Description: CURRENT TRANSFORMER (OHTL) Record No.

:
Bay no.: Drawing ref.: Sheet: 1 of 5
Contractor: Contract no.: Substation No :

1. GENERAL DATA AND INFORMATION:

Project: PPG-HVPT
Substation: PPG-RAFIDIYA
Client: ENI-ZFOD
Bay:
Testing Device: Omicron CPC 100
Testing date:

2. CT DATA:

Serial no:
Tag no.:
Phase.:
Ratio.: 400/1 A
Rating.: 132Kv
Manufacturer.: TRENCH
Class: 30VA, 5P20 / 30VA, 5P20 / 5VA, 0.2FS5

3. MECHANICAL CHECKS & VISUAL INSPECTION:

Item Description Checked


1 Check no damage on installed equipment
2 Check grounding cable are connected as per drawing
3 Check tightness for links
4 Check ferrules as per the wiring connections
5 Check CT name plate data for correctness
6 Oil level
7 Oil leakage

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Description: CURRENT TRANSFORMER (OHTL) Record No.:
Bay no.: Drawing ref.: Sheet: 2 of 5
Contractor: Contract no.: Substation No :

4. ELECTRICAL TEST

4.1.INSULATION RESISTANCE TEST:

Phase Insulation resistance (MΩ) Remarks


Primary - earth
Primary - secondary
Secondary - earth

Applying voltages:
 Primary To Ground : 5 KV for 1 minute
 Primary To Secondary : 2.5 KV for 1 minute
 Secondary To Ground : 1KV for 1 minute

Criteria:
 Primary to ground & primary to secondary = More than 1 G.Ω
 Secondary to ground = More than 100 M.Ω

4.2.WINDING RESISTANCE:

Ambient temp: o
C

Winding Resistance
Phase
Core 1
Core 2
Core 3

Criteria:

4.3.POLARITY TEST:
Primary injection at P1 +Ve and P2 -Ve

Phase Terminals Assessment

Core 1 1S1-1S2
Core 2 2S1-2S2
Core 3 3S1-3S2
5.

5.1.RATIO TEST:

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Description: CURRENT TRANSFORMER (OHTL) Record No.:
Bay no.: Drawing ref.: Sheet: 3 of 5
Contractor: Contract no.: Substation No :

Core Primary current (A) Secondary current (A) Expected current % error
1S1-1S2 400 A 1A
2S1-2S2 400 A 1A
3S1-3S2 400 A 1A

Criteria:

6. MAG - CURVE:
5.1 Core 1

Function: Location CT#


Make: Phase Ratio
V kp: SL # Class
I mag SL #
Earthed SL #

Ter.
Sl.# V I mA
1
2
3
V volts

4
5
6
7
8
Vkp I mA

Criteria:

5. MAG - CURVE:
5.2 Core 2

Locatio
Function: CT#
n

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Description: CURRENT TRANSFORMER (OHTL) Record No.:
Bay no.: Drawing ref.: Sheet: 4 of 5
Contractor: Contract no.: Substation No :

Make: Phase 2S1-2S2 Ratio


V kp: SL # Class
I mag SL #
Earthed SL #

Ter.
Sl.# V I mA
1
2
3
V volts

4
5
6
7
8
Vkp I mA

Criteria:

5.MAG - CURVE:
5.3 Core 3

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Description: CURRENT TRANSFORMER (OHTL) Record No.:
Bay no.: Drawing ref.: Sheet: 5 of 5
Contractor: Contract no.: Substation No :

Function: Location CT#


Make: Phase 3S1-3S2 Ratio
V kp: SL # Class
I mag SL #
Earthed SL #

Ter.
Sl.# V I mA
1
2
3
V volts

4
5
6
7
8
Vkp I mA

Criteria:

6.BURDEN TEST:

CORE TERMINALS EXPECTED ACTUAL ASSESMENT


BURDEN BURDEN

1S1-1S2
1

2S1-2S2
2
3S1-3S2
3

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date: