4 GXT-RT
4 GXT-RT
GXT-RT
Double Conversion On Line
1000, 2000, 3000VA
Rack-Tower Convertible Model
NEW GXT-RT at a Glance
GXT-RT
9 Double Conversion On-Line
Topology
9 DSP Controlled
9 Standard back up & Long…really
long back-up models
9 Rack-Tower adaptability
9 Almost Unity (0.99) Power factor at
input
9 <5% iTHD at input
9 Capability to handle extreme low
and high input voltage
9 Capability of handling Extreme
fluctuation of generator frequency
9 Built-in Dynamic Bypass
9 Standard User friendly UPS
monitoring software & Auto shut-
down software
9 Optional SNMP card
GXT-RT : UPS Technology
GXT-RT
z On-Line Double conversion
Bypass
Bypass
– Highest Effectiveness
against all kinds of power PFC / Rectifier Inverter
Class-
Class-D
supply aberrations Input
Class-D
SPD & EMC
EMC Load
SPD & Filter
EMC Filter Filter
EMC Filter
– Zero Transfer Time DC/DC
Charger DC/DC
Charger Converter
Converter
– Dynamic Bypass
Battery
– Ideal for Mission Critical
application to ensure
highest availability
z Warranty Card
GXT-RT : Product Snap
GXT-RT -Shots…..Contd.
Snap-Shots…..Contd.
Configuration Software
z No additional Software CD needed
– What you get is a Configuration method
– With Local PC connected to UPS you can
set up your computer to communicate
with UPS
z Configuration Parameters:
– UPS Voltage set: 220V, 230V, 240V
– Bypass Output Enable/Disable
>>V?
– Auto Battery Test Enable/Disable >>V220, <<220V
z Widest range of acceptable input voltage variation for battery charging: 100V to 300V
– Maximized use of utility to enhance battery life & autonomy time
z Widest Acceptable voltage range for bypass operation: -45% to +20%, settable
at 6 steps
– Most flexible for any site condition ensures output power stability under any
application specific
z Acceptable voltage range for UPS start : 0-288V; Black-Start feature available.
– Need to start UPS under abnormal condition? No Problem!
Value For Money …contd.
Money…contd.
z Rack & Tower Model, all in one!
– Mounting kits are delivered FREE!
– Very Easy to configure. No special Tools!
– Rack: Distribution of power to the server,
nearest to load. This ensures better load
performance
– Tower: Distribution of power to non-rack
mounted critical loads.
– Light & rugged Modules…easy to carry and
mount
• Less than 10Kg for all Modules except 1kVA
Standard back-
back-up
• Approx 20Kg Battery Modules
– Reduced Depth of UPS to 400mm
• Sufficient room space in back helps better heat
dissipation in Rack. Improves heat managment in
Rack for improved availability.
Value For Money …contd.
Money…contd.
z Minimal Transfer time ensures safe working condition and
longer life for the critical loads
– Zero millisecond to Battery mode.
– Approximately 4 milliseconds for UPS to Bypass mode.
z Excellent Steady state & transient performance enhances
equipment life
– Can be set to any voltage, 220, 230, 240V with configuration
software.
– Voltage Regulation within +/-2%
– Sinusoidal output voltage waveform, even on battery mode
(Voltage harmonic distortion < 2%)
– Steady frequency of 50Hz +/- 0.2%
Value For Money …contd.
Money…contd.
z Very High Efficiency saves money (more than 88%)
– Saves energy bill similar to continuous running of an
incandescent lamp
z High overload capacity saves the critical loads from shutting
down, in the event of sudden switching of a high inrush load.
This increases availability to a great extent.
– Continuous over load till 105% Battery Mode