SVTMAN
SVTMAN
DO2000
Service Tool Users´s Guide
The service tool front panel consists of a display with 2 lines, 16 characters per line, and 16
keys.
Some keys have a second function which is activated by pressing first the blue button
(represented by the % sign below) and then the key.
The used key arrangement is as shown below:
keys: +----------+---------+---------+---------+
| MODULE | 7 | 8 | 9 |
| |.........|.........|.........|
| (M) |%%%%%%%%%|%%%%%%%%%|%%%%%%%%%|
|----------+---------+---------+---------|
| FUNCTION | 4 | 5 | 6 |
| |.........|.........|.........|
| (F) |%%%%%%%%%|%%%%%%%%%|%%%%%%%%%|
|----------+---------+---------+---------|
| SET | 1 | 2 | 3 |
| |.........|.........|.........|
| (S) |% ON %|% UP %|% DOWN %|
|----------+---------+---------+---------|
|%%%%%%%%%%| 0 | GO ON | CLEAR |
|%%%%%%%%%%|.........|.........|.........|
|%%%%%%%%%%|% OFF %|%GO BACK%|% ENTER %|
+----------+---------+---------+---------+
2 Connection to DCSS
The service tool can be connected with the DCSS by two ways, directly when plugged onto
the DCSS logic board and indirectly if serial link is connected to the MCSS or OCSS in a
311/411 system configuration.
When connected to any subsystem, the service tool conducts self-tests and then executes
the set-up sequence. The following display will be made when normal communication is
established with any subsystem.
+----------------+
| SELF TEST |
|-OK- MECS-MODE |
+----------------+
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 4 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
3 Dialog Operations
"MODULE"
|
+---------+---------+
| | |
"FUNCTION" ... ...
|
+-------+-------+-------+-------+
| | | | |
"SET" ... ... ... ...
,----------------.
MODULE LEVEL | DCSS = 3 | <----- M ---+
`----------------´ |
|"3" |
,----------------. ^
FUNCTION LEVEL |MONITOR=1 TEST=2| <----- F ---+
|SETUP=3 INSPEC=4| |
`----------------' ^
SET LEVEL | <----- S ---+
,-----------------+--------+-------+----------------. |
|"1" |"2" |"3" |"4" |
,---------------. ,---------------. ,---------------. ,----------------. |
|STATUS = 1 ( 6)| |EVENT = 1 (13)| |INST = 1 (18)| |INSPCT R= 1 (26)| ^
|COMND = 2 ( 9)| |ERROR = 2 (14)| |PROF = 2 (23)| |CONTIN R= 2 (28)| |
|INP = 3 (10)| |PART = 3 (15)| |OTHER = 3 (24)| `----------------' |
|OUTP = 4 (10)| |CYCLECT= 4 (15)| |ENG = 4 (25)| |
|POSITN = 5 (10)| `---------------' |
|RAM = 6 (12)| |
`---------------' ^
4 MODULE Operations
The following action will be taken when the "MODULE" key on the service tool panel is
pressed:
5 FUNCTION Operations
When the key "3" is pressed in MODULE operation or when the "FUNCTION" key is
pressed at lower layer of the hierarchy, the following display will be monitored:
+----------------+
|MONITOR=1 TEST=2|
|SETUP=3 INSPEC=4|
+----------------+
If a key "1" to "4" is pressed the operation shifts to the SET menu level.
6 SET Operations
+----------------+ +----------------+
|STATUS=1 COMND=2| |POSITION=5 RAM=6|
|INP=3 OUTP=4 >| < press GOON/GOBACK > | >|
+----------------+ +----------------+
Press the "<GO ON>" or "<GO BACK>" key to toggle between the displays.
Pressing the keys "1" to "6" at this time the operation will shift to the corresponding field.
+----------------+
|aa: mmm ccc sss|
| any display |
+----------------+
Description of the first status display line for a DISCRETE INTERFACE configuration
or for RELAY CONTROLLER:
[] = opened
<> = opening
][ = closed
>< = closing
<P> = passenger protection activated
Description of the first status display line for a SERIAL INTERFACE configuration:
cccc = door command state given from MCSS via serial link:
Reversal inputs
in operation:
| DOB | LRD | EDP
--------------------------------------------
DED = deenergize ----- | ----- | -----
OPD1 = open door ----- | ----- | -----
OPD2 = open door ----- | ----- | -----
CLD1 = close door ----- | ----- | -----
CLD2 = close door D | L | E
CLD3 = close door D | L | e
CLD4 = close door D | l | e
CLD5 = close door D | ----- | ----- (NDG)
CLD6 = close door D | ----- | e
CLD7 = close door d | ----- | e
CLD8 = close door d | ----- | -----
ss = Door State:
[] = opened
<> = opening
][ = closed
>< = closing
<P> = passenger protection activated
If the safety link is interrupted, indicated by the EDS-signal, the DCSS shuts down and
disables the motor supply. In this mode the Service Tool displays:
+----------------+
| EMERGENCY STOP |
| |
+----------------+
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 9 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
GENERAL: +----------------+
| Status Display |
|1111 < 2 3 4 |
+----------------+
The different number fields in the display show the available door command and the system
reaction, if the reversal inputs DOB, LRD or EDP are activated. Lower case letters represent
the command "limited", upper case letters the command "full door reversal". A hyphen
means no door reversal (see page 8).
