25 Kva 1ø LV Box With Meter Box TN-2827

Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

TN-2760, AVVNL Schedule - V (A)

Manufacturer Guarantee Technical Particulars for Supply of 25 kVA 11/√3/0.240 KV TN-2827

S. No. Description Unit 25 KVA


1
Manufacturer's Name Mangal Electrical Industries Pvt. Ltd
E-40 TO E46 & E46A SHREE KHATU
SHYAM JI
a Postal Address:
INDUSTRIAL AREA REENGUS (302404)
E-40 TO E46 & E46A SHREE KHATU
b Manufacturer’s Works Address: SHYAM JI INDUSTRIAL AREA REENGUS
(302404)
2 Make & Country of origin: INDIA
3 Continuous max rating as per this specification KVA 25
4 Normal ratio of Transformer KV 11/√3/0.240
5 Method of connection HV / LV
6 Max. Current density in windings
a High voltage Amp/Sq. mm 1.6
b Lower voltage Amp/Sq. mm 1.6
7 Max. hot spot temp Deg.C <98 (35)
8 Max. Observable oil temperature (Ambient air 85
a Deg.C
temp on which the above is based ) (50)
Max. Winding temperature 90
b Deg.C
(Ambient air temp on which the above is based ) (50)
9 Total losses at normal voltage frequency, rated current and 75
Deg.C at 50% & Watts 110 W & 300 W
100% loading (max.)
10 Fulx Density (Max.) Tesla 1.47
11 Percentage no load current at rated frequency (without any
positive tolerance)
a At rated voltage 1.5% + 30% tol. as per IS/SPEC
b At 112.5% rated volatge 3% + 30% tol. as per IS/SPEC
12 i Efficiency at normal voltage: Unity power factor
At 50% load % 99.25
At 75% load % 99.05
At full load % 98.81
ii 0.8 power factor
At 50% load % 99.07
At 75% load % 98.81
At full load % 98.52
13 regulation as % of normal voltage
a At unity power factor % 1.174
b At 0.8 power factor lagging % 3.217
14
Impedance voltage at normal ratio between HV and LV winding % 4% +/- 10%
15 Type of Transformer, Shell type/Core type Wound core. Shell type, Amorphous Wound Core
16 Type of Insulation used in
a HV winding Polyesteramide enamal ( Class-H)
b LV winding DPC
17 Impluse test volatge level `KVrms
a HV winding 75 kvp
b LV winding NA
18 HV bushing detail:-
a Rating of the bushing 12 KV, 250A
b Impulse strength KVP 75
c Power frequence withstand voltage, dry and wet KV (Rms) 28
d IS reference IS:3347 & IS:2099
e Make & Country of origin: As per Specification
19 LV bushing detail:-
a Rating of the bushing 1.1 KV, 250 A
b Impulse strength NA
c Power frequence withstand voltage, dry and wet 3
d IS reference IS:3347 & IS:2099
e Make & Country of origin: As per Specification
20 Minimum external clearances (in air as per IS:1180)
a HV phase to earth mm 140
b LV phase to earth mm 40/20 (box inside)
21 Minimum internal clearances
a Clearance between inner wall of tank and coil mm 12
b Radial clearance between HV & LV winding mm 2
c Radial clearance of LV coil from core mm 2
d End clearance of HV coil from Yoke mm 15
e Minimum Gap between core & tank bottom mm 5
22 HV coil constructional details:-
a Conductor cross section (min.0 Sq. mm 5.2279
b Bare conductor size dia mm 2.58
c Covered conductor size dia mm 2.68
d Coil I.D. mm 166 x 289
e Coil O.D. mm 260 x 385
f Coil axial length mm 247 (Including End Packing)
g Total no. of turns per phase 1267
h Inter layer insulation 4 Mill Epoxy dotted kraft paper
23 LV coil constructional details:-
a Conductor cross section (min.) Sq. mm 112.64
b Bare conductor size dia 8.7 x 3.3 ( 2W x 2D)
c Covered conductor size dia mm 9.10 x 3.70
d Coil I.D. mm 95 x 221
e Coil O.D. mm 160 x 283
f Coil axial length mm 247 (Including End Packing)
g Total no. of turns per phase 48
h Inter layer insulation 4 Mill Epoxy dotted kraft paper
24 Characteristics of transformer oil As per IS-335
25 Total content of oil ltr 57
26 i Approximate overall dimensions
a Height mm 990
b Breadth mm 660
c width mm 600
ii Tank Internal dimensions
a Diameter mm 450
b Height mm 630
iii Tank sheet thickness
a Side mm 2
b Top mm 2.5
c Bottom mm 2.5
27 Weight of insulated conductor
HV (min) kg 17.8
LV (min) kg 10.8
28 Weight of core (min) kg 99.5
29 Weight of fittings and accessories kg 41
30 Weight of oil kg 41
31 Weight of complete transformer arranged for transport kg 219
32 Core Details:-
a Step width mm 213
b Stack thickness mm 44.5 x 2
c Cross sectional area Sq. mm 189.57
d Effective core area Sq. mm 163.03
e Core window height mm 260
33 Resistance for windings at 75 Deg.c per phase
a HV Ohms 8.65
b LV Ohms 0.0135
34 Material of bushing rod and nuts & Bushing caps
a HV M-12 Brass
b LV M-12 Brass
35 Make, type of LV Breakers
36 Particulars of HV fuse As per Specification
a System voltage KV 12 KV
b Current Amp 3.94 A
c Max. design voltage IN CORDINATION WITH LT
d Min. melting time IN CORDINATION WITH LT
e Total clearing time IN CORDINATION WITH LT
f Inerrupting rating IN CORDINATION WITH LT
g Mounting VERTICAL
h Make JVVNL APPROVED
37 All the fitting and accessories shall be provided as per IS: 1180
YES
(part-1)-2014/spec.
38 Whether the metal parts of HV/LV Bushing are as per relevant IS and
