0% found this document useful (0 votes)
25 views5 pages

PSP - Par Personal Solution-Pac: General Parameters File Descritption

This document describes the parameters for a personal solution package monitoring software. It outlines various configuration settings for automatic startup, delays, monitoring intervals, communication ports and logs. The parameters are organized into sections for general settings, monitoring, communication, inter-process communication, tracing and file names.

Uploaded by

nn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views5 pages

PSP - Par Personal Solution-Pac: General Parameters File Descritption

This document describes the parameters for a personal solution package monitoring software. It outlines various configuration settings for automatic startup, delays, monitoring intervals, communication ports and logs. The parameters are organized into sections for general settings, monitoring, communication, inter-process communication, tracing and file names.

Uploaded by

nn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
You are on page 1/ 5

Personal Solution-Pac : General parameters file descritption

============================================================

Note : - Comments may be inserted in the parameter file


by beginning the comment line with ;
- Default installation file PSP_PAR.INI is saved in
DEFAULT directory under PSP directory.

General parameters [General]


============================
AutomaticStartup
----------------
1 : automatic start of Personal Solution-Pac at system boot is enabled.
0 : automatic start is disabled.

DelayAfterBoot (0 - 9999 seconds)


---------------------------------
Delay between system initalization and effective start of PSP modules.

PSP Monitoring Module parameters [Monitoring]


=============================================
ShutdownDuration (0 - 9999 seconds)
-----------------------------------
Duration of system shutdown.

ShutdownTimer (0 - 9999 minutes)


--------------------------------
Maximum time between power failure and system shutdown.

LowBatteryTime (0 - 9999 seconds)


---------------------------------
When UPS is on battery and battery remaining time goes under this minimum
time, PSP start system shutdown (low battery condition).

GracePeriod (0 - 9999 minutes)


------------------------------
Delay between utility failure and first utility failure notification to
administrator and/or users.

IntervalBetweenMessages (1 - 9999 minutes)


------------------------------------------
Delay between periodic messages sent to administrator and/or users after
utility failure.

DateTimeFormat
--------------
Format string of date and time displayed in messages sent to administrator
and/or users.
The format string consists of one or more codes. The formatting codes are
preceded by a percent sign (%). Characters that do not begin with % are
displayed unchanged. Valid formatting codes are :

%a Abbreviated weekday name


%A Full weekday name
%b Abbreviated month name
%B Full month name
%d Day of month as decimal number (01 - 31)
%H Hour in 24-hour format (00 - 23)
%I Hour in 12-hour format (01 - 12)
%j Day of year as decimal number (001 - 366)
%m Month as decimal number (01 - 12)
%M Minute as decimal number (00 - 59)
%S Second as decimal number (00 - 59)
%U Week of year as decimal number, with Sunday as first day of week (00 - 51)
%w Weekday as decimal number (0 - 6; Sunday is 0)
%W Week of year as decimal number, with Monday as first day of week (00 - 51)
%y Year without century, as decimal number (00 - 99)
%Y Year with century, as decimal number
%% Percent sign

CommunicationDelay (60 - 9999 seconds)


--------------------------------------
Maximum delay between Monitoring module start and communication is established
with the UPS.

TaskSchedulingRate (100 - 99999 milliseconds)


---------------------------------------------
Internal delay between tasks.

DownConfirmChar
---------------
NetWare only : if specified, confirmation character pushed to system console
to confirm system shutdown if files are left opened.

PSP Communication Module parameters [Communication]


===================================================
SerialPort
----------
Serial port used for communication with UPS.
Windows 95 only : use "Auto" to enable automatic detection of serial port
with a MGE UPS Systems "Plug and Play" UPS.

BaudRate (2400 bauds)


---------------------
Serial baud rate used for communication with UPS.

UTalkTimeout (50 - 99999 milliseconds)


--------------------------------------
Timeout for serial communication.

MaxTimeoutError (1 - 9999)
--------------------------
Maximum number of timeouts for serial communication with UPS.
After this number of timeouts, serial communication is reinitialized.

TaskSchedulingRate (100 - 99999 milliseconds)


---------------------------------------------
Internal delay between tasks.

PnPIdString
-----------
Windows 95 only : Identification string for "Plug and Play" UPS detection.

Inter-process communication parameters [Ipc]


============================================
ChannelWaitTimeout (1000 - 99999 milliseconds)
----------------------------------------------
Internal timeout delay for communication channels.

CommandTimeout (500 - 99999 milliseconds)


-----------------------------------------
Internal timeout for inter-process communication.

TablePurgeDelay (1 - 9999 minutes)


----------------------------------
Purge delay of internal commands table buffer.

Trace parameters [Trace]


========================
VerboseLevel (0-4)
------------------
Trace messages level.
Windows NT : Using this parameter when modules are running as services
will cause rapid growth of system application log.

UPSTrace
--------
1 : serial communication is logged.
0 : serial communication is not logged.

UPSTraceFile
------------
Serial communication log filename.

UPSTraceFileSize (500 - 9999 lines)


-----------------------------------
Serial communication log maximum size.

File names and sizes [Files]


============================
LogScript
---------
Script file that logs events.

ShutdownScript
--------------
Script file that starts system shutdown.

BroadcastScript
---------------
Script file that sends messages.

ScheduleFile
------------
Customizable schedule filename.

ActionFile
----------
Customizable actions filename.

EventFile
---------
Customizable events filename.
LogFile
-------
Event log filename.

LogFileSize (500 - 9999 lines)


------------------------------
Event log maximum size.

Commands activation flags


=========================
The commands below are activated if the corresponding parameter is
set to 1 and disabled if set to 0

Initialisation commands activation flags [InitCommands]


=======================================================
Not applicable.

Startup commands activation flags [StartupCommands]


===================================================
If activated, this command is sent once after module starts.

Bn?
---
Command "Nominal Battery time"

Monitoring commands activation flags [MonitoringCommands]


=========================================================
If activated, these commands are sent periodically during
the monitoring cycle.

Bn
--
Command "Battery time remaining"

Us
--
Command "Utility status"

Ps
--
Command "Bypass status"

Ss
--
Command "System status"

Bs
--
Command "Battery status"

SStat
-----
Pseudo-command "Serial status"

Shutdown commands activation flags [ShutdownCommands]


=====================================================
If activated, these commands are sent to turn UPS Off.
SnX
---
Command "Set remote shutdown delay"

Sm0
---
Command "Set delay before Power On"

Sx5
---
Command "Valid automatic restart"
Sx0
---
Command "UPS OFF"