hm1520 Strain Gage Module
hm1520 Strain Gage Module
Model HM1520
Instruction Manual
DECEMBER 2001
The examples and diagrams in this manual are included solely for
illustrative purposes. Because of the many variables and requirements
associated with any particular installation, the Allen-Bradley Company or
Helm Instrument Company cannot assume responsibility or liability for
actual use based on the examples and diagrams.
PLC, PLC2, PLC3, and PLC5 are registered trademarks of the Allen-Bradley Company, Inc.
SLC, SLC500, PanelView, RediPANEL, Dataliner are trademarks of Allen-Bradley Company, Inc.
IBM is a registered trademark of International Business Machines, Incorporated.
StrainGage is a registered trademark of the Helm Instrument Company, Inc.
Table of Contents
StrainGage Load Module
User Manual
Table of Contents
Strain Gage Module
User Manual
Preface...................................................................................................P-1
Who Should Use this Manual .......................................................... P-1
Purpose of this Manual .................................................................... P-1
Contents of this Manual ............................................................. P-2
Related Documentation .............................................................. P-3
Terms and Abbreviations................................................................. P-4
Common Techniques Used in this Manual ...................................... P-6
Product Support......................................................................... P-6
Your Questions or Comments on this Manual ........................... P-6
Getting
Chapter 2 .............................................................................................. 2-1
Started
Getting Started................................................................................. 2-1
Required Tools and Equipment ....................................................... 2-1
System Operation ............................................................................ 2-2
Sensor Wiring .................................................................................. 2-2
Guide
Block Diagrams ................................................................................. 5-2
Preface
Preface
Read this preface to familiarize yourself with the rest of this manual. This
preface covers the following topics:
Who Should Use this manual if you are responsible for the design, installation, programming,
Use this or maintenance of an automation control system that used Allen-Bradley small
Manual logic controllers.
You should have a basic understanding of SLC 500 products. You should
understand electronic process control and be able to interpret the ladder logic
instructions required to generate the electronic signals that control your
application. If you do not, contact your local Allen-Bradley representative for the
proper training before using this product.
Purpose of This manual is a learning and reference guide for the Helm StrainGage Module.
This Manual It contains the information you need to install, wire, and use the module.
P-1
Preface
Contents of this
Manual
Chapter Title Content
B Ladder Program
P- 2
Preface
Related
Documentation
The following documents contain information that may be helpful to you as you
use Allen-Bradley SLC products. To obtain a copy of any of the Allen-Bradley
documents listed, contact your local Allen-Bradley office or distributor.
A description on how to install and use your MicroLogix 1500 Programmable Controller 1764-IN001A-ML-P
MicroLogix Programmable Controller Base Units Installation Instructions and
Wiring Diagrams
A description on how to install the processor MicroLogix 1500 Processor Installation 1764-IN002A-ML-P
into the MicroLogix 1500 Base unit. Instructions
View power usage of expansion modules to Expansion Modules System Qualifier RA Website Download
determine power supply requirements
An article on wire sizes and types for National Electrical Code Published by the
grounding electrical equipment National Fire
Protection
Association of
Boston, MA.
P-3
Preface
Terms and
Abbrevia-
tions The following terms and abbreviations are used throughout this manual. For definitions of terms
not listed here refer to Allen-Bradley’s Industrial Automation Glossary, Publication ICCG-7.1.
Channel - Refers to one of two, strain gage inputs available on the modules terminal block.
Chassis - A hardware assembly that houses devices such as I/O modules, adapter modules,
processor modules, and power supplies.
Configuration Word - Contains the channel configuration information needed by the module to
configure and operate each channel. Information is written to the configuration word through
the logic supplied in your ladder program.
Data Word - A 16-bit integer that represent the value of the analog input channel. The channel
data word is valid only when the channel is enabled.
Load/Force - Measurement of impact during a machine cycle. Sensors provide the input for
this measurement.
Look Window - Resolver or cam activated window, which allows specific degrees in a machine
cycle to be processed.
Low Alarm Inhibit - Number of consecutive machine cycles where low alarm is inhibited. Used
in a process where machine cycles several times before running speed is established.
LSB - (Least Significant Bit) Refers to a data increment defined as the full scale range divided
by the resolution. The bit that represents the smallest value within a string of bits.
Monitor Parts Mode - Status condition used during production run. Sample and compare logic
is enabled. On resolver based systems, tracking alarm limits can be enabled.
Multiplexer - A switching system that allows several input signals to share a common A/D
converter.
Remote Configuration - A control system where the chassis can be located several thousand
feet from the processor chassis.
P-4
Preface
Terms and
Abbrevia-
tions
(continued) Resolution - The smallest detectable change in a measurement, typically expressed in
engineering units (e.g. 0.15C) or as a number of bits. For example a 12-bit system has 4,096
possible output states. It can therefore measure 1 part in 4096.
Reverse Load - Measurement of negative load/force being exerted on machine following the
break-through of material. Also referred to as snap through.
Sample - Load/force values established from a series of machine cycles. Also defined as
benchmark.
Sample Count - User input value used to specify how many machine cycles to base the sample
on.
Sampling time - The time required by the A/D converter to sample an input channel.
Scale - Value used to describe the press/machine overall tonnage. Set for maximum value of
one channel. For example, settings for a 150 ton press = 75.
Setup Mode - Status condition of monitor typically enables during die setup. Machine capacity
alarms are enabled. On resolver based systems, press curve alarm can be enabled. This
mode is also used during machine and resolver calibrations.
Status Word - Contains status information about the channel’s current configuration and
operational state. You can use this information in your ladder program to determine whether
the channel data word is valid.
Target Load - A reference load established by the user. Used primarily during setup to improve
setup time.
Tolerance /Trend Alarm - User defined upper and lower control limits established during the
sample and compare process. These limits are established on the peak load and will activate
the machine stop relay when exceeded.
