
P13 16-19 Analog ----
parameters. These values are found under feature 54
on the ISN. P14 20-23 Analog ----
SYS 1 Suction
P15 24-27 Analog
TABLE 35 – ISN RECEIVED DATA Temp. (EEV Only)
P16 28-31 Analog Ambient Air Temp.
ISN
CONTROL DATA SYS 1 Suction
PAGE
P17 32-35 Analog Superheat
SETPOINT
P03 (EEV Only)
COOLING
SYS 1 Run Time
P04 LOAD LIMIT STAGE (0,1, 2) P18 36-39 Analog
(Seconds)
P05 –
P06 – P19 40-43 Analog SYS 1 Suction
Pressure
START/STOP COMMAND
P07
(0 = STOP, 1 = RUN) SYS 1 Discharge
P20 44-47 Analog
P08 — Pressure
P09 — P21 48-51 Analog ----
HISTORY BUFFER REQUEST P22 52-55 Analog ----
P10
(0 = CURRENT DATA, 1 = LAST HISTORY DATA)
SYS 1 EEV
P23 56-59 Analog Output %
(EEV Only)
Transmitted Data
SYS 1
P24 60-63 Analog
After receiving a valid transmission from the ISN, the Anti-Recycle Timer
unit will transmit either operational data or history buffer Anti-Coincidence
P25 64-67 Analog
data depending on the “History Buffer Request” on Timer
ISN PAGE 10. Data must be transmitted for every ISN P26 68-71 Analog
SYS 2 Suction
page under feature 54. If there is no value to be sent to a Temp. (EEV Only)
particular page, a zero will be sent. TABLES 36 and 37 SYS 2 Run Time
P27 72-75 Analog
show the data values and page listings for this unit. (Seconds)
SYS 2
P28 76-79 Analog
Suction Pressure
ISN PAGES listed are ENG PAGE
SYS 2
REFERENCES and must be decoded P29 80-83 Analog
Discharge Pressure
to the corresponding PAGE REF P30 84-87 Analog ----
point map related to the communica- P31 88-91 Analog ----
tions protocol type utilized. The latest SYS 2
point map information is listed on the P32 92-95 Analog Suction Superheat
Johnson Controls Group Equipment (EEV Only)
Integration website. SYS 2
P33 96-99 Analog
Anti-Recycle Timer
SYS 2 EEV
P34 100-103 Analog Output %
(EEV Only)
P35 104-107 Analog # of Compressors
P36 108 Digital SYS 1 Alarm
P37 109 Digital SYS 2 Alarm

186 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

ISN CONTROL (CON’T)


TABLE 36 – ISN TRANSMITTED DATA (CONT’D)
ISN ISN
CHARACTER TYPE DATA CHARACTER TYPE DATA
PAGE PAGE
Evaporator Heater SYS 1 Condenser
P38 110 Digital P61 133 Coded
Status Fan Stage
Evaporator Pump P62 134 Coded ----
P39 111 Digital
Status
SYS 2 Condenser
P63 135 Coded
SYS 1 Fan Stage
P40 112 Digital
Comp. 2 Run
P64 136 Coded ----
SYS 2
P41 113 Digital Unit Control Mode
Comp. 2 Run
(0=Leaving Water,
SYS 1 Liquid Line 1=Return Water,
P42 114 Digital Solenoid Valve or P65 137 Coded 2=Discharge Air,
EEV Pilot Solenoid 3=Suction Press.,
SYS 1 Hot Gas 4=Cooling
P43 115 Digital 5=Heating)
Bypass Valve
SYS 1 P66 138-141 Analog Anti-Recycle Timer
P44 116 Digital
Comp. 2 Run Leaving Chilled Liquid
P67 142-145 Analog
SYS 2 Temp. Cutout
P45 117 Digital
Comp. 2 Run Low Ambient
P68 146-149 Analog
SYS 2 Liquid Line Temp. Cutout
P46 118 Digital Solenoid Valve or P69 150-153 Analog ----
EEV Pilot Solenoid
Low Suction
P70 154-157 Analog
Lead System Pressure Cutout
P47 119 Digital
(0=SYS 1, 1=SYS 2)
High Discharge
P71 158-161 Analog
SYS 1 Pressure Cutout
P48 120 Digital
Comp.3 Run
P72 162-165 Analog Setpoint
SYS 2
P49 121 Digital P73 166-169 Analog Cooling Range
Comp. 3 Run
P74 170-173 Analog ----
Chilled Liquid Type
P50 122 Digital P75 174-177 Analog ----
(0=Water, 1=Glycol)
Ambient Control Mode SYS 1 Discharge
P51 123 Digital (0=Std. Ambient, P76 178-181 Analog Temp.
1=Low Ambient) (EEV Only-Optional)
Local/Remote SYS 1 Discharge
Control Mode P77 182-185 Analog Superheat
P52 124 Digital (EEV Only- Optional)
(0=Local,
1=Remote) SYS 2 Discharge
Units P78 186-189 Analog Temp.
P53 125 Digital (EEV Only- Optional)
(0=Imperial, 1= SI)
Lead/Lag Control SYS 2 Discharge
P54 126 Digital Mode P79 190-193 Analog Superheat
(0=Manual,1= Remote) (EEV Only- Optional)
P55 127 Digital ---- P80 194 Digital ---- 10
* SYS 1 P81 195 Digital ----
P56 128 Coded
Operational Code P82 196 Digital ----
* SYS 1 P83 197 Digital ----
P57 129 Coded
Fault Code
P84 198 Digital ----
* SYS 2
P58 130 Coded
Operational Code
* SYS 2
P59 131 Coded
Fault Code
P60 132 Coded ----

