Release Overview 607
Release Overview 607
Release 6.0.7
Rev. A
Valmet 0-i
Refer to this publication for complete and accurate information that helps you better operate and service Valmet Inc.
equipment. Your comments and suggestions are welcome.
Valmet Inc.
2750 Morris Road
Lansdale, PA 19446
Attention: Manager, Technical Publications
This document is the exclusive intellectual property of Valmet, Inc. and/or its subsidiaries (collectively “Valmet”) and is
furnished solely for operating and maintaining the supplied equipment and/or software. Use of the document for any
other project or purpose is prohibited. All copyrights to the document are reserved by Valmet. Accordingly, the
document or the information contained therein shall not (whether partly or entirely) be reproduced, copied or disclosed to
a third party without prior written consent of Valmet.
Printed in the United States of America
All Rights Reserved
0-ii Valmet
Contents
Introduction................................................................................................................................................................. 1-1
Overview................................................................................................................................................................... 1-1
Windows 7 ........................................................................................................................................................ 1-1
Release 6.0.7 Update Details ................................................................................................................................ 1-2
New maxVUE V4 Compatibility Option .......................................................................................................... 1-2
maxSCRIPT Run Command Enhancement ....................................................................................................... 1-2
New Report Subsystem Features ....................................................................................................................... 1-3
New Report Print Preview Application ............................................................................................................. 1-3
Legacy Report Migration .................................................................................................................................. 1-3
Event Subsystem – Duplicate Events for same Point ........................................................................................ 1-3
New maxSTORIAN Statistics ........................................................................................................................... 1-3
New CheckBIOS Utility.................................................................................................................................... 1-3
Virtual DPU Backup ......................................................................................................................................... 1-4
maxDNA List Control Pop-up Navigation ........................................................................................................ 1-4
SimConsole Improvements ............................................................................................................................... 1-5
Release 6.0.6 Update Details ................................................................................................................................ 1-6
Integrated PROFIBUS installation .................................................................................................................... 1-6
Integrated Field Care Installation ...................................................................................................................... 1-6
maxDPUTools changes ..................................................................................................................................... 1-6
Documentation Updates .................................................................................................................................... 1-6
Release 6.0.5 Update Details ................................................................................................................................ 1-8
Special Applications ......................................................................................................................................... 1-8
Maximum Operator Security Level Enforcement ............................................................................................. 1-8
Convert Slider Control VB Script ..................................................................................................................... 1-8
Legacy HWTest Display Change in Behavior .................................................................................................. 1-9
Support for DPU/ACN MR 6.1 ......................................................................................................................... 1-9
ACN MR Details Display ................................................................................................................................. 1-9
maxDPUTOOLS MIO Download of Redundant MIO .................................................................................... 1-10
Allow maxSTATION Installation on Windows Server 2008 .......................................................................... 1-10
Auto Update of Sizable Trend Assignments ................................................................................................... 1-10
Last Button Expanded ..................................................................................................................................... 1-10
Sizable Trend Date and Time Color................................................................................................................ 1-10
Documentation Updates .................................................................................................................................. 1-10
Navigation Button Configuration .................................................................................................................... 1-11
Release 6.0.4.1 Update Details ........................................................................................................................... 1-11
Point Call-up Button ....................................................................................................................................... 1-11
LSS HID Alarming ......................................................................................................................................... 1-11
Release 6.0.4 Update Details .............................................................................................................................. 1-12
Special Applications ....................................................................................................................................... 1-12
VB Script to Convert Trend Displays ............................................................................................................. 1-13
Enhancements to the Bar Control .................................................................................................................... 1-13
Simulator Control Console .............................................................................................................................. 1-14
Valmet 0-1
Release Overview
0-2 Valmet
Chapter 1
Introduction
Overview
maxSTATION Release 6.0.7 is a full install update to Release 6.0.6
intended to support existing customer upgrades to WINDOWS 7, and
include fixes (refer to Bugs Fixed Section) to previous 6.0.x Releases.
