Olr New
Olr New
Olr New
SEDIMENT AREA
NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT
1 SOP 1 57 ~ 82 57 54.8
2 SOP 2 57 ~ 82 57 54.8
3 AOP 1 12 ~ 18 12 10.7
4 AOP 2 9 ~ 13 11 10.7
5 WATER JET PUMP 1 70 ~ 105 70 67.9
6 WATER JET PUMP 2 70 ~ 105 70 67.9
7 WATER JET PUMP 3 70 ~ 105 70 67.9
8 WATER JET PUMP 4 70 ~ 105 70 67.9
9 CEP 1 70 ~ 105 70 67.8
10 CEP 2 70 ~ 105 70 67.8
11 CEP 3 70 ~ 105 70 67.8
12 CEP 4 70 ~ 105 70 67.8
13 GVC 1 9 ~ 13 9 6.3
14 GVC 2 12 ~ 17.6 12 6.3
15 GVC 3 9 ~ 13 9 6.3
16 GVC 4 12 ~ 17.6 12 6.3
17 RECYCLE FAN 1 36 ~ 52 36 43
18 RECYCLE FAN 2 36 ~ 52 44 43
19 INDUSTRIAL PUMP 1 18 ~ 25 21 21.3
20 INDUSTRIAL PUMP 2 BY PASS 21.3
21 DRAINAGE PUMP 1 20 ~ 32 28 28.8
22 DRAINAGE PUMP 2 20 ~ 32 28 28.8
23 MOTOR SWEEPER 1 UNIT 1 1.6 ~ 2.5 1.6 2.03
24 MOTOR SWEEPER 2 UNIT 1 1.6 ~ 2.5 2 2.03
25 MOTOR SWEEPER 3 UNIT 1 1.6 ~ 2.5 2.3 2.03
26 MOTOR SWEEPER 1 UNIT 2 1.6 ~ 2.5 2.3 2.03
27 MOTOR SWEEPER 2 UNIT 2 1.6 ~ 2.5 2.5 2.03
28 MOTOR SWEEPER 3 UNIT 2 1.6 ~ 2.5 1.6 2.03
29 SCREW BED MATERIAL 1 7.5 ~ 11 7.5 8.7
30 SCREW BED MATERIAL 2 7.5 ~ 11 7.5 8.7
31 TURNING GEAR 1 17 ~ 25 17 8.8
32 TURNING GEAR 2 17 ~ 25 17 8.8
33 CONDENSER CLEANING SYSTEM 1 14 ~ 22 16 14.4
34 CONDENSER CLEANING SYSTEM 2 14 ~ 22 14 14.4
35 CONDENSER STREANER MOTOR 1 1 ~ 1.6 1 1.5
36 CONDENSER STREANER MOTOR 2 1 ~ 1.6 1 1.5
37 CONDENSER STREANER MOTOR 3 1 ~ 1.6 1.2 1.5
38 CONDENSER STREANER MOTOR 4 1 ~ 1.6 1.2 1.5