JOHNSON CONTROLS 187


Maintenance
FORM 150.67-NM1 (308)

ISN CONTROL (CON’T)


TABLE 37 – ISN OPERATIONAL AND FAULT CODES
P56/58 OPERATIONAL CODE P57/59 FAULT CODE
0 NO ABNORMAL CONDITION 0 NO FAULT
1 UNIT SWITCH OFF 1 VAC UNDER VOLTAGE
2 SYSTEM SWITCH OFF 2 LOW AMBIENT TEMPERATURE
3 LOCK-OUT 3 HIGH AMBIENT TEMPERATURE
4 UNIT FAULT 4 LOW LEAVING CHILLED LIQUID TEMP
5 SYSTEM FAULT 5 HIGH DISCHARGE PRESSURE
6 REMOTE SHUTDOWN 6 HIGH DIFFERENTIAL OIL PRESSURE
7 DAILY SCHEDULE SHUTDOWN 7 LOW SUCTION PRESSURE
8 NO RUN PERMISSIVE 8 HIGH MOTOR CURRENT
9 NO COOL LOAD 9 LLSV NOT ON
10 ANTI-COINCIDENCE TIMER ACTIVE 10 LOW BATTERY WARNING
11 ANTI-RECYCLE TIMER ACTIVE 11 HIGH OIL TEMPERATURE
12 MANUAL OVERRIDE 12 HIGH DISCHARGE TEMPERATE
13 SUCTION LIMITING 13 IMPROPER PHASE ROTATION
14 DISCHARGE LIMITING 14 LOW MOTOR CURRENT / MP / HPCO
15 CURRENT LIMITING 15 MOTOR CURRENT UNBALANCED
16 LOAD LIMITING 16 LOW DIFFERENTIAL OIL PRESSURE
17 COMPRESSOR(S) RUNNING 17 GROUND FAULT
18 HEAT PUMP LOAD LIMITING 18 MP /HPCO
19 LOW EVAPORATOR TEMPERATURE
INCORRECT REFRIGERANT
20
PROGRAMMED
21 POWER FAILURE, MANUAL RESET
REQUIRED
22 UNIT MOTOR CURRENT
23 LOW SUPERHEAT
24 SENSOR FAIL
25 DISCHARGE INHIBIT
26 MP/HPCO INHIBIT
27 PUMP TRIP
28 PUMP FAIL MAKE FLOW
* The operational and fault codes sent to ISN pages 56 through 59 are defined in Table 36. Note that this table of fault and operational codes
is for all DX products.