234 shows additional reversal devices info for command currently selected
with 2 = 'D' for full, 'd' for limited reversal
'--' for no reversal on DOB operated
Use the key "<GO ON>" or "<GO BACK>" to scroll through the available commands.
Press the key "<ENTER>" to confirm the new command.
The different number fields in the display show the discrete inputs, lower case letters
represent the state "off", upper case letters the state "ON".
ATTENTION!
The inputs are changing if the door is controlled by the Top of Car Inspection Box according
to the British Standard BS7255:
EXAMPLE: +----------------+
|D1: RDY OPN <> |
| inh dol dos |
+----------------+
GENERAL: +----------------+
| Status Display |
| 1111 2222 3333 |
+----------------+
The different number fields in the display show the discrete outputs, lower case letters
represent the state "off", upper case letters the state "ON".
RELAY CONTROLLER:
1111 REL1 (DOL:door fully open) 2222 REL2 (DCL:door fully closed)
3333 REL3 (GH:door closed)
SCROLL!
4444 REL4 (SGL: 30% before closed) 5555 REL5 (PMY: for high speed drive)
6666 REL6 (SGSout: reopen signal)
EXAMPLE: +----------------+
|D1: RDY OPN <> |
|POSIT = 145 mm |
+----------------+
GENERAL: +----------------+
| Status Display |
|POSIT = xxxx mm|
+----------------+
The door position is calculated according to the speed encoder pulses and is displayed in
[mm]. It corresponds to the door way and is '0mm, if the door is fully closed.
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 12 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
EXAMPLE: +----------------+
|D1: RDY OPN <> |
|0FA6:F0 E0 BE B6|
+----------------+
GENERAL: +----------------+
| Status Display |
|nnnn:d0 d1 d2 d3|
+----------------+
Use the key "<GO ON>" or "<GO BACK>" to increment or decrement the RAM address or
type in the address with the number keys.
To enter the hexadecimal RAM address use number keys and confirm it by the
"<ENTER>" key.
The hex 'A' is entered by pressing the 'BLUE' key and the number 4.
The hex 'B' is entered by pressing the 'BLUE' key and the number 5.
The hex 'C' is entered by pressing the 'BLUE' key and the number 6.
The hex 'D' is entered by pressing the 'BLUE' key and the number 7.
The hex 'E' is entered by pressing the 'BLUE' key and the number 8.
The hex 'F' is entered by pressing the 'BLUE' key and the number 9.
+----------------+
|EVENT=1 ERROR=2 |
|PART=3 CYCLCNT=4|
+----------------+
Pressing the keys "1" to "4" at this time the operation will shift to the corresponding field.
Press <GO ON> or <GO BACK> to scroll through the events, which occurred since the last
system reset.
Press <ENTER> to delete the displayed event.
Press <SEL Out> to delete complete event-log, Runtimer and -counter.
Press <ON> or <OFF> to toggle between the displays of the first line.
NOTE: The events are not stored permanently ! They are lost after disconnecting the
main power.
Press <GO ON> or <GO BACK> to scroll through the errors, which occurred since the last
system reset.
Press <ON> or <OFF> to toggle between the displays of the first line.
NOTE:
The errors are not stored permanently ! They are lost after disconnecting the
main power.
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 15 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
EXAMPLE: +----------------+
|: GAA30320AAA |
|DO2000 15NOV1996|
+----------------+
GENERAL: +----------------+
| GAAcccccvvv |
|tttt dddddddddd |
+----------------+
EXAMPLE: +----------------+
|R: 0006943267 |
|T: 01:012:23:59 |
+----------------+
When the key "3" is pressed in FUNCTION operation or when the "SET" key is pressed at
lower layer of the hierarchy, the system will shift to the setup function and the following
display is shown:
+----------------+
|INST= 1 PROF= 2 |
|OTHER= 3 ENG = 4|
+----------------+
Pressing the keys "1" to "4" at this level you will shift to the corresponding field and a
changing of the setup parameters is possible.