not under size (YES/NO). If Metal parts are under size, then the lot may YES
be rejected at firm's works.
39 Whether each HV, LV & Neutral terminal shall be duly indelibly marked
with its terminal numbers. (e.g. HV phase terminal as 1.1 , HV neutral
terminal as 1.2, LV phase terminal as 2.1, LV neutral terminal as 2.2) by YES
stamping with Min. letter size of 40x40 mm. If No, then the lot may be
rejected at firm's works.
40 Whether, the Lugs for LV terminal of the transformer have been crimped
with a crimping tool and suly insulated. If No, then the lot may be YES
rejected at firm's works.
41 Whether the gasket of LV box is of one piece instead of pieces. If No,
As per drawing
then the lot may be rejected at firm's works.
42 Whether the core has been earthed through copper earthing foil of 25
mm width & 1 mm thickness bolted on core clamp after removing YES
channel paint. If No, then the lot may be rejected at firm's works.
43 Whether the Rating & Terminal Marking Plate is non-detachable & has
been affixed with Min. 08 rivets (4 nos. on corner and 1 no. each on
width side and length side) and the base of the Rating & Terminal YES
Marking Plate is continuously welded with the tank. If No, then the lot
may be rejected at firm's works.
44 Whether the internal electrical clearance in oil are found as per
YES
specification. If No, then the lot may be rejected at firm's works.
45 Whether the external electrical clearance are found as per specification.
YES
If No, then the lot may be rejected at firm's works.
46 whether any core stamping found rusted & damaged (hole observed in
NO
stamping). If Yes, then the lot may be rejected at firm's works.
47 Whether Amorphous/CRGO are directly imported either from the
manufacturer or through their accredited marketing organization of
repute (and not through any agent). Whether the copy of the invoice of
YES
Amorphous/CRGO core material has been provided by the supplier at
the time of inspection and same has been verified by the inspecting
officer. If No, then the lot may be rejected at firm's works.
48 Whether the Hexagonal head of antitheft fasteners are detached at M&P
YES
box sliding cover. If No, then the lot may be rejected at firm's works.
49 Whether the detail of Make, Rating, Sr. No. and TN/Order No. are
punched or an identity plate with said details is welded on core coil YES
assembly. If No, then the lot may be rejected at firm's works.
50 Whether Bi-metallic connectors on HV Bushing are provided as per
YES
specification. If No, then the lot may be rejected at firm's works.
51 Whether Press Board used has been of senapathy whitely/ Raman make/
Techno Electric, Hyderabad and Perma wood or haldu wood blocks has
YES
been used for Top and Bottom yoke insulation. If No, then the lot may
be rejected at firm's works.
52 Whether dry type film thickness (DFT) of paint is as per specification.
YES
If No, then the lot may be rejected at firm's works.
53 Whether Oil level gauge of prismatic glass, indicating minimum position
corresponds to the operating temperature of 30 deg. C as per IS: 1180
YES
part - 1: 2014, has been provided above the internal circuit breaker
height. If No, then the lot may be rejected at firm's works.
54 Whether make of HV/LV Bushing is as per specification/PO. If No, then
YES
the lot may be rejected at firm's works.
55 Whether Technical cum Identification plate of size 125 x75 x 2.5 mm
having detail as per specification punched with letters of size 8mm
YES
x6mm shall be continuously welded to the main tank body in clearly
visible position. If No, then the lot may be rejected at firm's works.
56 Whether following mentioned are as per specification/approved drawing
of M&P box: 1. Size
of PVC Copper cable 2. Size
YES
of lugs 3.
make of inbuilt circuit breaker If
No, then the lot may be rejected at firm's works.
57 Whether Provision shall be made for connecting the neutral HV terminal
to local earth through a strip having width of 25 mm and 1 mm YES
thickness. If No, then the lot may be rejected at firm's works
58 Whether the circular bottom plate edges of the tank should be folded
upward, for at least 25mm to have sufficient overlap with vertical side
YES
wall of the transformer. If No, then the lot may be rejected at firm's
works.
59 Whether the HV bushing pocket shall be embossed to top side of the top
cover so as to eliminate ingression of moisture & water and the edges of
YES
the top cover shall be formed, so as to cover the top end of the tank and
gasket. If No, then the lot may be rejected at firm's works.
60 Whether the creep age distance of HV & LV bushing are as per IS or
YES
not. If No, then the lot may be rejected at firm's works.
DISTRIBUTION TRANSFORMER
MANGAL ELECTRICAL INDUSTRIES PVT LTD
E-40 to E46 , E46A, SHREE KHATU SHYAM JI INDUSTRAL AREA, REENGUS, SIKAR, RAJASTHAN 332404
CML no. 8400125310
1 PHASE TRANSFORMER
STANDARD IS : 1180 (Part-1)/2014 ENERGY EFFICIENCY LEVEL 1

