Olr New

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 1648

SOOT BLOWER UNIT 1

NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 ROTARY SOOT BLOWER 1 1.6 ~ 2.5 1.6 1.05


2 ROTARY SOOT BLOWER 2 1.6 ~ 2.5 1.6 1.05
3 ROTARY SOOT BLOWER 3 1.6 ~ 2.5 1.6 1.05
4 ROTARY SOOT BLOWER 4 1.6 ~ 2.5 1.6 1.05
5 LRSB 1 1.6 ~ 2.5 1.6 1.56
6 LRSB 2 1.6 ~ 2.5 1.6 1.56
7 LRSB 3 1.6 ~ 2.5 1.6 1.56
8 LRSB 4 1.6 ~ 2.5 1.6 1.56
9 LRSB 5 1.6 ~ 2.5 1.6 1.56
10 LRSB 6 1.6 ~ 2.5 1.6 1.56
11

SOOT BLOWER UNIT 1


NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 ROTARY SOOT BLOWER 1 1.6 ~ 2.5 1.6 1.05


2 ROTARY SOOT BLOWER 2 1.6 ~ 2.5 1.6 1.05
3 ROTARY SOOT BLOWER 3 1.6 ~ 2.5 1.6 1.05
4 ROTARY SOOT BLOWER 4 1.6 ~ 2.5 1.6 1.05
5 LRSB 1 1.6 ~ 2.5 1.6 1.56
6 LRSB 2 1.6 ~ 2.5 1.6 1.56
7 LRSB 3 1.6 ~ 2.5 1.6 1.56
8 LRSB 4 1.6 ~ 2.5 1.6 1.56
9 LRSB 5 1.6 ~ 2.5 1.6 1.56
10 LRSB 6 1.6 ~ 2.5 1.6 1.56
11
NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 ASH CONDITIONER 6.3 ~ 10 6.3 6.4


2 FLUDIZATION BLOWER 6.3 ~ 10 6.3 6.73
3 BIAXIAL SCREW 25 ~ 40 28 30.3
4 BAG HOUSE 4 ~ 6.3 4 2.2
5 DRY ASH DISCHARGER 1.25 ~ 2 1.25 0.6
6 BED MATERIAL CONVEYOR 5.2 ~ 7.5 7.5 7.2
7 BED MATERIAL BACKET ELEVATOR 5.2 ~ 7.5 7.5 5.1
8
9
NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 VIBRATING FEEDER 1 1.7 ~ 2.4 1.7 1.15


2 VIBRATING FEEDER 2 1.7 ~ 2.4 1.7 1.15
3 VIBRATING SCREEN 7.5 ~ 11 7.5 8.8
4 DE IRON SEPARATOR 5
5 BELT CONVEYOR 1 18 ~ 25 23.6
6 BELT CONVEYOR 2 30 ~ 45 35 30.7
7 BELT CONVEYOR 3 12 ~ 17.6 12 15.6
8 COAL CRUSHER 206
9
NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 SPRAY PUMP 1 7 ~ 10 8 14.8


2 SPRAY PUMP 2 7 ~ 10 8 14.8
3 ACW 1 140 ~ 200 150 139.6
4 ACW 2 140 ~ 200 150 139.6
5 ACW MAKE UP 1 18 ~ 27 23 21.3
6 ACW MAKE UP 2 18 ~ 27 23 21.3
7 COOLING TOWER FAN 1 (ACW) 30 ~ 45 30 36.5
8 COOLING TOWER FAN 2 (ACW) 30 ~ 45 30 36.5
9 JOCKEY PUMP 9 ~ 13 9 8.6
MOTOR RAPPING ESP UNIT 1
NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 EMITTING RAPPING 1 1 ~ 1.6 1.1 1.2


2 EMITTING RAPPING 2 1 ~ 1.6 1.1 1.2
3 EMITTING RAPPING 3 1 ~ 1.6 1.1 1.2
4 COLLECTING RAPPING 1 1 ~ 1.6 1.1 1.2
5 COLLECTING RAPPING 2 1 ~ 1.6 1.1 1.2
6 COLLECTING RAPPING 3 1 ~ 1.6 1.1 1.2

MOTOR RAPPING ESP UNIT 2


NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 EMITTING RAPPING 1 1 ~ 1.6 1.1 1.2


2 EMITTING RAPPING 2 1 ~ 1.6 1.1 1.2
3 EMITTING RAPPING 3 1 ~ 1.6 1.1 1.2
4 COLLECTING RAPPING 1 1 ~ 1.6 1.1 1.2
5 COLLECTING RAPPING 2 1 ~ 1.6 1.1 1.2
6 COLLECTING RAPPING 3 1 ~ 1.6 1.1 1.2

NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 AIR COMPRESSOR 1 80 ~ 110 100 167.3


2 AIR COMPRESSOR 2 80 ~ 110 100 167.3
3 AIR COMPRESSOR 3 80 ~ 110 100 167.3
NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 RAW WATER PUMP 1 23 ~ 32 26 29