A list of all setup parameters and their value range is shown in the appendix.
A parameter is stored permanently in the Flash memory not before the menu is left with one
of the function key (Modul, Functio or Set).
EXAMPLE: +----------------+
|START OPEN SPEED|
|0008 <-- 0012 Hz|
+----------------+
GENERAL: +----------------+
|1111111111111111|
|2222 <-- 3333 44|
+----------------+
Use "<GO ON>" / "<GO BACK>" to scroll through the available setup parameter.
Use the number keys to enter a new value and confirm it with the "<ENTER>" key.
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 17 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
The parameter input is checked to a certain degree by the DCSS before it is overwritten by
a new value. During the parameter entering the value is checked against the upper and
lower limit. If the parameter exceeds this limit it will not be stored into the Flash memory and
the error counter will be incremented.
NOTE:
It is not recommendable to change the parameters during a door movement, because the
system will be shut down immediately.
When the door supervisor is in the 'READY' mode and the door is not in the fully open or
close position, a changing of the setup parameters is not allowed and the following display
will be shown:
+----------------+
|DOOR IS RUNNING |
|PLEASE WAIT |
+----------------+
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 18 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
,--------------------.
| SET UP ROUTINE |
| GOON WITH ENTER |
`--------------------'
,--------------------.
| DEFAULT PARAMTR? |
| YES = 1 NO = 2 |
`--------------------'
Enter '1' to write a set of DEFAULT parameter into the EEPROM or enter '2' to go to
next step
,-------------------.
| Interf: xxxxxxxxx | xxxxxxxxxxx : DISCRETE
| use GOON / ENTER | SERIAL
`-------------------' Interf.BOX
According to the selected Interface Type the following Menu display differs.
If a DISCRETE Interface was selected no additional SET_UP appears and the Motor check
program will start.
,------------------.
| ADDRESS: nnnn | nnnn = DCSS_1 (front door)
| use GOON / ENTER | DCSS_2 (altern. Door)
`------------------’ DCSS_3 (for dobble -
DCSS_4 deck cars )
,-----------------.
|Controller Type? |
| use GOON / Enter|
`-----------------’
,-----------------. ,-----------------.
| Type: MCS 411 | | Other (311...) |
| use GOON / ENTER| GOON |use GOON / ENTER |
`-----------------’ ----> `-----------------´
,-----------------.
| DOS Signal ? |
| YES=1 NO=2 |
`-----------------’
With this parameter the function of the Relay REL3 on the Interface Box can be
programmed. Some Relay controller need a DOS signal, managed by the Relay 3. If the
parameter DOS signal is set, confirmed by entering a ‘1’, the Relay will be set during
opening and will be dropped off by reaching the DOL position.
If the parameter is set to ´2´ the Relay will be set only if the door is nearly closed and will be
dropped off during opening.
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 20 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
,--------------------.
| CHK MOTOR ROTATN |
| CLS=1 OPN=2 NO=3 |
`--------------------'
Enter a command: '1' for close, '2' for open door or '3' to pass over
,--------------------.
| DOOR IS ........? | closing if '1' had been entered
| YES=1 NO=2 | opening if '2' had been entered
`--------------------'
Watch door movement and confirm with '1' if door runs in right direction. If not, enter
'2' and the procedure will be repeated with an opposite sign.
,--------------------.
| ERR ROTOR SENSE | displayed if error of rotor sense
| GOON WITH ENTER |
`--------------------'
,--------------------.
| ROTOR SENSE OK | displayed if rotor sense is ok
| GOON WITH ENTER |
`--------------------'
,--------------------.
| CHK SPEEDENCODER |
| CLS=1 OPN=2 NO=3 |
`--------------------'
Enter a command: '1' for close, '2' for open door or '3' to pass over
,--------------------.
| SPEEDENCD OK? ....| >< encoder direction signal: close
| YES = 1 NO = 2 | <> encoder direction signal: open
`--------------------'
If encoder direction signal according to door movement enter '1'. If not enter '2' and
the procedure will be repeated with a changed sign.
,--------------------.
| ENCODER SENSE OK |
| GOON WITH ENTER |
`--------------------'
To learn these unknown values the door has to move two times. At the first move the
routine checks the resolution of the encoder device, which can be very high and leads to an
overflow of the counting register or can be very low which leads to bad performances and
great errors during velocity- and position calculation.
To avoid these bad effects, the resolution of the encoder is adapted during the recognition
to an optimum value, to get the best results independent of the given door hardware.