Tracking Alarm - Requires resolver input. The sample and compare process is applied to the
entire forming force based on user selected upper and lower control limits.
Trend Deviation - Percent of change, high and low, from sample value to current value.
Update Time - The time required for the module to sample and convert the input signals of all
enables input channels and make the resulting data values available to the SLC processor.
P-5
Preface
Common
Techniques The following conventions are used throughout this manual:
Used in this
• Bulleted lists such as this one provide information, not procedural steps.
Manual • Numbered lists provide sequential steps or hierarchical information.
P-6
Chapter 1
Overview You have just purchased the most advanced load monitoring solution available.
HELM INSTRUMENT COMPANY, INC. manufactures a complete line of load
monitoring control solutions for use on metal stamping, forging, compaction and
assembly presses; cold forming, cold heating, injection molding and die cast
machines.
Standard or custom transducers and load cells are available for in-die monitoring
of transfer or progressive tooling.
At HELM, quality is inherent not only in the design of our products but in the
attitudes of our employees as well. We’re working together to give you the best.
After all, that’s what our business is all about - providing innovative
instrumentation to help make your manufacturing process more productive and
your operation more effective.
Critical setup information can be stored and uploaded as part of a die recipe
program. An optional resolver input module is used to compare machine/press
tonnage to crank angle for real time signature analysis.
Components The Helm StrainGage module is attached to the controller or to an adjacent I/O
module on the din rail. The system is comprised of two parts; the input module
and two Helm Strain gage based sensors.
Strain Gain The primary part of the load monitoring system centers around the measurement.
Transducer The basic function of the Helm Strain Gain sensor is to detect the amount of
deflection imposed on the press or die as parts are being formed. All Strain Gain
Operation sensors are matched to within 1% and therefore can be replaced without
recalibration of the machine.
The Helm Strain Gain sensors can be mounted to strategic high stress areas of
the machine frame or strategically located in tooling or applied to stop blocks.
Signals from these sensors are routed to the StrainGage module for processing.
The Helm Strain Gage is capable of measuring either a tension or compression
signal.
• Sample and Compare Logic - processor memorizes the sample or benchmark load
StrainGage and compares each machine cycle against this sample.
Module
Features • User programmable Sample Count - selectable number of machine cycles on
which to base the sample.
• High and Low Capacity Alarm Sets - a discrete load limit for a maximum allowable
load and a minimum allowable load.
• High and Low Trend Alarm Sets - set as a percentage of load change on an
established sample.
• Low Alarm Inhibit - User programmable option to disable low alarm during process
start-up.
Page 1-1
Chapter 1
Hardware The StrainGage module can be attached to the controller or to an adjacent I/O
Overview module before or after din rail mounting. It is a Class 1 module (uses eight input
words and eight output words). It interfaces to strain gage based transducers
(350ohm or 700ohm).
The module can accept input from two sensors. The module has no output
channels. Module configuration requires manual and user programmable setup.
The StrainGage module receives and stores digitally converted analog data into
its image table for retrieval by processor. The module supports connections from
any combination of up to two strain gage sensors.
Any combination of Helm Strain Gage sensors can be used. Contact Helm for
additional information on the type and application of different sensor options.
The Helm module requires (1) input from a cam switch or a proximity
sensor for establishing the peak look window
Page 1-2
Chapter 1
Page 1-3
Chapter 2
Getting This chapter can help you to get started using the Helm StrainGage
Started module. The procedures included here assume that you have a basic
understanding of PLC products. You should understand electronic
process control and be able to interpret the ladder logic instructions
required to generate the electronic signals that control your application.
If you have any questions or are unfamiliar with the terms used or
concepts presented in the procedural steps, always read the referenced
chapters and other recommended documentation before trying to apply
the information.
Page 2-1
Chapter 2
System The StrainGage module communicates to the processor through the parallel
Operation backplane interface and receives +5Vdc and +24Vdc power from the power
supply through the backplane. No external power supply is required. The
MicroLogix and CompactLogix platforms can support up to 8 I/O modules. You
may install up to 3 StrainGage modules using the base power supply. An
additional power supply can be added to support more than 3 modules. Refer to
publication 17864-UM100A-US-P for information on expansion power supply
systems.
Each individual channel on the module can receive input signals from strain gage
based sensors. The module converts the analog values directly into digital
values.
Sensor The sensors are wired to the modules using the rightmost bank of inputs.
Wiring The pin-out is shown below.
Page 2-2
Chapter 33
Channel This chapter explains how the StrainGage module and the processor communicate
Configuration Through the module's input and output image. It lists the preliminary setup and operation
Data and required before the module can function.
Status With RS Logic 500 software, verify the module ID code.
Product ID Code = 1
Expansion General Configuration
StrainGage Vendor ID = 3
Module ID Product Type = 9
Code = 1 Product Code = 1
Series/Major Rev/Minor Rev = B
No special I/O configuration (SPIO CONFIG) information is required. The module ID code
automatically assigns the correct number of input and output words. The following memory map
shows how the output and input image tables are defined.
Output Image The 8 word output image (output from the CPU to the module) contains
Information that you configure to define the way a specific channel will work.
Example – If you want to configure channel 2 on the module located in slot 4
in the SLC chassis, your address would be O:4.2.
(o = file type : =element delimiter 4=slot .=word delimiter 2=word)
Bit Look Window Signal CH 1&2 O:e.0/0
Page 3-1
Output
Image Chapter 33
(cont.)
Peak Look Window Bit 0 (O:2/0)
When set on (1) the look window is active. When set off (0), the look window is inactive. The
module will process data while look window is active.
Page 3-2
Chapter 33
Data Table The 8-word module input image (input from the module to the CPU) represents data
Input Image words and status words. Input words (data words) hold the input data that represents
the values of the sensor inputs.