188 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

BACNET AND MODBUS DATA COMMUNICATION

Data can be read and in some cases modified using In some cases, BACnet parameters may need to be
a serial communication BACnet or Modbus network modified. Modification is accomplished by pressing
connection. This information allows communications of the PROGRAM, DOWN ARROW, DOWN ARROW,
chiller operating parameters and external control changes DOWN ARROW, DOWN ARROW, and ENTER keys
to setpoint, load limiting, and start/stop commands. in sequence. The list below shows the displays for the
values that may be modified:

DE MODIFIER ADDRESS P2 PROTOCOL


XXXXX XXXXXXXXXX

DE MODIFIER OFFSET P2 MANUAL MAC


XX ADDRESS XXX

P1 PROTOCOL P2 BAUD RATE


XXXXXX XXXXX

P1 MANUAL MAC P2 PARITY


ADDRESS XXX XXXXX

P1 BAUD RATE P2 STOP BITS


XXXXX X

P1 PARITY REAL TIME ERROR ##


XXXXX RESET 1 = YES, 0 = NO 0

P1 STOP BITS
X

10

JOHNSON CONTROLS 189


Maintenance
FORM 150.67-NM1 (308)

The table below shows the minimum, maximum, and default values.

TABLE 38 - MINIMUM, MAXIMUM AND DEFAULT VALUES


DESCRIPTION MINIMUM MAXIMUM DEFAULT
DE MODIFIER ADDRESS -1 41943 -1
DE MODIFIER OFFSET -1 99 -1
P1 BAUD RATE 1200 76800 4800
1200, 4800, 9600, 19200, 38400, 76800, AUTO SELECTABLE
P2 BAUD RATE 1200 57600 1200
1200, 4800, 9600, 19200, 38400, 57600 SELECTABLE
P1, P2 MANUAL MAC ADDRESS -1 127 -1
P1, P2 PARITY NONE IGNORE NONE
NONE, EVEN, ODD, IGNORE SELECTABLE
P1 PROTOCOL BACNET API BACNET
BACNET, API SELECTABLE
P2 PROTOCOL TERMINAL MODBUS CLIENT API
TERMINAL, MODBUS IO, MODBUS SERVER, API, MODBUS CLIENT SELECTABLE
P1, P2 STOP BITS 1 2 1
RESET REAL TIME ERROR NO YES NO

190 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

The table below shows the real time error numbers and a description of each.

TABLE 39 - REAL TIME ERROR NUMBERS


ERROR NUMBER (##) DESCRIPTION
0 ALL OK
1 DATUM TYPE OK TEST FAILED
2 ENGLISH TEXT TOO LONG
3 FLOATING POINT EXCEPTION
4 GET PACKET FAILED
5 GET TYPE FAILED
6 INVALID UNIT CONVERSION
7 INVALID HARDWARE SELECTION
8 REAL TIME FAULT
9 SPANISH TEXT TOO LONG
10 THREAD EXITED
11 THREAD FAILED
12 THREAD STALLED
13 IO BOARD RESET
14 BRAM INVALID
15 BACNET SETUP FAILED

10

JOHNSON CONTROLS 191


Maintenance
FORM 150.67-NM1 (308)

Chiller data that can be read and modified using specific Modbus Register Addresses; and the data associated with
the addresses, is outlined in the following description:

SERIAL COMMUNICATION ANALOG VALUE DATA


This data can be read and modified using a BACnet or Modbus network connection. The Modbus Register Address
for these points is 1025 + AV #.

AV BACNET NAME ANALOG VALUE DESCRIPTION


SETPOINT
1 REM_SETP COOLING SETPOINT (HP ONLY), 99 = AUTO
(40 °F - 70 °F)
2 SP_REM_SP_S1 SYS 1 SETPOINT (SUCTION PRESSURE CONTROL)
3 LOAD_LIMIT LOAD LIMIT STAGE (0, 1, 2)
4 REM_CR COOLING RANGE (DAT MODE ONLY)
5 SP_REM_SP_S2 SYS 2 SETPOINT (SUCTION PRESSURE CONTROL)
6 REM_SP_HEAT HEATING SETPOINT (HP ONLY) 99 = AUTO (95 °F - 122 °F)
7 HP_MODE MODE (HP ONLY) (0 = PANEL, 1 = COOLING, 2 = HEATING)

SERIAL COMMUNICATION BINARY VALUE DATA


This data can be read and modified using a BACnet or Modbus network connection. The Modbus Register Address
for these points is 1537 + BV #.