The DVD includes a folder that contains an installation file for Chinese
Fonts. This is not installed automatically, but is available for Chinese
Windows installations.
The release DVD also includes a folder that contains an installation file
for .Net 4.0. This should be automatically installed if not already on
the station, but some Chinese Windows laptops failed this installation.
This folder is included so that the .Net package can be manually
installed without going to the Internet to download files. In order to
fully use .Net on Chinese Windows, a Chinese language pack (not
included on the DVD) should also be installed.
Windows 7
Release 6.x runs only in a computer running Microsoft Windows 7.
Windows 7 64 bit Professional and above are supported by this release
of maxSTATION.
Valmet 1-1
Release Overview
The option to disable (by user) the ghost image that appears briefly
when closing a pop-up has been added.
Change the MCS Registry User default setting from “No” to “Yes” to
eliminate this new feature. Then restart the system.
1-2 Valmet
New Report Subsystem Features
The Report Subsystem has been enhanced as follows:
1. Separate Start of Shift Time
2. New Shift information added to the database
3. New Report attributes
4. User interface improvements when creating reports
5. Improvements to online Report user interfaces
Valmet 1-3
Release Overview
Each cell may be configured to allow the use to take an action when
that cell is clicked – write a value or set the selected point for the
information shown by that cell.
1-4 Valmet
"Popups\%{%{param1}.objtype}\%{%{param1}.objtype}-control.mn"
This works as long as the user clicks inside a cell on the List Control
where every cell is associated with the same system point. The list
control sets the selected point and requests maxVUE Runtime to
navigate to the pop-up.
However, if there is a border around the List Control and the user
actually clicks on the border around the List Control, the selected point
is not set (because the click was not in a cell) and the pop-up content
will be based on whatever the selected point is at that time.
"Popups\%{%{param1}.objtype}\%{%{param1}.objtype}-control.mn" dp1=%{%{param1}.tagname}
Note that this means all pop-up navigate (e.g. right click menus,
horizontal toolbars) must use this technique.
SimConsole Improvements
New features have been added to the SimConsole interface:
1. Reset Wait Time Setup – the user may specify a time in
seconds to wait before commanding Virtual DPUs to start
running.
2. Protected Scenarios – the user may define specific scenarios as
protected to keep them from accidentally being overwritten or
deleted.
3. Reset time improvement – Virtual DPUs are now commanded
to reload simultaneously if running on different maxSTATIONs
instead of processing each one serially.
Valmet 1-5
Release Overview
maxDPUTools changes
Changes have been made to the Online differences, DPU upload, and DPU
Bulk Upload dialog displays to include the showing of the current status of both
DPUs of a DPU pair. The intent is to allow the user to choose the Inactive Hot
member of a DPU pair for the selected operation. Previously for differences
and Bulk Upload, only the active DPU was used by default. Selecting the
Inactive Hot DPU will produce the same results as using the Active DPU, and
avoids the additional loading on the Active DPU, which has the potential to
slow peer-to-peer subscription data transfer, causing problems when these data
transfers are critically timed. The dialog displays now accentuate with highlight
text that an Inactive Hot DPU is the preferred choice to use when present.
Documentation Updates
1-6 Valmet
278609 System Resources
5 278588 maxScript User’s Guide
278589 Atoms – Function Block Programmers Guide
278623 maxLinks User’s Guide
278711 maxAPPs User’s Guide
278715 HART Configuration Guide
278718 DPU-ACN Links Configuration Guide
278730 maxSTORIAN User’s Guide
278740 DPU MR User’s Guide
278745 PROFIBUS Windows 7 User’s Guide (new)
278747 maxEDC User’s Guide
278748 maxDNA Windows 7 Fieldcare User’s Guide
(new)
Valmet 1-7
Release Overview
1-8 Valmet
found in the C:\Mcs\Setup folder that will convert displays that use the
Slider to use the Bar control. Instructions on its use may be found in
Volume 2 Publication 278605 Auxiliary Functions User’s Guide.