Input words (status bits) contain the various status conditions and reflect the
configuration settings you have entered into the output configuration words.
To obtain the status of Channel 2 Capacity Alarm Bit of the module located in slot 2 of
the rack, use address I:2
(I =file type : =element delimiter 2 =slot . =word delimiter 0 =word / 2 =bit)
Page 3-3
Chapter 33
Note: If O:e.0/1 is set to 1 then A/D Value is integer word for calibration set.
Page 3-4
Chapter 33
Using RS Logics 500 software, reserve two integer file’s for tonnage monitoring. Reserve one counter for tonnage
monitoring.
For illustration purposes in this manual, we have reserved Integer file N10:0 - N10:25.
Page 3-5
Chapter 34
A complete listing of a sample ladder logic program is included at the back of this manual.
Examples shown here are for reference.
All values are 0 (default) on initial start-up. This means that all alarms are
disabled. You must make the following adjustments for proper operation:
Steps 2 and 3 require adjustment to the three position toggle switch on the inside panel of the module.
⇒ From your operator interface, put the tonnage module into bypass mode. (Both the setup and run lights on
the tonnage module should be off.)
Rung 3:2
| PANELVIEW | CH'S 1&2 |
| MODE | MODULE |
| BUTTON | BYPASS BIT |
| (BYPASS) | |
| N10:20 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 3 1 |
NOTE: Make sure that only 1 bit is set at any time for Panel Mode, integer N10:20.
Page 4-1
Chapter 34
Step 3. Set Calibration Numbers
Always make sure that the three-position switch is in ON (top) position for
Normal operation.
The remaining setup procedures can be accomplished with the Run Mode
bit in either Bypass, Peak or Monitor Parts Mode. However, the Bypass
Mode should only be used when setting calibration values or zero
balancing the sensor input.
This setting is based off of one channel. It represents the maximum allowable load or tonnage from one sensor
location. Integer N10:14 should be set from your operator interface.
Rung 3:21
| CH'S 1&2 |
| SCALE INFO |
| |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:15| |
| | 0| |
| |Dest O:4.1| |
| | 0| |
| +------------------+ |
Setting Machine Capacity Scale using (1) two channel force module:
If 2 sensors are installed on the left and right sides of a 60 ton press, set the Scale to 30 (maximum capacity of
one sensor).
Use the following table as a reference for setting the Machine Capacity Scale for a single force module installation
with two sensors. Divide the press/machine capacity by the number of sensors (2) and set Scale to the result.
If 2 sensors are installed in the tooling rather than on the press structure, set the Machine Capacity Scale to the
highest load/tonnage of one sensor.
Page 4-2
Chapter 34
Divide the Machine capacity by the number of sensors and set Machine Capacity Scale on all modules to the result.
Example: If 2 load modules are used for monitoring a straight side press with 4 sensors mounted on the press columns,
set the Machine Capacity Scale on both modules to the highest load/tonnage of one sensor.
Use the following table as a reference for setting the Machine Capacity Scale for a system comprised of (2) force modules
and (4) sensors.
NOTE: Although the range of values for capacity alarm settings is 0 to 9999, it is recommended that you do not enter
values that exceed the capacity rating of the machine/press. A value of 0 disables capacity alarm set.
To determine the maximum rating for each channel, divide the total machine/press capacity by the number of sensor
inputs. EXAMPLE: A press or slide rated at 100 tons with a (2) channel force module would have a capacity alarm
setting of 50 tons per sensor input.
This setting differs from the Scale setting as it can be adjusted up or down depending on the nature of the process.
Rung 3:23
| CH1 HIGH |
| CAPACITY |
| ALARM |
| SETTING |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:11| |
| | 0| |
| |Dest O:4.3| |
| | 0| |
| +------------------+ |
Page 4-3
Chapter 34
Step 6. Set Minimum Low Alarm
The range of this value is 0 to 9999. A value of 0 disables Minimum Low Alarm. Use a value here that represents a
minimum load/tonnage that is acceptable for the process.
Use this alarm setting when running in Peak Mode to alarm against low load/tonnage hits.
Rung 3:22
| CH1 LOW |
| CAPACITY |
| ALARM |
| SETTING |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:13| |
| | 0| |
| |Dest O:4.2| |
| | 0| |
| +------------------+ |
Page 4-4
Chapter 34
The sample count is a user programmable parameter that tells the processor how many machine strokes are
required to establish sample or benchmark load values. The value can range from 0 to 16. A value of 0
invalidates the Monitor Parts mode. You should set Sample Count to a minimum of 1 to enable Monitor Parts
mode.
Note: Each time you change Monitor Parts mode bit from ON to OFF, the sample value is cleared. During
normal operations, Monitor Parts mode is enabled when beginning a process run. If the process varies due to
change in material thickness, for example, it may be necessary to take a new sample.
Rung 3:34
| | D0 BIT OF |
| PANELVIEW | SAMPLE |
| ENTRY | COUNT |
| | |
| N10:18 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 0 8 |
Rung 3:35
| | D1 BIT OF |
| PANELVIEW | SAMPLE |
| ENTRY | COUNT |
| N10:18 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 1 9 |
Rung 3:36
| | D2 BIT OF |
| PANELVIEW | SAMPLE |
| ENTRY | COUNT |
| N10:18 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 2 10 |
Rung 3:37
| | D3 BIT OF |
| PANELVIEW | SAMPLE |
| ENTRY | COUNT |
| N10:18 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 3 11 |
Rung 3:38
| | D4 BIT OF |
| PANELVIEW | SAMPLE |
| ENTRY | COUNT |
| N10:18 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 4 12 |
Page 4-5
Chapter 34
The Trend Alarm settings are established as a percentage of allowable change in load. These percentages
are applied to the sample load values. There is a High Trend Alarm set and a Low Trend Alarm set for each
channel. The limits can range from 0 to 99%. A setting of 0 disables the alarm.