KVA 25 MAX. TOTAL LOSS AT 50% RATED LOAD W 110

HV 11000 / 3 MAX. TOTAL LOSS AT 100% RATED LOAD W 300


VOLTS AT NO LOAD (V)
LV 240 TYPE OF COOLING ONAN

HV 75 OIL °C 35
BIL (kV Peak) TEMP. RISE
LV NA WDG °C 40

105
HV 3.94 MASS OF OIL kg 41
CURRENT (A)
LV 104.17 TOTAL MASS kg 219
FREQUENCY Hz 50 VOLUME OF OIL Ltr 49
VECTOR GROUP 1-PHASE MONTH & YEAR OF MFG. /2023
/2024
IMPEDANCE VOLT % 4 SERIAL NO. *
DISPATCH DATE - EXPIRY DATE G.P. -
CONDUCTOR MATERIAL HV FUSE RATING amp 10

175
ALUMINIUM

CUSTOMER - JVVNL

P.O. No.

MADE IN INDIA
SUBTRACTIVE POLARITY

Signal Light
1.1 2.1

ICB

2.1 2.2(n)
70
1.1 1.2(N)

HV FUSE LINK

1.2(N) 2.2(n)

105

MANGAL ELECTRICAL INDUSTRIES PVT LTD, JAIPUR


Title:
RATING AND DIAGRAM PLATE
Rating :

25 KVA, 11/√3/0.240 KV, 1Ø, 50 Hz, ONAN, DISTRIBUTION TRANSFORMER


Buyer's Reference:
ALUMINIUM WOUND Scale
NOTES :-
- AMORPHOUS CORE N.T.S.
1- ' * ' MARKED ITEMS SHOULD BE PUNCHED AT THE TIME OF DISPATCH.
2- MINIMUM 8 RIVETS FOR FIXING. ENERGY EFFICIENCY LEVEL 1 DATE : 30.03.22 REV.No.

3- MATERIAL - STAINLESS STEEL 0.9 WITH TOLERANCE ± 0.1 MM. THICK. DRN BY

00
DRAWING No.

4- ALL DIMENSIONS ARE IN MM. MITESH


SKY|TRAFO ME/RP/92
TANK INSIDE DIAMETER (d) mm 450
TANK INSIDE HEIGHT (h) mm 630
OVERALL HEIGHT (H) mm 990 Min. AIR CLEARANCES IN mm.
OVERALL BREADTH (B) mm 660 6 VOLTAGE H.V. L.V.
OVERALL WIDTH (W) mm 600 PHASE TO PHASE NA NA
PHASE TO EARTH 140 40 / 20(box inside)
WEIGHTS / QTY.
7
TRANSFORMER OIL Ltrs. 49 18 21 QR code 1
TOTAL TRANSFORMER Kg. 219 8 20 Technical cum Identification Plate 1
TRANSFORMER OIL Kg. 41
TANK & FITTINGS Kg. 41 1.2 17 19 19 Anti-theft SS bolt 1
INTERNAL ASSEMBLY Kg. 137 18 Oil Filling Hole with Cover (1 1/4") 1
17 Thermometer Pocket with cap 1
4 14
16 Prismatic Oil Level Gauge 1
15 Lifting lugs for complete unit 2
1.1 9 14 Pole mounting bracket (as per spec) 2
13 Signal light* 1
10 3
12 Internal Circuit Breaker handle* 1
11 Tank Earthing terminal 2
15 1 10 Pressure relief device 1
2.1
9 L.V. Bushing 2
8 Top cover clamp (Rim type) 1
13
7 H.V. Neutral bushing 1
2.2(n)
12 6 H.V. Bushing 1
5 Rating & terminal marking plate 1
21 4 H.V. Terminal marking 1 set
3 L.V. Terminal marking 2 set
20
2 Earthing terminal (LV box) 2
1 LV cable box* 1
S. No. Description Qty.
MANGAL ELECTRICAL INDUSTRIES PVT LTD, JAIPUR
Title:
OUTLINE GENERAL ARRANGEMENT DRAWING (3D)
Rating :
5 25 KVA, 11/√3/0.240 KV, 1Ø, 50 Hz, ONAN, DISTRIBUTION TRANSFORMER
Notes :-
Buyer's Reference:
1- All dimensions are in mm. Tolerance as per spec. 2 ALUMINIUM WOUND Scale
2- This drawing shows only general disposition of fittings. - AMORPHOUS CORE N.T.S.
3- Tank side plate - 2.0 mm. Thk.M.S. 11 16 ENERGY EFFICIENCY LEVEL 1 DATE : 30.03.22 REV.No.
Top & bottom - 2.5 mm. Thk.M.S. DRN BY DRAWING No.
4- Paint Shade : Olive Green Color conforming to No. 220 of IS : 5 / 1961 S KMITESH
Y|TRAFO ME/GA/92/3D
1.1
CONDUCTOR SIZE 12 2
11
LV HV 2.2
Bare 8.7 x 3.3 2.58 Dia 10
Aluminium DPC Polyesterimide
enamel (Class H)
2.1
Conductor
- 1
Configuration 2W x 2D
15
CORE SIZE 13 3
Core Window Height 260 mm
Core build up 2 x 44.5 mm
Core Sheet width 213 mm
Coil Dimensions 4
LV HV
ID 95 x 221 166 x 289 8
OD 160 x 283 260 x 385 1.2 15 QR code 1