Valmet 1-9
Release Overview
Documentation Updates
1-10 Valmet
Multiple documents have been updated in this release. In addition,
some new documents have been added for the application specials that
have been added with this release.
Volume Document
1 278561 System Power and Grounding
278596 maxPAC Hardware Reference Guide
278599 maxSTATION Operator’s Guide
278740 DPU MR User’s Guide
2 278594 Auxiliary Functions User’s Guide
278605 maxDPU Auxiliary Functions User’s Guide
3 278568 Model IOP Quad PAT Module
278577 Model MAS Auto/Manual Station Installation
5 278709 maxCALCS Performance Calculations User
Guide
278721 Terminal Server User’s Guide
278724 File Sync User’s Guide
278728 Network Diagnostics User’s Guide
278730 maxSTORIAN User’s Guide
278746 GSM Link User’s Guide (new)
278747 maxEDC User’s Guide (new)
6 278742 maxACN MR User’s Guide
Valmet 1-11
Release Overview
1-12 Valmet
These applications have been moved to sub-folders in C:\Mcs and if
they exist on a target station, will be removed from
C:\Custom\Applications and saved in C:\Temp\CustomApplications.
The new MNT files may be imported using the maxVUE Editor which
will convert the displays to use the newer Sizable Trend Wrapper.
2. Under the "Bitmap" tab, a "Use HalfTone" check box. Use this
to display bitmap using half tone drawing mode.
Valmet 1-13
Release Overview
Chinese Fonts
1-14 Valmet
The Release DVD for 6.0.4 includes a folder called “Chinese Fonts”
that includes an installation file for systems that are using Chinese
Windows. Double click the file to install useful Chinese Fonts.
Time Sync
The 6.0.4 Release includes the Time Sync application for using a
maxSTATION to maintain system time. For details, please refer to
Publication 278609 System Resources User’s Guide.
ACN MR Support
The 6.0.4 Release includes support for the ACN MR controller. For
details, please refer to documentation in Volume 6 of the maxDOCS
folders.
Documentation Updates
The 6.0.4 Release includes updates to various publications.
Volume 1
278599 – maxSTATION Operator’s Guide; Updates for Special
Applications added as a new chapter; Display updates for the
ACN MR and DPU MR controllers.
Volume 2
278594 – maxSTATION Auxiliary Functions User’s Guide;
updated details regarding the use of Alternate Language in the
Event Summary display; Updates for Special Applications
added as a new chapter.
Volume 3
Volume 4
Volume 5
Valmet 1-15
Release Overview
1-16 Valmet
a. Updated maxDPUTools support and master files for the
configuration of DPU MR and ACN MR.
b. A new UNIXToDOSFileConversion for EWS Import files
in a folder hierarchy
maxLINKS
The maxLINKS suite is included.
The program’s operation is identical to release 4.5.1.
NOTE: The maxLINKS functionality has only been qualified for use
with the MODBUS TCP and MODBUS Serial. Testing remains
ongoing for other protocols. Please contact Lansdale for information on
the use of other link types.
Transfer Tool
The transfer tool is included.
The program’s operation is identical to release 4.5.1.
DPUMRSetup
This program has been updated to support SD card and network
programming for both the DPU MR and ACN MR.
Terminal Server
The Terminal server was updated to now support flexible IP address
use.
Valmet 1-17
Release Overview
1-18 Valmet
Release 6.0.2 Update Details
maxDPUTools
Improvements have been added to validate the maxPAC bus address
assignments based on the rules for modulo address alignment, and span
of addresses required per the different buffer types combined with
maxPAC attribute setting. Fast DIB address ranges will also be
validated.
Data validation for the address will take place on the detail grid as entry
is completed. Dropdowns have been added to now show HEX address
format as well as integer value. Complete Validation can be demanded
but will also run prior to an install. Errors such as invalid or
overlapping address assignments will prevent a download from starting
until corrected. A docked validation pane will appear on demand to
show the results and allow navigation to the detail when correction is
needed.