2 RAW WATER PUMP 2 23 ~ 32 26 29
3 MMF BACK WASH 23 ~ 32 26 29
4 UF BACK WASH 23 ~ 32 26 29
5 PURE PUMP 1 4~6 4 4.9
6 PURE PUMP 2 4~6 4 4.9
7 REGEN PUMP 4~6 4 3.5
8 RO FEED PUMP 1 12 ~ 18 12 14.9
9 RO FEED PUMP 2 12 ~ 18 12 14.9
10 RO CLEANING 7 ~ 10 7 8.2
11 FLUSHING PUMP 7 ~ 10 7 8.2
12 BWRO 1 17 ~ 25 17 21
13 BWRO 2 17 ~ 25 17 21
14 AIR BLOWER 12 ~ 18 14 11
15 DEMIN MOTOR 1 7 ~ 10 7 6.3
16 DEMIN MOTOR 2 7 ~ 10 7 6.3

DOSING PUMP AREA


NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 LP DOSING PUMP 1 1.2 ~ 1.6 1.2 1.12


2 LP DOSING PUMP 2 1.2 ~ 1.6 1.2 1.12
3 LP AGITATOR 1.5 ~ 2 1.75 1.57
4 HP DOSING PUMP 1 2.5 ~ 4 3 2.85
5 HP DOSING PUMP 2 2.5 ~ 4 3 2.85
6 HP DOSING PUMP 3 2.5 ~ 4 3 2.85
7 HP AGITATOR 1 1.25 ~ 1.75 1.75 1.57
8 HP AGITATOR 2 1.25 ~ 1.75 1.75 1.57

SEDIMENT AREA
NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 TRANSFER PUMP 1 23 ~ 32 28.5 29


2 TRANSFER PUMP 2 23 ~ 32 28.5 29
3 TRANSFER PUMP 3 23 ~ 32 28.5 29
4 BLOWER OUTLATE VALVE 16 ~ 24 22 29.7
5 MAKE UP COOLING TOWER 1 16 ~ 24 22 35
6 MAKE UP COOLING TOWER 2 16 ~ 24 22 35
INTAKE AREA
NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 FLOCULANT DOSING PUMP 1 1 ~ 1.6 1.4 1.1


2 FLOCULANT DOSING PUMP 2 1 ~ 1.6 1.4 1.1
3 COUGULANT DOSING PUMP 1 1 ~ 1.6 1.4 1.1
4 COUGULANT DOSING PUMP 2 1 ~ 1.6 1.4 1.1
5 FLOCULANT AGITATOR 2.5 ~ 4 3 3.68
6 COGULANT AGITATOR 2.5 ~ 4 3 3.68
NO MOTOR NAME OLR RANGE OLR SETTING RATED CURRENT

1 SOP 1 57 ~ 82 57 54.8
2 SOP 2 57 ~ 82 57 54.8
3 AOP 1 12 ~ 18 12 10.7
4 AOP 2 9 ~ 13 11 10.7
5 WATER JET PUMP 1 70 ~ 105 70 67.9
6 WATER JET PUMP 2 70 ~ 105 70 67.9
7 WATER JET PUMP 3 70 ~ 105 70 67.9
8 WATER JET PUMP 4 70 ~ 105 70 67.9
9 CEP 1 70 ~ 105 70 67.8
10 CEP 2 70 ~ 105 70 67.8
11 CEP 3 70 ~ 105 70 67.8
12 CEP 4 70 ~ 105 70 67.8
13 GVC 1 9 ~ 13 9 6.3
14 GVC 2 12 ~ 17.6 12 6.3
15 GVC 3 9 ~ 13 9 6.3
16 GVC 4 12 ~ 17.6 12 6.3
17 RECYCLE FAN 1 36 ~ 52 36 43
18 RECYCLE FAN 2 36 ~ 52 44 43
19 INDUSTRIAL PUMP 1 18 ~ 25 21 21.3
20 INDUSTRIAL PUMP 2 BY PASS 21.3
21 DRAINAGE PUMP 1 20 ~ 32 28 28.8
22 DRAINAGE PUMP 2 20 ~ 32 28 28.8
23 MOTOR SWEEPER 1 UNIT 1 1.6 ~ 2.5 1.6 2.03
24 MOTOR SWEEPER 2 UNIT 1 1.6 ~ 2.5 2 2.03
25 MOTOR SWEEPER 3 UNIT 1 1.6 ~ 2.5 2.3 2.03
26 MOTOR SWEEPER 1 UNIT 2 1.6 ~ 2.5 2.3 2.03
27 MOTOR SWEEPER 2 UNIT 2 1.6 ~ 2.5 2.5 2.03
28 MOTOR SWEEPER 3 UNIT 2 1.6 ~ 2.5 1.6 2.03
29 SCREW BED MATERIAL 1 7.5 ~ 11 7.5 8.7
30 SCREW BED MATERIAL 2 7.5 ~ 11 7.5 8.7
31 TURNING GEAR 1 17 ~ 25 17 8.8
32 TURNING GEAR 2 17 ~ 25 17 8.8
33 CONDENSER CLEANING SYSTEM 1 14 ~ 22 16 14.4
34 CONDENSER CLEANING SYSTEM 2 14 ~ 22 14 14.4
35 CONDENSER STREANER MOTOR 1 1 ~ 1.6 1 1.5
36 CONDENSER STREANER MOTOR 2 1 ~ 1.6 1 1.5
37 CONDENSER STREANER MOTOR 3 1 ~ 1.6 1.2 1.5
38 CONDENSER STREANER MOTOR 4 1 ~ 1.6 1.2 1.5

You might also like