AXIAL HT. 247 (INCLUDING END PACKING) 14 CORE EARTHED ON CORE CLAMP 1
13 IDENTITY PLATE 1
12 INTERNAL CIRCUIT BREAKER* 1
11 HV LEAD -
10 LV LEAD -
9 CORE (AMORPHOUS) 2 nos
9 8
7
LV & HV COIL (ALUMINIUM)
BOTTOM CORE CLAMP (2mm)
1 set
1
6 COIL SEPARATOR 1 set
5 CHANNEL SEPARATOR 1 set
4 END INSULATION 1 set
5 3 TOP CORE CLAMP (2mm) 1
2 LOCKING CUM LIFTING LUG 2
1 HV FUSE LINK* 1
SL.No. LIST OF FITTINGS Qty.
MANGAL ELECTRICAL INDUSTRIES PVT LTD, JAIPUR
Title:
INTERNAL CONSTRUCTIONAL DETAIL DRAWING (3D)
Rating :
7 6
25 KVA, 11/√3/0.240 KV, 1Ø, 50 Hz, ONAN, DISTRIBUTION TRANSFORMER
Buyer's Reference:
ALUMINIUM WOUND Scale
Notes :- AMORPHOUS CORE N.T.S.
1- All dimensions are in mm. Tolerance as per spec.
14 -
ENERGY EFFICIENCY LEVEL 1 DATE : 30.03.22 REV.No.
DRN BY DRAWING No.
2- This drawing shows only general disposition of fittings.
SMITESH
KY|TRAFO ME/IC/92/3D
1.1 12
11
LV SIDE 2.2 (n)
1.2 (N) HV SIDE
2.1
1 10
2
3
8
6
4
7
5
9
H.V. SIDE VIEW SIDE VIEW L.V. SIDE VIEW
Note: The outer coil assembly is covered with craft paper and this is integral part of the transformer hence it could not be opened during physical verification.
12 INTERNAL CIRCUIT BREAKER * 1
11 HV LEAD -
10 LV LEAD -
9 CORE (AMORPHOUS CORE) 2 Nos
CONDUCTOR SIZE Coil Dimensions 8 LV & HV COIL (ALUMINUM) 1 Set
LV HV LV HV 7 BOTTOM CORE CLAMP 1
Bare 8.7 x 3.3 2.58 Dia ID 95 x 221 166 x 289
Polyesteramide
6 COIL SEPARATOR 1 Set
Aluminium DPC OD 160 x 283 260 x 385
Conductor
enamal (Class-H) 5 CHANNEL SEPARATOR 1 Set
2W x 2D - AXIAL HT. 247 (Including End Packing)
Configuration 4 END INSULATION 1 Set
3 TOP CORE CLAMP 1
2 LOCKING CUM LIFTING LUG 2
CORE SIZE
1 HV FUSE LINK * 1
Core Window Height 260 mm
Core Build Up 2 x 44.5 S. NO. LIST OF FITTINGS QTY
Core Sheet Width 213 mm MANGAL ELECTRICAL INDUSTRIES PVT. LTD.
INTERNAL CONSTRUCTION DETAIL DRAWING
Rating 25 KVA
KV Class 11/ 3/0.240 KV, 1Ø, 50 Hz
Doc. No. DWG No. OGA/25/01 REV. 0
NAME DATE SCALE CUSTOMER :
DRN. BY MITESH 04-08-2023 N.T.S. DATE
'*' MARKED ITEM NOT PROVIDED AT THE TIME OF TESTING. CHD. BY AMIT REV. 01
APPR. BY AMIT REV. 02
BIRD GUARD
TERMINAL
CONNECTOR
6
10 15
16 1
13 7
9
H

2.2 (n) 2.1


1.2 (N) 3
12
20
h

5 14
11
d
'*' MARKED ITEM NOT PROVIDED AT THE TIME OF TESTING.
B
HV SIDE SIDE VIEW LV SIDE 20 TECHNICAL PLATE * 1
(MOUNTING) 19 ANTI-THEFT SS BOLT * 1
18 OIL FILLING HOLE WITH COVER (141") 1
19 14
17 THERMOMERTER POCKET 1
16 OIL LEVEL GAUGE 1
17 15 LIFTING LUGS 2
18 14 POLE MOUNTING BRACKET 2
Tank Inside Dimensions (mm) Weights/Qty (kg) 13 SIGNAL LIGHT * 1
TRANSFORMER OIL ltrs 49 12 INTERNAL CIRCUIT BREAKER HANDLE 1
Diameter (d) 450 11 TANK EARTHING TERMINAL 2
TOTAL TRANSFORMER 219
Height (h) 630 10 PRESSURE RELIEF DEVICE 1
W

TRANSFORMER OIL 41
9 L.V. BUSHING 2
Overall Dimensions (mm) TANK & FITTINGS 41 8 TOP COVER CLAMP 1
INTERNAL ASSEMBLY 137
1.1 Height (H) 990 7 H.V. NEUTRAL BUSHING 1
Min. Air Clearances (mm) 6 H.V. BUSHING 1
4 Breadth (B) 660
VOLTAGE H.V. L.V. 5 RATING & TERMINAL MARKING PLATE 1
2 Width (W) 600 PHASE TO PHASE NA NA 4 H.V. TERMINAL MARKING
1
SET
PHASE TO EARTH 140 40/20 (box inside)
3 L.V. TERMINAL MARKING
1
TOP VIEW SET
2 EARTHING TERMINAL (LV BOX) * 2
1 LV CABLE BOX 1
S. NO. DESCRIPTION QTY
MANGAL ELECTRICAL INDUSTRIES PVT. LTD.
Note:- OUTLINE GENERAL ARRANGEMENT DRAWING
1. ALL DIMENSIONS ARE IN MM. TOLERANCE +/- 10%.. Rating 25 KVA
2. THIS DRAWING SHOWS ONLY GENERAL DISPOSTION OF FITTINGS. KV Class 11/ 3/0.240 KV, 1Ø, 50 Hz
3. TANK SIDE PLATE - 2.0 mm. Thk. M.S. DOC No. DWG No. OGA/25/01 REV. 0
TOP & BOTTOM PLATE - 2.5 mm. Thk. M.S. NAME DATE SCALE CUSTOMER :
DRN. BY MITESH 04-08-2023 N.T.S. DATE
4. PAINT SHADE : OLIVE GREEN COLOR CONFORMING TO NO. 220 OF IS : 5/1961.
CHD. BY AMIT REV. 01
APPR. BY AMIT REV. 02
B

C
A

E D
MATERIAL - AMORPHOUS CORE
Dimensions
(MM)
FLUX DENSITY CALCULATION
A 260
CORE DIMENSION :-
B 90
WIDTH - 213 mm.
STACK - 44.5 mm. C 44.5

No. OF LOOPS - 2 Nos. D 213


GROSS AREA - 18957 Sq. mm.
STACKING FACTOR - 0.86 E 179
NET CORE AREA (A) - 16303.02 Sq. mm. Nos. 2
FREQUENCY (f) - 50 Hz.
No. OF LV TURNS (N) - 48 Weight 98 kg
SECONDARY VOLTAGE (V) - 0.240 kV

FLUX DENSITY = MANGAL ELECTRICAL INDUSTRIES PVT LTD, JAIPUR


Title:
9 CORE DRAWING
0.240 x 10
= 1.381 TESLA Rating :

4.44 x 50 x 16303.02 x 48 25 KVA, 11/√3/0.240 KV, 1Ø, 50 Hz, ONAN, DISTRIBUTION TRANSFORMER
Buyer's Reference:
ALUMINIUM WOUND Scale
- AMORPHOUS CORE N.T.S.
Notes :- ENERGY EFFICIENCY LEVEL 1 DATE : 30.03.22 REV.No.

1) All dimensions are in mm. DRN BY

00
DRAWING No.

Unless othewise specified. SMITESH


KY|TRAFO ME/CD/92
MANGAL ELECTRICAL INDUSTRIES PVT LTD, JAIPUR
THERMAL ABILITY TO WITHSTAND SHORT CIRCUIT
25 KVA - 6.351/0.24 - 1Ø TRANSFORMER
Core: AMORPHOUS Conductor: ALUMINIUM
S.No Description Unit LV HV
A. Per Unit Impedance (ez) 0.0400 0.0400
A / Sq.
B. Working current density mm
0.925 0.753
A / Sq.
C. Current density (F1) under short circuit C = B/A mm
23.12 18.82
D. Ambient temperature Deg. C 50 50
E. Winding temperature Rise Deg. C 40 40
F. Initial temperature q0 = (D + E) Deg. C 90 90
Max. permissible average winding temperature (q2) as per
G. Deg. C 180 180
IEC : 60076 Table 3
H. Duration of short circuit (t) Sec. 2 2
Highest average winding temperature attained after short
I. Deg. C. 105.1 99.9
circuit q1 = q0 + {[(2 x (q0 + 225)] / [(45700/(J2 x t)-1]}