BV BACNET NAME BINARY VALUE DESCRIPTION


1 START_STOP START / STOP COMMAND
2 SS_SYS1 SYS 1 START / STOP COMMAND (SUCTION PRESSURE CONTROL)
3 SS_SYS2 SYS 2 START / STOP COMMAND (SUCTION PRESSURE CONTROL)

SERIAL COMMUNICATION ANALOG INPUT DATA


This data can be read using a BACnet or Modbus network connection and can NOT be modified using this connection.
The Modbus Register Address for these points is 513 + AI #.

AI BACNET NAME ANALOG INPUT DESCRIPTION


1 LCHLT LEAVING CHILLED LIQUID TEMP
2 RCHLT RETURN CHILLED LIQUID TEMP
3 DAT DISCHARGE AIR TEMP (COND UNIT ONLY)
4 S1_SUCT_TEMP SYS 1 SUCTION TEMPERATURE (EEV AND COND UNIT ONLY)
5 OAT AMBIENT AIR TEMPERATURE
6 S1_SUCT_SH SYS 1 SUCTION SUPERHEAT (EEV ONLY)
7 S1_RUN_TIME SYS 1 RUN TIME (SECONDS)
8 S1_SUCT_PR SYS 1 SUCTION PRESSURE
9 S1_DSCH_PR SYS 1 DISCHARGE PRESSURE
10 S1_CIR_TEMP SYS 1 COOLER INLET REFRIGERANT TEMPERATURE (R-407C ONLY)
11 S1_DEF_TEMP SYS 1 DEFROST TEMPERATURE (HP ONLY)
12 S1_EEV_OUT SYS 1 EEV OUTPUT % (EEV ONLY)
13 S1_AR_TIMER SYS 1 ANTI-RECYCLE TIMER
14 AC_TIMER ANTI-COINCIDENT TIMER
15 S2_SUCT_TEMP SYS 2 SUCTION TEMPERATURE (EEV AND COND UNIT ONLY)
16 S2_RUN_TIME SYS 2 RUN TIME (SECONDS)
17 S2_SUCT_PR SYS 2 SUCTION PRESSURE
Continued on next page
192 JOHNSON CONTROLS
FORM 150.67-NM1 (308)

Continued from previous page


AI BACNET NAME ANALOG INPUT DESCRIPTION
18 S2_DSCH_PR SYS 2 DISCHARGE PRESSURE
19 S2_CIR_TEMP SYS 2 COOLER INLET REFRIGERANT TEMPERATURE (R407C ONLY)
20 S2_DEF_TEMP SYS 2 DEFROST TEMPERATURE (HP ONLY)
21 S2_SUCT_SH SYS 2 SUCTION SUPERHEAT (EEV ONLY)
22 S2_AR_TIMER SYS 2 ANTI-RECYCLE TIMER
23 S2_EEV_OUT SYS 2 EEV OUTPUT % (EEV ONLY)
24 NUM_COMPS NUMBER OF COMPRESSORS
25 S1_OP_CODE SYS 1 OPERATIONAL CODE (DEFINITION IN ERROR! REFERENCE SOURCE NOT FOUND).
26 S1_FLT_CODE SYS 1 FAULT CODE (DEFINITION IN ERROR! REFERENCE SOURCE NOT FOUND).
27 S2_OP_CODE SYS 2 OPERATIONAL CODE (DEFINITION IN ERROR! REFERENCE SOURCE NOT FOUND).
28 S2_FLT_CODE SYS 2 FAULT CODE (DEFINITION IN ERROR! REFERENCE SOURCE NOT FOUND).
29 S1_DBG_CODE SYS 1 DEBUG CODE
30 S1_FAN_STAGE SYS 1 CONDENSER FAN STAGE
31 S2_DBG_CODE SYS 2 DEBUG CODE
32 S2_FAN_STAGE SYS 2 CONDENSER FAN STAGE
UNIT CONTROL MODE (1=LEAVING WATER, 2=RETURN WATER. 3=DISCHARGE AIR, 4=SUCTION
33 CONTROL_M0DE
PRESS, 5=COOLING, 6=HEATING)
34 AR_TIME ANTI-RECYCLE TIME (PROGRAMMED)
35 LCHLT_CUT LEAVING CHILLED LIQUID TEMP CUTOUT
36 LOW_AMB_CUT LOW AMBIENT TEMPERATURE CUTOUT
37 SUCT_P_CO_HT LOW SUCTION PRESSURE CUTOUT HEATING (HP ONLY)
38 L_SUCT_P_CO LOW SUCTION PRESSURE CUTOUT (COOLING ON HP UNITS)
39 H_DSCH_P_CO HIGH DISCHARGE PRESSURE CUTOUT
40 COOL_SETP SETPOINT
41 SP_SETP_S1 SETPOINT 1 (SP CONTROL)
42 CONTROL_RG COOLING RANGE
43 SP_CTL_RG_S1 COOLING RANGE 1 (SP CONTROL)
44 SP_SETP_S2 SETPOINT 2 (SP CONTROL)
45 HEAT_SETP HEATING SETPOINT (HP ONLY)
46 SP_CTL_RG_S2 COOLING RANGE 2 (SP CONTROL)
47 HEAT_RANGE HEATING RANGE (HP ONLY)
48 S1_DSCH_TEMP SYS 1 DISCHARGE TEMPERATURE (EEV ONLY)
49 S1_DSCH_SH SYS 1 DISCHARGE SUPERHEAT (EEV ONLY)
50 S2_DSCH_TEMP SYS 2 DISCHARGE TEMPERATURE (EEV ONLY)
51 S2_DSCH_SH SYS 2 DISCHARGE SUPERHEAT (EEV ONLY)