With the second move the complete doorway is measured. This value must be very
accurate, because it will be now the reference for the door position calculation.
At the end of the learn run the actual position is displayed in [mm].
To leave the menu the user has to press the menu-key 'M'.
,--------------------.
| START LEARN_RUN |
| PRESS <ENTER> |
`--------------------'
,--------------------.
| LEARN_RUN |
| DOOR is CLOSING |
`--------------------'
To find a defined position the door is closing first. If the door is fully closed the
program goes to the next step.
,--------------------.
| LEARN_RUN |
| DOOR is OPENING |
`--------------------'
Door is opening and learns the door environment to adapt the encoder-pulses for
the position- and velocity calculation. If the door is fully opened it will close again.
,---------------------.
| LEARN_RUN |
| POSITION: xxxxx | xxxxx: Position in increments
`---------------------'
Now the door is closing and the position is measured and displayed in absolute
increments.
If the door is fully closed the program goes to the next step.
,---------------------.
| POSITION: xxxxx | xxxxx: Position in mm
| Finish PRESS "M" |
`---------------------'
Use the keys "SET", "FUNCTION" or "MODULE" to interrupt the installation routine.
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 23 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
The Installation Routine can be selected only, if the SVTOOL is plugged directly onto the
DCSS. In other cases it will display:
+----------------+
| NOT AVAILABLE |
|PLUG SVT ON DCSS|
+----------------+
If the Top of Car Inspection switch (TCI) is not operated, the following error message will be
displayed:
+----------------+
|SET INSPECTION |
|SWITCH TCI |
+----------------+
All velocity parameters are declared as default values by the door type specification.
Generally it is not necessary to change these parameters.
VOLTAGE BOOST voltage offset when frequency is zero to increase motor torque
PASSENGER PROTEC slip limit for obstacle detection / passenger protection
TCI with BS7255 door control with TCI Box according to British Stand. BS7255
MCS411: GSM-DIST to adjust GSM distance (only for MCS411 )
--- Additional Parameter for Relay Controller (with Interface Box) ----
When the key "4" is pressed in FUNCTION operation or when the "SET" key is pressed at
lower layer of the hierarchy, the following displays will be made:
+----------------+
|INSPECTION RUN=1|
|CONTINUOUS RUN=2|
+----------------+
Pressing the keys "1" or "2" at this level the operation will shift to the corresponding field.
The commands with the corresponding number are displayed on the SVTOOL and can be
scrolled with the GOON/GOBACK key.
After entering the first command the door supervisor state will change from 'SHUT DOWN
MODE' to 'INITIALIZE MODE' and the door will perform an Initialization run into the given
direction in order to determine its position.
Afterwards the supervisor mode changes to 'READY' and the door movement corresponds
to the normal speed profile.
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 27 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
EXAMPLE: +----------------+
|D1: RDY INSP >< |
|CLS_1=1 op_1=2 >|
+----------------+
GENERAL: +----------------+
| Status Display |
|CLS_1=1 OP_2=2 >|
+----------------+
Lower case letters represent the state "off", upper case letters the state "ON".
NOTE:
After leaving this menu point, the given door command will become invalid.
The inspection mode will be interrupted by pulling off the Service Tool plug.
If the TCI switch is not operated, the following error message will be displayed:
+----------------+
|SET INSPECTION |
|SWITCH TCI |
+----------------+
Part : 4 - C9
OTIS FIELD COMPONENT MANUAL No. :GAA24350AW11IVa
European and Transcontinental
Operations Vintage : 01 / 1
Service Tool User´s Guide
PRODUCT Page : 28 / 28
ADMINISTRATION DCSSIV - DO2000
Service Tool Manual Date : 10-Feb-1997
This function provides a continuous door run if the Top of Car Inspection switch 'TCI' is
operated and the Service Tool is plugged directly onto the DCSS. After starting the
Continuous run (press key [1]) the door first performs an initialize run to determine the
actual position. Afterwards the door opens and closes alternately with the normal speed
profile.
EXAMPLE: +----------------+
|D1: RDY INSP |
|START=1 stop=2|
+----------------+
GENERAL: +----------------+
| Status Display |
|start=1 stop=2|
+----------------+
Lower case letters represent the state "off", upper case letters the state "ON".
Use the keys "1" or "2" to start or stop the continuous run.
NOTE:
When leaving this menu point the continuous run will not be interrupted automatically. It
must be switched off by pressing the key [2], pulling off the Service Tool plug or by resetting
the Inspection switch.
If the Top of Car Inspection is not operated, the following error message will be displayed:
+----------------+
|SET INSPECTION |
|SWITCH TCI |
+----------------+