These alarms are active when the Monitor Parts Mode bit is ON. When monitor parts mode is enabled, the
sample process takes place.
Example: Monitor Parts mode is enabled with a sample count of 4 and high and low Trend Alarms set at
10%. The load generated on the next 4 machine cycles is averaged to obtain the sample value for each
channel. A sample of 30 tons is calculated for channel 1 and a sample of 40 tons is calculated for channel 2.
If any succeeding machine stroke develops tonnage of 33 (10% of 30 = 3 tons) or higher on channel 1 the
High Trend Alarm is reached and the alarm bit is turned ON. If tonnage falls to 27, the Low Trend Alarm set
is reached and the alarm bit is turned ON.
You have completed the basic setup and the module is operational.
Page 4-6
Chapter 34
Additional
Application
Notes
Mode Status
The three modes are Bypass, Peak, Monitor Parts
Bypass Mode
Used for module setup and at the time of calibration. All alarms are disabled in bypass mode.
Rung 3:2
| PANELVIEW | CH'S 1&2 |
| MODE | MODULE |
| BUTTON | BYPASS BIT |
| (BYPASS) | |
| N10:20 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 3 1 |
Peak Mode
In Peak Mode operation, the high capacity alarms and the low minimum alarms are active. There is no
sample calculation and high and low Trend alarms are inactive. This mode is used primarily during machine
setup operations.
Rung 3:3
| PANELVIEW | CH'S 1&2 |
| MODE | MODULE |
| BUTTON | PEAK MODE |
| (PEAK) | BIT |
| N10:20 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 4 2 |
When Monitor Parts Mode bit is turned ON, the sample is calculated based on the number of sample counts
and the high and low Trend alarms are activated. The High Capacity and Low Minimum Alarms remain
active.
Rung 3:4
| PANELVIEW | |
| MODE | CH'S 1&2 |
| BUTTON | MODULE |
| (MONITOR | MONITOR |
| PARTS) | PARTS BIT |
| N10:20 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 5 3 |
The panel function switch in these 3 rungs need to be a button on your operator interface (multistate
pushbutton with 3 states) that writes 3 different values to tag N7:6
Page 4-7
Chapter 34
High Capacity and Low Capacity Alarm bits - Channel 1 & Channel 2
Rung 3:8
| |
| |
| CH1 HIGH CH1 HIGH |
| CAPACITY CAPACITY |
| ALARM BIT ALARM |
| I:4 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 0 | 0 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:9
| |
| |
| CH1 LOW CH1 LOW |
| CAPACITY CAPACITY |
| ALARM BIT ALARM |
| I:4 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 1 | 1 | |
| |
+++ +++
+++ +++
| |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:10
| |
| |
| CH2 HIGH CH2 HIGH |
| CAPACITY CAPACITY |
| ALARM BIT ALARM |
| I:4 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 2 | 2 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:11
| |
| |
| CH2 LOW CH2 LOW |
| CAPACITY CAPACITY |
| ALARM BIT ALARM |
| I:4 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 3 | 3 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Page 4-8
Chapter 34
Trend High and Low Alarm bits
Rung 3:12
| |
| |
| CH1 HIGH CH1 HIGH |
| TREND TREND |
| ALARM BIT ALARM |
| I:4 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 4 | 4 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:13
| |
| |
| CH1 LOW CH1 LOW |
| TREND TREND |
| ALARM BIT ALARM |
| I:4 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 5 | 5 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:14
| |
| |
| CH2 HIGH CH2 HIGH |
| TREND TREND |
| ALARM BIT ALARM |
| I:4 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 6 | 6 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:15
| |
| |
| CH2 LOW CH2 LOW |
| TREND TREND |
| ALARM BIT ALARM |
| I:4 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 7 | 7 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Page 4-9
Chapter 34
Rung 2:13
CAUSES EITHER E-STOP OR TOP STOP RELAY TO DROP OUT WHEN THERE IS A TONNAGE
FAULT
| CH'S 1&2 | E-STOP OR |
| MODULE | TOP STOP |
| ALARM BIT | RELAY |
| N10:16 O:2 |
|----]/[---------------------------------------------------------------------------------------------------------------( )-----|
| 11 0 |
Page 4-10
Chapter 34
In some processes it may be necessary to inhibit the Low Capacity alarm during machine ramp up. Use
the following example to set the low alarm inhibit bit based on a counter.
Rung 3:0
| PANELVIEW | CH'S 1&2 |
| LOW ALARM | MODULE |
| INHIBIT | LOW |
| INDICATOR | INHIBIT |
| | ALARM |
| N10:16 O:4 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 10 6 |
Rung 2:0
| PRESS IN |
| MOTION BIT |
| N10:21 C5:5 |
|----]/[--------------------------------------------------------------------------------------------------------+--(RES)-----+-|
| 8 | | |
| | PANELVIEW | |
| | LOW ALARM | |
| | INHIBIT | |
| | INDICATOR | |
| | N10:16 | |
| +----(L)-----+ |
| 10 |
NOTE: Use N10:21/8 when using Helm’s resolver module and Helm’s press in motion ladder logic
or use customer’s own press in motion bit.
Rung 2:1
| PANELVIEW |
| AND CH'S |
| 1&2 MODULE LOW ALARM |
| CAM CYCLE INHIBIT |
| BIT COUNTER |
| N10:21 C5:5 +CTU---------------+ |
|----] [------]/[------------------------------------------------------------------------------------+COUNT UP +-(CU)-|
| 8 DN |Counter C5:5+-(DN) |
| |Preset 4| |
| |Accum 1| |
| +------------------+ |
Rung 2:2
| PRESS IN PANELVIEW |
| MOTION BIT LOW ALARM |
| INHIBIT |
| INDICATOR |
| N10:21 C5:5 N10:16 |
|----] [------] [------------------------------------------------------------------------------------------------------(U)-----|
| 8 DN 10 |
Rung 2:4
MOVES LOW ALARM INHIBIT COUNTS ENTERED FROM PANELVIEW INTO THE PRESET OF THE
LOW ALARM INHIBIT COUNTER
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:17| |
| | 0| |
| |Dest C5:5.PRE| |
| | 4| |
| +------------------+ |
Page 4-11
Chapter 34
Peak Look Window
Rung 2:3
SETS UP CAM WINDOW FOR TONNAGE MODULE
| PANELVIEW |
| AND CH'S |
| 1&2 MODULE |
| CAM CYCLE |
| BIT |
| +LIM---------------+ N10:21 |
|-+LIMIT TEST +-------------------------------------------------------------------------------------------------( )-----|
| |Low Lim 90| 0 |
| | | |
| |Test N153:0| |
| | 0| |
| |High Lim 220| |
| | | |
| +------------------+ |
- OR –
Rung 2:7
| | |
| prox probe| |
| or rotary | ch's 1&2 |
| cam input | cam bit |
| I:4 N10:21 |
|----] [---------------------------------------------------------------( )-----|
| 0 0 |
Note: Customer mapped in input.
Input for the Look Window can be obtained from a rotary cam limit switch, proximity probe or position
resolver.
N10:21/1 Indicates the machine stop and start status on the Panel.
This bit is set to 1 (ON) when a module alarm occurs.
N10:21/0 Set bit to 1 (ON) during peak window time, clear at other times.
Page 4-12
System Chapter 35
Trouble-
shooting
Guide
Page 5-1
System Chapter 35
Trouble-
shooting
Guide
(contd.)
Alarm
in Peak Mode
Check press
Correct problem
parallelism
Check calibration numbers Out of
Parallel parallel
Incorrect
Dial in correct
calibration number
Run press
Page 5-2
System Chapter 35
Trouble-
shooting
Guide
(contd.)
Alarm in
Monitor Parts Mode
No alarm No
Re sample with Check for broken shear
press running collar, linkage, or other Correct problem
press or die damage Yes
None
Out of
parallel
Parallel
Page 5-3
Chapter 35
System
Trouble-
shooting
Guide
(contd.)
No
Yes
Is relay jumped out
Run press Remove jumper
at press controls
No
No
Replace relay
Page 5-4
Chapter 35
System
Trouble-
shooting
Guide
(contd.)
Uneven load
distribution
OK Parallel None
Out of Yes Out of
Correct Check the parallelism Remove slug Check for slug build-up Correct Check the parallelism
problem of press & run press in die problem of press
parallel parallel
Page 5-5
Chapter 35
System
Trouble-
shooting
Guide
(contd.)
Erratic readings
Yes
Check for die
Correct problem
problem
None
Yes
Check for variation
Correct problem
in stock
None
Yes
Check for press
Correct problem
problem
Page 5-6
Appendix A
Isolation 500 VDC continuous between inputs and chassis ground, and
between inputs and backplane
a.) If you are using Helm HR-1101 resolver for position input and
are using our sample ladder:
Rung 2:0
| helm's | press in |
| press in | motion bit |
| motion bit| |
| N12:0 N10:21 |
|----] [---------------------------------------------------------------( )-----|
| 4 0 |
Rung 2:1
| customer | press in |
| press in | motion bit |
| motion bit| |
| N7:0 N10:21 |
|----] [---------------------------------------------------------------( )-----|
| 0 0 |
Rung 2:7
| | |
| prox probe| |
| or rotary | ch's 1&2 |
| cam input | cam bit |
| I:4 N10:21 |
|----] [---------------------------------------------------------------( )-----|
| 0 0 |
Rung 2:4
| |
| prox probe |
| or rotary ch's 1&2 |
| cam input cam bit |
| I:4 N10:21 |
|----] [--------------------------------------------------------+----( )-----+-|
| 0 | 0 | |
| | | |
| | | |
| | ch's 3&4 | |
| | cam bit | |
| | N11:21 | |
| +----( )-----+ |
| 0 |
Rung 2:5
| ch's 1&2 | top stop |
| module | or e-stop |
| alarm bit | relay |
| N10:16 O:7 |
|----]/[---------------------------------------------------------------( )-----|
| 11 0 |
Rung 2:6
| ch's 1&2 |ch's 3&4 | top stop |
| module |module | or e-stop |
| alarm bit |alarm bit | relay |
| N10:16 N11:16 O:7 |
|----]/[--------]/[----------------------------------------------------( )-----|
| 11 11 0 |
Rung 2:0
| PRESS IN |
| MOTION BIT |
| N10:21 C5:5 |
|----]/[--------------------------------------------------------------------------------------------------------+--(RES)-----+-|
| 0 | | |
| | PANELVIEW | |
| | LOW ALARM | |
| | INHIBIT | |
| | INDICATOR | |
| | N10:16 | |
| +----(L)-----+ |
| 10 |
Rung 2:1
| PANELVIEW |
| AND CH'S |
| 1&2 MODULE LOW ALARM |
| CAM CYCLE INHIBIT |
| BIT COUNTER |
| N10:21 C5:5 +CTU---------------+ |
|----] [------]/[------------------------------------------------------------------------------------+COUNT UP +-(CU)-|
| 0 DN |Counter C5:5+-(DN) |
| |Preset 4| |
| |Accum 1| |
| +------------------+ |
Rung 2:2
| PRESS IN PANELVIEW |
| MOTION BIT LOW ALARM |
| INHIBIT |
| INDICATOR |
| N10:21 C5:5 N10:10 |
|----] [------] [------------------------------------------------------------------------------------------------------(U)-----|
| 0 DN 10 |
Rung 2:3
SETS UP CAM WINDOW FOR TONNAGE MODULE
| PANELVIEW |
| AND CH'S |
| 1&2 MODULE |
| CAM CYCLE |
| BIT |
| +LIM---------------+ N10:21 |
|-+LIMIT TEST +-------------------------------------------------------------------------------------------------( )-----|
| |Low Lim 600| 0 |
| | | |
| |Test N153:0| |
| | 0| NOTE: CENTERS SIGNITURE IN LOOKWINDOW |
| | | |
| |High Lim 2830| |
| | | |
| +------------------+ |
Rung 2:4
MOVES LOW ALARM INHIBIT COUNTS ENTERED FROM PANELVIEW INTO THE PRESET OF THE
LOW ALARM INHIBIT COUNTER
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:17| |
| | 0| |
| |Dest C5:5.PRE| |
| | 4| |
| +------------------+ |
Rung 2:13
CAUSES EITHER E-STOP OR TOP STOP RELAY TO DROP OUT WHEN THERE IS A TONNAGE
FAULT
| CH'S 1&2 | E-STOP OR |
| MODULE | TOP STOP |
| ALARM BIT | RELAY |
| N10:16 O:7 |
|----]/[---------------------------------------------------------------------------------------------------------------( )-----|
| 11 0 |
Rung 2:14
| |
|-------------------------------------------------------------+END+------------------------------------------------------------|
| |
Ladder Programming
Appendix B – Section 3
Rung 3:0
| |
| |
| press in |
| motion bit |
| N10:21 C5:5 |
|----]/[--------------------------------------------------------------------------------------------------------+--(RES)-----+-|
| 0 | | |
| | PANELVIEW | |
| | LOW ALARM | |
| | INHIBIT | |
| | INDICATOR | |
| | N10:16 | |
| +----(L)-----+ |
| 10 |
Rung 3:1
| PANELVIEW |
| AND CH'S |
| 1&2 MODULE LOW ALARM |
| CAM CYCLE INHIBIT |
| BIT COUNTER |
| N10:21 C5:5 +CTU---------------+ |
|----] [------]/[------------------------------------------------------------------------------------+COUNT UP +-(CU)-|
| 0 DN |Counter C5:5+-(DN) |
| |Preset 4| |
| |Accum 1| |
| +------------------+ |
Rung 3:2
| PANELVIEW |
| LOW ALARM |
| press in INHIBIT |
| motion bit INDICATOR |
| N10:21 C5:5 N10:16 |
|----] [------] [------------------------------------------------------------------------------------------------------(U)-----|
| 0 DN 10 |
Rung 3:3
SETS UP CAM WINDOW FOR TONNAGE MODULE
| PANELVIEW |
| AND CH'S |
| 1&2 MODULE |
| CAM CYCLE |
| BIT |
| +LIM---------------+ N10:21 |
|-+LIMIT TEST +------------------------------------------------------------------------------------------+----( )-----+-|
| |Low Lim 600| | 0 | |
| | | | | |
| |Test N153:0| | | |
| | 124| | | |
| |High Lim 2830| NOTE: CENTERS SIGNITURE IN LOOKWINDOW | | |
| | | | | |
| +------------------+ | | |
| | | |
| | | |
| | | |
| | CH'S 3&4 | |
| | MODULE CAM | |
| | CYCLE | |
| | BIT | |
| | N11:21 | |
| +----( )-----+ |
| 0 |
Rung 3:4
| PANELVIEW | |
| LOW ALARM | CH'S 3&4 |
| INHIBIT | LOW ALARM |
| INDICATOR | INHIBIT |
| | MAP IN |
| N10:16 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 10 4 |
Ladder Programming
Appendix B – Section 3
Rung 3:7
MOVES LOW INHIBIT COUNTS THAT IS ENTERED FROM PANELVIEW INTO PRESET OF THE LOW
ALARM INHIBIT COUNTER
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:17| |
| | 4| |
| |Dest C5:5.PRE| |
| | 4| |
| +------------------+ |
Rung 3:9
COPIES SCALE INFORMATION FROM CH'S 1&2 TONNAGE MODULE 1 INTO CH'S 3&4 TONNAGE
MODULE 2
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:15| |
| | 1000| |
| |Dest N11:15| |
| | 1000| |
| +------------------+ |
Rung 3:27
DROPS OUT RELAY WHEN THERE IS A TONNAGE FAULT
| CH'S 1&2 |CH'S 3&4 | TOP STOP |
| MODULE |MODULE | RELAY OR |
| ALARM BIT |ALARM BIT | E-STOP |
| | RELAY |
| N10:16 N11:16 O:7 |
|----]/[--------]/[----------------------------------------------------------------------------------------------------( )-----|
| 11 11 0 |
Rung 3:28
| |
|-------------------------------------------------------------+END+------------------------------------------------------------|
| |
Ladder Programming
Appendix B – Section 4
Rung 3:0
| PANELVIEW | CH'S 1&2 |
| LOW ALARM | MODULE |
| INHIBIT | LOW |
| INDICATOR | INHIBIT |
| | ALARM |
| N10:16 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 10 6 |
Rung 3:1
| PANELVIEW | CH'S 1&2 |
| AND CH'S | MODULE |
| 1&2 MODULE| LOOK |
| CAM CYCLE | WINDOW |
| BIT | SIGNAL |
| N10:21 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 0 0 |
Rung 3:2
| PANELVIEW | CH'S 1&2 |
| MODE | MODULE |
| BUTTON | BYPASS BIT |
| (BYPASS) | |
| N10:20 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 3 1 |
Rung 3:3
| PANELVIEW | CH'S 1&2 |
| MODE | MODULE |
| BUTTON | PEAK MODE |
| (PEAK) | BIT |
| N10:20 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 4 2 |
Rung 3:4
| PANELVIEW | |
| MODE | CH'S 1&2 |
| BUTTON | MODULE |
| (MONITOR | MONITOR |
| PARTS) | PARTS BIT |
| N10:20 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 5 3 |
Rung 3:5
| PANELVIEW | |
| & CH'S 1&2| CH'S 1&2 |
| REVERSE | MODULE |
| LOAD | REV LOAD |
| BUTTON | BIT |
| N10:21 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 6 5 |
Rung 3:6
| SAMPLE |
| SETTING |
| +MOV---------------+ |
|-------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:18| |
| | 0| |
| |Dest C5:0.PRE| |
| | 0| |
| +------------------+ |
Rung 3:7
| MODULE 1 |PANELVIEW SAMPLE |
| CYCLE |MODE COUNTER |
| BIT |BUTTON |
| |(MONITOR |
| | PARTS) |
| N10:21 N10:20 +CTD---------------+ |
|----] [--------] [--------------------------------------------------------------------------------+COUNT DOWN +-(CD)-|
| 0 5 |Counter C5:0+-(DN) |
| |Preset 0| |
| |Accum 0| |
| +------------------+ |
Rung 3:8
| PANELVIEW SAMPLE |
| MODE COUNTER |
| BUTTON |
| (PEAK) |
| N10:20 C5:0 |
|-+----] [-----+----------------------------------------------------------------------------------------------------(RES)----|
| | 4 | |
| | S:1 | |
| +--] [-------+ |
| 15 |
Ladder Programming
Appendix B – Section 4
Rung 3:9
| CURRENT |
| SAMPLE |
| COUNT |
| +MOV---------------+ |
|--------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source C5:0.ACC| |
| | 0| |
| |Dest N10:19| |
| | 0| |
| +------------------+ |
Rung 3:10
| | PANELVIEW |
| | LEARN |
| | CYCLE |
| | INDICATOR |
| C5:0 N10:16 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| DN 9 |
Rung 3:11
| |
| |
| CH1 HIGH CH1 HIGH |
| CAPACITY CAPACITY |
| ALARM BIT ALARM |
| I:2 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 0 | 0 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:12
| |
| |
| CH1 LOW CH1 LOW |
| CAPACITY CAPACITY |
| ALARM BIT ALARM |
| I:2 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 1 | 1 | |
| |
| |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:13
| |
| |
| CH2 HIGH CH2 HIGH |
| CAPACITY CAPACITY |
| ALARM BIT ALARM |
| I:2 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 2 | 2 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:14
| |
| |
| CH2 LOW CH2 LOW |
| CAPACITY CAPACITY |
| ALARM BIT ALARM |
| I:2 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 3 | 3 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Ladder Programming
Appendix B – Section 4
Rung 3:15
| |
| |
| CH1 HIGH CH1 HIGH |
| TREND TREND |
| ALARM BIT ALARM |
| I:2 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 4 | 4 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:16
| |
| |
| CH1 LOW CH1 LOW |
| TREND TREND |
| ALARM BIT ALARM |
| I:2 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 5 | 5 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:17
| |
| |
| CH2 HIGH CH2 HIGH |
| TREND TREND |
| ALARM BIT ALARM |
| I:2 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 6 | 6 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:18
| |
| |
| CH2 LOW CH2 LOW |
| TREND TREND |
| ALARM BIT ALARM |
| I:2 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(L)-----+-|
| 7 | 7 | |
| | CH'S 1&2 | |
| | MODULE | |
| | ALARM BIT | |
| | N10:16 | |
| +----(L)-----+ |
| 11 |
Rung 3:19
| PANELVIEW |
| TONNAGE |
| FAULT CH1 HIGH |
| RESET TREND |
| BUTTON ALARM |
| N10:21 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(U)-----+-|
| 7 | 4 | |
| | | |
| | | |
| | CH1 LOW | |
| | TREND | |
| | ALARM | |
| | N10:16 | |
| +----(U)-----+ |
| | 5 | |
| | | |
| | | |
| | CH2 HIGH | |
| | TREND | |
| | ALARM | |
| | N10:16 | |
| +----(U)-----+ |
| | 6 | |
| | | |
| | | |
| | CH2 LOW | |
| | TREND | |
| | ALARM | |
| | N10:16 | |
| +----(U)-----+ |
| 7 |
Ladder Programming
Appendix B – Section 4
Rung 3:20
| PANELVIEW |
| TONNAGE |
| FAULT CH1 HIGH |
| RESET CAPACITY |
| BUTTON ALARM |
| N10:21 N10:16 |
|----] [--------------------------------------------------------------------------------------------------------+----(U)-----+-|
| 7 | 0 | |
| | | |
| | | |
| | CH1 LOW | |
| | CAPACITY | |
| | ALARM | |
| | N10:16 | |
| +----(U)-----+ |
| | 1 | |
| | | |
| | | |
| | CH2 HIGH | |
| | CAPACITY | |
| | ALARM | |
| | N10:16 | |
| +----(U)-----+ |
| | 2 | |
| | | |
| | | |
| | CH2 LOW | |
| | CAPACITY | |
| | ALARM | |
| | N10:16 | |
| +----(U)-----+ |
| 3 |
Rung 3:21
| PANELVIEW | |
| TONNAGE | CH'S 1&2 |
| FAULT | MODULE |
| RESET | ALARM |
| BUTTON | RESET BIT |
| N10:21 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 7 4 |
Rung 3:22
| PANELVIEW | |
| ALARM | |
| RESET | MODULE 1 |
| BUTTON | ALARM |
| | BIT |
| N10:21 N10:16 |
|----] [----------------------------------------c---------------------------------------------------------------------(U)-----|