10

JOHNSON CONTROLS 193


Maintenance
FORM 150.67-NM1 (308)

SERIAL COMMUNICATION BINARY INPUT DATA


This data can be read using a BACnet or Modbus network connection and can NOT be modified using this connection.
The Modbus Register Address for these points is 1281 + BI #.

BI BACNET NAME BINARY INPUT DESCRIPTION


1 S1_ALARM SYS 1 ALARM
2 S2_ALARM SYS 2 ALARM
3 EVAP_HTR EVAPORATOR HEATER STATUS
4 EVAP_PUMP EVAPORATOR PUMP STATUS
5 SI_C1_RUN SYS COMP 1 RUN
6 S2_C1_RUN SYS 2 COMP 1 RUN
7 S1_LLSV SYS 1 LIQUID LINE SOLENOID VALVE
8 S1_MODE_SV SYS 1 MODE SOLENOID VALVE (HP ONLY)
9 S1_HGBV SYS 1 HOT GAS BYPASS VALVE
10 S1_BHS BIVALENT HEAT SOURCE (HP ONLY)
11 S1_C2_RUN SYS 1 COMP 2 RUN
12 S2_C2_RUN SYS 2 COMP 2 RUN
13 S2_LLSV SYS 2 LIQUID LINE SOLENOID VALVE
14 S2_MODE_SV SYS 2 MODE SOLENOID VALVE (HP ONLY)
15 LEAD_SYS LEAD SYSTEM (0 = SYS 1, 1 = SYS 2)
16 S1_C3_RUN SYS 1 COMP 3 RUN
17 S2_C3_RUN SYS 2 COMP 3 RUN
18 CH_LIQ_TYPE CHILLED LIQUID TYPE (0 = WATER, 1 = GLYCOL)
19 AMB_MODE AMBIENT CONTROL MODE (O = STD AMB, 1 = LOW AMB)
20 CNTL_MODE_ LOCAL / REMOTE CONTROL MODE (0 = LOCAL, 1 = REMOTE)
21 DATA_UNIT UNITS (0 = IMPERIAL, 1 = SI)
22 AUTO_LL LEAD / LAG CONTROL MODE (0 = MANUAL, 1 = AUTO)

194 JOHNSON CONTROLS


FORM 150.67-NM1 (308)