The Hardware tab has also been improved to show the range of bus
addressing used by a buffer, and will include yellow or red background
highlighting of problems along with error message tooltips.
Advance configuration support has been added for the new model DPU
MR and ACN MR. Each has a 6.0 release version master configuration
included. The configuration file types will use file extents of
“DPUMR”, and “ACNMR” to distinguish them from the “4E” and
“4F”. Upwards conversion is supported for migration of existing
configurations to the newer versions as needed.
Valmet 1-19
Release Overview
1-20 Valmet
maxVUE Editor and Runtime
The option to display all Buttons with rounded corners has been added.
The option to add a surrounding glow to a button when the mouse is
placed hovering over the button has also been added.
Valmet 1-21
Release Overview
Terminal Server
Release 6.0.2 adds support for a Microsoft Windows Server 2008 R2
Terminal Server that allows limited access to a maxDNA system from
the Internet. Refer to the updated “278721_Terminal Server User's
Guide_A5.doc”
1-22 Valmet
Chapter 2
Bugs Fixed
Valmet 2-1
Release Overview Release 6.0.5
2-2 Valmet
6.0.7 Reports maxHISRepsvr (6-3218, 3901,3211) – Fixed report
wrapper calculations bug; fixed problem using same
report for multiple intervals; added new separate
shift start time, new protocol optimization for Control
panel; add backwards compatibility for generated
files without a papersize assignment
6.0.7 Reports maxHISReportEditor 6-(3901) - Added Separate shift
start time configuration. Corrected export options.
Added point group up/down sorting buttons
6.0.7 Reports Report Control Panel (6-3901) – Improved user
interface; dynamic resize for wide vs. 4 x 3 monitor
screens
6.0.7 Reports Note that in Windows 7 the legacy report export
options for Lotus 123 and Excel 5.0 Extended are no
longer supported due to a change in Crystal reports.
These will now be automatically changed to Excel
5.0, when a report definition is opened in the editor.
6.0.7 Reports ReportPrintPreview – new application to show
Report Previews without the Report Control Panel
6.0.7 Reports (6-3316) - In the report editor correct the double click
selection of a Group or Point in a Group for
modification.
6.0.7 OPC - MAXOPCServer & MAXOPCHDAServer (6-2838) -
Add missing AppId to the registry required for OPC
Client to Server connections
6.0.7 OPC OPC90Gateway (6-2271) - Use DPMS prefix in
OBJType import for simulator. Use one reference
subscription to synchronously write value and quality
6.0.7 OPC MAXOPCAEClient (6-2813) - Correct the failure of
subscription, when a warning status is returned
6.0.7 maxDPUTools (6-2030) - Correct import library out-of-date
comparison after a DPU revision upgrade
6.0.7 maxDPUTools (6-2104) – Added missing EB attributes for use as
references to the 6.1 DPUMR master configuration.
Now dated as 11/Aug/2015.
6.0.7 maxDPUTools (6-1601) – Changed the display layout of the Bulk
Configuration Upload dialog to fit in 1024 X 768
screen resolution.
6.0.7 maxDOCS (6-727) - Fixed the table of contents and other
cleanup of Power and Grounding manual 278561;
(6-3905),(6-35), (6-244) (6-2337)- fixed missing
diagrams for Ethernet Buffer in the atoms manual;
278589 Clarified SCM version in Links manual.
Fixed the installation instructions for Ethereal.
Updated FB Status attribute in the atoms manual
6.0.7 File Sync maxFileSyncViewer (6-2423) – Fixed slow dialog
update when some maxSTATIONS are not up
6.0.7 Point Browser (6-3726) – Fix Atoms Types GRP browsing that
showed no groups when any GRPs were locked
Valmet 2-3
Release Overview Release 6.0.5
2-4 Valmet
6.0.6 maxVUE MCSEnumFieldsControl – Corrected initial data
display problems and database disconnect on exit.