NOTE :
q1 CALCULATED IS LESS THAN q 2 SPECIFIED IN IS 2026 (Part 5) : 2011
MANGAL ELECTRICAL INDUSTRIES PVT LTD, JAIPUR
HEAT DISSIPATION CALCULATION OF 25 KVA - 6.351/0.24 - 1Ø TRANSFORMER

Core: AMORPHOUS Conductor: ALUMINIUM


COOLING CALCULATION
1 Tank Inside Dia mm 450.0
2 Avg. Tank Inside Height mm 630.0
3 Tank Side Sheet Area M² 0.891
4 Watts Dissipated by Tank Surface / Sq. Mtr. W 500
5 Total Loss at 50 % loading W 110
6 Total Loss at 100 % loading W 300
7 Tolerance 0% W 0.00
8 Total watts to be dissipated W 300.0
9 Total Watts Dissipated by Tank W 445.3
10 Extra Dissipation W 145.3

Transformer is capable of giving continuous rated output without exceeding the specified
temperature rise because losses dissipated by tank are more than losses to be dissipated.
174
30 30 117
30 30
237
2 NOS. MA FLAT 50X8 mm at L=553 MM (1.736 KG Each)
NOTE:
1. All Dimension in MM.
MANGAL ELECTRICAL INDUSTRIES PVT. LTD.
2. Not to Scale the Drg. CLAMP FOR MOUNTING
Rating 25 KVA
3. Hole size 17.5 mm. KV Class
DOC No. DWG No. LV/25/02 REV. 0
4. If Transformer installed at 4 Meter Height from groung level.
NAME DATE SCALE CUSTOMER :
DRN. BY MITESH 04-08-2023 N.T.S. DATE
CHD. BY AMIT REV. 01
APPR. BY AMIT REV. 02
30 177 30
L-ACCORDING L-ACCORDING
TO SIZE OF TANK TO SIZE OF TANK
237
237
100
25
TANK OF 1- Ø 25 KVA TRF
MANGAL ELECTRICAL INDUSTRIES PVT. LTD.
NOTE:
Rating 25 KVA
1. All Dimension in MM.
KV Class
2. Not to Scale the Drg. DOC No. DWG No. LV/25/03 REV. 0
3. Hole size 17.5 mm. NAME DATE SCALE CUSTOMER :
DRN. BY MITESH 04-08-2023 N.T.S. DATE
4. MS Flat 50x8 mm. CHD. BY AMIT REV. 01
APPR. BY AMIT REV. 02
TANK WALL
1 8
M12
1
7 2
4
6
METER
5
3
SIDE VIEW
FRONT VIEW SIDE VIEW
LV CABLE BOX WELDED
WITH TANK WALL
Description
10 KVA 8 LUGS -
Cat No / Thk Qty. 7 METER 1
Lugs for LT Terminal 7043 / 2 mm 4
GLASS (SIZE 115X150X6 MM) FOR METER
6 1
Outgoing LT Terminals 1.1 KV / 250 A 2
5 SLIDING COVER WITH GLASS 1
Terminals ends for Meter ACP-254 / 10x2mm 4
4 OUTGOING BUSHING 2
3 BODY EARTHING TERMINAL (M10 BOLT) 2
25 KVA
Description 2 PVC COVERED CABLR -
Size
Copper Flexible Cable LT Terminal to
1 LV CABLE BOX WITH METER DISTRIBUTION BOX -
70² MM
Meter & Outgoing Bushings
S. NO. DESCRIPTION QTY
Electrical Clearance Inside MANGAL ELECTRICAL INDUSTRIES PVT. LTD.
Box min LV BOX WITH METER BOX FOR SINGLE PHASE TRANSFORMER
Rating 25 KVA
P-E 20 mm
KV Class 6.351/.240 KV, 1Ø, ONAN, DISTRIBUTION TRANSFORMER
NOTE: DOC No. DWG No. REV. 0
TOP VIEW ALL DIMENSTION ARE IN MM & TOLERANCE +- 5 % DRN. BY
NAME
MITESH
DATE
08-07-2023
SCALE
N.T.S.
CUSTOMER :
DATE
CHD. BY AMIT REV. 01
APPR. BY AMIT REV. 02