TEMPERATURE CONVERSION CHART

Temperature Conversion Chart - Temperature Conversion Chart -


Actual Temperatures Differential Temperatures
°F = °C °C = °F °F = °C °C = °F
0 -17.8 -18 -0.4 0 0 0 0
4 -15.6 -16 3.2 4 2.2 2 3.6
8 -13.3 -14 6.8 8 4.4 4 7.2
12 -11.1 -12 10.4 12 6.7 6 10.8
16 -8.9 -10 14 16 8.9 8 14.4
20 -6.7 -8 17.6 20 11.1 10 18
24 -4.4 -6 21.2 24 13.3 12 21.6
28 -2.2 -4 24.8 28 15.6 14 25.2
32 0.0 -2 28.4 32 17.8 16 28.8
36 2.2 0 32 36 20 18 32.4
40 4.4 2 35.6 40 22.2 20 36
44 6.7 4 39.2 44 24.4 22 39.6
48 8.9 6 42.8 48 26.7 24 43.2
52 11.1 8 46.4 52 28.9 26 46.8
56 13.3 10 50 56 31.1 28 50.4
60 15.6 12 53.6 60 33.3 30 54
64 17.8 14 57.2
68 20.0 16 60.8
72 22.2 18 64.4 Pressure Conversion Chart -
76 24.4 20 68 Gauge or Differential
80 26.7 22 71.6
84 28.9 24 75.2 PSI = BAR BAR = PSI
88 31.1 26 78.8 20 1.38 1.5 21.8
92 33.3 28 82.4 30 2.07 2 29
96 35.6 30 86 40 2.76 2.5 36.3
100 37.8 32 89.6 50 3.45 3 43.5
104 40.0 34 93.2 60 4.14 3.5 50.8
108 42.2 36 96.8 70 4.83 4 58
112 44.4 38 100.4 80 5.52 4.5 65.3
116 46.7 40 104 90 6.21 5 72.5
120 48.9 42 107.6 100 6.9 5.5 79.8
124 51.1 44 111.2 110 7.59 6 87
128 53.3 46 114.8 120 8.28 6.5 94.3
132 55.6 48 118.4 130 8.97 7 101.5
136 57.8 50 122 140 9.66 7.5 108.8
140 60.0 52 125.6 150 10.34 8 116
144 62.2 54 129.2 160 11.03 8.5 123.3
148 64.4 56 132.8 170 11.72 9 130.5
152 66.7 58 136.4 180 12.41 9.5 137.8
156 68.9 60 140 190 13.1 10 145
160 71.1 62 143.6 200 13.79 10.5 152.3
164 73.3 64 147.2 210 14.48 11 159.5
168 75.6 66 150.8 220 15.17 11.5 166.8
172 77.8 68 154.4 230 15.86 12 174
176 80.0 70 158 240 16.55 12.5 181.3
180 82.2 72 161.6 250 17.24 13 188.5
184 84.4 74 165.2 260 17.93 13.5 195.8
188 86.7 76 168.8 270 18.62 14 203
192 88.9 78 172.4 280 19.31 14.5 210.3
196 91.1 80 176 290 20 15 217.5 10
200 93.3 82 179.6 300 20.69 15.5 224.8
204 95.6 84 183.2 310 21.38 16 232
208 97.8 86 186.8 320 22.07 16.5 239.3
212 100.0 88 190.4 330 22.76 17 246.5
216 102.2 90 194 340 23.45 17.5 253.8
220 104.4 92 197.6 350 24.14 18 261
224 106.7 94 201.2 360 24.83 18.5 268.3
228 108.9 96 204.8 370 25.52 19 275.5
232 111.1 98 208.4 380 26.21 19.5 282.8
236 113.3 100 212 390 26.9 20 290
240 115.6 102 215.6 400 27.59 20.5 297.3
244 117.8 104 219.2

JOHNSON CONTROLS 195


R410-A
PRESSURE TEMPERATURE CHART

PSIG TEMP ˚F PSIG TEMP ˚F


0 -60 78 20
2 -58 80 21
4 -54 85 24
6 -50 90 26
8 -46 95 29
10 -42 100 32
12 -39 105 34
14 -36 110 36
16 -33 115 39
18 -30 120 41
20 -28 125 43
22 -26 130 45
24 -24 135 47
26 -20 140 49
28 -18 145 51
30 -16 150 53
32 -14 160 57
34 -12 170 60
36 -10 180 64
38 -8 190 67
40 -6 200 70
42 -4 210 73
44 -3 220 76
46 -2 225 78
48 0 235 80
50 1 245 83
52 3 255 85
54 4 265 88
56 6 275 90
58 7 285 92
60 8 295 95
62 10 305 97
64 11 325 101
66 13 355 108
68 14 375 112
70 15 405 118
72 16 500 134
74 17 600 149
76 19 700 159

P.O. Box 1592, York, Pennsylvania USA 17405-1592 Tele. 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2008 www.York.com ALL RIGHTS RESERVED
Form 150.67-NM1 (308)
Supersedes 150.67-NM1 (507)

You might also like