6.0.6 Reports MaxPrintSvr – Updated the Crystal report format
type for an HTML export to be HTML V4.0 rather
than 3.2 which is no longer available.
6.0.6 Reports MCS_MAXVUE_CONTROLPanel - Add back in the
demand export options for HTML and EXCEL.
6.0.6 Reports maxHisRepSvr - (6-3633) - corrected filtered Event
Query request.
6.0.6 Startup Startup (6-2812) - Run the applications using
ShellExecute API for which elevation is required.
6.0.6 maxVUE (6-4760) - fix crash attempting move to another page
of a multi-page Sheet after opening a pop-up for the
selected point (presumably Block on that Sheet).
6.0.6 maxVUE MCSTrendControl - (5-2529) - Validate the syntax of
dynamic trend requests and don't pass them on to
maxSTORIAN if they are bad.
6.0.6 maxDPUTools Correction to Upload and differencing - During
master configuration version discovery only compare
the downloaded configuration version stored as the
/System.Title for a virtual DPU.
6.0.6 maxVUEEditor (5-4118) - Correction for stall out when canceling the
security password entry initiated before an auto-
arrange.
6.0.6 maxDPUTools (6-983) – For the DPU MR master configurations,
change the FB Buffer LookAhead default value to 1
rather than 8.
6.0.6 maxVUE Add "MR" to DPU MR details displays' bitmap.
6.0.6 maxDPUTools (6-4868) - Correct reference validation to accept a
.Quality sub-attribute included in a reference.
6.0.6 MAXMergeAlm (6-3924) - Expanded the limit of merge alarm
sources to 100 from 20. Also now allow for an LSS
specification of the local station name as [name] in
brackets. Do not include any _lss suffix! It is implied.
This second entry will be ignored, but this allows for
a common ini file to be used among all workstations,
rather than having to comment out the local station
on each.
6.0.6 maxVUEEditor (6-4221) - fix Import of rotated bitmaps.
6.0.6 MAXMergeAlm (6-2929) - Fix alarm summary subscription routing of
alarm text and point description using a pivot
identifier, when multiple instances of the same alarm
service are registered and have equal Quality of
service, as in OPC client redundancy.
6.0.6 SBP (6-1411) - added code to protect against multi-cast
subscriptions by treating them as 'normal'.
6.0.6 maxSTORIAN/Back (6-1959) - Correct loss of data on network breaks.
FillHoles
6.0.6 SBP (6-64) - add flush logic for output buffers.
Valmet 2-5
Release Overview Release 6.0.5
6.0.6 CsvExport and (6-2629) - A hand edited import file list of points
mxsExport needs to be compared case insensitive when
matched against maxStorian configuration.
6.0.6 maxOPCServer (6-2896) - Add an SBP service to allow browser
access to dialog data when running as session 0.
6.0.6 AnnunTask (6-4931) - Correct memory leak introduced in 6.0.5
when running as a service.
6.0.6 maxVUE MCSButtonControl (6-64) - fix potential for solid loop
which can cause Runtime hang
6.0.6 maxVUE MCSTextState (6-64) - fix potential for solid loop
which can cause Runtime hang
6.0.6 maxVUE MCSTimeState (6-64) - fix potential for solid loop
which can cause Runtime hang
6.0.6 maxDPUTools Updated Dpu MR version 6.1 - Added Fast maxPAC
option to TC and RTD for use with new revision
modules.
6.0.6 maxVUEEditor SbpMonitor\maxRRSView - (6-2023 & 6-71) - fix
crash when maxRRSView ocx display is opened in
Editor
6.0.6 SBP (6-64) - change pipe wait timeout from 12 sec to
100 ms; add IpcShutdownAllMyConnections
interface.
6.0.6 maxVUE (6-64) - add call to IpcShutdownAllMyConnections
immediately before creating new maxVUE Runtime.