| 7 11 |
Rung 3:23
| CH'S 1&2 |
| SCALE INFO |
| |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:15| |
| | 0| |
| |Dest O:2.1| |
| | 0| |
| +------------------+ |
Rung 3:24 |
CH1 LOW |
| CAPACITY |
| ALARM |
| SETTING |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:12| |
| | 0| |
| |Dest O:2.2| |
| | 0| |
| +------------------+ |
Rung 3:25
| CH1 HIGH |
| CAPACITY |
| ALARM |
| SETTING |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:11| |
| | 0| |
| |Dest O:2.3| |
| | 0| |
| +------------------+ |
Ladder Programming
Appendix B – Section 4
Rung 3:26
| CH2 LOW |
| CAPACITY |
| ALARM |
| SETTING |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:14| |
| | 0| |
| |Dest O:2.4| |
| | 0| |
| +------------------+ |
Rung 3:27
| CH2 HIGH |
| CAPACITY |
| ALARM |
| SETTING |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source N10:13| |
| | 0| |
| |Dest O:2.5| |
| | 0| |
| +------------------+ |
Rung 3:28
| CH 1 TREND |
| DEVIATION |
| IN PERCENT |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source I:2.3| |
| | 0| |
| |Dest N10:1| |
| | 0| |
| +------------------+ |
Rung 3:29
| CH 2 TREND |
| DEVIATION |
| IN PERCENT |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source I:2.4| |
| | 0| |
| |Dest N10:2| |
| | 0| |
| +------------------+ |
Rung 3:30
| +MUL---------------+ |
|-----------------------------------------------------------------------------------------------------+-+MULTIPLY +-+-|
| | |Source A N10:4| | |
| | | 0| | |
| | |Source B 256| | |
| | | | | |
| | |Dest N10:7| | |
| | | 0| | |
| | +------------------+ | |
| | | |
| | TREND | |
| | HIGH\LOW | |
| | ALARM | |
| | SETTING | |
| | FOR CH1 | |
| | +ADD---------------+ | |
| +-+ADD +-+ |
| |Source A N10:7| |
| | 0| |
| |Source B N10:3| |
| | 0| |
| |Dest O:2.6| |
| | 0| |
| +------------------+ |
Ladder Programming
Appendix B – Section 4
Rung 3:31
| +MUL---------------+ |
|-----------------------------------------------------------------------------------------------------+-+MULTIPLY +-+-|
| | |Source A N10:6| | |
| | | 0| | |
| | |Source B 256| | |
| | | | | |
| | |Dest N10:7| | |
| | | 0| | |
| | +------------------+ | |
| | TREND | |
| | HIGH\LOW | |
| | ALARM | |
| | SETTING | |
| | FOR CH2 | |
| | +ADD---------------+ | |
| +-+ADD +-+ |
| |Source A N10:7| |
| | 0| |
| |Source B N10:5| |
| | 0| |
| |Dest O:2.7| |
| | 0| |
| +------------------+ |
Rung 3:32
DISPLAYS PEAK TONNAGE FOR CHANNEL 1 AS LONG AS MODULE IS NOT IN SETUP MODE
| PANELVIEW |
| MODE |
| BUTTON |
| (BYPASS) |
| N10:20 +MOV---------------+ |
|----]/[--------------------------------------------------------------------------------------------------+MOVE +-|
| 3 |Source I:2.1| |
| | 0| |
| |Dest N10:8| |
| | 0| |
| +------------------+ |
Rung 3:33
DISPLAYS CAL NUMBER FOR CHANNEL 1 ON PANELVIEW
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source I:2.1| |
| | 0| |
| |Dest N10:22| |
| | 0| |
| +------------------+ |
Rung 3:34
DISPLAYS PEAK TONNAGE FOR CHANNEL 2 AS LONG AS MODULE IS NOT IN SETUP MODE
| PANELVIEW |
| MODE |
| BUTTON |
| (BYPASS) |
| N10:20 +MOV---------------+ |
|----]/[--------------------------------------------------------------------------------------------------+MOVE +-|
| 3 |Source I:2.2| |
| | 0| |
| |Dest N10:9| |
| | 0| |
| +------------------+ |
Rung 3:35
DISPLAYS CAL NUMBER FOR CHANNEL 2 ON PANELVIEW
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source I:2.2| |
| | 0| |
| |Dest N10:23| |
| | 0| |
| +------------------+ |
Rung 3:36
| CH 1 |
| AVERAGE |
| of SAMPLES |
| IN TONS |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source I:2.5| |
| | 0| |
| |Dest N10:24| |
| | 0| |
| +------------------+ |
Rung 3:37
| CH 2 |
| AVERAGE |
| of SAMPLES |
| IN TONS |
| +MOV---------------+ |
|---------------------------------------------------------------------------------------------------------+MOVE +-|
| |Source I:2.6| |
| | 0| |
| |Dest N10:25| |
| | 0| |
| +------------------+ |
Ladder Programming
Appendix B – Section 4
Rung 3:38
| | D0 BIT OF |
| PANELVIEW | SAMPLE |
| ENTRY | COUNT |
| | |
| N10:18 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 0 8 |
Rung 3:39
| | D1 BIT OF |
| PANELVIEW | SAMPLE |
| ENTRY | COUNT |
| N10:18 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 1 9 |
Rung 3:40
| | D2 BIT OF |
| PANELVIEW | SAMPLE |
| ENTRY | COUNT |
| N10:18 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 2 10 |
Rung 3:41
| | D3 BIT OF |
| PANELVIEW | SAMPLE |
| ENTRY | COUNT |
| N10:18 O:2 |
|----] [---------------------------------------------------------------------------------------------------------------( )-----|
| 3 11 |
Rung 3:42
| |
|-------------------------------------------------------------+END+------------------------------------------------------------|
| |