6.0.6 OPCGatewayConfig (OPC90) - Remove access repair, it stalls on a very
large configuration. Preserve ref entry when re-
importing. Clone attributes for a user defined
objtype. Allow RW access combined with a
reference.
6.0.6 maxVUE (ACN MR testing) - MEIBC Detail Popup MIO status
modifications; TMode text expanded
6.0.6 maxEDC Added xlsSbpServer.reg file to installation (both
maxSTATION and maxEDC)
6.0.6 maxDPUTools (6-3674) - correct search criteria results that
compare numeric values.
6.0.6 maxVUE MCSEnumFields (IR#84) - correct logic to handle
multiple enumeration fields on one display; do not
unload database in destructor
6.0.6 maxSCRIPT (6-2634) Expand the pointer table size of allowed
constants and subscriptions from 200 to 512.
6.0.6 maxSTORIAN (5-146) Improve slow midnight retrieval with
prioritizing of retrieval vs. storage.
6.0.6 maxVUE maxDNA_PtDetails_exe - fix v-scroll limits, disallow
windows resizing, only minimize.
6.0.6 maxEDC On an install, add maxEDC Server, Point Browser
mmc & DCOM port to Firewall settings for maxEDC
Client.
6.0.6 maxScript SBP (6-2178) - Correction for local huge string data
subscription lost data.
2-6 Valmet
6.0.6 maxDPUTools HART Library (2879) - Allow short reply to cmd 15
from the Sierra device, that does not include PV H/L
limits.DPU version 4.6, MR versions 6.0 and 6.1
libraries updated.
Valmet 2-7
Release Overview Release 6.0.5
6.0.5 Quick Trend Pop-up Correct the logic to use the configured Hi/Lo Range
and Hi/Lo Alarm information
6.0.5 Tracking Trend Add resize logic so the control draws to fix its given
space
6.0.5 Op Data Groups Improve the user interface for this tool
6.0.5 Graphic Point Improve the display of data on this application
Details
6.0.5 OPC Gateway Convert special characters from Rovisys Imported
Config tagnames to an underscore
6.0.5 VB Sbp Interface Do not issue Subscribe request for blank tagnames
OCX
6.0.5 HealthLog Collecting HealthLog statistics generated enough
SBP activity that it could significantly slow down peer
to peer response between DPU4Fs. This was fixed
by throttling the read requests.
6.0.5 maxARCHIVER Fix hang when corrupted maxSTORIAN filename
has been created
6.0.5 Sbp Control Modified the Subscribe logic to not make a
subscription request if an identifier is not specified
6.0.5 Graphical Add logic to query the DPU for valid Relative Index
Configurator (within a Group) before pasting a Block
6.0.5 Event Summary & Fix Date Conversion bug found when local station
Event Management Short date format was changed
6.0.5 Alarm Summary Fix Date Conversion bug found when local station
Short date format was changed
6.0.5 maxTOOLSUpdate Fix the Emergency down and Initial output state for
and new.mdb downloading the Valve controller control block in
maxTOOLS.
2-8 Valmet
6.0.4 TimeSync Atom help Updated the help for the Time Sync Atom
6.0.4 maxVUE Editor Corrected WMF Export of Sheets that had filled text
objects
6.0.4 Terminal Server Corrected problem with folder permissions set up
during installation
6.0.4 dpmsFSTOUT pop- This pop-up had been missing from the Windows 7
up Release
6.0.4 maxDPUTools Improvements for maxPAC buffer display and
addition
6.0.4 OPCServerConfig Fix configuration notification between this tool and
the OPCServer
6.0.4 maxFileSyncViewer Fix crash when a display using the
maxFileSyncViewer control is opened in maxVUE
Editor
6.0.4 maxLinks Fix problem with Serial Communications to PLC5
Model
6.0.4 mxsArchiveMounts Fix crash when a display using the
mxsArchiveMounts control is opened in maxVUE
Editor
6.0.4 mxsPanel Fix crash when a display using the mxsPanel control
is opened in maxVUE Editor
6.0.4 Browser Fix crash when a display using the Browser control is
opened in maxVUE Editor
6.0.4 maxTRANSPORT Fix problem with startup on Chinese Windows
6.0.4 maxDPUTOOLS Fix problem when maxDPUTools did not fully exit
after performing a version update
6.0.4 maxDPUTOOLS Fix date comparison failure in Chinese Windows
6.0.4 maxVUE Editor Fix failure to create Cross Reference database when
processing a display with a string consisting of 1
double quote
6.0.4 maxSCRIPT Fix crash in maxVUE Runtime – mostly manifested
when opening pop-ups.
6.0.4 Report Control Fix Remote Print Preview function
Panel
6.0.4 maxDPUTOOLS Fix crash when editing data in Graphical
Configuration Sheet view
6.0.4 Events Added support for Russian characters in the Event
Summary display
6.0.4 Sbp Fix memory leak when more than 10 local Sbp
Clients are active in a maxSTATION
6.0.4 maxDPUTOOLS Fixed <F9> attribute selection when an external
identifier is used
6.0.4 maxTRANSPORT Do not overwrite user specified names for non-
maxNET A/B networks
6.0.4 maxVUE Editor Fix crash that occurred when a maxSCRIPT
reference to a default bitmap was not for a bitmap
6.0.4 ModBusHelper Fix crash during message creation
6.0.4 Sbp Correct processing of Daylight Savings Time change
Valmet 2-9
Release Overview Release 6.0.5
6.0.4 maxVUE Editor Fix GDI Resource leak during Bulk Import/Export
functions
6.0.4 maxLINKS Fix crash during MiniConf configuration; fix crash
when installing modbus+ type configuration on
startup
6.0.4 maxDPUTOOLS Correct clearing of references when copying a
custom block in Graphical Configuration mode
2-10 Valmet
6.0.2 Report Subsystem Improved to allow Print Preview of Reports from
security level 0
6.0.2 MCS DateOrTime Corrected for Y2K issues
Control
6.0.2 maxDPUTOOLS Fix crash when users attempts to close
maxDPUTools immediately after doing a download
6.0.2 maxDPUTOOLS Fix timeouts of SBP connection when opening a
Graphical Config Sheet with an exceptionally large number of output
users; show tagname for user (on Sheet) if available.
6.0.2 maxTRANSPORT Problem 5-4732 – Fix problems with Tunnel socket
transport of Huge Transactions; added alarm for
failure of the Tunnel network. Fix crash seen at
customer site’s backup Historian.
Valmet 2-11
Chapter 3
Overview
If you are upgrading from an earlier version of maxDNA, please follow
these extra steps to ensure that your system gets updated properly.
C:\Custom
If you are converting from a Windows XP station, your C:\Custom
folder may be copied from the XP station to the Windows 7 station. Do
not rename or delete the Windows 7 Custom Folder. Copy the contents
of your XP C:\Custom folder directly into your Windows 7 C:\Custom
folder.
Note that the report export options for Lotus 123 and Excel 5.0
Extended are no longer supported due to a change in Crystal reports.
These will be automatically changed to Excel 5.0, when a report
definition is opened in the editor.
Perform these steps on the station that will run the History Report
Server before configuring the server to run. Failure to perform these
steps may cause the Report Server to abort.
Valmet 3-1
Release Overview Release 6.0.5
3-2 Valmet
If you are upgrading from Windows XP you should inspect your
Startup Configuration with respect to the History Report Server. In
Windows 7, the History Report Server must be run as a Service.
Startup Config
If you are upgrading from Windows XP and have copied your Windows
XP version of the C:\Custom\Sbp\maxDNA.ini file you MUST update
this file before starting the system running. The Startup Config utility
will automatically update the file for you.
Valmet 3-3
Release Overview Release 6.0.5
3-4 Valmet